division 28

advertisement
SECTION 280500 - COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
PART 1 -GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
2.
3.
Sleeves for raceways and cables.
Grout.
Common electronic safety and security installation requirements.
PART 2- PRODUCTS
2.1
SLEEVES FOR RACEWAYS AND CABLES
A.
Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.
B.
Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain
ends and integral waterstop, unless otherwise indicated.
C.
Sleeves for Rectangular Openings: Galvanized sheet steel.
1.
Minimum Metal Thickness:
a.
b.
2.2
For sleeve cross-section rectangle perimeter less than 50 inches and no side more than 16
inches, thickness shall be 0.052 inch.
For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches and 1 or
more sides equal to, or more than, 16 inches, thickness shall be 0.138 inch.
GROUT
A.
Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout,
noncorrosive, non-staining, mixed with water to consistency suitable for application and a 30-minute
working time.
PART 3 ·EXECUTION
3.1
COMMON REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY INSTALLATION
A.
Comply with NECA 1.
B.
Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wallmounting items.
C.
Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install
components and equipment to provide maximum possible headroom consistent with these requirements.
D.
Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both
electronic safety and security equipment and other nearby installations. Connect in such a way as to
facilitate future disconnecting with minimum interference with other items in the vicinity.
E.
Right of Way: Give to piping systems installed at a required slope.
3.2
SLEEVE INSTALLATION FOR ELECTRONIC SAFETY AND SECURITY PENETRATIONS
A.
Electronic safety and security penetrations occur when raceways, pathways, cables, wireways, or cable
trays penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.
B.
Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings
are used. Install sleeves during erection of slabs and walls.
c.
Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D.
Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless
openings compatible with firestop system used are fabricated during construction of floor or wall.
E.
Cut sleeves to length for mounting flush with both surfaces of walls.
F.
Seal space outside of sleeves with grout for penetrations of concrete and masonry
COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
PROJECT NO. 01329-01
280500- 1
1.
Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed surfaces
smooth; protect grout while curing.
G.
Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and
raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with
requirements in Division 07 Section "Joint Sealants.".
H.
Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at
raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with
firestop materials. Comply with requirements in Division 07 Section "Penetration Firestopping."
I.
Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch
annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.
3.3
SLEEVE-SEAL INSTALLATION
A.
Install to seal exterior wall penetrations.
B.
Use type and number of sealing elements recommended by manufacturer for raceway or cable material
and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in
annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause
sealing elements to expand and make watertight seal.
3.4
FIRESTOPPING
A.
Apply firestopping to penetrations of fire-rated floor and wall assemblies for electronic safety and security
installations to restore original fire-resistance rating of assembly. Firestopping materials and installation
requirements are specified in Division 07 Section "Penetration Firestopping."
END OF SECTION 280500
COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
PROJECT NO. 01329-01
280500-2
SECTION 280513- CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
PART 1 -GENERAL
1.1
SUMMARY
A.
Section Includes:
1.
Fire alarm wire and cable.
2.
Identification products.
QUALITY ASSURANCE
1.2
A.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a
qualified testing agency, and marked for intended location and application.
PART 2- PRODUCTS
2.1
PATHWAYS
A.
Support of Open Cabling: NRTL labeled for support of cabling, designed to prevent degradation of cable
performance and pinch points that could damage cable.
1.
2.
3.
B.
Support brackets with cable tie slots for fastening cable ties to brackets.
Lacing bars, spools, J-hooks, and 0-rings.
Straps and other devices.
Conduit and Boxes: Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical
Systems."
1.
Outlet boxes shall be no smaller than 2 inches wide, 3 inches high, and 2.5 inches deep.
FIRE ALARM WIRE AND CABLE
2.2
A.
Manufacturers: Subject to compliance with requirements available manufacturers offering products that
may be incorporated into the Work include, but are not limited to, the following:
1.
2.
3.
4.
5.
Comtran Corp.
Draka USA.
Genesis Cable Products; Honeywell International, Inc.
Rockbestos-Suprenant Cable Corporation.
West Penn Wire/COT; a division of Cable Design Technologies.
B.
General Wire and Cable Requirements: NRTL listed and labeled as complying with NFPA 70, Article 760.
C.
Signaling Line Circuits: Twisted, shielded pair, size as recommended by system manufacturer.
1.
D.
Circuit Integrity Cable: Twisted shielded pair, NFPA 70, Article 760, Classification Cl, for powerlimited fire alarm signal service Type FPL. NRTL listed and labeled as complying with UL 1424 and
UL 2196 for a 2-hour rating.
Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, color-coded insulation.
1.
2.
Low-Voltage Circuits: No. 16 AWG, minimum.
Line-Voltage Circuits: No. 12 AWG, minimum.
IDENTIFICATION PRODUCTS
2.3
A.
Manufacturers: Subject to compliance with requirements, available manufacturers offering products that
may be incorporated into the Work include, but are not limited to, the following:
1.
2.
3.
4.
Brady Corporation
HellermannTyton.
Kroy LLC.
Panduit Corp.
B.
Comply with UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and
inks used by label printers.
C.
Comply with requirements in Division 26 Section "Identification for Electrical Systems."
CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
PROJECT NO. 01329-01
280513- 1
2.4
SOURCE QUALITY CONTROL
A.
Testing Agency: Engage a qualified testing agency to evaluate cables.
B.
Factory sweep test coaxial cables at frequencies from 5 MHz to 1 GHz. Sweep test shall test the
frequency response, or attenuation over frequency, of a cable by generating a voltage whose frequency is
varied through the specified frequency range and graphing the results.
C.
Cable will be considered defective if it does not pass tests and inspections.
D.
Prepare test and inspection reports.
PART 3 -EXECUTION
INSTALLATION OF PATHWAYS
3.1
A.
Comply with TIA/EIA-569-A for pull-box sizing and length of conduit and number of bends between pull
points.
B.
Comply with requirements in Division 26 Section "Raceway and Boxes for Electrical Systems." for
installation of conduits and wireways.
C.
Install manufactured conduit sweeps and long-radius elbows whenever possible.
INSTALLATION OF CONDUCTORS AND CABLES
3.2
A.
Comply with NECA 1.
B.
General Requirements for Cabling:
1.
2.
3.
4.
5.
6.
Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at
indicated outlets or terminals.
Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from
cabinets, boxes, fittings, outlets, and terminals.
Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations
on bending radii. Install lacing bars and distribution spools.
Do not install bruised, kinked, scored, deformed, or abraded cable. Do not splice cable between
termination, tap, or junction points. Remove and discard cable if damaged during installation and
replace it with new cable.
Cold-Weather Installation: Bring cable to room temperature before dereeling. Heat lamps shall not
be used for heating.
Pulling Cable: Do not exceed manufacturer's instructions as to allowable pulling tension. Monitor
cable pull tensions.
FIRE ALARM WIRING INSTALLATION
3.3
A.
Comply with NECA 1 and NFPA 72.
B.
Wiring Method: Install wiring in metal raceway according to Division 26 Section "Raceway and Boxes for
Electrical Systems."
1.
Fire alarm circuits and equipment control wiring associated with the fire alarm system shall be
installed in a dedicated raceway system. This system shall not be used for any other wire or cable.
c.
Wiring Method:
1.
2.
3.
Cables and raceways used for fire alarm circuits, and equipment control wiring associated with the
fire alarm system, may not contain any other wire or cable,
Fire-Rated Cables: Use of 2-hour, fire-rated fire alarm cables, NFPA 70, Types Ml and Cl, is not
permitted.
Signaling Line Circuits: Power-limited fire alarm cables shall not be installed in the same cable or
raceway as signaling line circuits.
D.
Wiring within Enclosures: Separate power-limited and non-power-limited conductors as recommended by
manufacturer. Install conductors parallel with or at right angles to sides and back of the enclosure.
Bundle, lace, and train conductors to terminal points with no excess. Connect conductors that are
terminated, spliced, or interrupted in any enclosure associated with the fire alarm system to terminal
blocks. Mark each terminal according to the system's wiring diagrams. Make all connections with
approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors.
E.
Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets, or equipment
enclosures where circuit connections are made.
CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
PROJECT NO. 01329-01
280513- 2
F.
Color-Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use
one color-code for alarm circuit wiring and another for supervisory circuits. Color-code audible alarmindicating circuits differently from alarm-initiating circuits. Use different colors for visible alarm-indicating
devices. Paint fire alarm system junction boxes and covers red.
G.
Risers: Install at least two vertical cable risers to serve the fire alarm system. Separate risers in close
proximity to each other with a minimum one-hour-rated wall, so the loss of one riser does not prevent the
receipt or transmission of signals from other floors or zones.
H.
Wiring to Remote Alarm Transmitting Device: 1-inch conduit between the fire alarm control panel and the
transmitter. Install number of conductors and electrical supervision for connecting wiring as needed to suit
monitoring function.
3.4
FIRESTOPPING
A.
3.5
Comply with requirements in Division 07 Section "Penetration Firestopping."
GROUNDING
A.
3.6
For low-voltage wiring and cabling, comply with requirements in Division 26 Section "Grounding and
Bonding for Electrical Systems."
IDENTIFICATION
A.
3.7
Comply with requirements for identification specified in Division 26 Section "Identification for Electrical
Systems."
FIELD QUALITY CONTROL
A.
Tests and Inspections:
1.
2.
Visually inspect cable jacket materials for UL or third-party certification markings. Inspect cabling
terminations to confirm color-coding.
Visually inspect cable placement, cable termination, grounding, and bonding.
END OF SECTION 280513
CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY
PROJECT NO. 01329-01
280513- 3
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 283100- FIRE DETECTION AND ALARM
PART 1 -GENERAL
1.1
SUMMARY
A.
This Section includes fire alarm systems.
B.
Definitions:
1.
2.
3.
C.
System Description:
1.
D.
FACP: Fire alarm control panel.
LED: Light-emitting diode.
Definitions in NFPA 72 apply to fire alarm terms used in this Section.
Non-coded, addressable system; multiplexed signal transmission dedicated to fire alarm service
only with interface to existing fire alarm system.
Performance Requirements:
1.
2.
Comply with NFPA 72.
Fire alarm signal initiation shall be by one or more of the following devices:
a.
Smoke detectors.
3.
Fire alarm signal shall initiate the following actions:
a.
b.
c.
d.
e.
f.
g.
4.
System trouble signal initiation shall be by one or more of the following devices or actions:
a.
b.
c.
d.
e.
f.
g.
h.
i.
5.
Alarm notification appliances shall operate continuously.
Identify alarm at the FACP and remote annunciators.
Transmit an alarm signal to the remote alarm receiving station.
Release fire and smoke doors held open by magnetic door holders.
Switch heating, ventilating, and air-conditioning equipment controls to fire alarm mode.
Record events in the system memory.
Transmit an alarm signal to the elevator controllers for car recall.
Open circuits, shorts and grounds of wiring for initiating device, signaling line, and
notification-appliance circuits.
Opening, tampering, or removal of alarm-initiating and supervisory signal-initiating devices.
Loss of primary power at the FACP.
Ground or a single break in FACP internal circuits.
Abnormal ac voltage at the FACP.
A break in standby battery circuitry.
Failure of battery charging.
Abnormal position of any switch at the FACP or annunciator.
Fire-pump power failure, including a dead-phase or phase-reversal condition.
System Trouble and Supervisory Signal Actions: Ring trouble bell and annunciate at the FACP and
remote annunciators. Record event.
SUBMITTALS
1.2
A.
Product Data: For each type of product indicated.
B.
Shop Drawings:
1.
2.
System Operation Description: Detailed description for this Project, including method of operation
and supervision of each type of circuit and sequence of operations for manually and automatically
initiated system inputs and outputs. Manufacturer's standard descriptions for generic systems are
not acceptable.
Device Address List: Coordinate with final system programming.
C.
Field quality-control test reports.
D.
Operation and maintenance data.
QUALITY ASSURANCE
1.3
A.
Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units
required for this Project.
FIRE DETECTION AND ALARM
PROJECT NO. 01329-01
283100- 1
B.
Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100,
by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
PART 2- PRODUCTS
2.1
MANUFACTURERS
A.
Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that
may be incorporated into the Work include, but are not limited to, the following:
B.
Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1.
FACP and Equipment:
a.
SimplexGrinnell LP; a Tyco International Company- New devices to match existing.
2.
Wire and Cable:
a.
b.
c.
d.
2.2
Comtran Corporation.
Helix/HiTemp Cables, Inc.; a Draka USA Company.
Rockbestos-Suprenant Cable Corporation; a Marmon Group Company.
West Penn Wire/COT; a division of Cable Design Technologies.
EXISTING FIRE ALARM SYSTEM
A.
2.3
Compatibility with Existing Equipment: Fire alarm system and components shall operate as an extension
of an existing system.
FACP
A.
General Description:
1.
2.
Modular, power-limited design with electronic modules, UL 864 listed.
Addressable control circuits for operation of mechanical equipment.
B.
Elevator Controls: Heat detector operation shuts down elevator power by operating a shunt trip in a circuit
breaker feeding the elevator.
C.
Elevator Controls: Water-flow alarm connected to sprinkler in an elevator shaft and elevator machine
room shuts down elevators associated with the location without time delay.
1.
2.4
A field-mounted relay actuated by the fire detector or the FACP closes the shunt trip circuit and
operates building notification appliances and annunciator.
SYSTEM SMOKE DETECTORS
A.
General Description:
1.
2.
3.
UL 268 listed, operating at 24-V de, nominal.
Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or trouble)
to the FACP.
Multipurpose type, containing the following:
a.
4.
5.
6.
B.
Integral Addressable Module: Arranged to communicate detector status (normal, alarm, or
trouble) to the FACP.
Plug-in Arrangement: Detector and associated electronic components shall be mounted in a plugin module that connects to a fixed base. Provide terminals in the fixed base for connection of
building wiring.
Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore them to
normal operation.
Integral Visual-Indicating Light: LED type. Indicating detector has operated and power-on status.
Photoelectric Smoke Detectors:
1.
2.
Sensor: LED or infrared light source with matching silicon-cell receiver.
Detector Sensitivity: Between 2.5 and 3.5 percent/foot) smoke obscuration when tested according
to UL 268A.
WIRE AND CABLE
2.5
A.
Wire and cable for fire alarm systems shall be UL listed and labeled as complying with NFPA 70,
Article 760.
FIRE DETECTION AND ALARM
PROJECT NO. 01329-01
283100-2
B.
Signaling Line Circuits: Twisted, shielded pair, size as recommended by system manufacturer.
1.
C.
Circuit Integrity Cable: Twisted shielded pair, NFPA 70 Article 760, Classification Cl, for powerlimited fire alarm signal service. UL listed as Type FPL, and complying with requirements in
UL 1424 and in UL 2196 for a 2-hour rating.
Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, color-coded insulation.
1.
2.
Low-Voltage Circuits: No. 16 AWG, minimum.
Line-Voltage Circuits: No. 12 AWG, minimum.
PART 3- EXECUTION
3.1
EQUIPMENT INSTALLATION
A.
Connecting to Existing Equipment: Verify that existing fire alarm system is operational before making
changes or connections.
1.
2.
3.
3.2
Connect new equipment to the existing control panel in the existing part of the building.
Connect new equipment to the existing monitoring equipment at the Supervising Station.
Expand, modify, and supplement the existing equipment as necessary to extend the existing]
functions to the new points. New components shall be capable of merging with the existing
configuration without degrading the performance of either system.
WIRING INSTALLATION
A.
Install wiring according to the following:
1.
2.
B.
Wiring Method: Install wiring in metal raceway according to Division 26 Section "Raceway and Boxes for
Electrical Systems."
1.
C.
NECA 1.
TIAIEIA 568-A.
Fire alarm circuits and equipment control wiring associated with the fire alarm system shall be
installed in a dedicated raceway system. This system shall not be used for any other wire or cable.
Wiring Method:
1.
2.
3.
Cables and raceways used for fire alarm circuits, and equipment control wiring associated with the
fire alarm system, may not contain any other wire or cable.
Fire-Rated Cables: Use of 2-hour fire-rated fire alarm cables, NFPA 70 Types Ml and Cl, is not
permitted.
Signaling Line Circuits: Power-limited fire alarm cables shall not be installed in the same cable or
raceway as signaling line circuits.
D.
Wiring within Enclosures: Separate power-limited and non-power-limited conductors as recommended by
manufacturer. Install conductors parallel with or at right angles to sides and back of the enclosure.
Bundle, lace, and train conductors to terminal points with no excess. Connect conductors that are
terminated, spliced, or interrupted in any enclosure associated with the fire alarm system to terminal
blocks. Mark each terminal according to the system's wiring diagrams. Make all connections with
approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors.
E.
Cable Taps: Use numbered terminal strips in junction, pull, and outlet boxes, cabinets, or equipment
enclosures where circuit connections are made.
F.
Color-Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use
one color-code for alarm circuit wiring and a different color-code for supervisory circuits. Color-code
audible alarm-indicating circuits differently from alarm-initiating circuits. Use different colors for visible
alarm-indicating devices. Paint fire alarm system junction boxes and covers red.
IDENTIFICATION
3.3
A.
Identify system components, wiring, cabling, and terminals according to Division 26 Section "Identification
for Electrical Systems."
B.
Install instructions frame in a location visible from the FACP.
c.
Paint power-supply disconnect switch red and label "FIRE ALARM."
FIRE DETECTION AND ALARM
PROJECT NO. 01329-01
283100-3
3.4
FIELD QUALITY CONTROL
A.
Perform the following field tests and inspeGtions and prepare test reports:
1.
2.
3.
4.
Before requesting final approval of the installation, submit a written statement using the form for
Record of Completion shown in NFPA 72.
Perform each electrical test and visual and mechanical inspection listed in NFPA 72. Certify
compliance with test parameters.
Visual Inspection: Conduct a visual inspection before any testing. Use as-built drawings c;tnd
system documentation for the inspection. Identify improperly located, damaged, or nonfunctional
equipment, and correct before beginning tests.
Testing: Follow procedure and record results complying with requirements in NFPA 72.
a.
5.
Detectors that are outside their marked sensitivity range shall be replaced.
Test and Inspection Records:
Prepare according to NFPA 72, including demonstration of
sequences of operation by using the matrix-style form in Appendix A in NFPA 70.
END OF SECTION 283100
FIRE DETECTION AND ALARM
PROJECT NO. 01329-01
283100-4
Download