ANNEXURE–A
Technical Specifications and Compliance Sheet
Sr
Specifications
Complied /
Deviation
Not complied
(If any)
Technical Specification for Racks, Precision Cooling system, Fire Detection,
Suppression & Alarm System and Water Leak Detection System:
1 Racks & Precision cooling system should be of
same make.
2 The 42U rack should be designed to meet the
safety requirements of the modern data centre.
3 Both the front and rear door should have got a
comfort handle with different locking options.
4 The rack should be suitable for baying to a high
performance cooling rack, with automatic door
opening system integrated for emergency purpose.
5 Cable entry should be entered via the roof plate and
via the gland plate without affecting the climatic
conditions inside the rack.
6 Server and Network racks should be of IP54
category with certification for dust and water
protection.
7 The rack should have glazed front door, divided
sheet steel door at the rear, solid, multi-piece roof
plate for side cable entry on both sides, open base
frame, without side panels.
8 The rack should have two 19” mounting levels, front
and rear, on depth stays. Complete earthing kit
should be supplied with rack. The Rack should
have security lock base mount, gland plates.
9 All frame sections of the rack should be with integral
system punching on a 25 mm DIN pitch pattern,
which allows convenient interior installation by
simple fitting and securing of equipment.
10 The rack should have Multi-piece roof plate for side
cable entry via brush strips across the entire
enclosure depth. Roof plate for retrofitting,
removable despite already made cable routing.
11 The rack should have Cut-out for accommodating a
fan module already integrated and closed by a
cover. For supporting the passive ventilation it
should be possible to raise the cover by means of
spacers.
12 Rear mounting angles of the rack should be
prepared for both-sided accommodation of a Power
Distribution Unit (PDU) in 1 U form factor for
enclosure
electrification,
without waste
of
installation volume.
13 Rack should have UL, CUL approvals.
14 The PDU rating should be 96 amps with 48amp X 2
circuts.
Sr
Specifications
15 The PDU shall be mounted vertically in Racks and
should occupy Zero U of rack space.Units that
mount vertically shall be optimized to fit in Racks.
16 PDU shall have IEC industrial Socket for input
power connection and IEC C13 and C19 sockets for
output connections minimum 20 in number.
17 Each rack should have C13 power outlets 24nos
and C19 power outlets 8nos.
18 The vertical busbar should be H-shaped aluminium
section. It should have Shock-hazard-protected
design.
19 The PSM 6-way IEC320 plug-in module should
have 6 power outputs with black IEC320 C 13 slots
without fuses.
20 The PSM 4-way IEC320 C19 plug-in module should
have 4 power outputs with black IEC320 C19 slots
including over current protection.
21 The rack should be equipped with Temperature,
Humidity, smoke and Water leakage sensors.
22 Precision Cooling System for Rack should be Dx
based in-rack cooling up to 12KW.
23 The design of the precision cooling system should
optimised for data centre use.
24 Precision Cooling System should have integrated
air/water heat exchanger and should be mounted
on the side of the rack.
25 Precision Cooling System should be capable for
providing cooling for 2 Racks.
26 Precision Cooling System should have 4 integrated
EC Fan Modules for maximum efficiency and
minimum electrical energy consumption. Fans
should be hot swappable.
27 The air/water heat exchanger and rack should
remain separate from each other to eliminate the
risk of water penetrating into the rack.
28 Precision Cooling System should have integrated
condensate and leakage management.
29 Precision Cooling System should have intelligent
sensor network to monitor the air and water
temperatures, water follow rate and leakage
management.
30 Precision Cooling System should have Fan module
for Capacity expansion.
31 Precision Cooling System should have touch
display.
32 Precision Cooling System should have connection
hose, top/bottom.
33 Precision Cooling System should be able to monitor
temperature, Humidity, Smoke & Water Leakage.
Complied /
Not complied
Deviation
(If any)
Sr
Specifications
34 Condenser system (outdoor unit) – Refrigeration
required for in-rack cooling unit. It should include
piping from condenser system to in-rack cooling
system.
35 It should have monitoring and alarm management
for all physical parameters via SNMP and Ethernet.
A BACnet link should be possible as an option.
36 The fire suppression system should be Novec 1230
based fire suppress system.
37 The fire suppression system should be Rack Based
system.
38 The fire suppression system should be equipped
with a 2-stage smoke analysis extractor system.
39 The eco-friendly, non-toxic (NovecTM1) 1230
should be used as the extinguisher medium in the
fire suppression system.
40 Sensitive hardware such as servers, storage and
switches should not impaired by the extinguisher
medium.
41 While opening an enclosure door, activation of the
extinguisher system should be blocked by the two
access sensors (door monitoring).
42 The fire suppression system should comply IP 20 to
EN 60 529 Protection category.
43 The fire suppression system should have 3.2Kg
Novec TM 1230 Extinguisher.
44 The fire suppression system should have 2
scattered-light sensors with different sensitivities.
45 The fire suppression system should have manual
trigger input.
46 The fire suppression system should have
extinguisher blocking input via door contact.
47 The fire suppression system should have Prealarm, Fire, extinguishing, collective fault outputs.
48 Water Leak Detection System complete with
sensors, wiring connections, I/O modules, alarm
modules, control panel, etc.
49 Monitoring and control software with email and SMS
alert to be supplied.
Technical Specification for UPS:
1 The UPS System should be rack based.
2 The UPS should be scalable up to 10 KVA.
3 The UPS should have feature of soft start.
4 The UPS should have IGBT Based Rectifier.
5 It should be possible to install 2 UPS units in
Parallel.
6 The UPS should have CE Certification.
7 The UPS should have RS232 Serial Interface- 2 No.
in the system enclosure + 1 no. on each module
Complied /
Not complied
Deviation
(If any)
Sr
Specifications
Complied /
Not complied
(smart port) for the monitoring and integration.
The UPS should have SNMP Adaptor Card for
monitoring and integration.
9 The UPS should be supplied with 30 Minutes
Battery Backup.
Technical Specification for CCTV Surveillance & Access Control System:
1 The CCTV surveillance and access control system
should include One CCTV Camera, One 04
Channel DVR, One bio-metric and proximity card
based Access control System.
2 Indoor Dome IR Camera should be 600 TVL Sony
CCD, 3.6mm Fixed lens, Auto White Balance, Auto
Gain Control, Back Light Compensation, Wide
Dynamic Range, CE, FCC & RoHS Certified Indoor
Dome IR Camera.
3 04 Channel DVR should be capable for D1
Recording and remote viewing whenever required.
4 The Access Control system should be based on
combination of Biometric and Proximity card
Readers (with PIN and without PIN).
5 The Access Control System should have minimum
false denial of access. It shall not grant the access
to the unauthorized entity under any circumstances.
6 Door position sensors shall be provided as required
and shall be properly integrated with the Door
Controller System and Application Software.
7 The application software shall mean the access &
time management software that shall be supplied
together with the system in order to provide a
Graphical User Interface (GUI) for human –
machine interface.
8 Monitoring and control Software with email and
SMS alert to be supplied.
8
Authorized Signature:
Name:
Designation:
Seal of firm: