TSI NOVA 48/230

advertisement
TSI BRAVO 24/230
New Energy Effective DC/AC inverter
The TSI “Twin Sine Inverter” is the very latest generation of power modules that is creating a
revolution in the DC/AC inverter world.
TSI concept is a modular “hot swap” solution that eliminates all «single point of failure” such has
external static switches and the limit of the number of units in parallel is only linked with the bus
communication limitation (32 modules). It brings Scalability, Availability, Footprint, Efficiency. TSI is
SAFE for your load and your operation.

Efficiency 95% to compare to the global 88% efficiency of conventional solution TCO reduced
o Reduces Energy losses by 70%
o Positive Carbon Impact “Green solution”.

Elimination of external static switch and rectifier
o The static switch functionalities are integrated in each TSI module EPC
o The rectifier is needed only to charge the battery

Expandable solution and modular architecture.
o Up to 32 modules can be connected in parallel
o Real Hot Swap solution
o Simplified installation and commissioning

AC mains filtering
o Unity power factor at AC input
o Wide AC input range 150Vac to 275 Vac with stabilized AC ouput 230VAC. Ideal for “severe” AC
input environnement and critical AC loads
Specifications can change without notice. New data will be updated on our Web site:
http://www.cetamerica.com/
or
http://www.cet.be/
The present equipment is protected by several international patents, trademarks and copyrights.
Technical features
TSI BRAVO 24/230
GENERAL
DATASHEET 1.0
AC OUTPUT SPECIFICATIONS
EN 61000-4
EN 61000-5-2
EN 55022 (Class A)
IEC 60950
Forced
Doubled
240000 hrs
EMC (immunity)
EMC (emission)
Safety
Cooling
Isolation
MTBF
Efficiency (Typical)
Enhanced Power Conversion
On Line
94%
89%
Dielectric strength DC/AC
4300Vdc
230 V
200 – 240 V
2%
50 - 60 Hz
0.03 %
<1.5 %
Nominal voltage (AC) (*)
Voltage range (AC)
Voltage accuracy
Frequency
Frequency accuracy
Total harmonic distortion
(resistive load)
Load impact recovery time
Turn on delay
Nominal current
0.4 ms
20 s
8.7 A
Protected against reverse current
3 disconnection levels on ACout and DCin power ports
4 disconnection levels on ACin port
Crest factor at nominal power
RoHS 6
Connection I/O
Short circuit clear up capacity
2,8:1
With short circuit management and protection
Compliant
Terminal block
10 x In for 20msec
Protected against inversion of polarity
Self adaptive to wide operating conditions and
comprehensive table of troubleshooting codes
Available while Mains is available at AC input port
With magnitude control and management
Short circuit current after clear up capacity
2,1 In
Short circuit current after 15 sec
1,5 In
AC OUTPUT POWER
TRANSFER PERFORMANCE
Nominal Output power
1500 VA
Output power (resistive load)
1200 W
Short time overload capacity
150% 15 second
Permanent overload capacity
110%
Admissible
Full power rating from
load power factor
0 inductive to 0 capacitive
Internal temperature management and switch off
DC INPUT SPECIFICATIONS
Nominal voltage (DC)
24 V
Voltage range (DC)
Nominal current (at 24Vdc and 1200W
output)
Maximum input current (for 15 second)
Input voltage boundaries user selectable
19 – 32 V
56 A
84 A
AC INPUT SPECIFICATIONS
Nominal voltage (AC)
Voltage range (AC)
Brownout
Conformity range
Power Factor
Frequency range (selectable)
Synchronization range
230 V
150 – 300 V
150 to 185 V
1070 W @150V
Adjustable
>99%
50 - 60 Hz
47 – 53 Hz
57 – 63 Hz
Maximum voltage interruption
Total transient voltage duration (max)
ENVIRONMENT
Altitude above sea without derating
<1500m
Derating slope upper than 1500m
0.8% by 100m
-20 to 50 °C
Ambient temperature
-40 to 70 °C
Storage temperature
95% , non condensing
Relative humidity
SIGNALLING & SUPERVISION
Display
Alarms output
Supervision
Synoptic LED
Dry contacts on shelf
Use optional devices
WEIGHT & DIMENSIONS (MODULE)
Width (mm)
Depth (mm)
Height (mm)
Weight (kg)
Material (casing)
102 mm
Module: 435 Shelf: 515
2U
5 Kg
Coated steel
(*) Operation within lower voltage networks leads
to derating of power performances.
Specifications can change without notice. New data will be updated on our Web site:
http://www.cetamerica.com/
0s
0s
or
http://www.cet.be/
The present equipment is protected by several international patents, trademarks and copyrights.