SAS-RV - STANDARD AUTOMATION SOFT

advertisement
Project
Contractor
Rep Firm
Engineering
SAS-RV - STANDARD AUTOMATION
SOFT-STARTER
3Ø, 200 ~ 600V, 1/2-75HP
Special Instructions:
FEATURES AND OPTIONS
• Soft start
• UL Type 3R Enclosed (4 and 4X available)
Full-Load Rated Contactor Bypass
Adjustable Current Limit, Initial Voltage, Start/Stop Time
SCR Over-Temperature detection
Shorted SCR detection
Across-the-line Start for Emergency Situations
Door mounted Hand/Off/Auto (HOA) keypad
• Combination versions include disconnect
• Automation compatible
Comprehensive inputs/outputs for building automation systems
Reduces installation costs
Increased energy savings
• Electronic motor protection
Molded case circuit breaker provides branch and short circuit
protection
High interrupting ratings for maximum electrical system
compatibility
No fuses required
Lockable handle for safety
Optional Features
• Surge Supressors
Class 10 electronic overload
Stall/Locked rotor
Phase unbalance
Cycle fault
Optional factory installed surge supressors (208-240V, or 480-600V)
• Universal power supply
Automatically detects voltage (200 to 600VAC)
Converts to 24V for control power
• Control inputs/outputs eliminate interposing
relays
One N.O dry input for auto run and one wet input for auto run
Status relay output
SAS-RV Submittal
Date
Project
Contractor
Rep Firm
Engineering
SIZING INFORMATION TABLE
UL/NEMA Type 3R/4/4X Outdoor Enclosure
Combination Standard Automation Soft Starter - 3-Phase, 200~575VAC
Includes Molded Case Circuit Breaker Disconnect
UL Three Phase HP
SAS-RV Part Number
SCIC KAIC @
Contactor
NEMA Size
Contactor
Type
Disconnect
Part-Number
208V
230V
460V
575V
200/230V
460V
600V
SAS[ ]-RV-9/J-G15
2
2
5
5
100
65
14
00
MRC-9B
UTE100ENU FTU 15A
SAS[ ]-RV-18/J-G20
3
3
7.5
10
100
65
14
0
MRC-18B
TD125HU FTU 125 20A
SAS[ ]-RV-22/J-G30
5
5
10
15
100
65
14
0+
MRC-22B
UTE100ENU FTU 30A
SAS[ ]-RV-32/J-G40
5
7.5
15
20
100
65
14
1
MRC-32A
UTE100ENU FTU 40A
SAS[ ]-RV-40/J-G50
7.5
10
20
25
100
65
14w
SAS[ ]-RV-40/J-G60
10
10
25
30
100
65
14
1+
MRC-40A
SAS[ ]-RV-50/J-G80
-
15
30
40
100
65
14
2
MRC-50LA TD125HU FTU 125 80A
MRC-65LA UTE100ENU FTU 100A
UTE100ENU FTU 50A
TD125HU FTU 125 60A
SAS[ ]-RV-65/J-G100
15
20
40
50
100
65
14
2+
SAS[ ]-RV-85/J-G125
20
25
50
60
100
65
14
3
MRC-85LA TD125HU FTU 125 125A
SAS[ ]-RV-100/J-G150
25
30
60
75
100
65
18
3+
MRC-100LA TS250HU FTU 250 150A
Standard Automation Soft Starter - 3-Phase, 200~575VAC
UL/NEMA Type 3R/4/4X Outdoor Enclosure
Standard
SCIC KAIC @
UL Three Phase HP
SAS-RV Part Number
High Fault*
SCIC KAIC @
Contactor
NEMA SIze
Contactor
Type
208V
230V
460V
575V
460V
600V
SAS[ ]-RV-9/J
2
2
5
7.5
5
100
65
14
00
MRC-9B
SAS[ ]-RV-18/J
5
5
10
15
5
100
65
14
0
MRC-18B
SAS[ ]-RV-32/J
7.5
10
20
25
5
100
65
14
1
MRC-32A
SAS[ ]-RV-40/J
10
10
30
30
5
100
65
14
1+
MRC-40A
SAS[ ]-RV-50/J
15
15
30
40
5
100
65
14
2
MRC-50LA
SAS[ ]-RV-100/J
25
30
60
75
10
100
65
18
3+
MRC-65LA
200/230V/460V 200/230V
*A molded case circuit breaker must be used in order to obtain the high fault SCIC KAIC ratings
SAS-RV Options
Options
Description
SAS-SRG240
208-240V surge supressor
SAS-SRG480
480-600V surge supressor
SAS-RV Submittal
Date
Project
Contractor
Rep Firm
Engineering
SPECIFICATION TABLE
SAS-RV Specification
Starter Type
SAS-RV - Standard Automation Starter - Reduced Voltage (Soft Starter)
200-600VAC, 3-Phase, 50/60Hz input, Reduced voltage starter
NEMA Type 3R Enclosedt
User Interface
Hand-Off-Auto
Door mounted Hand-Off-Auto keypad (water-tight-membrane)
Programming
Internal dials
Mode Indication
Integrated LEDs, Hand-Off-Auto-Run-Fault indication
Standard Control Operations
Voltage Atuo-Run Accepts 12-130VAC/DC. Applying voltage will send a run command to the starter when in Auto mode.
Inputs
Dry Contact Auto-Run Normally Open dry contact. When closed, the starter will be commanded to run when in Auto mode.
Normally Open relay contact.
Status Relay Status Relay will close when the motor draws a user defined percentage of the FLA setting.
Contact Ratings: 0.3A @ 125VAC, 1A @ 24VAC
Output
Starts 6/hour, 20 seconds max start time @ 400% FLA, 30 seconds max start time @ 300@ FLA
Overload Type Electronic, I2t trip curve
Operational
Power Fail Modes Restart in last mode (Hand/Off/Auto) with no delay (default)
Fault Reset Adjustable: Manual or Automatic
Environmental
Ambient Operating Temp -5° to 140° F (-20° to 60° C)
Ambient Storage Temp -5° to 185° F (-20° to 85° C)
Relative Humidity 5% to 95% non-condensing
Motor / Soft Starter Protection
Adjustment / Description
Overload Current Setting Range Differs per model
Default Setting
Per FLA
Overload Trip Class Class 10, Trip current = 115% of FLA setting
Overload Service Factor 1.15
10
1.15
Cycle Fault Always On,, Trips if contactor cycle rate exceeds 20 starts/minute
Current Phase Unbalance Always On, Trips @ 50% current phase unbalance
Locked Rotor / Stall Always On,, Trips within 0.5 seconds
Shorted SCR Always On, Trips upon detection of a shorted SCR or no motor
Open SCR Always On, Trips if no current is detected during startup or bypass
SCR Over-Temperature Always On, Trips if any SCR reaches 125oC
Across-The-Line Start On/Off, Allows the user to start the motor across-the-line
SAS-RV Submittal
On
50%
On
On
On
On
Off
Date
Project
Contractor
Rep Firm
Engineering
SUBMITTED EQUIPMENT SCHEDULE
QTY Tag
Part #
HP
Voltage Phase Enclosure
Part Number Anatomy
SAS3R-RV-32/J-G17
Contactor Size (9, 18, 32, etc.)
Disconnect Amperes Rating
Enclosure Rating (Type 1 or 3R)
SAS Submittal
Starter Type Nema Size
Date
Project
Contractor
Rep Firm
Engineering
COMPONENT SPECIFICATIONS
The following section details the various components’ sizing and ratings. To locate your component part
numbers for the EMS refence the sizing information table above.
MANUAL MOTOR STARTERS
MOLDED CASE CIRCUIT BREAKERS
MOLDED CASE CIRCUIT BREAKER SPECIFICATIONS
UTE Series
Frame size
Rated current ln
Number of poles
Rated operational voltage, Ue AC
Breaking Type
AC 50/60Hz
A
V
kA
120/240V
240V
480V
600V
Reference standard
Available breaker types
UTE100
UTE150
UTE100
15–100
3
480
UTE150
40–150
2, 3
600
ET
50
50
25
-
Mechanical life
Electrical life @600V AC
Weight 3-pole lbs (kg)
Basic dimension, WxHxD
Operations
Operations
NT
65
65
35
-
UL489
Fixed thermal, fixed magnetic, FTU
UL489
Fixed thermal, fixed magnetic, FTU
Adjustable-thermal, fixed-magnetic,
FMU
Adjustable-thermal, fixed-magnetic,
FMU
-
Accessories
ET
50
50
25
-
NT
65
65
35
-
Adjustable-thermal, Adjustablemagnetic (3 pole), ATU
AX - Auxiliary switch
AL - Alarm switch
SHT - Shunt trip
UVT - Undervoltage trip
EHU - Extended rotary handle
FH - Flange handle
AX - Auxiliary switch
AL - Alarm switch
SHT - Shunt trip
UVT - Undervoltage trip
EHU - Extended rotary handle
FH - Flange handle
PL, PHL - Locking devices
(removable, fixed)
PL, PHL - Locking devices
(removable, fixed)
MIT - Mechanical interlock device
MIT - Mechanical interlock device
5,000
5,000
1,000
1,000
12.57lbs (5.7kg)
4.19lbs (1.9kg)
2.01 x 5.12 x 3.44in (51 x 130 x 87.5mm) 8.5 x 16.26 x 6in (216x413x152.5mm)
SAS-RV Submittal
(Reference Only)
STOP
TIME
seconds
10
5
15
20
25
0.2
30
seconds
Contractor
Dry
Project
WIRING DIAGRAMS
H1
3
4
INITIAL
VOLTAGE
SAS-RV CONTROL WIRING
5
55
10
CURRENT
LIMIT
7
1
8
FLA (A)
START
TIME
9
Overload Setting
(Reference Only)
70
%
A2
24V
M Output to
contactor coil
SAS-RV
POWER WIRING
GATE DRIVE PCB
25
C-
A1
H4
40
6
12-250VAC/DC Input
Status
C+
Contactor
Coil
PCB Power
V1
Normally
Open Input
O2
O1
Relay
Output
Keypad
2
V2
Voltage Auto Run
Input
Engineering
Rep Firm
Date
D2
D1
Auto Run
Input
CAT-5
CAT-5
L1
L2
L3
250
175
325
100
10
20
25
5
2
MCCB
(Optional)
S1
Temp
Sensor S2
400
%
15
T1
T2
T3
L1
L2
L3
43 31
T1
T2
T3
44 32
T1
T2
T3
30
STOP
TIME
seconds
10
5
15
20
25
0.2
30
seconds
Dry
Input
D2
D1
Auto Run
Voltage Auto Run V2
Input
V1
Contactor
Coil
PCB Power
H1
Status
C+
L3
L2
L1
SOFT STARTER
24V
M Output to
A2
contactor coil
A1
C-
H4
H1
12-250VAC/DC Input
O2
O1
Relay
Output
Keypad
OL
Normally
Open Input
T3
T2
M
T1
H4
M
SAS-RV
POWER WIRING
L1
L2
3PH
L3
MCCB
(Optional)
STARTER ENCLOSURE DIMENSIONS
T1
T2
T3
NOTE: DASHED LINES INDICATE FIELD WIRING
UL Type 3R/4/4X Dimensions
W
OL
Starter Size
H1
NEMA Size 00–2, Combo
NEMA Size 00–1, Combo
L3
L2
NEMA Size 2+–3+, Combo
L1
SOFT STARTER
*All dimensions are in inches
T3
T2
H
W
D
22
15
10
H4
T1
32
L1
L2
L3
43 31
T1
T2
T3
44 32
M
15
10
H
T1
T2
T3
M
3PH
NOTE: DASHED LINES INDICATE FIELD WIRING
D
SAS-RV Submittal
Download