WIM1-H - Time Overcurrent Relay with Multi-Characteristic Contents 1 General 2 Characteristics and Features 3 Working Principle 3.1 Tripping Outputs 3.1.1 Adaptation of Current Transformer and Tripping Device 3.1.2 Limiting of the Relay Short Circuit Measuring Currents 3.1.3 Average Value Correction 3.2 Setting of the relay 3.2.1 Setting of the switches 3.2.2 Settings at the CHAR - switch 3.3 Overcurrent tripping 3.4 Fast short-circuit tripping 3.5 Integrated safety routine 3.6 Setting example 3.7 Remote tripping 3.8 Overcurrent - short-circuit indications 3.8.1 Tripping indication by means of flag indicator 4 Relay testing and commissioning 4.1 Checking the set values 4.2 Secondary injection test 4.2.1 Test equipment 4.2.2 Example of test circuit for WIM1-H relays 4.2.3 Checking the operating and resetting values of the relay 4.2.4 Checking the relay operating time 4.2.5 Checking the high set element of the relay 4.3 Primary injection test 4.4 Maintenance 4.5 Tripping characteristics 5 Technical Data 2 1 General The WIM1-H is a current fed time overcurrent relay with multi-characteristics. Definite time and inverse time tripping characteristics can be selected. The WIM1-H does not require an auxiliary voltage supply, consequently it can also be used for switchboards without built-in batteries. It derives its power supply energy from the current transformer from which, for special applications, it can also feed the power that is necessary to give the tripping impulse to the circuit breaker. Due to its wide setting ranges, the tripping characteristic can be selected to protect a wide variety of different equipment. 2 Characteristics and Features • Auxiliary voltage supply is not required • User-friendly setting procedure with wide setting ranges • Four 16-position setting switches for tripping current and time • DIP - switch to adjust the tripping characteristic, ranges and frequency • High measuring accuracy through an efficient microprocessor and digital processing of the measuring values • High operating reliability through internal selfsupervision (watchdog) • Protective functions selectable:definite time overcurrent protection (DMT) and inverse time overcurrent protection (IDMT) • Selectable INVERSE - tripping charcteristics according to BS 142 resp. IEC 255-4: normal inverse very inverse extremely inverse • Remote tripping via external voltage • Electro pulse output for the direct triggering of the circuit breaker • Tripping indication via external flag indicator with mechanical reset • Compact construction • Insensitive to extreme environmental conditions • High-accuracy components and over-rating guarantee precision, reliability and a long service life • In accordance with the specified technical data, it complies with the requirements of VDE - regulation 0435-303, IEC 255, VDE 0843 TB WIM1-H 07.97 E 3 Working Principle The alternating currents induced by the mains current transformers provide the WIM1-H's supply energy and form the measuring value. The measuring currents are galvanically isolated via the input transformers, decoupled from high-frequency interferences by analog RC-filters and then converted into current proportional voltages. These voltages are rectified and the rectified mean value is calculated by the microprocessor. Measurings are made in two steps acc. to the auto ranging method. For very distorted current curve shape an average value correction is provided in the short circuit measuring range. The A/D converter sampling frequency for the detection of the rectification mean value is 1600 Hz per cycle (every 0.625 ms) at 50 Hz and 1920 Hz (every 0.521 ms) at 60 Hz. Depending on the mean value and the adjusted tripping characteristic, the tripping time, if activated, is calculated by means of a time optimised protective program. An integrated watchdog supervises this protective program. Figure 1 Block Diagram ➀ ➁ ➂ ➃ ➄ Setting switch for tripping characteristic Decoder Measuring value storage Tripping amplifier Flag indicator TB WIM1-H 07.97 E ➅ ➆ ➇ ➈ ➉ Remote tripping Tripping relays Energy store Saturation resistance Trip solenoid 3 3.1 Tripping Outputs For direct tripping of the circuit breaker from the WIM1-H an electro pulse output is used (terminal 10+ and terminal 11-). The tripping energy is either taken direct from the relay input measuring current or a trip energy store. The tripping pulse on-time is 0.2 s. Concerning voltage level and energy content the tripping pulse varies dependent on the following operational conditions: Remote tripping During remote tripping a 50 V DC tripping pulse, ±10%, is sent with an energy of 2.5 Ws. Relay input measuring currents >15A AC ±10% Tripping via the internal trip energy store. The loading level or pulse amplitude varying between 50 V DC ±10% (min. value) and ≈100 V DC, dependent on the input measuring current and tripping delay. The energy differs between 2.5 Ws and ≈10 Ws. Relay input measuring currents <15 A AC ±10% In case of tripping, the input measuring current is directly sent to the tripping coil of the c.b. via a rectifier circuit. The voltage level of the tripping pulse and the energy depend on the input measuring current and the impedance of the tripping coil. Each tripping consists of a cycle of 5 trip attempts with an on-time of 0.2 s per pulse. The interval following these attempts is necessary for recharging the internal trip energy store (2000 µF). The time required for this is between 0.05 s and 2.5 s max, dependent on the relay input measuring current. The charging condition of the trip energy store is constantly supervised during the charging procedure. After elapsing of the tripping delay, the trip cycle is always repeated. 3.1.1 Adaptation of Current Transformer and Tripping Device The tripping energy for relay input measuring currents <15 A AC ±10 % down to the lowest tripping limit (I> = 1A, tI> = 0.2 s) or (I>> = 2 A, tI>> = 0.05s) is taken via a rectifier circuit directly from the relay input measuring current or the main CT. In correlation with the tripping coil, rating of the main CT must be such that tripping is guaranteed at the specified lowest tripping limits. But overrating of the CT (when the type used is too large) has to be avoided either (see para. 3.1.2). 3.1.2 Limiting of the Relay Short Circuit Measuring Currents In case of relatively high power consumption of the tripping device, the main CT must be rated accordingly, especially with regard to the lowest tripping limit. This means that the main CT is clearly overrated in the short circuit range which gives rise to excessive relay short circuit measuring currents. By providing additional saturation resistors in the relay measuring current path, the main CT is higher loaded in the short circuit range, resulting in saturation of the CT. The saturation resistors should be rated 0.5Ω to 1Ω for 100W to 150 W. Saturation resistors must be resistant to pulses (min. ≈ 1.5 kW for 1 s at R = 0.5Ω). For this application the use of heavy-duty resistors is recommended (e.g. DRALORIC ZBS 30/133 to ZBS 30/165). Limiting the relay short circuit measuring currents by means of lower rating of the main CT is only possible if the needed tripping capacity is also reduced. 3.1.3 Average Value Correction The relay input measuring currents are ascertained as rectifying average value in two steps by means of the auto ranging method. In the upper measuring range (short circuit range), large distortions of the sine-wave form occur which are adversely influenced by the saturation resistors. For this reason an average value correction has been provided in the upper measuring range compensating the influence of this wave-form distortion to the measuring value of the input current. 4 TB WIM1-H 07.97 E 3.2 Setting of the relay All switches for the relay setting are located on the plate of the WIM1-H. The function designation is indicated next to the switches. To adjust the values below, four 16-position BCD switches are available: I> I>> tI> tI>> Overcurrent pickup value high set pickup value trip delay for the overcurrent element trip delay for the high set element To select the tripping characteristic and the nominal frequency, there is a DIP switch set. This set is designated CHAR. Two LEDs signalize pickup of the overcurrent element I> and the high set element I>>. Figure 2: Front plate/wiring sceme IMPORTANT NOTICE it's only allowed to connect the terminals 1S1, 2S1 and 3S1 to earth. TB WIM1-H 07.97 E 5 3.2.1 Setting of the switches 3.3 Before commissioning, it is essential to select the nominal frequency, tripping characteristic and tripping ranges (CHAR switches 1-8). Furthermore, the selector switches I>, tI>, I>>, tI>> have to be adjusted to the appropriate pickup currents and trip delays. By means of DIP - switches 2 - 5, it is possible to select either one of the three dependent or one independent tripping characteristic. 3.2.2 Settings at the CHAR - switch The equations on which the characteristics are based are detailed on page 11, paragraph "dependent overcurrent time protection". The following table shows the adjustment values for the appropriate switch positions of switches I> and tI>. The functions of the individual DIP - switches are detailed in the following table: Switch no. 1 2 3 4 5 6 8 OFF position nominal frequency 50 Hz high set element blocked range 1 for tI> (DMT) Overcurrent tripping The possible characteristics are shown on page 9, in four diagrams. ON position nominal frequency 60 Hz characteristic normal inverse characteristic very inverse characteristic extremely inverse characteristic definite time high set element activated range 2 for tI> (DMT) Table 1: Functions of the CHAR - switch Switch position IDMT I> = IN x 0 1 2 3 4 5 6 7 8 9 A B C D E F 1.0 1.0 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 tI> time factor 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 DMT tI> [s] range 1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 range 2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Table 2: Setting values for the overcurrent element 6 TB WIM1-H 07.97 E 3.4 Fast short-circuit tripping 3.6 In addition to the definite time or inverse time overcurrent tripping, it is possible to adjust a fast high set tripping. It has two setting ranges for the high set pickup current (see the following table). The high set element always has a definite time characteristic. Switch position 0 1 2 3 4 5 6 7 8 9 A B C D E F I>> / IN I>> 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 tI>> [s] tI>> 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.0 1.0 1.0 1.0 1.0 Setting example The tripping characteristic as shown below is to be adjusted. Its sections consist of one inverse time characteristic (normal inverse) for the overcurrent tripping (section 1) and one definite time characteristic for the high set element (section 2). The nominal frequency is 50 Hz. The following settings must be made: 10 t[s] 1 Table 3: Setting values for the high set element 3.5 Integrated safety routine In case of incorrect adjustment, for example if no, two, or several characteristics have been selected, the WIM1-H runs in a safety routine providing the lowest tripping values. To avoid damage, the relay automatically selects the following safety setting in this mode: Automatic safety setting (DEFINITE TIME characteristic) Value I> tI> I>> tI>> Is = 1 x IN 0.2 s 2 x IN 0.05 s 0.1 1 2 3 4 5 6 7 8 9 10 20 I/IN Fig 3: Example of a characteristic DIPswitch 1 2 OFF 3 4 x x 5 6 8 x ON Function x x x x Table 4: Automatic safety setting nominal frequency 50 Hz characteristic Normal inverse characteristic Very inverse characteristic Extremely inverse Definite time characteristic high set element active switch position optional (only for independent overcurrent tripping) Table 5: CHAR-switch TB WIM1-H 07.97 E 7 Switch I> tI> I>> tI>> Switch position 4 3 8 2 Setting value 1.2 A 0.4 A 6.0 A 0.2 A Table 6: Step switches 3.7 Remote tripping 4 Relay testing and commissioning The test instructions following below help to verify the protection relay performance before or during commissioning of the protection system. To avoid a relay damage and to ensure a correct relay operation, be sure that: • the rated current of the relay corresponds to the plant data on site. • the current transformer circuits are connected to the relay correctly. • all signal circuits and output circuits are connected correctly. The input "remote tripping" (terminals 13 and 14) allows tripping by an external alternating voltage, e.g. by a thermal tripping coil, a Buchholz protection or other remote tripping commands. Bypassing the measuring circuits, this input has a direct effect on the tripping circuit. A signal 230 V/AC may only be fed for a maximum duration of 20 minutes. The tripping time delay depends on the input voltage (see technical data). The input terminals are galvanically isolated from the electronic part of the relay. 4.1 3.8 For a correct relay operation, be sure that the frequency DIP-switch (50Hz/60Hz) has been selected correctly according to your system frequency (50 or 60Hz). Overcurrent - short-circuit indications At the front plate there are two LEDs to indicate pickup of the relay. If the adjusted pickup value of the overcurrent element I> is exceeded, the LED I> will lights up and a calculated delay expires until the relay trips. LED I>> lights up if high set tripping has been selected and the additionally adjusted pickup value for I>> has been exceeded. 3.8.1 Tripping indication by means of flag indicator A tripping can be indicated mechanically through the flag indicators WI1-SZ2 and WI1-SZ3 which are optionally available. After tripping, they have to be reset manually. For the connection of the flag indicators, see the connection diagrams on page 5. 8 Checking the set values Check all relay set values and see if they are set correctly as you have desired. Set values can be modified by means of the DIP-switches on the front. 4.2 Secondary injection test 4.2.1 Test equipment • Ammeter with class 1 or better • Single-phase current supply unit adjustable from 0 to ≥ 2.3 x IN (2.5 A AC) • Timer to measure the operating time (Accuracy ±10 ms) • Switching device • Test leads and tools Important note ! The permanent load carrying capacity must not exceed 2.3 x In. TB WIM1-H 07.97 E 4.2.2 Example of test circuit for WIM1-H relays 0 For testing WIM1-H relays, only current input signals are required. The following diagram shows a simple example of a single phase test circuit with adjustable current energizing the WIM1-H relay under test. 4.2.3 Checking the operating and resetting values of the relay 4.2.4 Checking the relay operating time Inject a current which is less than the relay set value I> in the phase 1, 2 or 3 of the relay and gradually increase the current until the relay starts, i.e. at the moment when the LED I> lights up. Read the operating current indicated by the ammeter. The deviation must not exceed ±5% of the set operating value. Furthermore, gradually decrease the current until the relay resets, i.e. the LED I> extinguishes. Check that the resetting current is greater than 0.97 times the operating current. Repeat the test by means of injecting current in the other phases in the same manner. To check the relay operating time, a timer must be connected to the trip output 10 - 11. The timer should be started simultaneously with the current injection into the current input circuit and stopped by the trip impulse. Set the current to a value corresponding to twice the operating value and inject the current instantaneously. The operating time measured by the timer should have a deviation of less than ±3% of the set value or ±10 ms. Repeat the test on the other phases or with the inverse time characteristics in the similar manner. In case of inverse time characteristics the injected current should be selected according to the characteristic curve, e.g. two times IS. The tripping time may be red from the characteristic curve diagram or calculated with the equations given under "technical data". Please observe that during the secondary injection test the test current must be very stable, not deviating more than 1%. Otherwise the test results may be wrong. TB WIM1-H 07.97 E 9 4.2.5 Checking the high set element of the relay To test the high set element, its trippping delay has to be set much longer than the tripping delay of the overcurrent element. Set a current to the set operate value of I>>. Set I> to 1 A. Set I> to 2 A. Set tI> to 1,7 s. Set tI>> to 1 s. Inject the current (2.3 A) and check that the LED I>> lights up after 1 s. Repeat the test with injected current around the operate value and seek the operate value in this manner. Set the desired time delay tI>> of high set element. Inject a current corresponding to twice the operate value of I>> if possible and measure the operate time with timer in the same manner as in para. 0. 4.4 Maintenance Maintenance testing is generally done on site at regular intervals. These intervals vary among users depending on many factors: e.g. the type of protective relays employed; the importance of the primary equipment being protected; the user's past experience with the relay, etc. For electromechanical or static relays, maintenance testing will be performed at least once a year according to the experiences. For digital relays like WIM1-H, this interval can be substantially longer. A testing interval of two years for maintenance will be recommended. During a maintenance test, the relay functions including the operating values and relay tripping characteristics as well as the operating times should be tested. Note: During test of the high set element, great care must be taken to ensure that the test currents and their duration do not exceed the current circuit thermal withstand given in the technical data. 4.3 Primary injection test Generally, a primary injection test could be carried out in the similar manner as the secondary injection test described above. With the difference that the protected power system should be, in this case, connected to the installed relays under test on line, and the test currents should be injected to the relay through the current transformers with the primary side energized. Since the cost and potential hazards are very high for such a test, primary injection tests are usually limited to very important protective relays in the power system. 10 TB WIM1-H 07.97 E 5 Technical Data Measuring input Rated data: nominal current In = 1A, 50/60 Hz Power consumption in current circuit at I = 1A =1xIN: S = 5 VA Thermal withstand capability of the current circuit: rated surge current for one half-cycle 135 x IN rated short-period current for 1 s 54 x IN short-period load carrying capacity for 10 s 17 x IN permanent load carrying capacity 2.3 x IN Input for the remote tripping Nominal voltage: Power consumption: 230 V/AC, max. 20 min. 6 VA/220 V Tripping time: dependent on the input voltage; U = 230 V ± 20% tmax = 2.5 s Tripping: periodically for the input voltage range from U = 0.8 to 1.2 UN, if no current flows lower operating value 90 V AC, if current flows frequency dependent on U Accuracy Basic accuracy (related to the current): Basic accuracy of the tripping time delay: Influence of frequency: Influence of temperature: ± 5% ± 3% or ± 10 ms in the range of ± 5% of the nominal frequency the current deviation is 0.5% per Hz 0 0 ± 1.5% at - 40 C to 55 C: Specified ambient service Temperature range for storage: Temperature range for service: 0 0 - 40 C to + 85 C 0 0 - 40 C to + 55 C General data Drop-out to pickup ratio: Returning time: Minimal response time: Time lag error class index E: TB WIM1-H 07.97 E 97% 20 ms 50 ms 10 ms 11 Definite time overcurrent protection (DMT) I> range 1; steps 1 - 2.3 x IN; 0.1 x IN 0.2 - 1.7 s; 0.1 s Is tI> range 2; steps 2 - 17 s; 1 s Inverse time overcurrent protection (IDMT) Tripping characteristics according to IEC255-4 (BS 142): Normal Inverse t= Very Inverse t= Extremely Inverse t= with: I> t tI> I IS = = = = 014 . ⋅ tI > (I / Is) 0.02 −1 135 . ⋅ tI > / I ( Is) − 1 80 ⋅ t I > (I / Is) 2 −1 tripping time delay time multiplier fault current set value of the current I tI> range 1; steps 1 - 2.3 x IN; 0.1 x IN 0.1 - 1.6; 0.1 Electro Pulse Output Terminal 10 (+), terminal 11 (-) Trip: recurring cycle with 5 pulses of 200 ms each. For currents < 15A AC ± 10 % the first pulse is not supported by the energy store. Depending on the relay current, intervals lasting from 50 ms up to 2.5s. Internal trip energy store: 2000 µF / 100 V DC (recharging 50 V DC ± 10 % up to 100 V DC ± 10 % depends on the current). When the upper interval limit is exceeded (2.5 s), the actual energy storage is released for tripping 50 to 100 V ± 10 % Output voltage: 12 TB WIM1-H 07.97 E Tripping energy at remote tripping: at currents >15A AC ±10 %: at currents <15A AC ±10 %: 2.5 Ws 2.5 Ws up to 10 Ws (dependent on the relay current or the stored energy) at 200 ms pulse on-time direct dependent on the impedance of the tripping coil and the respective relay current. (Dependent on the relay current or the stored energy. A reliable lowest tripping limit depends mainly on the adjustment between main CT and tripping coil). Indication elements Overcurrent indication: Short-circuit current indication: Flag, optionally: LED I> LED I>> external flag, with mechanical reset function for the indication of a tripping Type tests Regulations: VDE 0435, part 303, IEC 255-4, BS 142, VDE 843 part 2, 3, 4 high voltage tests according to VDE 0435, part 303 Insulation voltage test: Surge voltage test: High frequency test: 2.5 KV / 50 Hz; 1 min. 5 KV / 1.2 / 50 µs, 0.5 Ws 2.5 KV / 1 MHz Immunity from disturbance by: electro-static discharge (ESD) acc. to VDE 0843 part 2 resp. IEC 801-2: severity level 4 test voltage 8 kV Electrical fast transient (Burst): test acc. to VDE 0843 part 4 resp. IEC 801-4 severity level 4 test voltage 4 kV burst duration 1 - 15 ms spike frequency 1; 2.5; 5 KHZ Radio interference suppression test as per DIN VDE 57871: limit value class B Radiated electromagnetic field test as per VDE 0843 part 3: field strength 10 V/m Mechanical tests Shock: Vibration: class 1, DIN IEC 41 B (CO) 38 class 1, DIN IEC 41 B (CO) 35 Enclosure, housing, installation Protection class: Material: Width, height, depths: Fastening type: Weight: Installation position: order designation: TB WIM1-H 07.97 E electronics: IP 40 signal and control terminals: IP 20 transformer connection terminals: IP 00 Macrolon 6030, self-extinguishing see dimensional drawings with screws 1.8 kg optional WIM1-H1-EL2 13 5.1 Tripping characteristics 100 100 10 10 t[s] tI>= t[s] 1.6 1.4 1.2 1.0 0.8 tI>= 1.6 1.3 1.0 0.8 0.6 0.5 0.4 0.3 1 0.6 0.5 0.4 1 0.3 0.2 0.2 0.3 0.1 0.1 0.1 1 2 3 4 5 6 7 8 9 10 20 1 2 I/IS 3 4 5 6 7 8 9 10 20 I/IS Fig. 4: Normal inverse Fig. 6: Very inverse 100 100 10 10 t[s] tI>= 1 1 0.1 0.1 0.01 t[s] 1.6 1.3 1.0 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0.01 1 2 3 4 5 6 7 8 9 10 20 1 Fig. 5: Extremely inverse 14 10 100 I/IN I/IS Fig. 7: Definite time TB WIM1-H 07.97 E Fig. 8: Dimensional drawing WIM1-H Installation depth: 110 mm Flag indicator WIZ-SZ2 TB WIM1-H 07.97 E 15 Flag indicator WIZ-SZ3 16 TB WIM1-H 07.97 E Woodward SEG GmbH & Co. KG Krefelder Weg 47 ⋅ D – 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) ⋅ D – 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet Homepage http://www.woodward-seg.com Documentation http://doc.seg-pp.com Sales Phone: +49 (0) 21 52 145 635 ⋅ Telefax: +49 (0) 21 52 145 354 e-mail: kemp.electronics@woodward.com Service Phone: +49 (0) 21 52 145 614 ⋅ Telefax: +49 (0) 21 52 145 455 e-mail: kemp.pd@woodward.com