23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0950 STABILIZATION OF HARMONIC INSTABILITY IN AC DISTRIBUTION POWER SYSTEM WITH ACTIVE DAMPING Changwoo YOON cyo@et.aau.dk Xiongfei WANG Claus Leth BAK Aalborg University – Denmark xwa@et.aau.dk clb@et.aau.dk ABSTRACT This paper deals stabilizing method of the interaction problems among the interconnected power electronics based power devices in a power distribution system. Even if each of the inverters in the network is stable individually, the combined network stability cannot be assured unless holistic stability assessment is performed. The impedance based stability criterion is used to study the effect of the active damping on the system stability. A benchmark of a Cigré power distribution network is modeled under the impedance based stability criterion and validated using the PSCAD/EMTDC simulation. The result shows that not all inverters need to have active damping for stabilizing the network but some of inverters can effectively change the impedance of the network, thus overall network becomes stable. INTRODUCTION Today, distributed generation based on renewable energy, characterized by a large number of inverters, is increasing rapidly [1]. As a result of this trend, unexpected problems such as the harmonic interactions among the interconnected inverters in the power system are increasing [2], [3]. In the inverter, DC electric energies from the renewable resources is converted to sinusoidal voltages or currents through the Voltage Source Inverters (VSI) with Pulse Width Modulation (PWM) techniques. During the process of converting, power filters are necessary to remove harmonic voltages or current in the output. These days, Inductor-Capacitor-Inductor (LCL) filter is a widespread solution for its high attenuation capability at high frequencies and with its small filter value [4]. However, its high order filter structure, which fivess the sufficient attenuation, has a side effect that it is a destabilizing factor of the VSI and might resonate above the control bandwidth. In order to deal with this problem, the resonance peak of the inverter should be lowered in order not to be affected by the phase drop at the filter resonance frequency. There are mainly two types of damping approaches, one is the passive damping method which inserts real resistors into the filter topology to dissipate excessive energy from the resonance [5], [6], and the other one is the active damping, which emulates the behavior of the passive damping by adding additional control loops and/or feedback signals [4], [7], [8]. The passive damping can be implemented simple and inexpensive ways, but it reduces the overall system efficiency, so in applications putting emphasis on their CIRED 2015 Frede BLAABJERG fbl@et.aau.dk efficiency like PV systems are not appropriate. Instead of dissipating it, the energy can be collected by the work of additional control efforts. However, it requires additional sensors for feedback signal or state estimators, which complicates their control loops and sometimes they are also sensitive to the filter parameter variation. Recently, research clearly stating the stability of an inverter by the relation between LCL filter resonance frequency and the unavoidable time delay from its digital implementation has been published [9]. This exactly defined the boundary of the stable region of LCL-filtered inverter without any damping method; it means the inverter can be stable with its high resonance peak. However, it is valid only for single inverter case and if the inverter is somewhere on the distribution network and connected together with other devices, this cannot always be stable from the node impedance [10]–[12]. Therefore, the resonance peak in the filter may need to be dampened in order not to be vulnerable from varying impedances in the network. One important thing to note is that adding a damping function to the inverter also can be useful to the nearby inverters. This damping function changes the impedance of the frequencies of concerns and helps the other converters to achieve stability. Therefore, not all of the inverters in the network are needed to have a damping function, but some of them can successfully stabilize the overall network. In order to prove this concept, a Cigré benchmark of a small-scale network [13] is selected for the network model and five different inverters are designed under the harmonic emission guideline [14]. The Impedance Based Stability Criterion (IBSC) is adopted to analyze the effect of active damping in inverters. Finally, time-domain simulation is performed in PSCAD/EMTDC environment to validate the analysis. The result shows two inverters with active damping among five can stabilize the overall network. TEST SYSTEM AND MODELING This section describes the test system for validating the effects of active damping in a distribution network. Also it discusses about the average switching modeling method for the inverter modeling. Then the time-domain implementation method is introduced as well. Finally, the network parameters and the inverter model are unified from the IBSC method and so as to perform the stability analysis. Test system Fig. 1 shows the Cigré benchmark model of the European LV distribution network. In order to show clearly show 1/5 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0950 the effect of the interacting inverters, only the cables and the inverters are considered. The voltage of the network is a three-phase line-to-line 400 V with 50 Hz. This distribution network is connected from the 20 kV medium voltage feeder with 400 kVA transformer. Each node is connected with underground cable and their positive sequence impedances are given in Table I. Passive loads, which cause unbalances in the network, are neglected for the simplicity. Grid inverters are designed under the harmonic emission guideline IEEE-519 [14] and their specifications are denoted in Table II. 400kVA 6% Rx R15 R6 Inv.1 R8 R17 R9 R18 Inv.2 Fig. 1. Simplified benchmark model of European LV distribution network. (Inv.1 ~ Inv.5 are Voltage Source Inverters) TABLE I. POSITIVE SEQUENCE IMPEDANCE OF UNDERGROUND CABLE. Node Length Resistance Inductance (From-To) [m] [mΩ] [uH] R1-R2 35 10.04 18.62 R2-R3 35 10.04 18.60 R3-R4 35 10.04 18.60 R4-R6 70 20.09 37.21 R6-R9 105 30.13 55.81 R9-R10 35 10.04 18.60 R4-R15 135 155.52 196.8 R6-R16 30 34.56 43.73 R9-R17 30 34.56 43.73 R10-R18 30 34.56 43.73 Transformer 3.2 40.74 TABLE II. GRID INVERTER SPECIFICATIONS AND THEIR PARAMETERS. Inverter name Inv. 1 Inv. 2 Inv. 3 Inv. 4 Inv. 5 Power rating [kVA] 35 25 3 4 5.5 Base Frequency, f0 [Hz] 50 Switching Frequency, fs [Hz] 103 1.6×103 103 (Sampling frequency ) DC-link voltage, Vdc [kV] 0.8 Harmonic emission recommendation Parasitics values Controller gain CIRED 2015 Lf [mH] Cf [uF] Lg [mH] rLf [mΩ] rCf [mΩ] rLg [mΩ] KP KI ig αβ ÷ den ig PLL trigger θ S&H Control Gc(z) num 1 2 vPCC i*αβ iαβ αβ Vdc i*g,dq αβ dq ig abc Fig. 3. PSCAD implementation of an inverter with active damping. Inv.5 R10 abc R14 R5 R7 1/ZLg CB Lg rLg iCf Limiter Node R16 Filter values rLf rCf Cf PWM R3 Inv.3 Lf vM Vdc R11 R13 ZCf Fig. 2. Averaged switching model of an inverter with active damping. z-1 R12 1/ZLf KAD Supply point Inv.4 Gd Bus R2 R4 Gc vM KAD 20kV : 0.4kV vPCC i*g Inverter Model Averaged switching model On the part of the IBSC for stability analysis, lumped admittance models of two interconnected systems are required [12]. One is the object of stability analysis called source admittance (Ysx), and the other one is the existing stable system that provides a stable datum called the load admittance. Normally, the source admittance becomes an output admittance of the inverter and the load admittance can be an input admittance of the stable network. Fig. 2. shows an averaged switched model of grid inverter with active damping. The output admittance of the inverter YO can be obtained by rearranging the block diagram with the following condition [15] YSx YO vPCC ig Z Lf Z Cf K ADGd Z Lf Z Lg ( Z Lf Z Lg ) Z Cf K ADGd Z Lf GC Gd Z Cf where, Gc represents the current controller, Gd is the equivalent model of digitizing delay, KAD is the active damping gain, and the filter impedances ZLf, ZLg and ZCf are as follows, GC K P 3.8 2.8 3 4 1.3 0.9 119.3 88 14.5 11 40.8 28.3 16.6 18 1500 1500 KI s s w02 2 Gd e1.5Ts s (2) (3) 1 sC f (4) Z Lf rLf sL f (5) Z Lg rLg sLg (6) ZCf rCf IEEE519 0.87 1.2 5.1 22 15 2 0.22 0.3 1.7 27.3 37.7 160.2 7.5 11 21.5 6.9 9.4 53.4 5.4 8.05 28.8 1000 1000 1500 (1) i*g 0 Also the open loop gain TOL can be derived as follows, TOL GC Gd ZCf Z Lf Z Lg ( Z Lf Z Lg )ZCf K ADGd Z Lf (7) 2/5 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0950 inverse of diagonal impedances. Time-domain simulation model Fig. 3. shows the time-domain model for PSCAD/ EMTDC simulation. In order to model the real system of the digital controller, sample and hold function is made and a digital resonance controller Gc(z) is used from (2) with the Tustin discretizing method, giving: K sin(2 f 0TS ) z 2 1 (8) GC ( z ) K P I 2 2 f 0 z 2 2cos(2 f 0TS ) z 1 This controller is driven by an external triggering signal for sample and hold. The controller operates in the stationary reference frame. YLx 1/ Zxx YSx where, ‘x’ indicates the inverter numbering. The Impedance Based Stability Criterion The two components for the IBSC are obtained, one is the source admittance of grid inverter (1) and the other one is the load admittance of stable network (11). If the ratio of these two quantities called the minor loop gain Tmx satisfies the Nyquist stability criterion, then the system with the grid inverter with the network is stable. Tmx Network model for the load admittance Previously, the source admittance of the inverter is obtained in (1). However, the load admittance on that node needs to be calculated. The Kirchhoff’s Current Law (KCL) admittance matrix is used to solve the admittance relation [11]. So the reference nodes, including the nodes of interest in the network, are set and named as a vector [V] and the current sources (grid inverters) attached to the nodes are named as a vector [I]. By arranging all the relations of the reference node voltages and the currents are derived as follows. Y17 Y27 Y72 Y82 Y77 Y87 VR 6 I Inv.1 V I Y18 R10 Inv.2 V I Y28 R18 Inv.3 V I R16 Inv.4 V I Y78 R15 Inv.5 I V Y88 R 3 R 3 VR 4 0 V R 9 0 (9) VR 6 V R10 Z VR18 11 Z 21 VR16 VR15 Z 71 VR 3 V Z81 R4 VR 9 [Z ] Z12 Z 22 Z17 Z 27 Z 72 Z82 Z 77 Z87 40 30 20 10 -10 0 -180 -360 100 Frequency (Hz) 1000 Fig. 4. Characteristics of individually stable inverters given in Table II. Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 15 (10) The diagonal elements in [Z] are representing the equivalent impedances of the node, which produce the node voltage by the current of the connected grid inverter. However, these diagonal elements include the output impedance of the grid inverter, which is not identified. Therefore, a stable load admittance can be obtained by subtracting the unidentified source admittance from the CIRED 2015 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 50 0 [I ] I Inv.1 I Z18 Inv.2 I Z 28 Inv.3 I Inv.4 I Inv.5 Z 78 I Z88 R 3 0 0 ACTIVE As explained in [9], the stable region of the inverter with LCL filter is determined by the sample frequency of the inverter and the resonance frequency of the LCL filter. If the LCL filter resonance frequency is higher than 1/6 of the switching frequency fs, the inverter becomes stable without any damping method. Therefore, in TABLE II, the grid inverters are designed according to this stability region, (7) is used for each inverter the stability analysis as shown in Fig. 4. All inverters are designed stable individually, and Fig. 5 shows time-domain simulation of the respective inverter currents with ideal grid voltage. 60 So all the admittances connected to the node are included in the matrix [Y]. In order to get the relation of the node voltage created by the node currents, [Y]-1 is multiplied both sides of (9) and the impedance matrix [Z] is obtained. [V ] WITH Stable inverter in ideal grid w/o damping Magnitude (dB) Y12 Y22 [I ] (12) Phase (deg) Y11 Y 21 Y71 Y81 [V ] YSx YLx SYSTEM STABILIZING DAMPING 10 Current (kA) [Y ] (11) 5 0 -5 -10 -15 0.1 0.12 0.14 Time (sec) 0.16 0.18 0.2 Fig. 5. Operation of stable inverters connected to the ideal grid voltage. Necessity in damping with grid impedance However, if these inverters are located in the network in Fig. 1, their stable operation cannot be assured from the 3/5 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0950 6 4 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 Inv.1 Inv.2 8 4 Imaginary Axis additional impedance at their connected node. These cases can be estimated by the IBSC. Each node in the system can have its own minor loop gain (12), and its stability is assessed by the Nyquist stability criterion. Fig. 6 shows the Nyquist diagram of the inverters. One thing to note is that Fig. 6 is drawn at one inverter in the network at a time in order not to include the effect of the other inverters. The interactions between the inverters are presented in the next section. Inv. 5 is the only stable inverter when the grid impedance changes, and the rest of them become unstable. Thus, all the inverters except the Inv. 5 may need active damping in order to be stable. Fig. 7 shows a stabilized effect from active damper. 0 -4 -8 -8 -6 -4 -2 Real Axis 0 2 4 Fig. 9. Unstable inverters in the network without active damping. 20 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 Current (A) Imaginary Axis 2 0 0 -2 -20 -4 -6 -20 -10 Real Axis 0 0 Fig. 6. Unstable inverters in the network without active damping. 4 3 Imaginary Axis 2 0 -2 -3 -3 -2 -1 Real Axis 0 1 Fig. 7. Individually stabilized inverters with active damping. Inv.1 0 -20 20 Inv.2 0 Current (A) -20 20 20 -20 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 Inv.4 0 Current (A) 0 -20 20 0.1 Even if the inverter is stable when it operates alone, it may easily become unstable, when the other inverters are participating in the network. As shown in Fig. 9, inverters, especially Inv. 1 and Inv. 2 are becoming unstable, when they operate together at the same time. The time domain simulations in Fig. 10 show the unstable inverters. Inv. 1 and Inv. 2 are no longer stable sinusoidal waveforms as compared to the stable cases in Fig. 8. Therefore, the active damping gains in the inverters are increased in order to stabilize the overall network. There are many possible gains to obtain stability. In this case Inv. 3 and Inv. 4 are changed. Inv.3 0 20 0.08 Interaction among inverters -1 20 0.04 Time (sec) 0.06 Fig. 8 compares the respective unstable and stabilized inverter output currents, which are estimated by the Nyquist plots shown in Fig. 6 and Fig. 7. The inverters in the network are stable when the inverter operates one at a time for all inverters. Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 1 -4 0.02 Fig. 10. Instability from the interaction of the inverters. Inv.5 -20 0 W/O damping -20 0.1 0.12 0.14 W/ active damping 0.16 Time (sec) 0.18 0.2 Fig. 8. Unstable inverter w/o damping and stabilized w/ damping (KAD,Inv.1 = 1, KAD,Inv.2 = 1, KAD,Inv.3 = 4, KAD,Inv.4 = 5). CIRED 2015 0 0.02 0.04 Time (sec) 0.06 0.08 0.1 Fig. 11. Stabilized inverters with increased gains (KAD,Inv.1 = 1, KAD,Inv.2 = 1, KAD,Inv.3 = 10, KAD,Inv.4 = 12). 4/5 23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015 Paper 0950 Fig. 11 shows the stabilized waveform of the inverters by the action of additional gain changes in active damping in Inv. 3 and Inv. 4. It is related to the impedance changes in the network caused by the impedance change in Stable network with reduced active damping Furthermore, the system stability can be obtained by reduced efforts, if the gains are properly chosen. In this case, only the Inv. 1 and Inv. 2 are having active damping functions with increased gains. Fig. 12 shows the stabilized waveforms of inverter currents. As compared to Fig. 11, the transient high frequency oscillations are much reduced by the proper selection of gains. Also, the Nyquist plot shows the stable operations of the inverters in Fig. 13. 20 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 0 -20 0 0.02 0.04 Time (sec) 0.06 0.08 0.1 Fig. 12. Stabilized inverters with two active damping functions (KAD,Inv.1 = 2, KAD,Inv.2 = 3). 40 Inv.1 Inv.2 Inv.3 Inv.4 Inv.5 Imaginary Axis 20 0 -20 -40 -30 -20 -10 0 Real Axis 10 20 30 Fig. 13. Stabilized inverters with two active damping functions. CONCLUSION This paper demonstrates the role of an active damping function for stabilizing an unstable inverter. The damping function can stabilize the inverter itself as well as the unstable network suffering from the interactions among other inverters. The result shows that not all the inverters in the network are needed active damping functions if some of the inverters are designed properly. Therefore, the overall network is successfully stabilized. In order to prove this concept, Cigré small-scale benchmark case is selected for the network model and five different inverters are designed under the harmonic emission guideline. The Impedance Based Stability Criterion (IBSC) is adopted to analyze the effect of the active damping in inverters. Finally, time-domain simulations are performed in the PSCAD/EMTDC tool. CIRED 2015 Acknowledgments This work was supported by The European Research Council (ERC) under the European Union’s Seventh Framework Program (FP/2007- 2013)/ERC Grant Agreement no. [321149-Harmony]. REFERENCES [1] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview of Control and Grid Synchronization for Distributed Power Generation Systems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, Oct. 2006. [2] J. H. R. Enslin and P. J. M. Heskes, “Harmonic Interaction Between a Large Number of Distributed Power Inverters and the Distribution Network,” IEEE Trans. Power Electron., vol. 19, no. 6, pp. 1586–1593, Nov. 2004. [3] X. Wang, F. Blaabjerg, and W. Wu, “Modeling and Analysis of Harmonic Stability in an AC Power-Electronics-Based Power System,” IEEE Trans. Power Electron., vol. 29, no. 12, pp. 6421–6432, Dec. 2014. [4] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 263–272, Jan. 2006. [5] W. Wu, Y. He, T. Tang, and F. Blaabjerg, “A New Design Method for the Passive Damped LCL and LLCL Filter-Based Single-Phase Grid-Tied Inverter,” IEEE Trans. Ind. Electron., vol. 60, no. 10, pp. 4339–4350, Oct. 2013. [6] R. Peña-Alzola, M. Liserre, F. Blaabjerg, R. Sebastián, J. Dannehl, and F. W. Fuchs, “Analysis of the Passive Damping Losses in LCLFilter-Based Grid Converters,” IEEE Trans. Power Electron., vol. 28, no. 6, pp. 2642–2646, Jun. 2013. [7] D. Pan, X. Ruan, C. Bao, W. Li, and X. Wang, “Capacitor-CurrentFeedback Active Damping With Reduced Computation Delay for Improving Robustness of LCL-Type Grid-Connected Inverter,” IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3414–3427, Jul. 2014. [8] Chenlei Bao, Xinbo Ruan, Xuehua Wang, Weiwei Li, Donghua Pan, and Kailei Weng, “Step-by-Step Controller Design for LCL-Type GridConnected Inverter with Capacitor–Current-Feedback ActiveDamping,” IEEE Trans. Power Electron., vol. 29, no. 3, pp. 1239–1253, Mar. 2014. [9] S. G. Parker, B. P. McGrath, and D. G. Holmes, “Regions of Active Damping Control for LCL Filters,” IEEE Trans. Ind. Appl., vol. 50, no. 1, pp. 424–432, Jan. 2014. [10] X. Wang, F. Blaabjerg, and P. C. Loh, “An Impedance-Based Stability Analysis Method for Paralleled Voltage Source Converters,” in Proc. The 2014 International Power Electronics Conference, 2014, pp. 1529–1535. [11] X. Wang, F. Blaabjerg, M. Liserre, Z. Chen, J. He, and Y. Li, “An Active Damper for Stabilizing Power-Electronics-Based AC Systems,” IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3318–3329, Jul. 2014. [12] J. Sun, “Impedance-Based Stability Criterion for Grid-Connected Inverters,” IEEE Trans. Power Electron., vol. 26, no. 11, pp. 3075– 3078, Nov. 2011. [13] “Benchmark Systems for Network Integration of Renewable and Distributed Energy Resources C06.04.02,” CIGRE, 2014. [14] D. Committee, I. Power, and E. Society, “IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems,” vol. 2014, pp. 1–29, 2014. [15] X. Wang, X. Ruan, S. Liu, and C. K. Tse, “Full Feedforward of Grid Voltage for Grid-Connected Inverter With LCL Filter to Suppress Current Distortion Due to Grid Voltage Harmonics,” IEEE Trans. Power Electron., vol. 25, no. 12, pp. 3119–3127, Dec. 2010. 5/5