BATTERY ENCLOSURE DESIGN - AS/NZS 4509 Applicable Standards Building Code of Australia AS/NZS 3000 Australian wiring rules AS 3011 Parts 1&2 Secondary batteries installed in buildings AS 2676 Parts 1&2 Installation and maintenance guide secondary batteries in a building AS 4086 Secondary batteries for use with stand-alone power systems AS/NZS 4509 Parts 1 & 2 Stand alone power systems AS 3947 Low Voltage Switch gear and fuse disconnectors AS 3439 Type Tested Switch gear assemblies Building Code of Australia V1 Section C2.12: Separation of equipment Batteries installed in buildings Class 2-9 applies to: Over 24V 10 Ah Requires FRL fire rating construction separation not less than 120/120/120. F – Structural Adequacy R - Integrity L - Insulation BCA V2 Class 1 &10 Buildings Detached home - no mention of secondary battery provisions Secondary batteries not an integral part of detached housing design except for remote power systems. BCA V1 identifies problems with secondary batteries in buildings Class 2 -9 battery back-up grid connected in detached houses is reasonable that the requirements of V1 should be considered for Class 1 buildings AS/NZS 3000 Wiring Rules Wiring rules for electrical installations and a requirement of AS/NZS 4509, AS 2676 and AS 4086 All electrical work associated with a battery installation must comply with these Standards AS3011 Secondary batteries installed in buildings Readily accessible Battery accommodation – lockable, well ventilated room, enclosure or restricted area Structurally adequate for the weight of the batteries DC switch boards should be located externally or segregated from the battery accommodation Batteries – no exposed live parts Battery cables – flexible, clearly identified and rated for voltage and fault current of battery Battery requirements Overcurrent protection – HRC fuse or circuit breaker in all unearthed battery cables of a fault current capacity equal to or exceeding the fault current of the battery Switch gear – rated for d.c. operation and where the fault level of the battery exceeds 20kA form 4 segregation is required Battery requirements Battery voltage – switches or links are required to limit the battery voltage to less than 120 V d.c. for maintenance. Unearthed batteries above 120 V require earth leakage detection Warning signs – required for fire, explosion, acid burn, battery voltage, battery capacity, start up and shut down procedures for the battery system Typical gel battery fault levels Sonnenschein A600 Solar to IEC 896-2 Type of cell Short Circuit Current OPzV 4/295 2215 Amps OPzV 6/625 4205 Amps OPzV 8/1130 6795 Amps OPzV 12/1960 10480 Amps OPzV 24/3920 20970 Amps • AGM fault current normally 50% higher than gel • If battery data is not available AS 2676 suggests: 35 times C3 to calculate the fault current • 35 x 750Ah @ 3hr rate = 22kA Typical flexible cable fault levels Cross Sectional Area Short Current (1 sec) 90°C 110°C 10mm² 1,430 A 1,320 A 25mm² 3,575 A 3,300 A 50mm² 7,150 A 6,600 A 70mm² 10,010 A 9,240 A 150mm² 21,450 A 19,800 A Battery cables must be resilient to sulphuric acid and protected against mechanical damage Battery overcurrent protective devices HRC fuses and circuit breakers rated for d.c. at the battery voltage fault current capacity = > fault level battery values clearly stated on the device or confirmation in writing obtained polarised d.c. circuit breakers should NEVER be used for this purpose some HRC fuses and circuit breakers rated for a.c. operation may not be suitable for d.c. applications Ventilation adequate ventilation requirement of any battery installation for the dispersion of hydrogen gas and cooling of the battery hydrogen levels must not exceed 2% by volume vents should be located at highest point of battery accommodation Calculations provided in AS 2676 & AS 4086 Ventilation Cooling the battery may be achieved by natural convection or forced ventilation. As a general rule every 10°C above rated battery temperature will halve the battery life. The battery manufacturer or AS 2676 should be consulted for the minimum air flow required to adequately cool the battery. Ventilation vented lead acid battery in equalise charge per kWh of battery capacity requires 0.5m³ per hour of airflow based on a convection air speed of 0.1m/sec will require a ventilation opening of 15cm² and half of this value for VRLA batteries AS 2676 and AS 4086 Standards refer to specific details for the installation and maintenance of secondary batteries in buildings and compliance is referred to in AS 3011 Standards should be read carefully and in conjunction with AS 3011 AS/NZS 4509.1 – Safety Batteries should not be housed near combustible or flammable materials, spark or heat sources Safety signs should be positioned in clear view of the batteries Battery enclosure must be designed to prevent entry by children, be vermin proofed and display the appropriate safety and warning signs including shut down procedures AS 3947 & AS 3439 AS 3947 and AS 3439 are references for appropriate switch gear to be used in battery installations AS 3947 refers to low voltage fuse switch disconnectors no reference for use in DC circuits? AS 3439 is the standard that will be used for installations in excess of 20kA requiring form 4 segregation Thank you for your indulgence and I hope this information may be of some use. Cheers, Warren Christensen - Powersafe Solar warren@powersafesolar.com.au