 Wiring Diagram: Elite RS Panels
Connections and specifications for all A and H series models
Man-1215
This wiring diagram describes models of the Kentec A and H Series Elite RS Panel. All models of the A Series Elite RS
Panel support Apollo loop protocol. All models of the H Series Elite RS Panel support Hochiki loop protocol. All models
provide 1 and 2 loop operation.
Reference Wiring Diagram Models for part numbers and descriptions of all fire control panels included in this document.
The operation of this product is intended for indoor use only.
Contents
Power Output Circuits .......................... 5 Contents
Limited Energy Circuits ........................ 5 Contents ................................................ 1 Supervised Circuits .............................. 6 Fascia View ........................................... 2 Signaling Line Circuits ......................... 6 Wire Gauge ............................................ 2 Notification Appliance Circuit .............. 6 Related Documentation ........................ 2 A Series Documents ...................................2 H Series Documents ...................................2 NAC Output Parameters ............................. 6 Maximum Current Ratings ......................... 7 Single and Dual Circuit Synchronization .. 7 Connection Diagram ............................. 3 Communication Circuits ....................... 7 A Series Models...........................................3 H Series Models...........................................3 Phone Line Connections (Optional models
If equipped) ................................................. 7 RS485 Serial Bus ........................................ 7 eNET Terminals ........................................... 8 Main Supply Circuit .............................. 4 Relay Circuits ........................................ 8 Elite RS Models ..................................... 3 Line Connection ..........................................4 Power Supply ..............................................4 Rechargeable Battery Circuit .....................5 Ground Fault Indications ..................... 5 24V OUT and AUX 24V .......................... 8 If You Need Help .................................... 8 File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 1 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
Fascia View
The figure below illustrates the fascia view of the Elite RS Panel:
Figure 1-1
Elite RS Fascia View
P2R
P2T
L2R
L2T
P1R
P1T
L1R
L1T
Wire Gauge
Connect 18 to 14 AWG wiring for all field terminations except the AC input. Connect 14 AWG wiring for line, neutral and
ground terminations of the AC input.
Related Documentation
The following documents shall be used to provide additional information for installing and operating A and H series
models of the Elite RS Panel:
A Series Documents
•
Elite RS Panel Installation Manual, A Series, Man-1200-, Rev. E01.XX
•
Operating Instructions, A Series, Man-1214, Rev. E06.XX
•
Door Label, A Series, K3534-00, Rev. E01.XX
H Series Documents
•
Elite RS Panel Installation Manual, H Series, K3529-00, Rev. E01.XX
•
Operating Instructions, H Series, Man-1214, Rev. E06.XX
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 2 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
•
Door Label, H Series, K3534-00, Rev. E01.XX
Connection Diagram
The figure below illustrates the connection diagram of the Elite RS and eLAN RS Panel:
Figure 1-2
Elite RS Connection Diagram
Earth Ground
NAC 1
10K EOL Resistor
S2030 TELCO 1
SLC 1
Zero-Ohm Resistor
S2026
SLC 2
Zero- Ohm Resistor
S2026
NAC 2
10K EOL Resistor
S2030
TELCO 2
24V OUT 24 VDC
Network
IN
AUX 24V
24 VDC
L L P P
1 1 1 1
T R T R
Comms
85
RS4
Network
OUT
Relays
L L P P
2 2 2 2
T R T R
38 39 40 41
1 2
E E
3 4 5 6
7
8 9 10
11 12 13 14
+
-
+
15 16 17 18
-
+
-
19 20 21 22
+
-
24V OUTAUX 24V NAC 1 NAC2
+
-
23 24 25
+
-
SLC 1 IN SLC 1 OUT
26 27 28
NC
C
NO
TROUBLE
29 30 31
NC
C
NO
FIRE
32 33 34 35
NC
C
NO
36 37
+
-
+
-
+
-
+
SUPERVISORYNET OUTNET IN COMMS
-
+
-
SLC2 OUT SLC2 IN
Elite RS Models
This section describes A and H Series models of the Elite RS Panel.
A Series Models
One loop A Series models include the No Communication K0850, the Non-Expandable, No Communication K0870, the
eNet Interface K0855, the Integrated Dialer K0856, the Non-Expandable, Integrated Dialer K0876 and the eNet Interface
& Integrated Dialer K0857.
Two loop A Series models include the No Communication with Loop Expansion Module K0860, the eNet Interface with
the Loop Expansion Module K0865, the Integrated Dialer with the Loop Expansion Module K0866 and the eNet
Interface & Integrated Dialer with the Loop Expansion Module K0867.
H Series Models
One loop Hochiki models include the No Communication K0810, the Non-Expandable, No Communication K0830, the
Integrated Dialer K0816, the Non-Expandable, Integrated Dialer K0836 and the eNet Interface & Integrated Dialer K0817.
Two loop Hochiki models include the No Communication with Loop Expansion Module K0820, the eNet Interface K0825,
the Integrated Dialer K0826 and the eNet Interface & Integrated Dialer K0827.
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 3 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
Main Supply Circuit
The main supply circuit includes specifications for the line connection and the power supply:
Line Connection
Terminals
Description
L
2.1 A max
230 VAC @ 50/60 Hz
1.1 A max
AC Neutral
Earth Ground
G
115 VAC @ 50/60 Hz
N
Current
AC Line
Voltage
Power Supply
Parameter
Description
Rating
115 VAC @ 250 VA
230 VAC @ 250 VA
AC Input Fuse
3 A, 250 VAC, Slow-Blow, 5 x 20 mm
Input (Supervised)
115 VAC 50/60 Hz or
230 VAC 50/60 Hz
Transfer Voltage
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
115 VAC transfer @ 75 VAC,
230 VAC transfer @ 160 VAC
Page 4 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
Rechargeable Battery Circuit
Parameter
Description
Standby-Battery Type
Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries
Standby-Battery Charging
Two standby batteries wired in series
Charge Current
Fast charge: 1.25 A
Trickle charge: 1.25 A (voltage limited)
Output Current
0 - 4 Amps
Standby-Operating Time
24 Hours
Battery Charge Voltage
27.6 VDC
Maximum Current Draw
From Batteries
4 Amps
Ground Fault Indications
A ground fault indication occurs when 30K Ohms or less exists between earth-ground and the following field terminals of
the Elite RS Panel:
•
24V OUT
•
AUX 24V
•
NAC 1and NAC 2
•
SLC1 and SLC2
•
NET
•
COMMS
Power Output Circuits
Special application outputs are provided on the NAC 1 and NAC 2 terminals of the Elite RS Panel:
Limited Energy Circuits
All circuits of the Elite RS Panel are power limited except AC input/output and battery.
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 5 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
Supervised Circuits
All circuits of the Elite RS Panel are supervised except relay terminals for TROUBLE, FIRE, SUPERVISORY and
TELCO.
Terminals of 24 V OUT and AUX 24 V are not supervised for open circuit conditions, but are supervised for ground faults
and short circuits.
Signaling Line Circuits
Authorized Signaling Line Circuits of this Fire Control Panel operate Apollo or Hochiki loop protocol.
Terminals
Description
SLC1 IN, SLC1 OUT
and SLC2 IN, SLC2 OUT
Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
Style 4.
Notification Appliance Circuit
The Elite RS Fire Control provides operation of Notification Appliance Circuits on the terminals of NAC 1 and NAC 2.
NAC Output Parameters
Parameter
Description
Fuse
Self-resetting 1.6 A electronic
Regulated Continuous Current
Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.
Regulated Pulsed Current:
Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.
Special Application
24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.
Supervision
EOL Device, VF1539-00
Synchronization
Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device VF1539-00 to the output of each
Synchronization Module installed.
The Elite-RS Panel provides internal device synchronization between the
outputs of NAC 1 and NAC 2 when operating NAC devices from Gentex,
Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.
NFPA Operation Type
Class B, Style Y
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 6 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
Maximum Current Ratings
The total sum of device loads in the NAC circuit must not exceed the maximum current specified for the Elite RS Panel
when operating in Continuous Regulated, Pulsed regulated or Special Application mode.
Reference NAC manufacturer data sheets for individual device loads and then compare the total sum to the maximum
current capability of the Elite RS Panel in regulated or special application mode.
Single and Dual Circuit Synchronization
NAC channels 1 and 2 of the Elite RS Panel provide single and dual circuit synchronization. Single circuit synchronization
provides a synchronized output on one of two NAC channels. Dual circuit synchronization provides a synchronized output
on both NAC channels.
Communication Circuits
Phone Line Connections (Optional models If equipped)
Terminal
Description
L1T
TELCO Line 1 Tip
L1R
TELCO Line 1 Ring
P1T
TELCO Phone 1 Tip
P1R
TELCO Phone 1 Ring
L2T
TELCO Line 2 Tip
L2R
TELCO Line 2 Ring
P2T
TELCO Phone 2 Tip
P2R
TELCO Phone 2 Ring
RS485 Serial Bus
Terminal
Rating
COMMS (+)
(+) Data 3.3 VDC @ 30 mA max
COMMS (-)
(-) Data
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 7 of 8
Wiring Diagram - Elite RS and eLAN RS Panels
eNET Terminals
Terminal
Rating
NET OUT (+)
(+) Data 3.3 VDC @ 30 mA max
NET OUT (-)
(-) Data
NET IN (+)
(+) Data 3.3 VDC @ 30 mA max
NET IN (-)
(-) Data
Relay Circuits
Parameter
Description
Operation
Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).
Current
1A maximum, volt free change over contact
Voltage
30 VDC max
Power Factor
1.0 PF
24V OUT and AUX 24V
Terminal
Description
24V OUT
Regulated 24 VDC @ 360 mA max
AUX 24V
Regulated 24 VDC @ 360 mA max
If You Need Help
If you need technical support contact Kentec at +44(0)1322 222121 or e‐mail techsupport@kentec.co.uk. Kentec technical support is available Monday through Friday, 8:00 AM to 5:00 PM Man-1245
File: S8485, Part Number: Man-1215
Revision E01.04, Date: May 2015
Page 8 of 8