"Dec. 22, 19742. H. K. SCHRAGE' ' 2,306,226 HIGH VOLTAGE POWER TRANSMISSION ' Filed' Feb. 7, 1941 Z Fig.1. ' ' 2 Sheets-Sheet 1 V ‘ F59. : 5”. ‘x 5 g X41405 7' 5541 _ Mommy. Dec. 22, 1942'. 2,306,226 H. K. SCHRAGE HIGH VOL'IH‘RGIEIw POWER TRANSMISSION Filed Feb. 7, 1941 2 Sheets-Sheet 2 gwiiawtom: I‘ Ma?a» m 804,7, WW f$% Maw” . Patented Dec. 22, 1942 entree stares rarest eerie Hidde Klaas Schrage, Ennetbaden, Switzerland, assignor to Aktiengesellschaft Brown, Boveri & Cie., Baden, Switzerland Application February 7, 1941, Serial No. 377,937 In Switzerland February 10, 1940 11 Claims. This invention relates to high voltage trans mission lines, and particularly to transmission lines wherein disturbances arising from short circuits are minimized. Most interruptions in high voltage lines are due to single phase arcing earths (insulator ?ash overs) caused by excess voltages occurring during lightning disturbances. If the neutral point is earthed a single phase short circuit will occur in (Cl. 171-87) high voltage transmission system embodying the principles of the invention in which the six line conductors are fed by two three-phase systems not interlinked together; Figs. 7 and 8 are diagrammatic representations of high voltage transmission systems embodying the principles of the invention, in which the six line conductors are fed by three non-interlinked single-phase systems; the system, resulting in the circuit breaker open 10 Fig. 9 is a diagrammatic representation of a :ing and the supply being interrupted. In most system showing how in the case of three non .Europeanhigh voltage transmission systems the interlinked single phase feeding systems the neutral point is generally not directly earthed mutual capacities of the line phases and the but connected over an earth leakage coil to capacities of these line phases with respect to earth; in most cases single phase arcing earths 15 earth can be compensated by choking coils. Fig. do not cause the circuit breaker to open because 9 corresponds to the transmission system shown they are extinguished by the aforesaid coils. On in Fig. 8. the other hand if a short circuit occurs between In the Figures 1-9 the six line conductors of two or all three phases of the system, an inter the transmission line are designated by ruption in transmission cannot be prevented even 20 UVWXYZ. if the system is provided with earth leakage coils. It will be obvious to those skilled in the art The object of the present invention is to pro- _ that in the voltage vector diagrams shown in vide an improved high voltage power transmis Figs. 2, 3, 4 and 5 the voltages between the line sion system in which short circuits between conductors UVWXYZ are represented by the phases or simultaneous earths in more than one 25 distances between the corresponding points phase line do not generally produce any short UVWXYZ of the vector diagrams. So for in circuit currents and therefore no tripping of the stance in Fig. 2 showing the voltage vector dia circuit breakers. According to the invention this gram of the line in normal conditions the dis is achieved by passing a six-phase current over tance Z-—U represents the voltage between the six line conductors which are spatially arranged 30 line conductors Z and U, the distance Z-—~W as in a three-phase double line, this current represents the voltage between the line con ?owing either over two three-phase systems ductors Z and W, etc. Comparing vector diagram Fig. 2 with Fig. 1 showing the local arrangement which are not interlinked or over three single phase systems which are also not interlinked. of the phases UVWXYZ on the masts, it is seen This arrangement can be still further improved that in these figures the relative position of the if the capacitive charging currents which occur phases is essentially the same, so that vector dia with the aforementioned short-circuits or earths gram Fig. 2 also could represent the local ar rangement of the line conductors. This corre and ?ow over the points where the faults occur, are compensated by choking coils when these spondence between vector diagram 2 and the 40 local arrangement of the conductors has the ad currents attain dangerous values. The invention is explained in greater detail by vantage that in normal working conditions the voltage between adjacent phases is a minimum. means of the constructional examples illustrated diagrammatically in the accompanying drawings, Comparing a three phase double line with a six phase line according to the invention, the line in which; Fig. 1 is a diagrammatic representation of a 45 voltage to earth being the same in both cases, it typical six conductor transmission line spatially ‘will be seen that for the three phase double line arranged as a three-phase double line; the voltage between adjacent phase is \/3 times Fig. 2 is a vector diagram of the voltages of the as high as for the six phase line. Fig. 6 represents a high voltage transmission six line conductors in normal conditions, when no short circuits or earths exist; Figs. 3, 4 and 5 are voltage vector diagrams of the six line conductors in diiierent cases of short-circuits between line conductors or in the case of earths of these conductors; Fig. 6 is a diagrammatic representation of a 50 system for which the six line conductors are fed by two three phase systems not interlinked to gether. The three phase power bus bars 13 feed the low tension three phase winding t of the power transformer which is provided with two non-interlinked three phase high voltage wind 2,306,226 ings T1 and T2. These high voltage transformer windings T1 and T2 constitute the two non-inter linked three phase feeding systems mentioned be fore. The high voltage terminals UoVoWo of the winding T1 are connected to the line conductors UVW through the circuit breakers ucw; in the same way the high voltage terminals XoYoZo, of the winding T2 are connected to the line con ductors XYZ through the circuit breaker rye. high voltage windings cf the transformer and UoVoWo and XoYcZo being the ten inals of the high voltage side of the transformer supplying the high voltage line. The windings T1 and T2 can be located in one and the same tr nsformer. The individual conductors of the high voltage line are designated by UVWX'ZZ. mal six-phase operation are closed. During nor switches iwwxyz If a fault occurs on one of the high The purpose of the circuit breakers 11/03’ and of 10 voltage conductors which does not disappear again of its own accord, that is if for instance an insulator on the phase conductor U is dam aged, then in order to be able to repair or re— A very important advantage which exists when place this insulator, just as in the case of a three the neutral points of the transformer windings phase double line, the left half of the high volt T1 and T2 are either not connected with each age line, that is to say the phase conductors UY Z other at all, or when these neutral points are must be put out of operation and the power is only connected ?exibly over choke coils will now then transmitted temporarily as three~phase be explained. If in this case a conductive con current over the phase conductors Vi X. This nection between neighboring phases of the trans mission line is formed, for instance a flash over 20 change over is made by opening the switches ways and closing the switch it’. The trans between phase V and X occurs, this does not re former windings T1 then supply the conductors sult in a short circuit in one of the three phase VWX and the service is maintained temporarily systems UVW and XYZ but only in a displace in this manner. The change over can be made ment of the voltages of both three phase systems relative to each other; each of the three phase 25 without interrupting the service if ?rst the switches says are opened, then the switch a’ systems is more or less unaffected and the trans closed, and finally the switch opened. With mission of power can be continued ‘without inter the arrangement shown in Fig. contrary to ruption. A short circuit between the phase con standard three-phase double systems, a short ductors V and X results in a voltage displacement as shown in vector diagram Fig. 3. Between ad 30 circuit between two adjacent phases of the high voltage line does not result in an interruption of jacent conductors, for instance between phase the service. If the short-circuit extinguishing Z and V, there will be a voltage equal to or are suppression coil or is correctly dimensioned \/3><phase voltage, that is to say a voltage equal a short-circuit are occurring between both to that existing with three phase double lines in normal service. When there is an arc between 35 phases will extinguish of its own accord. If on the other hand a short-circuit arc occurs be the phase conductors V and X a current flows tween thr e adjacent phases of the high voltage over this are which is determined on the one line, for instance between the VXW, then hand by the mutual capacity of the systems with this system of connections an interr .;:tion UVW and XYZ and on the other hand by the mutual voltage displacement EE’ of the neutral 40 will no longer be avoided. It is, however, also possible to avoid an in points of these systems. If the neutral points E terruption in the power transmission when a and E’ of both systems are for instance con short-circuit occurs between three adjacent nected with each other over a choking coil 0: phases of the high voltage line, if the six-phase (Figs. 3 and 6) the current in the choking coil high voltage line is not supplied by two three will also flow over the arc and the choking coil phase windings but by a single three-phase wind can be dimensioned in such a manner that the ing with open phases which are either not inter capacity current and the choking coil current linked or are merely connected together by means compensate each other so that the arc extin of choking coils. Fig. '1 shows the diagram of guishes of its own accord, as is the case with the connections to be used in such a case. UoliaVtYo earth arc in high voltage lines having earth and W020 represent the high voltage terminals leakage coils. A common earth leakage coil 1) of the transformer windings T1, T2 and T3 sup~ can be provided for both systems UVW and plying the high voltage transmission line, the XYZ independently of the “short-circuit extin low voltage winding not being shown. The guishing coil” 11 by connecting the coil 2) to the three phases of the high voltage winding ‘are not middle of the coil a as shown in Fig. 6. The coil interlinked. The mid-points of the high a then serves at the time as a potential divider voltage transformer windings for instance for the connection of the earth leakage coil 2). connected to a choking coil (1 the neutral point By using a short circuit extinguishing coil and N of which is earthed over the choking coil D. an earth leakage coil it is thus possible to make During normal operation the switches utwrye certain that the arc is extinguished both in the the choke coils a and b will be explained further on. case of an arcing earth and a short circuit be are closed and the switches 3 open. tween the neighboring phases of a high voltage line. To construct a six-phase high voltage power transmission line according to the invention the actual high voltage line itself does not require any alteration and the same high voltage line age diagram of the high voltage line in normal The volt design. Fig. stored. operation is shown in Fig. 2. If a short-circuit occurs on the high voltage line, for instance be tween two adjacent phases W and X a voltage displacement such as is shown in Fig. Li will re sult. The service can thus continue without in terruption for a time. If the short-circuit are as for a three-phase double line can be used. between W and X disappears then the symmetri The transformers, high-voltage switchgear, etc. can be of standard three-phase or single-phase 70 cal voltage diagram shown in Fig. 2 will be re 6 shows diagrammatically the fundamental system of connections for such a six-phase power transmission arrangement, t being the low voltage windings, of a transformer fed by power bus bars B, T1 and T2 being the If a short-circuit occurs between the three phases VXW then the voltage will be dis placed as shown in Fig. 5. Also in this case the service can be maintained. The six-phase high ‘voltage system arranged as shown in Fi . 7 is 2,306,226 therefore to a high degree unaffected by short circuits. Only when the short-circuit is not re 3 stricted to three neighbouring phases is an in terruption of the service unavoidable; such a disturbance is, however, extremely improbable. If with the arrangement shown in Fig. 7 one half of the high voltage line, for instance the phases ZUY, has to be made free of voltage to enable a rep-air to be undertaken, the service can be maintained with three phases over the conductors VXW. The switches u’vw and both 1O suppress1on coil 03 is connected in delta switches s are then closed, whilst the remaining switches must be kept open’. This change-over the mid-points of the three phases which are not can also be accomplished without interrupting interlinked; three single-phase earth leakage the service. The switches s are closed ?rst, switches rye opened, switch a’ closed and ?nally switch it opened. coils D are also connected to the same mid - points, each of the three phases being provided During normal undisturbed operation with the arrangement shown in Fig. 7 the three-phase choking coil a’, and the single-phase choking coil D are free from voltage. If two or three-phase short-circuits of the kind shown in Figs. 4. and 5 respectively occur in the high voltage line an un symmetrical three-phase voltage forms at the ter minals of the three-phase choking coil 11 so that the neutral point N of the choking coil acquires parallel with the aforesaid charging currents, it a voltage equal to the average voltage of the high- . is possible to obtain practically complete com voltage line. pensation of the currents at the ‘fault points when as there are only short voltage line to earth is zero and the choking coil D is in this case free from voltage. In most cases, however, it will not be just a question of claim: 1. A high voltage transmission system compris ing six high voltage line conductors spatially ar pure short-circuits between phases but rather a combined arcing earth and short-circuit; that is . ranged as a three-phase double line, at least one to say the arc will occur simultaneously between two or three phases and also between these phases step-up transformer at one end of said line, and at least one step-down transformer at the on the one hand and the earth on the other hand. If in the case 40" not exceeding three. 2. A high voltage transmission system corn prising six high voltage line conductors spatially corresponding to the centre of gravity of the siX points UVWXYZ, these be 45 arranged as a three-phase double line, at least ing assumed to be of equal mass. On the other hand if the short-circuit point V'VVX has at the same time a short to earth the earth voltage will be displaced to VXW. rl‘he neutral point N (Fig. '7) has then no longer earth potential and the choking coil D is under voltage. The three phase are suppression coil 12 must be dimensioned according to the mutual capacity of the six high voltage conductors. The single-phase earth leak- . age coil D must be dimensioned according to the ence of 180°. 3. A high voltage transmission system com prising six high voltage line conductors spatially arranged as a three-phase double line, at least one step-up transformer at one end of said line, and at least one step-down transformer at the other end of said line, the high voltage windings of said transformers being connected to said con~ ductors to provide three non-interlinked single phase circuits having an electrical phase differ earths as well as against short-circuits in all cases when one, two or three adjacent phases of ence of 120°. the high voltage line have earths or short-circuits or both together. 4. A high voltage transmission system com prising six high voltage line conductors spatially arranged as a three-phase double line, two elec trically separated three-phase high voltage transformer windings at each end of said line connected to said conductors to provide two non-interlinked three-phase circuits, and a choke three-phase operation has been described. It is therefore clear that at the end of the line the order in which the switch operations have to oc cur is the same as at the beginning of the line. It is therefore expedient to provide means Where 75 ‘2,306,226 4. 5. A high voltage transmission system- com prising six high voltage line conductors spatially arranged as a three-phase double line, two elec trically separated three-phase high voltage transformer windings at each end of said line connected to said conductors to provide two non interlinked three-phase circuits, a'choke coil at least at one end of the line connecting the neu prising six high voltage line conductors spa tially arranged as a three-phase doubleline, at least one'step-up transformer at one end of said line, at least one step-down transformer at the other end of said line, the high voltage windings of said transformers being connected to said conductors to provide a plurality of non interlinked circuits each comprising an odd num ber of phases not exceeding three, and switch tral points of both of said separated three-phase means for converting said line to three-phase ll) transformer windings dimensioned to compen transmission on three of said conductors. sate the capacitive charging current at the fault 9. A high voltage transmission system com point when a short circuit occurs between any prising six high ~voltage line conductors spa tially arranged as a three-phase double line, two non-interlinked conductors of the transmis sion line, and an earth leakage coil connected to three electrically separated high voltage trans the mid-point of said choke coil. former windings at each end of said line con 6. A high voltage transmission system corn nected to said conductors to provide three non prising six high voltage line conductors spatially interlinked single-phase circuits, and earth leak arranged as a three-phase double line, three elec age coils connected to the mid-point of each of trically separated high voltage transformer wind the single-phase transformer windings at least ings at each end of said line connected to said at one end of the line. conductors to provide three non-interlinked sin 10. A high voltage transmission system com gle-phase circuits, and a three-phase choke coil prising six high voltage line conductors spa at least at one end of the line connecting the tially arranged as a three-phase double line, mid-points of the three separated single-phase three electrically separated high voltage trans transformer windings dimensioned to compen sate the capacitive charging currents at the fault points when a short circuit occurs between any nected to said conductors to provide three non former windings at each end of said line con interlinked single-phase circuits, and single phase choke oils connecting the mid-points of non-interlinked conductors of the transmission line. 7. A high voltage transmission system com 30 prising six high voltage line conductors spatially the three single-phase transformer‘ windings at least at one end of the line. electrically separated high voltage transformer 11. A high voltage transmission system com prising six high voltage line conductors spa tially arranged as a three-phase double line, windings at each end of said line connected to three electrically separated high voltage trans said conductors to provide three non-interlinked single-phase circuits, a three-phase choke coil former windings at each end of said line con nected to said conductors to provide three non at least at one end of the line connecting the interlinked single-phase circuits, single-phase arranged as a threaphase double line, three mid~points of the three separated single-phase transformer windings dimensioned to compen~ sate the capacitive charging currents at the fault 40 choke coils connecting the mid-points of the three single-phase transformer windings at least at one end of the line, and earth leakage coils points when a short circuit occurs between any connected to the mid-point of said single-phase non-interlinked conductors or" the transmission transformer windings. line, and an earth leakage coil connected to the neutral point of said choke coil. 8. A high voltage transmission system com HIDDE KLAAS SCHRAGE.