Utilization of Line Surge Arresters in Transmission Lines Hetal Pranlal Instituto Superior Técnico, Av. Rovisco Pais 1, 1049-001 Lisboa, Portugal Abstract – Surges generated by lightning strokes can lead to failures in the supply of electricity, therefore they have brought several concerns in the design and operation of transmission lines due to the consequences of these for the various components. This dissertation presents the results of the work performed with the aim of studying the use of line surge arresters on transmission lines, using the simulation program ATPDraw. The physical phenomenon associated to lightning is explained, as well as the characterization of the discharge waveforms and the establishment of an equivalent electric model for its representation. The models of the components of the electrical system that are considered relevant to the study of the electromagnetic transients generated by the incidence of lighting strokes were also analysed. Assuming that the stroke hits the top of the transmission tower and considering discharge currents with different peak values and different characteristic times, several simulations were performed with the aim of studying the influence of ground resistance and the adjacent towers in the evolution of the voltages in the phase conductors and in the insulators, analyzing the backflashovers as well. It is also performed the study of the voltages in the insulators when line surge arresters are installed. Finally, the installation of line surge arresters in uniform and non-uniform lines was simulated, performing the analysis of the backflashovers that occurs and studying the strategy of the installation of this devices that leads to the reduction of backflashovers. It was found that the installation of line surge arresters in three phases of one of the circuits when uniform lines are considered leads to best results. In non-uniform lines, the installation of arresters in the transmission towers that have the highest grounding resistances and in the adjacent towers presents a significant reduction in backflashovers, eliminating backflashovers in one of the line circuit. Keywords: Lightning Stroke, Transmission Line, Backflashover, Grounding Resistance, Line Surge Arresters, ATPDraw I. Introduction A transmission line is designed to ensure an insulation level higher than the maximum instantaneous voltage. The insulation level is selected based on surges that are predictable to occur, whether their source are internal or external. Internal origin surges refer to those produced by switching or disconnecting operations. On other hand, the external surges are generally caused by lightning flashes. When a lightning strikes a component of the power system a current of high amplitude and short duration is injected to that power system, caused by the establishment of an electric arc through an ionized channel formed between a thundercloud and the point of impact, called arc of return. The current previously mentioned produces waves that travel through the conductor “paths” near the impact point, which is associated with characteristic impedance, called surge impedance. This phenomenon produces overvoltages which amplitude corresponds to the product of surge impedance with the instantaneous value of the discharge current. Lightning discharges are responsible for a significant number of interruptions in electricity supply, because when a lightning stroke hits a transmission tower, the overvoltage generated can lead to the backflashover of the insulators, leading to line operation failure. Therefore, lightning induced overvoltages assume a high importance for dimensioning the insulation of high voltage electrical installations. To minimize the effects of discharges, ground wires are strategically placed in the transmission lines. The ground wires are normally connected to earth at all towers creating a preferential path for the discharge of the lightning current. However, the existence of this wires do not exclude the possibility of direct discharges on the phase conductors, by shielding failure, or the appearance of electric arcs at insulator strings, causing problems in the continuity of service. The use of line surge arresters on transmission lines to prevent backflashovers of the insulator strings has been studied over the years. The arresters prevent backflashovers by maintaining the voltage at the insulators below their maximum capability. In general, for lines without ground wires, the placement of line surge arresters in all towers is an alternative. For lines protected with ground wires, the arresters are installed in remote locations where maintenance is difficult or where there is a high soil resistivity (sand, rocky terrain). Currently, the surge arresters are used in transmission lines to improve reliability of service. However, due to economic reasons, it is not possible to equip all towers with these devices. Therefore, it is necessary to study the best strategy for placement of surge arresters to ensure a certain level of protection against lightning. Thus, it is primordial the understanding of the phenomenon that are associated with backflashover, as well as with their installation. Since, in case of a double circuit line, it is not desirable to have both circuits operation failure, the surge arresters can have a very important role in preventing this situation, because a proper installation of arresters can lead to a significant reduction of backflashovers, eliminating them in one of the line circuits. 1 In this work is pretended to understand the phenomena that are associated to backflashover, as well as the influence of line surge arrester utilization. For the simulation performed in the study it was used the application ATP, which have a graphic processor, ATPDraw. II. Line Surge Arresters A. State of Art The literature suggests that the line surge arresters should be installed at the towers which have higher ground resistances [2], as well as at towers that are installed at local peaks or high altitude locations [3]. In [4] is proposed to install line surge arresters at towers that combine high exposure to lightning with high ground resistance. According to [2], depending on the value of the ground resistance, the arresters should be installed in more than one phase, as it is shown in Table I. It is also proposed that the configuration of the arresters placement to be uniform along the section of the line, even if the ground resistance is different in some towers. Table I Line Surge Arresters Placement Configuration [2] Ground Resistance, RT (Ω) Surge Arresters Placement RT ≤ 10 No arresters 10 < RT ≤ 20 One phase 20 < RT ≤ 40 Two phases RT > 40 Three phases Currently in Portugal there are two transmission lines which are protected with line surge arresters, Sines-Tunes and Recarei-Canelas. Arresters are installed in five towers of Sines-Tunes line. Despite having studies done, there isn’t a large utilization of these devices. B. ZnO Surge Arresters The line surge arrester should act as an open circuit at power system frequency, limit overvoltages below the insulation level of the transmission line and return the system to its normal operating mode so that transients overvoltages are suppressed. Consequently, a surge arrester should have a very high resistance when the system is in normal operating mode and a relatively low resistance during transient overvoltages. Based on this it can be concluded that its V-I characteristic must be non-linear. These devices are essentially made of one or more sparks connected in series with one or more non-linear resistors. Usually there are incorporated resistant and capacitive voltage dividers to ensure a proper distribution of the voltage applied to the various elements. In normal operation, the sparks inserted between the non-linear resistors are not disrupted and a reduced intensity current determined by the voltage dividers go through the surge arrester connected between the phase conductor and earth. The modern surge arresters use metal oxide varistors (MO) with a highly non-linear V-I characteristic. The varistors are constituted by a powder of zinc oxide (ZnO) and traces of other metals oxides united in a ceramic mold. Its characteristics do not require the use of sparks. Thus, the electrical behaviour of these devices is only determined by the blocks of MO. There are two types of zinc oxide arresters (ZnO) for surge protection. The first type does not include sparks in its constitution, which is directly connected to the phase conductor. This type of surge arrester has the advantage of not having delays in absorbing the overvoltage energy. The other type presents sparks in its composition, which are inserted between the arrester and the phase conductor, also functioning as an insulator between them. The spark arresters only operate when lightning strikes the transmission line or tower, being out of service in every other situation, including switching overvoltages. This means that there is a current going through the arrester during a very small period of time, corresponding to the discharge time. This type of surge arresters has a bigger lifetime and a more reliable operation then the other type. The non-linear characteristic of the surge arrester is formed by exponential segments and each segment can be approximated by equation (1). (1) Where i and v represents the surge current and voltage, respectively, and p, q and Vref are the component constants. III. Study Data and Modelling A. Study Data Base Case In this work is performed a study of the 150 kV SinesTunes line, which is a double circuit line with the configuration presented in Fig. 1, called cross configuration. Fig. 1 - Sines-Tunes 150 kV line phases configuration - cross configuration. The grounding resistances of the line under study are represented in Fig. 2. 2 Table II Distribution parameters [1] Grounding Resistance (Ω) 400 350 Parameter 300 250 200 150 100 50 1 10 19 28 37 46 55 64 73 82 91 100 109 118 127 136 145 154 163 172 181 190 199 208 217 226 235 244 253 0 Tower Fig. 2 - Sines-Tunes line grounding resistances. (2) √2 Where M corresponds to the average value and β to the logarithmic standard deviation. The expression of the probability distribution is given by the equation (3). / (3) √2 To calculate the distribution parameters that allow obtaining the discharge current, that are the peak value, rise time, half-wave time and growth rate, it is necessary to transform the log-normal distribution in a normal distribution, using a change of variables. 1 / √2 Being the change of variables given by (5). ln / β Peak Value 61 kA 1.33 kA Rise Time 4.7 µs 0.49 µs Growth Rate 29.4 µs 0.55 µs Half-wave Time 30.2 µs 0.93 µs The characteristic parameters of the discharge currents obtained for 80, 60, 40, 20, 10 e 5% probability of being exceed is presented in Table III. Table III Based on the figure presented it was decided to study one section of the line that has very high grounding resistance: towers 69-81. The next step consists in determining the discharge currents to carry out the studies. [1] proposes a concave waveform for the discharge current representation, which parameters follows a log-normal distribution whose probability density is given by equation (2). / 1 1 M (4) (5) Setting the value of P(X’) the calculation of X’ is done by using the inverse function of error, being implemented using a mathematical program (MATLAB), and then obtain X. The parameters of the probability distribution to calculate the parameters that characterize the discharge current are presented in Table II, calculated according [1]. Discharge currents parameters Probability Peak (%) Value Rise Time Growth Rate Halfwave Time 80 20.0129 2.0483 12.5809 13.7716 60 28.5679 3.1706 19.9236 23.8425 40 38.8160 4.6192 29.6031 38.2527 20 55.4088 7.1499 46.8805 66.2261 10 72.3052 9.9127 66.1152 99.8361 5 90.0796 12.9828 87.8220 140.119 In the simulations only line sections are represented. The remaining line is implemented using infinite length line connected to power sources intended to impose the line voltage. The most significant parameter of these sources is the voltage angle, because it influences the value of the voltage that will be at the insulator strings, which is given by (6). (6) Based on the above equation, the worst case corresponds to the lower phases because they have the lower coupling factor with the ground wire. It is considered that de R’S’T’ circuit has the worst case scenario. The values of the voltages angles in both circuits at the moment of the discharge are presented in the Table IV. Table IV Voltages angle at the moment of discharge. Phase Voltage Angle S -60º R 60º T 180º T’ 180º R’ 60º S’ -60º The study cases of the 150 kV Sines-Tunes line presented in this work are represented in Table V. 3 Table V Table VII Case studied for non-uniform line Cases studied for uniform line Case Ipeak (kA) 1 Tower Hit by Lightning 39 74 Case Ipeak (kA) Grounding Phases that Resistance (Ω) Flashover 1 39 80 T, T’ 2 55 80 T, T', S' Uniform Line The same discharge currents presented in Table III are used to perform the study of a uniform line. However, it is necessary to establish a criterion for the selection of the grounding resistances to be simulated. Fig. 3 shows the probability of the grounding resistance of Sines-Tines line being exceeded. 90 Lightning Current Once the characteristic parameters of the discharge current are calculated, it is possible to reconstruct that current wave in ATPDraw, by using a current source with a parallel resistance, which has the purpose to represent the lightning path impedance as shown is Fig. 4. This resistance value is taken to be 400 Ω. 80 70 60 50 40 30 20 10 Fig. 4 - Lightning stoke model used in ATPDraw. 0 1 14 27 40 53 66 79 92 105 118 131 144 157 170 183 196 209 222 235 248 261 274 287 300 313 326 339 352 Prtobability of the value be exceeded (%) 100 B. Modelling Grounding Resistance (Ω) Transmission Line Fig. 3 - Probability of the value of the grounding resistance being exceeded. The criterion established for selecting the grounding resistance is based in the previous figure. The resistances that have 30, 20, 15, 10, 5, 2 e 1 % probability of being exceeded were selected, presented in Table VI. For this simulation it was considered that the section of the line has 17 towers, 16 spans of 446.9 meters each, connected to 20 km lines at its end that subsequently connects to voltage sources of 150 kV with the angles described in Table IV. Table VI Grounding resistances values used for uniform line study Probability (%) Grounding Resistance (Ω) 30 22 20 31 15 40 10 54 5 80 2 136 1 338 The cases that were studied in this work are presented in Table VII. The line parameters vary with frequency and ATPDraw offers possibility to use various frequency dependent line models to represent overhead transmission lines. In this study JMarti model was selected. The ground wire is represented as a phase wire connected to the top of the towers. Tower For simplification purposes and since the study of the different tower models are not the aim of the study, the towers were represented by short-circuits. Grounding Resistance The grounding resistance is represented by a linear resistance. Insulators The insulator strings were represented by a high value resistance in parallel with a low value resistance that is connected in series with a voltage controlled switch, which only conduct when the voltage across its terminals exceeds the value presented in equation (7). 4 · (7) Where ld corresponds to the insulators electrodes, E0 to the electric field, which value is taken to be 750 V/km and V(t) to the instantaneous voltage value. Fig. 5 presents the model used in ATPDraw. 900 [kV] T 680 S 460 240 R 20 -200 Fig. 5 - Insulator string model used in ATPDraw. 0 10 20 30 (f ile contornamentoinv erso.pl4; x-v ar t) v :TOP -S v :TOP 40 -R v :TOP 50 [us] 60 -T Fig. 7 - Insulators voltages of RST circuit in the tower hit by the discharge. Line Surge Arresters The selection of the appropriate line surge arrester is done based on the arrester Maximum Continuous Operating Voltage (MCOV), which is calculated by the equation (7). 1.1 (1) √3 Where Vm represents the line voltage level. The multiplicative factor derives from the fact that during the line operation the voltage of the line can get a value 10% above of the line voltage level. The surge arresters are represented in ATPDraw by a MOV block, Fig. 6, modelled by a current dependent exponential resistance, which follows equation (1). 12 [kA] 10 T 8 6 4 R 2 0 S -2 -4 0 10 20 30 (f ile contornamentoinv erso.pl4; x-v ar t) c:TOP -S c:TOP 40 -R c:TOP 50 [us] 60 -T Fig. 8 - Insulators currents of RST circuit in the tower hit by the discharge. 900 [kV] S’ 680 Fig. 6 - Surge arrester model used in ATPDraw. 460 For the simulations, ABB PEXLIM R surge arresters were used, which characteristic is presented in Table VIII. Table VIII R’ 240 T’ 20 Surge arrester characteristic Rated Voltage, Ur (kV) 120 TOV Max. Residual Voltage (kV) MCOV (kV) with Current Wave 8/20 µs (kV) for 1 sec 98 138 5kA 10kA 20kA 40kA 294 311 349 398 -200 0 10 20 (f ile contornamentoinv erso.pl4; x-v ar t) v :TOP 30 -T' v :TOP -R' 40 50 [us] 60 v :TOP -S' Fig. 9 – Insulators voltages of R'S'T' circuit in the tower hit by the discharge. 11 [kA] 9 IV. Study of Backflashovers in Uniform Line without Line 7 S’ 5 Surge Arresters 3 T’ 1 In Fig. 7 to Fig. 10 are represented the voltages and currents in the insulators for both RST and R’S’T’ circuits for the simulation of the case from Table VII. -1 R’ -3 0 10 20 (f ile contornamentoinv erso.pl4; x-v ar t) c:TOP -T' 30 c:TOP -R' 40 50 [us] 60 c:TOP -S' Fig. 10 – Insulators currents of R'S'T' circuit in the tower hit by the discharge. When a lightning hits a tower, its potential increases because a big portion of discharge current is conduct by the grounding resistance of that tower, being the remaining 5 current transmitted by the ground wires to the adjacent towers and subsequent spans. After the discharge incidence, the voltage of the insulators increases as a result of the tower and the phase’s potential increases (because of ground wire coupling). When backflashover occurs the voltage across the insulators decreases to approximately zero and a current circulates across the air gap, as shown in Fig. 8 and Fig. 10. A phase flashover implies the decrease of the tower potential and the increase of the phase’s potential. Tower potential decreases because a new path of conduction is inserted, the phase wires. Phase conductor’s potential increase as result of phases coupling. It is observed in the presented waves that the phases that don’t flashover have a decrease in their insulator voltages when other phase flashover. This occurs because the tower potential decrease is bigger than the phase’s potential increase. If the discharge current has not reached its peak, the tower and phases potential increases again, as well as the voltage across the insulators, as shown in Fig. 7 and Fig. 9. After the backflashover, the potential of phase is approximately equal to the tower potential. In the figures presented it is possible to visualize that the waves have two oscillations with different period, one with 3 µs and other with 12 µs. The first oscillation is justified by the reflections of the adjacent towers (the span has 446.9 meters, corresponding to a propagation time of 1.5 µs) as a result of the portion of the current that is transmitted by the ground wire to those towers. The second oscillation is explained by the flashovers that occur in neighbouring towers. To understand this phenomenon it is presented Table IX. This table represent the flashover in the tower and in the phase. The shaded column represents the tower hit by the lightning is the phenomenon that is observed in Fig. 10, at 25 µs the current of the insulators in phase T’ increases, that corresponds the flashover in the tower N-4, which occurs at 19 µs, plus the propagation time of the 4 spans. After 12 µs the current increases again, being this increase smaller. This phenomenon is observed because the reflection travels again through the phase conductor to the phase that has suffered a flashover and comes back. Since the flashover in the phases T and T’ occurs in the immediately adjacent towers, the travel time is much lower, so it is only observed the current growth, followed by its decrease. To a better understanding of the neighboring towers effect the values of the maximum potential of the tower that is hit by the lightning are presented in Table X. Table X Maximum voltage values in the tower hit by the discharge in one tower case and in uniform line case Maximum Voltage in the Tower Hit by the Discharge Ipeak (kA) (MV) One Tower Maximum Voltage in the Tower Hit by Uniform Line the Discharge Reduction (%) 20 1.02 1.01 0.98 29 1.26 1.24 1.59 39 1.66 1.47 11.4 55 2.28 1.99 12.7 72 2.84 2.38 16.2 90 3.50 2.80 20.0 In Table X it is possible to observe that the tower potential decrease, which is explained by the new conducting path provided by the ground wire and the reflections of the adjacent towers, which does not exist in the situation of only one tower. Table IX Flashovers in uniform line for case 2 V. Study of Backflashovers in Uniform Line with Line Case 2 ‐ R0 = 80 Ω, Ipico = 55 kA F a s e N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N Surge Arresters N N N N N N N N - - - - - - - - 1 2 3 4 5 6 7 8 S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - T - - - - - - - - - - T’ - - - - - - - - - - - R’ - - - - - - - - - - S’ - - - - - - - - - - - - - - - - - - - - - To understand the effect that surge arresters causes the Fig. 11 is presented. It illustrates the voltage across the phase S’ insulator when case 2 is simulated, with and without arresters installed. In Fig. 12 the current that circulates through the arresters in case 2 when these devices are installed in all phases of the circuit R’S’T’ are represented. As it is possible to observe in the table above, in T’ phase the flashover occurs in the tower that is hit by the lightning, N, and in towers that are 4 spans apart, N-4. The flashover of the same phase in other towers triggers a reflection that propagates through the phase wire. When that reflection reaches the tower N, the current suffers a big increase. That 6 900 Table XII [kV] Flashovers in uniform line for case 2, no arresters 680 With Arresters Case 2 ‐ R0 = 80 Ω, Ipico = 55 kA 460 No Arresters Without Arresters F 240 a s 20 e -200 0.00 0.02 (f ile Descarregadores.pl4; x-v ar t) v :TOP 0.04 -S' 0.06 0.08 [ms] 0.10 v :TOP3 -S'3 Fig. 11 - Phase S' insulator voltage with and without arresters for case 2. 4000 [A] 3500 N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N N N N N N N N - - - - - - - N - 1 2 3 4 5 6 7 8 S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - T - - - - - - - - - - T’ - - - - - - - - - - - - R’ - - - - - - - - - - - - - S’ - - - - - - - - - - - N - - - - - - - 3000 Table XIII 2500 Flashovers in uniform line for case 2, arresters in phase S’ S’ 2000 1500 T’ Case 2 ‐ R0 = 80 Ω, Ipico = 55 kA 1000 500 0 0.00 Arrester in phase S’ R’ 0.02 F 0.04 (f ile Descarregadores.pl4; x-v ar t) c:TOP3 -PHAC 0.06 c:TOP3 -PHAA 0.08 [ms] 0.10 c:TOP3 -PHAB Fig. 12 - Currents in arresters installed in all phases of R'S'T' circuit for case 2. For the study of the backflashovers in uniform line with installation of surge arresters the case 1 presented in Table VII was simulated, for the configurations of arresters placement given in Table XI. The arresters are installed in every tower simulated, only in the circuit R’S’T’, because this circuit has the best case scenario regarding the angles of the line voltage. a s e N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N N N N N N N N - - - - - - - - 1 2 3 4 5 6 7 8 S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - - - - - - - - - - - T - - - - T’ - - - - R’ - - - - - S’ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - N Table XIV Flashovers in uniform line for case 2, arresters in phase S’ and R’ Table XI Surge arresters placement configurations simulated Case 2 ‐ R0 = 80 Ω, Ipico = 55 kA Configuration 1 No arresters Configuration 2 Arrester in phase S’ F Configuration 3 Arresters in phase S’ and R’ a Configuration 4 Arresters in phase S’, R’ and T’ Arresters in phase S’ and R’ s e Table XII to Table XV are presented for a better visualization of the results. The shaded column represents the tower hit by the lightning and the shaded lines correspond to the phases that have arresters installed. N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N N N N N N N N - - - - - - - - 1 2 3 4 5 6 7 8 S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - T - - - - - - - - - - T’ - - - - - - R’ - - - - - S’ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7 Table XV flashover caused by the potential of the phase being bigger than the potential of the tower and, in this case, it can’t be called backflashover. These phenomena are represented in Fig. 13 and Fig. 14, where the first correspond to backflashover and the second to the other type of flashover. Flashovers in uniform line for case 2, arresters in phase S’, R’ and T’ Case 2 ‐ R0 = 80 Ω, Ipico = 55 kA Arresters in phase S’, R’ ans T’ F a s e 1.6 N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N N N N N N N N *10 6 - - - - - - - - 1.3 1 2 3 4 5 6 7 8 N S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - T - - - - - - - - - - T’ - - - - - - - - - - - - - - - - - R’ - - - - - - - - - - - - - - - - - S’ - - - - - - - - - - - - - - - - - - - Tower 1.0 0.7 0.4 0.1 Phase -0.2 0 10 20 (f ile Unif ormeResis80.pl4; x-v ar t) v :TOP_N 30 40 50 *10 -6 60 v :T_N Fig. 13 - Tower and phase (T') potential in the tower N for the simulation of the case 2 without arresters. Based on the tables above, it is possible to conclude that the installation of surge arresters improve the line performance by reducing the flashovers. When these devices are installed in more than one phase it is possible to conclude that the improvement is bigger. It is observed that the flashover in some phases do not occur in the towers immediately adjacent to the tower hit by the lightning. Due to the case 2 complexity, it was simulated case 1 and the results are presented in Table XVI. 1.2 *10 6 1.0 Tower 0.8 0.6 0.4 0.2 Table XVI 0.0 Flashovers in uniform line for case 1, no arresters Phase -0.2 0 10 20 (f ile Unif ormeResis80.pl4; x-v ar t) v :TOP_N2 30 40 50 *10 -6 60 v :T_N2C Fig. 14 - Tower and phase (T') potential in the tower N-2 for the simulation of the case 2 without arresters. Case 1 ‐ R0 = 80 Ω, Ipico = 39 kA No Arresters F a s e N N N N N N N N - - - - - - - - 8 7 6 5 4 3 2 1 N N N N N N N N N - - - - - - - - 1 2 3 4 5 6 7 8 S - - - - - - - - - - - - - - - - - R - - - - - - - - - - - - - - - - - T - - - - - - - - - - - - - - T’ - - - - - - - - - - - - - - - - R’ - - - - - - - - - - - - - - - - - S’ - - - - - - - - - - - - - - - - - The phenomenon mentioned happens because when a lightning hits a tower, the potential of every tower increase, as well as of the phases. When a phase flashover, the potential of that phase increases or decreases so it can equate the potential of the tower. As we move away from the tower where the flashover has occurred, the potential of the phase maintains practically its value, but the tower potential decreases. Therefore, in some cases, the potential of the phase is bigger than the potential of the tower and it causes the flashover of the insulators. Consequently, it is concluded that exists two types of flashovers in uniform line: flashover caused by the potential of the tower being bigger than the potential of the phase, backflashover, or VI. Study of Backflashovers in Non-uniform Line In this section is wanted to study section of Sines-Tunes line, considering it non-uniform, ie, considering the nonuniformity of the grounding resistances along the line. The study was performed in the towers 69-81, for the case 1. The surge arresters in this study are installed in all phases of R’S’T’ circuit, but it is analysed de difference of installing those devices only in the towers with high grounding resistance and also in the adjacent towers. Table XVII to Table XIX are presented as results, where the shaded columns correspond to the tower where the lightning hits and shaded towers represents where the arresters are installed. 8 Table XVII Flashovers in non-uniform line (tower 69-81) without arresters Case 1 – Ipeak = 55 kA No Arresters F a 69 70 - - 71 72 73 74 75 76 77 78 79 80 81 - - - - - - s e S R T T’ R’ S’ - - - - - - - - - Table XVIII 71 - - - 72 73 74 75 - - 76 77 78 79 80 81 - - - - s e S R T T’ R’ S’ - - - - - Table XIX Flashovers in non-uniform line (tower 69-81) with arresters in towers 72-77 Case 1 – Ipeak = 55 kA Arresters in Tower 72-77 F a 69 70 - - 71 72 73 - - 74 75 76 - - - 77 78 79 80 81 - - - - s e S R T T’ R’ S’ - - - Resistance Adjacent of the Towers Tower Hit Grounding by Resistance Lightning (Ω) (Ω) F 70 Grounding (kA) Case 1 – Ipeak = 55 kA Arresters in Towers 73-76 69 Table XX Grounding resistance values of the tower hit by lightning that needs the installation of arresters in adjacent towers. Ipeak Flashovers in non-uniform line (tower 69-81) with arresters in towers 73-76 a Since these results are very complex, a simplified nonuniform line was simulated, where only one tower, the tower that is hit by the lightning has a higher resistance, while the other towers have grounding resistance of 22 Ω, to understand when it is necessary to install arresters in the adjacent towers to eliminate flashovers in R’S’T’ circuit. In Table XX are presented the values of the grounding resistances, for different lightning currents, which need the installation of arresters in the adjacent towers, besides the towers with high grounding resistances. In these tables it is observed that the installation of arresters in the towers with high grounding resistance and in its adjacent towers, the flashovers in circuit R’S’T’ are eliminated. 39 170 22 13% 55 77 22 29% 72 49 22 45% 90 37 22 59% It is possible to conclude that the discharge current increase causes an increase in the difference between the grounding resistance of the tower hit by lightning and the adjacent towers that needs the installation of arresters. VII. Conclusions - The evolution of the voltages and currents in insulators present two type of oscillation. The first is justified by the reflection of the adjacent towers. The second is explained next. A phase flashover generates waves that propagate through the phase wire. If the flashover occurs at a phase located in the tower hit by lightning neighbourhood, the wave generated propagates through the phase wire and when it arrives at the tower, the current that circulate in the air gap of the insulator that suffered the flashover increases. - In the study of uniform line it was observed that flashovers occur because two reasons: tower potential higher than phase potential (backflashover) or phase potential higher than tower potential. - Line surge arresters installation leads to a limitation of the peak of the insulators voltage, preventing its flashover. - When arresters are installed in all phases of the circuit having the best case scenario regarding the angle of the line voltage, it is verified a reduction of flashovers. - The installation of arresters in the three phases of the circuit mentioned above, at the tower with higher grounding resistance and at its adjacent leads to the elimination of all flashovers in that circuit. 9 - In the study of the simplified non-uniform line it was concluded that for higher discharge currents the value of the grounding resistance of the tower hit by lightning needing installation of arresters in adjacent towers to eliminate flashovers in R’S’T’ circuit is lower. REFERENCES [1] CIGRÉ Working Group 33.01, Guide to Procedures for Estimating the Lightning Performance of Transmission Lines, 1991. [2] Oscar Kastrup, Luiz Cera Zanetta Jr., Lightning Performance Assessment with Line Arresters, Transmission and Distribution Conference, pp: 288, 1996. [3] Karthik Munukutla, Vijay Vittal, Gerald T. HEydt, Daryl Chipman, Brian Keel, A Practical Evaluation of Surge Arrester Placement for Transmission Line Lighntning Protection, IEEE Transactions on Power Delivery, Vol. 25, pp: 1743, 2010. [4] E. J. Tarasiewicz, F. Rimmer, A. S. Morched, Transmission Line Arrester Energy, Cost, and Risk Analysis for Partially Shielded Transmission Lines, IEEE Transactions on Power Delivery, Vol. 15, nº 3, pp. 919 – 924, 2000 10