SpectrAlert More Choices More Features More Flexibility Less Power

advertisement
SpectrAlert
More Choices
More Features
More Flexibility
Less Power
wall
Wall-mount SpectrAlert ™ Product installation is
An innovative and ef fi-
simple because the
cient circuit design
back box is left open
allowed System Sensor
for wiring. A universal
to revolutionize notifi-
mounting plate comes
cation devices with
its line of SpectrAler t
with each unit and
™
offers one-screw mount-
wall-mount strobes,
ing, fur ther reducing
horn/strobes, and
install time.
horns. This new design
results in dramatically
reduced current draw
and a lower overall installed cost.
ceiling
Ceiling-mount SpectrAlert™
series draw up to 40%
SpectrAler t’s newest
less current than compet-
strobes, horn/strobes,
itive designs.
and speaker/strobes are
designed specifically for
A unique, circular design
the ceiling. Based on the
blends with other ceiling-
same principles as the
mount devices such
popular wall-mount mod-
as smoke detectors, for
els, the ceiling-mount
an unobtrusive installation. And this aesthetic is
common throughout the
ceiling product line,
for a consistent appearance. Installer-friendly
features such as captured
mounting screws and dip
switch horn tone selections simplify installation.
SpectrAlert™ Speakers
To reduce installation
SpectrAler t™ speakers
costs, they can be
and speaker/strobes
mounted to a 4 in. x
give you the fidelity
4 in. x 2-1/8 in. back
sound quality essential
box, without an exten-
to voice evacuation.
sion ring.
These products provide
a broad frequency range
and low harmonic distor tion for cr ystal clear
sound per formance,
making them ideal for
hotel, hospital, and
voice
commercial applications.
sync
Synchronization is Easy
may be interconnected
The SpectrAler t
with other Sync •Circuit ™
Sync•Circuit ™ Module
modules for multi-zone
is designed to make
synchronization. It is
installations that
compatible with wall
require signal synchro-
or ceiling-mount strobes,
nization easy. This
horn/strobes, speaker/
patented product syn-
strobes, and wall-
chronizes SpectrAler t™
mount horns.
strobes to flash at 1Hz
and SpectrAler t™ horns
to sound at temporal 3
over one pair of wires.
This technology can
also silence horns, and
SpectrAlert Specifications
ULC Canadian Models are available.
SpectrAlert Wall Mount Horn/Strobes
Red Model
White Model
Voltage
Candela
Avg. mA* @Nom. VDC
P1215
P1215W
12
15
124
Avg. mA* @Nom.FWR**
167
P121575
P121575W
12
15/75
152
181
P2415
P2415W
24
15
68
78
P241575
P241575W
24
15/75
74
82
P2430
P2430W
24
30
92
100
P2475
P2475W
24
75
148
167
P24110
P24110W
24
110
165
209
Avg. mA @Nom.FWR**
SpectrAlert Wall Mount Strobes
Red Model
White Model
Voltage
Candela
Avg. mA @Nom. VDC
S1215
S1215W
12
15
114
157
S121575
S121575W
12
15/75
142
171
S2415
S2415W
24
15
43
60
S241575
S241575W
24
15/75
49
64
S2430
S2430W
24
30
67
82
S2475
S2475W
24
75
123
159
S24110
S24110W
24
110
140
191
SpectrAlert Wall Mount Horns
Red Model
White Model
Voltage
Candela
Avg. mA* @Nom. VDC
Avg. mA* @Nom.FWR**
H12/24
H12/24W
12/24
NA
10/25
10/18
SpectrAlert Wall Mount Weatherproof
Red Model
Description
Voltage
Candela
Avg. mA* @Nom. VDC
Avg. mA* @Nom.FWR**
P121575K
Horn/Strobe
12
15/75
124
167
P241575K
Horn/Strobe
24
15/75
74
82
P2475K
Horn/Strobe
24
75
148
167
P24110K
Horn/Strobe
24
110
165
209
S121575K
Strobe
12
15/75
142
171
S241575K
Strobe
24
15/75
49
64
S2475K
Strobe
24
75
123
159
S24110K
Strobe
24
110
140
191
H12/24K
Horn
12/24
NA
10/25
10/18
SpectrAlert Wall Mount AGENT, EVAC, FUEGO Models
Red Model
Description
Voltage
Candela
Avg. mA* @Nom. VDC
Avg. mA* @Nom.FWR**
P241575AG
AGENT Horn/Strobe
24
15/75
74
82
P241575EV
EVAC Horn/Strobe
24
15/75
74
82
P241575F
FUEGO Horn/Strobe
24
15/75
74
82
S241575AG
AGENT Strobe
24
15/75
49
64
S241575EV
EVAC Strobe
24
15/75
49
64
S241575F
FUEGO Strobe
24
15/75
49
64
*Horn and Horn/strobe current draws assume horn is set at temporal 3, electromechanical tone, and high audibility.
** FWR = Full Wave Rectified
SpectrAlert Ceiling Mount Horns/Strobes
Red Model
White Model
Voltage
Candela
Avg. mA* @Nom. VDC
PC2415
PC2415W
24
15
71
Avg. mA* @Nom.FWR**
89
PC241575
PC241575W
24
15/75
79
96
PC2430
PC2430W
24
30
91
113
PC2475
PC2475W
24
75
150
174
PC2495
PC2495W
24
95
176
207
PC24115
PC24115W
24
115
214
264
PC24177
PC24177W
24
177
314
334
Avg. mA @Nom.FWR**
SpectrAlert Ceiling Mount Strobes
Red Model
White Model
Voltage
Candela
Avg. mA @Nom. VDC
SC2415
SC2415W
24
15
48
55
SC241575
SC241575W
24
15/75
56
62
SC2430
SC2430W
24
30
68
79
SC2475
SC2475W
24
75
127
140
SC2495
SC2495W
24
95
153
173
SC24115
SC24115W
24
115
191
230
SC24177
SC24177W
24
177
291
300
Avg. mA @Nom.FWR**
SpectrAlert Ceiling Mount Speaker/Strobes
White Model
Voltage
Candela
Avg. mA @Nom. VDC
SP2C2415
24
15
48
55
SP2C241575
24
15/75
56
62
SP2C2430
24
30
68
79
SP2C2475
24
75
127
140
SP2C2495
24
95
153
173
SP2C24115
24
115
191
230
SP2C24177
24
177
291
300
SpectrAlert Dual Voltage Evacuation Speakers
Red Model
White Model
Description
Speaker Voltage
–
SP200W
Round 73⁄8” grille, 1⁄4 -2 watt power tap
25.0/70.7 Vrms
SP201R
SP201W
Square, 5” grille, 1⁄4 -2 watt power tap
25.0/70.7 Vrms
SpectrAlert Wall Mount Speaker/Strobes
Red Model
White Model
Voltage
Candela
Avg. mA @Nom. VDC
SP2R2415
SP2W2415
24
15
43
Avg. mA @Nom.FWR**
60
SP2R241575
SP2W241575
24
15/75
49
64
SP2R2430
SP2W2430
24
30
67
82
SP2R2475
SP2W2475
24
75
123
159
SP2R24110
SP2W24110
24
110
140
191
SpectrAlert Sync•Circuit Module
Red Model
White Model
Voltage
Candela
Avg. mA* @Nom. VDC
Avg. mA* @Nom.FWR**
MDL
MDLW
12/24
NA
16
24
SpectrAlert Accessory Mounting Plates
Red Model
White Model
Description
S-MP
S-MPW
Small footprint mounting plate for single gang only
BBS
BBSW
Sur face-mount back box skir t
D-MP
D-MPW
Universal mounting plate (replacement)
WBB
—
Weatherproof back box
BBSC
BBSCW
Sur face-mount back box skir t for ceiling mount products
BBS-SP2R
BBS-SP2W
Sur face-mount back box skir t for wall mount speaker/strobe
*Horn and Horn/strobe current draws assume horn is set at temporal 3, electromechanical tone, and high audibility.
** FWR = Full Wave Rectified
SpectrAlert is the full line of
notification devices that
saves you time and money while
giving you flexibility and
end-user appeal. The savings
you realize are tangible — less
power consumption means
more devices per circuit and
fewer power supplies. Less
time to install means more time
to focus on other business.
™
System Sensor
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800.SENSOR2
Fx: 630.377.6495
www.SystemSensor.com
Fx Documents:
800-736-7672 ext. 3
© 2000 System Sensor
The company reser ves
the right to change
specifications at any time.
A05–1026–01
Download