Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ Harmonics and Interharmonics Measurement using Group-harmonic Energy Distribution Minimizing Algorithm Hsiung Cheng Lin, Chao Hung Chen, Liang Yih Liu Abstract—The Fast Fourier Transform (FFT) is still a widely-used tool for analyzing and measuring both stationary and transient signals in power system harmonics. However, the misapplications of FFT can lead to incorrect results caused by some problems such as aliasing effect, spectral leakage and picket-fence effect. A strategy of iterative Group-harmonic Energy Distribution Minimizing (GEDM) algorithm is developed for system-wide harmonic/inter-harmonic evaluation in power systems. The proposed algorithm can restore the dispersing spectral leakage energy caused by the FFT, and regain its harmonic/inter-harmonic magnitude and respective frequency. Every iteration loop for harmonic/interharmonic evaluation can guarantee to be convergent. Consequently, not only high-precision in integer harmonic measurement can be retained, but also the inter-harmonics can be identified accurately, particularly under system frequency drift. The numerical example is presented to verify the proposed algorithm in term of robust, fast and precise performance. Index Terms— harmonics, inter-harmonics, group-harmonics, DFT, FFT I. INTRODUCTION W ITH increasing use of power electronic systems and time-variant non-linear loads in industry, the generated power harmonics and interharmonics have resulted in serious power line pollution. Power supply quality is therefore aggravated. Traditional harmonics may cause negative effects such as signal interference, overvoltage, data loss, equipment malfunction, equipment heating and damage, etc. The noise on data transmission line is also related with harmonics. At some special systems, harmonic current components may cause effect of carrier signals, and thus interfere other carrier signals. As a result, some facilities may be affected. Once harmonics source enter computer instruments, the data stored in the computer may be lost up to ten times. Moreover, harmonics may also cause transformer and capacitor over heating, thus reducing their working life. The resulting rotor heating and pulsating output torque will decrease the driver’s efficiency [1-8]. Manuscript received Nov. 25, 2010; revised Feb. 17, 2011. This work was supported by the National Science Council of the Republic of China, Taiwan under Grant No. NSC 99-2221-E-167 -034. Hsiung Cheng Lin is with the Department of Electronic Engineering, National Chin-Yi University of Technology, Taiwan (e-mail: hclin@ncut.edu.tw). Chao Hung Chen is with the Department of Automation Engineering, Chienkuo Technology University, Taiwan (e-mail: jauhorng.chen@gmail.com). Liang Yih Liu is with the Department of Automation Engineering, Chienkuo Technology University, Taiwan (e-mail: lliu@cc.ctu.edu.tw). The presence of power system interharmonics has not only brought many problems as harmonics but produced additional problems. For instance, there are thermal effects, low frequency oscillation of mechanical system, light and CRT flicker, interference of control and protection signals, high frequency overload of passive parallel filter, telecommunication interference, acoustic disturbance, saturation of current transformer, subsynchronous oscillatoions, voltage fluctuations, malfunctioning of remote control system, erroneous firing of thyristor apparatus, and the loss of useful life of induction motors, etc. These phenomenons may even happen under low amplitude [1-4]. Conventionally, Discrete Fourier transform (DFT) method is efficient for signal spectrum evaluation because of the simplicity and easy implementation. The use of the FFT can reduce the computational time required for DFT by several orders of magnitude. An improper use of DFT (or FFT) based algorithms can, however, lead to multiple interpretations of spectrum [4-6]. For example, if the periodicity of DFT data set does not match the periodicity of signal waveforms, the spectral leakage and picket-fence effect will occur. Since the power system frequency is subject to small random deviations, some degree of spectral leakage can not be avoided. A number of algorithms, e.g., short time Fourier Transform [7], least-square approach [8-10], Kalman filtering [11-12], artificial neural networks [6,13], have been proposed to extract harmonics. The approaches may either suffer from low solution accuracy or less computational efficiency. None is reported to perform well in interharmonic identification under system frequency variations though each demonstrates its specific advantages. The presence of interharmonics strongly poses difficulties in modeling and measuring the distorted waveforms. This is mainly due to: 1) very low values of interests of interharmonics (about one order of quantity less than for harmonics), 2) the variability of their frequencies and amplitudes, 3) the variability of the waveform periodicity, and 4) the great sensitivity to the spectral leakage phenomenon. In recent years, the effect caused by interharmonics is being worsened apparently. Therefore, now the development of accurate interharmonics measurement has attracted great attention both industry and academics. This point of view is fully supported by exploring a number of publications (2007-2011) related to this field [14-36]. However, the published outcome may still suffer from low accuracy, long computational time, complexity or measurement limitation, etc. Accordingly, it is still an essential research issue to be carried on in this field. IEC 61000-4-7 established a well disciplined measurement method for harmonics/interharmonics. This standard recently (Advance online publication: 24 August 2011) Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ has been revised to add methodology for measuring inter-harmonics [37]. The key to the measurement of both harmonics and inter-harmonics in the standard is the utilization of a 10 or 12 cycle sample window upon which to perform the Fourier transform. However, the spectrum resolution with 5 Hz is not sufficiently precise to reflect the practical inter-harmonic locations for both 50 Hz and 60 Hz systems. This paper presents harmonic/inter-harmonic identification using FFT-based GEDM approach which retains the merits of FFT analysis and extends to inter-harmonic identification under system frequency variation environments. This paper is organized as follows. Section II gives a background of the concept of system harmonic/interharmonic measurement. Section III presents the proposed GEDM algorithm. In Section IV, the model validation with a numerical example is demonstrated. Performance results under system frequency drift is included and discussed. Conclusions are given in Section V. I s* [ f k ] = P * [ f k ] (5) An interesting way to view this phenomenon is to observe the FFT implementation, shown in Fig.1. Most leakages can be collected into one group and are considered as though they were all at the dominant harmonic frequency. The amplitude of inter-harmonics (and/or sub-harmonics) can be thus identified. II. BACKGROUND OF SYSTEM HARMONIC/INTERHARMONIC MEASUREMENT The measurement of inter-harmonics is difficult with results depending on many factors. Based on the so-called “group” suggested by IEC 61000-4-7, the concept of group-harmonic is introduced as follows [32]. By the Parseval relation in its discrete form, the power of the waveform, P, can be expressed as N / 2 −1 1 N / 2−1 (1) P= i s [ n] 2 = ∑ I s [ k ] 2 ∑ N n=0 k =0 Both positive and negative values of spectral components are considered to transform the frequency dominant sampled signal into a periodic time dominant signal. Therefore, actual signals spectral components relevant to symmetrical frequencies are complex conjugates each other. However, most real-world frequency analysis instruments display only the positive half of the frequency spectrum because the spectrum of a real-world signal is symmetrical around DC. Thus, the negative frequency information is redundant. For this reason, the power at the discrete frequency f k can be expressed as (2) P[ f k ] = I s [k ] 2 + I s [ N − k ] 2 = 2 I s [k ] 2 where k=0,1, 2,…,N/2-1. The RMS value of the harmonic amplitude at the discrete frequency f k is (3) I h [ f k ] = P[ f k ] = 2 I s [k ] The power of the harmonic at f k may disperse over a frequency band around the f k due to the spectral leakage. Hence, the total power of harmonics within the adjacent frequencies around f k can be restored into a “group power” * [5]. Each “group power”, i.e., P [ f k ] , can be collected between f k − ∆k and f k + ∆k as follows. +τ P*[ f k ] = ∑ I h [ f k +∆k ] 2 (4) ∆k = −τ where τ is an integer number and denotes the group bandwidth. Consequently, each harmonic amplitude can be estimated as Fig. 1 IEC subgrouping of “bins” for both harmonics and interharmonics (graph reproduced from [3]) III. THE PROPOSED ITERATIVE GROUP-HARMONIC ENERGY DISTRIBUTION MINIMIZING ALGORITHM The power line waveform s (t ) (voltage/current) is sampled using the sampling rate f s ( = 1 ) , which has the Ts fundamental frequency f d , as follows. (6) s(n) = s(t ) t =nTs , n = 0,1,2,...., N − 1 where N is the sampled point of Fourier fundamental period Tf . In general, the distorted signal can be composed of three parts, as follows. (7) s(n) = sd (n) + sh (n) + si (n) where s d (n) is the fundamental component, sh (n) is the harmonic components, and si (n) represents the interharmonic components. III.1 The Group-Harmonic Bin Power Algorithm The length of the sampled window for FFT analysis plays the critical point to determinate if the spectrum can be achieved accurately. Based on the empirical observation using FFT, the second stronger amplitude is found to be located at the right side of the dominant component, i.e., I h [ f k +1 ] > I h [ f k −1 ] , in case of overlong truncated-window. On the contrary, the second stronger amplitude is located at the left side of the dominant component, i.e., I h [ f k +1 ] < I h [ f k −1 ] , the truncated-window length is insufficient for FFT analysis. Accordingly, the proposed GEDM approach is to develop the mechanism for correcting the window length according to the situation on the dispersed energy. This proposed GEDM method in deed extends the “group” concept that has been mentioned by IEC 61000-4-7 and some papers [3, 5, 20, 36-37]. (Advance online publication: 24 August 2011) Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ (5) Check if P ** [ f k ] ≤ Pmin . If yes, the iteration loop stops ' and determine N = N ' . The fundamental frequency f d Amplitude and amplitude Ad' can be obtained. Otherwise, go back to Step (2) to repeat the procedure until P ** [ f k ] ≤ Pmin . Note that Pmin is a predefined minima power value. III.2 The proposed GEDM Algorithm The proposed Iterative Group-harmonic Energy Distribution Minimizing (GEDM) algorithm that integrated with the GBP algorithm is demonstrated as follows. Frequency (Hz) f d' Fig. 2 Amplitude distribution around the dominant component Based on the above concept, the Group-Harmonic Bin Power (GBP) algorithm is proposed and described as follows. Ad'f d' ∆f ' s (n) ' s (t ) f s = 5kHz, N = 1000 sd' (n) + sh' (n) si' (n) = s ' (n) - [ sd' (n) + sh' ( n)] I h [ f k +1 ] > I h [ f k −1 ] I h [ f k +1 ] < I h [ f k -1 ] P ** [ f k ] ≤ Pmin Fig. 4 Flowchart of the proposed GEDM algorithm f d' Ad' (1) Determine the new ∆f ' = f s using the GBP method and N' find the correct fundamental frequency f d' and its respective amplitude Ad' . Accordingly, the fundamental Fig. 3 The flowchart of the proposed GBP Algorithm (1) Set f s = 5kHz ,N=1000 for sampling the power line signal. (2) Implement FFT. (3) If I h [ f k +1 ] > I h [ f k −1 ] , N=N-1. Otherwise, go to next step. (4) If I h [ f k +1 ] < I h [ f k −1 ] , N=N+1. Otherwise, go to next step. frequency signal sd' ( n) and its harmonic signals sh' ( n ) can be obtained, as follows. s ' (n) = s(t ) t= n = sd' (n) + sh' (n) + si' (n), n = 0,1,2,3,..., N ' −1 (8) f s' ' ' (2) Reconstruct the sd (n) and sh ( n) and form a composed waveform. Therefore, the new waveform that only contains interharmonic components without sd' ( n ) and sh' (n) can be obtained as follows. (Advance online publication: 24 August 2011) Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ (9) si' (n) = s ' (n) - [sd' (n) + sh' (n)] (3) Assume the major interharmonic component (biggest amplitude) as the fundamental component. (4) Repeat steps (1) to (3) until all major interharmonics are regained. IV. MODEL VALIDATION WITH A NUMERICAL EXAMPLE The proposed GEDM algorithm has been tested by the synthesized line signal (voltage/current) to verify the effectiveness of harmonic/inter-harmonic analysis. The following example is used to illustrate the harmonic analysis of a distorted waveform. s( t ) = sin( 2πf d t - 35 ° ) + 0.3 sin( 2π ⋅ 3 ⋅ f d ⋅ t - 51 ° ) + 0 .25 sin( 2π ⋅ 5 ⋅ f d ⋅ t + 48 ° ) + 0.2 sin( 2π ⋅ 131 ⋅ t + 12 ° ) + 0.25 sin( 2π ⋅ 213.5 ⋅ t - 75 ° ) + 0.1 sin( 2π ⋅ 351 ⋅ t ) Step (a): Measurement of fundamental and integer harmonics with a 0.29 Hz frequency drift In this case, the fundamental frequency component including 3rd harmonic and 5th harmonic is considered to have a 0.29 Hz variation. The dispersed power of the harmonics over around the frequency band is significantly reduced from 0.0088 to about zero within only 6 iteration loops, shown in Fig. 7. Fig.8 indicates that each harmonic is approaching toward its true amplitude step by step. The amplitudes of fundamental, third and fifth component are thus obtained as 1.0, 0.3 and 0.24 at the sixth iteration loop from 0.99, 0.28 and 0.22 at the first iteration loop, respectively. Also, the fundamental frequency is found as 60.29 Hz, matching the true one. (10) 0.01 where f d = 60.29 Hz is the fundamental frequency. Generally, the system frequency drift is a concern in power systems because it may vary slightly from time to time due to the change of system loads. This effect, in deed, influences the traditional FFT spectrum analysis. As above, the line signal has a fundamental frequency, i.e., 60.29 Hz, with 0.29 Hz drift and a scaled amplitude of 1V. The 3rd and 5th harmonic components are included in the synthesized waveform to present a possible distorted waveform situation. Non-integer components, i.e., interharmonic, such as 131 Hz, 213.5 Hz, and 351 Hz are to be considered, reflecting a possible polluted line case. Note that above harmonics/interharmonics are assigned different magnitudes and phases. According to the equation (10), we set f s = 5 kHz, 0.009 0.008 Dispersed Power 0.007 0.006 0.005 0.004 0.003 0.002 0.001 0 1 2 3 4 Iteration Number 5 6 Fig. 7 Convergent curve of the dispersed power at the harmonic components N = 1000 , i.e., ∆f = 5 Hz, and the waveform is shown in Fig. 5. As can be seen in Fig. 6, a considerable spectrum leakage occurs using FFT so that the result is unable to represent its actual spectrum. 1.2 1 Fundamental Harmonic(60.29Hz) 0.8 Amplitude Third Harmonic(180.87Hz) Fifth Harmonic(301.45Hz) 0.6 0.4 0.2 0 1 2 3 4 5 6 Iteration Number Fig. 8 Amplitude tracking curve of the harmonic components Fig. 5 The distorted waveform Step (b): Measurement of the interharmonic at 213.5 Hz In this stage, all harmonic components acquired at Step (a) are excluded in the new waveform so that the interharmonic at 213.5 Hz is assumed as the fundamental component. The dispersed power of the supposed fundamental band (interharmonic at 213.5 Hz) is considerably reduced from 0.013 to almost zero within 8 iteration loops, shown in Fig. 9. Accordingly, its amplitude is obtained as 0.25 from 0.21 and the 213.5 Hz component is thus confirmed, shown in Fig. 10. Fig. 6 Spectrum of the distorted waveform using FFT The following steps are illustrated to find the true harmonics/interharmonics. (Advance online publication: 24 August 2011) Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ 0.014 0.3 0.012 0.25 0.2 Amplitude Dispersed Power 0.01 0.008 0.006 0.15 0.1 0.004 0.05 0.002 0 0 1 1 2 3 4 5 6 7 Iteration Number 3 4 5 6 7 8 9 Iteration Number Fig. 12 Amplitude tracking curve of the 131 Hz interharmonic Fig. 9 Convergent curve of the dispersed power at the 213.5 Hz interharmonic 0.26 0.25 0.24 Dispersed Power 2 8 0.23 0.22 Step (d): Measurement of the interharmonic at 351 Hz In the last stage, all harmonics, 213.5 Hz and 131 interharmonic are excluded in the new waveform. Therefore, only 1 interharmonic (351 Hz) is remained. The dispersed power of the supposed fundamental band (interharmonic at 351 Hz) is going down quickly to almost zero from 0.0088 within only 4 iteration loops, shown in Fig. 13. As a result, its amplitude is obtained as 0.1 from 0.093 and the 351 Hz component is thus confirmed, shown in Fig. 14. 0.21 0.01 0.009 0.2 0.008 0.19 2 3 4 5 6 7 8 Iteration Number Fig. 10 Amplitude tracking curve of the 213.5 Hz interharmonic 0.007 Dispersed Power 1 0.006 0.005 0.004 0.003 Step (c): Measurement of the interharmonic at 131 Hz In this stage, all harmonics and 213.5 Hz interharmonic are excluded in the new waveform. Similarly, the dispersed power of the supposed fundamental band (interharmonic at 131 Hz) is approaching toward to zero from 0.0039 within 9 iteration loops, shown in Fig. 11. Accordingly, its amplitude is obtained as 0.2 from 0.19 and the 131 Hz component is therefore confirmed, shown in Fig. 12. 0.002 0.001 0 1 2 3 4 Iteration Number Fig. 13 Convergent curve of the dispersed power at the 351 Hz interharmonic 0.2 0.18 0.16 0.004 0.14 0.0035 0.12 Amplitude Dispersed Power 0.0045 0.003 0.0025 0.1 0.08 0.06 0.002 0.04 0.0015 0.02 0.001 0 1 0.0005 2 3 4 Iteration Number 0 1 2 3 4 5 6 7 8 9 Fig. 14 Amplitude tracking curve of the 351 Hz interharmonic Iternation Number Fig. 11 Convergent curve of the dispersed power at the 131 Hz interharmonic V. CONCLUSIONS Although the DFT (or FFT) has certain limitations in the harmonic analysis, it is still widely used in industry today. The harmonic/inter-harmonic identification using FFT-based GEDM algorithm has been developed to be extracted accurately and efficiently. The test results confirm that the proposed GEDM method can guarantee the tracking of each harmonic/interharmonic amplitude to be convergent at every (Advance online publication: 24 August 2011) Engineering Letters, 19:3, EL_19_3_17 ______________________________________________________________________________________ iteration loop by the GBP algorithm. There is no theoretical restriction in the locations of inter-harmonic components while the group bandwidth ( τ ) of each harmonic/inter-harmonic should be chosen appropriately. Moreover, the GEDM methodology has been implemented successfully by a LabVIEW programming so that it can be easily extended to other software packages like microprocessor for on-line measurement. Additionally, the proposed GEDM can provide an advanced improvement for most measurement devices with some inherent errors because of the spectrum leakages caused by harmonics/inter-harmonics. [18] [19] [20] [21] [22] REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] Hao Qian, Rongxiang Ahao, and Tong Chen, “Interharmonics Analysis Based on Interpolating Windowed FFT Algorithm”, IEEE Trans. Del., Vol. 22, no. 2, April 2007, pp. 1064-1069. D. Gallo, R. Langella, and A. Testa, “Interharmonics, Part 2: Aspects Related to Measurement and Limits”, Sixth International Workshop on Power Definitions and Measurements under Non-Sinusoidal Conditions, Milano, 13-15, Oct. 2003, pp.174-181. Testa, A.; Akram, M.F.; Burch, R.; Carpinelli, G.; Chang, G.; Dinavahi, V.; Hatziadoniu, C.; Grady, W.M.; Gunther, E.;Halpin, M.; Lehn, P.; Liu, Y.; Langella, R.; Lowenstein, M.;Medina, A.; Ortmeyer, T.; Ranade, S.; Ribeiro, P.; Watson, N.; Wikston, J.; Xu, W., “Interharmonics: Theory and Modeling”, IEEE Trans. Del., vol. 22, no.4, Otc. 2007, pp. 2335-2348. Masoud Karimi-Ghartemani and M. Reza Iravani, “Measurement of harmonics/inter-harmonics of time-varying frequency”, IEEE Trans. on Power Delivery, Vol. 20, No. 1, Jan. 2005, pp. 23-31. C.S. Moo and Y.N. Chang, “Group-harmonic identification in power systems with nonstationary waveforms”, IEE Proc.-Gen. Trans. Distri., Vol. 142, No. 5, Sep. 1995, pp. 517-522. H.C. Lin, “Intelligent neural network based adaptive power line conditioner for real-time harmonics filtering”, IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 5, Sep. 2004, pp.561-567. Kwok, H.K.; Jones, D.L, ”Improved instantaneous frequency estimation using an adaptive short-time Fourier transform”, IEEE Trans. on Signal Processing, Vol. 48, Issue 10, Oct. 2000, pp.2964-2972. Soliman, S.A.; Alammari, R.A.; El-Hawary, M.E.; Mostafa, M.A.; “Effects of harmonic distortion on the active and reactive power measurements in the time dominant: a single phase system”, 2001 IEEE Power Tech Proceedings, Vol.1, 10-13 Sep. 2001, Page(s):6. M. Bettayeb and U. Qidwai, “Iterative estimation of power system harmonics”, Elect. Power Syst. Res., Vol. 47, 1998, pp. 143-152. Al-Kandari, A.; El-Naggar, K.M., “Time dominant modeling and identification of nonlinear loads using discrete time-filtering estimator”, 2003 IEEE Transmission and Distribution Conference and Exposition, Vol.1, 7-12 Sept. 2003, pp.126-131. A.A. Girgis, W.B. Chang, and E.B. Makram, “A digital iterative measurement scheme for on-line tracking of power system harmonics”, IEEE Trans. on Power Delivery, Vol. 6, No. 3, Jul. 1991, pp. 1153-1160. Macias, J.A.; Gomez, A.; “Self-Tuning of Kalman Filters for Harmonic Computation”, IEEE Trans. on Power Delivery, Vol. 21, Issue 1, Jan. 2006, pp.501-503. H.C. Lin, “Intelligent Neural Network based Fast Power System Harmonic Detection”, IEEE Trans. on Industrial Electronics, Vol. 54, No. 1, Feb. 2007, pp.43-52. Jing Yong; Tayjasanant, T.; Xu Wilsun; Caixin Sun, “Characterizing Voltage Fluctuations Caused by a Pair of Interharmonics”, IEEE Trans. on Power Delivery, Vol. 23, Issue 1, Jan. 2008, pp.319–327. Miron, Anca; Chindris, M.; Cziker, A., “Interharmonics analysis using Fourier Transform and virtual instrumentation”, 10th International Conference on Electrical Power Quality and Utilisation, EPQU 2009, 15-17 Sep. 2009, pp.1-4. Taekhyun Kim; Powers, E.J.; Grady, W.M.; Arapostathis, A., “Detection of Flicker Caused by Interharmonics”, IEEE Trans. on Instrumentation and Measurement, Vol. 58, Issue 1, Jan. 2009, pp.152-160. Wiczynski, G., “Standard measurement of interharmonics in a power supply system while evaluating obnoxiousness of a flicker”, 13th [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] International Conference on Harmonics and Quality of Powe, ICHQP 2008, Sep. 28-Oct. 1 2008, pp.1-4. Chang, G.W.; Cheng-I Chen; Quan-Wei Liang, “A Two-Stage ADALINE for Harmonics and Interharmonics Measurement”, IEEE Trans. on Industrial Electronics, Vol. 56, Issue 6, June 2009, pp.2220-2228. Valenzuela, Javier; Pontt, Jorge, “Real-time interharmonics detection and measurement based on FFT algorithm”, Applied Electronics, AE 2009, 9-10 Sep. 2009, pp.259–264. H.C. Lin, “Inter-Harmonic Identification using Group-Harmonic Weighting Approach Based on the FFT”, IEEE Transactions on Power Electronics, Vol. 23, Issue 3, May 2008, pp. 1309-1319. Zhu, T.X., “Exact Harmonics/Interharmonics Calculation Using Adaptive Window Width”, IEEE Trans. on Power Delivery, Vol. 22, Issue 4, Oct. 2007, pp.2279-2288. Petrovic, P.B.; Stevanovic, M.R., “Digital Processing of Synchronously Sampled AC Signals in the Presence of Interharmonics and Subharmonics”, IEEE Trans. on Instrumentation and Measurement, Vol. 56, Issue 6, Dec. 2007, pp.2584-2598. Drapela, J., “A time domain based flickermeter with response to high frequency interharmonics”, 13th International Conference on Harmonics and Quality of Power, ICHQP 2008, Sep. 28 -Oct. 1 2008, pp.1-7. Chang, G.W.; Chen, C.I.; Liu, Y.J.; Wu, M.C., “Measuring power system harmonics and interharmonics by an improved fast Fourier transform-based algorithm”, IET Generation, Transmission & Distribution, Vol. 2, Issue 2, March 2008, pp.193-201. San Martin, J.; Pontt, J.; Bello, F.; Aguilera, R., “Interharmonics Power Losses Estimation in Power Transformer fed High Power Cycloconverter Drive”, IEEE Industry Applications Society Annual Meeting, IAS '08, 5-9 Oct. 2008, pp.1-5. Halpin, S.M.; Singhvi, V., “Limits for Interharmonics in the 1-100-Hz Range Based on Lamp Flicker Considerations”, IEEE Trans. on Power Delivery, Vol. 22, Issue 1, Jan. 2007, pp.270-276. Gu, I.Y.-H.; Bollen, M.H.J., “Estimating Interharmonics by Using Sliding-Window ESPRIT”, IEEE Trans. on Power Delivery, Vol. 23, Issue 1, Jan. 2008, pp.13-23. Petrovic, P.B., “Calculation of Measurements Uncertainties in Case of Asynchronous Sampling of Complex AC Signals”, IEEE Instrumentation and Measurement Technology Conference Proceedings, IMTC 2008, 12-15 May 2008, pp.1701-1706. Smith, K.S.; Li Ran, “Torsional Resonance Risk Management in Islanded Industrial Power Systems Supplying Large VFDs”, IEEE Trans. on Industry Applications, Vol. 44, Issue 6, Nov.-Dec. 2008, pp.1841-1850. Wei, Peiyu; Li, Jing; Li, Zhenmei, “Interharmonics monitoring of power network using modified covariance arithmetic and virtual instrument”, 9th International Conference on Electronic Measurement & Instruments, ICEMI '09, 16-19 Aug. 2009, pp.3-242-3-245. Cheng-I Chen; Chang, G.W., “Virtual Instrumentation and Educational Platform for Time-Varying Harmonic and Interharmonic Detection”, IEEE Transactions on Industrial Electronics, Vol. 57, 2010, pp.3334-3342. Ramirez, A.; “The Modified Harmonic Domain: Interharmonics”, IEEE Transactions on Power Delivery, Vol. 26 , Issue 1, 2011, pp. 235–241. Jian Cao; Tao Lin; Lin Liu; Jia-kai Ling; Xue-ling Huang; “Power System Interharmonics Analysis Based on new Time Frequency Algorithm”, 2011 Asia-Pacific Power and Energy Engineering Conference (APPEEC), 2011 , pp. 1-3. Nassif, A.B.; Jing Yong; Mazin, H.; Xiaoyu Wang; Xu, W., “An Impedance-Based Approach for Identifying Interharmonic Sources”, IEEE Transactions on Power Delivery, Vol. 26 , Issue 1, 2011 , pp. 333-340. Chang, G.W.; Shin-Kuan Chen; Huai-Jhe Su; Ping-Kuei Wang, “Accurate Assessment of Harmonic and Interharmonic Currents Generated by VSI-Fed Drives Under Unbalanced Supply Voltages”, IEEE Transactions on Power Delivery, Vol. 26, Issue 2, 2011, pp.1083-1091. H.C. Lin, C. H. Chen, L. Y. Liu, “Harmonics and Interharmonics Measurement using Group-harmonic Power Minimizing Algorithm”, Lecture Notes in Engineering and Computer Science: Proceedings of The World Congress on Engineering 2011, WCE 2011, 6-8 July, 2011, London, U.K. pp.1300-1305. IEC 61000-4-7: “Testing and measurement techniques: Harmonics and interharmonics: General guide on harmonics and interharmonics measurements and instrumentation for power supply systems and equipment connected thereto”, 2002. (Advance online publication: 24 August 2011)