Bid 16-17-01 Drawings Part 2

advertisement
N
05.16.16
CENTERPOINT 2
FIRE STATION
HCSHEET1
SAN JUAN COUNTY
150725
HANDICAP REQUIREMENTS
HC-1
BTW
TEH
05.16.16
KEYED NOTES
23.01
23.02
23.03
23.04
23.06
23.07
23.08
23.09
23.10
23.11
23.12
23.13
23.14
23.15
23.16
23.17
23.18
23.19
23.20
12"x12"
SLEEPING
107
A6
116CFM
12"x12"
6"x6"
6"x6"
SLEEPING
108
A6
116CFM
12"x12"
HALL
112 A6
146CFM
R.R.
111
23.15
M/D
B1
D
D
B1
LAUNDRY
W
F1
106
A6
40CFM
B1
BUNKER
104
W
23.07
23.16
23.10
23.11
CO
WX
24"x24"
23.09
A6
40CFM
VEST
105
F2
A6
53CFM
23.18
B2
CX1
B1
14"x14"
A6
45CFM 23.18
12"x12"
A6
45CFM
CX3
23.18
CX2
R.R.
113
8"DIA
.
. .
23.17
6"x6"
T
M/D
A6
35CFM
23.18
23.02
23.08
APPARATUS BAY
103
CX4
R.R.
114
STOR.
115
23.20
23.01
RH
14"x14"
CX5
23.19
23.04
M/D
B1
12"x6"
B1
14"x14"
T IT
112A
B1
SLEEPING
109
A6
116CFM
6"x6"
6"x6"
B1
SLEEPING
110
A6
120CFM
M/D
CU2
6"x6"
M/D
CU1
23.14
12"x12"
ROUTE 4" DIAMETER FLUE THROUGH THE ROOF. TERMINATE PER THE MANUFACTURER'S
INSTRUCTION.
ROUTE 4" DIAMETER OUTSIDE AIR INTAKE DUCT THROUGH THE ROOF. TERMINATE PER THE
MANUFACTURER'S INSTRUCTION.
DUCT RANGE HOOD, 7"DIA. THROUGH THE SIDEWALL. PROVIDE WALL CAP WITH BIRDSCREEN
AND CAP. CONNECTION TO HOOD BY ARCH.
ROUTE 4" RIGID DRYER DUCT THROUGH THE SIDEWALL. TERMINATE WITH ROUND WALL CAP
WITH BUILT IN BACKDRAFT DAMPER AND PAINT PER ARCHITECT.
CARBON MONOXIDE CONTROLLER PER SCHEDULE. CONNECT TO SENSORS, INTAKE LOUVER
DAMPER AND WALL EXHAUSTER.
COMBINATION CARBON MONOXIDE/NITROGEN DIOXIDE SENSOR MOUNTED AT 48"AFF. WITH 50'
RADIUS RANGE.
MOUNT RADIANT HEATER AT 6" BELOW THE JOISTS IN APPARATUS BAY. MAINTAIN 81" CLEAR
TO COMBUSTIBLES BELOW THE UNIT.
WALL EXHAUSTER TO BE ACTIVATED BY THE CO/NO2 CONTROLLER. INTERCONNECT WITH
MOTORIZED DAMPER ON INTAKE LOUVER. MOUNT FAN TO BE CENTERED IN ARCHITECTURAL
BAND. SEE ARCHITECTURAL ELEVATIONS.
MOUNT LOUVER AT 14'-8" TO THE BOTTOM OF THE LOUVER. LOUVER TO BE CENTERED IN THE
ARCHITECTURAL BAND ON THE OUTSIDE WALL.
ROUTE 6" DIA. RIGID DRYER DUCT THROUGH THE SIDEWALL. TERMINATE WITH ROUND WALL
CAP WITH BUILT IN BACKDRAFT DAMPER AND PAINT PER ARCHITECT.
THERMOSTAT TO CONTROL RADIANT HEATER.
RETURN AIR TO TRAVEL BELOW THE 1/4" UNDERCUT OF THE DOOR.
MOUNT CONDENSING UNITS ON CONCRETE PAD. MOUNT AWAY FROM THE ROOF DRIP LINE.
ROUTE BOILER FLUES THROUGH SIDEWALL. TERMINATE WITH SIDEWALL KIT PROVIDED WITH
BOILER.
ROUTE 8" DIA. FLUE FROM HOTSY THROUGH SIDEWALL.
PROVIDE 5/8" PEX TUBING ON 9" CENTERS THROUGHOUT THE ENTIRE APPARATUS BAY. SEE
THE BOILER PIPING SCHEMATIC AND RADIANT SLAB DETAIL FOR MORE INFORMATION.
CEILING EXHAUSTER WITH BACKDRAFT DAMPER TO BE CONTROLLED BY OCCUPANCY
SENSOR PROVIDE BY THE ELECTRICAL CONTRACTOR.
ROUTE 6" DIAMETER EXHAUST DUCT UP THROUGH THE SIDEWALL. TERMINATE WITH WALL
CAP WITH BIRDSCREEN. PAINT PER ARCHITECT. CEILING EXHAUSTER TO BE CONTROLLED BY
THEMROSTAT.
ROUTE 8" DIAMETER EXHAUST DUCT UP THROUGH THE ROOF TO ROOF CAP.
14"x14"
23.03
A8
200CFM
A6
148CFM
A6
148CFM
A6
148CFM
KITCHEN
100
23.12
T
23.06
T
CO
A8
200CFM
DAY ROOM
101
A6
148CFM
1
23.13
A8
160CFM
OFFICE
102
A6
148CFM
MECHANICAL FLOOR PLAN
1/8" = 1'-0"
04/27/2016
RODAHL & HUMMELL
ARCHITECTURE, P.C.
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
MECHANICAL FLOOR PLAN
Checked: Date:
Drawn:
DS
DS
2016-05-11 Of:
M101
MOTORIZED DAMPER, TYP.-2
RETURN AIR DUCT, SEE
MECHANICAL PLAN FOR
CONTINUATION TO RETURN
GRILLE.
MECHANICAL GENERAL NOTES
NOTE: ROUTE DRAIN LINES TO NEAREST
FLOOR SINK WITHIN THE BUILDING
SEE PLAN FOR SIZE
AND CONTINUATION.
1.
PROVIDE AND INSTALL ALL MATERIAL AND EQUIPMENT AS REQUIRED BY UPC, UMC,
NFPA, LIFE SAFETY CODE, GAS CODE, AND ALL OTHER LOCAL CODES AND
ORDINANCES THAT APPLY. WHERE THERE IS A DISCREPANCY BETWEEN THE CODES
OR ORDINANCES AND THE DRAWINGS, THE MORE STRINGENT APPLICATION SHALL
APPLY.
2.
LAYOUT AND INSTALL COMPLETE AND FUNCTIONAL MECHANICAL SYSTEMS,
INCLUDING TEMPORARY CUTOFF OF EXISTING UTILITIES. PERFORM ALL CUTTING,
PATCHING, AND REPAIR ASSOCIATED WITH INSTALLING THE SYSTEMS.
AVOID INTERFERENCE WITH FITLER ACCESS.
3" PVC COMBUSTION AIR, TERMINATE
PER MANUFACTURER'S INSTRUCTIONS.
OSA FROM LOUVER
3" PVC FLUE TO CONCENTRIC
ADAPTERS THRU ROOF, TERMINATE
PER MANUFACTURER'S INSTRUCTIONS.
F#
FILTER ACCESS THIS SIDE
3.
DX COIL
FLEX. CONN., TYP.
G
30" CLEAR SERVICE AREA
SUPPLY AIR DUCT, SEE
MECHANICAL PLAN FOR
CONTINUATION.
SEAL DRAIN
PAN
PENETRATIONS
1" GAS LINE WITH GAS COCK, UNION AND DRIP
LEG. SEE PLUMBING PLAN FOR CONTINUATION
SUSPEND FROM STRUCTURE
ABOVE FROM VIBRATION
ISOLATORS
4.
5.
LINE SETS
1½" DEEP DRAIN PAN
COIL DRAIN
DRAIN PAN DRAIN
D2
SCALE: NTS
INSULATE ALL BRANCH DUCT
AND COVER CONNECTIONS
WITH DUCT WRAP.
1"x18 GAGE SHEETMETAL
SUPPORT STRAP. ATTACH
TO STRUCTURE ABOVE.
10' O.C. MINIMUM
CONCRETE SLAB
WIRE
MESH OR
REBAR
HANGER
STRAPS NO POP
RIVETS
ALLOWED.
#10 x 3/4" SELF TAPPING
CADIUM PLATED SCREWS TO
ANCHOR STRAPS TO DUCT.
(TYPICAL)
VOLUME DAMPER
V/D
INSULATED FLEX DUCT SHEETMETAL SCREWS.
NO SAGS OR SHARP TURNS MAX RUN LIMITED TO
4 FEET STRETCH DUCT RUN FOR SMOOTH
INTERIOR.
USE ADJUSTABLE ROUND
SHEETMETAL DUCT ELBOW
WHERE AN IMMEDIATE TURN
FROM DIFFUSER.
SUB SOIL
STAINLESS STEEL ADJUSTABLE
ADJUSTABLE DUCT BAND.
(TYPICAL)
PROVIDE ALL DUCTWORK CONNECTIONS AND TRANSITIONS AT GRILLES, DIFFUSERS,
REGISTERS, FILTERS, COILS, AND OTHER LOCATIONS WHERE REQUIRED.
CONSTRUCT ALL TRANSITIONS AND CONNECTIONS ACCORDING TO SMACNA
STANDARDS.
7.
TESTING AND BALANCING AGENCY: PROVIDE AND INSTALL SHEAVES AND ALL
EQUIPMENT NECESSARY TO PROVIDE PLUS OR MINUS 10% OF THE CFM REQUIRED
FROM EACH DIFFUSER AND REGISTER.
8.
PROVIDE AND INSTALL ALL MECHANICAL EQUIPMENT, TRANSFORMERS, RELAYS, AND
OTHER ELEMENTS NECESSARY FOR A COMPLETE OPERATING SYSTEM. COMPLETE
ALL 24 VOLT CONTROL WIRING AND EQUIPMENT TO THE ABOVE. ALL LINE VOLTAGE
WIRING TO THE ABOVE SHALL BE COMPLETED BY THE ELECTRICAL CONTRACTOR.
REFER TO COORDINATION SCHEDULE ON ELECTRICAL DRAWINGS.
9.
ALTER DIMENSIONS OF THE DUCTWORK IN THE CEILING SPACE FROM SIZES
INDICATED ON THE DRAWINGS AT SPECIFIC LOCATIONS WHEN NECESSARY TO FIT
THE DUCTWORK IN THE SPACE PROVIDED. REROUTE DUCTWORK IN CEILING SPACE
TO AVOID OTHER MECHANICAL EQUIPMENT, LIGHT FIXTURES, ETC. MAINTAIN THE
SAME FREE AREA AND SUBMIT PROPOSED CHANGES TO THE ENGINEER FOR
APPROVAL. BE RESPONSIBLE FOR VERIFYING SPACE LIMITATIONS BEFORE
DUCTWORK FABRICATION AND MAKE CHANGES ACCORDINGLY. PROVIDE ALL
NECESSARY TRANSITIONS.
B1
CO
12. PROVIDE ACOUSTICAL LINER ON ALL SOUND TRAPS AT ALL RETURN AIR GRILLES.
PROVIDE ACOUSTICAL LINER ON ALL TRANSFER DUCTS.
C1
RADIANT SLAB DETAIL
C2
**ALTERNATE BID**
SCALE: NTS
TYPICAL DIFFUSER CONNECTION DETAIL
ROUTE 3" PVC FLUE AND OUTSIDE AIR PIPE THROUGH
SIDEWALL. TERMINATE EACH PER MANUFACTURER'S
INSTRUCTIONS.
1" INSULATED LINE
AIR PURGE VALVE
WALL, SEE ARCHITECTURAL
DRAWINGS
ALUMINUM HOUSING
16. PROVIDE TURNING VANES IN ALL RECTANGULAR DUCTWORK AT ELBOWS AND TEES
WHETHER SHOWN ON THE PLANS OR NOT. THE ONLY EXCEPTION IS RETURN AIR
TRANSFER DUCTS BETWEEN ROOMS.
VENTING
THROUGH ROOF
3
_"
4
TO MAKEUP WATER
ASSEMBLY, SEE PLUMBING
FOR DETAIL.
GAS ISOLATION VALVE
GAS DIRT LEG
FLASHING
DISCHARGE HOOD
24" MINIMUM
P/T TAP, TYPICAL
WIRSBO TruFLOW 7
LOOP MANIFOLD
WITH ISOLATION
VALVES.
18. ALL PLENUM INSTALLED MATERIALS MUST BE PLENUM RATED OR WRAPPED IN A
LISTED SYSTEM TO ACHIEVE A VALUE LOWER THAN 25 FLAME SPREAD AND 50
SMOKE DEVELOPMENT RATING.
2" CLEARANCE THIMBLE
G
T
WX
4"∅
P1
INLINE BOILER INJECTION PUMP: CAST-IRON BODY, SELF LUBRICATING, NO
MECHANICAL SEAL, FIELD REPLACEABLE CARTRIDGE.
"TACO" **ALTERNATE BID#1**
UNIT GPM TDH HP
P1
7
30'
1/8
ROOM MOUNTED
THERMOSTAT
DRAIN LINE WITH
NEUTRALIZER TO DRAIN
T&P VALVE LINE FULL
SIZE TO DRAIN
(14) 5/8" PEX TUBING 250'
APPARATUS BAY LOOPS
B1
BOILER PIPING SCHEMATIC
SCALE: NTS
**ALTERNATE BID**
BACK
DRAFT
DAMPER
B2
WALL EXHAUST FAN DETAIL
B3
SCALE: NTS
SECURE TO STRUCTURE ABOVE AS
RECOMMENDED BY SMACNA.
1"x16 GA. GALV.
METAL STRAP
SHEET METAL
SCREW RIVET OR
BOLT TO BOTH
SIDES OF DUCT.
MAX. SIDE
TYPE "A"
8 FT. MAX. HANGER SPACING
ALSO PROVIDE 3 HANGERS AT
EACH TAKE-OFF OR BRANCH
DOUBLE-NUT &
WASHER @ END
OF ROD
MAX. SIDE
FOR
BRACING
ANGLES SEE NOTES
WX
GARAGE EXHAUSTER: BELT DRIVE, PROPELLER EXHAUSTER WITH OPTIONAL WIRE
GUARD AND WALL COLLAR.
"COOK"
ESP
("WC)
UNIT MODEL CFM
BHP HP ELEC.
RPM
CONTROLLED BY
WX 20XMP 1962
0.35"
.41 .50 120V/1∅
1205
CO/NO2 SENSORS
XT
EXPANSION TANK: 5.0 GALLON ACCEPTANCE VOLUME
"TACO" MODEL CX30-125 **ALTERNATE BID#1**
A
CEILING DIFFUSER: 4-WAY ADJUSTABLE VERTICAL/HORIZONTAL THROW STEEL
24"x24" FACE UNLESS OTHERWISE INDICATED ON PLAN, SEE PLAN FOR NECK SIZE,
CFM AND CEILING TYPE. NC < 30.
"KRUEGER" MODEL 1450 A
B
CEILING RETURN GRILLE: EGG-CRATE STYLE, 24"x24" FACE UNLESS OTHERWISE
INDICATED ON PLAN. SEE PLAN FOR NECK SIZE, CFM AND CEILING TYPE. PROVIDE
OBD WHEN GRILLE IS USED FOR EXHAUST. NC<30.
"KRUEGER" MODEL EGC-5
LV
LOUVER: ALUMINUM, WEATHER RESISTANT BLADE DESIGN, COLOR PER ARCHITECT.
A MINIMUM OF 0.01OZ. OF WATER CARRY-OVER AT 1250 FPM FREE AREA VELOCITY
0.185"W.C. PRESSURE DROP AT 1250 FPM FREE AREA VELOCITY.
"CESCO" MODEL X6D3
A2
M/D MOTORIZED DAMPER: EXTRUDED ALUMINUM OPPOSED BLADE WITH BELIMO 120V
POWER, SPRING RETURN ACTUATOR. CLASS 1 MAXIMUM LEAKAGE RATE AT 4 CFM
PER SQ.FT. AT 1.0"W.C. AMCA 500D TESTED. .
"CESCO" MODEL CDA
M036B
MECHANICAL SYMBOLS LEGEND
12
18
30
42
54
60
84
96
96
A
A
A/B
B
B
B
C
C
D
A6
100CFM
CEILING DIFFUSER DESIGNATION = TYPE "A" WITH A 6"
DIAMETER NECK AT CFM SHOWN
UNION
B1
CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 1'X1'
GAS COCK
B2
CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 2'X2'
THERMOMETER
C16"x16"
100CFM
SIDEWALL DIFFUSER DESIGNATION = TYPE "C" WITH A 16"x16"
FACE AT CFM SHOWN
CHECK VALVE
UNIT DESIGNATION
1
23.01
WATER HAMMER ARRESTER
GATE VALVE
OS&Y
SOLENOID
PLUG, CIRCUIT SETTER OR
GAUGE COCK
PRESSURE GAUGE
SUPPLY DIFFUSER
TYPE "B", "C" & "D" 8 FT. MAX.
HANGER SPACING.
RETURN GRILLE
SIDEWALL SUPPLY
3-WAY VALVE
BACKFLOW PREVENTER
RELIEF VALVE
FLEX DUCT
SIDEWALL RETURN
BALL VALVE
CENTERS; TYPE "C" 1½"x1½"x3/16"
MOTORIZED, FIRE, FIRE/SMOKE
VOLUME DAMPER
T
DUCT HANGER DETAIL
R
CO 2
SCALE: NTS
M088
H
THERMOSTAT, REMOTE SENSOR
OR HUMIDISTAT
CARBON DIOXIDE SENSOR
NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS
GLOBE VALVE
STRAINER
STRAINER WITH DRAIN VALVE
RODAHL & HUMMELL
ARCHITECTURE, P.C.
REDUCED PRESSURE
BACKFLOW PREVENTER
2-WAY VALVE
BUTTERFLY VALVE
04/27/2016
PRV
KEYED NOTE DESIGNATION
NOTES:
1. FOR SEVERAL DUCTS ON ONE HANGER TYPE "B"-"C" OR "D" MAY BE USED. SIZE OF HANGER WILL BE SELECTED ON THE SUM
OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF DUCT SCHEDULE.
2. SCHEDULE FOR ANGLES FOR BRACING: TYPE "B" 1½"x1½"x1/8" ANGLE MAX. SPACING 8'-0"
ANGLE MAX. SPACING 8'-0" CENTERS; TYPE "D" 2"x2"x¼" MAX. SPACING 4'-0" CENTERS.
CONTROL
B1 DELAY/RELY
SCALE: NTS **DELETE IF BOILER SYSTEM ALTERNATE BID IS ACCEPTED**
DUCT SCHEDULE
DUCT
DIMENSIONS
TYPE
INCHES
HANGER
UP THRU
14
20
32
44
56
62
86
OVER
MODEL
0013
RADIANT TUBE HEATER DETAIL
M053
HANGER ROD SIZE:
TYPE "B" ¼"
TYPE "C" ¼"
TYPE "D" 3/8"
ELEC
120V/1∅
RADIANT HEATERS: TWO-STAGE, PROPANE FIRED RADIANT TUBE HEATER. PROVIDE
WALL-MOUNTED THERMOSTAT, OSA AND FLUE ROOF TERMINATION CAP
ELECTRICAL = 120 V/1∅/5 A
"REVERBERAY" MODEL **DELETE IF BOILER ALTERNATE IS ACCEPTED**
HEATING
WEIGHT
INPUT MBH LENGTH COMMENTS
UNIT
MODEL
HORIZONTAL MOUNTING
235LBS.
RH
DET3-50
125/82
30'
TUBE HEATER
SLOPE PER MANUFACTURER'S
RECOMMENDATIONS
AIR INTAKE COLLAR
RPM
1725
RH
B1
18" STAND
DISTANCE
FROM COIL FT.
25
20
FURNACE: PROPANE FIRED, ELECTRIC COOLING, INDIRECT FIRED, CONDENSING
FURNACE CAPABLE OF INPUT AS LISTED. PROVIDE COOLING COIL LISTED, LINE SET,
AUTO CHANGE OVER, WALL-MOUNTED PROGRAMMABLE SET BACK 24 V
THERMOSTAT, FILTER AND CONCENTRIC VENTING KIT FOR VERTICAL VENTING.
ORIFICE FOR 5600' ABOVE SEA LEVEL ELEC.=120 V/1∅. PROVIDE A CONDENSATE
PUMP W/ 6' POWER CORD.
"TRANE"
HEAT
COOL INPUT
OA ESP
WGT
UNIT MODEL
MBH MBH CFM CFM " W.C. LBS. MCA MOCP FLOW
F1 TDX040A9H21B 22.1 40
872 120 0.50
135
9.7
15
HORIZ.
F2 TDX060A9H31B 32.9 60
1300 198 0.90
155
9.7
15
HORIZ.
P1
XT2
WGT.
LBS.
130
261
F1F2
RP
CHAIN
MAX.
AMPS MCA ELEC
30
18.0 208-230V/1∅
60
35.0 208-230V/1∅
DRYER BOX: UPWARD FLOW, 2X4 WALL SIZE.
"GUY GRAY" MODEL DB-350
17. FIELD VERIFY THAT ALL NEW DUCTWORK CAN FIT WITHIN THE SPACE PROVIDED
PRIOR TO FABRICATING ANY NEW DUCTWORK. EXISTING DUCTWORK SHOWN IS
FROM ORIGINAL AS-BUILT DRAWINGS AND NOT ALL CONFIGURATIONS HAVE BEEN
VERIFIED.
4" GOOSENECK
WITH INSECT
SCREEN
BALL VALVE, TYP.
COOL
MBH
21.1
32.9
DB
M092
M168
CONTROL
INTEGRAL
CX1- CEILING EXHAUSTER: DIRECT DRIVE CEILING MOUNTED EXHAUSTER WITH
CX5 BACKDRAFT DAMPER, VIBRATION ISOLATOR KIT, INTEGRAL GRILLE, AND
BIRDSCREEN. 120 V/1∅
"COOK"
ESP
UNIT MODEL CFM
("WC) WATTS ACCESSORIES CONTROLLED BY
CX1 GC124
75
0.25"
50
ROOF JACK
OCCUPANCY SENSOR
CX2 GC164
150
0.25"
109
OCCUPANCY SENSOR
ROOF JACK
150
0.25"
109
CX3 GC164
OCCUPANCY SENSOR
ROOF JACK
CX4 GC124
75
0.25"
50
ROOF JACK
OCCUPANCY SENSOR
CX5 GC124
75
0.25"
50
WALL CAP
THERMOSTAT
15. REVIEW THE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE ON THE
ELECTRICAL DRAWINGS FOR CLARIFICATION OF WORK BETWEEN DISCIPLINES.
SCALE: NTS
EWT/LWT
90°F./110°F.
CARBON MONOXIDE/NITROGEN DIOXIDE CONTROLLER: DIGITAL CONTROLLER WITH
PROGRAMMING INTERFACE, TWO 24V OUTPUT RELAYS TO CONTROL FAN AND
DAMPER, FIVE INPUT CONTACTS. PROVIDE REMOTE COMBINATION CO/NO2 SENSORS
WITH MANUAL OVERRIDE CAPABILITIES. 120V/1A.
"ARMSTRONG" AMC-1AD1
UNIT MODEL
CU1 4TTB4024
CU2 4TTB3036
13. PROVIDE ONE UNION AT ALL VALVES OR SUITABLE MEANS OF REMOVAL WITHOUT
PIPE CUTTING ON SCREWED PIPING. UNIONS REQUIRED ON COPPER PIPING AT
EQUIPMENT CONNECTION.
14. PROVIDE CONDENSATE DRAINS FROM ALL REFRIGERATED AIR HANDLING UNITS TO
THE NEAREST FLOOR SINK WITHIN THE BUILDING.
OUTPUT
MBH AMPS WEIGHT
63
0.5
125LBS.
MBH
80
CU1- CONDENSING UNITS: 14 SEER REMOTE, AIR-COOLED CONDENSING UNITS FOR USE
CU2 WITH FURNACE COILS LISTED. PROVIDE R-410A REFRIGERANT, CRANKCASE HEATER,
AND LOW AMBIENT KIT. EAT=80°F./60°F., AMBIENT CONDITIONS = 94°F DB/63°F WB
UNIT TO BE CONTROLLED BY THERMOSTAT PROVIDED WITH FURNACE.
"TRANE" MODEL AS INDICATED.
11. COORDINATE ALL PROPOSED ROOF PENETRATIONS WITH GENERAL CONTRACTOR
AND ARCHITECT AND RELOCATE IF NECESSARY.
FACTORY FABRICATED ROUND
TO RECTANGULAR OR SQUARE
ADAPTER. SEE DIFFUSER
SCHEDULE.
BOILER: DIRECT VENT, CONDENSING, PROPANE, 95%+ EFF. BOILER CONSTRUCTED
IN COMPLIANCE WITH SECTION IV OF ASME CODE. COMPLETE W/ ASME CSD-1
CONTROLS, 5:1 TURNDOWN MODULATING FIRING, HIGH LIMIT TEMP. CONTROLLER
MANUAL RESET, FLOW SWITCH, LOW WATER CUTOFF, CAPACITY AT EWT/LWT= MBH
OUTPUT AT 5500' ASL., HIGH & LOW GAS PRESSURE SWITCHES, CONDENSATE
NEUTRALIZER KIT, SIDEWALL VENT TERMINATION KIT. 120V/1PH.
"LOCHINVAR" KNIGHT **ALTERNATE BID#1**
UNIT MODEL
B1
KBN81
10. COORDINATE WITH THE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT
LAYOUT OF DIFFUSERS, GRILLES AND CEILING MOUNTED EQUIPMENT.
ROUND RIGID DUCT. SEE PLANS
FOR SIZES
INSULATION PER ARCH. R-13
DIFFUSER
VERIFY THAT DIFFUSERS, REGISTERS, GRILLES, DUCTWORK AND ALL EQUIPMENT
SPECIFIED IS CORRECT FOR FIELD INSTALLATION BEFORE ORDERING OR
FABRICATING. PROVIDE A WRITTEN REQUEST FOR INFORMATION TO THE ENGINEER
FOR A RULING ON HOW TO PROCEED IF CONDITIONS EXIST THAT WILL NOT ALLOW
FOR THE INSTALLATION OF THE EQUIPMENT SPECIFIED.
PROVIDE AND INSTALL DAMPERS IN THE BRANCH DUCTS, NEAR THE MAIN, SERVING
DIFFUSERS AND GRILLES TO ALLOW PLUS OR MINUS 10% OF THE CFM REQUIRED
FROM EACH DIFFUSER AND REGISTER AS LISTED ON THE PLANS.
M152B
5/8" PEX WITH OXYGEN BARRIER,
9"O.C. EMBEDDED IN SLAB AS
SHALLOW AS STRUCTURALLY
FEASIBLE
VIBRATIONALLY ISOLATE ALL EQUIPMENT AND PIPING FROM THE BUILDING
STRUCTURE. COORDINATE TO ASSURE THAT AS QUIET AN OPERATING SYSTEM AS
POSSIBLE IS INSTALLED.
6.
HORIZONTAL FURNACE DETAIL
MECHANICAL SCHEDULE
#
ARCHITECTURE
10"x10"
CLEAR INSIDE DUCT
DIMENSION (NEW)
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
MECHANICAL DETAILS AND
SCHEDULES
Checked: Date:
Drawn:
REV
DS
2016-05-11 Of:
M601
KEYED NOTES
22.01
22.02
22.03
22.04
22.05
22.06
22.07
22.08
22.09
22.10
22.28
GCO
22.04
22.45
WH2
22.33
22.14
22.22
22.36
22.35
22.19
FPHB
22.20
2"SS
S2
LAUNDRY
106
22.17
1"CW
1"HW
3/4"HWR
R.R.
113 22.44
L
FD
TMV
2"V
FPHB
L
TMV
WC
R.R.
SH 114
FD
SH
WC
1/2"HW
22.35
IMB
FS
22.34
22.38
S1
TMV
GD
DW
WC
S3
22.15
U
3/4"CW
3/4"HWR
22.15
3"SS
HB
3"VTR
22.17
22.15
22.16
3"VTR
2"V
22.24
1"A
22.30
3"VTR
22.12
2"V
22.40
1-1/2"LPG
1-1/4"
FD
WH1
22.33
4"SS
22.16
22.05
22.28
GCO
4"SS
22.43
DCO
FCO
4"SS
4"SS
2"LPG
22.06
22.08
22.22
22.23
22.24
22.25
22.26
22.27
4"SS
22.27
22.42
22.07
22.28
22.29
22.30
22.31
22.32
22.33
DAY ROOM
101
22.31
22.31
22.31
3/4"A
HB
22.23
22.29
FPHB
22.22
HB
22.34
22.35
22.36
FPHB
22.37
22.22
FCO
OFFICE
102
22.20
22.21
2"V
22.11
STOR.
115
22.44
KITCHEN
100
2"V
2"LPG
22.14
22.16
22.11
22.12
22.13
22.14
22.15
22.16
22.17
22.18
22.19
22.41
BV
2"SS
2"VTR
1-1/4"CW
1"HW
WCO
L
TMV
4"SS
22.25
1"CW
1"CW
3/4"LPG
3/4"A
1"CW
APPARATUS BAY
103
1-1/2"CW
22.28
GCO
3"VTR
22.21
2"V
FS
1"A
3/4"CW
R.R.
111
FD
3/4"LPG
S4
WCO
ICE HB
22.26
1"CW
HALL
112
VEST
105
1-1/2"CW
22.22
2"V
W
22.13
1"LPG
22.13
IT
112A
BUNKER
FS 104
1-1/2"CW
22.18
SLEEPING
107
S5
FD2
22.10
22.23
3"SS
SLEEPING
108
1"LPG
SLEEPING
109
1"HW
1"LPG
22.32
SLEEPING
110
D
D
WB
W
22.09
22.23
22.39
22.37
1-1/4"LPG
22.03
22.23
22.38
22.02
22.46
22.39
22.40
22.41
22.42
22.01
22.43
22.44
22.45
22.46
1
N
1-1/2"CW FROM SITE. FOR CONTINUATION SEE CIVIL DWGS.
1-1/2"CW RISE IN FURRED WALL TO ABOVE CEILING.
1-1/2"CW DROP TO WATER ENTRANCE. SEE DETAIL.
1-1/2"CW RISE FROM WATER ENTRANCE.
500 GALLON PRECAST OIL INTERCEPTOR. SEE DETAIL.
2-WAY CLEAN-OUT TO GRADE. SEE DETAIL.
2"LPG BELOW GRADE (BY PLUMBING CONTRACTOR) FROM LPG TANK ON SITE. SEE CIVIL
DWGS. FOR LPG TANK LOCATION.
2"LPG RISE FROM BELOW GRADE TO SHUT-OFF VALVE AT 16" ABOVE GRADE. OFFSET AT 24"
ABOVE GRADE THROUGH WALL INTO BUILDING AND RISE TO HIGH STRUCTURE.
1-1/4"LPG DROP TO HOTSY MACHINE. SEE GAS CONNECTION DETAIL.
1"CW DROP. MAKE CONNECTION TO HOTSY MACHINE/HOSE REEL (BY OWNER) VIA BALL VALVE
AND PER MANUFACTURER'S RECOMMENDATION. VERIFY EXACT REQUIREMENTS WITH
OWNER.
3/4"LPG DROP TO RADIANT HEATER. SEE GAS CONNECTION DETAIL.
1-1/4"LPG DROP ALONG WALL, THROUGH WALL INTO LOWER CEILING SPACE.
3/4"LPG CONNECTION TO FURNACE ABOVE CEILING. SEE GAS CONNECTION DETAIL.
1"LPG DROP TO WATER HEATER (WH). SEE GAS CONNECTION DETAIL.
3/4"CW DROP, 3"SS DOWN AND 2"V RISE FROM WATER CLOSET.
1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM LAVATORY.
1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 2"V RISE FROM SHOWER.
1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM SINK.
1"CW, 1"HW DROP EXPOSED TO PRECAST FLOOR SINK (S5) FAUCET. SEE SCHEDULE. 3"SS
DOWN AND 2"V RISE FROM SINK DRAIN (FD2).
3/4"CW, 3/4"HW DROP, 2"SS DOWN AND 2"V RISE FROM WASHER BOX (WB).
3/4"CW, 3/4"HW DROP TO WASHER/EXTRACTOR AND FULL SIZE INDIRECT WASTE TO FLOOR
SINK.
3/4"CW DROP TO HOSE BIBB(S).
3/4"A DROP TO AIR OUTLET. SEE DETAIL.
3/4"CW DROP, 2"SS DOWN AND 2"V RISE FROM URINAL.
1/2"CW DROP TO ICE MAKER BOX (IMB) AND FULL SIZE INDIRECT WASTE TO FLOOR SINK.
1"A RISE FROM (OWNER FURNISHED/CONTRACTOR INSTALLED) AIR COMPRESSOR. SEE
DETAIL.
4"TRAPPED CONNECTION TO TRENCH DRAIN. COORDINATE WITH GENERAL CONTRACTOR.
EXTEND 2"V RISE ALONG WALL AND OFFSET OVERHEAD TO 3"VTR.
GRADE CLEANOUT. SEE DETAIL.
1-1/2"CW OFFSET THROUGH WALL AND RISE TO HIGH STRUCTURE.
(2)2"V RISE FROM BELOW GRADE. CONNECT AT 42" ABOVE FLOOR AND 2"V RISE TO HIGH
STRUCTURE. OFFSET TO 3"VTR.
COORDINATE PIPE ROUTING OVER PATH OF OVERHEAD DOOR TRAVEL.
3"SS DOWN AND 2"V RISE FROM FLOOR SINK.
1"CW DROP, 1"HW RISE FROM WATER HEATER AND 3/4"HWR DOWN (WH1 ONLY) TO WATER
HEATER RETURN CONNECTION. ROUTE 3"PVC FLUE AND INTAKE THROUGH ROOF. TERMINATE
WITH FACTORY VENT KIT. SEE WATER HEATER DETAIL SHEET P601.
3/4"LPG DROP TO STOVE. SEE GAS CONNECTION DETAIL.
2"SS DOWN AND 2"V RISE FROM FLOOR SINK.
OFFSET 3/4"CW, 3/4"HW TO SINK (S4) FAUCET AND PRE-RINSE. COLLECT FULL SIZE (COPPER)
INDIRECT WAASTE FROM EACH COMPARTMENT OF SINK AND ROUTE TO PRECAST FLOOR
SINK. TERMINATE WITH ELBOW TURNED DOWN.
3/4"CW OFFSET AND CONNECTION TO ICE MACHINE VIA BALL VALVE AND BACKFLOW
PREVENTOR (BFP2), AND FULL SIZE INDIRECT WASTE TO FLOOR SINK.
1/2"CW, 1/2"HW DROP, 2"SS DOWN AND 1-1/2"V RISE FROM SINK. OFFSET TO SINK AS
REQUIRED. PROVIDE SEPARATE HW STOP VALVE AND CONNECT TO ADJACENT DISHWASHER.
ROUTE DISHWASHER DRAIN TO DISPOSER DISHWASHER PORT.
3/4"LPG DROP TO BOILER. SEE GAS CONNECTION DETAIL.
1-1/4"CW DROP TO LOWER CEILING.
3/4"CW, 3/4"HW DROP, 3"SS DOWN AND 2"V RISE FROM MOP SINK (S3).
1-1/2"CW CONNECTION (VALVED) TO BFP3 OVERHEAD. EXTEND FIRE SPRINKLER PIPING TO
SEMI-RECESSED FIRE SPRINKLER HEADS LOCATED IN SLEEPING ROOMS, HALL, RR113 AND
RR1114 CEILINGS PER NFPA 13R.
4"SS TO SITE. FOR CONTINUATION SEE CIVIL DWGS.
2"V RISE TO ABOVE CEILING.
3/4"LPG DROP TO DRYER. SEE GAS CONNECTION DETAIL.
BUILDING SHUT-OFF VALVE IN VALVE BOX.
PLUMBING FLOOR PLAN
1/8" = 1'-0"
24" HOLE FOR MANHOLE
RING AND COVER - GASTIGHT.
INLET
2" COUPLING FOR VENT
INLET & OUTLET- 4" PVC
COUPLING
4"
SAND/OIL INTERCEPTOR
1. PROVIDE PARTITION BAFFLES, AND INLET AND
OUTLET BAFFLES WITH VENTS.
2. TRAFFIC RATED
3. DESIGN IN ACCORDANCE WITH 2003 ICP
SECTION 1017.1
OUTLET
CLEAN-OUT
GASTIGHT 24"
MANHOLE COVER
77"
INLET
CAST IRON FITTINGS
4" MIN.
4"
GRADE VARIABLE
AS SHALLOW
AS POSSIBLE
TO SEWER
12"
OIL
EFFLUENT
SAND
6"
4/27/16
RODAHL & HUMMELL
ARCHITECTURE, P.C.
115"
61"
A1
2
SAND/OIL INTERCEPTOR
SCALE: N.T.S.
500 GALLON CAPACITY
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
PLBG OI DTL
CENTERPOINT 2
FIRE STATION
1/8" = 1'-0"
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
PLUMBING FLOOR PLAN
Checked: Date:
Drawn:
Author
Checker 2016-05-11 Of:
P101
PLUMBING GENERAL NOTES
LPG
3"INTAKE/3"VENT,
TERMINATE PER
MANUFACTURER'S
RECOMMENDATION
1-1/2" MIN.
#3 REBAR
#3 BRAZED TO C.I., (TYP)
COMPLETE ALL WORK IN FULL COMPLIANCE WITH THE UMC, UPC, UBC, LIFE SAFETY
CODE, N.F.P.A. AND ALL LOCAL CODES AND ORDINANCES.
2.
CAREFULLY LAYOUT AND INSTALL THE PLUMBING SYSTEMS INCLUDING ALL
COORDINATION WITH MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL
EQUIPMENT AND ANY OTHER EQUIPMENT THAT MAY REQUIRE COORDINATION
EFFORTS. COORDINATE TEMPORARY CUT-OFF OF WATER AND SEWER WITH UTILITY
PROVIDERS. PERFORM ALL NECESSARY TRENCHING, BACK FILLING, CUTTING,
PATCHING, REPAIRING, ETC. ASSOCIATED WITH THE INSTALLATION OF THE
PLUMBING SYSTEM SHOWN ON THE PLANS AND DESCRIBED IN THE SPECIFICATIONS.
WH1
ADJUSTABLE CAST IRON
FERRULE WITH SCORIATED
SECURED TOP (TYP.)
BRONZE TAPERED
THREADED PLUG (TYP.)
1"
WH2
1" CHAMFER
6"
3.
VERIFY ALL INVERTS BEFORE ROUTING ANY AND ALL PIPING. NO COMPENSATION
WILL BE MADE FOR THE CONTRACTOR'S FAILURE TO COORDINATE WORK WITH SITE
CONDITIONS. BECOME TOTALLY FAMILIAR WITH ALL ASPECTS OF THE WORK AND ALL
CONSTRAINTS AND LIMITATIONS OF THE WORK REQUIRED.
4.
ROUTE PIPING AS NEARLY AS POSSIBLE TO THE ROUTING INDICATED ON THE PLANS,
BUT MAKE MINOR CHANGES IN ROUTING TO ACCOMMODATE THE CONDITIONS AT
THE SITE. DO NOT UNDERTAKE MAJOR REROUTING OF PIPING WITHOUT WRITTEN
APPROVAL FROM ENGINEER. MAKE ALL REQUIRED TRANSITIONS, OFFSETS, MINOR
RE-LOCATIONS, AND ALL ASSOCIATED FITTINGS, PIPING, AND EQUIPMENT TO
INSTALL A COMPLETE AND OPERATIONAL SYSTEM.
MIN
FINISHED GRADE
CHECK VALVE,
TYP.
TMV
WB
SOIL PIPE RISER (TYP).
TWO-WAY CLEANOUT
ROUTE DRAIN TO FLOOR
SINK VIA CONDENSATE
NEUTRALIZATION KIT
3/4"
EXPANSION TANK (XT)
MAIN
5.
WATER HEATER DETAIL
D1
DOUBLE CLEANOUT TO GRADE
D2
SCALE: N.T.S.
SCALE: N.T.S.
P??
P04
PROVIDE A POLISHED SCORIATED NICKEL-BRONZE
ACCESS COVER AND FRAME. PROVIDE CARPET
IN CARPETED AREAS
1-1/2" CW
TO BUILDING
6.
FINISH
FLOOR
CW SERVICE (OVERHEAD)
FROM SITE, SEE PLAN
#3 BRAZED TO C.I.
C.O. TO FINISHED FLOOR
1-1/2"
4" 2500 PSI
CONCRETE.
1" CHAMFER MIN.
PRESSURE GAUGE
STRAINER
16" SQ.
COMPACTED
SUBGRADE
THE PROXIMITY OF WATER AND SEWER LINES SHALL BE AS FOLLOWS, UNLESS
WRITTEN APPROVAL FROM THE STATE HEALTH DEPARTMENT SPECIFIES DIFFERENT
CONDITIONS: WHENEVER POSSIBLE, IT IS DESIRABLE TO LAY PARALLEL WATER AND
SEWER LINES AT LEAST TEN FEET APART HORIZONTALLY, AND THE WATER LINE
SHOULD BE AT A HIGHER ELEVATION THAN THE SEWER LINE. IF THIS IS NOT
POSSIBLE, SEPARATE TRENCHES WILL BE REQUIRED IN ALL CASES (THIS SHALL BE
EFFECTIVE EVEN THOUGH ONE LINE HAS BEEN INSTALLED PRIOR TO THE OTHER),
AND THE WATER LINE SHALL BE AT LEAST ONE FOOT ABOVE THE SEWER LINE.
WHERE LINES INTERSECT THE WATER LINE SHALL BE SLEEVED FOR TEN FEET ON
EACH SIDE OF THE INTERSECTION.
ALL CONTRACTORS BIDDING ON THIS PROJECT ARE CAUTIONED TO VISIT THE SITE
AND MAKE ALL NECESSARY INQUIRIES TO DETERMINE THE EXISTING CONDITIONS
PRIOR TO SUBMITTING THEIR BIDS. NO SUBSEQUENT ALLOWANCE WILL BE MADE TO
COMPENSATE FOR LACK OF PRE-BID INSPECTIONS BY THE SUCCESSFUL
CONTRACTOR. ANY LINES ENCOUNTERED WHICH MAY INTERFERE WITH NEW
CONSTRUCTION SHALL BE RELOCATED IF ACTIVE AND ABANDONED IF INACTIVE BY
THIS CONTRACTOR UNDER THIS CONTRACT BY FIRST CONTACTING THE ARCHITECT
FOR A RULING AS TO THEIR REMOVAL, RELOCATION, ETC.
7.
PROVIDE ACCESS PANELS TO ALL INACCESSIBLE PLUMBING EQUIPMENT.
8.
INSULATE ALL NEWLY INSTALLED PIPING (DOMESTIC HOT, COLD, AND RECIRC.
WATER) IN THE BUILDING. LABEL PIPE WITH FLUID TYPE AND FLOW DIRECTION.
9.
PROVIDE WALL CLEANOUTS AT ALL URINALS, SINKS AND LAVATORIES.
WH1
TANKLESS WATER HEATER: GAS-FIRED CONDENSING WALL MOUNTED WATER
HEATER, 67°F TEMPERATURE RISE @ 5.6 GPM FLOW, 199.9 MBH INPUT, INTEGRAL
CIRCULATING PUMP, DUAL STAINLESS STEEL HEAT EXCHANGERS, INTERNAL
CONTROL SYSTEM, 2" PVC VENT KIT AND CONDENSATE NEUTRALIZATION KIT.
ELECTRICAL: 120V-1∅-60Hz.
"NAVIEN" MODEL NPE-240A
WH2
TANKLESS WATER HEATER: GAS-FIRED CONDENSING WALL MOUNTED WATER
HEATER, 67°F TEMPERATURE RISE @ 5.7 GPM FLOW, 199.9 MBH INPUT, DUAL
STAINLESS STEEL HEAT EXCHANGERS, INTERNAL CONTROL SYSTEM, 2" PVC VENT
KIT AND CONDENSATE NEUTRALIZATION KIT.
ELECTRICAL: 120V-1∅-60Hz.
"NAVIEN" MODEL NPE-240S
WHA
XT
WATER HAMMER ARRESTER: PRE-CHARGED AIR CHAMBER PERMANENTLY SEALED
FROM WATER SYSTEM, BALL VALVE FOR ISOLATION, NPT BRASS ADAPTER.
PROVIDE A 12"x12" ACCESS PANEL.
"WATTS" SERIES 15.
EXPANSION TANK: POTABLE WATER USE, 175 MAX. WORKING PRESSURE, 2.0
GALLONS TOTAL VOLUME, 40 PSIG FACTORY PRECHARGE.
"AMTROL" MODEL ST-5C
1-1/2"
SYMBOL
DESCRIPTION
GROUTED PLUG WHERE
C.O. OCCURS AT END
OF LINE.
45 DEGREE `Y' BRANCH.
BACKFLOW PREVENTER
(BFP1)
WATER ENTRY ASSEMBLY
C2
SCALE: N.T.S.
L
LAVATORY: A.D.A. COMPLIANT,COUNTERTOP, VITREOUS CHINA,, 4" FAUCET
CENTERS, CHROME PLATED GRID DRAIN, OFFSET TAILPIECE "TRUE-BRO" LAV
GUARD "AMERICAN STANDARD" 7385.003 SINGLE LEVER CHROME PLATED FAUCET
LESS POP-UP DRAIN, 1.5 GPM AERATOR.
"AMERICAN STANDARD" AQUALYN 0476.028
WASTE = 2 IN., VENT = 1 - 1/2 IN., CW = 1/2 IN. HW = 1/2"
S1
SINK: (KITCHEN) A.D.A. COMPLIANT, STAINLESS STEEL TWO COMPARTMENT SINK
CONSTRUCTED OF 18 GAUGE TYPE 302 SS, REAR OFFSET DRAIN LOCATION.
ELKAY LKA-4100 FAUCET LESS SPRAYER, 1.5 GPM AERATOR.
"ELKAY" MODEL LRAD-3319 (6-1/2" DEEP).
WASTE = 2"., VENT = 1-1/2"., CW = 1/2"; HW = 1/2"
S2
SINK: (LAUNDRY) A.D.A. COMPLIANT, STAINLESS STEEL SINGLE COMPARTMENT
SINK CONSTRUCTED OF 18 GAUGE TYPE 302 SS, REAR OFFSET DRAIN LOCATION.
ELKAY LKA-4100 FAUCET LESS SPRAYER, 1.5 GPM AERATOR.
"ELKAY" MODEL LRAD-2522 (6-1/2" DEEP).
WASTE = 2"., VENT = 1-1/2"., CW = 1/2"; HW = 1/2"
S3
MOP SINK: 24"x24" PRECAST TERRAZZO, STAINLESS STEEL CAPS ON ALL
CURBS, WALL MOUNTED 3 STATION MOP HOLDER. RIGID SPOUT, VACUUM
BREAKER, PAIL HOOK, WALL BRACE AND 3/4" THREADED HOSE OUTLET.
"CHICAGO" MODEL 445-897SRCXKCP FAUCET.
"FIAT" MODEL TSB100
WASTE = 3 IN., VENT = 2 IN., CW & HW = 3/4 IN.
S4
SINK: (APPARATUS BAY) 3-COMPARTMENT TYPE 304 16 GA. STAINLESS STEEL SINK
WITH DUAL DRAINBOARDS, SEAMLESS CONSTRUCTED, REAR 8" BACKSPLASH WITH
(2) 8" CENTER PUNCHES FITTED WITH K-112 12" SWINGSPOUT FAUCET AND DTA-53
PRE-RINSE SPRAY. (3)18"x 24" COMPARTMENTS EACH FITTED WITH TWIST HANDLE
DRAIN VALVE WITH STRAINER,
"ADVANCE-TABCO" 93-63-54-18RL
INDIRECT WASTE = 2" (X3)., CW = 3/4"; HW = 3/4"
S5
PRECAST FLOOR SINK: PRECAST CURBS BY GENERAL CONTRACTOR. PROVIDE
TRIM INCLUDING RIGID SPOUT FAUCET WITH VACUUM BREAKER, PAIL HOOK,
WALL BRACE AND 3/4" THREADED HOSE OUTLET. ALSO SEE FD2 SCHEDULE.
"CHICAGO" MODEL 445-897SRCXKCP FAUCET.
WASTE = 3 IN., VENT = 2 IN., CW & HW = 3/4 IN.
SH
SHOWER, PRESSURE BALANCING VALVE WITH LEVER HANDLE, INTEGRAL
STOPS, 30"SLIDE BAR AND 69"METAL HOSE, 1.5GPM FLOW CONTROL, 36"x 36x
75-3/4" HIGH MOLDED VIKRELL 3-WALL MODULAR SURROUND AND BASE.
"MOEN" 8346EP15 TRIM, "STERLING" 72100100
WASTE = 2 IN., VENT = 1 - 1/2 IN., CW & HW = 1/2 IN.
HOT WATER SUPPLY (140°F) (HW)
HOT WATER RETURN (HWR)
LIQUID PROPANE GAS (11"w.c.)
LPG
11. PRESSURE TEST, FLUSH AND DISINFECT ALL DOMESTIC WATER PIPING PER
CHAPTER 6 OF THE PLUMBING CODE PRIOR TO CALLING FOR FINAL INSPECTION.
COMPRESSED AIR
A
12. TERMINATE ALL PLUMBING VENTS NOT LESS THAN 25' FROM ANY VENTILATION AIR
INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR AND MECHANICAL DWGS.
TERMINATE WITH VENT CAP (VC).
SANITARY WASTE (ABOVE FLOOR)
SAN
SANITARY WASTE (SAN) (BELOW FLOOR)
CLEANOUT DETAIL
CHECK VALVE
SCALE: N.T.S.
BFP1 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, LEAD FREE, BRONZE BODY WITH
STAINLESS STEEL SPRINGS, REDUCED PRESSURE PRINCIPLE, TWO "Y" PATTERN
CHECK VALVES AND ONE HYDRAULICALLY DEPENDENT DIFFERENTIAL RELIEF
VALVE, BALL SHUT OFF VALVES AND FUNNEL DRAIN KIT. ASSE STANDARD 1013.
"FEBCO" MODEL LF825Y
BFP2 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, DUAL CHECK, LEAD FREE, IN-LINE
CONTINUOUS PRESSURE APPLICATION.
"WATTS" LF7
GAS COCK
BFP3 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, DOUBLE CHECK, LEAD FREE CAST
COPPER BODY, STAINLESS STEEL SPRINGS, 175 PSI MAX. WORKING PRESSURE,
ASSE 1015.
"FEBCO" LF850
RELIEF VALVE
CO
EXTERIOR CLEANOUT: PVC OR ABS FEMALE ADAPTER WITH CLEANOUT PLUG.
LOCATED 2 IN. BELOW GRADE.
CO
INTERIOR FLOOR CLEAN OUT: CAST IRON CLEAN OUT WITH THREADED
ADJUSTABLE HOUSING, SV HUB OUTLET, FLANGED FERRULE WITH PLUG AND
ROUND SCORIATED POLISHED BRONZE SECURED TOP.
"ZURN" MODEL ZB-1400- (VERIFY SURFACE TYPE)
FD
FLOOR DRAIN: CAST IRON FLOOR DRAIN WITH TRAP GUARD, VANDAL PROOF
SECURED TOP, NICKEL BRONZE STRAINER.
"ZURN" MODEL Z-415 W/ TYPE B STRAINER
WASTE = 2 IN., VENT = 2 IN.
FD2
FLOOR DRAIN: CAST IRON FLOOR DRAIN WITH TRAP GUARD, VANDAL PROOF
SECURED TOP, NICKEL BRONZE STRAINER.
"ZURN" MODEL Z-415 W/ TYPE B STRAINER
WASTE = 3 IN., VENT = 2 IN.
STRAINER
TERMINATE WITH
VENT CAP (VC)
UNION
WATER HAMMER ARRESTER
SEE PLAN FOR
CONTINUATION
PRESSURE SWITCH, GAUGE
VALVE, UNIONS AND FLEX
HOSE BY COMPRESSOR
MANUFACTURER
RUBBER BOOT
12" MIN.
SEAL WATERTIGHT
ROOFING OVER BASE
CONTINUOUS
RUBBER BOOT
URINAL: A.D.A. COMPLIANT, VITREOUS CHINA W/ WASHOUT ACTION, 3/4" TOP SPUD
INLET 2 IN. OUTLET, ADJUSTABLE FLOOR SUPPORTED WALL CARRIER, "AMERICAN
STANDARD" 6045.013.002 1.0 PINT MANUAL FLUSH VALVE.
"AMERICAN STANDARD" WASHBROOK MODEL 6590.125
WASTE = 2 IN., VENT = 1-1/2 IN., CW = 1 IN.
COLD WATER (CW)
BALL VALVE
SOLENOID
PRV
1"
BACKFLOW PREVENTER
CLEANOUT
TEE
PRESSURE
GUAGE 0-160 PSI
AIR COMPRESSOR
(OWNER
FURNISHED)
SEE ARCH.
DWG's FOR
ROOF
CONST.
8" MIN.
U
KEYED NOTE
VENT
10. PERFORM PRESSURE TEST OF WASTE/VENT LINE PER CODE. COMPLETE A
SUCCESSFUL TEST PRIOR TO COVERING THE WORK.
TO FLOOR
SINK
FLUSH TANK WATER CLOSET: A.D.A COMPLIANT, 1.28 GPF FLOOR MOUNTED
VITREOUS CHINA, SIPHON JET, ELONGATED TOILET, EVERCLEAN SURFACE. OPEN
FRONT SEAT LESS COVER, BOLT CAPS. FLUSH LEVER OPPOSITE SIDEWALL.
"AMERICAN STANDARD" CADET MODEL 3339.128.
WASTE = 3", VENT = 2", CW = 3/4"
UNIT DESIGNATION
1/8 BEND
SOIL PIPE RISER.
WC
PLUMBING SYMBOLS LEGEND
C.O. TO GRADE
1-#3 REBAR, CONT.
C1
THERMOSTATIC MIXING VALVE: 1/2"-1" (SEE PLAN FOR SIZE)ASSE 1070 AND 1017,
POINT-OF-USE MIXING VALVE. SET AT 105°F. COLD WATER 50°F.; HOT WATER
140°F.;
"APOLLO"
MODEL
MVB POWDER COATED METAL WASHER BOX WITH QUARTER
WASHER BOX:
WHITE
TURN VALVES AND WATER HAMMER ARRESTORS
"GUY GRAY" MODEL 82158
WASTE = 2 IN.; VENT = 2 IN.; CW = 3/4 IN.; HW = 3/4 IN.
WCO WALL CLEANOUT: BRASS PLUG WITH ROUND STAINLESS STEEL SECURED ACCESS
COVER, SEE PLAN FOR SIZE.
"ZURN" MODEL Z-1468
UNION, TYP.
BALL VALVE,
TYP.
SCHEDULE
SCHEDULE
1.
3000 PSI CONCRETE
3/4"
GAS COCK
18" MIN
24" MIN
STAINLESS STEEL
ACCESS COVER W/
COUNTERSUNK SCREW
FLOOR SINK
VENT THRU ROOF
DCO
BLOW DOWN
VALVE
CO
INCREASE TO NEXT LARGER
PIPE SIZE (EXCEPT 4")
FINISHED WALL
NEOPRENE VIBRATION
ISOLATION PAD (YTP.)
VENT, REQUIRED SIZE
FPHB HOSE BIBB: FREEZELESS, AUTOMATIC DRAINING, WALL HYDRANT: BRASS WITH
POLISHED CHROME PLEATED CASTING, KEY OPERATED, AND CHROME PLATE
VACUUM BREAKER, 3/4" FPT, MIN. 12" LENGTH
"WOODFORD" MODEL 67-3/4 IN
DOUBLE CLEAN OUT
CLEAN OUT
M
METER
(E)
(EXISTING)
IW
INDIRECT WASTE
GC
GENERAL CONTRACTOR
GD
GARBAGE DISPOSER, WITH DISHWASHER PORT WHERE APPLICABLE.
KITCHEN AID KCD1075B (BY G.C., SEE ARCH.).
ELECTRICAL: 115V-1PH, 3/4 HP
HB
HOSE BIBB: ANTI-CONTAMINATION CLOSE COUPLED TRIMLINE WALL HYDRANT
EQUIPPED WITH A VACUUM BREAKER-BACKFLOW PREVENTER, CAPABLE OF
FITTING IN A 4" WALL THICKNESS.
"WOODFORD" MODEL B75
IMB
B1
VENT THRU ROOF DETAIL
B2
SCALE: N.T.S.
AIR COMPRESSOR PIPING
B3
SCALE: N.T.S.
P40
WALL CLEANOUT DETAIL
SCALE: N.T.S.
P41
P95
PC
PLUMBING CONTRACTOR
TYP
TYPICAL
ICE MAKER BOX: 20 GAUGE, GALVANIZED STEEL RECESSED BOX WITH
OUTLET ANGLE VALVE.
"GUY GRAY" MODEL BIM875
1/ "
2
INLET,
1/ "
4
OI
NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS
SAND/OIL INTERCEPTOR: 500 GALLON PRECAST TRAFFIC RATED CONCRETE
INTERCEPTOR, GAS TIGHT BOLTED MANHOLE COVERS, EXTENSION RINGS AS
REQUIRED.
"FOUR CORNERS PRECAST"
WATER HAMMER
ARRESTOR
BALL VALVE
1"
1/2" CW
QUICK CONNECT
COUPLER
PROVIDE GAS PRESSURE
REGULATOR (WHERE REQUIRED)
VENTED TO OUTDOORS WHEN
LOCATED INSIDE
GAS COCK
12" SWINGSPOUT
FAUCET
18"DRAINBOARD
8" HIGH
BACKSPLASH
2" VENT
1"
4/27/16
GAS
CONNECTOR OR
RIGID PIPE
1/2" HW
CLEANOUT
14"
3/4"CA
PRESSURE REGULATOR
WITH PRESSURE GAUGE
(0-175 PSI)
PRE-RINSE
SPRAY
WASHING MACHINE
SUPPLY AND
DRAIN UNIT
TWIST HANDLE
DRAIN (TYP. 3)
2" STANDPIPE
MIN. 6" DIRT LEG
MIN. 6"
DIRT LEG
FINISHED FLOOR
UNION
ARCHITECTURE
UNION
2" WASTE
2"INDIRECT WASTE
ROUTED TO ADJACENT
PRECAST FLOOR SINK
LONG RADIUS
THREADED CAP
A1
COMPRESSED AIR DROP DETAIL
A2
SCALE: N.T.S.
P??
RODAHL & HUMMELL
ARCHITECTURE, P.C.
18"W x 24"
COMPARTMENT X3
WASHER BOX CONNECTION
A3
SCALE: N.T.S.
P42
GAS CONNECTION DETAIL
SCALE: N.T.S.
A4
SINK S4 DETAIL
SCALE: N.T.S.
ADJUSTABLE
BULLET FEET)
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
PLUMBING DETAILS AND
SCHEDULES
Checked: Date:
Drawn:
Author
Checker 2016-05-11 Of:
P601
ELECTRICAL SYMBOLS LEGEND
FIRE ALARM
SWITCHING
LIGHTING
RECTANGULAR FIXTURE, CEILING MOUNTED
(DIMENSIONS AS SHOWN)
A
FACP
FIRE ALARM (FA) CONTROL PANEL
ANN
FA ANNUNCIATOR
ROUND FIXTURE, CEILING MOUNTED
(DIMENSIONS AS SHOWN)
A
A
B
C
TRACK LIGHTING
(LENGTH AS SHOWN, HEADS NOT TO SCALE)
A
POLE MOUNTED FIXTURE
(HEADS NOT TO SCALE)
ARM SYMBOL ADDITION
INDICATES WALL MOUNTING
A
A
DOT SYMBOL ADDITION
INDICATES PENDANT MOUNTING
A
A
FA CEILING MOUNTED FA HORN/STROBE
F
FA ADA STROBE
F
FA CEILING MOUNTED FA STROBE
F
FA FIRE ALARM PULL STATION
F/S
FA FIRE/SMOKE DAMPER
RI
FA REMOTE INDICATOR
FS
FA FLOW SWITCH
TS
FA TAMPER SWITCH
1.
PROVIDE, INSTALL, AND COORDINATE ALL WORK INDICATED BY THESE DRAWINGS. THIS CONSISTS OF
FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS IN ADDITION TO PERFORMING ALL OPERATIONS
INCLUDING CUTTING, CHANNELING & UNDERGROUND TRENCHING, BACK FILL & TAMPING NECESSARY FOR THE
INSTALLATION OF COMPLETE POWER, LIGHTING, OR OTHER SYSTEMS AS SHOWN.
2.
PERFORM ALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER IN FULL COMPLIANCE WITH ALL
APPLICABLE, ADOPTED, CODES; INCLUDING, BUT NOT LIMITED TO THE NATIONAL ELECTRICAL CODE (NEC),
UBC, IBC, NFPA, AND ADA. ALL LOCAL AND STATE REQUIREMENTS WILL BE OBSERVED DURING THE
PERFORMANCE OF THIS WORK.
3.
NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND ANY ASSOCIATED
LEGAL OR SAFETY REQUIREMENTS ARE DETECTED. THE ENGINEER WILL MODIFY THE CONTRACT DOCUMENTS
ACCORDINGLY. IF THE CONTRACTOR PROCEEDS W/ ANY WORK WHICH IS IN VARIANCE OF KNOWN LEGAL OR
SAFETY REQUIREMENTS, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR THIS WORK AND WILL PROMPTLY
CORRECT THE WORK, WHEN NOTIFIED WITHOUT ADDITIONAL COST TO THE OWNER.
4.
FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK. NOTIFY THE ENGINEER OF ANY
DISCREPANCIES BEFORE PROCEEDING. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED
WITHOUT PROPER NOTICE PLUS PRIOR DETERMINATION OF TIME AND COST TO THE OWNER.
5.
CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FOREIGN
MATTER, PAINT, OR DIRT, GREASE, UNNEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE
ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FOR THE PREMISES.
WALL OCCUPANCY SENSOR (ARROWS INDICATE VIEW)
6.
COORDINATE ALL PHASES OF THE ELECTRICAL WORK WITH THE ARCHITECT AND GENERAL CONTRACTOR.
PERFORM WORK TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER.
POWER OUTLETS
7.
OBTAIN, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO
ASSURE THAT PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES
INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT ELECTRICAL
CONTRACTOR'S EXPENSE.
8.
VERIFY ELECTRICAL DEVICE LOCATIONS WITH ARCHITECTURAL CASE WORK DETAILS PRIOR TO ANY ROUGH-IN.
9.
VERIFY FINAL LOCATIONS OF ALL SINKS WITH THE PLUMBING CONTRACTOR PRIOR TO ROUGH-IN. ANY
ELECTRICAL DEVICES LOCATED ABOVE COUNTER AND BEHIND FINAL SINK LOCATIONS WILL BE SHIFTED A
MINIMUM OF 8'' TO EITHER SIDE OF SINK. ANY ELECTRICAL DEVICES LEFT BEHIND SINK AT TIME OF FINAL
ELECTRICAL WALK THROUGH WILL BE RELOCATED AT ELECTRICAL CONTRACTOR'S EXPENSE.
10.
PRIOR TO INSTALLATION, THE OWNER RESERVES THE RIGHT TO RELOCATE ANY ELECTRICAL DEVICE, UP TO A
DISTANCE OF 12", WITHOUT ADDITIONAL CHARGE.
11.
FIELD VERIFY AND COORDINATE THE EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT WITH ALL TRADES
PRIOR TO INSTALLATION. WHERE EXACT LOCATIONS ARE NECESSARY, THEY ARE DIMENSIONED ON THESE
DRAWINGS. WHERE THERE IS A QUESTION OF ADEQUATE CLEARANCE OR COORDINATION BETWEEN TRADES, THIS
CONTRACTOR WILL PREPARE AS BUILT DRAWINGS FOR ENGINEERS REVIEW.
12.
CONTACT UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV., ETC.) PRIOR TO
TRENCHING IN ORDER TO IDENTIFY UNDERGROUND UTILITIES. CONTRACTOR SHALL LOCATE SECONDARY SERVICE
FEEDERS, UNDER- GROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC., PRIOR TO TRENCHING.
ANY CUT DAMAGED UNDER- GROUND UTILITIES SHALL REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE.
13.
UTILIZE COPPER CONDUCTORS, RATED FOR 600 VOLTS, TYPE THHN/THWN INSULATION, UNLESS OTHERWISE
INDICATED. MINIMUM WIRE SIZE #12 AWG AND STRANDED FOR #8 AWG OR LARGER, RUN WIRING IN CONDUIT
INCLUDING LOW VOLTAGE AND CONTROL WIRING, UNLESS OTHERWISE NOTED.
14.
UTILIZE 1/2 INCH E.M.T. CONDUIT MINIMUM. WHERE REQUIRED TO PROTECT FROM PHYSICAL DAMAGE, USE
RIGID OR IMC TYPE CONDUIT. RUN CONDUIT CONCEALED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. USE
FLEXIBLE METALLIC CONDUIT WHERE NEEDED. PROVIDE EXPANSION FITTINGS FOR CONDUIT CROSSING
EXPANSION JOINTS.
15.
SUPPORT ALL CONDUIT INDEPENDENTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FROM VENTILATION
DUCTS, MECHANICAL PIPING, SUSPENDED CEILING GRIDS, OR THEIR HANGERS. USE ONLY ACCEPTABLE
METHODS OF SUPPORT.
16.
TERMINATING & SPLICING: MAKE ALL JOINTS & SPLICES IN BRANCH CIRCUIT WIRING, #10 AWG & SMALLER,
W/ AN APPROVED SOLDER LESS TOOL OR TWIST ON CONNECTORS. #8 AWG AND LARGER USE HIGH
COMPRESSION BARREL SPLICES WITH SHRINK WRAP AND MANUFACTURER'S COMPATIBLE CONNECTORS IN
GUTTERS, AND SIMILAR LOCATIONS; BUT NOT ALLOWED IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT 2
OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT.
17.
EMT CONDUIT FITTINGS: IN DRY LOCATIONS USE STEEL SET SCREW TYPE OR "REGAL" DIE CAST SET SCREW
COUPLINGS AND CONNECTORS. DIE CAST FITTINGS WILL NOT BE USED ON THIS PROJECT. DAMP/ WET
LOCATIONS: USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTIONS.
18.
SURFACE RACEWAY: WHEREVER CONCEALED CONDUIT IN FINISHED AREAS IS NOT POSSIBLE, INSTALL SURFACE
MOUNTED RACEWAYS EQUAL TO WIREMOLD. RUN SURFACE RACEWAYS IN CORNER OF WALL AND CEILING. ALL
RACEWAYS THAT ARE EXPOSED WILL REQUIRE ARCHITECT'S/ ENGINEER'S APPROVAL PRIOR TO ROUGH-IN.
COLOR BY ARCHITECT.
19.
TYPE NM (ROMEX CABLE) AND NMC CABLE WILL NOT BE ALLOWED ON THIS PROJECT.
S
20A, 1 POLE TOGGLE SWITCH
S3
S4
SK
20A, 3-WAY TOGGLE SWITCH
SN
20A, NETWORKED SWITCH
SD
DIMMER SWITCH
20A, 4-WAY TOGGLE SWITCH
20A, 1 POLE KEY OPERATED SWITCH
PUSHBUTTON SWITCH
TC
TIME CLOCK SWITCH
PH
PHOTOSENSOR
RC
ROOM CONTROLLER (ABOVE CEILING)
CEILING OCCUPANCY SENSOR (ARROWS INDICATE VIEW)
FA GAS DETECTOR
FA SMOKE DETECTOR
EXIT SIGNS
(FILL INDICATES NUMBER OF FACES)
WITH
LIGHTS
F
HALF FILLED SYMBOL
INDICATES EMERGENCY VERSION
A-E
A-E
FA ADA HORN/STROBE. V=VOICE/STROBE
V
BOX SYMBOL ADDITION
INDICATES FLOOR OR IN-GROUND MOUNTING
A
A
F
HD
FA HEAT DETECTOR
20A, 120V, DUPLEX RECEPTACLE
DS
FA DUCT SMOKE DETECTOR
20A, 120V, FOURPLEX RECEPTACLE
WITH DOUBLE
ARROW FACE
2P-4W RECEPTACLE (SEE PANEL SCHEDULE FOR DETAILS)
NOTES:
1. Lower case letters after a comma in the fixture designation indicate switching. For
example, "A3, b" indicates a type A3 fixture controlled by switch b.
2. A fixture designation ending in "-E" indicates an emergency fixture, even where the
fixture symbol may too small to show a half fill clearly.
3. Dimensions and mounting heights in the lighting fixture schedule supercede
information implied by these symbols. Symbols are for general reference only.
POWER DISTRIBUTION
G
20A, 120V - GROUND FAULT PROTECTED (AT RECEPT.
OR BREAKER, AS REQUIRED FOR ACCESSIBILITY)
WP
20A, 120V - WEATHERPROOF IN USE COVER
GROUND FAULT PROTECTED (AT RECEPT.
OR BREAKER, AS REQUIRED FOR ACCESSIBILITY)
SURFACE MOUNTED ELECTRICAL PLUG-IN
RACEWAY
20A, 120V, DUPLEX RECEPTACLE, HALF SWITCHED
DISCONNECT SWITCH
COMMUNICATIONS
S
T
2P
SPECIAL RECEPTACLE
20A FRACTIONAL HORSEPOWER DISCONNECT
SWITCH WITH THERMAL OVERLOAD
PROTECTION. 2P = 2 POLE
DATA OUTLET
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 120V
FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 120V
MOTOR OR EXHAUST FAN
SIMPLEX TYPE RECEPTACLE
CONTROL STATION
20A, 120V, DUPLEX RECEPTACLE, ABOVE COUNTER
DATA OUTLET, ABOVE COUNTER
ANALOG PHONE OUTLET
M
METER
COMBINATION DATA & ANALOG PHONE OUTLET
R
RELAY
COMBINATION DATA & ANALOG PHONE OUTLET, ABOVE COUNTER
G
GROUND CONNECTION
ANALOG PHONE OUTLET, ABOVE COUNTER
BOX INDICATES FLUSH MOUNTING IN FLOOR
CIRCLE INDICATES FLUSH MOUNTING IN CEILING
3
M
M
S
SUBSCRIPT INDICATES QUANTITY OF PORTS (IF MORE THAN 1)
4
S
M
MICROPHONE:
CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY
S
SPEAKER:
CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY
J
DOOR CONTROLS
THERMOSTAT OUTLET BOX: SINGLE GANG
BACK BOX, PLASTER RING (UNLESS
OTHERWISE NOTED) 1/2''CONDUIT
AND PULL CORD TO MECH UNIT
T
2
J
J
JUNCTION BOX, CEILING, WALL AND
FLOOR MOUNTED RESPECTIVELY
BRANCH CIRCUIT PANEL BOARD,
SEE SCHEDULE FOR MOUNTING
T
AO
AUTOMATIC DOOR OPENER
DH
MAGNETIC DOOR HOLDER
PS
DOOR POSITION SWITCH
EL
ELECTRIC LOCK/STRIKE
KP
KEY PAD
KC
KEY CARD READER
PAD MOUNT TRANSFORMER
ABBREVIATIONS
WALL MOUNTED HORN/SPEAKER
T
WALL MOUNT TRANSFORMER
WIRELESS ACCESS POINT
WAP
SURGE PROTECTION DEVICE
TVSS
B
BELL
GROUND
C
CLOCK OUTLET, SINGLE RECEPTACLE WITH BRACKET & CLOCK
C/S
COMBINATION CLOCK & SPEAKER WALL MOUNTED
TV
TELEVISION OUTLET
CONDUIT STUB-OUT
LIGHTNING/SURGE ARRESTOR
LA
S IC
INTERCOM CONTROL SWITCH
S IV
INTERCOM VOLUME CONTROL
C1D1 RATED SEALS
SECURITY SYSTEM INFRARED MOTION SENSOR
SITE PLAN
SECURITY SYSTEM CAMERA
OR
NURSE CALL
NP
PULL CORD, WALL MOUNTED
NP
PULL CORD, CEILING MOUNTED
NB
CALL BUTTON
NL
INDICATOR LIGHT
NC
CONTROL STATION
UGP
UNDERGROUND ELECTRICAL PRIMARY FEEDER
UGE
UNDERGROUND ELECTRICAL FEEDER
UGC
UNDERGROUND COMMUNICATIONS
OHE
OVERHEAD ELECTRICAL FEEDER
OHP
OVERHEAD ELECTRICAL PRIMARY FEEDER
TV
UNDERGROUND TELEVISION CABLE
T
UNDERGROUND TELEPHONE CABLE
MOUNTING
WALL MOUNTED
KEY
MOUNTING HEIGHTS
A
90'' TO TOP AND NOT LESS THAN 6'' BELOW
FINISHED CEILING WHERE REQUIRED
80'' TO BOTTOM AND NOT GREATER THAN 96''
TO BOTTOM
F
F
F
B
TV
PNL
CB
S C DS
48''
J
G
F
E
D
H
C
B
T
GENERAL ELECTRICAL NOTES
TV
NOT TO SCALE
NOTES:
1. VERIFY ALL MOUNTING HEIGHTS
WITH ARCHITECT PRIOR TO ROUGH-IN.
2. DIMENSIONS ARE TO TOP OF DEVICE WITH TRIM.
ADJUST BACK BOX LOCATION AS REQUIRED.
C
6'-0''
D
48'' TO TOP AFF
E
20'' TO TOP AFF
F
3''
G
6''AC
H
5'-0'' TO HANDLE
J
6'-6''MAX
3. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST
EDITION OF THE AMERICANS WITH DISABILITIES ACT. (ADA)
AC
AFF
ABOVE COUNTER
ABOVE FINISHED FLOOR
20.
AFG
ARCH
BC
ABOVE FINISHED GRADE
ARCHITECTURAL
BELOW COUNTER
FEEDER RACEWAY: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE & OUTLET BOX BONDING
JUMPERS, A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR. TERMINATE EACH END ON
SUITABLE LUG, BUS, OR BUSHING.
21.
C
CONDUIT
ELECTRONIC/ COMPUTER EQUIPMENT AND SPECIAL EQUIPMENT BRANCH CIRCUITS: IN ADDITION TO RACEWAY
BONDING REQUIRED BY CODE AND OUTLET BOX BONDING JUMPERS, INSTALL A SEPARATE, INSULATED, GREEN
EQUIPMENT GROUND CONDUCTOR WITHIN BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE
LUG, BUS, OR BUSHING.
EC
ELEC
EMT
ELECTRICAL CONTRACTOR
ELECTRICAL
ELECTRICAL METALLIC TUBING
22.
MAINTAIN A MINIMUM OF 24 INCH SEPARATION BETWEEN POWER CONDUITS AND SIGNAL CONDUITS. ROUTE
CONDUITS SO AS NOT CROSS EACH OTHER.
GC
GEC
GRC
GENERAL CONTRACTOR
GROUND ELECTRODE CONDUCTOR
GALVANIZED RIGID CONDUIT
23.
PROVIDE WIRING DEVICES RATED FOR THE GIVEN APPLICATION AS REQUIRED BY CODE.
24.
INSTALL EXTERIOR WIRING IN CONDUIT. UTILIZE WEATHERPROOF FITTINGS AND WEATHERPROOF BOXES/ COVERS.
25.
GRD
GROUND
SIZE ALL BOXES AND ENCLOSURES PER THE NATIONAL ELECTRICAL CODE. WORKING SPACE FOR ELECTRICAL
INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 110.
GFI
GROUND FAULT INTERRUPTER
26.
IG
ISOLATED GROUND
IMC
INTERMEDIATE METALLIC CONDUIT
LA
LIGHTNING ARRESTOR
MC
MECHANICAL CONTRACTOR
PROVIDE A 20 AMP, 120 VOLT, RECEPTACLE OUTLET INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT OF ROOF TOPS, ATTICS, AND
CRAWL SPACES PER NEC 210-63. LOCATE THE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25' OF THE
EQUIPMENT. INSTALL A GFCI RECEPTACLE AT ROOF TOP LOCATIONS WITH CAST BOX, WEATHERPROOF COVER
PLATE, AND MOUNT ONTO A THREADED IMC CONDUIT SECURELY FASTENED IN PLACE IN ACCORDANCE WITH
NEC 314-23.
MECH
MECHANICAL
27.
NIC
NOT IN CONTRACT
INSTALL AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET AT OR NEAR EQUIPMENT REQUIRING
SERVICING SUCH AS HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT IN ATTIC OR UNDERFLOOR
SPACES PER NEC 210-70. LOCATE SWITCH AT POINT OF ENTRY TO THE ATTIC OR UNDERFLOOR SPACE.
NTS
NOT TO SCALE
28.
BRANCH CIRCUITS: UTILIZE #10 AWG CONDUCTORS ON ALL RUNS OVER 100'-0".
OHE
OVERHEAD ELECTRICAL FEEDER
OHP
OVERHEAD PRIMARY FEEDER
29.
PHASE PROTECTION: INSTALL PHASE PROTECTION ON ALL NEW 3 PHASE MOTORS 1HP AND ABOVE AND ALL
3PH AIR HANDLING UNITS. MANUFACTURED BY CUTLER HAMMER D65 OR SQUARE D MPS.
OHS
OVERHEAD SECONDARY FEEDER
30.
PVC
POLYVINYL CHLORIDE
PLMBG
PLUMBING
MULTIPLE PHASE HOME RUNS MAY SHARE A COMMON NEUTRAL EXCEPT WHEN A DIMMER/ DIMMING SYSTEM IS
USED, & WHEN ELECTRONIC/ COMPUTER EQUIPMENT CONNECTIONS ARE REQUIRED. VERIFY W/ ENGINEER
PRIOR TO ROUGH-IN.
PNL
PANEL
31.
PROVIDE ACCESS PANELS WITHIN THE ELECTRICAL BID. TURN OVER TO THE APPROPRIATE TRADE FOR
INSTALLATION. REFER TO ARCHITECTURAL SPECIFICATION SECTIONS.
RTU
ROOFTOP UNIT
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSER
32.
UG
UNDERGROUND
UGE
UNDERGROUND ELECTRICAL FEEDER
UGP
UNDERGROUND PRIMARY FEEDER
COORDINATE SHORT CIRCUIT RATING OF PANELBOARDS AND OVER-CURRENT PROTECTION WITH UPSTREAM
OVER- CURRENT PROTECTION AND AVAILABLE SCA. PROPERLY IDENTIFY ALL PANELBOARDS W/ LAMINATE
LABEL & TYPE ALL PANEL SCHEDULES. INSTALL PANELBOARDS AS INDICATED ON DRAWINGS AND SCHEDULES.
PROVIDE CIRCUIT BREAKERS AS REQUIRED. USE "HACR" BREAKERS FOR HEATING /AIR CONDITIONING LOADS,
PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER BREAKERS AS REQUIRED. PROVIDE A GROUND BAR KIT WITHIN
EACH DISTRIBUTION PANEL, BRANCH CIRCUIT PANEL, AND LOAD CENTER.
UPS
UN INTERRUPT ABLE POWER SUPPLY
33.
WP
WEATHERPROOF
INSTALL METERING AND ELECTRICAL SERVICE ENTRANCE EQUIPMENT IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE AND LOCAL ELECTRIC UTILITY SYSTEM STANDARDS.
XFMR
TRANSFORMER
34.
EXTEND ALL CONDUIT AND CONDUCTORS, INSTALL ELECTRICAL EQUIPMENT AS NECESSARY, AND MAKE ALL
FINAL CONNECTIONS TO MECHANICAL AND OWNER FURNISHED EQUIPMENT. LEAVE ALL EQUIPMENT IN OPERABLE
CONDITION WITH APPROPRIATE OVERLOAD AND SERVICE DISCONNECT PROTECTION AS REQUIRED BY THE
APPLICABLE CODES. FOLLOW MANUFACTURERS INSTALLATION GUIDELINES WHERE APPLICABLE.
35.
COORDINATE WITH THE MECHANICAL /PLUMBING /CONTROLS CONTRACTOR TO INSURE THAT ALL REQUIRED
COMPONENTS OF CONTROL WORK ARE INCLUDED AND FULLY UNDERSTOOD. NO ADDITIONAL COST SHALL
ACCRUE TO THE OWNER AS A RESULT OF LACK OF SUCH COORDINATION. REFER TO THE ELECTRICAL
CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT AND THE MECHANICAL-ELECTRICAL RESPONSIBILITY
TABLE.
36.
CEILING PENETRATIONS IN FIRE RATED CEILINGS SHALL CONFORM TO THE REQUIREMENTS OF IBC SECTION
712. IF AGGREGATE PENETRATION AREA (DETERMINE AGGREGATE AREA FOR ALL DISCIPLINES PENETRATING
CEILING AREA) EXCEEDS AREA ALLOWED, THE ELECTRICAL CONTRACTOR SHALL INCLUDE, AS REQUIRED, A FIRE
RATED ENCLOSURE FOR EACH FIXTURE IN THAT AREA. LIGHTING FIXTURE TYPE MAY REQUIRE ''IC'' RATING.
CONSULT ARCH. FOR DETAILS.
GENERAL NOTES
26.##
KEYED NOTE
M ##
MECHANICAL EQUIPMENT IDENTIFICATION
K#
KITCHEN EQUIPMENT IDENTIFICATION
2016-05-11
NOTE: SOME OF THE SYMBOLS SHOWN MAY NOT APPEAR ON ALL DOCUMENTS OR PLANS.
RODAHL & HUMMELL
ARCHITECTURE, P.C.
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
ELECTRICAL LEGEND
Checked: Date:
Drawn:
NB
AW
2016-05-11 Of:
E001
KEYED NOTES
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
TYPE
B1
CO
CU1
CU2
CX1
CX2
CX3
CX4
CX5
F1
F2
GD
MD
DESCRIPTION
BOILER, PROPANE
CO2/NO2 DETECTORS CONTROLLER
CONDENSING UNIT
CONDENSING UNIT
CEILING EXHAUSTER
CEILING EXHAUSTER
CEILING EXHAUSTER
CEILING EXHAUSTER
CEILING EXHAUSTER
FURNACE, PROPANE
FURNACE, PROPANE
GARBAGE DISPOSAL, 3/4 HP
MOTORIZED DAMPER
ELECTRICAL
120 V/1-60 VA
120 V/1-120 VA
240 V/2-4320 VA
240 V/2-8400 VA
120 V/1-50 VA
120 V/1-109 VA
120 V/1-109 VA
120 V/1-50 VA
120 V/1-50 VA
120 V/1-1164 VA
120 V/1-1164 VA
120 V/1-1656 VA
120 V/1-50 VA
P1
RH
SD
WH1
WH2
WX
INLINE BOILER INJECTION PUMP
RADIANT HEATER
MOTORIZED DAMPER
TANKLESS WATER HEATER, GAS
TANKLESS WATER HEATER, GAS
GARAGE EXHAUSTER
120 V/1-330 VA
120 V/1-600 VA
120 V/1-10 VA
120 V/1-100 VA
120 V/1-100 VA
120 V/1-1175 VA
CB AT PANEL
20 A
20 A
30 A
60 A
15 A
15 A
15 A
15 A
15 A
15 A
15 A
20 A
15 A
DISC. AT UNIT
PROVIDE SWITCH
CORD/PLUG
PROVIDE 30A 3R
PROVIDE 60A 3R
SWITCH ON O.S.
SWITCH ON O.S.
SWITCH ON O.S.
SWITCH ON O.S.
PROVIDE SWITCH
PROVIDE SWITCH
PROVIDE SWITCH
PROVIDE SWITCH
PROVIDE SWITCH
CONDUCTORS
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#10 CU + #10 CU GROUND
#6 CU + #10 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12CU + #12CU GROUND
#12 CU + #12 CU GROUND
15 A
15 A
15 A
15 A
15 A
15 A
CORD/PLUG
PROVIDE SWITCH
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
PROVIDE SWITCH
PROVIDE SWITCH
PROVIDE SWITCH
#12CU + #12CU GROUND
#12CU + #12CU GROUND
#12 CU + #12 CU GROUND
26.01
NOTES
26.02
ALTERNATE BID #1
26.03
CONTROL BY SECOND RELAY ON OCC SENSOR
CONTROL BY SECOND RELAY ON OCC SENSOR
CONTROL BY SECOND RELAY ON OCC SENSOR
CONTROL BY SECOND RELAY ON OCC SENSOR
CONTROL BY THERMOSTAT
PROVIDE RECEPTACLE FOR CONDENSATE PUMP ON SAME CKT
PROVIDE RECEPTACLE FOR CONDENSATE PUMP ON SAME CKT
26.04
26.08
26.09
INTERCONNECT APP. BAY MD WITH WX FOR SIMULTANIOUS
OPERATION
ALTERNATE BID #1
DELETE IF ALTERNATE BID #1 IS ACCEPTED
26.11
26.12
26.13
PROVIDE PHONE LINE AND BELL ON BAY CEILING TO NOTIFY OCCUPANTS WHEN PHONE IS
RINGING.
PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS
FULLY OPEN. CONNECT TO RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR (SEE LIGHTING
PLAN). INDICATOR LIGHT TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY OPEN, AND
REMAIN RED OTHERWISE.
PROVIDE CEILING MOUNTED CORD REEL ON DRIVER'S SIDE OF BAY. COORDINATE REEL
MODEL AND EXACT LOCATION WITH OWNER.
PROVIDE ONE RECEPTACLE AT 24" AFF FOR GAS RANGE, ONE RECEPTACLE IN CABINET
ABOVE FOR BROAN F403004 HOOD, AND ONE RECEPTACLE IN CABINET ABOVE FOR
MICROWAVE. FOR RECEPTACLES MARKED AS GFCI BUT NOT IN READILY ACCESSIBLE
LOCATION, PROVIDE GFCI BREAKER AT PANEL.
PROVIDE EMPTY 1" CONDUIT FROM CO (CO2 SENSOR CONTROLLER) TO CO2 SENSORS,
MOTORIZED DAMPERS (M/D), AND WALL EXHAUSTER (WX), FOR CONTROLS CABLE BY
OTHERS.
CIRCUIT CEILING EXHAUSTER WITH ROOM LIGHTS, AND CONTROL VIA SECOND RELAY IN
OCCUPANCY SENSOR.
DATA AND RECEPTACLE AT 12'-0" AFF FOR FUTURE WAP.
J-BOX WITH PULL WIRE AND 1/2" CONDUIT ABOVE DOOR ON INSIDE FOR FUTURE DOOR
CONTROLLER BY OTHERS.
COMBINATION SMOKE/CARBON MONOXIDE DETECTOR. HARD WIRED WITH BATTERY BACKUP.
KIDDE KN-COSM-IBA. 120V.
OWNER EQUIPMENT CONNECTION SCHEDULE
TYPE
CP
DR
GDO
GDR
GWS
HOTSY
ICE
SCBA
WS
DESCRIPTION
ELECTRICAL
240 V/2-5280 VA
120 V/1-864 VA
120 V/1-864 VA
240 V/2-14640 VA
240 V/2-1920 VA
240 V/2-8160 VA
120 V/1-1272 VA
240 V/2-11040 VA
120 V/1-1176 VA
AIR COMPRESSOR
SMALL DRYER
GARAGE DOOR OPENER, 1/3 HP
GEAR DRYER
GEAR WASHER
PRESSURE WASHER, GAS
ICE MACHINE
SCUBA (AIR COMPRESSOR), 10 HP
SMALL WASHER
CB AT PANEL
40 A
20 A
20 A
80 A
20 A
40 A
15 A
50 A
20 A
DISC. AT UNIT
PROVIDE 60A
CORD/PLUG
CORD/PLUG
PROVIDE 80A
PROVIDE 30A
PROVIDE 60A
PROVIDE SWITCH
PROVIDE 60A
CORD/PLUG
CONDUCTORS
#8 CU + #10 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#4 CU + #8 CU GROUND
#12 CU + #12 CU GROUND
#8 CU + #10 CU GROUND
#12 CU + #12 CU GROUND
#6 CU + #6 CU GROUND
#12CU + #12CU GROUND
CU1
NOTES
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
ASSUMED IDENTICAL TO VALLEY #1 EQUIPMENT
CU2
SERVICE
DISCONNECT
MD
A - 21,23
MD
A - 20,22
WP
2
2
2
2
B - 18
B - 16
SLEEPING
109
SD
SLEEPING
107
A - 24
SLEEPING
108
B - 17
LAUNDRY
106
A - 34 A - 30
A - 9,11
A - 12,14
MD
A - 36
WP
R.R.
111
R.R.
113
PANEL B
B - 14
CX1
26.12
CX2
26.09
J
26.09
26.08
PANEL A
B - 27
R.R.
114
CO
WH1
G
CX4
26.02
G
DAY ROOM
101
B - 30
GDO
26.03
26.03
A - 16
A - 18
B - 12
B - 26
J
26.08
CO
J
B-4
GDO
A-7
B - 23
G
A-5
GDO
26.02
B - 11
OFFICE
102
B - 28
26.12
26.12
2016-05-11
A - 26
G
B-7
G
G
J
RODAHL & HUMMELL
ARCHITECTURE, P.C.
WP
DISHWASHER
26.02
26.03
B - 24
B - 10
B-2
GD
A - 27
J
G
B-1
84" AFF
G
G
G
G
26.04
RH
26.09
G
84" AFF
KITCHEN
100
CO
26.11
B-8
B-6
B-9
B-5
B-3
CO
A - 15
STOR.
115
26.08
APPARATUS BAY
103
26.09
G
96" AFF
26.08
J
REFRIGERATOR
A - 17
26.01
A-6
FREEZER
A - 8,10
WX
A - 29
A - 25
F2
CX3
J
SCBA
A - 2,4
WP
CX5
SD
VEST
105
HALL
112
A - 1,3
26.08
A - 19
G
B - 25
SD
A - 28
CP
HOTSY
G
IT
112A
A - 13
CO
GWS
B - 13
B - 15
MICROWAVE
RANGE
SD
G
SLEEPING
110
SD
BUNKER
104
G
SD
WS
P1
ICE
WH2
MD
B - 19
F1
SD
GDR
WP
2
B - 20
26.13
DR
B1
WP
B - 22
2
2
2
B - 21
G
MD
J
26.12
ARCHITECTURE
N
1
ELECTRICAL POWER FLOOR PLAN
1/8" = 1'-0"
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
ELECTRICAL PLAN
Checked: Date:
Drawn:
NB
AW
2016-05-11 Of:
E101
KEYED NOTES
LIGHTING FIXTURE SCHEDULE
TYPE
A
D
DESCRIPTION
MOUNTING
ASSYMETRIC UP/DOWN WALL FIXTURE, DIMMABLE WALL
DOOR EXIT SIGNAL LIGHT
WALL
EX
EXL
H
EXIT SIGN, RED ON WHITE
EXIT SIGN WITH EMERGENCY LIGHTS
HIGH BAY, WIDE DISTRIBUTION, WITH INTEGRAL
OCCUPANCY SENSOR
HIGH BAY, WIDE DISTRIBUTION, WITH INTEGRAL
OCCUPANCY SENSOR AND EM BATTERY
4' LINEAR LENSED
DECORATIVE PENDANT AT BAR
SQUARE LIGHT, OUTDOOR, WITH PHOTOCELL
SQUARE LIGHT, WET LOCATION, WITH EM
BATTERY PACK
SQUARE LIGHT, INDOOR WET LOCATION, NO
PHOTOCELL
TROFFER, 2'X2'
TROFFER, 2'X4'
TROFFER, 2'X4', WITH EM BATTERY PACK
WALLPACK WITH PHOTOCELL AND COLD
WEATHER EM BATTERY
HE
L
P
S
SE
SI
T2
T4
T4E
W4
HEIGHT
8' AFF
6' AFF
LAMP
LED
LED
ELECTRICAL
120 V/1-37 VA
120 V/1-10 VA
UNIVERSAL
UNIVERSAL
SUSPENDED
ABOVE DOOR
17' AFF
LED
LED
LED
120 V/1-5 VA
120 V/1-5 VA
120 V/1-155 VA
MAKE
FINELITE
LIGHTING
SPECIALTIES
COMPASS
COMPASS
COLUMBIA
SUSPENDED
17' AFF
LED
120 V/1-155 VA
SURFACE
SUSPENDED
SURFACE
SURFACE
CEILING
7' AFF
CEILING
CEILING
LED
LED
LED
LED
SURFACE
CEILING
CEILING
CEILING
CEILING
ABOVE DOOR
RECESSED-GRID
RECESSED-GRID
RECESSED-GRID
WALL
26.02
MODEL
S17-LED-VCF-PF-2-SO-40K-SC-120
SG20-12RG-LED
CCT
40K
N/A
CRI
MIN 80
N/A
LUMENS
2,500
N/A
OPTIC
ASSYMETRIC
N/A
40K
40K
40K
MIN 80
MIN 80
MIN 80
N/A
N/A
16,000
N/A
N/A
WIDE
COLUMBIA
CER
CCR
LLHV4-40M-WST-EU-SFA-WG-OS1360 +LHVQM5
LHVQM5
LLHV4-40M-WST-EU-SFA-WG-ELL14 + LHVQM5
40K
MIN 80
16,000
WIDE
120 V/1-25 VA
120 V/1-14 VA
120 V/1-20 VA
120 V/1-20 VA
COLUMBIA
SPECTRUM
KENALL
KENALL
LCL4-40LW-EU
PF0614-LEDGV14W-40K-DS101-CP13-CD-FINISH
MS11FL-PP-DB-20L50K-SCC-120-BPC
MS11FL-PP-DB-20L40K-SCC-120-BPC-LEL
40K
40K
50K
40K
MIN 80
MIN 80
MIN 80
MIN 80
2,500
1,000
1,350
1,350
DIFFUSE
N/A
DIFFUSE
DIFFUSE
LED
120 V/1-20 VA
KENALL
MS11FL-PP-MW-20L40K-SCC-120-BPC
40K
MIN 80
1,350
DIFFUSE
LED
LED
LED
LED
120 V/1-22 VA
120 V/1-40 VA
120 V/1-40 VA
120 V/1-45 VA
COLUMBIA
COLUMBIA
COLUMBIA
LITHONIA
LCAT22-40MWG-EU
LCAT24-40MLG-EDU
LCAT24-40MLG-EDU-ELL14
OLW-31
40K
40K
40K
50K
MIN 80
MIN 80
MIN 80
N/A
22,000
5,000
5,000
3970
WIDE
WIDE
WIDE
-
NOTES
SEE PLAN KEYNOTES FOR
CONTROL
26.07
26.10
PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS
FULLY OPEN. CONNECT TO RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR (SEE LIGHTING
PLAN). INDICATOR LIGHT TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY OPEN, AND
REMAIN RED OTHERWISE.
TYPE H FIXTURES INCLUDE AN INTEGRAL OCCUPANCY/DAYLIGHT SENSOR, AND WALL
SWITCHES FUNCTION AS A MANUAL OVERRIDE TO OFF. TYPE HE FIXTURES ARE UNSWITCHED,
AND HAVE NO SENSOR.
PROVIDE AND LOCATE OCCUPANCY SENSORS REQUIRED FOR FULL COVERAGE OF ROOM PER
MANUFACTURER'S INSTRUCTIONS. TEST AND ADJUST SENSORS AS NEEDED TO ENSURE
PROPER FUNCTION. TYPICAL ALL OCCUPANCY SENSORS.
UNSWITCHED
OWNER STANDARD FIXTURE,
NO SUBSTITUTIONS
CONTROL DEVICE SCHEDULE
TYPE
Dimmer
O-C
O-C2
O-W1
O-W2
RC
DESCRIPTION
LOW VOLTAGE DIMMER WITH ON/OFF TOGGLE
CEILING OCCUPANCY SENSOR
CEILING OCCUPANCY SENSOR, 2 RELAY
WALL OCCUPANCY SENSOR
WALL OCCUPANCY SENSOR, 2 RELAY
LOCAL ROOM CONTROLLER FOR
COORDINATION OF MULTIPLE INPUT DEVICES
MOUNTING
WALL
CEILING
CEILING
WALL
WALL
ABOVE CEILING
HEIGHT
SWITCH HEIGHT
N/A
N/A
SWITCH HEIGHT
SWITCH HEIGHT
N/A
SENSING TECH
N/A
DUAL
DUAL
DUAL
DUAL
N/A
RELAYS
PER PLAN
1
2
1
2
PER PLAN
SWITCH(ES)
INTEGRAL
PROVIDE REMOTE PER PLAN
PROVIDE REMOTE PER PLAN
1 - INTEGRAL
2 - INTEGRAL
PER PLAN
NOTES
MUST BE COMPATIBLE WITH RC
LOCATE ABOVE ACCESSIBLE CEILING
PANEL SERV.
DISC.
D
D
D
SLEEPING
110
T4
A
SLEEPING
109
T4
D
A
A
A
SLEEPING
108
T4
SLEEPING
107
T4
LAUNDRY
106
L
H, a
BUNKER
104
L
S
3
HALL
112
O-C
T4
O-W1
3
R.R.
111 T2
SE
S
T2 R.R.
113
T4E, c
A
B - 34
g
O-W2
EX
SI
c d f g
T4, c
R.R.
114
T2
A
PANEL B
T4, g
HE
STOR.
115
A
O-C2
B - 29
T4, c
T4, c
T4, c
T4E, g
P, f
T4, d
26.10
T4, d
T4E, d
26.10
EX
T4, d
OFFICE
102
T4, d
T4, d
O-W1
T4, d
T4
33
KITCHEN
100
T4, g
H, b
H, b
O-C
DAY ROOM
101
RC
H, a
33
O-C
H, b
26.07
TYP.
H, a
P, f
HE
APPARATUS BAY
103
TYP.
L
P, f
S
H, a
26.07
O-W2
D D D D
SE
EX
VEST
105
T4E
SI
O-C2
A - 33
PANEL A
B - 32
EX
H, b
O-W1
EX
T4E
H, b
A - 32
O-W1
IT
112A T2
H, a
L
EXL
W4
26.02
26.02
D
D
D
2016-05-11
T4
W4
SE
d
b EXL
a
CIRCUIT WITH
DOOR OPENERS
26.02
b
a
W4
W4
A - 31
RODAHL & HUMMELL
ARCHITECTURE, P.C.
EX
S
SE
S
ARCHITECTURE
N
1
ELECTRICAL LIGHTING FLOOR PLAN
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
CENTERPOINT 2
FIRE STATION
SAN JUAN COUNTY
1/8" = 1'-0"
Drawn:
NB
Filename:
0725_FLOOR
Project:
1527
Sheet:
LIGHTING PLAN
Checked: Date:
AW
2016-05-11 Of:
E102
PANEL B
2 SERVICE DISC
1
1
25000
NM
3 PANEL A
1
2
20513
M
4 PANEL B
1
3
12031
M
Set(s)
250 AL 12862 240 30
2
of
0.00009
0.000041
0.243 0.805
2
Set(s)
250 AL 12122 240 100 0.00009
of
0.000052
1
Set(s)
250 AL 12122 240 50
of
0.000052
0.00009
NOTES TO THE CONTRACTOR:
100
Segment
Voltage Drop
CUMULATIVE
VOLTAGE DROP
at the secondary of the utility transformer
FAULT
CURRENT
Motor
Contribution
M
f
Conductor
Reactance
(X)
Conductor
Resistance
(R)
Length (L)
L-L Volts (E)
'C' value
Wire/Bus
0
Conduit Type
Source (Point)
1
Source Isc
Phase
1 SERVICE
Point
Description
SHORT CIRCUIT & VOLTAGE DROP CALCULATIONS
25000
-
-
20513
0.5%
0.5%
0.705 0.586
12031
1.7%
2.1%
0.414 0.707
8511
0.4%
2.5%
LEGEND:
1. THE DISTANCES SHOWN ARE FOR CALCULATION PURPOSES ONLY. THEY
SHALL NOT BE USED FOR CONTRACTOR TAKEOFFS, NOR FOR BIDDING.
2. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY FIELD CONDITION THAT
RESULTS IN A CHANGE OF 10% OR GREATER CIRCUIT DISTANCE
NM = NON-MAGNETIC CONDUIT
M = MAGNETIC CONDUIT
FB = FEEDER BUSWAY
PB = PLUG-IN BUSWAY
XFMR = TRANSFORMER
CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD:
L=
I=
LENGTH OF CIRCUIT TO THE FAULT IN FT (1 WAY).
AVAILABLE SHORT-CIRCUIT CURRENT IN AMPS AT
THE BEGINNING OF THE CIRCUIT.
C = 'C' FACTOR CONSTANT FROM THE TABLE OF 'C'
VALUES FOR THE CONDUCTORS.
E = LINE-TO-LINE OR LINE-TO NEUTRAL VOLTAGE.
IP = PRIMARY SHORT CIRCUIT CURRENT IS =
IS = SECONDARY SHORT CIRCUIT CURRENT
Vs = SECONDARY VOLTAGE
Vp = PRIMARY VOLTAGE
Isca (1) = SHORT CIRCUIT CURRENT AT FAULT POINT #1
Isca (2) = SHORT CIRCUIT CURRENT AT FAULT POINT #2
Isca (2) = Isca (1) x M(1) M = 1/(1+f)
FEEDER: 'f (3Ø) = 1.732 x L x Isca
CxE
XFMR: 'f (3Ø) = IP(sca)x Vp x 1.73 x %Z
100,000 x kVA
FEEDER: 'f (1Ø) = 2 x L x Isca
CxE
XFMR: 'f (1Ø) = IP(sca)x Vp x %Z
100,000 x kVA
ISsca = Vp x M x IP(sca)
Vs
Location:
Supply From:
Mounting:
Enclosure:
DAYROOM 101
A
RECESSED
NEMA 1
PANEL A
Volts: 120/240 Single
Phases: 1
Wires: 3
A.I.C. Rating: 22,000
Mains Type: MLO
Mains Rating: 200 A
Location:
Supply From:
Mounting:
Enclosure:
Notes:
Volts: 120/240 Single
Phases: 1
Wires: 3
A.I.C. Rating: 22,000
Mains Type: MLO
Mains Rating: 400 A
Notes:
A
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
VESTIBULE 106
SERV. DISC.
RECESSED
NEMA 1
Circuit Description
KITCHEN HOOD
MICROWAVE
GAS RANGE
REC - NW Cntr
REC - 100 NE Cntr
REC - 100 W Cntr
REC - 104, 105, 106
REC- IT 112A
REC- IT 112A
WASHING MACHINE
DRYER
REC - Dayroom TVs
SMOKE/CO2 DETECTORS
WH1
LGT- DAYROOM
Spare
Spare
Spare
Spare
Spare
Spare
Load Classification
HVAC
Lighting
Motor
Other
Receptacle
B
Trip
Poles
Poles
300
1656
20
1
1
1600
1200
20
1
1
50
600
20
1
1
1600
600
20
1
1
1600
1600
20
1
1
1600
900
20
1
1
540
1080
20
1
1
900
720
20
1
1
900
720
20
1
1
1176
720
20
1
1
864
720
20
1
1
360
900
20
1
1
70
630
20
1
1
100
540
15
1
1
728
900
20
1
1
0
1077
20
1
1
0
180
20
1
1
0
20
1
0
20
1
0
20
1
0
20
1
Total Load:
13138 VA
13993 VA
Total Amps:
109 A
117 A
Connected Load Demand Factor
Demand
100 VA
100.00%
100 VA
1694 VA
125.00%
2118 VA
1974 VA
100.00%
1974 VA
4860 VA
100.00%
4860 VA
18530 VA
76.98%
14265 VA
A
Trip
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
15
20
Circuit Description
GARBAGE DISPOSER
DISHWASHER
REFRIGERATOR
FREEZER
REC - 100 Island
REC - 102
REC - EXT, RRs, STOR,...
REC - 107
REC - 108
REC - 109
REC - 110
REC - Dayroom 101
REC - Dayroom 101
REC - Dayroom 101
REC - Dayroom 101
LGT- SMALL ROOMS
LGT- EXT CANOPIES
Panel Totals
Total Conn. Load: 27158 VA
Total Est. Demand: 23317 VA
Total Conn.: 113 A
Total Est. Demand: 97 A
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
Circuit Description
HOTSY
-GDO - Mid and South
Cord Reels
GDR
-ICE
RH
WX
REC. - BAY E WALL
CU1
-F2
REC. - BAY S WALL
REC - BAY NE GFCI
LGT- EXT BAY DOORS
LGT- BAY SOUTH
Spare
Spare
Spare
Spare
Spare
Spare
Spare
TVSS
PANEL B
--
Load Classification
HVAC
Lighting
Motor
Motor - Largest
Other
Receptacle
B
Trip
Poles
Poles
4080
5520
40
2
2
4080
5520
---1728
864
20
1
1
1080
2640
20
1
2
7320
2640
80
2
-7320
960
--2
1272
960
15
1
-600
120
15
1
1
1175
720
15
1
1
720
4200
20
1
2
2160
4200
30
2
-2160
1164
--1
1164
540
15
1
1
540
390
20
1
1
540
100
20
1
1
180
930
20
1
1
930
250
20
1
1
0
50
20
1
1
0
20
1
0
20
1
0
20
1
0
20
1
0
20
1
0
20
1
0
30
1
12930
200
2
13873
--Total Load:
50036 VA
45584 VA
Total Amps:
417 A
380 A
Connected Load Demand Factor
Demand
16358 VA
100.00%
16358 VA
3734 VA
125.00%
4668 VA
11321 VA
100.00%
11321 VA
11040 VA
125.00%
13800 VA
30852 VA
100.00%
30852 VA
22670 VA
72.06%
16335 VA
Trip
50
-20
40
-20
-20
20
60
-15
20
15
15
20
20
20
Circuit Description
SCBA
-GDO - North
CP
-GWS
-CO/NO2 Detector
REC. - W Garage
CU2
-F1
REC - EXT BAY DOORS
B1, P1
WH2
LGT- BAY NORTH
MDs
CX5
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
Panel Totals
Total Conn. Load: 95975 VA
Total Est. Demand: 93334 VA
Total Conn.: 400 A
Total Est. Demand: 389 A
EXTERIOR
RISER GENERAL NOTES
INTERIOR
NEW
UTILITY
TRANS.
240V
1 PH
1.
ALL UNDERGROUND CONDUIT TO BE SCHEDULE 80 PVC.
2.
ALL EXPOSED EXTERIOR CONDUIT TO BE RIGID STEEL.
3.
THIS DIAGRAM IS SCHEMATIC, AND NOT INTENDED TO SPECIFY CONDUIT
ROUTING OR FEED SIDE OF PANELS.
4.
WHERE ALUMINUM FEEDERS ARE SPECIFIED, VERIFY THAT ASSOCIATED
PANELS ARE RATED FOR ALUMINUM CONDUCTORS.
5.
TERMINAL SCREWS ON ALL ALUMINUM FEEDERS SHALL BE TORQUED TO
CONDUCTOR MANUFACTURER'S SPECIFICATIONS AT CONSTRUCTION, AND
RE-TORQUED 90 DAYS AFTER COMMISSIONING.
2
PANEL B
MLO - 240V / 1PH
1
400A
OCP
# 1/0 AL
UTILITY METER
# 1/0 AL
CT
CABINET
NTR
BUS
GRD
BUS
MLO - 240V / 1PH
PANEL A
3
#
RISER KEYED NOTES
1.
NEW 240V SINGLE PHASE SERVICE, ASSUMED TO BE WITHIN 30 FT OF THE
SERVICE DISCONNECT. COORDINATE WITH FEUS.
2.
EXTERIOR SERVICE DISCONNECT WITH OCP (FUSE OR BREAKER
ACCEPTABLE). MINIMUM INTERRUPT RATING 22,000A.
3.
2 SETS OF (3) 250 MCM AL + # 1 AL GROUND IN 2.5" CONDUIT.
4.
1 SET OF (3) 250 MCM AL + # 1 AL GROUND IN 2.5" CONDUIT.
4
2016-05-11
#4 CU
#4 CU
3
TO STRUCTURAL STEEL
#2 CU
20' LOOP 30" BELOW GRADE
20'-0"
20
'-0
"
1
RODAHL & HUMMELL
ARCHITECTURE, P.C.
TO UFER GROUND
"
'-0
20
(3) 3/4" X 10' COPPER CLAD
STEEL GROUND RODS
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
ELECTRICAL RISER DIAGRAM
CENTERPOINT 2
FIRE STATION
1/8" = 1'-0"
SAN JUAN COUNTY
Filename:
0725_FLOOR
Project:
1527
Sheet:
ELECTRICAL RISER AND PANELS
Checked: Date:
Drawn:
AW
JL
2016-05-11 Of:
E501