Safety Control Relay HR1S-AF ••2NC safety input type, such as E-Stops or Interlock Switches ••EN ISO 13849-1 PLe, Safety Cat 4 compliant, and EN 62061 SIL 3 ••Welding detection of start switch ••Fault diagnosis function with dual safety circuits. ••Internal relay operations can be moni­tored with LED Indicator. ••Finger-safe protection ••22.5mm wide, 35mm DIN rail mounting ••UL listed, CSA certified, TÜV NORD approved Terminal Style Integrated Terminal Block Removable Terminal Block A1/A2 Fuse K1 K2 Specifications Operating Temperature –25 to +55°C (no freezing) Degree of Protection Terminal: IP20, Housing: IP40 Rated Power Voltage 24V AC (–15 to +10%) 50/60 Hz 24V DC (–15 to +10%) Power Consumption 5 VA maximum (24V AC) 2.5W maximum (24V DC) Overcurrent Protection Electronic (Note) Control Circuit Voltage 24V Performance Level (PL) e (EN ISO 13849-1) Safety Category 4 (EN ISO 13849-1) Safety Integrity Level (SIL) 3 (EN 62061) Input Synchronization Time When S11-S12, S21-S22 are interrupted: 20 ms maximum When power is interrupted: 60 ms maximum Unlimited Overvoltage Category III Pollution Degree 2 Rated Insulation Voltage 300V Maximum Input Resistance 90Ω Safety Outputs 3NO Response Time Output Contact Ratings Instantaneous (Stop Cat 0) Safety Circuit AC-15 C300: Ue= 240VAC, Ie=0.75A DC-13 Ue=24VDC, Ie=2A Minimum Applicable Load Operation Frequency Rated Current 99 Part Numbers HR1S-AF5130B HR1S-AF5130PB Terminal Arrangement Dimensions (mm) Part Numbers 22.5 114 LED Indicator ••A1/A2 Fuse: Turns on when power circuit is normal. Turns off when power is interrupted or the electronic fuse blows. ••K1: Turns on when K1 relay operates. ••K2: Turns on when K2 relay operates. 17V/10mA (initial value) 1200 operations/h maximum Safety circuit output total: 18A maximum Each safety circuit output: 6A maximum Wire Size HR1S-AF5130B: 1 × 2.5 mm2, 2 × 0.75 mm2 maximum HR1S-AF5130PB: 1 × 2.5 mm2, 2 × 1.5 mm2 maximum Weight 250g Note: Short-circuit of S11 and S21 activates the overcurrent protection circuit, interrupting the power supply. The safety output turns off. Normal status is restored when the short-circuit is removed. Use a 4A fuse (Type gL) for power line protection. Use a 4A fuse (Type gL) or a 6A fast blow fuse for output line protection. The HR1S-AF5130PB terminal block can be removed and installed as shown, allowing for easy installation and replacement of modules. HR1S-AF Wiring Diagram Safety Category 4 Example Circuit (using an emergency stop switch) When not using a start switch (automatic start) The Safety Category is achieved by the entire control system. Take any connected safety equipment and wiring into consideration. L (+) A1 S33 S34 S39 13 23 33 F1 (Fuse: 4A gL) When not monitoring the start switch (welding of 24V AC/DC start switch cannot be detected) K3 S2 13 S2 13 K4 14 14 A1 S33 S34 S39 When monitoring S2 S34 13 23 33 S11 S12 S21 S1 11 21 Emergency 12 Stop Switch 22 S2 13 14 A1 S22 14 24 S34 S39 13 K3 K4 A2 S11 S12 S21 13 Safety Output 3 Circuits 14 Input A ESC: External Start Condition F1: Protection fuse for the power of safety relay module K3, 4: Safety contactor S1 Safety Guard Open F1 (Fuse: 4A gL) K3 S4 K4 A1 ESC: External Start Condition F1: Protection fuse for the power of safety relay module K3, K4: Safety contactor Start Switch When monitoring S4 S33 When not monitoring S4 S34 S39 13 23 33 14 24 34 K1 HR1S-AF LOGIC K2 A2 S11 S12 S21 S1 11 21 12 22 S2 11 12 S3 11 12 33 Limit switch or interlock switch for guard opening/closing Safety Category 3 Example Circuit (using multiple emergency stop switches) N (–) S33 Start Switch 34 N (–) ESC 23 (detecting the OFF status of start switch) LOGIC 24V AC/DC 33 When monitoring the start switch S39 K2 (1) = Start Switch Monitor 23 21 22 21 22 S22 Emergency Stop Switch 1 Emergency Stop Switch 2 Emergency Stop Switch 3 K3 K4 S22 Input B S2 22 HR1S-AF L (+) 13 21 S33 When not monitoring S2 K1 A2 Start Switch (1) ESC A1 Start Switch HR1S-AF Operation Chart When Using the Emergency Stop Switch Power ON Emergency Stop Switch 0 S11-S12 NC1 Start Switch Operation Emergency Stop Switch Operation 1 Emergency Stop Switch S21-S22 NC2 Start Switch S33-S34 NO ➀ Start Switch S33-S39 NO ➁ jWhen monitoring the start switch (detecting the OFF status of start switch) kWhen not monitoring the start switch (contact welding of start switch can­not be detected) Output 13-14(NO Contact) Output 23-24(NO Contact) Output 33-34(NO Contact) When not Using the Safety Guard (Automatic Start) Switch S1 Operated Power ON Input A (S21-S22) 0 Safety Guard Open Switch S2 Operated Safety Guard Open Safety Guard Closed 1 Input B (S21-S22) S33-S39 (short-circuit) Output 13-14 (NO contact) Output 23-24 (NO contact) Output 33-34 (NO contact) t = 0 to ∞ Output Contact Electrical Life 100 AC1: 230V Operating Current × 0.1A AC15: 230V DC1: 24V DC13: 24V 10 1 104 105 Operations 106 107 Specifications and other descriptions in this document are subject to change without notice. IDEC Corporation • 1175 Elko Drive • Sunnyvale, CA 94089 • 800-262-IDEC (4332) • Fax: 408-745-5258 • www.IDEC.com/usa ©2011 IDEC Corporation. All Rights Reserved. 06/11 PDF only.