BROCHURE GDS DISCONNECTORS / pdf / 3 MB

advertisement
GDS
Pole Mounted Disconnectors
Up to 52kV
General Information
The switch for every application
The GDS range is a modern switch system with components for different isolation and switching applications in
overheadlines and substations. The system is characterised by a high degree of flexibility in order to meet
different national standards as well as to meet various customer specifications.
The base in the switch system is the phase element. To this component can different accessories be added for
having the requested disconnector or switch specification.
The switch can be installed in all different pole types, wood, concrete, steel poles or substation structures.
Different insulator alternatives
The GDS can be supplied with a wide range of different insulators in order to meet different isolation
philosofies, enviromental conditions and different standards.
The components of the switch system allow for different insulators to be used due to the design with parallel
insulators without affecting the base and contact components.
As standard can porcelain, outdoor epoxy resin and silicon rubber insulators be offerd. Beside the standard
material can also insulators according to customer specifications be used.
2
Technical characteristics
Charctersistic
Applicable standards
Value
IEC 62271-102, IEC 60265
Rated voltage
24kV
36kV
Impulse withstand voltage Phase-Earth
125kV
170kV
Impulse withstand voltage over isolating distance
145kV
195kV
Power frequency voltage 1 min wet, Phase-Earth
50kV
70kV
Power frequency voltage 1 min wet, over isolating
distance
60kV
80kV
Rated frequency
50-60Hz
50-60Hz
Rated current *)
630A
630A
Short time current
25kA
25kA
Duration of short time current
3 sec.
3 sec
Peak withstand current
62,5kA
62,5kA
5kA
3kA
Interupting capacity with the loadbreak heads of mainly
active load at rated voltage and cosφ=0,7
630A
400A
Interupting capacity with the loadbreak heads of mainly
active load at rated voltage and cosφ=0,15 capacitive
25A
16A
Interupting capacity with the loadbreak heads of mainly
active load at rated voltage and cosφ=0,15 reactive
16A
4A
400A
400A
Interupting capacity with breaking whip of mainly active
load at rated voltage and cosφ=0,7
25A
16A
Interupting capacity with breaking whip of cable and line
changing currents at rated voltage
15A
10A
Making capacity
Ringinterupting capacity with the loadbreak heads of
mainly active load at rated voltage and cosφ=0,3
reactive
Permissible ice load
Up to 20mm
Mechanical endurance
>2000 operations
-50oC to +50oC
Temperature range
Insulator material
Insulator creepage distance
Porcelain,Silicon rubber, Outddoor epoxy
resin
Various for different insulators
*) 630A is standard value. Alternative current ratings are 800A, 1250A and 2000A.
3
Phase elements
Article
No.**
Type
Insulator material
Rated
voltage
Rated current’
Weight, kg
2862003
GP2G
Outdoor epoxy resin
24kV
630A
30
A6737
GP2P
Porcelain
24kV
630A
33
A7513
GP2G4
Outdoor epoxy resin
36kV
630A
33
A7332
GP2S
Silicon rubber
36kV
630A
36
A7598
GDS36/52-6600
Porcelain
52kV
630A
60
A8268
GDSS26/52-6600
Silicon rubber
52kV
630A
54
*) 630A is the standard current rating. Other rated currents
available on request
**) Numbers are for sets of three units
GP2G
GP2S
GP2P
GDS36/52-6600
GP2G4
GDSS36/52-6600
4
Loadbreaking accessories
Breaking whip
Article No.*
Type
2862006
GBGK1
Rated
voltage
12-36kV
For Phase element type
Weight, kg
GP2G,GP2P,GP2S,GP2G4
2,5
GBGK1
Loadbreak head
Article No.*
Type
A6733
GLBD1
A6733-2
GLBD2
Rated
voltage
For Phase element type
Weight, kg
12-24kV
GP2G,GP2P,GP2S,GP2G4
12
36kV
GP2S, GP2G4, GDS36/52-6600, GDSS36/52-6600
12
GLBD
*) Set of three
5
Connecting accessories
Extension part
Article
No.**
Type
Insulator material
Rated
voltage
Rated
current
For Phase
element
type
Weight,
kg
2862011
GF2G
Outdoor epoxy resin
24kV
630A
GP2G
18
A6729-2
GF2P
Porcelain
24kV
630A
GP2P
20
A6729-5
GF2G4
Outdoor epoxy resin
36kV
630A
GP2G4
20
2862009
GF2S
Silicon rubber
36kV
630A
GP2S
19
GF2G
Extension Part for integrated surge arrester
Article
No.**
Type
Height of surge
arrester
Rated
current
For Phase
element type
Weight, kg
2862123
GF2PI*
630A
GP2G,GP2P,
GP2S
15
5821934
GF2PI1*
630A
GP2G,GP2P,
GP2S
15
**) Surge arrester is not included in articel number
GF2PI
6
Connecting accessories
Cable connection Part
Article
No.**
Rated
voltage
Rated
current
Outddor epoxy resin
24kV
630A
GP2G
22
GK2P
Porcelain
24kV
630A
GP2P
23
A6732-5
GK2G4
Outdoor epoxy resin
36kV
630A
GP2G4
23
2862014
GK2S
Silicon rubber
36kV
630A
GP2S
23
Type
Insulator material
2862016
GK2G
A6732-2
For Phase
element type
Weight, kg
GK2G
Cable connection Part for integrated surge arrester
Article
No.**
2862124
Type
Height of surge
arrester
GK2PI*
Rated
current
For Phase
element type
630A
GP2G,GP2P,
GP2S
Weight, kg
14
**) Surge arrester is not included in articel number
GK2PI
7
Fuse combinations
For RP33 type fuse tubes
Article
No.**
Rated
voltage
Rated
current
Outddor epoxy resin
24kV
80A
GP2G
21
GS3P
Porcelain
24kV
80A
GP2P
22
GS3S
Silicon rubber
24kV
80A
GP2S
22
Type
Insulator material
2862037
GS3G
A6741-2
2862035
For Phase
element type
Weight, kg
GS3G assembled on
GP2G
For fuses with dimensions according to DIN 43625
Article
No.**
Type
Insulator material
Rated
voltage
Rated
current
For Phase
element type
Weight, kg
2862071
GS5RG
Outddor epoxy resin
24kV
20A
GP2G
23
2862069
GS5RS
Silicon rubber
24kV
20A
GP2S
24
GS5Rs assembled on
GP2S
8
Connecting accessories
Hinge terminal bar and connection bars
Article No.
Type
Weight, kg
A6530*
GPK
3
A7997
CPAU
0,2
A7335
CSP
0,4
GPK
CPAU
CSP
Cable connection bar
Article No.
Type
A6847*
GCCB
Weight, kg
2,4
GCCB
Connecting clamps
Article
No.*
Type
Conductor
crossection
16-120mm2
Weight, kg
EKN1
2862056
GKG16
Al
0,8
2862057
GKG43
Al 50-240mm2
1
2862058
GKG44
Al 16-120mm2
Cu 10-95mm2
0,8
A3037
EKN1
Cu 10-120mm2
0,4
GKG
9
*) Article number is for set of three
Overvoltage protection accessories
Spark gaps
Article
No.**
Type
Placement
For Phase
element type
Weight, kg
5221927
GHG
Horizontal over
support insulator
GP2G, GP2P
0,5
A6951
GSG1
Horizontal with
crossarm bracket
GP2G,GP2P,
GP2S,GP2G4
10,5
GHG
GSG1
10
Overvoltage protection accessories
Surge arrester brackets
Article
No.*
Type
Placement
Weight, kg
2862121
GSAB
Attached to base of phaseelement or
accessorie
4
2862120
GVP
Together with crossarm clamp GRF
3
*) Article number is for set of three
GSAB
GSAB on cable connection part
GVP on crossarm clamp GRF
GSAB on phase element
GVP
11
Earthing accessories
Article
No.**
Type
Placement
For Phase element
type
Weight, kg
A7681
EB2
Fixed contact side of phase element
GP2G, GP2P
15
A7998
EB3
Fixed contact side of phase element
GP2S,GP2G4
16
A8062
EB4
Rocking contact side of phase element
GP2G, GP2P
15
A8034-1
GIL6
Mechanical interlock when earth blades
installed on both sides of phase element
-
2
A3500*)
JOPO
Earth bolt for connection of portable earthing
tool
All types
1
A6906
GJP
Earth contact for rocking insulator. When
disconnector opens, rocking insulator gets
earth connected automatically
GP2P,GP2G,GP2S
7
*) Article number is for set of 6 pcs
**) Article numbers include three earth blades with mechanical interlock. Associated equipment such as phase coupling tubes,
operating rods, operating handles must be ordered separately.
EB4
EB2
GJK
JOPO
12
Handoperating Mechanisms
GHM
Operating handles
Article No.
Type
Indication label
Weight
A6731
GHM
I-0
4
A6941
GHM2
ON-OFF
4
A6941-J
GHM2-J*
Earth On-Earth Off
4
A6941/AU
GHM/AU**
ON-OFF
4
A8215
GHMEI***
I-0
10
*) The GHM2-J are assembled for reversed operation direction
**) The A6941/AU has flexible copper leads between the pole
bracket and handle
***) Handoperating mechanism with electrical interlock. When
ordering indicate voltage for the locking magnet
GHMEI
Auxillary contacts and accessories
Article No.
Type
Comment
Weight
A7460
GHMSK
1NO+1NC contact
0,4
A8216
GHMDI
1NO+1NC x2
1
A7459
GHMIV*
Interlocking wheel
with one slot
0,2
A7459-1
GHMIV-1*
Interlocking wheel
with double slots
0,2
*) Castell interlocks are not included with the interlocking wheel, but can be supplied on request
GHMDI
GHMSK Installed on GHM
Installed on GHM
GHMIV
Installed on GHM
13
Handoperating Mechanisms
GHS1
Hookstick operating mechanism
Article No.
A7380
Type
GHS1
Weight
8
The GHS1 has a automatic resetting of the latchpin when
operated.
Accessories
Article No.
A8327
Type
GHSSL
Comment
Stickoperated
safety lock
attachment
Weight
0,5
14
Operating rods with accessories
Operating rods
Article No.
Description
Type
Length,mm
2862032
Complete rod set with upper and lower rod.Telescopically
adjustable length
GMR1
5800-7600
A7435
Complete rod set with upper and lower rod.Telescopically
adjustable
GMR2
7300-9100
A7352-1
Upper operating rod with fork for connection to the operating lever
GMR3
3250
A7352-2
Intermediate operating rod
GMR4
3250
A7352-3
Lower operating rod with telescopically length adjustable section
GMR5
2000-3800
Telescopical rod set with forks in both ends for connection to
hookstick operating mechanism
GMR6
2000-3800
Extension rod with coupling socket for operating rods. Including
one extra rod guide
GFR2
2000
GMR17
3500-5300
A7373
2862034
A8174
Complete operating rod for substation disconnectors
GMR6
Operating rod accessories
Article
No.
Type
Suitable for crossarm
Weight
A6734
GMK
Operating lever
1
A7635
GMK5
Operating lever for earth blades
1
A6742
GSI
Rod insulator up to 24kV
0,5
A7550
GSI2
Rod insulator up to 52kV
1,3
A7354
GRC
Rod coupling socket
0,3
A6743
GSS
Rod guide
0,7
A7944
GSS2
Rod guide
2,5
GRC
GSS
GMK
GMK5
GSS2
GSI
15
Pole assembling crossarms
Crossarms
Article No.
Type
Dimensions
Weight
5821911
GFLR1
80x80x2000
19kg
5821912
GFLR2
100x100x2000
25kg
A6611-21
GFLR21
100x100x2500
31kg
A8000
GFLR24
80x80x2400
22kg
Note: The GFLR24 Crossarm have no holes drilled
Crossarm assembling parts
For single-pole installation
Article No.
Type
Suitable for
crossarm
Weight
5821919
GFLRME
GFLR1&GFLR2
4
A8139-1
GFLRME-1
GFLR21
4
Article No.
Type
A7962
PBRC
Suitable for
crossarm
GFLR1,GFLR2,
GFLR21, GFLR24
Weight
7
Note: The PBRC pole bracket should not be used when
conductors are terminated to the crossarm.
For H-pole installation
Article
No.
5821920
Type
GFLRMP
Suitable for crossarm
GFLR1,GFLR2,
GFLR21
Weight
2
16
Crossarm assembling accessories
Crossarm clamps
Article No.
Type
Suitable for crossarms
Weight
2862091
GRF1
Box tubes and C-channels with max dimensions100x130mm (WxH)
0,6 kg
2862092
GRF2
Box tubes and C-channels with max dimensions130x180mm (WxH)
0,7 kg
A6915
GRF3
Angle channels with max dimensions 130x180 (WxH)
0,7 kg
17
Mast Head Loadbreaklswitch 24kV,630A
Handle operation, epoxy resin insulators
Component
Type
Qty
GP2G
1
GPK
1
Loadbreak head
GLBD1
1
Phase coupling tube
GMA16
1
Crossarm clamps
GRF1
3
Operating lever
GMK
1
Operating tube
GMR2
1
Assembling crossarm
GFLR1
1
Operating handle
GHM
1
Rod guide
GSS
2
Rod insulator
GSI
1
Phase element
Hinge Terminal bar
Ordering number for the complete unit
Remark
A7535
Crossarm assembling parts (to be ordered separately)
Component
Type
Qty
Remark
Single pole assembling parts
GFLRME
1
Article number 5821919
H-pole assembling parts
GFLRMP
1
Article number 5821920 (pole distance
2000mm c/c)
18
Mast Head installed disconnector 24kV,630A
With Hookstick operation, epoxy resin insulators
Component
Type
Qty
GP2G
1
GPK
1
Breaking whip
GBGK1
1
Phase coupling tube
GMA20
1
Crossarm clamps
GRF6
3
Operating lever
GMK
1
Pole bracket
PBRC
1
Operating tube
GMR16
1
Assembling crossarm
GMA24
1
Telescopical oåperating rod
GMR17
1
GHS1
1
-
1
Phase element
Hinge Terminal bar
Hookstick operating mechanism
Resin operating tube
Ordering number for the complete unit
Ordering number for the complete unit, but with
assembled loadbreakhaeds
Remark
Bolts for pole not included
Not supplied by Gevea
A8176
A8176/GLBD1
19
Vertical disconnector 24kV,630A
With earth blades, epoxy resin insulators
Component
Type
Qty
Phase element
GP2G
1
Earth blade set
EB4
1
Breaking whip
GBGK1
1
Phase coupling tube
GMA16
2
Crossarm clamps
GRF1
3
Operating lever
GMK
1
Operating lever
GMK5
1
Operating tube
GMR2
2
Rod coupling socket
GRC
2
Rod guide
GSS
4
Operating handle for disconnector
GHM
1
GHM2-J
1
Operating handle for earth blade
Ordering number for the complete unit excluding
assembling crossarm
Ordering number for the complete unit including
assembling crossarm and pole attacment accessories
Remark
Include mechanical interlock
A8336-1
A8336
20
Masthead installed disconnector 24kV,630A
assembled on square concrete pole 200x200mm
Ordering No.
Description
A8099
Complete unit including crossarm and
operating mechanism. With assembled
breaking whips
A8099/LB
Complete unit including crossarm and
operating mechanism. With assembled
loadbreak head
21
Masthead installed disconnector 24kV,630A
assembled in steel pole
Ordering No.
Description
A8184/GBGK1
Complete unit including crossarm and
operating mechanism. With assembled
breaking whips
A8184
Complete unit including crossarm and
operating mechanism. With assembled
loadbreak head
22
Substation installed loadbreakswitch 36kV,630A
With earthblades, epoxy resin insulators
Component
Type
Qty
Phase element
GP2G4
1
Extension part
GF2G4
1
Loadbreak head
GLBD1
1
Phase coupling tube
GMA25
2
Crossarm clamps
GRF1
6
Operating lever
GMK
1
For disconnector blade
Operating lever
GMK5
1
For eathblade
Operating tube
GMR17
2
Operating handle
GHM2
1
For disconnector blade
Operating handle
GHM2-J
1
For earthblade
EB4
1
Includes mechanical interlock
CPAU
6
Earth blade
Connection palm
Ordering number for the complete unit
Remark
A8137
23
AB GEVEA
Tlf. +46 11 184800
S-600 12 Norrköping
Fax. +46 11 182350
Sweden
E -mail. Info@gevea.se
www.gevea.se
24
Version 2010-02-10 Eng
Box 12043
Download