1084 Installation Guide Compatible Equipment All Hardwired Control Panels, for example: 9800+ 8-16 zone control panel 808 8-12 zone control panel 816 8-16 zone control panel 496350 Issue 1 1 of 8 1084 Introduction The 1084 Twintec ® Twin Technology Detector is an indoor motion detector for use in wired intruder alarm systems and is suitable for commercial burglar alarm systems. The 1084 Twintec combines both Microwave and Passive Infra Red (PIR) technologies in a single small detector, giving a conical surveillance area as shown in Figure 1. Figure 1. Detector Surveillance Area 2 of 8 496350 Issue 1 1084 Technical Specification The Twintec is Microprocessor based and uses digital signal processing techniques combined with Energy/Frequency analysis on PIR channel and M.E.V. (Multi Event Verification) on microwave channel. Complete metallic shielding of the electronic circuitry stops false alarms caused by RFI. Optical and software filters stop false alarms caused by white light and fluorescent lighting. The range of the microwave sensor may be selected to limit coverage to the area requiring protection. Two sets of relay contacts are provided. The alarm contacts are Single Pole Change-over in alarm (NO/C/NC) and the tamper contacts are closed with the cover on. Technical Specification The detector comprises a white textured ABS chassis, a cover containing the lens and a metallic shielded printed circuit board which can be removed to aid installation. Supply Voltage 8-15V DC. Current 20mA. Relay Output SPCO, 30V, 100mA DC. Change-over in alarm with 22ohm resistor in series Tamper Output SPST, 30V, 100mA DC. Closed with cover on. Detection Pattern Conical (see Figure 1). Operating Temp -10°C to +55°C. MW Range Adjustable100- 30% by potentiometer. Microwave Dielectric Resonant Oscillator with microstrip antenna 10.687 GHz. Infra Red Sensor Dual element pyroelectric detector, hermeticallysealed. Microwave In the event of microwave section failure, Supervision reverts unit to PIR only operation and causes PIR to convert from Single Edge to Double Edge PIR operation. Alarm/Test/Trouble LED flashes every second if programmed for Trouble. Detector pcb ‘Trouble’ output also operates with open collector to 0V. RFI/EMI Immunity Unit will not alarm when subjected to RFI signals of 1MHz to 1GHz with a field strength of 10 Volts/ Metre. Fluorescent Tube Will not alarm from an 80W, 1.83m tube positioned 482mm above and 1.98m Immunity in front of the unit and cycled I minute On and 30 seconds Off. 496350 Issue 1 3 of 8 Wiring Connections 1084 LED Indicators 5 LEDs. 2 x Red - Alarm/Test/Trouble. 2 x Green - PIR. 1 x Yellow - M/W. Mounting Flat ceiling mounting. (Flush Mount Kit available). Physical Dia. x Depth 120 x 55mm. Approval DTI Spec. MPT1349. Warranty 5 years. Recommended mounting height is between 2.4m and 4.6m (Figure 2). Avoid heights in excess of 4.6m as the detection sensitivity declines to an inadmissible level. Figure 2. Graph of Range vs Mounting Height (see Fig 1 for a, b and c) Specification subject to change at any time. Wiring Connections 1. 2. 3. 4. 5. 6. 4 of 8 Ensure that the wiring has no power applied. Connect terminals 1, 2 and/or 3 to the control panel or warning device, depending on circuit requirements. Connect terminal 4 to the positive supply. Connect terminal 5 to the 0V supply. Use Terminal 6 (EOL) as a connection point for EOL devices. If the control panel has a 0V Test facility, connect terminal 7 (Test) to the control panel Test connection. If connected the ‘Walk Test’ LEDs will be enabled only when ‘Walk Test’ is selected at the control panel. If no Test facility is available at the control panel, a switch can be used to switch the 0V supply to terminal 7. 496350 Issue 1 1084 7. 8. Adjusting the Surveillance Pattern Terminal 8, an open collector, will go to 0V if the microwave supervision detects a malfunction in the microwave detector. Connect to control panel ‘Trouble’ input or to other signalling device. Connect terminals 9 and 10 to the control panel ‘Tamper’ circuit or other warning device. Figure 3. Connecting the 1084 Adjusting The Surveillance Pattern Once the detector is installed, the surveillance pattern of both the microwave and PIR sensors must be adjusted to suit the protected area. To check the actual coverage of the detector, place links on the appropriate jumper links as described below for each function, then walk test the protected area. Note: A walk test can be carried out on either the microwave sensor or the PIR sensor, or both detectors simultaneously. Microwave Pattern Adjustment The detector works best with the microwave sensor adjusted to the minimum sensitivity necessary. Proceed as follows: 1. Remove the cover and fit link across Test jumper pins (Figures 4 and 5). 496350 Issue 1 5 of 8 Adjusting the Surveillance Pattern 1084 Figure 4. Inside the 1084. Figure 5. Jumper Link Settings. 2. 3. 4. 5. 6. 7. 6 of 8 Fit link across Microwave jumper pins. Apply power to the detector and refit cover. Stand outside the protected area and wait for the Alarm LEDs to go out. Walk into the protected area and stop when the Alarm LEDs illuminate. Mark the position carefully. Repeat steps 4 and 5 throughout the protected area unit the complete microwave surveillance pattern has been mapped. If necessary adjust the Microwave range potentiometer to obtain the desired surveillance pattern. 496350 Issue 1 1084 PIR Pattern Adjustment PIR Pattern Adjustment 1. 2. 3. 4. 5. 6. Remove the cover and fit link across Test jumper pins (Figure 5). Fit link across PIR jumper pins. Apply power to the detector and refit cover. Stand outside the protected area and wait for the Alarm LEDs to go out. Walk into the protected area and stop when the Alarm LEDs illuminate. Mark the position carefully. Repeat steps 4 and 5 until the complete PIR surveillance pattern has been mapped. Masking It may be impossible to avoid problem areas within the surveillance pattern, for example; air currents. If false alarms are established during walk testing and the cause cannot be removed from the protected area, locate the cause and establish the lens segment covering the particular area. Mask the lens segment from the inside of the lens using only the masking material supplied. The centre lens should be masked when mounting the detector less than 2.4m high. Setting The Operational Mode When the surveillance pattern has been set up for both microwave and PIR sensor and any necessary masking has been done, the operational mode of the detector must be set. Setting The Walk Test Mode With a link fitted across the ‘Test’ terminals, the alarm LEDs will indicate movement at all times. However, where Alarm LED illumination is not desirable during the ‘Unset’ period, the link should not be fitted to the ‘Test’ jumper pins and should be left fitted to one pin only. In this mode the Alarm LEDs will only illuminate during a ‘Walk Test’ initiated by applying 0V to terminal 7, e.g., panel walk test, (or if the link is fitted across the ‘Test’ terminals). Setting ‘Trouble’ LED Mode The Alarm LEDs can be set to flash in the event of the microwave supervision detecting a microwave malfunction by fitting a link across the ‘Trouble’ jumper link. The operation of the microwave sensor and the PIR sensor will depend on the position of the links across the ‘Microwave’ and PIR jumper pins. 496350 Issue 1 7 of 8 PIR and Microwave Activation 1084 PIR And Microwave Activation This is the normal mode of operation and requires both the microwave and PIR sensors to detect movement before the alarm relay is activated. To achieve this mode of operation neither the PIR or Microwave jumper pins should be linked. PIR or Microwave Activation In this mode of operation the relay will be activated if either the PIR sensor or Microwave sensor detects movement. In this mode of operation, the detector is highly sensitive and should only be used in extremely secure environments, e.g., bank vault. To achieve this mode, both the PIR and microwave jumper pins should be linked. Final Testing Once both detection patterns have been adjusted and the operational mode has been selected, the operation of the complete detector should be tested as follows: 1. Select ‘Walk Test’ if applicable. 2. Clear the protected area and make four random direction walk tests. Walk at a rate of one normal step per second within the detection pattern. The unit should alarm within three out of the four walk tests. 3. Stand outside the protected pattern and operate any potential cause of false alarm, e.g., operate lights, open doors, etc. If the unit detects the deliberate cause of false alarm, try adjusting the detector pattern. 4. Stand outside the detection pattern and observe the detector operation for three to five minutes without doing anything. The detector should not alarm. If the detector does alarm, locate the cause and correct it. When walk testing, cross the sensitive zones at right angles in upright position. After each activation wait until the LED’s extinguish. 8 of 8 496350 Issue 1