Savings-by-Design EnergyDesignResources.Com Cx AssistantTM Sequences of Operation Developed by CTG Energetics, Inc. Under contract to Pacific Gas and Electric Company April 2004 Cx Assistant’s Sequence of Operation April 2004 IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended to serve as a standard form. The user of these documents should confer with qualified advisors with respect to its commissioning and other documentation. Cx Assistant’s Sequence of Operation April 2004 About Cx Assistant Energy Design Resources' Commissioning Assistant is a web-based tool designed to provide project-specific building commissioning information to design teams. The tool currently enables the users to accomplish the following six functions: 1. Evaluate probable commissioning cost. 2. Identify the appropriate commissioning scope for each project, and develop sample scope documents. 3. Develop a sample design intent document with specific inputs from their projects. 4. Develop a sample basis of design document with specific inputs from their projects. 5. Access sample commissioning specifications related to specific inputs for his/her construction project. 6. View sample sequence of operations for their HVAC equipment based upon the requirements in California Title 24- 2005. Modules are planned to be added in 2005 that will generate a Commissioning Plan, a Training Plan and a Systems Manual. Cx Assistant’s Sequence of Operation April 2004 About EDR Energy Design Resources offers a valuable palette of energy design tools and resources that help make it easier to design and build energy-efficient commercial and industrial buildings in California. The goal of this effort is to educate architects, engineers, lighting designers, and developers about techniques and technologies that contribute to energy efficient nonresidential new construction. Additionally, design tools that reduce the time you spend evaluating the energy use impact of your design decisions are provided here at no cost. Plus, we've designed them to be quick and easy to learn so you can begin designing more efficiently today. Did you know: Even though California already leads the nation in energy-efficient building construction, the state will again be tightening its energy standards for new construction in 2005? We want to help make it as easy as possible for you to transition to these new regulations. Perhaps more importantly, we also want to help you exceed these standards to create more efficient buildings that will be less expensive to own and operate. This approach should make owners, tenants, and clients happy. The development of Energy Design Resources is funded by California utility customers and administered by Pacific Gas and Electric Company, San Diego Gas & Electric, Southern California Edison, and Southern California Gas under the auspices of the California Public Utilities Commission. Cx Assistant’s Sequence of Operation April 2004 Table of Contents 1. 2. 3. 4. Split System Units with DX Cooling Economy Heat Pump Packaged Units Evaporative Cooler Units Packaged VVT Units 5. Standard Packaged Units 6. Four Pipe Fan Coil Units 7. Constant Air Volume (CAV) Units with Central Plant 8. Variable Air Volume (VAV Units with Air-Cooled Chiller 9. Variable Air Volume (VAV Units with Water-Cooled Chiller 10. Water Source Heat Pump System Cx Assistant’s Sequence of Operation April 2004 Cx Assistant’s Sequence of Operation April 2004 Notes: [SPLIT SYSTEM WITH DX COOLING]. The system consists of an indoor fan coil unit and an outdoor condensing unit that are connected by a direct expansion (DX) refrigerant loop. The fan coil unit has a supply fan and a cooling coil. The outdoor unit has a compressor, a heat rejection fan, and a condensing coil. This system is designed to provide cooling for machinery such as electrical transformers and computer equipment. The system does not include ventilation air. Vendor-provided packaged controls operate the equipment. Appropriate reference in the specifications should be made for products that are integrated with these sequences including packaged units, economizers, and the like. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. SEQUENCE OF OPERATION: SPLIT SYSTEM WITH DX COOLING SEQUENCES OF OPERATION 1. Occupied Periods (Normal occupied operation): The zone is typically unoccupied, but the unit is enabled to run, as needed, 24 hours per day, 7 days per week. 2. Fan Operation: Run the indoor unit fan when the unit is in cooling mode. Split System with DX Cooling 1 Cx Assistant’s Sequence of Operation April 2004 3. Temperature Control: A thermostat is used to determine when the space requires cooling. Set the thermostat for the following ranges: a. Cooling: 60° F to 85° F. The default is 75° F. Maintain a dead band of 1°F to cycle the system on and off. 4. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact. Once reset, the unit will resume the current mode of operation. 5. Shutdown: The fan and compressor will stop when the system goes to unoccupied mode or when there is no call for cooling. The fan runs for 1 minute after a shutdown has been initiated. 6. Fire Alarm: For fire alarm mode operation, the unit will be shut down by hardwired contact. Once reset, the affected unit will resume the current mode of operation. 7. Cooling Mode Enable: When the thermostat generates a call for cooling, enable the unit’s compressor. The supply air setpoint in cooling mode is 55° F. Allow the unit’s controls to cycle the compressor to supply the needed air temperature. The package unit’s internal controls protect the equipment from excessive operating conditions including low oil pressure, high discharge pressure, low suction pressure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low refrigerant charge, high and low refrigerant temperatures, etc. If excessive operating conditions occur, shut down the unit to protect it. 8. Cooling Mode Shutdown: If a call for cooling has been satisfied, a system failure has occurred, or the supply air temperature has fallen below 50° F for more than one minute, cycle the compressor off. After the compressor has shut down, continue running the supply fan for 5 minutes before shutting it down. 9. Space Temperature Alarm: An independent thermostat will sound an alarm if the room temperature rises above 78° F for more than 5 minutes. POINTS TABLE Key: X Indicates type of point (only 1 point is needed) CU Outdoor condensing unit with indoor fan coil (i.e. split system) Note that these points are typically hard wired and not readily accessible Point Name AI AO DI DO Analog Software Value Split System with DX Cooling Digital Software Value Other Software Value 2 Cx Assistant’s Sequence of Operation April 2004 CU Space Temperature X Alarm Setpoint-Cooling CU Cooling Alarm X CU Cooling Enable X CU Mode CU Fire Alarm X X CU Space Temperature Setpoint-Cooling X CU Space Temperature Setpoint-Deadband X Split System with DX Cooling 3 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of multiple packaged HVAC units each serving one or more zones in the building. The packaged units each have a supply fan, direct expansion (DX) cooling and heating (i.e. a heat pump), and an electric resistance back-up heater. The unit provides 100% outdoor air (i.e. “once-through” system). The system is controlled with vendor-provided packaged controls. Appropriate reference in the specifications should be made for products that are integrated with these sequences including packaged units, economizers, and the like. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. ECONOMY HEAT PUMP PACKAGED UNIT SEQUENCES OF OPERATION 1. Occupied Periods (Normal occupied operation): Operate the system on a programmed occupancy schedule from 7:00 AM to 6:00 PM, M-F. These periods are considered “occupied periods”. During occupied periods, run the system in Occupied Mode, including enabling the packaged unit fans. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. 3. Fan Operation (Ventilation Mode): Run the unit fans in all modes except unoccupied mode. Economy Heat Pump Packaged Unit 4 Cx Assistant’s Sequence of Operation April 2004 4. Temperature Control: A thermostat is used to determine each space’s required mode. Set each thermostat for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between heating and cooling setpoints. When the system is operating, the thermostat is either in heating, cooling, or ventilation mode. If a space’s temperature is more than 1.5° F higher than its temperature setpoint, the thermostat generates a call for cooling. Likewise, if a space’s temperature is more than 1.5° F lower than its temperature setpoint, the thermostat generates a call for heating. Otherwise, the thermostat generates a call for ventilation mode. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). 5. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact. Once reset, the affected unit(s) will resume the current mode of operation. 6. Cooling Mode Enable: When the zone thermostat generates a call for cooling, enable the unit’s compressor. The cooling mode supply air setpoint is 55° F. Allow the package unit’s controls to cycle the compressor to supply the needed air temperature. The package unit’s internal controls protect the equipment from excessive operating conditions including low oil pressure, high discharge pressure, low suction pressure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low refrigerant charge, high and low refrigerant temperatures, etc. If excessive operating conditions occur, shut down the unit to protect it. 7. Heating Mode Enable: When the zone thermostat generates a call for heating and outdoor temperature is above 42° F, switch the packaged unit heat pump to switch to heating mode. If the outdoor temperature is less than 42° F, lock out the heat pump t and enable the back-up resistance heater to supply heat to the zone. The package unit’s internal controls protect the equipment from excessive operating conditions including low oil pressure, high discharge pressure, low suction pressure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low refrigerant charge, high and low refrigerant temperatures, etc. If excessive operating conditions occur, shut down the unit to protect it. 8. Compressor Shutdown: If a call for cooling or heating has ended, a system failure has occurred, or the supply air temperature has fallen below 40° F (or risen above 120° F) for more than one minute, cycle the compressor off. After the compressor has shut down, continue running the supply fan for 5 minutes before shutting it down (even if an unoccupied period begins). 9. Unoccupied Mode: Unoccupied mode occurs during unoccupied periods. In unoccupied mode, disable the packaged unit. When a thermostat’s override button is depressed during an unoccupied period, operate the system in the occupied mode for one hour. At the end of the hour, return the system to unoccupied mode. Economy Heat Pump Packaged Unit 5 Cx Assistant’s Sequence of Operation April 2004 10. Warm-up Mode: Identify Warm-up start time using an optimal start strategy based on average zone temperature. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, enable the package unit in occupied mode. Terminate the warm-up mode after the average zone temperature has risen above 70°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 11. Cool-down Mode: Identify cool-down start time using an optimal start strategy based on average zone temperature. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, enable the packaged unit in occupied mode. Terminate the cool-down mode after the average zone temperature has fallen below 78°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 12. Night Setback/Setup: Enable system operation during unoccupied periods in the warm-up or cool-down mode if the space temperature falls below 55°F (adj.) or rises above 85°F (adj.). Stop the system when the thermostat reaches either its unoccupied cooling or unoccupied heating setpoints. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each unit – a total of “n” points are needed for this line item) OA outside air (OAT = outside air temperature) PKG packaged unit Note that these points are typically hard-wired and not readily accessible Point Name AI AO DI DO Analog Software Value OA DB Temp n PKG-n Cooling Alarm Other Software Value n PKG-n Fan Enable n PKG-n Heating Alarm n PKG-n Mode PKG Fire Alarm Digital Software Value n X PKG Warm-up Mode Low Temp Setpoint Economy Heat Pump Packaged Unit n 6 Cx Assistant’s Sequence of Operation PKG Cool -down Mode High Temp Setpoint April 2004 n PKG-n Override n PKG-n Space Temperature SetpointCooling n PKG-n Space Temperature SetpointHeating n PKG-n Space Temperature Unoccupied SetpointCooling n PKG-n Space Temperature Unoccupied SetpointHeating n PKG-n Space Temperature SetpointDeadband n Economy Heat Pump Packaged Unit 7 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of multiple packaged HVAC units each serving one or more zones in the building. The packaged units each have a supply fan, direct evaporative cooling and natural gas heating. The unit provides 100% outdoor air (i.e. “once-through” system). The system is controlled with vendor-provided packaged controls. Appropriate reference in the specifications should be made for products that are integrated with these sequences including packaged units, economizers, and the like. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. EVAPORATIVE COOLING PACKAGED UNIT SEQUENCES OF OPERATION 1. Occupied Periods (Normal occupied operation): Operate the system on a programmed occupancy schedule from 7:00 AM to 6:00 PM, M-F. These periods are considered “occupied periods”. During occupied periods, run the system in Occupied Mode, including enabling the packaged unit fans. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. 3. Fan Operation (Ventilation Mode): Run the unit fans in all modes except unoccupied mode. Evaporative Cooler Units 8 Cx Assistant’s Sequence of Operation April 2004 4. Temperature Control: A thermostat is used to determine each space’s required mode. Set each thermostat for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between heating and cooling setpoints. When the system is operating, the thermostat is either in heating, cooling, or ventilation mode. If a space’s temperature is more than 1.5° F higher than its temperature setpoint, the thermostat generates a call for cooling. Likewise, if a space’s temperature is more than 1.5° F lower than its temperature setpoint, the thermostat generates a call for heating. Otherwise, the thermostat generates a call for ventilation mode. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). 5. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact. Once reset, the affected unit(s) resume the current mode of operation. 6. Cooling Mode: When the zone thermostat generates a call for cooling, enable the evaporative cooler. Allow the packaged unit controls to operate the internal circulating pump that carries water to the cooling surface. Provide makeup water to the circulating pump basin as needed. The packaged unit’s internal controls protect the equipment from excessive operating conditions including low water level. If excessive operating conditions occur, shut off the circulating pump to protect it. When the call for cooling has ended, shut off the circulating pump. 7. Heating Mode Enable: When the zone thermostat generates a call for heating, the packaged unit will cycle on the gas heater to supply heat to the zone. The package unit’s internal controls protect the equipment from excessive operating conditions including high temperature, flame failure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low gas pressure, etc. If excessive operating conditions occur, shut down the unit to protect it. 8. Heating Mode Shutdown: If a call for heating has ended, a system failure has occurred, or the supply air temperature has risen above 120° F for more than one minute, cycle the heater off. After the heater has shut down, continue running the supply fan for 5 minutes before shutting it down (even if the unoccupied period begins) 9. Unoccupied Mode: Unoccupied mode occurs during unoccupied periods. In unoccupied mode, disable the packaged unit. When a thermostat’s override button is depressed during an unoccupied period, operate the system in the occupied mode for one hour. At the end of the hour, return the system to unoccupied mode. 10. Warm-up Mode: Identify Warm-up start time using an optimal start strategy based on average zone temperature. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, enable the packaged unit in heating mode. Terminate the warm-up mode after the average Evaporative Cooler Units 9 Cx Assistant’s Sequence of Operation April 2004 zone temperature has risen above 70°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 11. Cool-down Mode: Identify cool-down start time using an optimal start strategy based on average zone temperature. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, enable the unit in cooling mode. Terminate the cool-down mode after the average zone temperature has fallen below 78°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 12. Night Setback/Setup: Enable system operation during unoccupied periods in the warm-up or cool-down mode if the space temperature falls below 55°F (adj.) or rises above 85°F (adj.). Stop the system when the thermostat reaches either its unoccupied cooling or unoccupied heating setpoints. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) PKG packaged unit Note that these points are typically hard wired and not user accessible Point Name AI AO DI PKG-n Fan Enable DO Analog Digital Other Software Software Software Value Value Value n PKG-n Heating Alarm n PKG-n Mode PKG Fire Alarm n n PKG Warm-up Mode Low Temp Setpoint n PKG Cool -down Mode High Temp Setpoint n PKG-n Override PKG-n Space Temperature Setpoint-Cooling Evaporative Cooler Units n n 10 Cx Assistant’s Sequence of Operation April 2004 PKG-n Space Temperature Setpoint-Heating n PKG-n Space Temperature Unoccupied Setpoint-Cooling n PKG-n Space Temperature Unoccupied Setpoint-Heating n PKG-n Space Temperature Setpoint-Deadband n Evaporative Cooler Units 11 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of multiple packaged roof top HVAC units each serving variable volume / variable temperature (VVT) zone equipment. The packaged units each have a supply fan, direct expansion (DX) cooling, natural gas heating, outside air temperature cooling/heating lockout, and an integrated differential temperature economizer. The unit’s economizer uses return and exhaust dampers to regulate “free” cooling. Supply duct bypass dampers and variable volume terminal units control the supply air delivered to each zone. The system is controlled with vendorprovided packaged controls that operate in a master and slave fashion. Appropriate reference in the specifications should be made for products that are integrated with these sequences including packaged units, VVT equipment, and the like. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. PACKAGED GAS HEAT AND DX COOLING HVAC UNITS WITH ECONOMIZERS AND VARIABLE VOLUME, VARIABLE TEMPERATURE (VVT) ZONES SEQUENCES OF OPERATION System Modes 1. Occupied Periods (Normal occupied operation): Operate the system on a programmed occupancy schedule from 7:00 AM to 6:00 PM, M-F. These periods are considered “occupied periods”. During occupied periods, run the system in Occupied Mode, including enabling the packaged unit fans, opening the outside Packaged VVT Units 12 Cx Assistant’s Sequence of Operation April 2004 air dampers to minimum position, and operating the zone dampers to maintain at least minimum ventilation rates. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Start-up & System “changeover”: “Changeover” occurs at the beginning of every occupied period and whenever the VVT master controller switches between cooling and heating modes (use a hard-wired stop to signal changeover). During changeover, open the bypass damper fully and allow the air contained in the supply duct to circulate directly to the return air stream. When the supply air temperature reaches an acceptable temperature (80°F if the system is beginning a heating mode or 65° F if the system is beginning a cooling mode), modulate the damper closed. Stop modulating the bypass damper closed when the supply air duct static pressure transmitter, referenced to space pressure, registers the operating pressure of 1.0” WC. During operation, modulate the bypass damper to maintain the SA static pressure at a setpoint of 1.0” WC. 4. Occupied Modes: During occupied periods, the VVT master controller polls the slave controllers at least every 30 seconds to confirm their operating status. A call for a particular mode (heating, cooling, or ventilation) is based upon the number of requests for that mode from the slave controllers. Once the number of callers for a particular mode exceeds that of the other modes, the mode is changed. At the beginning of each new mode, the VVT master controller selects the reference zone (see Determination of Reference Zone). Do not change the mode more frequently than every 5 minutes. NOTE: To initiate a mode change, at least 2 (adjustable) slave controllers must request it. 5. Determination of the Reference Zone: When the system mode is changed, the master controller selects the zone with the greatest difference between room temperature and room setpoint. This becomes the reference zone. 6. Unoccupied Mode: Unoccupied mode occurs during unoccupied periods. In unoccupied mode, disable the packaged unit, close the outside air damper, and position the return/exhaust air dampers for full return air (no exhaust). When a zone sensor’s override button is depressed during unoccupied period, operate the system in the occupied mode for one hour. 7. Warm-up Mode: Identify Warm-up start time using an optimal start strategy based on outdoor air temperature and average zone temperature. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warmup period, initiate the warm-up mode. If building warm-up is required, command the return/exhaust air dampers to the return position (no exhaust) and enable the Packaged VVT Units 13 Cx Assistant’s Sequence of Operation April 2004 package unit. Terminate the warm-up mode after the average zone temperature has risen above 70°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 8. Cool-down Mode: Identify cool-down start time using an optimal start strategy based on outdoor air temperature and average zone temperature. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. If building cool-down is required, command the return/exhaust air damper to the return position (no exhaust) and enable the packaged unit. Terminate the cool-down mode after the average zone temperature has fallen below 78°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 9. Supply Temperature Limits: During any mode, when the supply air temperature exceeds 140° F, or falls below 50° F, disable the cooling or heating in the packaged unit and initiate an alarm in the VVT control system. VVT Zone Control 1. Temperature Control: A slave controller is used to determine each space’s required mode. Set each controller for the following ranges: 1. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. 2. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between heating and cooling setpoints. When the system is operating, the slave controller is either in heating, cooling, or ventilation mode. If a space’s temperature is more than 1.5° F higher than its temperature setpoint, the zone controller generates a call for cooling. Likewise, if a space’s temperature is more than 1.5° F lower than its temperature setpoint, the zone controller generates a call for heating. Otherwise, the controller generates a call for ventilation mode. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone with its own adjustable unoccupied heating and cooling setpoints. 2. Cooling Mode: When a zone controller calls for cooling and the supply air temperature is less than the space temperature, enable the zone controller to open the zone damper to provide cooling to the space. If the zone is calling for cooling and the supply air temperature is higher than the space temperature, the controller closes the damper to minimum position (minimum position is determined by air balance). 3. Heating Mode: When a zone controller calls for heating and the supply air temperature is greater than the space temperature, enable the zone controller to open the zone damper to provide heating to the space. If the zone is calling for heating and the supply air temperature is lower than the space temperature, the controller closes the damper to minimum position (minimum position is determined by air balance). Packaged VVT Units 14 Cx Assistant’s Sequence of Operation April 2004 4. Ventilation Mode: When in ventilation mode, enable the zone controller to open and close the zone damper to satisfy heating or cooling needs. 5. Night Setback/Setup: Enable system operation during unoccupied periods in the warm-up or cool-down mode if the lowest space temperature from a slave controller falls below 55°F (adj.) or rises above 85°F (adj.). Stop the system when the reference zone reaches either its unoccupied cooling or unoccupied heating setpoints. 6. Zone Grouping: Provide zone groups to establish enough heating or cooling load for the package system to work against when answering off-hours calls or setback calls. When one zone calls for system operation after hours, (either in the night setback mode or by authorized tenant request), command all zones in the associated group to come out of setback into normal operating temperature settings used for Occupied Modes. 7. Unoccupied Operation: When a zone override button is depressed during unoccupied period, operate the system in occupied mode for one hour. At the end of the hour, return the system to unoccupied mode. Packaged Unit 1. Fan Operation: Run the unit fans in all modes except unoccupied mode. Any time the supply fan is running, open the outside air damper to provide minimum outdoor air. 2. Shutdown: When shutdown is initiated, place the packaged unit in unoccupied mode. 3. Fire Alarm: For fire alarm mode operation, the supply fan will be shut down by hardwired contact. Once reset, the affected unit(s) will resume the current mode of operation. 4. Cooling Mode Enable: When the VVT master controller generates a call for cooling, enable the economizer mode in order to satisfy the cooling requirement. If the economizer mode cannot provide the required supply air temperature (55° F) for at least 2 minutes, disable economizer mode and enable the unit’s compressor. Reset the supply air temperature upward from 55°F to 65°F as the outdoor temperature falls from 90° F or greater to 65° F or lower. Allow the package unit’s controls to cycle the compressor to supply the needed air temperature. The package unit’s internal controls protect the equipment from excessive operating conditions including low oil pressure, high discharge pressure, low suction pressure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low refrigerant charge, high and low refrigerant temperatures, etc. If excessive operating conditions occur, generate an alarm on the VVT master controller and shut down the package unit to protect it. 5. Cooling Mode Shutdown: If a call for cooling has been satisfied, a system failure has occurred, or the supply air temperature has fallen below 50° F for more than one minute, cycle the compressor off. After the compressor has shut down, Packaged VVT Units 15 Cx Assistant’s Sequence of Operation April 2004 continue running the supply fan for 5 minutes before shutting it down (even if the unoccupied mode is issued by the VVT). 6. Enthalpy Economizer Mode: Enable enthalpy economizer mode when the VVT master controller issues a call for cooling or ventilation, and outdoor air temperature is 2° F less than return air temperature. Open outside air damper to 100%. Modulate the return air and exhaust air dampers in unison to maintain supply air temperature setpoint. When the return air enthalpy is 2 BTU/lb dry air (adjustable deadband) above the outdoor air enthalpy, the dampers are to be in the full exhaust position (exhaust damper fully open and return damper fully closed). As the return enthalpy decreases below this point, the dampers transition to a full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open). 7. Heating Mode Enable: When the VVT master controller generates a call for heating, transition the return & exhaust dampers to full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open), and the packaged unit will cycle on the gas heater to supply heat to the zone. Reset the supply air temperature upward from 90°F to 110°F as the outdoor temperature falls from 65° F or greater to 40° F or lower. The package unit’s internal controls protect the equipment from excessive operating conditions including high temperature, flame failure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low gas pressure, etc. If excessive operating conditions occur, generate an alarm on the VVT master controller and shut down the package unit to protect it. 8. Heating Mode Shutdown: If a call for heating has ended, a system failure has occurred, or the supply air temperature has risen above 120° F for more than one minute, cycle the heater off. After the heater has shut down, continue running the supply fan for 5 minutes before shutting it down (even if the unoccupied mode is issued by the VVT master controller). 9. Heating System Outdoor Air Temperature Lockout: If the outdoor air temperature rises above 68 ° F (adjustable), the heating system shall be locked out. If the outdoor air temperature falls below 65° F (adjustable), the heater will be allowed to function as required to maintain load. 10. Mechanical Cooling System Outdoor Air Temperature Lockout: If the outdoor air temperature is below 63° F (adjustable), the mechanical cooling system shall be locked out. If the outdoor air temperature rises above 65° F (adjustable), the compressors will be allowed to function as required to maintain load. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone - a total of "n" points are needed for this line item) Packaged VVT Units 16 Cx Assistant’s Sequence of Operation April 2004 OA outside air (OAT = outside air temperature) RTU rooftop unit (i.e. packaged unit) VVT variable volume and temperature terminal Point Name AI AO DI DO Analog Software Value OA DB Temp X OA RH X OA Enthalpy X Cooling Lockout Temp X Heating Lockout Temp X RTU- Low Limit Setpoint Temp n RTU- High Limit Setpoint Temp n RTU-n Economizer Staging Setpoint Temp n AHU-n RAT n AHU-n RA RH n AHU-n RA Enthalpy n RTU-n Staging Deadband Temp n RTU-n Cooling Alarm Packaged VVT Units Alarm Logic n RTU-n Cooling Status RTU-n Heating Alarm Other Software Value n RTU-n Fan Enable RTU-n Heating Status Digital Software Value n n Proof after 1 minute Proof after 1 minute n 17 Cx Assistant’s Sequence of Operation April 2004 RTU-n VVT Mode n RTU-n Economizer Mode n VVT Fire Alarm X VVT Mode Override X VVT Supply Pressure Setpoint VVT Supply Pressure X X VVT Warm-up Mode Low Temp Setpoint X VVT Cool -down Mode High Temp Setpoint X VVT Mode X VVT Low Limit Setpoint Temp X VVT High Limit Setpoint Temp X VVT Reference Zone X VVT Override X VVT Operating Mode VVT Supply Air Temperature X X VAV-n Supply Air Temp Reset VVT OAT X X VVT Bypass Mode VVT Bypass Status X X Zone-n Space Temperature Setpoint-Cooling n Zone-n Space n Packaged VVT Units 18 Cx Assistant’s Sequence of Operation April 2004 Temperature Setpoint-Heating Zone-n Space Temperature Unoccupied Setpoint-Cooling n Zone-n Space Temperature Unoccupied Setpoint-Heating n Zone-n Space Temperature Setpoint-Deadband n Zone-n Damper Command Zone-n Override Zone-n Operating Mode Packaged VVT Units n n n 19 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of multiple packaged roof top HVAC units each serving one or more zones in the building. The packaged units each have a supply fan, direct expansion (DX) cooling, natural gas heating, outside air temperature cooling/heating lockout, and an integrated differential enthalpy economizer. The unit’s economizer uses return and exhaust dampers to regulate “free” cooling. The system is controlled with vendor-provided packaged controls. Appropriate reference in the specifications should be made for products that are integrated with these sequences including packaged units, economizers, and the like. The system(s) in your building that are most similar to the system described above include: • Packaged VAV System • Typical AHU Controls • proto 1 • Packaged VaV • classroom hvac • Underfloor • Roof-top packaged AC-4 • AH-1 • test ahu • AHU-1 • Central System • asdf • VAV • VAVS Please note that this sample sequence will have to be modified to meet the exact systems defined in your building. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. PACKAGED UNIT WITH ECONOMIZER, DX COOLING AND GAS HEAT Standard Packaged Units 20 Cx Assistant’s Sequence of Operation April 2004 SEQUENCES OF OPERATION 1. Occupied Periods (Normal occupied operation): Operate the system on a programmed occupancy schedule from 7:00 AM to 6:00 PM, M-F. These periods are considered “occupied periods”. During occupied periods, run the system in Occupied Mode, including enabling the packaged unit fans and opening the outside air dampers to minimum position. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Fan Operation (Ventilation Mode): Run the unit fans in all modes except unoccupied mode. Any time the supply fan is running, open the outside air damper to provide minimum outdoor air. 4. Temperature Control: A thermostat is used to determine each space’s required mode. Set each thermostat for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. Standard Packaged Units 21 Cx Assistant’s Sequence of Operation 5. 6. 7. 8. 9. April 2004 b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between heating and cooling setpoints. When the system is operating, the thermostat is either in heating, cooling, or ventilation mode. If a space’s temperature is more than 1.5° F higher than its temperature setpoint, the thermostat generates a call for cooling. Likewise, if a space’s temperature is more than 1.5° F lower than its temperature setpoint, the thermostat generates a call for heating. Otherwise, the thermostat generates a call for ventilation mode. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone with its own adjustable unoccupied heating and cooling setpoints. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact. Once reset, the affected unit(s) will resume the current mode of operation. Cooling Mode Enable: When the zone thermostat generates a call for cooling, enable the economizer mode in order to satisfy the cooling requirement. If the economizer mode cannot provide the required supply air temperature (55° F, adjustable) for at least 2 minutes, disable economizer mode and enable the unit’s compressor. Allow the package unit’s controls to cycle the compressor to supply the needed air temperature. The package unit’s internal controls protect the equipment from excessive operating conditions including low oil pressure, high discharge pressure, low suction pressure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low refrigerant charge, high and low refrigerant temperatures, etc. If excessive operating conditions occur, shut down the unit to protect it. Cooling Mode Shutdown: If a call for cooling has been satisfied, a system failure has occurred, or the supply air temperature has fallen below 50° F for more than one minute, cycle the compressor off. After the compressor has shut down, continue running the supply fan for 5 minutes before shutting it down (even if an unoccupied period begins). Enthalpy Economizer Mode: Enable enthalpy economizer mode when the zone thermostat issues a call for cooling or ventilation, and outdoor air temperature is 2° F less than return air temperature. Open outside air damper to 100%. Modulate the return air and exhaust air dampers in unison to maintain supply air temperature setpoint. When the return air enthalpy is 2 BTU/lb dry air (adjustable deadband) above the outdoor air enthalpy, the dampers are to be in the full exhaust position (exhaust damper fully open and return damper fully closed). As the return enthalpy decreases below this point, the dampers transition to a full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open). Heating Mode Enable: When the zone thermostat generates a call for heating, transition the return & exhaust dampers to full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open), and the packaged unit will cycle on the gas heater to supply heat to the zone. The package unit’s internal controls protect the equipment from excessive operating Standard Packaged Units 22 Cx Assistant’s Sequence of Operation April 2004 conditions including high temperature, flame failure, excessive cycling (more than one every 5 minutes or 6 cycles/hour), low gas pressure, etc. If excessive operating conditions occur, shut down the unit to protect it. 10. Heating Mode Shutdown: If a call for heating has ended, a system failure has occurred, or the supply air temperature has risen above 120° F for more than one minute, cycle the heater off. After the heater has shut down, continue running the supply fan for 5 minutes before shutting it down (even if the unoccupied period begins). 11. Unoccupied Mode: Unoccupied mode occurs during unoccupied periods. In unoccupied mode, disable the packaged unit, close the outside air damper, and position the return/exhaust air dampers for full return air (no exhaust). When a thermostat’s override button is depressed during an unoccupied period, operate the system in the occupied mode for one hour. At the end of the hour, return the system to unoccupied mode. 12. Warm-up Mode: Identify Warm-up start time using an optimal start strategy based on outdoor air temperature and average zone temperature. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warmup period, initiate the warm-up mode. If building warm-up is required, command the return/exhaust air dampers to the return position (no exhaust) and enable the package unit. Terminate the warm-up mode after the average zone temperature has risen above 70°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 13. Cool-down Mode: Identify cool-down start time using an optimal start strategy based on outdoor air temperature and average zone temperature. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. If building cool-down is required, command the return/exhaust air dampers to the return position (no exhaust) and enable the packaged unit. Terminate the cool-down mode after the average zone temperature has fallen below 78°F (adjustable) and transition the system to occupied mode (if scheduled) or to unoccupied mode. 14. Night Setback/Setup: Enable system operation during unoccupied periods in the warm-up or cool-down mode if the space temperature falls below 55°F (adj.) or rises above 85°F (adj.). Stop the system when the thermostat reaches either its unoccupied cooling or unoccupied heating setpoints. 15. Heating System Outdoor Air Temperature Lockout: If the outdoor air temperature rises above 68 ° F (adjustable), the heating system shall be locked out. If the outdoor air temperature falls below 65° F (adjustable), the heater will be allowed to function as required to maintain load. 16. Mechanical Cooling System Outdoor Air Temperature Lockout: If the outdoor air temperature is below 63° F (adjustable), the mechanical cooling system shall be locked out. If the outdoor air temperature rises above 65° F (adjustable), the compressors will be allowed to function as required to maintain load. Standard Packaged Units 23 Cx Assistant’s Sequence of Operation April 2004 Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) OA outside air (OAT = outside air temperature) RTU rooftop unit (i.e. packaged unit) Note that these points are typically hard wired and not user accessible Point Name AI AO DI DO Analog Software Value OA DB Temp X OA RH X OA Enthalpy X Cooling Lockout Temp X Heating Lockout Temp X RTU-n Low Limit Setpoint Temp n RTU-n High Limit Setpoint Temp n RTU-n Economizer Staging Setpoint Temp n RTU-n RAT n RTU-n RA RH n RTU-n RA Enthalpy n RTU-n Staging Deadband Temp n RTU-n Cooling Alarm n RTU-n Cooling Status Standard Packaged Units Other Software Value n RTU-n Fan Enable RTU-n Heating Status Digital Software Value n n 24 Cx Assistant’s Sequence of Operation April 2004 RTU-n Heating Alarm n RTU-n Mode n RTU-n Economizer Mode n RTU Fire Alarm X RTU-n Minimum Air Damper Command n RTU-n Economizer/Return air damper Command n RTU-n Warm-up Mode Low Temp Setpoint n RTU-n Cool -down Mode High Temp Setpoint n RTU-n Override n RTU-n Space Temperature SetpointCooling n RTU-n Space Temperature SetpointHeating n RTU-n Space Temperature Unoccupied SetpointCooling n RTU-n Space Temperature Unoccupied SetpointHeating n RTU-n Space Temperature SetpointDeadband n Standard Packaged Units 25 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of Primary/Secondary chilled and hot water loops that serve multiple four-pipe fan coil units (FCUs) for each zone in the building. Each FCU has a constant volume supply fan, a chilled water cooling coil, a hot water heating coil, and a ducted air intake for ventilation air (outdoor air). Barometric relief dampers maintain building pressurization and allow building air to be exhausted outside. The chilled water loop includes water-cooled chillers and variable speed secondary chilled water pumps. The hot water loop includes two-stage boilers and variable speed secondary hot water pumps. A building automation system (BAS) controls the HVAC equipment. Appropriate reference in the specifications should be made for products that are integrated with these sequences including chillers, boilers, variable frequency drives (VFDs), and the like. Controls: Furnish control device with an interface for monitoring and control of points specified in the points table. The points table includes the minimum acceptable list of interface points. The selected component controls shall easily integrate into the BAS and allow for the collection, control, trending, and archiving of the specified points with a minimal need for intermediary gateways or hardwired connections to link control systems together. Interoperable control systems are preferred. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. FOUR PIPE FAN COIL UNITS WITH A CENTRAL PLANT, WATER COOLED CHILLERS AND COOLING TOWERS Four Pipe Fan Coil Units 26 Cx Assistant’s Sequence of Operation April 2004 SEQUENCES OF OPERATION Fan Coil Units (FCUs) 1. Occupied Periods (Normal operation): When an isolation area is scheduled to be occupied, operate the fan coil units that serve it. These scheduled periods are considered “occupied periods”. 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Fan Operation: Run the unit fans in all modes except unoccupied mode. 4. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact interface. Simultaneously, the fire alarm control must notify the BAS of the fire event to enable the BAS to disable the affected units. Once the fire alarm is reset, enable the affected unit(s) to resume normal operation. 5. Duct Pressure Safety: If negative static pressure over 2” WC is measured in the mixed air plenum or positive supply duct static pressure over 3” WC is measured in the supply duct, disable the fan via a hard wired interlock and initiate an equipment specific alarm (i.e. “FC-3 High Static Pressure” or “FC-2 Low Static Pressure”) at the operator workstation. An operator must reset each fan’s differential pressure switch before the fan may be re-enabled. Provide a local or BAS reset for this purpose. 6. Temperature Control: Use a solid state, electronic wall temperature sensor to switch the fan coil unit between “fan operation”, “cooling mode”, and “heating mode”. Each mode will vary the FCUs supply air temperature in order to satisfy the zone’s temperature setpoint. Set each temperature sensor for the following ranges: 1. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. 2. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between the heating and cooling setpoints. When the zone is in this deadband, set the fan coil unit to operate in “fan operation” mode only. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone its own adjustable unoccupied heating and cooling setpoints. 7. Cooling Mode: When the zone temperature rises to the cooling setpoint, begin modulating the chilled water valve with a control loop. When the cooling valve opens more than 30% (adj.), send a call for cooling to the central plant to maintain Four Pipe Fan Coil Units 27 Cx Assistant’s Sequence of Operation April 2004 a cooling mode supply air temperature setpoint of 55° F (adjustable). When the cooling valve closes to 5% (adj.), cancel the call for cooling . 8. Heating Mode: When the zone temperature falls to the heating setpoint, begin modulating the hot water valve. When the heating valve opens more than 10% (adj.), send a call for heating to the central plant to maintain a heating mode supply air temperature setpoint of 110° F (adjustable). When the heating valve closes to 5% (adj.), cancel the call for heating. 9. Filter Status: A differential pressure indicator is used to manually determine if the filter is dirty. The filter status indicator is not connected to the BAS. Isolation Areas 1. Isolation Areas: There are XX isolation areas as indicated on the plans. Each area is composed of 1 or more spaces served by 1 or more fan coil units that are operated together. Configure each isolation area separately from other isolation areas. Configuration includes scheduling and operational modes. The default occupancy schedule is 7:00 AM to 6:00 PM, M-F. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Occupied Mode: Prior to an occupied period, initiate a Warm-up mode or Cooldown mode if necessary. During Occupied Mode, enable operation of the system, including enabling the fan coil units that serve this area. At the end of an occupied period, initiate unoccupied mode. 3. Warm-up Mode: Use an optimal start strategy to initiate the warm-up start time. Base optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, initiate the warmup mode. The optimal start period should pre-heat the building so that the average zone temperature is 70°F (adjustable) by the occupied period. If building warmup is required, enable the fan coil units. Leave the chilled water valve closed (or in bypass), and leave the general exhaust fans off. Enable the central heating plant but leave the central cooling disabled. After the average zone temperature has risen above 70°F (adjustable), terminate the warm-up cycle, and initiate occupied mode. 4. Cool-down Mode: Use an optimal start strategy to initiate the cool-down start time. Base the optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. The optimal start period should pre-cool the building so that the average zone temperature is 78°F (adjustable) by the occupied period. If a cool-down cycle is required, enable the fan coil units and leave the general exhaust fans off. Enable the chilled water system but leave the central heating disabled. After the average zone temperature has dropped below 78°F (adjustable), terminate the cool-down cycle and initiate occupied mode. Four Pipe Fan Coil Units 28 Cx Assistant’s Sequence of Operation April 2004 5. Night Setback/Setup Mode: During an unoccupied period, start the fan coil units in the warm-up or cool-down mode if a zone temperature falls below the unoccupied heating setpoint or rises above the unoccupied cooling setpoint. End the setback/setup mode when the zones are below/above their unoccupied setpoints. 6. Unoccupied Mode: During unoccupied periods, disable the fan coil units, close their chilled water valves (or put them in bypass), and close their hot water valves (or put them in bypass). Cancel calls for central plant cooling and heating. When a thermostat override button is depressed during unoccupied period, operate the isolation area in occupied mode for one hour as follows: Operate the fan coil units in the isolation area in occupied mode except for the general exhaust fans (leave them off). Enable the central plant. Chilled Water System 1. Cooling Mode Enable/Disable: When building comfort cannot be maintained, the fan coil units call for supplementary cooling by sending a cooling request to the central plant. When all of the FCU chilled water valve positions fall below 5% full open, cancel the call for cooling and initiate chiller shutdown. 2. Secondary Chilled Water Pump Enable: When the BAS registers a call for central plant cooling, enable both the secondary chilled water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 5 seconds. Modulate the speed of the pumps in order to maintain a differential pressure setpoint of 15 PSID (adj.) at the central plant. Inhibit starting of the primary pumps and chiller if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Chilled Water Pump Enable (Chiller Initiation): When the BAS registers a call for central plant cooling, determine the lead chiller as indicated below. Open the chilled water isolation valve to the lead chiller. If the valve has not proofed open after 30 seconds, close the valve and enable and start the lag chiller. Repeat valve operation with lag chiller. If both valves fail to open, initiate chiller shutdown operation and send equipment specific critical alarm (“CH-1 CHW Isolation Valve Failed to Open”) to operator workstation. If valve proofs open, enable the primary chilled water pump dedicated to the lead chiller. After 30 seconds, proof flow. If the flow is not proved by a differential pressure switch, disable the pump, close the valve and set the lag chiller as the lead chiller. If both pumps fail to provide flow, initiate the chiller shutdown operation. If either pump fails, send equipment specific critical alarms to the operator workstation. 4. Chiller Enable: Upon proof of primary chilled water and condenser water flow, enable the selected chiller. A hard-wired flow switch will act as a back up to ensure that chiller only starts with chilled water flow. Set the chilled water Four Pipe Fan Coil Units 29 Cx Assistant’s Sequence of Operation 5. 6. 7. 8. April 2004 temperature supply temperature to 45° F (adjustable). After 30 seconds, prove chiller operation by means of a hard-wired current switch. If the chiller fails to prove operation, initiate its shutdown sequence. Then, enable the lag chiller and it’s primary pump. If both chillers fail to proof, send an equipment specific alarm (“Chillers Failed”) to the operator workstation. During operation, use the chillers internal safeties to cause an alarm and shut down the machine. If the chiller does not develop at least a 3°F temperature difference after 15 minutes of being proved on, initiate an alarm on the operator work station. Operate the chillers and their associated primary pumps lead/lag. Swap the lead and lag chillers (as well as their primary pumps) on Sunday at 3:00 AM as long as the lead chiller has operated at least 40 hours and all equipment are disabled. Chiller Staging: If the chilled water return temperature rises to 12°F (adjustable) above the chilled water setpoint, enable lag chiller operation and start the chiller. Run both chillers until the chilled return temperature falls to 5°F above the chilled water setpoint. At this point, initiate the lag chiller shutdown sequence. Continue running the lead chiller until the chilled water return temperature falls to the setpoint minus the deadband. Chiller Shutdown: Upon a call from the BAS or an internal chiller alarm, initiate chiller shutdown. Disable the chiller but continue to run the primary pump and the condenser water pump serving the chiller for 5 minutes. After 5 minutes, disable the pumps and close the chiller’s isolation valves. If no other chiller is enabled, initiate the condenser water system shutdown and shutoff the secondary water pumps. Use a timer in the BAS to keep the chiller from cycling on and off more often than every 5 minutes [this may be redundant to the chiller’s internal safeties]. Chiller Safeties: Initiate chiller shutdown if the BAS senses low chilled water flow, low condenser water flow, low chilled water temperature (less than 38° F), or high condenser water temperature (over 90° F). Initiate an equipment specific alarm at the operator workstation. Chilled Water System Outdoor Air Temperature Lockout: If the outdoor air temperature falls below 63° F (adjustable), lock out the chilled water system such that the chillers and chilled water pumps do not run. If the outdoor air temperature rises above 65° F (adjustable) for 20 minutes (adjustable), enable the chilled water system. Condenser Water System 1. Chemical Treatment: Provide chemical treatment for the cooling towers via an automatic chemical feed and bleed system. Run the water treatment system independently of the BAS. 2. Safeties: Disable the condenser water pump and the chiller operation if the water level in the cooling tower basin falls below the minimum. Initiate an equipment specific alarm (“Low Water Level in CT-1”) at the operator workstation. 3. Condenser Water Pump Enable: When the BAS registers a call for cooling from the central plant, enable the lead condenser water pump. Prove condenser water Four Pipe Fan Coil Units 30 Cx Assistant’s Sequence of Operation April 2004 flow within 30-seconds (adjustable) using a differential pressure switch. If the flow is not proved, disable the pump, and enable and start the lag pump. Send equipment specific critical alarm (“CWP-1 Failed”) to the operator workstation. The lag pump is also enabled by the start-up of the lag chiller. If both pumps fail to provide flow, initiate chiller shutdown operation and initiate a critical alarm (“Condenser Water Pumps failed”) to the operator workstation. Swap the lead and lag pumps on Sunday at 3:00 AM as long as the lead pump has operated at least 40 hours and both pumps are shut down. 4. Condenser Water Temperature Control: Prior to operation of the condenser water pump, the cooling tower bypass valve should be in the bypass position (bypassing the cooling towers) and the cooling tower fans shut off. Once condenser water flow is proved, operate the cooling tower fan and bypass valve in order to maintain a condenser water supply setpoint between 75° F and 85° F. Modulate the condenser water bypass valve so that at 80° F condenser water supply temperature, the water is not bypassing the cooling tower. Start both cooling tower fans at minimum speed when the water temperature increases to 82°F. Modulate the tower fans speed as necessary to maintain the setpoint temperature. If the temperature exceeds the high limit of 90° F, initiate the chiller shutdown sequence and send an equipment specific alarm (“Condenser Water High Limit Temperature”) to the operator workstation. As the temperature falls below 82 ° F, disable the fans and modulate the bypass valve to maintain setpoint temperature. If the condenser supply temperature falls below the low limit of 70° F after running for 5 minutes, initiate the chiller shutdown sequence and send an equipment specific alarm (“Condenser Water Low Limit Temperature”) to the operator workstation. 5. Condenser Water System Shutdown: When the lag chiller is shutdown, disable the lag chilled water pump after a 5 minute run time. Adjust the condenser water fan speed and bypass valve positions to maintain temperature as indicated elsewhere. When the lead chiller is shutdown, run the lead condenser water pump for 5 minute. Then disable the cooling tower fans, disable the lead pump, and modulate the bypass valve to full bypass. Heating Hot Water System 1. Heating Mode Enable: Generate a call for heating from zone controllers if any of the zone valve positions is greater than 10% (adjustable) of full open until all are below 5% (adjustable). 2. Secondary Hot Water Pump Enable: When the BAS registers a call for central plant heating, enable both the secondary hot water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 15 seconds using a differential pressure switch. Modulate the speed of the pumps in order to maintain a pressure drop of 10 PSID at the hot water using a differential pressure transmitter. Inhibit starting of the primary pumps and boiler if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. If either pump fails to Four Pipe Fan Coil Units 31 Cx Assistant’s Sequence of Operation 3. 4. 5. 6. 7. April 2004 start, initiate an equipment specific critical alarm at the operator workstation. When they are both enabled, lead and lag pumps should run at the same speed. Primary Hot Water Pump Enable (Boiler Initiation): Open the lead boiler’s isolation valves. If the valve opening fails to proof within 30-seconds, close the valve, enable the lag boiler, and send an equipment specific alarm (“B-1 Isolation Valve Failed to Open”) to the operator workstation. If valve opening is successful, enable the primary hot water pump dedicated to the lead boiler. If the flow is not proved within 30 seconds, disable the pump, close the valve and set the lag boiler as the lead boiler. If both valves fail to open, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. If both pumps fail to provide flow, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead and lag pumps. Boiler Enable: Upon proof of primary hot water flow, enable the selected boiler. Use a hard-wired flow switch as a back up to ensure that boiler only starts with hot water flow. Send an initial hot water temperature of 180° F to the boiler controller. After 60 seconds, prove boiler operation by means of a hard-wired current switch. Operate the boilers lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead position. Enable the lag boiler to start. If either or both boilers fail to prove or fail to proof when required to operate, initiate boiler shutdown and send equipment specific alarms to the operator workstation. During operation, use the boiler’s internal safeties to initiate an equipment alarm at the operator workstation and disable the machine. If the boiler does not develop at least a 3°F temperature difference after 15 minutes of being enabled initiate a equipment specific alarm at the operator workstation. Boiler Staging: Modulate internal boilers controls between the boiler’s two stages to meet the BAS water loop setpoint. If during boiler operation, the hot water temperature differential falls to 5°F (adjustable), initiate the lag boiler operation. Continue to run both boilers until the hot water temperature differential rises to 12° F. At this point, initiate the lag boiler shutdown sequence. Boiler Shutdown: When all calls for central plant heating are cancelled or an internal alarm occurs, initiate boiler shutdown. Provide the BAS with redundant sensors for hot water flow, hot water temperature Hi Limit (more than 200° F). Disable operation of the affected boiler(s) if the limits are exceeded. If both boilers trip or fail to proof, initiate an equipment specific alarm at the operator workstation. Prevent the boiler from cycling on and off more often than once every 5 minutes (this may be redundant to the boiler’s internal safeties). For each boiler, disable the boiler before shutting down its pump. After disabling the boiler, run the primary boiler pump serving the boiler for 5 minutes. After 5 minutes, shut down the primary boiler pump and close the hot water isolation valves. If no other boiler is enabled, shut off the secondary water pumps. Hot Water System Outdoor Air Temperature Lockout: If the outdoor air temperature rises above 75° F (adjustable), lock out the hot water system so the Four Pipe Fan Coil Units 32 Cx Assistant’s Sequence of Operation April 2004 boilers and hot water pumps do not run. If the outdoor air temperature falls below 70° F (adjustable) for 20 minutes (adjustable), enable the hot water system. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) B boiler DB dry-bulb CH chiller or chilled (i.e. CHW = chilled water) Cmd command COV change of value CT cooling tower FCU Fan coil unit OA outside air (OAT = outside air temperature) P pump (PP = primary pump, SP = secondary pump) R return (RAT = return air temperature) S supply (SAT = supply air temperature) SL secondary loop W water (CW = condenser water, HW = hot water) Resolution of analog inputs: °F 0.1 psid 0.005 ” water cfm 1 Four Pipe Fan Coil Units 33 Cx Assistant’s Sequence of Operation April 2004 rpm 1 kW 0.1 % 0.1 Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value Interval Show on or Graphic COV OA DB Temp X 15 X CHW Lockout Temp X COV 0.5,15 X HHW Lockout Temp X COV 0.5,15 X X1 15 X CHWS Temp X1 >60 when CH 15 flow after 1 minute, <38 X CHWR Temp CHW SL Pressure Drop Setpoint CHW SL Pressure Drop =Cmd COVX after 1 10%,15 minute X CHWSP-n Enable n1 CHWSP-n Override CHWSP-n Status COVX 10%,15 X COV X COV X Proof after 1 COV minute X n n1 CHWSP-n Four Pipe Fan Coil Units n >1000 COV 1 34 Cx Assistant’s Sequence of Operation Point Name April 2004 Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value Interval Show on or Graphic COV Runtime CHWSP-n Cycle Counter n CHWSP-n Cmd Speed CHWSP-n Run Speed >6 hour COV n =Cmd COVX after 1 10%,15 minute n CHWSP-n Alarm n CHWSP-n Power n CHWSP Lead/Lag X X COV X n1 15 X CH-n Outlet Temp n1 >60 when call for 15 cooling, <38 X CH Setpoint Temp X COV CH Staging Setpoint Temp X COV CH Staging Deadband Temp X COV CH-n Inlet Temp CH-n CHW Isolation Valve Cmd CH-n CHW Isolation Valve Feedback n1 n1 Four Pipe Fan Coil Units COV COV X 35 Cx Assistant’s Sequence of Operation Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value CH-n CW Isolation Valve Cmd CH-n CW Isolation Valve Feedback April 2004 n1 COV n1 CH-n Alarm n n1 CH-n Enable Interval Show on or Graphic COV CH-n Override n COV X COV X COV X COV X CH-n CHW flow status n1 COV X CH-n CW flow status n1 COV X Proof after 1 COV minute X 1 CH-n Status n CH-n Chiller Runtime CH-n ReStart Timer n >1000 n 5 Minutes to restart CH-n Cycle Counter n CH Lead/Lag X CHWPP-n Enable X COV X COV X Proof after 1 COV minute X n n1 CHWPP-n Runtime Four Pipe Fan Coil Units n COV COV n1 CHWPP-n Override CHWPP-n Status >6 hour COV 1 >1000 COV 1 36 Cx Assistant’s Sequence of Operation Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value CHWPP Lead/Lag CWR Temp CWS Temp X Interval Show on or Graphic COV COV X X1 15 X X1 >87 , < 72 when 15 flowing for 5 minutes X CWP-n Enable n1 CW-n Override COV X COV X Proof after 1 COV minute X n CWP-n Status n 1 CWP-n Runtime n CWP Lead/Lag >1000 X CW Bypass Cmd CW Bypass Feedback April 2004 COV 1 COV COVX 10%,15 X =Cmd COVX after 1 10%,15 minute X CW Temp Set point X COV0.5,15 CW Minimum Temp X COV CW Maximum Temp X COV CW Temp Set point deadband X COV Four Pipe Fan Coil Units X X 37 Cx Assistant’s Sequence of Operation Point Name April 2004 Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value CW Valve Set point Temp X CT-n Alarm COV n CT-n Enable n 1 n CT-n Power n CT-n Runtime n COV X COV X Proof after 1 COV minute X 15 CT-n Cycle Counter n CT Lead/Lag X CT-n Low Water Alarm n X1 Four Pipe Fan Coil Units >6 hour COV COV X COV X X =Cmd COVX after 1 10%,15 minute X HWSP-n override COV 1 X COVX 10%,15 X HWSP-n Enable >1000 >180 or <110 when 15 CH flow after 1 minute HW SL Pressure Drop Setpoint HW SL Pressure Drop X n CT-n Status HWS Temp COV 1 CT-n Override Interval Show on or Graphic COV n1 n COV X COV X 38 Cx Assistant’s Sequence of Operation Point Name April 2004 Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value HWSP-n Status Proof after 1 COV minute n1 HWSP-n Runtime n HWSP-n Cycle Counter HWSP-n Cmd Speed Interval Show on or Graphic COV n >1000 COV 1 >6 hour COV X n1 =Cmd COVX after 1 10%,15 minute HWSP-n Run n Speed HWSP Lead/Lag X B-n Inlet Temp n COV X 15 X >190 or <110 when 15 CH flow after 1 minute X B-n Outlet Temp n1 B Setpoint Temp X COV B Staging Setpoint Temp X COV B Staging Deadband Temp X COV B-n Isolation Valves n1 B-n Alarm B-n Enable Four Pipe Fan Coil Units COV n n1 COV X COV X 39 Cx Assistant’s Sequence of Operation Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value B-n HW Isolation Valve Cmd B-n HW Isolation Valve Feedback n1 n1 n B-n Re-Start Timer COV X COV X Proof after 1 COV minute X n >1000 n 5 Minutes to restart B-n Cycle Counter n B Lead/Lag X HWPP-n Enable >6 hour HWPP-n Runtime n HWPP Lead/Lag COV X COV X Proof after 1 COV minute X >1000 X n1 FCU-n Operating Four Pipe Fan Coil Units n COV X n n1 COV 1 COV n1 HWPP-n Override FCU-n Fire Alarm X n B-n Status HWPP-n Status COV n B-n Runtime Interval Show on or Graphic COV COV B-n Override B-n HW flow status April 2004 COV 1 COV X COV X COV X 40 Cx Assistant’s Sequence of Operation Point Name April 2004 Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value Interval Show on or Graphic COV Mode FCU-n Mode Override FCU-n SAT n 15 X COV X Proof after 1 COV minute X n1 FCU-n Supply Fan Status n 1 FCU-n Supply Fan Runtime n FCU-n CHWV Bypass Cmd >1000 COV 1 COVX 10%,15 n =Cmd COVX after 1 10%,15 minute n FCU-n HHWV Bypass Cmd FCU-n HHWV Bypass Feedback X n FCU-n Supply Fan Enable FCU-n CHWV Bypass Feedback COV COVX 10%,15 n =Cmd COVX after 1 10%,15 minute n FCU-n Warm-up Mode Low Temp Setpoint n COV X FCU-n CoolDown Mode High Temp Setpoint n COV X FCU-n Call Four Pipe Fan Coil Units n COV 41 Cx Assistant’s Sequence of Operation Point Name April 2004 Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value Interval Show on or Graphic COV for Heating FCU-n Call for Cooling n FCU-n Space Temperature n Sensor COV COV0.5,15 X FCU-n Space Temperature SetpointCooling n COV X FCU-n Space Temperature SetpointHeating n COV X FCU-n Space Temperature Unoccupied SetpointCooling n COV X FCU-n Space Temperature Unoccupied SetpointHeating n COV X FCU-n Space Temperature SetpointDeadband n COV X 1 When a gateway is used to integrate controls, these points shall be hardwired to the DDC system. Four Pipe Fan Coil Units 42 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of Primary/Secondary chilled and hot water loops, multiple air handling units (AHUs), and 1 single duct constant air volume (CAV) terminal unit for each zone in the building. The CAV units provide conditioned air to the occupied space and, at the perimeter of the building, they include a hot water coil and automatic two-way valve to reheat the main supply air. Each AHU has a constant volume supply fan, a chilled water cooling coil, and an outdoor air damper with a 2-position actuator. Barometric relief dampers maintain building pressurization and allow building air to be exhausted outside. The chilled water loop includes air-cooled chillers and variable speed secondary chilled water pumps. The hot water loop includes two-stage boilers and variable speed secondary hot water pumps. A building automation system (BAS) controls the HVAC equipment. Appropriate reference in the specifications should be made for products that are integrated with these sequences including chillers, boilers, and the like. Controls: Furnish control device with an interface for monitoring and control of points specified in the points table. The points table includes the minimum acceptable list of interface points. The selected component controls shall easily integrate into the BAS and allow for the collection, control, trending, and archiving of the specified points with a minimal need for intermediary gateways or hardwired connections to link control systems together. Interoperable control systems are preferred. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. CONSTANT-AIR VOLUME (CAV) UNITS WITH A CENTRAL PLANT, AIR COOLED CHILLERS Constant Air Volume Units with Central Plant 43 Cx Assistant’s Sequence of Operation April 2004 SEQUENCES OF OPERATION Air Handling Units (AHUs) 1. Occupied Periods (Normal operation): When an isolation area is scheduled to be occupied, operate the air handling unit that serves it. These scheduled periods are considered “occupied periods”. 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Fan Operation: Run the unit fans in all modes except unoccupied mode. Open the minimum outside air dampers when the supply fan is running. Proof the supply fan using an external current switch (CS). 4. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply fan by a hardwired contact interface. Simultaneously, the fire alarm control must notify the BAS of the fire event to enable the BAS to disable the affected units. Once the fire alarm is reset, enable the affected unit(s) to resume normal operation. 5. Duct Pressure Safety: If negative static pressure over 2” WC is measured in the mixed air plenum or positive supply duct static pressure over 3” WC is measured in the supply duct, disable the fan via a hard wired interlock and initiate an equipment specific alarm (i.e. “AH-3 High Static Pressure” or “AH-2 Low Static Pressure”) at the operator workstation. An operator must reset each fan’s differential pressure switch before the fans may be re-enabled. Provide a local or BAS reset for this purpose. 6. Supply Air Temperature Control: The chilled water valve modulates to maintain the supply air temperature when at least one zone serves by the unit is calling for cooling. The supply air temperature setpoint is 55° F (adjustable). When the valve opens more than 30% (adj.), send a call for cooling to the central plant. When the valve closes to 5% (adj.), cancel the call for cooling. If no zones are calling for cooling, close the chilled water valve. 7. Filter Status: Whenever the supply fan is running, send an equipment specific alarm (“AH-1 Dirty Filter”) to the operator workstation if the differential pressure over the filter exceeds 150% (adjustable) of the its design value. Isolation Areas 1. Isolation Areas: There are XX isolation areas as indicated on the plans. Each area is composed of 1 or more spaces served by 1 or more CAV terminal units that are operated together. Configure each isolation area separately from other isolation areas. Configuration includes scheduling and operational modes. The default occupancy schedule is 7:00 AM to 6:00 PM, M-F. Constant Air Volume Units with Central Plant 44 Cx Assistant’s Sequence of Operation April 2004 NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Occupied Mode: Prior to an occupied period, initiate a Warm-up mode or Cooldown mode if necessary. During Occupied Mode, enable operation of the system, including enabling the air handling unit fans that serve this area and opening the outdoor air dampers to100% open. At the end of an occupied period, initiate unoccupied mode. 3. Warm-up Mode: Use an optimal start strategy to initiate the warm-up start time. Base optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, initiate the warmup mode. The optimal start period should pre-heat the building so that the average zone temperature is 70°F (adjustable) by the occupied period. If building warmup is required, enable the air handling units. Leave the chilled water valve closed (or in bypass), and leave the general exhaust fans off. Enable the CAV unit hot water valves to normal occupied operation. Enable the central heating plant but leave the central cooling disabled. After the average zone temperature has risen above 70°F (adjustable), terminate the warm-up cycle, and initiate occupied mode. 4. Cool-down Mode: Use an optimal start strategy to initiate the cool-down start time. Base the optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. The optimal start period should pre-cool the building so that the average zone temperature is 78°F (adjustable) by the occupied period. If a cool-down cycle is required, enable the air handling units and leave the general exhaust fans off. Enable the chilled water system but leave the central heating and CAV hot water valves disabled. After the average zone temperature has dropped below 78°F (adjustable), terminate the cool-down cycle and initiate occupied mode. 5. Night Setback/Setup Mode: During an unoccupied period, start the air-handling unit in the warm-up or cool-down mode if a zone temperature falls below the unoccupied heating setpoint or rises above the unoccupied cooling setpoint. End the setback/setup mode when the zones are below/above their unoccupied setpoints. 6. Unoccupied Mode: During unoccupied periods, close CAV unit hot water valves (or put them in bypass), disable the air handling units, close their chilled water valves (or put them in bypass), and close their outside air damper(s). Cancel calls for central plant cooling and heating. When a thermostat override button is depressed during unoccupied period, operate the isolation area in occupied mode for one hour as follows: Operate the air handling unit in occupied mode except for the general exhaust fans (leave them off). Enable the central plant. CAV Zone Control Constant Air Volume Units with Central Plant 45 Cx Assistant’s Sequence of Operation April 2004 1. Temperature Control: Use a solid state, electronic wall temperature sensor to adjust the zone setpoint. Set each temperature sensor for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between the heating and cooling setpoints. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone its own adjustable unoccupied heating and cooling setpoints. 2. Zone Cooling Mode: When the zone’s temperature rises to 1°F (adjustable) above its setpoint, send a call for cooling to the air handling unit. 3. Zone Heating Mode (Perimeter Zones Only): When the zone’s temperature falls to 1 ° F (adjustable) below its setpoint, the zone is in heating mode. Modulate the reheat coil control valve to satisfy the space temperature. Once the valve opens to more than 10% (adj.), send a call for heating to the central plant. When the valve closes to 5% (adj.), cancel the call for heating. Chilled Water System 1. Cooling Mode Enable/Disable: When building comfort cannot be maintained, the air handlers call for cooling by sending a cooling request to the central plant. When all of the AHU chilled water valve positions fall below 5% full open, cancel the call for cooling and initiate chiller shutdown. 2. Secondary Chilled Water Pump Enable: When the BAS registers a call for central plant cooling, enable both the secondary chilled water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 5 seconds. Modulate the speed of the pumps in order to maintain a differential pressure setpoint of 15 PSID (adj.) at the central plant. Inhibit starting of the primary pumps and chiller if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Chilled Water Pump Enable (Chiller Initiation): When the BAS registers a call for central plant cooling, determine the lead chiller as indicated below. Open the chilled water isolation valve to the lead chiller. If the valve has not proofed open after 30 seconds, close the valve and enable and start the lag chiller. Repeat valve operation with lag chiller. If both valves fail to open, initiate chiller shutdown operation and send equipment specific critical alarm (“CH-1 CHW Isolation Valve Failed to Open”) to operator workstation. If valve proofs open, enable the primary chilled water pump dedicated to the lead chiller. After 30 seconds, proof flow. If the flow is not proved by a differential pressure switch, disable the pump, close the valve and set the lag chiller as the lead chiller. If both Constant Air Volume Units with Central Plant 46 Cx Assistant’s Sequence of Operation 4. 5. 6. 7. 8. April 2004 pumps fail to provide flow, initiate the chiller shutdown operation. If either pump fails, send equipment specific critical alarms to the operator workstation. Chiller Enable: Upon proof of primary chilled water, enable the selected chiller. A hard-wired flow switch will act as a back up to ensure that chiller only starts with chilled water flow. Set the chilled water temperature supply temperature to 45° F (adjustable). After 30 seconds, prove chiller operation by means of a hard-wired current switch. If the chiller fails to prove operation, initiate its shutdown sequence. Then, enable the lag chiller and it’s primary pump. If both chillers fail to proof, send an equipment specific alarm (“Chillers Failed”) to the operator workstation. During operation, use the chillers internal safeties to cause an alarm and shut down the machine. If the chiller does not develop at least a 3°F temperature difference after 15 minutes of being proved on, initiate an alarm on the operator work station. Operate the chillers and their associated primary pumps lead/lag. Swap the lead and lag chillers (as well as their primary pumps) on Sunday at 3:00 AM as long as the lead chiller has operated at least 40 hours and all equipment are disabled. Chiller Staging: If the chilled water return temperature rises to 12°F (adjustable) above the chilled water setpoint, enable lag chiller operation and start the chiller. Run both chillers until the chilled return temperature falls to 5°F above the chilled water setpoint. At this point, initiate the lag chiller shutdown sequence. Continue running the lead chiller until the chilled water return temperature falls to the setpoint minus the deadband. Chiller Shutdown: Upon a call from the BAS or an internal chiller alarm, initiate chiller shutdown. Disable the chiller but continue to run the primary pump serving the chiller for 5 minutes. After 5 minutes, disable the pump and close the chiller’s isolation valves. If no other chiller is enabled, shutoff the secondary water pumps. Use a timer in the BAS to keep the chiller from cycling on and off more often than every 5 minutes [this may be redundant to the chiller’s internal safeties]. Chiller Safeties: Initiate chiller shutdown if the BAS senses low chilled water flow or low chilled water temperature (less than 38° F). Initiate an equipment specific alarm at the operator workstation. Chilled Water System Outdoor Air Temperature Lockout: If the outdoor air temperature falls below 63° F (adjustable), lock out the chilled water system such that the chillers and chilled water pumps do not run. If the outdoor air temperature rises above 65° F (adjustable) for 20 minutes (adjustable), enable the chilled water system. Heating Hot Water System 1. Heating Mode Enable: Generate a call for heating from zone controllers if any of the zone valve positions is greater than 10% (adjustable) of full open until all are below 5% (adjustable). 2. Secondary Hot Water Pump Enable: When the BAS registers a call for central plant heating, enable both the secondary hot water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Constant Air Volume Units with Central Plant 47 Cx Assistant’s Sequence of Operation 3. 4. 5. 6. April 2004 Proof the start of both of the pumps after 15 seconds using a differential pressure switch. Modulate the speed of the pumps in order to maintain a pressure drop of 10 PSID at the hot water using a differential pressure transmitter. Inhibit starting of the primary pumps and boiler if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. If either pump fails to start, initiate an equipment specific critical alarm at the operator workstation. When they are both enabled, lead and lag pumps should run at the same speed. Primary Hot Water Pump Enable (Boiler Initiation): Open the lead boiler’s isolation valves. If the valve opening fails to proof within 30-seconds, close the valve, enable the lag boiler, and send an equipment specific alarm (“B-1 Isolation Valve Failed to Open”) to the operator workstation. If valve opening is successful, enable the primary hot water pump dedicated to the lead boiler. If the flow is not proved within 30 seconds, disable the pump, close the valve and set the lag boiler as the lead boiler. If both valves fail to open, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. If both pumps fail to provide flow, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead and lag pumps. Boiler Enable: Upon proof of primary hot water flow, enable the selected boiler. Use a hard-wired flow switch as a back up to ensure that boiler only starts with hot water flow. Send an initial hot water temperature of 180° F to the boiler controller. After 60 seconds, prove boiler operation by means of a hard-wired current switch. Operate the boilers lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead position. Enable the lag boiler to start. If either or both boilers fail to prove or fail to proof when required to operate, initiate boiler shutdown and send equipment specific alarms to the operator workstation. During operation, use the boiler’s internal safeties to initiate an equipment alarm at the operator workstation and disable the machine. If the boiler does not develop at least a 3°F temperature difference after 15 minutes of being enabled initiate a equipment specific alarm at the operator workstation. Boiler Staging: Modulate internal boilers controls between the boiler’s two stages to meet the BAS water loop setpoint. If during boiler operation, the hot water temperature differential falls to 5°F (adjustable), initiate the lag boiler operation. Continue to run both boilers until the hot water temperature differential rises to 12° F. At this point, initiate the lag boiler shutdown sequence. Boiler Shutdown: When all calls for central plant heating are cancelled or an internal alarm occurs, initiate boiler shutdown. Provide the BAS with redundant sensors for hot water flow, hot water temperature Hi Limit Constant Air Volume Units with Central Plant 48 Cx Assistant’s Sequence of Operation April 2004 (more than 200° F). Disable operation of the affected boiler(s) if the limits are exceeded. If both boilers trip or fail to proof, initiate an equipment specific alarm at the operator workstation. Prevent the boiler from cycling on and off more often than once every 5 minutes (this may be redundant to the boiler’s internal safeties). For each boiler, disable the boiler before shutting down its pump. After disabling the boiler, run the primary boiler pump serving the boiler for 5 minutes. After 5 minutes, shut down the primary boiler pump and close the hot water isolation valves. If no other boiler is enabled, shut off the secondary water pumps. 7. Hot Water System Outdoor Air Temperature Lockout: If the outdoor air temperature rises above 75° F (adjustable), lock out the hot water system so the boilers and hot water pumps do not run. If the outdoor air temperature falls below 70° F (adjustable) for 20 minutes (adjustable), enable the hot water system. Points Table: Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) AHU air handling unit B boiler CH chiller or chilled (i.e. CHW = chilled water) Cmd command COV change of value DB dry-bulb CAV constant air volume terminal unit OA outside air (OAT = outside air temperature) P pump (PP = primary pump, SP = secondary pump) R return (RAT = return air temperature) S supply (SAT = supply air temperature) Constant Air Volume Units with Central Plant 49 Cx Assistant’s Sequence of Operation April 2004 SL secondary loop Temp temperature W water (CHW = chilled water, HW = hot water) Resolution of analog inputs: °F 0.1 psid 0.005 ” water cfm 1 rpm 1 kW 0.1 % 0.1 Analog Digital Other Alarm Point Name AI AO DI DO Software Software Software Logic Value Value OA DB Temp X Interval Show on or Graphic COV 15 X CHW Lockout Temp X COV 0.5,15 X HHW Lockout Temp X COV 0.5,15 X CHWR Temp CHWS Temp CHW SL Pressure Drop Setpoint X1 15 X >60 when CH flow after 1 minute, <38 X1 X Constant Air Volume Units with Central Plant 15 X COVX 10%,15 50 Cx Assistant’s Sequence of Operation CHW SL Pressure Drop April 2004 =Cmd after 1 minute X CHWSP-n Enable n1 CHWSP-n Override n1 CHWSP-n Runtime n CHWSP-n Cycle Counter CHWSP-n Cmd Speed COV X COV X Proof after 1 minute COV X >1000 COV 1 >6 hour COV n CHWSP-n Status n COVX 10%,15 n CHWSP-n Alarm n CHWSP Lead/Lag X CH-n Inlet Temp COV n1 15 X >60 when call for cooling, <38 CH-n Outlet Temp n1 CH Setpoint Temp X COV CH Staging Setpoint Temp X COV CH Staging Deadband Temp X COV CH-n CHW Isolation Valve Cmd n1 Constant Air Volume Units with Central Plant X 15 X COV 51 Cx Assistant’s Sequence of Operation CH-n CHW Isolation Valve Feedback April 2004 n1 COV X COV X COV X COV X COV X Proof after 1 minute COV X n >1000 COV 1 n 5 Minutes to restart CH-n Alarm n CH-n Alarm Text n CH-n Enable n1 CH-n Override n CH-n Status n1 CH-n Chiller Runtime CH-n ReStart Timer CH-n Cycle Counter n CH Lead/Lag X CHWPP-n Enable CHWPP-n Runtime X COV X COV X Proof after 1 minute COV X >1000 COV 1 n n1 n CHWPP Lead/Lag HWS Temp X1 Constant Air Volume Units with Central Plant COV COV n1 CHWPP-n Override CHWPP-n Status >6 hour X COV >180 or <110 X 15 X 52 Cx Assistant’s Sequence of Operation April 2004 when B flow after 1 minute HW SL Pressure Drop Setpoint HW SL Pressure Drop =Cmd after 1 minute X HWSP-n Enable n1 HWSP-n override n1 HWSP-n Runtime n HWSP-n Cycle Counter n X COV X Proof after 1 minute COV X >1000 COV 1 >6 hour COV n1 HWSP-n Alarm n HWSP Lead/Lag X B-n Inlet Temp COVX 10%,15 COV n HWSP-n Status HWSP-n Cmd Speed COVX 10%,15 X COV n 15 X >190 or <110 when B flow after 1 minute B-n Outlet Temp n1 B Setpoint Temp X COV B Staging X COV Constant Air Volume Units with Central Plant X 15 X 53 Cx Assistant’s Sequence of Operation April 2004 Setpoint Temp B Staging Deadband Temp X B-n Alarm COV n B-n Alarm Text n COV X COV X X B-n Enable n1 COV B-n HW Isolation Valve Cmd n1 COV B-n HW Isolation Valve Feedback n1 COV X COV X Proof after 1 minute COV X n >1000 COV 1 n 5 Minutes to restart B-n Override n B-n Status n B-n Runtime B-n ReStart Timer B-n Cycle Counter n B Lead/Lag X HWPP-n Enable HWPP-n Runtime X COV X COV X Proof after 1 minute COV X >1000 COV 1 n n1 n Constant Air Volume Units with Central Plant COV COV n1 HWPP-n Override HWPP-n Status >6 hour 54 Cx Assistant’s Sequence of Operation April 2004 HWPP Lead/Lag X AHU-n Fire Alarm n1 AHU-n Operating Mode n AHU-n Mode Override n COV X COV X COV X COV X AHU-n SAT n 15 X AHU-n OAT n 15 X AHU-n OA Damper Cmd n COVX 10%,15 AHU-n Supply Fan Enable n1 COV X COV X AHU-n Supply Fan Status AHU-n CHWV Bypass Cmd Proof after 1 minute n1 COVX 10%,15 n AHU-n Warm-up Mode Low Temp Setpoint n COV X AHU-n Cool-Down Mode High Temp Setpoint n COV X COV X AHU-n Filter Alarm n Constant Air Volume Units with Central Plant 55 Cx Assistant’s Sequence of Operation April 2004 AHU-n Call for Cooling n COV CAV-n n Zone Temp COV0.5,15 X CAV-n Zone Temp SetpointCooling n COV X CAV-n Zone Temp SetpointHeating n COV X CAV-n Zone Temp Unoccupied SetpointCooling n COV X CAV-n Zone Temp Unoccupied SetpointHeating n COV X CAV-n Zone Temp SetpointDeadband n COV X COV X CAV-n Override n CAV-n Operating Mode CAV-n HW Valve Cmd n n Constant Air Volume Units with Central Plant COV COVX 10%,15 56 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of Primary/Secondary chilled and hot water loops, multiple air handling units (AHUs), and 1 single duct variable air volume (VAV) terminal unit for each zone in the building. The VAV units (VAV boxes) adjust the air volume delivered to the occupied space and, at the perimeter of the building, VAV boxes include a hot water coil and automatic two-way valve to re-heat the main supply air. Each AHU has a variable volume supply fan, a variable volume return fan, a chilled water cooling coil, and a set of dampers that act as an airside economizer. The economizer has a 2position outdoor air damper and the return and exhaust air dampers are modulated to regulate “free” cooling. The chilled water loop includes air-cooled chillers and variable speed secondary chilled water pumps. The hot water loop includes two-stage boilers and variable speed secondary hot water pumps. A building automation system (BAS) controls the HVAC equipment. Appropriate reference in the specifications should be made for products that are integrated with these sequences including chillers, boilers, variable frequency drives (VFDs), and the like. Controls: Furnish control device with an interface for monitoring and control of points specified in the points table. The points table includes the minimum acceptable list of interface points. The selected component controls shall easily integrate into the BAS and allow for the collection, control, trending, and archiving of the specified points with a minimal need for intermediary gateways or hardwired connections to link control systems together. Interoperable control systems are preferred. The system(s) in your building that are most similar to the system described above include: • Central VAV Air Handling Units • Built-Up VAV Air Handlers • 1 • Jail • 123 • vav • j • VAV system • System • System 1 • AH-1 • Central • Air Handling Unit AH-3 • VAV retrofit • Jail • HVAC test • East MOB • AHU with air-cooled chiller • AHU 1 • AC-1 • AHU-1 • roof • The Plant • HVAC - Enthalpy Economizer • HVAC - Minimum OA Variable Air Volume Units with Air-Cooled Chiller 57 Cx Assistant’s Sequence of Operation April 2004 Please note that this sample sequence will have to be modified to meet the exact systems defined in your building. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. VARIABLE-AIR VOLUME (VAV) UNITS WITH A CENTRAL PLANT, AIR COOLED CHILLERS SEQUENCES OF OPERATION Air Handling Units (AHUs) 1. Occupied Periods (Normal operation): When an isolation area is scheduled to be occupied, operate the air handling unit that serves it. These scheduled periods are considered “occupied periods” 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. Variable Air Volume Units with Air-Cooled Chiller 58 Cx Assistant’s Sequence of Operation April 2004 3. Fan Operation: Run the unit fans in all modes except unoccupied mode. Open the minimum outside air dampers when the supply fan is running. Proof the supply fan using an external current switch (CS). Interlock each return fan to its respective supply fan. 4. Supply and Return Fan Capacity Control: When the fans are running, vary the supply fan (SF) speed to maintain the supply duct static pressure setpoint. Reset the duct pressure setpoint from 1.5” to 0.2” (adjustable) based on the damper position of the most open VAV damper as long as that damper is at least 90% open (In other words the static setpoint will be reset to maintain the VAV box requiring the most static pressure at 90% open.). Vary the return fan (RF) speed to allow the return fan to volumetrically track the supply fan by maintaining the scheduled fixed flow offset equal to XXX CFM (adjustable) between the SF and RF. 5. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply and return fans by a hardwired contact interface at each fan’s variable frequency drive (VFD) E-stop contact. Simultaneously, the fire alarm control must notify the BAS of the fire event to enable the BAS to disable the affected units. Once the fire alarm is reset, enable the affected unit(s) to resume normal operation. 6. Differential Enthalpy Economizer Mode: Enable differential enthalpy economizer mode when there is a call for cooling or ventilation, and outdoor air temperature is 2° F less than return air temperature. Open outside air damper to 100%. Modulate the return air and exhaust air dampers in unison and modulate the chilled water valve, as required, to maintain supply air temperature setpoint. Maintain the chilled water valve in the closed position when outdoor air enthalpy is below 21 BTU/lb dry air (adjustable). When the return air enthalpy is 2 BTU/lb dry air (adjustable deadband) above the outdoor air enthalpy, the dampers are to be in the full exhaust position (exhaust damper fully open and return damper fully closed). As the return enthalpy decreases below this point, the dampers transition to a full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open). 7. Supply Air Temperature Control: Operate economizer mode dampers and chilled water valve in conjunction to maintain the supply air temperature. When the outside air temperature is not sufficient to provide “free” cooling, open the chilled water valve to maintain the supply air temperature setpoint. When the valve opens more than 30% (adj.), send a call for cooling to the central plant. When the valve closes to 5% (adj.), cancel the call for cooling. Reset the supply air temperature upward from 55°F to 65°F as the outdoor temperature falls from above 90° F to below 65° F. 8. Filter Status: Establish the filter pressure drop alarm with the system in operation at actual flow rate as follows: Where DP 100 is the high limit pressure drop at design cfm (determine limit from filter manufacturer) and DP x is the high limit at speed signal x (expressed as a fraction of full supply fan signal). For instance, the setpoint at 50% of speed Variable Air Volume Units with Air-Cooled Chiller 59 Cx Assistant’s Sequence of Operation April 2004 would be (0.5) 1.4 or 38% of the design high limit pressure drop. Send an equipment specific alarm (“AH-1 Dirty Filter”) to the operator workstation at 150% (adjustable) of the value calculated during system operation. Isolation Areas 1. Isolation Areas: There are XX isolation areas as indicated on the plans. Each area is composed of 1 or more spaces served by 1 or more VAV terminal units that are operated together. Configure each isolation area separately from other isolation areas. Configuration includes scheduling and operational modes. The default occupancy schedule is 7:00 AM to 6:00 PM, M-F. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Occupied Mode: Prior to an occupied period, initiate a Warm-up mode or Cooldown mode if necessary. During Occupied Mode, enable operation of the system, including enabling the air handling unit fans that serve this area and opening the outdoor air dampers to100% open. At the end of an occupied period, initiate unoccupied mode. 3. Warm-up Mode: Use an optimal start strategy to initiate the warm-up start time. Base optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, initiate the warmup mode. The optimal start period should pre-heat the building so that the average zone temperature is 70°F (adjustable) by the occupied period. If building warmup is required, enable the air handling units and set the return fan tracking offset to 0. Set the economizer mode to the return position, leave the chilled water valve closed (or in bypass), and leave the general exhaust fans off. Enable the VAV units to normal occupied operation. Enable the central heating plant but leave the central cooling disabled. After the average zone temperature has risen above 70°F (adjustable), terminate the warm-up cycle, and initiate occupied mode. 4. Cool-down Mode: Use an optimal start strategy to initiate the cool-down start time. Base the optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. The optimal start period should pre-cool the building so that the average zone temperature is 78°F (adjustable) by the occupied period. If a cool-down cycle is required, enable the air handling units, command the return fan tracking offset to 0, and leave the general exhaust fans off. Enable the VAV units to normal occupied operation. Enable the chilled water system but leave the central heating disabled. After the average zone temperature has dropped below 78°F (adjustable), terminate the cool-down cycle and initiate occupied mode. 5. Night Setback/Setup Mode: During an unoccupied period, start the air-handling unit in the warm-up or cool-down mode if a zone temperature falls below the unoccupied heating setpoint or rises above the unoccupied cooling setpoint. End Variable Air Volume Units with Air-Cooled Chiller 60 Cx Assistant’s Sequence of Operation April 2004 the setback/setup mode when the zones are below/above their unoccupied setpoints. 6. Unoccupied Mode: During unoccupied periods, disable VAV units, disable the air handling units, close their chilled water valves (or put them in bypass), close their outside air damper(s) and position their return/exhaust air dampers for full return air (no exhaust). Cancel calls for central plant cooling and heating. When a thermostat override button is depressed during unoccupied period, operate the isolation area in occupied mode for one hour as follows: Operate the air handling unit in occupied mode except for the return-fan volumetric tracking offset (set it to 0) and the general exhaust fans (leave them off). Enable the central plant. VAV Zone Control 1. Temperature Control: Use a solid state, electronic wall temperature sensor to adjust the zone velocity controller setpoint. Airflow to the zone will fluctuate between its minimum and the maximum and supply air temperature will vary in order to maintain a constant room temperature based on this setpoint. Set each temperature sensor for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between the heating and cooling setpoints. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone its own adjustable unoccupied heating and cooling setpoints. 2. Zone Cooling Mode: When the zone’s temperature rises to 1°F (adjustable) above its setpoint, the zone is in cooling mode and the VAV damper begins to modulate open. As the temperature rises 2° F hotter than its setpoint, the VAV damper is fully open and the zone’s airflow is increased to maximum. As the zone’s temperature approaches the cooling setpoint, modulate the air volume toward minimum. 3. Zone Heating Mode (Perimeter Zones Only): When the zone’s temperature falls to 1 ° F (adjustable) below its setpoint, the zone is in heating mode and the VAV damper modulates to minimum airflow. Once the valve opens to more than 10% (adj.), send a call for heating to the central plant. Modulate the reheat coil control valve to satisfy the space temperature within the reset bounds. Reset the supply air temperature upward from 90°F to 110°F as the outdoor temperature falls from 65° F or greater to 40° F or lower. When the valve closes to 5% (adj.), cancel the call for heating. Variable Air Volume Units with Air-Cooled Chiller 61 Cx Assistant’s Sequence of Operation April 2004 Chilled Water System 1. Cooling Mode Enable/Disable: When building comfort cannot be maintained by economizer mode outdoor air temperature, the air handlers call for supplementary cooling by sending a cooling request to the central plant. When all of the AHU chilled water valve positions fall below 5% full open, cancel the call for cooling and initiate chiller shutdown. 2. Secondary Chilled Water Pump Enable: When the BAS registers a call for central plant cooling, enable both the secondary chilled water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 5 seconds. Modulate the speed of the pumps in order to maintain a differential pressure setpoint of 15 PSID (adj.) at the central plant. Inhibit starting of the primary pumps and chiller if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Chilled Water Pump Enable (Chiller Initiation): When the BAS registers a call for central plant cooling, determine the lead chiller as indicated below. Open the chilled water isolation valve to the lead chiller. If the valve has not proofed open after 30 seconds, close the valve and enable and start the lag chiller. Repeat valve operation with lag chiller. If both valves fail to open, initiate chiller shutdown operation and send equipment specific critical alarm (“CH-1 CHW Isolation Valve Failed to Open”) to operator workstation. If valve proofs open, enable the primary chilled water pump dedicated to the lead chiller. After 30 seconds, proof flow. If the flow is not proved by a differential pressure switch, disable the pump, close the valve and set the lag chiller as the lead chiller. If both pumps fail to provide flow, initiate the chiller shutdown operation. If either pump fails, send equipment specific critical alarms to the operator workstation. 4. Chiller Enable: Upon proof of primary chilled water, enable the selected chiller. A hard-wired flow switch will act as a back up to ensure that chiller only starts with chilled water flow. Set the chilled water temperature supply temperature to 45° F (adjustable). After 30 seconds, prove chiller operation by means of a hard-wired current switch. If the chiller fails to prove operation, initiate its shutdown sequence. Then, enable the lag chiller and it’s primary pump. If both chillers fail to proof, send an equipment specific alarm (“Chillers Failed”) to the operator workstation. During operation, use the chillers internal safeties to cause an alarm and shut down the machine. If the chiller does not develop at least a 3°F temperature difference after 15 minutes of being proved on, initiate an alarm on the operator work station. Operate the chillers and their associated primary pumps lead/lag. Swap the lead and lag chillers (as well as their primary pumps) on Sunday at 3:00 AM as long as the lead chiller has operated at least 40 hours and all equipment are disabled. 5. Chiller Staging: If the chilled water return temperature rises to 12°F (adjustable) above the chilled water setpoint, enable lag chiller operation and start the chiller. Variable Air Volume Units with Air-Cooled Chiller 62 Cx Assistant’s Sequence of Operation April 2004 Run both chillers until the chilled return temperature falls to 5°F above the chilled water setpoint. At this point, initiate the lag chiller shutdown sequence. Continue running the lead chiller until the chilled water return temperature falls to the setpoint minus the deadband. 6. Chiller Shutdown: Upon a call from the BAS or an internal chiller alarm, initiate chiller shutdown. Disable the chiller but continue to run the primary pump serving the chiller for 5 minutes. After 5 minutes, disable the pump and close the chiller’s isolation valves. If no other chiller is enabled, shutoff the secondary water pumps. Use a timer in the BAS to keep the chiller from cycling on and off more often than every 5 minutes [this may be redundant to the chiller’s internal safeties]. 7. Chiller Safeties: Initiate chiller shutdown if the BAS senses low chilled water flow or low chilled water temperature (less than 38° F). Initiate an equipment specific alarm at the operator workstation. 8. Chilled Water System Outdoor Air Temperature Lockout: If the outdoor air temperature falls below 63° F (adjustable), lock out the chilled water system such that the chillers and chilled water pumps do not run. If the outdoor air temperature rises above 65° F (adjustable) for 20 minutes (adjustable), enable the chilled water system. Heating Hot Water System 1. Heating Mode Enable: Generate a call for heating from zone controllers if any of the zone valve positions is greater than 10% (adjustable) of full open until all are below 5% (adjustable). 2. Secondary Hot Water Pump Enable: When the BAS registers a call for central plant heating, enable both the secondary hot water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 15 seconds using a differential pressure switch. Modulate the speed of the pumps in order to maintain a pressure drop of 10 PSID at the hot water using a differential pressure transmitter. Inhibit starting of the primary pumps and boiler if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. If either pump fails to start, initiate an equipment specific critical alarm at the operator workstation. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Hot Water Pump Enable (Boiler Initiation): Open the lead boiler’s isolation valves. If the valve opening fails to proof within 30-seconds, close the valve, enable the lag boiler, and send an equipment specific alarm (“B-1 Isolation Valve Failed to Open”) to the operator workstation. If valve opening is successful, enable the primary hot water pump dedicated to the lead boiler. If the flow is not proved within 30 seconds, disable the pump, close the valve and set the lag boiler as the lead boiler. If both valves fail to open, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. If both pumps fail to provide flow, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. After 40 hours of operation, on Variable Air Volume Units with Air-Cooled Chiller 63 Cx Assistant’s Sequence of Operation 4. 5. 6. 7. April 2004 Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead and lag pumps. Boiler Enable: Upon proof of primary hot water flow, enable the selected boiler. Use a hard-wired flow switch as a back up to ensure that boiler only starts with hot water flow. Send an initial hot water temperature of 180° F to the boiler controller. After 60 seconds, prove boiler operation by means of a hard-wired current switch. Operate the boilers lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead position. Enable the lag boiler to start. If either or both boilers fail to prove or fail to proof when required to operate, initiate boiler shutdown and send equipment specific alarms to the operator workstation. During operation, use the boiler’s internal safeties to initiate an equipment alarm at the operator workstation and disable the machine. If the boiler does not develop at least a 3°F temperature difference after 15 minutes of being enabled initiate a equipment specific alarm at the operator workstation. Boiler Staging: Modulate internal boilers controls between the boiler’s two stages to meet the BAS water loop setpoint. If during boiler operation, the hot water temperature differential falls to 5°F (adjustable), initiate the lag boiler operation. Continue to run both boilers until the hot water temperature differential rises to 12° F. At this point, initiate the lag boiler shutdown sequence. Boiler Shutdown: When all calls for central plant heating are cancelled or an internal alarm occurs, initiate boiler shutdown. Provide the BAS with redundant sensors for hot water flow, hot water temperature Hi Limit (more than 200° F). Disable operation of the affected boiler(s) if the limits are exceeded. If both boilers trip or fail to proof, initiate an equipment specific alarm at the operator workstation. Prevent the boiler from cycling on and off more often than once every 5 minutes (this may be redundant to the boiler’s internal safeties). For each boiler, disable the boiler before shutting down its pump. After disabling the boiler, run the primary boiler pump serving the boiler for 5 minutes. After 5 minutes, shut down the primary boiler pump and close the hot water isolation valves. If no other boiler is enabled, shut off the secondary water pumps. Hot Water System Outdoor Air Temperature Lockout: If the outdoor air temperature rises above 75° F (adjustable), lock out the hot water system so the boilers and hot water pumps do not run. If the outdoor air temperature falls below 70° F (adjustable) for 20 minutes (adjustable), enable the hot water system. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) Variable Air Volume Units with Air-Cooled Chiller 64 Cx Assistant’s Sequence of Operation April 2004 AHU air handling unit B boiler CH chiller or chilled (i.e. CHW = chilled water) Cmd command COV change of value DB dry-bulb M “mixed” such as the air in the mixed air plenum (MAT = mixed air temperature) OA outside air (OAT = outside air temperature) P pump (PP = primary pump, SP = secondary pump) R return (RAT = return air temperature) S supply (SAT = supply air temperature) SL secondary loop Temp temperature W water (CHW = chilled water, HW = hot water) Resolution of analog inputs: °F 0.1 psid 0.005 ” water cfm 1 rpm 1 kW 0.1 % 0.1 Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value Value Variable Air Volume Units with Air-Cooled Chiller Interval Show on or Graphic COV 65 Cx Assistant’s Sequence of Operation April 2004 OA DB Temp X 15 X OA RH X 15 X OA Enthalpy X CHW Lockout Temp X COV 0.5,15 X HHW Lockout Temp X COV 0.5,15 X CHWR Temp CHWS Temp X 1 15 X >60 when CH flow after 1 minute, <38 X 1 CHW SL Pressure Drop Setpoint CHW SL Pressure Drop 15 X COVX 10%,15 X =Cmd COVX after 1 10%,15 minute X CHWSP-n Enable n1 CHWSP-n Override COV X COV X Proof after 1 COV minute X n CHWSP-n Status n 1 CHWSP-n Runtime n CHWSP-n Cycle Counter CHWSP-n Cmd Speed 15 X n >1000 COV 1 >6 hour COV n Variable Air Volume Units with Air-Cooled Chiller 66 Cx Assistant’s Sequence of Operation CHWSP-n Run Speed April 2004 =Cmd COVX after 1 10%,15 minute n CHWSP-n Alarm n CHWSP-n Power n CHWSP Lead/Lag X X CH-n Inlet Temp COV n1 15 X >60 when call for cooling, <38 CH-n Outlet Temp n1 CH Setpoint Temp X COV CH Staging Setpoint Temp X COV CH Staging Deadband Temp X COV CH-n CHW Isolation Valve Cmd CH-n CHW Isolation Valve Feedback n1 n CH-n Alarm Text n CH-n Enable n1 CH-n Override CH-n CHW flow status 15 X COV n 1 CH-n Alarm X n n 1 Variable Air Volume Units with Air-Cooled Chiller COV X COV X COV X COV X COV X COV X 67 Cx Assistant’s Sequence of Operation CH-n Status April 2004 n1 Proof after 1 COV minute 10% high or low X CH-n Voltage 3n CH-n Amperage 3n 60 CH-n Power n 15 X CH-n Phase monitor alarm n COV CH-n Chiller Runtime CH-n ReStart Timer n >1000 n 5 Minutes to restart CH-n Cycle Counter n CH Lead/Lag X CHWPP-n Enable >6 hour CHWPP-n Override CHWPP-n Runtime n CHWPP-n Power n CHWPP Lead/Lag X 1 HWS Temp X 1 COV COV X COV X Proof after 1 COV minute X >1000 COV 1 X X HWR Temp COV 1 X n n 1 X COV n1 CHWPP-n Status 60 Variable Air Volume Units with Air-Cooled Chiller COV X 15 X >180 or <110 when B 15 X 68 Cx Assistant’s Sequence of Operation April 2004 flow after 1 minute HW SL Pressure Drop Setpoint HW SL Pressure Drop COVX 10%,15 X =Cmd COVX after 1 10%,15 minute X HWSP-n Enable n1 HWSP-n override n 1 HWSP-n Runtime n HWSP-n Cycle Counter n Proof after 1 COV minute X >1000 COV 1 >6 hour COV n n HWSP Lead/Lag B-n Outlet Temp X =Cmd COVX after 1 10%,15 minute HWSP-n Alarm B-n Inlet Temp COV n1 HWSP-n Run n Speed HWSP-n Power X n HWSP-n Status HWSP-n Cmd Speed COV X X COV n n1 Variable Air Volume Units with Air-Cooled Chiller X 15 X >190 or <110 when B flow after 1 15 X 69 Cx Assistant’s Sequence of Operation April 2004 minute B Setpoint Temp X COV B Staging Setpoint Temp X COV B Staging Deadband Temp X COV B-n Alarm n B-n Alarm Text n COV X COV X X B-n Enable n1 COV B-n HW Isolation Valve Cmd n1 COV B-n HW Isolation Valve Feedback n 1 B-n Override B-n HW flow status COV X COV X Proof after 1 COV minute X n n B-n Runtime B-n Re-Start Timer n >1000 n 5 Minutes to restart B-n Cycle Counter n B Lead/Lag X HWPP-n Override X n B-n Status HWPP-n Enable COV n1 n Variable Air Volume Units with Air-Cooled Chiller >6 hour COV 1 COV COV X COV X COV X 70 Cx Assistant’s Sequence of Operation HWPP-n Status April 2004 Proof after 1 COV minute n 1 HWPP-n Runtime n HWPP-n Power n HWPP Lead/Lag >1000 n 1 AHU-n Operating Mode n AHU-n Mode Override COV 1 X X AHU-n Fire Alarm X n COV X COV X COV X COV X AHU-n SAT n 15 X AHU-n OAT n 15 X AHU-n RAT n 15 X AHU-n RA RH 15 X n AHU-n RA Enthalpy n 15 X AHU-n MAT n 15 X AHU-n n Supply Flow Proof after 1 minute 15 X AHU-n Return Flow n Proof after 1 minute 15 X n <5000 CFM for 5 minutes 15 X AHU-n Outdoor Air Flow AHU-n Flow Offset AHU-n OA Damper Cmd n n Variable Air Volume Units with Air-Cooled Chiller COV COVX 10%,15 71 Cx Assistant’s Sequence of Operation April 2004 AHU-n RA Damper Cmd n COVX 10%,15 AHU-n MA Damper Cmd n COVX 10%,15 AHU-n Economizer High Ambient Lockout Temp n COV0.5,15 X AHU-n Economizer CHW Minimum Temp n COV0.5,15 X AHU-n Supply Reset Temp n COV0.5,15 X AHU-n Supply Pressure Setpoint n COVX 10%,15 AHU-n Supply Pressure n >3” AHU-n Supply Fan Enable n1 AHU-n Supply Fan Status n 1 AHU-n Supply Fan Runtime n AHU-n Supply Fan Cmd Speed AHU-nSupply Fan Run Speed AHU-n COV X Proof after 1 COV minute X >1000 n1 15 X COV 1 15 X =Cmd COVX after 1 10%,15 minute n n Variable Air Volume Units with Air-Cooled Chiller 72 Cx Assistant’s Sequence of Operation April 2004 Supply Fan Alarm AHU-n Supply Fan Power n AHU-n Return Fan Enable n1 AHU-n Return Fan Status n 1 AHU-n Return Fan Runtime n AHU-n Return Fan Cmd Speed AHU-nReturn Fan Run Speed COV X Proof after 1 COV minute X >1000 COV 1 n1 15 X =Cmd COVX after 1 10%,15 minute n AHU-n Return Fan Alarm n AHU-n Return Fan Power n AHU-n CHWV Bypass Cmd AHU-n CHWV Bypass Feedback X X COVX 10%,15 n =Cmd COVX after 1 10%,15 minute n AHU-n Warm-up Mode Low Temp Setpoint n COV X AHU-n CoolDown Mode High Temp n COV X Variable Air Volume Units with Air-Cooled Chiller 73 Cx Assistant’s Sequence of Operation April 2004 Setpoint AHU-n Filter Alarm n COV AHU-n Call for Cooling n X COV VAV-n Zone n Temp COV0.5,15 X VAV-n Zone Temp SetpointCooling n COV X VAV-n Zone Temp SetpointHeating n COV X VAV-n Zone Temp Unoccupied SetpointCooling n COV X VAV-n Zone Temp Unoccupied SetpointHeating n COV X VAV-n Zone Temp SetpointDeadband n COV X COV X VAV-n Override n VAV-n Operating Mode n VAV-n Supply Air n Temperature VAV-n Supply Air Temp Reset COV COV0.5,15 n Variable Air Volume Units with Air-Cooled Chiller X X 74 Cx Assistant’s Sequence of Operation VAV-n HW Valve Cmd n VAV-n n Damper Cmd Variable Air Volume Units with Air-Cooled Chiller April 2004 COVX 10%,15 COV X 75 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of Primary/Secondary chilled and hot water loops, multiple air handling units (AHUs), and 1 single duct variable air volume (VAV) terminal unit for each zone in the building. The VAV units (VAV boxes) adjust the air volume delivered to the occupied space and, at the perimeter of the building, VAV boxes include a hot water coil and automatic two-way valve to re-heat the main supply air. Each AHU has a variable volume supply fan, a variable volume return fan, a chilled water cooling coil, and a set of dampers that act as an airside economizer. The economizer has a 2position outdoor air damper and the return and exhaust air dampers are modulated to regulate “free” cooling. The chilled water loop includes water-cooled chillers and variable speed secondary chilled water pumps. The hot water loop includes two-stage boilers and variable speed secondary hot water pumps. A building automation system (BAS) controls the HVAC equipment. Appropriate reference in the specifications should be made for products that are integrated with these sequences including chillers, boilers, variable frequency drives (VFDs), and the like. Controls: Furnish control device with an interface for monitoring and control of points specified in the points table. The points table includes the minimum acceptable list of interface points. The selected component controls shall easily integrate into the BAS and allow for the collection, control, trending, and archiving of the specified points with a minimal need for intermediary gateways or hardwired connections to link control systems together. Interoperable control systems are preferred. The system(s) in your building that are most similar to the system described above include: • AH-1 Please note that this sample sequence will have to be modified to meet the exact systems defined in your building. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. Variable Air Volume Units with Water-Cooled Chiller 76 Cx Assistant’s Sequence of Operation April 2004 VARIABLE-AIR VOLUME (VAV) UNITS WITH A CENTRAL PLANT, WATER COOLED CHILLERS AND COOLING TOWERS SEQUENCES OF OPERATION Air Handling Units (AHUs) 1. Occupied Periods (Normal operation): When an isolation area is scheduled to be occupied, operate the air handling unit that serves it. These scheduled periods are considered “occupied periods”. 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Fan Operation: Run the unit fans in all modes except unoccupied mode. Open the minimum outside air dampers when the supply fan is running. Proof the supply fan using an external current switch (CS). Interlock each return fan to its respective supply fan. 4. Supply and Return Fan Capacity Control: When the fans are running, vary the supply fan (SF) speed to maintain the supply duct static pressure setpoint. Reset the duct pressure setpoint from 1.5” to 0.2” (adjustable) based on the damper Variable Air Volume Units with Water-Cooled Chiller 77 Cx Assistant’s Sequence of Operation 5. 6. 7. 8. 9. April 2004 position of the most open VAV damper as long as that damper is at least 90% open (In other words the static setpoint will be reset to maintain the VAV box requiring the most static pressure at 90% open.). Vary the return fan (RF) speed to allow the return fan to volumetrically track the supply fan by maintaining the scheduled fixed flow offset equal to XXX CFM (adjustable) between the SF and RF. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the supply and return fans by a hardwired contact interface at each fan’s variable frequency drive (VFD) E-stop contact. Simultaneously, the fire alarm control must notify the BAS of the fire event to enable the BAS to disable the affected units. Once the fire alarm is reset, enable the affected unit(s) to resume normal operation. Duct Pressure Safety: If negative static pressure over 2” WC is measured in the mixed air plenum or positive supply duct static pressure over 3” WC is measured in the supply duct, disable the fan VFDs via hard wired interlocks to their E-stop contacts and initiate an equipment specific alarm (i.e. “AH-3 High Static Pressure” or “AH-2 Low Static Pressure”) at the operator workstation. An operator must reset each fan’s differential pressure switch before the VFDs may be re-enabled. Provide a local or BAS reset for this purpose. Differential Dry-Bulb Economizer Mode: Enable differential economizer mode when there is a call for cooling or ventilation, and outdoor air temperature is 2° F less than return air temperature. Open outside air damper to 100%. Modulate the return air and exhaust air dampers in unison and modulate the chilled water valve, as required, to maintain supply air temperature setpoint. Maintain the chilled water valve in the closed position when outdoor air temperature is below 52° F (adjustable). When the return air temperature is 2° F (adjustable deadband) or more above the outdoor air temperature, exhaust and return dampers are to be in the full exhaust position (exhaust damper fully open and return damper fully closed). As the return air temperature decreases below this point, the dampers transition to a full return position (exhaust damper is closed to allow only minimum outdoor air and the return damper is fully open). Supply Air Temperature Control: Operate economizer mode dampers and chilled water valve in conjunction to maintain the supply air temperature. When the outside air temperature is not sufficient to provide “free” cooling, open the chilled water valve to maintain the supply air temperature setpoint. When the valve opens more than 30% (adj.), send a call for cooling to the central plant. When the valve closes to 5% (adj.), cancel the call for cooling. The supply air temperature is reset upwards from 90°F to 110°F as the outdoor temperature falls from 65° F or greater to 40° F or lower. Filter Status: Establish the filter pressure drop alarm with the system in operation at actual flow rate as follows: Where DP 100 is the high limit pressure drop at design cfm (determine limit from filter manufacturer) and DP x is the high limit at speed signal x (expressed as a fraction of full supply fan signal). For instance, the setpoint at 50% of speed Variable Air Volume Units with Water-Cooled Chiller 78 Cx Assistant’s Sequence of Operation April 2004 would be (0.5) 1.4 or 38% of the design high limit pressure drop. Send an equipment specific alarm (“AH-1 Dirty Filter”) to the operator workstation at 150% (adjustable) of the value calculated during system operation. Isolation Areas 1. Isolation Areas: There are XX isolation areas as indicated on the plans. Each area is composed of 1 or more spaces served by 1 or more VAV terminal units that are operated together. Configure each isolation area separately from other isolation areas. Configuration includes scheduling and operational modes. The default occupancy schedule is 7:00 AM to 6:00 PM, M-F. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Occupied Mode: Prior to an occupied period, initiate a Warm-up mode or Cooldown mode if necessary. During Occupied Mode, enable operation of the system, including enabling the air handling unit fans that serve this area and opening the outdoor air dampers to100% open. At the end of an occupied period, initiate unoccupied mode. 3. Warm-up Mode: Use an optimal start strategy to initiate the warm-up start time. Base optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is less than 69°F (adjustable) at the projected start of the warm-up period, initiate the warmup mode. The optimal start period should pre-heat the building so that the average zone temperature is 70°F (adjustable) by the occupied period. If building warmup is required, enable the air handling units and set the return fan tracking offset to 0. Set the economizer mode to the return position, leave the chilled water valve closed (or in bypass), and leave the general exhaust fans off. Enable the VAV units to normal occupied operation. Enable the central heating plant but leave the central cooling disabled. After the average zone temperature has risen above 70°F (adjustable), terminate the warm-up cycle, and initiate occupied mode. 4. Cool-down Mode: Use an optimal start strategy to initiate the cool-down start time. Base the optimal start strategy upon outdoor air temperature and average zone temperature within the isolation area. If the average zone temperature is greater than 79°F (adjustable) at the projected start of the cool-down period, initiate the cool-down mode. The optimal start period should pre-cool the building so that the average zone temperature is 78°F (adjustable) by the occupied period. If a cool-down cycle is required, enable the air handling units, command the return fan tracking offset to 0, and leave the general exhaust fans off. Enable the VAV units to normal occupied operation. Enable the chilled water system but leave the central heating disabled. After the average zone temperature has dropped below 78°F (adjustable), terminate the cool-down cycle and initiate occupied mode. 5. Night Setback/Setup Mode: During an unoccupied period, start the air-handling unit in the warm-up or cool-down mode if a zone temperature falls below the unoccupied heating setpoint or rises above the unoccupied cooling setpoint. End Variable Air Volume Units with Water-Cooled Chiller 79 Cx Assistant’s Sequence of Operation April 2004 the setback/setup mode when the zones are below/above their unoccupied setpoints. 6. Unoccupied Mode: During unoccupied periods, disable VAV units, disable the air handling units, close their chilled water valves (or put them in bypass), close their outside air damper(s) and position their return/exhaust air dampers for full return air (no exhaust). Cancel calls for central plant cooling and heating. When a thermostat override button is depressed during unoccupied period, operate the isolation area in occupied mode for one hour as follows: Operate the air handling unit in occupied mode except for the return-fan volumetric tracking offset (set it to 0) and the general exhaust fans (leave them off). Enable the central plant. VAV Zone Control 1. Temperature Control: Use a solid state, electronic wall temperature sensor to adjust the zone velocity controller setpoint. Airflow to the zone will fluctuate between its minimum and the maximum and supply air temperature will vary in order to maintain a constant room temperature based on this setpoint. Set each temperature sensor for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between the heating and cooling setpoints. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Provide each zone its own adjustable unoccupied heating and cooling setpoints. 2. Zone Cooling Mode: When the zone’s temperature rises to 1°F (adjustable) above its setpoint, the zone is in cooling mode and the VAV damper begins to modulate open. As the temperature rises 2° F hotter than its setpoint, the VAV damper is fully open and the zone’s airflow is increased to maximum. As the zone’s temperature approaches the cooling setpoint, modulate the air volume toward minimum. 3. Zone Heating Mode (Perimeter Zones Only): When the zone’s temperature falls to 1 ° F (adjustable) below its setpoint, the zone is in heating mode and the VAV damper modulates to minimum airflow. Modulate the reheat coil control valve to satisfy the space temperature within the reset bounds. Reset the supply air temperature upward from 90°F to 110°F as the outdoor temperature falls from 65° F or greater to 40° F or lower. Once the valve opens to more than 10% (adj.), send a call for heating to the central plant. When the valve closes to 5% (adj.), cancel the call for heating. Variable Air Volume Units with Water-Cooled Chiller 80 Cx Assistant’s Sequence of Operation April 2004 Chilled Water System 1. Cooling Mode Enable/Disable: When building comfort cannot be maintained by economizer mode outdoor air temperature, the air handlers call for supplementary cooling by sending a cooling request to the central plant. When all of the AHU chilled water valve positions fall below 5% full open, cancel the call for cooling and initiate chiller shutdown. 2. Secondary Chilled Water Pump Enable: When the BAS registers a call for central plant cooling, enable both the secondary chilled water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 5 seconds. Modulate the speed of the pumps in order to maintain a differential pressure setpoint of 15 PSID (adj.) at the central plant. Inhibit starting of the primary pumps and chiller if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Chilled Water Pump Enable (Chiller Initiation): When the BAS registers a call for central plant cooling, determine the lead chiller as indicated below. Open the chilled water isolation valve to the lead chiller. If the valve has not proofed open after 30 seconds, close the valve and enable and start the lag chiller. Repeat valve operation with lag chiller. If both valves fail to open, initiate chiller shutdown operation and send equipment specific critical alarm (“CH-1 CHW Isolation Valve Failed to Open”) to operator workstation. If valve proofs open, enable the primary chilled water pump dedicated to the lead chiller. After 30 seconds, proof flow. If the flow is not proved by a differential pressure switch, disable the pump, close the valve and set the lag chiller as the lead chiller. If both pumps fail to provide flow, initiate the chiller shutdown operation. If either pump fails, send equipment specific critical alarms to the operator workstation. 4. Chiller Enable: Upon proof of primary chilled water and condenser water flow, enable the selected chiller. A hard-wired flow switch will act as a back up to ensure that chiller only starts with chilled water flow. Set the chilled water temperature supply temperature to 45° F (adjustable). After 30 seconds, prove chiller operation by means of a hard-wired current switch. If the chiller fails to prove operation, initiate its shutdown sequence. Then, enable the lag chiller and it’s primary pump. If both chillers fail to proof, send an equipment specific alarm (“Chillers Failed”) to the operator workstation. During operation, use the chillers internal safeties to cause an alarm and shut down the machine. If the chiller does not develop at least a 3°F temperature difference after 15 minutes of being proved on, initiate an alarm on the operator work station. Operate the chillers and their associated primary pumps lead/lag. Swap the lead and lag chillers (as well as their primary pumps) on Sunday at 3:00 AM as long as the lead chiller has operated at least 40 hours and all equipment are disabled. 5. Chiller Staging: If the chilled water return temperature rises to 12°F (adjustable) above the chilled water setpoint, enable lag chiller operation and start the chiller. Variable Air Volume Units with Water-Cooled Chiller 81 Cx Assistant’s Sequence of Operation April 2004 Run both chillers until the chilled return temperature falls to 5°F above the chilled water setpoint. At this point, initiate the lag chiller shutdown sequence. Continue running the lead chiller until the chilled water return temperature falls to the setpoint minus the deadband. Condenser Water System 1. Chemical Treatment: Provide chemical treatment for the cooling towers via an automatic chemical feed and bleed system. Run the water treatment system independently of the BAS. 2. Safeties: Disable the condenser water pump and the chiller operation if the water level in the cooling tower basin falls below the minimum. Initiate an equipment specific alarm (“Low Water Level in CT-1”) at the operator workstation. 3. Condenser Water Pump Enable: When the BAS registers a call for cooling from the central plant, enable the lead condenser water pump. Prove condenser water flow within 30-seconds (adjustable) using a differential pressure switch. If the flow is not proved, disable the pump, and enable and start the lag pump. Send equipment specific critical alarm (“CWP-1 Failed”) to the operator workstation. The lag pump is also enabled by the start-up of the lag chiller. If both pumps fail to provide flow, initiate chiller shutdown operation and initiate a critical alarm (“Condenser Water Pumps failed”) to the operator workstation. Swap the lead and lag pumps on Sunday at 3:00 AM as long as the lead pump has operated at least 40 hours and both pumps are shut down. 4. Condenser Water Temperature Control: Prior to operation of the condenser water pump, the cooling tower bypass valve should be in the bypass position (bypassing the cooling towers) and the cooling tower fans shut off. Once condenser water flow is proved, operate the cooling tower fan and bypass valve in order to maintain a condenser water supply setpoint between 75° F and 85° F. Modulate the condenser water bypass valve so that at 80° F condenser water supply temperature, the water is not bypassing the cooling tower. Start both cooling tower fans at minimum speed when the water temperature increases to 82°F. Modulate the tower fans speed as necessary to maintain the setpoint temperature. If the temperature exceeds the high limit of 90° F, initiate the chiller shutdown sequence and send an equipment specific alarm (“Condenser Water High Limit Temperature”) to the operator workstation. As the temperature falls below 82 ° F, disable the fans and modulate the bypass valve to maintain setpoint temperature. If the condenser supply temperature falls below the low limit of 70° F after running for 5 minutes, initiate the chiller shutdown sequence and send an equipment specific alarm (“Condenser Water Low Limit Temperature”) to the operator workstation. 5. Condenser Water System Shutdown: When the lag chiller is shutdown, disable the lag chilled water pump after a 5 minute run time. Adjust the condenser water fan speed and bypass valve positions to maintain temperature as indicated elsewhere. When the lead chiller is shutdown, run the lead condenser water pump for 5 Variable Air Volume Units with Water-Cooled Chiller 82 Cx Assistant’s Sequence of Operation April 2004 minute. Then disable the cooling tower fans, disable the lead pump, and modulate the bypass valve to full bypass. Heating Hot Water System 1. Heating Mode Enable: Generate a call for heating from zone controllers if any of the zone valve positions is greater than 10% (adjustable) of full open until all are below 5% (adjustable) 2. Secondary Hot Water Pump Enable: When the BAS registers a call for central plant heating, enable both the secondary hot water pumps by a start-stop command from the BAS. Initially, start the pumps at 10% speed. Proof the start of both of the pumps after 15 seconds using a differential pressure switch. Modulate the speed of the pumps in order to maintain a pressure drop of 10 PSID at the hot water using a differential pressure transmitter. Inhibit starting of the primary pumps and boiler if both pumps fail to prove running status or fail while running. When the commanded speed falls below 40%, disable the lag pump. When the commanded speed rises above 60%, enable the lag pump. If either pump fails to start, initiate an equipment specific critical alarm at the operator workstation. When they are both enabled, lead and lag pumps should run at the same speed. 3. Primary Hot Water Pump Enable (Boiler Initiation): Open the lead boiler’s isolation valves. If the valve opening fails to proof within 30-seconds, close the valve, enable the lag boiler, and send an equipment specific alarm (“B-1 Isolation Valve Failed to Open”) to the operator workstation. If valve opening is successful, enable the primary hot water pump dedicated to the lead boiler. If the flow is not proved within 30 seconds, disable the pump, close the valve and set the lag boiler as the lead boiler. If both valves fail to open, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. If both pumps fail to provide flow, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead and lag pumps. 4. Boiler Enable: Upon proof of primary hot water flow, enable the selected boiler. Use a hard-wired flow switch as a back up to ensure that boiler only starts with hot water flow. Send an initial hot water temperature of 180° F to the boiler controller. After 60 seconds, prove boiler operation by means of a hard-wired current switch. Operate the boilers lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead position. Enable the lag boiler to start. If either or both boilers fail to prove or fail to proof when required to operate, initiate boiler shutdown and send equipment specific alarms to the operator workstation. During operation, use the boiler’s internal safeties to initiate an equipment alarm at the operator workstation and disable the machine. If the boiler does not develop at least a 3°F temperature difference after 15 minutes of being enabled initiate a equipment specific alarm at the operator workstation. Variable Air Volume Units with Water-Cooled Chiller 83 Cx Assistant’s Sequence of Operation April 2004 5. Boiler Staging: Modulate internal boilers controls between the boiler’s two stages to meet the BAS water loop setpoint. If during boiler operation, the hot water temperature differential falls to 5°F (adjustable), initiate the lag boiler operation. Continue to run both boilers until the hot water temperature differential rises to 12° F. At this point, initiate the lag boiler shutdown sequence. 6. Boiler Shutdown: When all calls for central plant heating are cancelled or an internal alarm occurs, initiate boiler shutdown. Provide the BAS with redundant sensors for hot water flow, hot water temperature Hi Limit (more than 200° F). Disable operation of the affected boiler(s) if the limits are exceeded. If both boilers trip or fail to proof, initiate an equipment specific alarm at the operator workstation. Prevent the boiler from cycling on and off more often than once every 5 minutes (this may be redundant to the boiler’s internal safeties). For each boiler, disable the boiler before shutting down its pump. After disabling the boiler, run the primary boiler pump serving the boiler for 5 minutes. After 5 minutes, shut down the primary boiler pump and close the hot water isolation valves. If no other boiler is enabled, shut off the secondary water pumps. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) AHU air handling unit B boiler CH chiller or chilled (i.e. CHW = chilled water) Cmd command COV change of value CT cooling tower DB dry-bulb M “mixed” such as the air in the mixed air plenum (MAT = mixed air temperature) OA outside air (OAT = outside air temperature) P pump (PP = primary pump, SP = secondary pump) Variable Air Volume Units with Water-Cooled Chiller 84 Cx Assistant’s Sequence of Operation April 2004 R return (RAT = return air temperature) S supply (SAT = supply air temperature) SL secondary loop Temp temperature W water (CW = condenser water, HW = hot water) Resolution of analog inputs: °F 0.1 psid 0.005 ” water cfm 1 rpm 1 kW 0.1 % 0.1 Interval Show on or Graphic COV Point Name Analog Digital Other Alarm AI AO DI DO Software Software Software Logic Value Value OA DB Temp X 15 X OA RH X 15 X OA Enthalpy CHWR Temp CHWS Temp CHW SL Pressure Drop Setpoint X 15 X X 1 15 X >60 when CH flow after 1 minute, <38 X 1 X Variable Air Volume Units with Water-Cooled Chiller 15 X COVX 10%,15 85 Cx Assistant’s Sequence of Operation CHW SL Pressure Drop =Cmd COVX after 1 10%,15 minute X CHWSP-n Enable n1 CHWSP-n Override n 1 CHWSP-n Runtime n CHWSP-n Cycle Counter n CHWSP-n Cmd Speed COV X Proof after 1 COV minute X >1000 COV 1 >6 hour COV =Cmd COVX after 1 10%,15 minute n n n CHWSP Lead/Lag CH-n Inlet Temp X n CHWSP-n Alarm CHWSP-n Power COV n CHWSP-n Status CHWSP-n Run Speed April 2004 X X COV n1 15 X >60 when call for cooling, <38 CH-n Outlet Temp n1 CH Setpoint Temp X COV CH Staging Setpoint Temp X COV CH Staging X COV Variable Air Volume Units with Water-Cooled Chiller X 15 X 86 Cx Assistant’s Sequence of Operation April 2004 Deadband Temp CH-n CHW Isolation Valve Cmd CH-n CHW Isolation Valve Feedback n1 n 1 CH-n CW Isolation Valve Cmd CH-n CW Isolation Valve Feedback COV COV n1 COV n 1 CH-n Alarm n CH-n Alarm Text n CH-n Enable X n1 CH-n Override n COV X COV X COV X COV X COV X CH-n CHW flow status n 1 COV X CH-n CW flow status n 1 COV X Proof after 1 COV minute X CH-n Status n1 10% high or low CH-n Voltage 3n CH-n Amperage 3n 60 CH-n Power n 15 X CH-n Phase monitor alarm CH-n Chiller n 60 COV n Variable Air Volume Units with Water-Cooled Chiller >1000 X COV 1 87 Cx Assistant’s Sequence of Operation April 2004 Runtime CH-n ReStart Timer 5 Minutes to restart n CH-n Cycle Counter n CH Lead/Lag X CHWPP-n Enable n 1 CHWPP-n Runtime n CHWPP-n Power n CHWPP Lead/Lag CWS Temp COV X COV X Proof after 1 COV minute X >1000 COV 1 X X COV X 1 X 15 X >87 , < 72 when flowing for 5 minutes X 1 CWP-n Enable n1 CW-n Override CWP-n Status X n CHWPP-n Status COV COV n1 CHWPP-n Override CWR Temp >6 hour COV X COV X Proof after 1 COV minute X n n 1 CWP-n Runtime n CWP-n n Variable Air Volume Units with Water-Cooled Chiller 15 X >1000 COV 1 X 88 Cx Assistant’s Sequence of Operation April 2004 Power CWP Lead/Lag X CW Bypass Cmd CW Bypass Feedback COV X COVX 10%,15 X =Cmd COVX after 1 10%,15 minute X CW Temp Set point X COV0.5,15 CW Minimum Temp X COV CW Maximum Temp X COV CW Temp Set point deadband X COV CW Valve Set point Temp X COV CT-n Alarm n CT-n Enable n CT-n Status n1 CT-n Power n CT-n Runtime n X COV X COV X Proof after 1 COV minute X 15 X CT-n Cycle Counter n CT Lead/Lag X CT-n Low Water Alarm HWR Temp COV n1 CT-n Override X n X Variable Air Volume Units with Water-Cooled Chiller >1000 COV 1 >6 hour COV COV X COV X 15 X 89 Cx Assistant’s Sequence of Operation April 2004 1 HWS Temp >180 or <110 when B flow after 1 minute X 1 HW SL Pressure Drop Setpoint HW SL Pressure Drop COVX 10%,15 X =Cmd COVX after 1 10%,15 minute X HWSP-n Enable n1 HWSP-n override n 1 HWSP-n Runtime n HWSP-n Cycle Counter n COV X Proof after 1 COV minute X >1000 COV 1 >6 hour COV =Cmd COVX after 1 10%,15 minute HWSP-n Alarm n n HWSP Lead/Lag B-n Inlet Temp X n1 HWSP-n Run n Speed HWSP-n Power COV n HWSP-n Status HWSP-n Cmd Speed 15 X X X n Variable Air Volume Units with Water-Cooled Chiller COV X 15 X 90 Cx Assistant’s Sequence of Operation April 2004 >190 or <110 when B flow after 1 minute B-n Outlet Temp n1 B Setpoint Temp X COV B Staging Setpoint Temp X COV B Staging Deadband Temp X COV B-n Alarm n B-n Alarm Text n 15 X COV X COV X X B-n Enable n1 COV B-n HW Isolation Valve Cmd n1 COV B-n HW Isolation Valve Feedback n 1 B-n Override B-n HW flow status B-n Re-Start Timer X COV X COV X Proof after 1 COV minute X n n B-n Status B-n Runtime COV n n >1000 n 5 Minutes to restart B-n Cycle Counter n B Lead/Lag X Variable Air Volume Units with Water-Cooled Chiller >6 hour COV 1 COV COV X 91 Cx Assistant’s Sequence of Operation HWPP-n Enable April 2004 n1 HWPP-n Override COV X COV X Proof after 1 COV minute X n HWPP-n Status n 1 HWPP-n Runtime n HWPP-n Power n HWPP Lead/Lag >1000 X X AHU-n Fire Alarm n 1 AHU-n Operating Mode n AHU-n Mode Override COV 1 n COV X COV X COV X COV X AHU-n SAT n 15 X AHU-n OAT n 15 X AHU-n RAT n 15 X AHU-n RA RH 15 X n AHU-n RA Enthalpy n 15 X AHU-n MAT n 15 X AHU-n n Supply Flow Proof after 1 minute 15 X AHU-n Return Flow n Proof after 1 minute 15 X n <5000 CFM for 5 minutes 15 X AHU-n Outdoor Air Flow Variable Air Volume Units with Water-Cooled Chiller 92 Cx Assistant’s Sequence of Operation AHU-n Flow Offset April 2004 n COV AHU-n OA Damper Cmd n COVX 10%,15 AHU-n RA Damper Cmd n COVX 10%,15 AHU-n MA Damper Cmd n COVX 10%,15 AHU-n Economizer High Ambient Lockout Temp n COV0.5,15 X AHU-n Economizer CHW Minimum Temp n COV0.5,15 X AHU-n Supply Reset Temp n COV0.5,15 X AHU-n Supply Pressure Setpoint n COVX 10%,15 AHU-n Supply Pressure n >3” AHU-n Supply Fan Enable n1 AHU-n Supply Fan Status n 1 AHU-n Supply Fan Runtime AHU-n Supply Fan Cmd Speed n n1 Variable Air Volume Units with Water-Cooled Chiller 15 X COV X Proof after 1 COV minute X >1000 COV 1 15 X 93 Cx Assistant’s Sequence of Operation AHU-nSupply Fan Run Speed =Cmd COVX after 1 10%,15 minute n AHU-n Supply Fan Alarm n AHU-n Supply Fan Power n AHU-n Return Fan Enable n 1 AHU-n Return Fan Runtime n AHU-n Return Fan Cmd Speed X Proof after 1 COV minute X >1000 COV 1 15 X =Cmd COVX after 1 10%,15 minute n n AHU-n Return Fan Power n AHU-n CHWV Bypass Cmd AHU-n Warm-up Mode Low Temp COV n1 AHU-n Return Fan Alarm AHU-n CHWV Bypass Feedback X n1 AHU-n Return Fan Status AHU-nReturn Fan Run Speed April 2004 X COVX 10%,15 n =Cmd COVX after 1 10%,15 minute n n Variable Air Volume Units with Water-Cooled Chiller COV X 94 Cx Assistant’s Sequence of Operation April 2004 Setpoint AHU-n CoolDown Mode High Temp Setpoint AHU-n Filter Alarm n n AHU-n Call for Cooling n COV X COV X COV VAV-n Zone n Temp COV0.5,15 X VAV-n Zone Temp SetpointCooling n COV X VAV-n Zone Temp SetpointHeating n COV X VAV-n Zone Temp Unoccupied SetpointCooling n COV X VAV-n Zone Temp Unoccupied SetpointHeating n COV X VAV-n Zone Temp SetpointDeadband n COV X COV X VAV-n Override VAV-n Operating Mode n n VAV-n Supply Air n Temperature Variable Air Volume Units with Water-Cooled Chiller COV COV0.5,15 X 95 Cx Assistant’s Sequence of Operation VAV-n Supply Air Temp Reset VAV-n HW Valve Cmd April 2004 n n VAV-n n Damper Cmd Variable Air Volume Units with Water-Cooled Chiller X COVX 10%,15 COV X 96 Cx Assistant’s Sequence of Operation April 2004 Notes: The system consists of multiple water source heat pump units, 2 boilers with primary pumps and 2 fluid coolers with integral pumps (not shown) all connected to a condenser water loop. The water source heat pump units (WSHP) have integral variable flow supply fans, internally controlled by the unit, that provide conditioned air to the occupied spaces. Outside air is provided through ducted air intakes. Barometric relief dampers maintain building pressurization and allow building air to be exhausted outside. The fluid coolers and boilers provide temperature control for the condenser water loop (or water loop) and two variable-speed water loop pumps circulate the water to each component of the system. Together the water loop, its pumps, the fluid coolers, and the boilers are described as the “water loop central plant”. A building automation system (BAS) controls the equipment. Appropriate reference(s) in the specifications should be made for products that are integrated with these sequences including fluid coolers, boilers, variable frequency drives (VFDs), and the like. Controls: Furnish control device with an interface for monitoring and control of points specified in the points table. The points table includes the minimum acceptable list of interface points. The selected component controls shall easily integrate into the BAS and allow for the collection, control, trending, and archiving of the specified points with a minimal need for intermediary gateways or hardwired connections to link control systems together. Interoperable control systems are preferred. The system(s) in your building that are most similar to the system described above include: Please note that this sample sequence will have to be modified to meet the exact systems defined in your building. Disclaimer: The files produced by Cx Assistant are not suitable for bidding without prior review by the project's architect or engineer of record. The information is provided to the user as a sample document that is based upon a hypothetical system design. It may need to be modified in order to suit specific project requirements prior to inclusion in contract documents. CONDENSER WATER LOOP HEAT PUMP SYSTEM Water Source Heat Pump System 97 Cx Assistant’s Sequence of Operation April 2004 SEQUENCES OF OPERATION Water Source Heat Pump Units 1. Occupied Periods (normal operation): Operate the system on a programmed occupancy schedule from 7:00 AM to 6:00 PM, M-F. These periods are considered “occupied periods”. During occupied periods, run the system in Occupied Mode. NOTE: Schedule occupied start time 1 hour before the building is expected to be occupied (for Title 24 required purge). 2. Unoccupied Periods: All hours not included in an occupied period are part of an “unoccupied period”. During these periods, the system is available for tenant calls as needed but is not running unless commanded. The following holidays are considered to be unoccupied periods: New Years Day, Memorial Day, Fourth of July, Labor Day, Thanksgiving and the following day, Christmas. These should be set up as re-occurring holidays for each zone. 3. Fan Operation: Run the unit fans in all modes except unoccupied mode. Minimum outside air will enter the unit when the supply fan is running based on the building’s pressurization. 4. Fire Alarm: Interface system with the fire alarm controls. When the fire alarm control initiates a fire alarm, shut down the affected supply fan(s) by hardwired contact interface at the contactor. Simultaneously, fire alarm control must notify the BAS of a fire event to enable the BAS to disable the affected units. Once the fire alarm is reset, enable the affected unit(s) to resume normal operation. 5. Occupied Mode: Prior to an occupied period, use an optimal start strategy to initiate a Warm-up mode or Cool-down mode. During Occupied Mode, enable operation of heat pump units and the water loop central plant. At the end of an occupied period, initiate water loop shutdown, disable the heat pump units, and close their condenser water valves. 6. Unoccupied Mode: During unoccupied periods, the heat pump unit’s supply fans are off and the heat pump unit’s condenser water (CW) valve is closed. Each heat pump unit, supported by the central plant, can be started by the BAS to respond to after-hours calls from the zone thermostats. When a thermostat override button is depressed during unoccupied period (i.e. after-hours call), operate the system in occupied mode for one hour. 7. Warm-up Mode: Base the Warm-up start time on an optimal start strategy calculated using outdoor air temperature and average zone temperature. If the average zone temperature is less than 69°F (adjustable), initiate the warm-up mode and set the Warm-up Mode Low Temperature Setpoint to 70°F (adjustable). Enable the water loop pumps, the boilers, and the boiler pumps. Once water loop is proved, enable the heat pump unit(s), as required, to operate in heating mode. Disable fluid coolers during warm-up mode. Terminate warm-up mode when the average zone temperature rises above the Warm-up Mode Low Temperature Water Source Heat Pump System 98 Cx Assistant’s Sequence of Operation April 2004 Setpoint and transition the system to occupied mode (if scheduled) or to unoccupied mode. 8. Cool-down Mode: Base the cool-down start time on an optimal start strategy calculated using outdoor air temperature and average zone temperature. If the average zone temperature is greater than 79°F (adjustable), initiate the cool-down mode and set the Cool-down Mode High Temperature Setpoint to 78°F (adjustable). To initiate a cool-down mode, enable the water loop pumps, and the fluid coolers. Once water loop flow is proved, enable each heat pump unit to operate in cooling mode. Disable the boilers during cool-down mode. Terminate Cool-down mode when the average zone temperature falls below the Cool-down Mode High Temperature Setpoint and transition the system to occupied mode (if scheduled) or to unoccupied mode. 9. Supply Air Temperature Control: When a call for heating or cooling is made from a zone thermostat, open the condenser water valve and prove flow with a flow switch. If flow is proved within 60 seconds of valve opening, the enable the heat pump unit. If the flow is not proved, generate an equipment specific alarm at the operator workstation. Prevent the heat pump compressor from cycling between cooling and heating more often than once every 3 minutes. Also, prevent the heat pump compressor from cycling on and off more often than once every 3 minutes. 10. Filter Status: Monitor the air filter condition with a differential pressure transducer to determine if the filter is dirty. 11. Zone Temperature Control: Use a programmable, solid state, electronic thermostat to adjust the zone velocity controller setpoint integral to each heat pump unit’s supply fan. Airflow to the zone will fluctuate between its minimum and the maximum to maintain a constant room temperature based on this setpoint. Set each thermostat for the following ranges: a. Occupied Heating: 55° F to 73° F during occupied hours. The default is 73° F. b. Occupied Cooling: 73° F to 85° F during occupied hours. The default is 78° F. Maintain a deadband of at least 5° F between heating and cooling setpoints. During unoccupied hours, set the heating setpoint default to 55° F (adjustable) and the cooling setpoint default to 85° F (adjustable). Allow each zone to have its own adjustable unoccupied heating and cooling setpoints. 12. Cooling Mode: When the thermostat indicates a call for cooling, set the heat pump to cooling mode. 13. Heating Mode: When the thermostat indicates a call for heating, set the heat pump to heating mode. 14. Night Setback/Setup: During an unoccupied period, enable the warm-up mode if any zone thermostat falls below the unoccupied heating setpoint and set the Warm-up Mode Low Temperature Setpoint equal to the unoccupied heating setpoint. Also, enable the cool-down mode if any zone thermostat rises above the unoccupied cooling setpoint and set the Cool-Down Mode High Temperature Water Source Heat Pump System 99 Cx Assistant’s Sequence of Operation April 2004 Setpoint equal to the unoccupied cooling setpoint. Allow each unit to have its own adjustable night setback and night setup setpoints. 15. Heat Pump Compressor Shutdown: If the unit stops generating a call for heating or cooling, the condenser water system shuts down, or a refrigeration fault occurs, disable the compressor operation. After the compressor is disabled, leave the flow control valve open for two minutes and then close it. Water Loop Central Plant 1. Chemical Treatment: Chemically treat the fluid cooler via an automatic chemical feed and bleed system. The fluid cooler water treatment system runs independently of the BAS. 2. Safeties: Disable the fluid cooler’s pump if the water level in the fluid cooler’s basin falls below its minimum allowable level. Initiate a Low Water Basin Alarm at the BAS operator workstation. 3. Water Loop Pump Enable: Start the pumps at 10% speed. If the flow is not proved within 60 seconds (adjustable) as indicated by a differential pressure switch, disable the pump(s), and initiate an equipment specific critical alarm (“CP-1 Failed”) at the operator workstation. Modulate the speed of the pumps in order to maintain a differential pressure setpoint of 15 PSID at the central plant. When the commanded speed falls below 40%, shut down the lag pump. When the commanded speed rises above 60%, start the lag pump. After 40 hours of operation, on Sunday at 3:00 AM when the system is in unoccupied mode, swap the lead and lag pumps. 4. Water Loop Cooling Temperature Control: When the water loop pumps are enabled, the fluid cooler bypass valve is in the bypass position (bypassing the fluid coolers) and the fluid cooler fans are off. As the water loop supply temperature increases to above 86° F, begin opening valve (to no bypass) and start the fluid cooler pump. As the water loop temperature increases to 87°F, start both fluid cooler fans at minimum speed. Modulate the fan speed to maintain 85°F. Below 84° F, cycle the fans off. If the water loop temperature exceeds the high limit of 90° F, generate an alarm at the operator workstation. As the water loop supply temperature falls below 83° F, begin modulating the bypass valve to full bypass and turn off the fluid cooler pump. 5. Water Loop Heating Temperature Control: When the water loop pumps are enabled, the boiler bypass valve is in the bypass position (bypassing the boilers) and the boilers are off. If the water loop supply temperature falls below 71° F for 3 minutes, begin opening the bypass valve (to no bypass) and enable the boiler pumps. As the condenser supply water temperature falls to 69° F, modulate the bypass valve to no bypass in order to maintain temperature. Enable the boilers when the bypass valve is all the way open (no bypass). If the water loop supply temperature falls below the low limit of 68° F, generate an alarm at the operator workstation. As the water loop supply temperature rises above 72° F for 3 minutes, initiate boiler shutdown and begin modulating the bypass valve to full bypass. Water Source Heat Pump System 100 Cx Assistant’s Sequence of Operation April 2004 6. Boiler Pump Enable (Boiler Initiation): When the boiler bypass valve begins to modulate open, open the isolation valves to the lead boiler. If the valve opening fails to prove within 60 seconds, close the valve, set the lag boiler as lead and send an equipment specific alarm (“B-1 Isolation Valve Failed to Open”) to the operator workstation. Repeat valve operation with lag boiler. If both valves fail to open, initiate boiler shutdown operation and send equipment specific alarms to the operator workstation. If valve opening is successful, enable the lead primary boiler pump. If the flow is not proofed within 60 seconds, disable the pump, and set the lag pump as lead. If both pumps fail to provide flow, initiate the boiler shutdown operation. Initiate equipment specific alarms at the operator workstation for the failure of either pump. The primary pumps are operated lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead and lag pumps. 7. Boiler Enable: Upon proof of primary hot water flow, enable the selected boiler. Provide a hard-wired flow switch to act as a back up to ensure that boiler only starts with hot water flow. Send an initial hot water temperature of 140° F to the boiler controller. Prove the boiler operation after 60 seconds in the following manner: if the boiler has not developed at least 3° F of differential temperature between its supply and return temperatures, disable the boiler and initiate its shutdown sequence. Operate the boilers lead/lag. After 40 hours of operation, on Sunday at 3:00 AM when both boilers and pumps are shut down, swap the lead position. Enable the lag boiler to start. If either or both boilers fail to prove or fail to proof when required to operate, initiate boiler shutdown and send equipment specific alarms to the operator workstation. During operation, use the boiler’s internal safeties to initiate an equipment alarm at the operator workstation and disable the machine. If the boiler does not develop at least a 3°F temperature difference after 15 minutes of being enabled initiate a equipment specific alarm at the operator workstation. 8. Boiler Staging: Modulate the internal boilers controls between the boiler’s two stages to meet the BAS water loop setpoint. If during boiler operation, the hot water temperature differential falls to 5°F (adjustable), initiate the lag boiler operation. Maintain operation of both boilers until the hot water temperature differential rises to 12° F. At this point, initiate the lag boiler shutdown sequence. 9. Boiler Shutdown: Upon a call from the BAS or an internal alarm, initiate the boiler shutdown. Provide the BAS with redundant sensors for hot water flow, hot water temperature Hi Limit (more than 200° F). Disable operation of the affected boiler(s) if the limits are exceeded. If both boilers trip or fail to proof, initiate an equipment specific alarm at the operator workstation. Prevent the boiler from cycling on and off more often than once every 5 minutes (this may be redundant to the boiler’s internal safeties). For each boiler, disable the boiler first before shutting down its pump. After disabling the boiler, run the primary boiler pump serving the boiler for 5 minutes. After 5 minutes, shut down the primary boiler pump and close the hot water isolation valves. Water Source Heat Pump System 101 Cx Assistant’s Sequence of Operation April 2004 10. Water Loop Shutdown: When water loop shutdown is initiated, run the pumps for 5 minutes and then shut them off. When the water loop is shut down due to being disabled or due to a fault, lockout operation of the heat pump compressors. Points Table Key: X Indicates type of point (only 1 point is needed) n Indicates type of point (1 point is needed for each zone – a total of “n” points are needed for this line item) B boiler FLC fluid cooler Cmd command COV change of value DB dry-bulb WSHP water-source heat pump unit HW Hot water M “mixed” such as the air in the mixed air plenum (MAT = mixed air temperature) OA outside air (OAT = outside air temperature) P pump (FLCP = fluid cooler pump, PP = primary pump) R return (FLCR = fluid cooler return water temperature) S supply (SAT = supply air temperature) SL secondary loop CW condenser water (i.e. water loop) Resolution of analog inputs: °F 0.1 Water Source Heat Pump System 102 Cx Assistant’s Sequence of Operation April 2004 psid 0.005 ” water cfm 1 rpm 1 kW 0.1 % 0.1 Point Name Analog Digital Other AI AO DI DO Software Software Software Value Value Value OA DB Temp X Alarm Logic CWS Temperature X CWR Temperature X CW Temp Set point X CW Minimum Temp X Water loop min. temp CW Maximum Temp X Water loop max. temp CW Pressure Drop Setpoint X =Cmd after 1 minute CW Pressure Drop X CWP-n Enable n1 CWP-n override n CWP-n Status CWP-n Runtime n CWP-n Cycle Counter >1000 n CWP-n Cmd Speed CWP-n Run Speed Proof after 1 minute n1 > 6 hour n1 =Cmd after 1 minute n CWP Lead/Lag Water Source Heat Pump System X 103 Cx Assistant’s Sequence of Operation April 2004 FLC Temp Set point deadband X FLC Bypass Valve Set point Temp X FLC Bypass Valve Cmd Position FLC Bypass Valve Feedback X =Cmd after 1 minute X FLC-n Inlet Temp X 1 FLC-n Outlet Temp >87 , < 72 when flowing for 5 minutes X1 FLC-n Enable n1 FLC-n Override n FLC-n Status n1 FLC-n Runtime n >1000 FLC-n Cycle Counter n FLC Lead/Lag X FLC-n Low Water Alarm > 6 hour n FLCP-n Enable n1 FLCP-n Override n FLCP-n Status Proof after 1 minute n1 HW Temp Set point deadband X HW Bypass Valve Set point Temp X HW Bypass Valve Cmd Position X HW Bypass Valve X Feedback HWR Temp Proof after 1 minute =Cmd after 1 minute X1 Water Source Heat Pump System 104 Cx Assistant’s Sequence of Operation HWS Temp April 2004 >180 or <110 when HW flow after 1 minute X1 B-n Inlet Temp n B-n Outlet Temp n1 B Setpoint Temp X B Staging Setpoint Temp X B Staging Deadband Temp X B-n Alarm n B-n Enable n1 B-n HW Isolation Valve Cmd n1 B-n HW Isolation Valve Feedback n1 B-n Override B-n HW flow status >190 or <110 when HW flow after 1 minute n n B-n Status n Proof after 1 minute B-n Runtime n >1000 B-n Re-Start Timer n 5 Minutes to re-start B-n Cycle Counter n B Lead/Lag X HWPP-n Enable n1 HWPP-n Override HWPP-n Status > 6 per hour n Proof after 1 minute n1 HWPP-n Runtime HWPP Lead/Lag Water Source Heat Pump System n >1000 X 105 Cx Assistant’s Sequence of Operation WSHP-n Fire Alarm April 2004 n1 WSHP-n Enable Cooling n1 WSHP-n Enable Heating n1 WSHP-n Supply Fan Enable n1 WSHP-n CWV Bypass Cmd n WSHP- Flow Status =Cmd after 1 minute n WSHP-n Warmup Mode Low Temp Setpoint n WSHP-n CoolDown Mode High Temp Setpoint n WSHP-n Zone Temperature Sensor n WSHP-n Zone Temperature Setpoint-Cooling n WSHP-n Zone Temperature Setpoint-Heating n WSHP-n Zone Temperature Unoccupied Setpoint-Cooling n WSHP-n Zone Temperature Unoccupied Setpoint-Heating n WSHP-n Zone Temperature SetpointDeadband n WSHP-n Override Water Source Heat Pump System n 106 Cx Assistant’s Sequence of Operation Water Source Heat Pump System April 2004 107