N 05.16.16 CENTERPOINT 2 FIRE STATION HCSHEET1 SAN JUAN COUNTY 150725 HANDICAP REQUIREMENTS HC-1 BTW TEH 05.16.16 KEYED NOTES 23.01 23.02 23.03 23.04 23.06 23.07 23.08 23.09 23.10 23.11 23.12 23.13 23.14 23.15 23.16 23.17 23.18 23.19 23.20 12"x12" SLEEPING 107 A6 116CFM 12"x12" 6"x6" 6"x6" SLEEPING 108 A6 116CFM 12"x12" HALL 112 A6 146CFM R.R. 111 23.15 M/D B1 D D B1 LAUNDRY W F1 106 A6 40CFM B1 BUNKER 104 W 23.07 23.16 23.10 23.11 CO WX 24"x24" 23.09 A6 40CFM VEST 105 F2 A6 53CFM 23.18 B2 CX1 B1 14"x14" A6 45CFM 23.18 12"x12" A6 45CFM CX3 23.18 CX2 R.R. 113 8"DIA . . . 23.17 6"x6" T M/D A6 35CFM 23.18 23.02 23.08 APPARATUS BAY 103 CX4 R.R. 114 STOR. 115 23.20 23.01 RH 14"x14" CX5 23.19 23.04 M/D B1 12"x6" B1 14"x14" T IT 112A B1 SLEEPING 109 A6 116CFM 6"x6" 6"x6" B1 SLEEPING 110 A6 120CFM M/D CU2 6"x6" M/D CU1 23.14 12"x12" ROUTE 4" DIAMETER FLUE THROUGH THE ROOF. TERMINATE PER THE MANUFACTURER'S INSTRUCTION. ROUTE 4" DIAMETER OUTSIDE AIR INTAKE DUCT THROUGH THE ROOF. TERMINATE PER THE MANUFACTURER'S INSTRUCTION. DUCT RANGE HOOD, 7"DIA. THROUGH THE SIDEWALL. PROVIDE WALL CAP WITH BIRDSCREEN AND CAP. CONNECTION TO HOOD BY ARCH. ROUTE 4" RIGID DRYER DUCT THROUGH THE SIDEWALL. TERMINATE WITH ROUND WALL CAP WITH BUILT IN BACKDRAFT DAMPER AND PAINT PER ARCHITECT. CARBON MONOXIDE CONTROLLER PER SCHEDULE. CONNECT TO SENSORS, INTAKE LOUVER DAMPER AND WALL EXHAUSTER. COMBINATION CARBON MONOXIDE/NITROGEN DIOXIDE SENSOR MOUNTED AT 48"AFF. WITH 50' RADIUS RANGE. MOUNT RADIANT HEATER AT 6" BELOW THE JOISTS IN APPARATUS BAY. MAINTAIN 81" CLEAR TO COMBUSTIBLES BELOW THE UNIT. WALL EXHAUSTER TO BE ACTIVATED BY THE CO/NO2 CONTROLLER. INTERCONNECT WITH MOTORIZED DAMPER ON INTAKE LOUVER. MOUNT FAN TO BE CENTERED IN ARCHITECTURAL BAND. SEE ARCHITECTURAL ELEVATIONS. MOUNT LOUVER AT 14'-8" TO THE BOTTOM OF THE LOUVER. LOUVER TO BE CENTERED IN THE ARCHITECTURAL BAND ON THE OUTSIDE WALL. ROUTE 6" DIA. RIGID DRYER DUCT THROUGH THE SIDEWALL. TERMINATE WITH ROUND WALL CAP WITH BUILT IN BACKDRAFT DAMPER AND PAINT PER ARCHITECT. THERMOSTAT TO CONTROL RADIANT HEATER. RETURN AIR TO TRAVEL BELOW THE 1/4" UNDERCUT OF THE DOOR. MOUNT CONDENSING UNITS ON CONCRETE PAD. MOUNT AWAY FROM THE ROOF DRIP LINE. ROUTE BOILER FLUES THROUGH SIDEWALL. TERMINATE WITH SIDEWALL KIT PROVIDED WITH BOILER. ROUTE 8" DIA. FLUE FROM HOTSY THROUGH SIDEWALL. PROVIDE 5/8" PEX TUBING ON 9" CENTERS THROUGHOUT THE ENTIRE APPARATUS BAY. SEE THE BOILER PIPING SCHEMATIC AND RADIANT SLAB DETAIL FOR MORE INFORMATION. CEILING EXHAUSTER WITH BACKDRAFT DAMPER TO BE CONTROLLED BY OCCUPANCY SENSOR PROVIDE BY THE ELECTRICAL CONTRACTOR. ROUTE 6" DIAMETER EXHAUST DUCT UP THROUGH THE SIDEWALL. TERMINATE WITH WALL CAP WITH BIRDSCREEN. PAINT PER ARCHITECT. CEILING EXHAUSTER TO BE CONTROLLED BY THEMROSTAT. ROUTE 8" DIAMETER EXHAUST DUCT UP THROUGH THE ROOF TO ROOF CAP. 14"x14" 23.03 A8 200CFM A6 148CFM A6 148CFM A6 148CFM KITCHEN 100 23.12 T 23.06 T CO A8 200CFM DAY ROOM 101 A6 148CFM 1 23.13 A8 160CFM OFFICE 102 A6 148CFM MECHANICAL FLOOR PLAN 1/8" = 1'-0" 04/27/2016 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: MECHANICAL FLOOR PLAN Checked: Date: Drawn: DS DS 2016-05-11 Of: M101 MOTORIZED DAMPER, TYP.-2 RETURN AIR DUCT, SEE MECHANICAL PLAN FOR CONTINUATION TO RETURN GRILLE. MECHANICAL GENERAL NOTES NOTE: ROUTE DRAIN LINES TO NEAREST FLOOR SINK WITHIN THE BUILDING SEE PLAN FOR SIZE AND CONTINUATION. 1. PROVIDE AND INSTALL ALL MATERIAL AND EQUIPMENT AS REQUIRED BY UPC, UMC, NFPA, LIFE SAFETY CODE, GAS CODE, AND ALL OTHER LOCAL CODES AND ORDINANCES THAT APPLY. WHERE THERE IS A DISCREPANCY BETWEEN THE CODES OR ORDINANCES AND THE DRAWINGS, THE MORE STRINGENT APPLICATION SHALL APPLY. 2. LAYOUT AND INSTALL COMPLETE AND FUNCTIONAL MECHANICAL SYSTEMS, INCLUDING TEMPORARY CUTOFF OF EXISTING UTILITIES. PERFORM ALL CUTTING, PATCHING, AND REPAIR ASSOCIATED WITH INSTALLING THE SYSTEMS. AVOID INTERFERENCE WITH FITLER ACCESS. 3" PVC COMBUSTION AIR, TERMINATE PER MANUFACTURER'S INSTRUCTIONS. OSA FROM LOUVER 3" PVC FLUE TO CONCENTRIC ADAPTERS THRU ROOF, TERMINATE PER MANUFACTURER'S INSTRUCTIONS. F# FILTER ACCESS THIS SIDE 3. DX COIL FLEX. CONN., TYP. G 30" CLEAR SERVICE AREA SUPPLY AIR DUCT, SEE MECHANICAL PLAN FOR CONTINUATION. SEAL DRAIN PAN PENETRATIONS 1" GAS LINE WITH GAS COCK, UNION AND DRIP LEG. SEE PLUMBING PLAN FOR CONTINUATION SUSPEND FROM STRUCTURE ABOVE FROM VIBRATION ISOLATORS 4. 5. LINE SETS 1½" DEEP DRAIN PAN COIL DRAIN DRAIN PAN DRAIN D2 SCALE: NTS INSULATE ALL BRANCH DUCT AND COVER CONNECTIONS WITH DUCT WRAP. 1"x18 GAGE SHEETMETAL SUPPORT STRAP. ATTACH TO STRUCTURE ABOVE. 10' O.C. MINIMUM CONCRETE SLAB WIRE MESH OR REBAR HANGER STRAPS NO POP RIVETS ALLOWED. #10 x 3/4" SELF TAPPING CADIUM PLATED SCREWS TO ANCHOR STRAPS TO DUCT. (TYPICAL) VOLUME DAMPER V/D INSULATED FLEX DUCT SHEETMETAL SCREWS. NO SAGS OR SHARP TURNS MAX RUN LIMITED TO 4 FEET STRETCH DUCT RUN FOR SMOOTH INTERIOR. USE ADJUSTABLE ROUND SHEETMETAL DUCT ELBOW WHERE AN IMMEDIATE TURN FROM DIFFUSER. SUB SOIL STAINLESS STEEL ADJUSTABLE ADJUSTABLE DUCT BAND. (TYPICAL) PROVIDE ALL DUCTWORK CONNECTIONS AND TRANSITIONS AT GRILLES, DIFFUSERS, REGISTERS, FILTERS, COILS, AND OTHER LOCATIONS WHERE REQUIRED. CONSTRUCT ALL TRANSITIONS AND CONNECTIONS ACCORDING TO SMACNA STANDARDS. 7. TESTING AND BALANCING AGENCY: PROVIDE AND INSTALL SHEAVES AND ALL EQUIPMENT NECESSARY TO PROVIDE PLUS OR MINUS 10% OF THE CFM REQUIRED FROM EACH DIFFUSER AND REGISTER. 8. PROVIDE AND INSTALL ALL MECHANICAL EQUIPMENT, TRANSFORMERS, RELAYS, AND OTHER ELEMENTS NECESSARY FOR A COMPLETE OPERATING SYSTEM. COMPLETE ALL 24 VOLT CONTROL WIRING AND EQUIPMENT TO THE ABOVE. ALL LINE VOLTAGE WIRING TO THE ABOVE SHALL BE COMPLETED BY THE ELECTRICAL CONTRACTOR. REFER TO COORDINATION SCHEDULE ON ELECTRICAL DRAWINGS. 9. ALTER DIMENSIONS OF THE DUCTWORK IN THE CEILING SPACE FROM SIZES INDICATED ON THE DRAWINGS AT SPECIFIC LOCATIONS WHEN NECESSARY TO FIT THE DUCTWORK IN THE SPACE PROVIDED. REROUTE DUCTWORK IN CEILING SPACE TO AVOID OTHER MECHANICAL EQUIPMENT, LIGHT FIXTURES, ETC. MAINTAIN THE SAME FREE AREA AND SUBMIT PROPOSED CHANGES TO THE ENGINEER FOR APPROVAL. BE RESPONSIBLE FOR VERIFYING SPACE LIMITATIONS BEFORE DUCTWORK FABRICATION AND MAKE CHANGES ACCORDINGLY. PROVIDE ALL NECESSARY TRANSITIONS. B1 CO 12. PROVIDE ACOUSTICAL LINER ON ALL SOUND TRAPS AT ALL RETURN AIR GRILLES. PROVIDE ACOUSTICAL LINER ON ALL TRANSFER DUCTS. C1 RADIANT SLAB DETAIL C2 **ALTERNATE BID** SCALE: NTS TYPICAL DIFFUSER CONNECTION DETAIL ROUTE 3" PVC FLUE AND OUTSIDE AIR PIPE THROUGH SIDEWALL. TERMINATE EACH PER MANUFACTURER'S INSTRUCTIONS. 1" INSULATED LINE AIR PURGE VALVE WALL, SEE ARCHITECTURAL DRAWINGS ALUMINUM HOUSING 16. PROVIDE TURNING VANES IN ALL RECTANGULAR DUCTWORK AT ELBOWS AND TEES WHETHER SHOWN ON THE PLANS OR NOT. THE ONLY EXCEPTION IS RETURN AIR TRANSFER DUCTS BETWEEN ROOMS. VENTING THROUGH ROOF 3 _" 4 TO MAKEUP WATER ASSEMBLY, SEE PLUMBING FOR DETAIL. GAS ISOLATION VALVE GAS DIRT LEG FLASHING DISCHARGE HOOD 24" MINIMUM P/T TAP, TYPICAL WIRSBO TruFLOW 7 LOOP MANIFOLD WITH ISOLATION VALVES. 18. ALL PLENUM INSTALLED MATERIALS MUST BE PLENUM RATED OR WRAPPED IN A LISTED SYSTEM TO ACHIEVE A VALUE LOWER THAN 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT RATING. 2" CLEARANCE THIMBLE G T WX 4"∅ P1 INLINE BOILER INJECTION PUMP: CAST-IRON BODY, SELF LUBRICATING, NO MECHANICAL SEAL, FIELD REPLACEABLE CARTRIDGE. "TACO" **ALTERNATE BID#1** UNIT GPM TDH HP P1 7 30' 1/8 ROOM MOUNTED THERMOSTAT DRAIN LINE WITH NEUTRALIZER TO DRAIN T&P VALVE LINE FULL SIZE TO DRAIN (14) 5/8" PEX TUBING 250' APPARATUS BAY LOOPS B1 BOILER PIPING SCHEMATIC SCALE: NTS **ALTERNATE BID** BACK DRAFT DAMPER B2 WALL EXHAUST FAN DETAIL B3 SCALE: NTS SECURE TO STRUCTURE ABOVE AS RECOMMENDED BY SMACNA. 1"x16 GA. GALV. METAL STRAP SHEET METAL SCREW RIVET OR BOLT TO BOTH SIDES OF DUCT. MAX. SIDE TYPE "A" 8 FT. MAX. HANGER SPACING ALSO PROVIDE 3 HANGERS AT EACH TAKE-OFF OR BRANCH DOUBLE-NUT & WASHER @ END OF ROD MAX. SIDE FOR BRACING ANGLES SEE NOTES WX GARAGE EXHAUSTER: BELT DRIVE, PROPELLER EXHAUSTER WITH OPTIONAL WIRE GUARD AND WALL COLLAR. "COOK" ESP ("WC) UNIT MODEL CFM BHP HP ELEC. RPM CONTROLLED BY WX 20XMP 1962 0.35" .41 .50 120V/1∅ 1205 CO/NO2 SENSORS XT EXPANSION TANK: 5.0 GALLON ACCEPTANCE VOLUME "TACO" MODEL CX30-125 **ALTERNATE BID#1** A CEILING DIFFUSER: 4-WAY ADJUSTABLE VERTICAL/HORIZONTAL THROW STEEL 24"x24" FACE UNLESS OTHERWISE INDICATED ON PLAN, SEE PLAN FOR NECK SIZE, CFM AND CEILING TYPE. NC < 30. "KRUEGER" MODEL 1450 A B CEILING RETURN GRILLE: EGG-CRATE STYLE, 24"x24" FACE UNLESS OTHERWISE INDICATED ON PLAN. SEE PLAN FOR NECK SIZE, CFM AND CEILING TYPE. PROVIDE OBD WHEN GRILLE IS USED FOR EXHAUST. NC<30. "KRUEGER" MODEL EGC-5 LV LOUVER: ALUMINUM, WEATHER RESISTANT BLADE DESIGN, COLOR PER ARCHITECT. A MINIMUM OF 0.01OZ. OF WATER CARRY-OVER AT 1250 FPM FREE AREA VELOCITY 0.185"W.C. PRESSURE DROP AT 1250 FPM FREE AREA VELOCITY. "CESCO" MODEL X6D3 A2 M/D MOTORIZED DAMPER: EXTRUDED ALUMINUM OPPOSED BLADE WITH BELIMO 120V POWER, SPRING RETURN ACTUATOR. CLASS 1 MAXIMUM LEAKAGE RATE AT 4 CFM PER SQ.FT. AT 1.0"W.C. AMCA 500D TESTED. . "CESCO" MODEL CDA M036B MECHANICAL SYMBOLS LEGEND 12 18 30 42 54 60 84 96 96 A A A/B B B B C C D A6 100CFM CEILING DIFFUSER DESIGNATION = TYPE "A" WITH A 6" DIAMETER NECK AT CFM SHOWN UNION B1 CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 1'X1' GAS COCK B2 CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 2'X2' THERMOMETER C16"x16" 100CFM SIDEWALL DIFFUSER DESIGNATION = TYPE "C" WITH A 16"x16" FACE AT CFM SHOWN CHECK VALVE UNIT DESIGNATION 1 23.01 WATER HAMMER ARRESTER GATE VALVE OS&Y SOLENOID PLUG, CIRCUIT SETTER OR GAUGE COCK PRESSURE GAUGE SUPPLY DIFFUSER TYPE "B", "C" & "D" 8 FT. MAX. HANGER SPACING. RETURN GRILLE SIDEWALL SUPPLY 3-WAY VALVE BACKFLOW PREVENTER RELIEF VALVE FLEX DUCT SIDEWALL RETURN BALL VALVE CENTERS; TYPE "C" 1½"x1½"x3/16" MOTORIZED, FIRE, FIRE/SMOKE VOLUME DAMPER T DUCT HANGER DETAIL R CO 2 SCALE: NTS M088 H THERMOSTAT, REMOTE SENSOR OR HUMIDISTAT CARBON DIOXIDE SENSOR NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS GLOBE VALVE STRAINER STRAINER WITH DRAIN VALVE RODAHL & HUMMELL ARCHITECTURE, P.C. REDUCED PRESSURE BACKFLOW PREVENTER 2-WAY VALVE BUTTERFLY VALVE 04/27/2016 PRV KEYED NOTE DESIGNATION NOTES: 1. FOR SEVERAL DUCTS ON ONE HANGER TYPE "B"-"C" OR "D" MAY BE USED. SIZE OF HANGER WILL BE SELECTED ON THE SUM OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF DUCT SCHEDULE. 2. SCHEDULE FOR ANGLES FOR BRACING: TYPE "B" 1½"x1½"x1/8" ANGLE MAX. SPACING 8'-0" ANGLE MAX. SPACING 8'-0" CENTERS; TYPE "D" 2"x2"x¼" MAX. SPACING 4'-0" CENTERS. CONTROL B1 DELAY/RELY SCALE: NTS **DELETE IF BOILER SYSTEM ALTERNATE BID IS ACCEPTED** DUCT SCHEDULE DUCT DIMENSIONS TYPE INCHES HANGER UP THRU 14 20 32 44 56 62 86 OVER MODEL 0013 RADIANT TUBE HEATER DETAIL M053 HANGER ROD SIZE: TYPE "B" ¼" TYPE "C" ¼" TYPE "D" 3/8" ELEC 120V/1∅ RADIANT HEATERS: TWO-STAGE, PROPANE FIRED RADIANT TUBE HEATER. PROVIDE WALL-MOUNTED THERMOSTAT, OSA AND FLUE ROOF TERMINATION CAP ELECTRICAL = 120 V/1∅/5 A "REVERBERAY" MODEL **DELETE IF BOILER ALTERNATE IS ACCEPTED** HEATING WEIGHT INPUT MBH LENGTH COMMENTS UNIT MODEL HORIZONTAL MOUNTING 235LBS. RH DET3-50 125/82 30' TUBE HEATER SLOPE PER MANUFACTURER'S RECOMMENDATIONS AIR INTAKE COLLAR RPM 1725 RH B1 18" STAND DISTANCE FROM COIL FT. 25 20 FURNACE: PROPANE FIRED, ELECTRIC COOLING, INDIRECT FIRED, CONDENSING FURNACE CAPABLE OF INPUT AS LISTED. PROVIDE COOLING COIL LISTED, LINE SET, AUTO CHANGE OVER, WALL-MOUNTED PROGRAMMABLE SET BACK 24 V THERMOSTAT, FILTER AND CONCENTRIC VENTING KIT FOR VERTICAL VENTING. ORIFICE FOR 5600' ABOVE SEA LEVEL ELEC.=120 V/1∅. PROVIDE A CONDENSATE PUMP W/ 6' POWER CORD. "TRANE" HEAT COOL INPUT OA ESP WGT UNIT MODEL MBH MBH CFM CFM " W.C. LBS. MCA MOCP FLOW F1 TDX040A9H21B 22.1 40 872 120 0.50 135 9.7 15 HORIZ. F2 TDX060A9H31B 32.9 60 1300 198 0.90 155 9.7 15 HORIZ. P1 XT2 WGT. LBS. 130 261 F1F2 RP CHAIN MAX. AMPS MCA ELEC 30 18.0 208-230V/1∅ 60 35.0 208-230V/1∅ DRYER BOX: UPWARD FLOW, 2X4 WALL SIZE. "GUY GRAY" MODEL DB-350 17. FIELD VERIFY THAT ALL NEW DUCTWORK CAN FIT WITHIN THE SPACE PROVIDED PRIOR TO FABRICATING ANY NEW DUCTWORK. EXISTING DUCTWORK SHOWN IS FROM ORIGINAL AS-BUILT DRAWINGS AND NOT ALL CONFIGURATIONS HAVE BEEN VERIFIED. 4" GOOSENECK WITH INSECT SCREEN BALL VALVE, TYP. COOL MBH 21.1 32.9 DB M092 M168 CONTROL INTEGRAL CX1- CEILING EXHAUSTER: DIRECT DRIVE CEILING MOUNTED EXHAUSTER WITH CX5 BACKDRAFT DAMPER, VIBRATION ISOLATOR KIT, INTEGRAL GRILLE, AND BIRDSCREEN. 120 V/1∅ "COOK" ESP UNIT MODEL CFM ("WC) WATTS ACCESSORIES CONTROLLED BY CX1 GC124 75 0.25" 50 ROOF JACK OCCUPANCY SENSOR CX2 GC164 150 0.25" 109 OCCUPANCY SENSOR ROOF JACK 150 0.25" 109 CX3 GC164 OCCUPANCY SENSOR ROOF JACK CX4 GC124 75 0.25" 50 ROOF JACK OCCUPANCY SENSOR CX5 GC124 75 0.25" 50 WALL CAP THERMOSTAT 15. REVIEW THE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE ON THE ELECTRICAL DRAWINGS FOR CLARIFICATION OF WORK BETWEEN DISCIPLINES. SCALE: NTS EWT/LWT 90°F./110°F. CARBON MONOXIDE/NITROGEN DIOXIDE CONTROLLER: DIGITAL CONTROLLER WITH PROGRAMMING INTERFACE, TWO 24V OUTPUT RELAYS TO CONTROL FAN AND DAMPER, FIVE INPUT CONTACTS. PROVIDE REMOTE COMBINATION CO/NO2 SENSORS WITH MANUAL OVERRIDE CAPABILITIES. 120V/1A. "ARMSTRONG" AMC-1AD1 UNIT MODEL CU1 4TTB4024 CU2 4TTB3036 13. PROVIDE ONE UNION AT ALL VALVES OR SUITABLE MEANS OF REMOVAL WITHOUT PIPE CUTTING ON SCREWED PIPING. UNIONS REQUIRED ON COPPER PIPING AT EQUIPMENT CONNECTION. 14. PROVIDE CONDENSATE DRAINS FROM ALL REFRIGERATED AIR HANDLING UNITS TO THE NEAREST FLOOR SINK WITHIN THE BUILDING. OUTPUT MBH AMPS WEIGHT 63 0.5 125LBS. MBH 80 CU1- CONDENSING UNITS: 14 SEER REMOTE, AIR-COOLED CONDENSING UNITS FOR USE CU2 WITH FURNACE COILS LISTED. PROVIDE R-410A REFRIGERANT, CRANKCASE HEATER, AND LOW AMBIENT KIT. EAT=80°F./60°F., AMBIENT CONDITIONS = 94°F DB/63°F WB UNIT TO BE CONTROLLED BY THERMOSTAT PROVIDED WITH FURNACE. "TRANE" MODEL AS INDICATED. 11. COORDINATE ALL PROPOSED ROOF PENETRATIONS WITH GENERAL CONTRACTOR AND ARCHITECT AND RELOCATE IF NECESSARY. FACTORY FABRICATED ROUND TO RECTANGULAR OR SQUARE ADAPTER. SEE DIFFUSER SCHEDULE. BOILER: DIRECT VENT, CONDENSING, PROPANE, 95%+ EFF. BOILER CONSTRUCTED IN COMPLIANCE WITH SECTION IV OF ASME CODE. COMPLETE W/ ASME CSD-1 CONTROLS, 5:1 TURNDOWN MODULATING FIRING, HIGH LIMIT TEMP. CONTROLLER MANUAL RESET, FLOW SWITCH, LOW WATER CUTOFF, CAPACITY AT EWT/LWT= MBH OUTPUT AT 5500' ASL., HIGH & LOW GAS PRESSURE SWITCHES, CONDENSATE NEUTRALIZER KIT, SIDEWALL VENT TERMINATION KIT. 120V/1PH. "LOCHINVAR" KNIGHT **ALTERNATE BID#1** UNIT MODEL B1 KBN81 10. COORDINATE WITH THE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT LAYOUT OF DIFFUSERS, GRILLES AND CEILING MOUNTED EQUIPMENT. ROUND RIGID DUCT. SEE PLANS FOR SIZES INSULATION PER ARCH. R-13 DIFFUSER VERIFY THAT DIFFUSERS, REGISTERS, GRILLES, DUCTWORK AND ALL EQUIPMENT SPECIFIED IS CORRECT FOR FIELD INSTALLATION BEFORE ORDERING OR FABRICATING. PROVIDE A WRITTEN REQUEST FOR INFORMATION TO THE ENGINEER FOR A RULING ON HOW TO PROCEED IF CONDITIONS EXIST THAT WILL NOT ALLOW FOR THE INSTALLATION OF THE EQUIPMENT SPECIFIED. PROVIDE AND INSTALL DAMPERS IN THE BRANCH DUCTS, NEAR THE MAIN, SERVING DIFFUSERS AND GRILLES TO ALLOW PLUS OR MINUS 10% OF THE CFM REQUIRED FROM EACH DIFFUSER AND REGISTER AS LISTED ON THE PLANS. M152B 5/8" PEX WITH OXYGEN BARRIER, 9"O.C. EMBEDDED IN SLAB AS SHALLOW AS STRUCTURALLY FEASIBLE VIBRATIONALLY ISOLATE ALL EQUIPMENT AND PIPING FROM THE BUILDING STRUCTURE. COORDINATE TO ASSURE THAT AS QUIET AN OPERATING SYSTEM AS POSSIBLE IS INSTALLED. 6. HORIZONTAL FURNACE DETAIL MECHANICAL SCHEDULE # ARCHITECTURE 10"x10" CLEAR INSIDE DUCT DIMENSION (NEW) 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: MECHANICAL DETAILS AND SCHEDULES Checked: Date: Drawn: REV DS 2016-05-11 Of: M601 KEYED NOTES 22.01 22.02 22.03 22.04 22.05 22.06 22.07 22.08 22.09 22.10 22.28 GCO 22.04 22.45 WH2 22.33 22.14 22.22 22.36 22.35 22.19 FPHB 22.20 2"SS S2 LAUNDRY 106 22.17 1"CW 1"HW 3/4"HWR R.R. 113 22.44 L FD TMV 2"V FPHB L TMV WC R.R. SH 114 FD SH WC 1/2"HW 22.35 IMB FS 22.34 22.38 S1 TMV GD DW WC S3 22.15 U 3/4"CW 3/4"HWR 22.15 3"SS HB 3"VTR 22.17 22.15 22.16 3"VTR 2"V 22.24 1"A 22.30 3"VTR 22.12 2"V 22.40 1-1/2"LPG 1-1/4" FD WH1 22.33 4"SS 22.16 22.05 22.28 GCO 4"SS 22.43 DCO FCO 4"SS 4"SS 2"LPG 22.06 22.08 22.22 22.23 22.24 22.25 22.26 22.27 4"SS 22.27 22.42 22.07 22.28 22.29 22.30 22.31 22.32 22.33 DAY ROOM 101 22.31 22.31 22.31 3/4"A HB 22.23 22.29 FPHB 22.22 HB 22.34 22.35 22.36 FPHB 22.37 22.22 FCO OFFICE 102 22.20 22.21 2"V 22.11 STOR. 115 22.44 KITCHEN 100 2"V 2"LPG 22.14 22.16 22.11 22.12 22.13 22.14 22.15 22.16 22.17 22.18 22.19 22.41 BV 2"SS 2"VTR 1-1/4"CW 1"HW WCO L TMV 4"SS 22.25 1"CW 1"CW 3/4"LPG 3/4"A 1"CW APPARATUS BAY 103 1-1/2"CW 22.28 GCO 3"VTR 22.21 2"V FS 1"A 3/4"CW R.R. 111 FD 3/4"LPG S4 WCO ICE HB 22.26 1"CW HALL 112 VEST 105 1-1/2"CW 22.22 2"V W 22.13 1"LPG 22.13 IT 112A BUNKER FS 104 1-1/2"CW 22.18 SLEEPING 107 S5 FD2 22.10 22.23 3"SS SLEEPING 108 1"LPG SLEEPING 109 1"HW 1"LPG 22.32 SLEEPING 110 D D WB W 22.09 22.23 22.39 22.37 1-1/4"LPG 22.03 22.23 22.38 22.02 22.46 22.39 22.40 22.41 22.42 22.01 22.43 22.44 22.45 22.46 1 N 1-1/2"CW FROM SITE. FOR CONTINUATION SEE CIVIL DWGS. 1-1/2"CW RISE IN FURRED WALL TO ABOVE CEILING. 1-1/2"CW DROP TO WATER ENTRANCE. SEE DETAIL. 1-1/2"CW RISE FROM WATER ENTRANCE. 500 GALLON PRECAST OIL INTERCEPTOR. SEE DETAIL. 2-WAY CLEAN-OUT TO GRADE. SEE DETAIL. 2"LPG BELOW GRADE (BY PLUMBING CONTRACTOR) FROM LPG TANK ON SITE. SEE CIVIL DWGS. FOR LPG TANK LOCATION. 2"LPG RISE FROM BELOW GRADE TO SHUT-OFF VALVE AT 16" ABOVE GRADE. OFFSET AT 24" ABOVE GRADE THROUGH WALL INTO BUILDING AND RISE TO HIGH STRUCTURE. 1-1/4"LPG DROP TO HOTSY MACHINE. SEE GAS CONNECTION DETAIL. 1"CW DROP. MAKE CONNECTION TO HOTSY MACHINE/HOSE REEL (BY OWNER) VIA BALL VALVE AND PER MANUFACTURER'S RECOMMENDATION. VERIFY EXACT REQUIREMENTS WITH OWNER. 3/4"LPG DROP TO RADIANT HEATER. SEE GAS CONNECTION DETAIL. 1-1/4"LPG DROP ALONG WALL, THROUGH WALL INTO LOWER CEILING SPACE. 3/4"LPG CONNECTION TO FURNACE ABOVE CEILING. SEE GAS CONNECTION DETAIL. 1"LPG DROP TO WATER HEATER (WH). SEE GAS CONNECTION DETAIL. 3/4"CW DROP, 3"SS DOWN AND 2"V RISE FROM WATER CLOSET. 1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM LAVATORY. 1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 2"V RISE FROM SHOWER. 1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM SINK. 1"CW, 1"HW DROP EXPOSED TO PRECAST FLOOR SINK (S5) FAUCET. SEE SCHEDULE. 3"SS DOWN AND 2"V RISE FROM SINK DRAIN (FD2). 3/4"CW, 3/4"HW DROP, 2"SS DOWN AND 2"V RISE FROM WASHER BOX (WB). 3/4"CW, 3/4"HW DROP TO WASHER/EXTRACTOR AND FULL SIZE INDIRECT WASTE TO FLOOR SINK. 3/4"CW DROP TO HOSE BIBB(S). 3/4"A DROP TO AIR OUTLET. SEE DETAIL. 3/4"CW DROP, 2"SS DOWN AND 2"V RISE FROM URINAL. 1/2"CW DROP TO ICE MAKER BOX (IMB) AND FULL SIZE INDIRECT WASTE TO FLOOR SINK. 1"A RISE FROM (OWNER FURNISHED/CONTRACTOR INSTALLED) AIR COMPRESSOR. SEE DETAIL. 4"TRAPPED CONNECTION TO TRENCH DRAIN. COORDINATE WITH GENERAL CONTRACTOR. EXTEND 2"V RISE ALONG WALL AND OFFSET OVERHEAD TO 3"VTR. GRADE CLEANOUT. SEE DETAIL. 1-1/2"CW OFFSET THROUGH WALL AND RISE TO HIGH STRUCTURE. (2)2"V RISE FROM BELOW GRADE. CONNECT AT 42" ABOVE FLOOR AND 2"V RISE TO HIGH STRUCTURE. OFFSET TO 3"VTR. COORDINATE PIPE ROUTING OVER PATH OF OVERHEAD DOOR TRAVEL. 3"SS DOWN AND 2"V RISE FROM FLOOR SINK. 1"CW DROP, 1"HW RISE FROM WATER HEATER AND 3/4"HWR DOWN (WH1 ONLY) TO WATER HEATER RETURN CONNECTION. ROUTE 3"PVC FLUE AND INTAKE THROUGH ROOF. TERMINATE WITH FACTORY VENT KIT. SEE WATER HEATER DETAIL SHEET P601. 3/4"LPG DROP TO STOVE. SEE GAS CONNECTION DETAIL. 2"SS DOWN AND 2"V RISE FROM FLOOR SINK. OFFSET 3/4"CW, 3/4"HW TO SINK (S4) FAUCET AND PRE-RINSE. COLLECT FULL SIZE (COPPER) INDIRECT WAASTE FROM EACH COMPARTMENT OF SINK AND ROUTE TO PRECAST FLOOR SINK. TERMINATE WITH ELBOW TURNED DOWN. 3/4"CW OFFSET AND CONNECTION TO ICE MACHINE VIA BALL VALVE AND BACKFLOW PREVENTOR (BFP2), AND FULL SIZE INDIRECT WASTE TO FLOOR SINK. 1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM SINK. OFFSET TO SINK AS REQUIRED. PROVIDE SEPARATE HW STOP VALVE AND CONNECT TO ADJACENT DISHWASHER. ROUTE DISHWASHER DRAIN TO DISPOSER DISHWASHER PORT. 3/4"LPG DROP TO BOILER. SEE GAS CONNECTION DETAIL. 1-1/4"CW DROP TO LOWER CEILING. 3/4"CW, 3/4"HW DROP, 3"SS DOWN AND 2"V RISE FROM MOP SINK (S3). 1-1/2"CW CONNECTION (VALVED) TO BFP3 OVERHEAD. EXTEND FIRE SPRINKLER PIPING TO SEMI-RECESSED FIRE SPRINKLER HEADS LOCATED IN SLEEPING ROOMS, HALL, RR113 AND RR1114 CEILINGS PER NFPA 13R. 4"SS TO SITE. FOR CONTINUATION SEE CIVIL DWGS. 2"V RISE TO ABOVE CEILING. 3/4"LPG DROP TO DRYER. SEE GAS CONNECTION DETAIL. BUILDING SHUT-OFF VALVE IN VALVE BOX. PLUMBING FLOOR PLAN 1/8" = 1'-0" 24" HOLE FOR MANHOLE RING AND COVER - GASTIGHT. INLET 2" COUPLING FOR VENT INLET & OUTLET- 4" PVC COUPLING 4" SAND/OIL INTERCEPTOR 1. PROVIDE PARTITION BAFFLES, AND INLET AND OUTLET BAFFLES WITH VENTS. 2. TRAFFIC RATED 3. DESIGN IN ACCORDANCE WITH 2003 ICP SECTION 1017.1 OUTLET CLEAN-OUT GASTIGHT 24" MANHOLE COVER 77" INLET CAST IRON FITTINGS 4" MIN. 4" GRADE VARIABLE AS SHALLOW AS POSSIBLE TO SEWER 12" OIL EFFLUENT SAND 6" 4/27/16 RODAHL & HUMMELL ARCHITECTURE, P.C. 115" 61" A1 2 SAND/OIL INTERCEPTOR SCALE: N.T.S. 500 GALLON CAPACITY ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 PLBG OI DTL CENTERPOINT 2 FIRE STATION 1/8" = 1'-0" SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: PLUMBING FLOOR PLAN Checked: Date: Drawn: Author Checker 2016-05-11 Of: P101 PLUMBING GENERAL NOTES LPG 3"INTAKE/3"VENT, TERMINATE PER MANUFACTURER'S RECOMMENDATION 1-1/2" MIN. #3 REBAR #3 BRAZED TO C.I., (TYP) COMPLETE ALL WORK IN FULL COMPLIANCE WITH THE UMC, UPC, UBC, LIFE SAFETY CODE, N.F.P.A. AND ALL LOCAL CODES AND ORDINANCES. 2. CAREFULLY LAYOUT AND INSTALL THE PLUMBING SYSTEMS INCLUDING ALL COORDINATION WITH MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT AND ANY OTHER EQUIPMENT THAT MAY REQUIRE COORDINATION EFFORTS. COORDINATE TEMPORARY CUT-OFF OF WATER AND SEWER WITH UTILITY PROVIDERS. PERFORM ALL NECESSARY TRENCHING, BACK FILLING, CUTTING, PATCHING, REPAIRING, ETC. ASSOCIATED WITH THE INSTALLATION OF THE PLUMBING SYSTEM SHOWN ON THE PLANS AND DESCRIBED IN THE SPECIFICATIONS. WH1 ADJUSTABLE CAST IRON FERRULE WITH SCORIATED SECURED TOP (TYP.) BRONZE TAPERED THREADED PLUG (TYP.) 1" WH2 1" CHAMFER 6" 3. VERIFY ALL INVERTS BEFORE ROUTING ANY AND ALL PIPING. NO COMPENSATION WILL BE MADE FOR THE CONTRACTOR'S FAILURE TO COORDINATE WORK WITH SITE CONDITIONS. BECOME TOTALLY FAMILIAR WITH ALL ASPECTS OF THE WORK AND ALL CONSTRAINTS AND LIMITATIONS OF THE WORK REQUIRED. 4. ROUTE PIPING AS NEARLY AS POSSIBLE TO THE ROUTING INDICATED ON THE PLANS, BUT MAKE MINOR CHANGES IN ROUTING TO ACCOMMODATE THE CONDITIONS AT THE SITE. DO NOT UNDERTAKE MAJOR REROUTING OF PIPING WITHOUT WRITTEN APPROVAL FROM ENGINEER. MAKE ALL REQUIRED TRANSITIONS, OFFSETS, MINOR RE-LOCATIONS, AND ALL ASSOCIATED FITTINGS, PIPING, AND EQUIPMENT TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM. MIN FINISHED GRADE CHECK VALVE, TYP. TMV WB SOIL PIPE RISER (TYP). TWO-WAY CLEANOUT ROUTE DRAIN TO FLOOR SINK VIA CONDENSATE NEUTRALIZATION KIT 3/4" EXPANSION TANK (XT) MAIN 5. WATER HEATER DETAIL D1 DOUBLE CLEANOUT TO GRADE D2 SCALE: N.T.S. SCALE: N.T.S. P?? P04 PROVIDE A POLISHED SCORIATED NICKEL-BRONZE ACCESS COVER AND FRAME. PROVIDE CARPET IN CARPETED AREAS 1-1/2" CW TO BUILDING 6. FINISH FLOOR CW SERVICE (OVERHEAD) FROM SITE, SEE PLAN #3 BRAZED TO C.I. C.O. TO FINISHED FLOOR 1-1/2" 4" 2500 PSI CONCRETE. 1" CHAMFER MIN. PRESSURE GAUGE STRAINER 16" SQ. COMPACTED SUBGRADE THE PROXIMITY OF WATER AND SEWER LINES SHALL BE AS FOLLOWS, UNLESS WRITTEN APPROVAL FROM THE STATE HEALTH DEPARTMENT SPECIFIES DIFFERENT CONDITIONS: WHENEVER POSSIBLE, IT IS DESIRABLE TO LAY PARALLEL WATER AND SEWER LINES AT LEAST TEN FEET APART HORIZONTALLY, AND THE WATER LINE SHOULD BE AT A HIGHER ELEVATION THAN THE SEWER LINE. IF THIS IS NOT POSSIBLE, SEPARATE TRENCHES WILL BE REQUIRED IN ALL CASES (THIS SHALL BE EFFECTIVE EVEN THOUGH ONE LINE HAS BEEN INSTALLED PRIOR TO THE OTHER), AND THE WATER LINE SHALL BE AT LEAST ONE FOOT ABOVE THE SEWER LINE. WHERE LINES INTERSECT THE WATER LINE SHALL BE SLEEVED FOR TEN FEET ON EACH SIDE OF THE INTERSECTION. ALL CONTRACTORS BIDDING ON THIS PROJECT ARE CAUTIONED TO VISIT THE SITE AND MAKE ALL NECESSARY INQUIRIES TO DETERMINE THE EXISTING CONDITIONS PRIOR TO SUBMITTING THEIR BIDS. NO SUBSEQUENT ALLOWANCE WILL BE MADE TO COMPENSATE FOR LACK OF PRE-BID INSPECTIONS BY THE SUCCESSFUL CONTRACTOR. ANY LINES ENCOUNTERED WHICH MAY INTERFERE WITH NEW CONSTRUCTION SHALL BE RELOCATED IF ACTIVE AND ABANDONED IF INACTIVE BY THIS CONTRACTOR UNDER THIS CONTRACT BY FIRST CONTACTING THE ARCHITECT FOR A RULING AS TO THEIR REMOVAL, RELOCATION, ETC. 7. PROVIDE ACCESS PANELS TO ALL INACCESSIBLE PLUMBING EQUIPMENT. 8. INSULATE ALL NEWLY INSTALLED PIPING (DOMESTIC HOT, COLD, AND RECIRC. WATER) IN THE BUILDING. LABEL PIPE WITH FLUID TYPE AND FLOW DIRECTION. 9. PROVIDE WALL CLEANOUTS AT ALL URINALS, SINKS AND LAVATORIES. WH1 TANKLESS WATER HEATER: GAS-FIRED CONDENSING WALL MOUNTED WATER HEATER, 67°F TEMPERATURE RISE @ 5.6 GPM FLOW, 199.9 MBH INPUT, INTEGRAL CIRCULATING PUMP, DUAL STAINLESS STEEL HEAT EXCHANGERS, INTERNAL CONTROL SYSTEM, 2" PVC VENT KIT AND CONDENSATE NEUTRALIZATION KIT. ELECTRICAL: 120V-1∅-60Hz. "NAVIEN" MODEL NPE-240A WH2 TANKLESS WATER HEATER: GAS-FIRED CONDENSING WALL MOUNTED WATER HEATER, 67°F TEMPERATURE RISE @ 5.7 GPM FLOW, 199.9 MBH INPUT, DUAL STAINLESS STEEL HEAT EXCHANGERS, INTERNAL CONTROL SYSTEM, 2" PVC VENT KIT AND CONDENSATE NEUTRALIZATION KIT. ELECTRICAL: 120V-1∅-60Hz. "NAVIEN" MODEL NPE-240S WHA XT WATER HAMMER ARRESTER: PRE-CHARGED AIR CHAMBER PERMANENTLY SEALED FROM WATER SYSTEM, BALL VALVE FOR ISOLATION, NPT BRASS ADAPTER. PROVIDE A 12"x12" ACCESS PANEL. "WATTS" SERIES 15. EXPANSION TANK: POTABLE WATER USE, 175 MAX. WORKING PRESSURE, 2.0 GALLONS TOTAL VOLUME, 40 PSIG FACTORY PRECHARGE. "AMTROL" MODEL ST-5C 1-1/2" SYMBOL DESCRIPTION GROUTED PLUG WHERE C.O. OCCURS AT END OF LINE. 45 DEGREE `Y' BRANCH. BACKFLOW PREVENTER (BFP1) WATER ENTRY ASSEMBLY C2 SCALE: N.T.S. L LAVATORY: A.D.A. COMPLIANT,COUNTERTOP, VITREOUS CHINA,, 4" FAUCET CENTERS, CHROME PLATED GRID DRAIN, OFFSET TAILPIECE "TRUE-BRO" LAV GUARD "AMERICAN STANDARD" 7385.003 SINGLE LEVER CHROME PLATED FAUCET LESS POP-UP DRAIN, 1.5 GPM AERATOR. "AMERICAN STANDARD" AQUALYN 0476.028 WASTE = 2 IN., VENT = 1 - 1/2 IN., CW = 1/2 IN. HW = 1/2" S1 SINK: (KITCHEN) A.D.A. COMPLIANT, STAINLESS STEEL TWO COMPARTMENT SINK CONSTRUCTED OF 18 GAUGE TYPE 302 SS, REAR OFFSET DRAIN LOCATION. ELKAY LKA-4100 FAUCET LESS SPRAYER, 1.5 GPM AERATOR. "ELKAY" MODEL LRAD-3319 (6-1/2" DEEP). WASTE = 2"., VENT = 1-1/2"., CW = 1/2"; HW = 1/2" S2 SINK: (LAUNDRY) A.D.A. COMPLIANT, STAINLESS STEEL SINGLE COMPARTMENT SINK CONSTRUCTED OF 18 GAUGE TYPE 302 SS, REAR OFFSET DRAIN LOCATION. ELKAY LKA-4100 FAUCET LESS SPRAYER, 1.5 GPM AERATOR. "ELKAY" MODEL LRAD-2522 (6-1/2" DEEP). WASTE = 2"., VENT = 1-1/2"., CW = 1/2"; HW = 1/2" S3 MOP SINK: 24"x24" PRECAST TERRAZZO, STAINLESS STEEL CAPS ON ALL CURBS, WALL MOUNTED 3 STATION MOP HOLDER. RIGID SPOUT, VACUUM BREAKER, PAIL HOOK, WALL BRACE AND 3/4" THREADED HOSE OUTLET. "CHICAGO" MODEL 445-897SRCXKCP FAUCET. "FIAT" MODEL TSB100 WASTE = 3 IN., VENT = 2 IN., CW & HW = 3/4 IN. S4 SINK: (APPARATUS BAY) 3-COMPARTMENT TYPE 304 16 GA. STAINLESS STEEL SINK WITH DUAL DRAINBOARDS, SEAMLESS CONSTRUCTED, REAR 8" BACKSPLASH WITH (2) 8" CENTER PUNCHES FITTED WITH K-112 12" SWINGSPOUT FAUCET AND DTA-53 PRE-RINSE SPRAY. (3)18"x 24" COMPARTMENTS EACH FITTED WITH TWIST HANDLE DRAIN VALVE WITH STRAINER, "ADVANCE-TABCO" 93-63-54-18RL INDIRECT WASTE = 2" (X3)., CW = 3/4"; HW = 3/4" S5 PRECAST FLOOR SINK: PRECAST CURBS BY GENERAL CONTRACTOR. PROVIDE TRIM INCLUDING RIGID SPOUT FAUCET WITH VACUUM BREAKER, PAIL HOOK, WALL BRACE AND 3/4" THREADED HOSE OUTLET. ALSO SEE FD2 SCHEDULE. "CHICAGO" MODEL 445-897SRCXKCP FAUCET. WASTE = 3 IN., VENT = 2 IN., CW & HW = 3/4 IN. SH SHOWER, PRESSURE BALANCING VALVE WITH LEVER HANDLE, INTEGRAL STOPS, 30"SLIDE BAR AND 69"METAL HOSE, 1.5GPM FLOW CONTROL, 36"x 36x 75-3/4" HIGH MOLDED VIKRELL 3-WALL MODULAR SURROUND AND BASE. "MOEN" 8346EP15 TRIM, "STERLING" 72100100 WASTE = 2 IN., VENT = 1 - 1/2 IN., CW & HW = 1/2 IN. HOT WATER SUPPLY (140°F) (HW) HOT WATER RETURN (HWR) LIQUID PROPANE GAS (11"w.c.) LPG 11. PRESSURE TEST, FLUSH AND DISINFECT ALL DOMESTIC WATER PIPING PER CHAPTER 6 OF THE PLUMBING CODE PRIOR TO CALLING FOR FINAL INSPECTION. COMPRESSED AIR A 12. TERMINATE ALL PLUMBING VENTS NOT LESS THAN 25' FROM ANY VENTILATION AIR INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR AND MECHANICAL DWGS. TERMINATE WITH VENT CAP (VC). SANITARY WASTE (ABOVE FLOOR) SAN SANITARY WASTE (SAN) (BELOW FLOOR) CLEANOUT DETAIL CHECK VALVE SCALE: N.T.S. BFP1 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, LEAD FREE, BRONZE BODY WITH STAINLESS STEEL SPRINGS, REDUCED PRESSURE PRINCIPLE, TWO "Y" PATTERN CHECK VALVES AND ONE HYDRAULICALLY DEPENDENT DIFFERENTIAL RELIEF VALVE, BALL SHUT OFF VALVES AND FUNNEL DRAIN KIT. ASSE STANDARD 1013. "FEBCO" MODEL LF825Y BFP2 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, DUAL CHECK, LEAD FREE, IN-LINE CONTINUOUS PRESSURE APPLICATION. "WATTS" LF7 GAS COCK BFP3 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, DOUBLE CHECK, LEAD FREE CAST COPPER BODY, STAINLESS STEEL SPRINGS, 175 PSI MAX. WORKING PRESSURE, ASSE 1015. "FEBCO" LF850 RELIEF VALVE CO EXTERIOR CLEANOUT: PVC OR ABS FEMALE ADAPTER WITH CLEANOUT PLUG. LOCATED 2 IN. BELOW GRADE. CO INTERIOR FLOOR CLEAN OUT: CAST IRON CLEAN OUT WITH THREADED ADJUSTABLE HOUSING, SV HUB OUTLET, FLANGED FERRULE WITH PLUG AND ROUND SCORIATED POLISHED BRONZE SECURED TOP. "ZURN" MODEL ZB-1400- (VERIFY SURFACE TYPE) FD FLOOR DRAIN: CAST IRON FLOOR DRAIN WITH TRAP GUARD, VANDAL PROOF SECURED TOP, NICKEL BRONZE STRAINER. "ZURN" MODEL Z-415 W/ TYPE B STRAINER WASTE = 2 IN., VENT = 2 IN. FD2 FLOOR DRAIN: CAST IRON FLOOR DRAIN WITH TRAP GUARD, VANDAL PROOF SECURED TOP, NICKEL BRONZE STRAINER. "ZURN" MODEL Z-415 W/ TYPE B STRAINER WASTE = 3 IN., VENT = 2 IN. STRAINER TERMINATE WITH VENT CAP (VC) UNION WATER HAMMER ARRESTER SEE PLAN FOR CONTINUATION PRESSURE SWITCH, GAUGE VALVE, UNIONS AND FLEX HOSE BY COMPRESSOR MANUFACTURER RUBBER BOOT 12" MIN. SEAL WATERTIGHT ROOFING OVER BASE CONTINUOUS RUBBER BOOT URINAL: A.D.A. COMPLIANT, VITREOUS CHINA W/ WASHOUT ACTION, 3/4" TOP SPUD INLET 2 IN. OUTLET, ADJUSTABLE FLOOR SUPPORTED WALL CARRIER, "AMERICAN STANDARD" 6045.013.002 1.0 PINT MANUAL FLUSH VALVE. "AMERICAN STANDARD" WASHBROOK MODEL 6590.125 WASTE = 2 IN., VENT = 1-1/2 IN., CW = 1 IN. COLD WATER (CW) BALL VALVE SOLENOID PRV 1" BACKFLOW PREVENTER CLEANOUT TEE PRESSURE GUAGE 0-160 PSI AIR COMPRESSOR (OWNER FURNISHED) SEE ARCH. DWG's FOR ROOF CONST. 8" MIN. U KEYED NOTE VENT 10. PERFORM PRESSURE TEST OF WASTE/VENT LINE PER CODE. COMPLETE A SUCCESSFUL TEST PRIOR TO COVERING THE WORK. TO FLOOR SINK FLUSH TANK WATER CLOSET: A.D.A COMPLIANT, 1.28 GPF FLOOR MOUNTED VITREOUS CHINA, SIPHON JET, ELONGATED TOILET, EVERCLEAN SURFACE. OPEN FRONT SEAT LESS COVER, BOLT CAPS. FLUSH LEVER OPPOSITE SIDEWALL. "AMERICAN STANDARD" CADET MODEL 3339.128. WASTE = 3", VENT = 2", CW = 3/4" UNIT DESIGNATION 1/8 BEND SOIL PIPE RISER. WC PLUMBING SYMBOLS LEGEND C.O. TO GRADE 1-#3 REBAR, CONT. C1 THERMOSTATIC MIXING VALVE: 1/2"-1" (SEE PLAN FOR SIZE)ASSE 1070 AND 1017, POINT-OF-USE MIXING VALVE. SET AT 105°F. COLD WATER 50°F.; HOT WATER 140°F.; "APOLLO" MODEL MVB POWDER COATED METAL WASHER BOX WITH QUARTER WASHER BOX: WHITE TURN VALVES AND WATER HAMMER ARRESTORS "GUY GRAY" MODEL 82158 WASTE = 2 IN.; VENT = 2 IN.; CW = 3/4 IN.; HW = 3/4 IN. WCO WALL CLEANOUT: BRASS PLUG WITH ROUND STAINLESS STEEL SECURED ACCESS COVER, SEE PLAN FOR SIZE. "ZURN" MODEL Z-1468 UNION, TYP. BALL VALVE, TYP. SCHEDULE SCHEDULE 1. 3000 PSI CONCRETE 3/4" GAS COCK 18" MIN 24" MIN STAINLESS STEEL ACCESS COVER W/ COUNTERSUNK SCREW FLOOR SINK VENT THRU ROOF DCO BLOW DOWN VALVE CO INCREASE TO NEXT LARGER PIPE SIZE (EXCEPT 4") FINISHED WALL NEOPRENE VIBRATION ISOLATION PAD (YTP.) VENT, REQUIRED SIZE FPHB HOSE BIBB: FREEZELESS, AUTOMATIC DRAINING, WALL HYDRANT: BRASS WITH POLISHED CHROME PLEATED CASTING, KEY OPERATED, AND CHROME PLATE VACUUM BREAKER, 3/4" FPT, MIN. 12" LENGTH "WOODFORD" MODEL 67-3/4 IN DOUBLE CLEAN OUT CLEAN OUT M METER (E) (EXISTING) IW INDIRECT WASTE GC GENERAL CONTRACTOR GD GARBAGE DISPOSER, WITH DISHWASHER PORT WHERE APPLICABLE. KITCHEN AID KCD1075B (BY G.C., SEE ARCH.). ELECTRICAL: 115V-1PH, 3/4 HP HB HOSE BIBB: ANTI-CONTAMINATION CLOSE COUPLED TRIMLINE WALL HYDRANT EQUIPPED WITH A VACUUM BREAKER-BACKFLOW PREVENTER, CAPABLE OF FITTING IN A 4" WALL THICKNESS. "WOODFORD" MODEL B75 IMB B1 VENT THRU ROOF DETAIL B2 SCALE: N.T.S. AIR COMPRESSOR PIPING B3 SCALE: N.T.S. P40 WALL CLEANOUT DETAIL SCALE: N.T.S. P41 P95 PC PLUMBING CONTRACTOR TYP TYPICAL ICE MAKER BOX: 20 GAUGE, GALVANIZED STEEL RECESSED BOX WITH OUTLET ANGLE VALVE. "GUY GRAY" MODEL BIM875 1/ " 2 INLET, 1/ " 4 OI NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS SAND/OIL INTERCEPTOR: 500 GALLON PRECAST TRAFFIC RATED CONCRETE INTERCEPTOR, GAS TIGHT BOLTED MANHOLE COVERS, EXTENSION RINGS AS REQUIRED. "FOUR CORNERS PRECAST" WATER HAMMER ARRESTOR BALL VALVE 1" 1/2" CW QUICK CONNECT COUPLER PROVIDE GAS PRESSURE REGULATOR (WHERE REQUIRED) VENTED TO OUTDOORS WHEN LOCATED INSIDE GAS COCK 12" SWINGSPOUT FAUCET 18"DRAINBOARD 8" HIGH BACKSPLASH 2" VENT 1" 4/27/16 GAS CONNECTOR OR RIGID PIPE 1/2" HW CLEANOUT 14" 3/4"CA PRESSURE REGULATOR WITH PRESSURE GAUGE (0-175 PSI) PRE-RINSE SPRAY WASHING MACHINE SUPPLY AND DRAIN UNIT TWIST HANDLE DRAIN (TYP. 3) 2" STANDPIPE MIN. 6" DIRT LEG MIN. 6" DIRT LEG FINISHED FLOOR UNION ARCHITECTURE UNION 2" WASTE 2"INDIRECT WASTE ROUTED TO ADJACENT PRECAST FLOOR SINK LONG RADIUS THREADED CAP A1 COMPRESSED AIR DROP DETAIL A2 SCALE: N.T.S. P?? RODAHL & HUMMELL ARCHITECTURE, P.C. 18"W x 24" COMPARTMENT X3 WASHER BOX CONNECTION A3 SCALE: N.T.S. P42 GAS CONNECTION DETAIL SCALE: N.T.S. A4 SINK S4 DETAIL SCALE: N.T.S. ADJUSTABLE BULLET FEET) 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: PLUMBING DETAILS AND SCHEDULES Checked: Date: Drawn: Author Checker 2016-05-11 Of: P601 ELECTRICAL SYMBOLS LEGEND FIRE ALARM SWITCHING LIGHTING RECTANGULAR FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) A FACP FIRE ALARM (FA) CONTROL PANEL ANN FA ANNUNCIATOR ROUND FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) A A B C TRACK LIGHTING (LENGTH AS SHOWN, HEADS NOT TO SCALE) A POLE MOUNTED FIXTURE (HEADS NOT TO SCALE) ARM SYMBOL ADDITION INDICATES WALL MOUNTING A A DOT SYMBOL ADDITION INDICATES PENDANT MOUNTING A A FA CEILING MOUNTED FA HORN/STROBE F FA ADA STROBE F FA CEILING MOUNTED FA STROBE F FA FIRE ALARM PULL STATION F/S FA FIRE/SMOKE DAMPER RI FA REMOTE INDICATOR FS FA FLOW SWITCH TS FA TAMPER SWITCH 1. PROVIDE, INSTALL, AND COORDINATE ALL WORK INDICATED BY THESE DRAWINGS. THIS CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS IN ADDITION TO PERFORMING ALL OPERATIONS INCLUDING CUTTING, CHANNELING & UNDERGROUND TRENCHING, BACK FILL & TAMPING NECESSARY FOR THE INSTALLATION OF COMPLETE POWER, LIGHTING, OR OTHER SYSTEMS AS SHOWN. 2. PERFORM ALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER IN FULL COMPLIANCE WITH ALL APPLICABLE, ADOPTED, CODES; INCLUDING, BUT NOT LIMITED TO THE NATIONAL ELECTRICAL CODE (NEC), UBC, IBC, NFPA, AND ADA. ALL LOCAL AND STATE REQUIREMENTS WILL BE OBSERVED DURING THE PERFORMANCE OF THIS WORK. 3. NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND ANY ASSOCIATED LEGAL OR SAFETY REQUIREMENTS ARE DETECTED. THE ENGINEER WILL MODIFY THE CONTRACT DOCUMENTS ACCORDINGLY. IF THE CONTRACTOR PROCEEDS W/ ANY WORK WHICH IS IN VARIANCE OF KNOWN LEGAL OR SAFETY REQUIREMENTS, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR THIS WORK AND WILL PROMPTLY CORRECT THE WORK, WHEN NOTIFIED WITHOUT ADDITIONAL COST TO THE OWNER. 4. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BEFORE PROCEEDING. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE PLUS PRIOR DETERMINATION OF TIME AND COST TO THE OWNER. 5. CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FOREIGN MATTER, PAINT, OR DIRT, GREASE, UNNEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FOR THE PREMISES. WALL OCCUPANCY SENSOR (ARROWS INDICATE VIEW) 6. COORDINATE ALL PHASES OF THE ELECTRICAL WORK WITH THE ARCHITECT AND GENERAL CONTRACTOR. PERFORM WORK TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER. POWER OUTLETS 7. OBTAIN, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO ASSURE THAT PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT ELECTRICAL CONTRACTOR'S EXPENSE. 8. VERIFY ELECTRICAL DEVICE LOCATIONS WITH ARCHITECTURAL CASE WORK DETAILS PRIOR TO ANY ROUGH-IN. 9. VERIFY FINAL LOCATIONS OF ALL SINKS WITH THE PLUMBING CONTRACTOR PRIOR TO ROUGH-IN. ANY ELECTRICAL DEVICES LOCATED ABOVE COUNTER AND BEHIND FINAL SINK LOCATIONS WILL BE SHIFTED A MINIMUM OF 8'' TO EITHER SIDE OF SINK. ANY ELECTRICAL DEVICES LEFT BEHIND SINK AT TIME OF FINAL ELECTRICAL WALK THROUGH WILL BE RELOCATED AT ELECTRICAL CONTRACTOR'S EXPENSE. 10. PRIOR TO INSTALLATION, THE OWNER RESERVES THE RIGHT TO RELOCATE ANY ELECTRICAL DEVICE, UP TO A DISTANCE OF 12", WITHOUT ADDITIONAL CHARGE. 11. FIELD VERIFY AND COORDINATE THE EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT WITH ALL TRADES PRIOR TO INSTALLATION. WHERE EXACT LOCATIONS ARE NECESSARY, THEY ARE DIMENSIONED ON THESE DRAWINGS. WHERE THERE IS A QUESTION OF ADEQUATE CLEARANCE OR COORDINATION BETWEEN TRADES, THIS CONTRACTOR WILL PREPARE AS BUILT DRAWINGS FOR ENGINEERS REVIEW. 12. CONTACT UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV., ETC.) PRIOR TO TRENCHING IN ORDER TO IDENTIFY UNDERGROUND UTILITIES. CONTRACTOR SHALL LOCATE SECONDARY SERVICE FEEDERS, UNDER- GROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC., PRIOR TO TRENCHING. ANY CUT DAMAGED UNDER- GROUND UTILITIES SHALL REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE. 13. UTILIZE COPPER CONDUCTORS, RATED FOR 600 VOLTS, TYPE THHN/THWN INSULATION, UNLESS OTHERWISE INDICATED. MINIMUM WIRE SIZE #12 AWG AND STRANDED FOR #8 AWG OR LARGER, RUN WIRING IN CONDUIT INCLUDING LOW VOLTAGE AND CONTROL WIRING, UNLESS OTHERWISE NOTED. 14. UTILIZE 1/2 INCH E.M.T. CONDUIT MINIMUM. WHERE REQUIRED TO PROTECT FROM PHYSICAL DAMAGE, USE RIGID OR IMC TYPE CONDUIT. RUN CONDUIT CONCEALED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. USE FLEXIBLE METALLIC CONDUIT WHERE NEEDED. PROVIDE EXPANSION FITTINGS FOR CONDUIT CROSSING EXPANSION JOINTS. 15. SUPPORT ALL CONDUIT INDEPENDENTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FROM VENTILATION DUCTS, MECHANICAL PIPING, SUSPENDED CEILING GRIDS, OR THEIR HANGERS. USE ONLY ACCEPTABLE METHODS OF SUPPORT. 16. TERMINATING & SPLICING: MAKE ALL JOINTS & SPLICES IN BRANCH CIRCUIT WIRING, #10 AWG & SMALLER, W/ AN APPROVED SOLDER LESS TOOL OR TWIST ON CONNECTORS. #8 AWG AND LARGER USE HIGH COMPRESSION BARREL SPLICES WITH SHRINK WRAP AND MANUFACTURER'S COMPATIBLE CONNECTORS IN GUTTERS, AND SIMILAR LOCATIONS; BUT NOT ALLOWED IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT 2 OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT. 17. EMT CONDUIT FITTINGS: IN DRY LOCATIONS USE STEEL SET SCREW TYPE OR "REGAL" DIE CAST SET SCREW COUPLINGS AND CONNECTORS. DIE CAST FITTINGS WILL NOT BE USED ON THIS PROJECT. DAMP/ WET LOCATIONS: USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTIONS. 18. SURFACE RACEWAY: WHEREVER CONCEALED CONDUIT IN FINISHED AREAS IS NOT POSSIBLE, INSTALL SURFACE MOUNTED RACEWAYS EQUAL TO WIREMOLD. RUN SURFACE RACEWAYS IN CORNER OF WALL AND CEILING. ALL RACEWAYS THAT ARE EXPOSED WILL REQUIRE ARCHITECT'S/ ENGINEER'S APPROVAL PRIOR TO ROUGH-IN. COLOR BY ARCHITECT. 19. TYPE NM (ROMEX CABLE) AND NMC CABLE WILL NOT BE ALLOWED ON THIS PROJECT. S 20A, 1 POLE TOGGLE SWITCH S3 S4 SK 20A, 3-WAY TOGGLE SWITCH SN 20A, NETWORKED SWITCH SD DIMMER SWITCH 20A, 4-WAY TOGGLE SWITCH 20A, 1 POLE KEY OPERATED SWITCH PUSHBUTTON SWITCH TC TIME CLOCK SWITCH PH PHOTOSENSOR RC ROOM CONTROLLER (ABOVE CEILING) CEILING OCCUPANCY SENSOR (ARROWS INDICATE VIEW) FA GAS DETECTOR FA SMOKE DETECTOR EXIT SIGNS (FILL INDICATES NUMBER OF FACES) WITH LIGHTS F HALF FILLED SYMBOL INDICATES EMERGENCY VERSION A-E A-E FA ADA HORN/STROBE. V=VOICE/STROBE V BOX SYMBOL ADDITION INDICATES FLOOR OR IN-GROUND MOUNTING A A F HD FA HEAT DETECTOR 20A, 120V, DUPLEX RECEPTACLE DS FA DUCT SMOKE DETECTOR 20A, 120V, FOURPLEX RECEPTACLE WITH DOUBLE ARROW FACE 2P-4W RECEPTACLE (SEE PANEL SCHEDULE FOR DETAILS) NOTES: 1. Lower case letters after a comma in the fixture designation indicate switching. For example, "A3, b" indicates a type A3 fixture controlled by switch b. 2. A fixture designation ending in "-E" indicates an emergency fixture, even where the fixture symbol may too small to show a half fill clearly. 3. Dimensions and mounting heights in the lighting fixture schedule supercede information implied by these symbols. Symbols are for general reference only. POWER DISTRIBUTION G 20A, 120V - GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) WP 20A, 120V - WEATHERPROOF IN USE COVER GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) SURFACE MOUNTED ELECTRICAL PLUG-IN RACEWAY 20A, 120V, DUPLEX RECEPTACLE, HALF SWITCHED DISCONNECT SWITCH COMMUNICATIONS S T 2P SPECIAL RECEPTACLE 20A FRACTIONAL HORSEPOWER DISCONNECT SWITCH WITH THERMAL OVERLOAD PROTECTION. 2P = 2 POLE DATA OUTLET CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 120V FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 120V MOTOR OR EXHAUST FAN SIMPLEX TYPE RECEPTACLE CONTROL STATION 20A, 120V, DUPLEX RECEPTACLE, ABOVE COUNTER DATA OUTLET, ABOVE COUNTER ANALOG PHONE OUTLET M METER COMBINATION DATA & ANALOG PHONE OUTLET R RELAY COMBINATION DATA & ANALOG PHONE OUTLET, ABOVE COUNTER G GROUND CONNECTION ANALOG PHONE OUTLET, ABOVE COUNTER BOX INDICATES FLUSH MOUNTING IN FLOOR CIRCLE INDICATES FLUSH MOUNTING IN CEILING 3 M M S SUBSCRIPT INDICATES QUANTITY OF PORTS (IF MORE THAN 1) 4 S M MICROPHONE: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY S SPEAKER: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY J DOOR CONTROLS THERMOSTAT OUTLET BOX: SINGLE GANG BACK BOX, PLASTER RING (UNLESS OTHERWISE NOTED) 1/2''CONDUIT AND PULL CORD TO MECH UNIT T 2 J J JUNCTION BOX, CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY BRANCH CIRCUIT PANEL BOARD, SEE SCHEDULE FOR MOUNTING T AO AUTOMATIC DOOR OPENER DH MAGNETIC DOOR HOLDER PS DOOR POSITION SWITCH EL ELECTRIC LOCK/STRIKE KP KEY PAD KC KEY CARD READER PAD MOUNT TRANSFORMER ABBREVIATIONS WALL MOUNTED HORN/SPEAKER T WALL MOUNT TRANSFORMER WIRELESS ACCESS POINT WAP SURGE PROTECTION DEVICE TVSS B BELL GROUND C CLOCK OUTLET, SINGLE RECEPTACLE WITH BRACKET & CLOCK C/S COMBINATION CLOCK & SPEAKER WALL MOUNTED TV TELEVISION OUTLET CONDUIT STUB-OUT LIGHTNING/SURGE ARRESTOR LA S IC INTERCOM CONTROL SWITCH S IV INTERCOM VOLUME CONTROL C1D1 RATED SEALS SECURITY SYSTEM INFRARED MOTION SENSOR SITE PLAN SECURITY SYSTEM CAMERA OR NURSE CALL NP PULL CORD, WALL MOUNTED NP PULL CORD, CEILING MOUNTED NB CALL BUTTON NL INDICATOR LIGHT NC CONTROL STATION UGP UNDERGROUND ELECTRICAL PRIMARY FEEDER UGE UNDERGROUND ELECTRICAL FEEDER UGC UNDERGROUND COMMUNICATIONS OHE OVERHEAD ELECTRICAL FEEDER OHP OVERHEAD ELECTRICAL PRIMARY FEEDER TV UNDERGROUND TELEVISION CABLE T UNDERGROUND TELEPHONE CABLE MOUNTING WALL MOUNTED KEY MOUNTING HEIGHTS A 90'' TO TOP AND NOT LESS THAN 6'' BELOW FINISHED CEILING WHERE REQUIRED 80'' TO BOTTOM AND NOT GREATER THAN 96'' TO BOTTOM F F F B TV PNL CB S C DS 48'' J G F E D H C B T GENERAL ELECTRICAL NOTES TV NOT TO SCALE NOTES: 1. VERIFY ALL MOUNTING HEIGHTS WITH ARCHITECT PRIOR TO ROUGH-IN. 2. DIMENSIONS ARE TO TOP OF DEVICE WITH TRIM. ADJUST BACK BOX LOCATION AS REQUIRED. C 6'-0'' D 48'' TO TOP AFF E 20'' TO TOP AFF F 3'' G 6''AC H 5'-0'' TO HANDLE J 6'-6''MAX 3. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST EDITION OF THE AMERICANS WITH DISABILITIES ACT. (ADA) AC AFF ABOVE COUNTER ABOVE FINISHED FLOOR 20. AFG ARCH BC ABOVE FINISHED GRADE ARCHITECTURAL BELOW COUNTER FEEDER RACEWAY: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE & OUTLET BOX BONDING JUMPERS, A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. 21. C CONDUIT ELECTRONIC/ COMPUTER EQUIPMENT AND SPECIAL EQUIPMENT BRANCH CIRCUITS: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE AND OUTLET BOX BONDING JUMPERS, INSTALL A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR WITHIN BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. EC ELEC EMT ELECTRICAL CONTRACTOR ELECTRICAL ELECTRICAL METALLIC TUBING 22. MAINTAIN A MINIMUM OF 24 INCH SEPARATION BETWEEN POWER CONDUITS AND SIGNAL CONDUITS. ROUTE CONDUITS SO AS NOT CROSS EACH OTHER. GC GEC GRC GENERAL CONTRACTOR GROUND ELECTRODE CONDUCTOR GALVANIZED RIGID CONDUIT 23. PROVIDE WIRING DEVICES RATED FOR THE GIVEN APPLICATION AS REQUIRED BY CODE. 24. INSTALL EXTERIOR WIRING IN CONDUIT. UTILIZE WEATHERPROOF FITTINGS AND WEATHERPROOF BOXES/ COVERS. 25. GRD GROUND SIZE ALL BOXES AND ENCLOSURES PER THE NATIONAL ELECTRICAL CODE. WORKING SPACE FOR ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 110. GFI GROUND FAULT INTERRUPTER 26. IG ISOLATED GROUND IMC INTERMEDIATE METALLIC CONDUIT LA LIGHTNING ARRESTOR MC MECHANICAL CONTRACTOR PROVIDE A 20 AMP, 120 VOLT, RECEPTACLE OUTLET INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT OF ROOF TOPS, ATTICS, AND CRAWL SPACES PER NEC 210-63. LOCATE THE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25' OF THE EQUIPMENT. INSTALL A GFCI RECEPTACLE AT ROOF TOP LOCATIONS WITH CAST BOX, WEATHERPROOF COVER PLATE, AND MOUNT ONTO A THREADED IMC CONDUIT SECURELY FASTENED IN PLACE IN ACCORDANCE WITH NEC 314-23. MECH MECHANICAL 27. NIC NOT IN CONTRACT INSTALL AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET AT OR NEAR EQUIPMENT REQUIRING SERVICING SUCH AS HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT IN ATTIC OR UNDERFLOOR SPACES PER NEC 210-70. LOCATE SWITCH AT POINT OF ENTRY TO THE ATTIC OR UNDERFLOOR SPACE. NTS NOT TO SCALE 28. BRANCH CIRCUITS: UTILIZE #10 AWG CONDUCTORS ON ALL RUNS OVER 100'-0". OHE OVERHEAD ELECTRICAL FEEDER OHP OVERHEAD PRIMARY FEEDER 29. PHASE PROTECTION: INSTALL PHASE PROTECTION ON ALL NEW 3 PHASE MOTORS 1HP AND ABOVE AND ALL 3PH AIR HANDLING UNITS. MANUFACTURED BY CUTLER HAMMER D65 OR SQUARE D MPS. OHS OVERHEAD SECONDARY FEEDER 30. PVC POLYVINYL CHLORIDE PLMBG PLUMBING MULTIPLE PHASE HOME RUNS MAY SHARE A COMMON NEUTRAL EXCEPT WHEN A DIMMER/ DIMMING SYSTEM IS USED, & WHEN ELECTRONIC/ COMPUTER EQUIPMENT CONNECTIONS ARE REQUIRED. VERIFY W/ ENGINEER PRIOR TO ROUGH-IN. PNL PANEL 31. PROVIDE ACCESS PANELS WITHIN THE ELECTRICAL BID. TURN OVER TO THE APPROPRIATE TRADE FOR INSTALLATION. REFER TO ARCHITECTURAL SPECIFICATION SECTIONS. RTU ROOFTOP UNIT TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER 32. UG UNDERGROUND UGE UNDERGROUND ELECTRICAL FEEDER UGP UNDERGROUND PRIMARY FEEDER COORDINATE SHORT CIRCUIT RATING OF PANELBOARDS AND OVER-CURRENT PROTECTION WITH UPSTREAM OVER- CURRENT PROTECTION AND AVAILABLE SCA. PROPERLY IDENTIFY ALL PANELBOARDS W/ LAMINATE LABEL & TYPE ALL PANEL SCHEDULES. INSTALL PANELBOARDS AS INDICATED ON DRAWINGS AND SCHEDULES. PROVIDE CIRCUIT BREAKERS AS REQUIRED. USE "HACR" BREAKERS FOR HEATING /AIR CONDITIONING LOADS, PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER BREAKERS AS REQUIRED. PROVIDE A GROUND BAR KIT WITHIN EACH DISTRIBUTION PANEL, BRANCH CIRCUIT PANEL, AND LOAD CENTER. UPS UN INTERRUPT ABLE POWER SUPPLY 33. WP WEATHERPROOF INSTALL METERING AND ELECTRICAL SERVICE ENTRANCE EQUIPMENT IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL ELECTRIC UTILITY SYSTEM STANDARDS. XFMR TRANSFORMER 34. EXTEND ALL CONDUIT AND CONDUCTORS, INSTALL ELECTRICAL EQUIPMENT AS NECESSARY, AND MAKE ALL FINAL CONNECTIONS TO MECHANICAL AND OWNER FURNISHED EQUIPMENT. LEAVE ALL EQUIPMENT IN OPERABLE CONDITION WITH APPROPRIATE OVERLOAD AND SERVICE DISCONNECT PROTECTION AS REQUIRED BY THE APPLICABLE CODES. FOLLOW MANUFACTURERS INSTALLATION GUIDELINES WHERE APPLICABLE. 35. COORDINATE WITH THE MECHANICAL /PLUMBING /CONTROLS CONTRACTOR TO INSURE THAT ALL REQUIRED COMPONENTS OF CONTROL WORK ARE INCLUDED AND FULLY UNDERSTOOD. NO ADDITIONAL COST SHALL ACCRUE TO THE OWNER AS A RESULT OF LACK OF SUCH COORDINATION. REFER TO THE ELECTRICAL CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT AND THE MECHANICAL-ELECTRICAL RESPONSIBILITY TABLE. 36. CEILING PENETRATIONS IN FIRE RATED CEILINGS SHALL CONFORM TO THE REQUIREMENTS OF IBC SECTION 712. IF AGGREGATE PENETRATION AREA (DETERMINE AGGREGATE AREA FOR ALL DISCIPLINES PENETRATING CEILING AREA) EXCEEDS AREA ALLOWED, THE ELECTRICAL CONTRACTOR SHALL INCLUDE, AS REQUIRED, A FIRE RATED ENCLOSURE FOR EACH FIXTURE IN THAT AREA. LIGHTING FIXTURE TYPE MAY REQUIRE ''IC'' RATING. CONSULT ARCH. FOR DETAILS. GENERAL NOTES 26.## KEYED NOTE M ## MECHANICAL EQUIPMENT IDENTIFICATION K# KITCHEN EQUIPMENT IDENTIFICATION 2016-05-11 NOTE: SOME OF THE SYMBOLS SHOWN MAY NOT APPEAR ON ALL DOCUMENTS OR PLANS. RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: ELECTRICAL LEGEND Checked: Date: Drawn: NB AW 2016-05-11 Of: E001 KEYED NOTES MECHANICAL EQUIPMENT CONNECTION SCHEDULE TYPE B1 CO CU1 CU2 CX1 CX2 CX3 CX4 CX5 F1 F2 GD MD DESCRIPTION BOILER, PROPANE CO2/NO2 DETECTORS CONTROLLER CONDENSING UNIT CONDENSING UNIT CEILING EXHAUSTER CEILING EXHAUSTER CEILING EXHAUSTER CEILING EXHAUSTER CEILING EXHAUSTER FURNACE, PROPANE FURNACE, PROPANE GARBAGE DISPOSAL, 3/4 HP MOTORIZED DAMPER ELECTRICAL 120 V/1-60 VA 120 V/1-120 VA 240 V/2-4320 VA 240 V/2-8400 VA 120 V/1-50 VA 120 V/1-109 VA 120 V/1-109 VA 120 V/1-50 VA 120 V/1-50 VA 120 V/1-1164 VA 120 V/1-1164 VA 120 V/1-1656 VA 120 V/1-50 VA P1 RH SD WH1 WH2 WX INLINE BOILER INJECTION PUMP RADIANT HEATER MOTORIZED DAMPER TANKLESS WATER HEATER, GAS TANKLESS WATER HEATER, GAS GARAGE EXHAUSTER 120 V/1-330 VA 120 V/1-600 VA 120 V/1-10 VA 120 V/1-100 VA 120 V/1-100 VA 120 V/1-1175 VA CB AT PANEL 20 A 20 A 30 A 60 A 15 A 15 A 15 A 15 A 15 A 15 A 15 A 20 A 15 A DISC. AT UNIT PROVIDE SWITCH CORD/PLUG PROVIDE 30A 3R PROVIDE 60A 3R SWITCH ON O.S. SWITCH ON O.S. SWITCH ON O.S. SWITCH ON O.S. PROVIDE SWITCH PROVIDE SWITCH PROVIDE SWITCH PROVIDE SWITCH PROVIDE SWITCH CONDUCTORS #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #10 CU + #10 CU GROUND #6 CU + #10 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12CU + #12CU GROUND #12 CU + #12 CU GROUND 15 A 15 A 15 A 15 A 15 A 15 A CORD/PLUG PROVIDE SWITCH #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND PROVIDE SWITCH PROVIDE SWITCH PROVIDE SWITCH #12CU + #12CU GROUND #12CU + #12CU GROUND #12 CU + #12 CU GROUND 26.01 NOTES 26.02 ALTERNATE BID #1 26.03 CONTROL BY SECOND RELAY ON OCC SENSOR CONTROL BY SECOND RELAY ON OCC SENSOR CONTROL BY SECOND RELAY ON OCC SENSOR CONTROL BY SECOND RELAY ON OCC SENSOR CONTROL BY THERMOSTAT PROVIDE RECEPTACLE FOR CONDENSATE PUMP ON SAME CKT PROVIDE RECEPTACLE FOR CONDENSATE PUMP ON SAME CKT 26.04 26.08 26.09 INTERCONNECT APP. BAY MD WITH WX FOR SIMULTANIOUS OPERATION ALTERNATE BID #1 DELETE IF ALTERNATE BID #1 IS ACCEPTED 26.11 26.12 26.13 PROVIDE PHONE LINE AND BELL ON BAY CEILING TO NOTIFY OCCUPANTS WHEN PHONE IS RINGING. PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS FULLY OPEN. CONNECT TO RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR (SEE LIGHTING PLAN). INDICATOR LIGHT TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY OPEN, AND REMAIN RED OTHERWISE. PROVIDE CEILING MOUNTED CORD REEL ON DRIVER'S SIDE OF BAY. COORDINATE REEL MODEL AND EXACT LOCATION WITH OWNER. PROVIDE ONE RECEPTACLE AT 24" AFF FOR GAS RANGE, ONE RECEPTACLE IN CABINET ABOVE FOR BROAN F403004 HOOD, AND ONE RECEPTACLE IN CABINET ABOVE FOR MICROWAVE. FOR RECEPTACLES MARKED AS GFCI BUT NOT IN READILY ACCESSIBLE LOCATION, PROVIDE GFCI BREAKER AT PANEL. PROVIDE EMPTY 1" CONDUIT FROM CO (CO2 SENSOR CONTROLLER) TO CO2 SENSORS, MOTORIZED DAMPERS (M/D), AND WALL EXHAUSTER (WX), FOR CONTROLS CABLE BY OTHERS. CIRCUIT CEILING EXHAUSTER WITH ROOM LIGHTS, AND CONTROL VIA SECOND RELAY IN OCCUPANCY SENSOR. DATA AND RECEPTACLE AT 12'-0" AFF FOR FUTURE WAP. J-BOX WITH PULL WIRE AND 1/2" CONDUIT ABOVE DOOR ON INSIDE FOR FUTURE DOOR CONTROLLER BY OTHERS. COMBINATION SMOKE/CARBON MONOXIDE DETECTOR. HARD WIRED WITH BATTERY BACKUP. KIDDE KN-COSM-IBA. 120V. OWNER EQUIPMENT CONNECTION SCHEDULE TYPE CP DR GDO GDR GWS HOTSY ICE SCBA WS DESCRIPTION ELECTRICAL 240 V/2-5280 VA 120 V/1-864 VA 120 V/1-864 VA 240 V/2-14640 VA 240 V/2-1920 VA 240 V/2-8160 VA 120 V/1-1272 VA 240 V/2-11040 VA 120 V/1-1176 VA AIR COMPRESSOR SMALL DRYER GARAGE DOOR OPENER, 1/3 HP GEAR DRYER GEAR WASHER PRESSURE WASHER, GAS ICE MACHINE SCUBA (AIR COMPRESSOR), 10 HP SMALL WASHER CB AT PANEL 40 A 20 A 20 A 80 A 20 A 40 A 15 A 50 A 20 A DISC. AT UNIT PROVIDE 60A CORD/PLUG CORD/PLUG PROVIDE 80A PROVIDE 30A PROVIDE 60A PROVIDE SWITCH PROVIDE 60A CORD/PLUG CONDUCTORS #8 CU + #10 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #4 CU + #8 CU GROUND #12 CU + #12 CU GROUND #8 CU + #10 CU GROUND #12 CU + #12 CU GROUND #6 CU + #6 CU GROUND #12CU + #12CU GROUND CU1 NOTES ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT CU2 SERVICE DISCONNECT MD A - 21,23 MD A - 20,22 WP 2 2 2 2 B - 18 B - 16 SLEEPING 109 SD SLEEPING 107 A - 24 SLEEPING 108 B - 17 LAUNDRY 106 A - 34 A - 30 A - 9,11 A - 12,14 MD A - 36 WP R.R. 111 R.R. 113 PANEL B B - 14 CX1 26.12 CX2 26.09 J 26.09 26.08 PANEL A B - 27 R.R. 114 CO WH1 G CX4 26.02 G DAY ROOM 101 B - 30 GDO 26.03 26.03 A - 16 A - 18 B - 12 B - 26 J 26.08 CO J B-4 GDO A-7 B - 23 G A-5 GDO 26.02 B - 11 OFFICE 102 B - 28 26.12 26.12 2016-05-11 A - 26 G B-7 G G J RODAHL & HUMMELL ARCHITECTURE, P.C. WP DISHWASHER 26.02 26.03 B - 24 B - 10 B-2 GD A - 27 J G B-1 84" AFF G G G G 26.04 RH 26.09 G 84" AFF KITCHEN 100 CO 26.11 B-8 B-6 B-9 B-5 B-3 CO A - 15 STOR. 115 26.08 APPARATUS BAY 103 26.09 G 96" AFF 26.08 J REFRIGERATOR A - 17 26.01 A-6 FREEZER A - 8,10 WX A - 29 A - 25 F2 CX3 J SCBA A - 2,4 WP CX5 SD VEST 105 HALL 112 A - 1,3 26.08 A - 19 G B - 25 SD A - 28 CP HOTSY G IT 112A A - 13 CO GWS B - 13 B - 15 MICROWAVE RANGE SD G SLEEPING 110 SD BUNKER 104 G SD WS P1 ICE WH2 MD B - 19 F1 SD GDR WP 2 B - 20 26.13 DR B1 WP B - 22 2 2 2 B - 21 G MD J 26.12 ARCHITECTURE N 1 ELECTRICAL POWER FLOOR PLAN 1/8" = 1'-0" 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: ELECTRICAL PLAN Checked: Date: Drawn: NB AW 2016-05-11 Of: E101 KEYED NOTES LIGHTING FIXTURE SCHEDULE TYPE A D DESCRIPTION MOUNTING ASSYMETRIC UP/DOWN WALL FIXTURE, DIMMABLE WALL DOOR EXIT SIGNAL LIGHT WALL EX EXL H EXIT SIGN, RED ON WHITE EXIT SIGN WITH EMERGENCY LIGHTS HIGH BAY, WIDE DISTRIBUTION, WITH INTEGRAL OCCUPANCY SENSOR HIGH BAY, WIDE DISTRIBUTION, WITH INTEGRAL OCCUPANCY SENSOR AND EM BATTERY 4' LINEAR LENSED DECORATIVE PENDANT AT BAR SQUARE LIGHT, OUTDOOR, WITH PHOTOCELL SQUARE LIGHT, WET LOCATION, WITH EM BATTERY PACK SQUARE LIGHT, INDOOR WET LOCATION, NO PHOTOCELL TROFFER, 2'X2' TROFFER, 2'X4' TROFFER, 2'X4', WITH EM BATTERY PACK WALLPACK WITH PHOTOCELL AND COLD WEATHER EM BATTERY HE L P S SE SI T2 T4 T4E W4 HEIGHT 8' AFF 6' AFF LAMP LED LED ELECTRICAL 120 V/1-37 VA 120 V/1-10 VA UNIVERSAL UNIVERSAL SUSPENDED ABOVE DOOR 17' AFF LED LED LED 120 V/1-5 VA 120 V/1-5 VA 120 V/1-155 VA MAKE FINELITE LIGHTING SPECIALTIES COMPASS COMPASS COLUMBIA SUSPENDED 17' AFF LED 120 V/1-155 VA SURFACE SUSPENDED SURFACE SURFACE CEILING 7' AFF CEILING CEILING LED LED LED LED SURFACE CEILING CEILING CEILING CEILING ABOVE DOOR RECESSED-GRID RECESSED-GRID RECESSED-GRID WALL 26.02 MODEL S17-LED-VCF-PF-2-SO-40K-SC-120 SG20-12RG-LED CCT 40K N/A CRI MIN 80 N/A LUMENS 2,500 N/A OPTIC ASSYMETRIC N/A 40K 40K 40K MIN 80 MIN 80 MIN 80 N/A N/A 16,000 N/A N/A WIDE COLUMBIA CER CCR LLHV4-40M-WST-EU-SFA-WG-OS1360 +LHVQM5 LHVQM5 LLHV4-40M-WST-EU-SFA-WG-ELL14 + LHVQM5 40K MIN 80 16,000 WIDE 120 V/1-25 VA 120 V/1-14 VA 120 V/1-20 VA 120 V/1-20 VA COLUMBIA SPECTRUM KENALL KENALL LCL4-40LW-EU PF0614-LEDGV14W-40K-DS101-CP13-CD-FINISH MS11FL-PP-DB-20L50K-SCC-120-BPC MS11FL-PP-DB-20L40K-SCC-120-BPC-LEL 40K 40K 50K 40K MIN 80 MIN 80 MIN 80 MIN 80 2,500 1,000 1,350 1,350 DIFFUSE N/A DIFFUSE DIFFUSE LED 120 V/1-20 VA KENALL MS11FL-PP-MW-20L40K-SCC-120-BPC 40K MIN 80 1,350 DIFFUSE LED LED LED LED 120 V/1-22 VA 120 V/1-40 VA 120 V/1-40 VA 120 V/1-45 VA COLUMBIA COLUMBIA COLUMBIA LITHONIA LCAT22-40MWG-EU LCAT24-40MLG-EDU LCAT24-40MLG-EDU-ELL14 OLW-31 40K 40K 40K 50K MIN 80 MIN 80 MIN 80 N/A 22,000 5,000 5,000 3970 WIDE WIDE WIDE - NOTES SEE PLAN KEYNOTES FOR CONTROL 26.07 26.10 PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS FULLY OPEN. CONNECT TO RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR (SEE LIGHTING PLAN). INDICATOR LIGHT TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY OPEN, AND REMAIN RED OTHERWISE. TYPE H FIXTURES INCLUDE AN INTEGRAL OCCUPANCY/DAYLIGHT SENSOR, AND WALL SWITCHES FUNCTION AS A MANUAL OVERRIDE TO OFF. TYPE HE FIXTURES ARE UNSWITCHED, AND HAVE NO SENSOR. PROVIDE AND LOCATE OCCUPANCY SENSORS REQUIRED FOR FULL COVERAGE OF ROOM PER MANUFACTURER'S INSTRUCTIONS. TEST AND ADJUST SENSORS AS NEEDED TO ENSURE PROPER FUNCTION. TYPICAL ALL OCCUPANCY SENSORS. UNSWITCHED OWNER STANDARD FIXTURE, NO SUBSTITUTIONS CONTROL DEVICE SCHEDULE TYPE Dimmer O-C O-C2 O-W1 O-W2 RC DESCRIPTION LOW VOLTAGE DIMMER WITH ON/OFF TOGGLE CEILING OCCUPANCY SENSOR CEILING OCCUPANCY SENSOR, 2 RELAY WALL OCCUPANCY SENSOR WALL OCCUPANCY SENSOR, 2 RELAY LOCAL ROOM CONTROLLER FOR COORDINATION OF MULTIPLE INPUT DEVICES MOUNTING WALL CEILING CEILING WALL WALL ABOVE CEILING HEIGHT SWITCH HEIGHT N/A N/A SWITCH HEIGHT SWITCH HEIGHT N/A SENSING TECH N/A DUAL DUAL DUAL DUAL N/A RELAYS PER PLAN 1 2 1 2 PER PLAN SWITCH(ES) INTEGRAL PROVIDE REMOTE PER PLAN PROVIDE REMOTE PER PLAN 1 - INTEGRAL 2 - INTEGRAL PER PLAN NOTES MUST BE COMPATIBLE WITH RC LOCATE ABOVE ACCESSIBLE CEILING PANEL SERV. DISC. D D D SLEEPING 110 T4 A SLEEPING 109 T4 D A A A SLEEPING 108 T4 SLEEPING 107 T4 LAUNDRY 106 L H, a BUNKER 104 L S 3 HALL 112 O-C T4 O-W1 3 R.R. 111 T2 SE S T2 R.R. 113 T4E, c A B - 34 g O-W2 EX SI c d f g T4, c R.R. 114 T2 A PANEL B T4, g HE STOR. 115 A O-C2 B - 29 T4, c T4, c T4, c T4E, g P, f T4, d 26.10 T4, d T4E, d 26.10 EX T4, d OFFICE 102 T4, d T4, d O-W1 T4, d T4 33 KITCHEN 100 T4, g H, b H, b O-C DAY ROOM 101 RC H, a 33 O-C H, b 26.07 TYP. H, a P, f HE APPARATUS BAY 103 TYP. L P, f S H, a 26.07 O-W2 D D D D SE EX VEST 105 T4E SI O-C2 A - 33 PANEL A B - 32 EX H, b O-W1 EX T4E H, b A - 32 O-W1 IT 112A T2 H, a L EXL W4 26.02 26.02 D D D 2016-05-11 T4 W4 SE d b EXL a CIRCUIT WITH DOOR OPENERS 26.02 b a W4 W4 A - 31 RODAHL & HUMMELL ARCHITECTURE, P.C. EX S SE S ARCHITECTURE N 1 ELECTRICAL LIGHTING FLOOR PLAN 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 CENTERPOINT 2 FIRE STATION SAN JUAN COUNTY 1/8" = 1'-0" Drawn: NB Filename: 0725_FLOOR Project: 1527 Sheet: LIGHTING PLAN Checked: Date: AW 2016-05-11 Of: E102 PANEL B 2 SERVICE DISC 1 1 25000 NM 3 PANEL A 1 2 20513 M 4 PANEL B 1 3 12031 M Set(s) 250 AL 12862 240 30 2 of 0.00009 0.000041 0.243 0.805 2 Set(s) 250 AL 12122 240 100 0.00009 of 0.000052 1 Set(s) 250 AL 12122 240 50 of 0.000052 0.00009 NOTES TO THE CONTRACTOR: 100 Segment Voltage Drop CUMULATIVE VOLTAGE DROP at the secondary of the utility transformer FAULT CURRENT Motor Contribution M f Conductor Reactance (X) Conductor Resistance (R) Length (L) L-L Volts (E) 'C' value Wire/Bus 0 Conduit Type Source (Point) 1 Source Isc Phase 1 SERVICE Point Description SHORT CIRCUIT & VOLTAGE DROP CALCULATIONS 25000 - - 20513 0.5% 0.5% 0.705 0.586 12031 1.7% 2.1% 0.414 0.707 8511 0.4% 2.5% LEGEND: 1. THE DISTANCES SHOWN ARE FOR CALCULATION PURPOSES ONLY. THEY SHALL NOT BE USED FOR CONTRACTOR TAKEOFFS, NOR FOR BIDDING. 2. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY FIELD CONDITION THAT RESULTS IN A CHANGE OF 10% OR GREATER CIRCUIT DISTANCE NM = NON-MAGNETIC CONDUIT M = MAGNETIC CONDUIT FB = FEEDER BUSWAY PB = PLUG-IN BUSWAY XFMR = TRANSFORMER CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD: L= I= LENGTH OF CIRCUIT TO THE FAULT IN FT (1 WAY). AVAILABLE SHORT-CIRCUIT CURRENT IN AMPS AT THE BEGINNING OF THE CIRCUIT. C = 'C' FACTOR CONSTANT FROM THE TABLE OF 'C' VALUES FOR THE CONDUCTORS. E = LINE-TO-LINE OR LINE-TO NEUTRAL VOLTAGE. IP = PRIMARY SHORT CIRCUIT CURRENT IS = IS = SECONDARY SHORT CIRCUIT CURRENT Vs = SECONDARY VOLTAGE Vp = PRIMARY VOLTAGE Isca (1) = SHORT CIRCUIT CURRENT AT FAULT POINT #1 Isca (2) = SHORT CIRCUIT CURRENT AT FAULT POINT #2 Isca (2) = Isca (1) x M(1) M = 1/(1+f) FEEDER: 'f (3Ø) = 1.732 x L x Isca CxE XFMR: 'f (3Ø) = IP(sca)x Vp x 1.73 x %Z 100,000 x kVA FEEDER: 'f (1Ø) = 2 x L x Isca CxE XFMR: 'f (1Ø) = IP(sca)x Vp x %Z 100,000 x kVA ISsca = Vp x M x IP(sca) Vs Location: Supply From: Mounting: Enclosure: DAYROOM 101 A RECESSED NEMA 1 PANEL A Volts: 120/240 Single Phases: 1 Wires: 3 A.I.C. Rating: 22,000 Mains Type: MLO Mains Rating: 200 A Location: Supply From: Mounting: Enclosure: Notes: Volts: 120/240 Single Phases: 1 Wires: 3 A.I.C. Rating: 22,000 Mains Type: MLO Mains Rating: 400 A Notes: A CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 VESTIBULE 106 SERV. DISC. RECESSED NEMA 1 Circuit Description KITCHEN HOOD MICROWAVE GAS RANGE REC - NW Cntr REC - 100 NE Cntr REC - 100 W Cntr REC - 104, 105, 106 REC- IT 112A REC- IT 112A WASHING MACHINE DRYER REC - Dayroom TVs SMOKE/CO2 DETECTORS WH1 LGT- DAYROOM Spare Spare Spare Spare Spare Spare Load Classification HVAC Lighting Motor Other Receptacle B Trip Poles Poles 300 1656 20 1 1 1600 1200 20 1 1 50 600 20 1 1 1600 600 20 1 1 1600 1600 20 1 1 1600 900 20 1 1 540 1080 20 1 1 900 720 20 1 1 900 720 20 1 1 1176 720 20 1 1 864 720 20 1 1 360 900 20 1 1 70 630 20 1 1 100 540 15 1 1 728 900 20 1 1 0 1077 20 1 1 0 180 20 1 1 0 20 1 0 20 1 0 20 1 0 20 1 Total Load: 13138 VA 13993 VA Total Amps: 109 A 117 A Connected Load Demand Factor Demand 100 VA 100.00% 100 VA 1694 VA 125.00% 2118 VA 1974 VA 100.00% 1974 VA 4860 VA 100.00% 4860 VA 18530 VA 76.98% 14265 VA A Trip 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 15 20 Circuit Description GARBAGE DISPOSER DISHWASHER REFRIGERATOR FREEZER REC - 100 Island REC - 102 REC - EXT, RRs, STOR,... REC - 107 REC - 108 REC - 109 REC - 110 REC - Dayroom 101 REC - Dayroom 101 REC - Dayroom 101 REC - Dayroom 101 LGT- SMALL ROOMS LGT- EXT CANOPIES Panel Totals Total Conn. Load: 27158 VA Total Est. Demand: 23317 VA Total Conn.: 113 A Total Est. Demand: 97 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 Circuit Description HOTSY -GDO - Mid and South Cord Reels GDR -ICE RH WX REC. - BAY E WALL CU1 -F2 REC. - BAY S WALL REC - BAY NE GFCI LGT- EXT BAY DOORS LGT- BAY SOUTH Spare Spare Spare Spare Spare Spare Spare TVSS PANEL B -- Load Classification HVAC Lighting Motor Motor - Largest Other Receptacle B Trip Poles Poles 4080 5520 40 2 2 4080 5520 ---1728 864 20 1 1 1080 2640 20 1 2 7320 2640 80 2 -7320 960 --2 1272 960 15 1 -600 120 15 1 1 1175 720 15 1 1 720 4200 20 1 2 2160 4200 30 2 -2160 1164 --1 1164 540 15 1 1 540 390 20 1 1 540 100 20 1 1 180 930 20 1 1 930 250 20 1 1 0 50 20 1 1 0 20 1 0 20 1 0 20 1 0 20 1 0 20 1 0 20 1 0 30 1 12930 200 2 13873 --Total Load: 50036 VA 45584 VA Total Amps: 417 A 380 A Connected Load Demand Factor Demand 16358 VA 100.00% 16358 VA 3734 VA 125.00% 4668 VA 11321 VA 100.00% 11321 VA 11040 VA 125.00% 13800 VA 30852 VA 100.00% 30852 VA 22670 VA 72.06% 16335 VA Trip 50 -20 40 -20 -20 20 60 -15 20 15 15 20 20 20 Circuit Description SCBA -GDO - North CP -GWS -CO/NO2 Detector REC. - W Garage CU2 -F1 REC - EXT BAY DOORS B1, P1 WH2 LGT- BAY NORTH MDs CX5 CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 Panel Totals Total Conn. Load: 95975 VA Total Est. Demand: 93334 VA Total Conn.: 400 A Total Est. Demand: 389 A EXTERIOR RISER GENERAL NOTES INTERIOR NEW UTILITY TRANS. 240V 1 PH 1. ALL UNDERGROUND CONDUIT TO BE SCHEDULE 80 PVC. 2. ALL EXPOSED EXTERIOR CONDUIT TO BE RIGID STEEL. 3. THIS DIAGRAM IS SCHEMATIC, AND NOT INTENDED TO SPECIFY CONDUIT ROUTING OR FEED SIDE OF PANELS. 4. WHERE ALUMINUM FEEDERS ARE SPECIFIED, VERIFY THAT ASSOCIATED PANELS ARE RATED FOR ALUMINUM CONDUCTORS. 5. TERMINAL SCREWS ON ALL ALUMINUM FEEDERS SHALL BE TORQUED TO CONDUCTOR MANUFACTURER'S SPECIFICATIONS AT CONSTRUCTION, AND RE-TORQUED 90 DAYS AFTER COMMISSIONING. 2 PANEL B MLO - 240V / 1PH 1 400A OCP # 1/0 AL UTILITY METER # 1/0 AL CT CABINET NTR BUS GRD BUS MLO - 240V / 1PH PANEL A 3 # RISER KEYED NOTES 1. NEW 240V SINGLE PHASE SERVICE, ASSUMED TO BE WITHIN 30 FT OF THE SERVICE DISCONNECT. COORDINATE WITH FEUS. 2. EXTERIOR SERVICE DISCONNECT WITH OCP (FUSE OR BREAKER ACCEPTABLE). MINIMUM INTERRUPT RATING 22,000A. 3. 2 SETS OF (3) 250 MCM AL + # 1 AL GROUND IN 2.5" CONDUIT. 4. 1 SET OF (3) 250 MCM AL + # 1 AL GROUND IN 2.5" CONDUIT. 4 2016-05-11 #4 CU #4 CU 3 TO STRUCTURAL STEEL #2 CU 20' LOOP 30" BELOW GRADE 20'-0" 20 '-0 " 1 RODAHL & HUMMELL ARCHITECTURE, P.C. TO UFER GROUND " '-0 20 (3) 3/4" X 10' COPPER CLAD STEEL GROUND RODS ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 ELECTRICAL RISER DIAGRAM CENTERPOINT 2 FIRE STATION 1/8" = 1'-0" SAN JUAN COUNTY Filename: 0725_FLOOR Project: 1527 Sheet: ELECTRICAL RISER AND PANELS Checked: Date: Drawn: AW JL 2016-05-11 Of: E501