ADDENDUM NO. 1 Bid Documents May 18, 2016 Re: MCC15-03CM Addendum #1 To: Bidders and All Others to Whom Bidding Documents have been issued. All items in this Addendum shall supersede or clarify the Bidding Documents as originally issued. The cost of the Work of all trades affected by the changes in this Addendum shall be included in the Base Bid or Alternates, on the Proposal Form, as applicable. Failure to do so may subject the Bidder to disqualification. This Addendum forms a part of the Contract Documents. It supplements and/or modifies them as follows: CHANGES TO SPECIFICATIONS: Item No. 01: Section 00 21 13 – 3.03: Add Content below: H. Bid forms shall only be obtained from the Construction Manager. Item No. 02: Section 00 21 13 – 6.01.D. Modify the following information: 1. All Sub-Bid e-mails shall be clearly marked with the Bidder’s Name, applicable Bid Section(s), and “MCC Advanced HVAC & Electrical Technology Building Bid” 2. Sub-Bids shall be submitted at or before 3:00pm on Wednesday, May 25, 2016. Item No. 03: Section 01 10 00 – 1.4.A.2: Delete Item. Item No. 04: Section 01 45 33.1, page 3: Delete Item #2. “Fabricator and Erector Certifications”. Item No. 05: Section 05 12 00 – 1.6.A. Modify the following information: A. Qualifications: The steel fabricator and erector conducting the work of this Section shall comply with the AISC “Specification for Structural Steel Buildings”, the AISC “Code of Standard Practice for Steel Buildings and Bridges”. Item No. 06: Section 08 31 00 BSD. See revised specification attached for information regarding manhole covers. Item No. 06: Section 08 71 00 – 2.18.A. Modify the following information: 4. Note: The Contractor shall submit all Fire Department Lock Box specifications and submittals to the Town of Manchester Fire Department for approval. Provide written verification of approval, for record to the Architect. Item No. 07: Section 09 21 16 – 2.01.D.3. Televisions to be installed by owner. Add the following information: i. Other items or equipment furnished by Owner to be wall mounted: Coordinate loads required with owner. Item No. 08: Section 10 14 25 – 2.01.B.3. Modify the following information: Lavallee Brensinger Architects | 155 Dow Street, Suite 400 | Manchester, NH 03101 | tel: 603-622-5450 | web: LBPA.com MCC15-03CM Page 2 Addendum #1 a. Capacity signs shall be provided for the following spaces: Ground Floor Classroom Block (applicable only when foldable partition doors are open). Item No. 09: Section 10 26 01 – 2.01.B. Modify the following information: A. Mop Room Wall Protection Panels Type 50lb: 0.060” thickness, engineered PETG (non-PVC); manufacturer’s accessories. Item No. 10: Section 10 56 13. See modified section attached. Item No. 12: Section 12 48 13 – 2.01: Mat is to be “MD” Type. Item No. 11: Section 22 00 00 – 1.12. Modify the following information: A. All plumbing work shall be installed in accordance with the New Hampshire State Plumbing and Gas Code and any regulations of the City of Manchester as the apply to the installation. Such laws and ordinances are to be considered a part of the Specification. Item No. 12: Section 23 – 2.15: Please note that any manufacturer able to meet the specifications and drawings are welcome to submit a bid as an equal to the manufacturers listed. Campus integration is not owned in the documents, but this is a BACnet open system, so any manufacturer with the same system should be able to interface. Item No. 13: Division 26 00 00: Add Medium-Voltage Cable Sections attached. Item No. 14: Appendix “A”– Geotechnical Report. Please note the following: 1. The building is primarily a cut. The on-site soils do not meet the slab base course specification attached to the geotechnical report. 2. Footings may bear on the native, proof-rolled sands. 3. The free draining fill is essentially the chimney drain and serves to relieve hydrostatic pressure against the walls. The slab base soil is for slab support, and gradation is similar. 4. Remove Appendix D, “Draft Earthwork Specifications” CHANGES TO DRAWINGS: Item No. 01: Drawing Sheet C-1: See SKC-01 and clarifications below: 1. 2. If it is determined in the field that the existing structure DMH 110 can be re-cored to accept the larger diameter culvert, then the structure may be utilized. However, if it is determined that there is not enough basin wall available to re-core, then the structure is to be replaced. The headwall will likely need to be rebuilt/replaced as increasing the diameter of the pipe from 24” to 36” is not expected to leave enough concrete/wall above the top of the pipe after re-coring. See attached for added detail. Also see attached for revised length of culvert. Item No. 02: Drawing Sheet C-2: See SKC-02, which coordinates with revised transformer location. Item No. 03: Drawing Sheet C-3. See SKC-03, which shows the UGE & C extending to the adjacent utility pole. MCC15-03CM Page 3 Addendum #1 Item No. 04: Drawing Sheet C-6: Modify erosion control matting (NAG SC-150) to be placed on slopes greater than 3:1. Reference SKC-04 attached. Item No. 05: Drawing Sheet C-7: The swale should be constructed/reconstructed to match the existing swale along the campus access road. See attached SKC-05 for intent. Item No. 06: Drawing Sheet C-8: Please note the following: 1. 2. 3. 4. 5. The gas main sleeve was installed during road construction to avoid disturbing the rebuilt campus road. See attached SKC-06 for added concrete headwall detail. See attached SKC-07 for added concrete patio detail. See attached SKC-08 for revised Concrete Sidewalk details. See attached SKC-09 for typical pavement detail. Item No. 06: Drawing Sheet A0.3: Delete Frame Type 5, which is not in the project. Item No. 07: Drawing Sheet A0.4: Add Type “6” Aluminum Storefront Frame Type to detail with missing title. Item No. 08: Aluminum Framing Clarifications. See attached SKA-01 and written instructions below: 1. 2. 3. 4. Add Vestibule Door X201 to Door schedule and plan (no changes required to door hardware specifications) Use new Aluminum Framing Type Tags for reference back to sheet A0.4. The storefront framing in detail H6/A6.6 is Storefront Framing Type 5. Use revised detail J7/A0.5. Item No. 09: Drawing A1.2: Modify the following information: 1. 2. Change composite manhole specification section reference to 08 31 00. Change wire mesh partition specification section reference to 10 56 13. Item No. 10: Drawing Sheet A3.0: Delete note “07 53 – DECK UNDERLAYMENT” from Type A Roof Assembly. Item No. 11: Drawing Sheet AI1.0: Modify the following information on the interior finish schedule: 1. 2. All Confined Space Training Rooms shall be finished similar to Room 118 Mop Room to have Wall Protection Type WPP-3, 0.060”, PETG Panels per specifications. Item No. 12: Drawing Sheet P900: See attached SKP-01 for added detail of Hydrocoil. Item No. 13: Drawing Sheet E001: See full revised sheet for added conduit and duct banks, altered notes. Item No. 14: Drawing Sheet E100: See attached SKE-01 for extraneous lights removed. MCC15-03CM Page 4 Addendum #1 Item No. 15: Drawing Sheet E101: See attached SKE-02 and SKE-03 for extraneous lights removed, outdoor EBU added. Item No. 16: Drawing Sheet E102: See attached SKE-04 for extraneous lights removed, lights added. Item No. 17: Drawing Sheet E201: EPO connections clarified, conduit & duct bank penetrations added, grounding clarified. Refer to SKE-05, SKE-06, and SKE-07. Item No. 18: Drawing Sheet E202: EPO connections clarified, Detail number added. Refer to SKE-08. Item No. 19: Drawing Sheet E203: Erroneous lights removed, unistrut moved to correct location. Refer to SKE-09, SKE10, and SKE-11. Item No. 20: Drawing Sheet E302: Sheet title corrected. Item No. 21: Drawing Sheet E400: Conductor sizes and connections clarified, conduit to gear clarified. Refer to full revised sheet attached. Item No. 22: Drawing Sheet E500: Fire Alarm Riser Diagram expanded. Outdoor EBU added. Refer to SKE-14 and SKE-15. Item No. 23: Drawing Sheet E600: Counterpoise detail added. Refer to SKE-13. Item No. 24: Drawing Sheet M000: Revised smoke detector note 10 under general notes to clarify that smoke detectors are furnished and wired by Division 26 00 00, installed in duct by 23 00 00. Refer to SKM-02. Item No. 25: Drawing M902: Added additional model information to flow meter and flow indicator. Refer to SKM-01. END OF ADDENDA #1 Manchester Community College Advanced HVAC & Electrical Technology Building 18 May 2016 Addendum 1 - Section 08 31 00 SECTION 08 31 00 ACCESS DOORS AND PANELS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wall access door and frame units. B. Ceiling access door and frame units. C. Floor access manhole cover and frame. D C. It is not intended that the Drawings or Specifications identify specific access door sizes or locations. Subcontractors whose work requires access panels in wall, floor, and ceiling assemblies shall thoroughly examine all Contract Documents and provide suitable access to all equipment, hardware, accessories and all other items that may require adjustment, observation or maintenance. Note: Access doors located in mechanical equipment or ductwork are provided as part of the work of Division 23 - HVAC. 1.02 RELATED REQUIREMENTS A. Section 03 30 00 – Concrete: Openings in concrete. B A. Section 09 90 00 - Painting and Coating: Field paint finish. C B. Division 22 - Plumbing D C. Division 23 - HVAC E D. Division 26 - Electrical 1.03 REFERENCE STANDARDS A. ITS (DIR) - Directory of Listed Products; Intertek Testing Services NA, Inc.; current edition. B. UL (FRD) - Fire Resistance Directory; Underwriters Laboratories Inc.; current edition. 1.04 SUBMITTALS A. See Section 01 30 00 - Administrative Requirements, for submittal procedures. B. Product Data: Provide materials, construction, profiles, types, finishes, hardware, locking provisions, and details of adjoining work. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Karp Associates, Inc. 1. Milcor by Commercial Products Group of Hart & Cooley, Inc. 2. Nystrom Products. 3. Larsens Manufacturing Co. 4. Substitutions: See Section 01 60 00 - Product Requirements. B. Units in Fire Rated Assemblies: Fire rating equivalent to the fire rated assembly in which they are to be installed. 1. Provide products listed and labeled by UL or ITS (Warnock Hersey) as suitable for the purpose specified and indicated. C. Floor Units: 1. Fibrelite. 2. GMI Composites Inc. 3. Substitutions: See Section 01 60 00 - Product Requirements. 15-039-00 CCSNH Project # MCC15-03CM ACCESS DOORS AND PANELS Page 1 of 2 Manchester Community College Advanced HVAC & Electrical Technology Building 18 May 2016 Addendum 1 - Section 08 31 00 2.02 WALL AND CEILING UNITS A. Door and Frame Units: Factory fabricated, fully assembled units with corner joints welded, filled, and ground flush; square and without rack or warp; coordinate requirements with assemblies units are to be installed in. 1. Material: Steel. B. Door and Frame Units: Formed steel. 1. Frames and flanges: 0.058 inch steel with anchoring devices appropriate for the related wall or ceiling construction. a. Exposed flanges shall be nominal one inch wide. b. Frames for gypsum board assemblies shall be furnished with edge trim for gypsum board mud-in frame installations. 2. Non-rated door panels: 0.070 inch single thickness steel sheet. 3. Non-rated door panels separating heated from non-heated space: 0.070 inch double sheet with integral non-combustible insulation filler. 4. Fire-rated door panels: 0.070 inch double sheet with integral non-combustible insulation filler. 5. Units in Fire Rated Assemblies: Fire rating equivalent to the fire rated assembly in which they are to be installed. a. Provide products listed and labeled by UL or ITS (Warnock Hersey) as suitable for the purpose specified and indicated. b. All doors in fire-rated construction shall be fire-rated in conformance with the fire rating requirement of the construction assembly and labeled "For Horizontal Installation" or "For Vertical Installation". c. All doors located in proximity to combustibles shall be labeled to indicate a maximum surface temperature rise of 250 degrees F. 6. Size: As indicated on the Drawings or as required to meet specific job requirements. 7. Hardware: a. Hinge: Concealed constant force closure spring type. b. Latch: Tool latch. c. All doors intended to allow a person to fully pass through shall be operable from the inside without the use of a tool or key. d. Horizontal Applications: Shall be equipped with restraints to prevent doors from falling open or closed upon release. All doors greater in size than 300 square inches and installed horizontally shall be provided with the following sign in 1/2" high red letters adjacent to the door lock: "Caution: Door will drop upon lock release". 8. Prime coat with baked on rust-inhibitive shop primer and shall be field painted to match adjacent surfaces. 9. Gasketing: For all doors that separate heated and unheated space. Extruded neoprene, around the perimeter of the door panel. 2.03 FLOOR UNITS A. Floor access manhole cover and frame: Factory fabricated, fiber reinforced polymer frame and cover assembly with integral gasket system. Non-conductive. 1. Size: 24 inches, clear opening. 2. Shape: Round. 3. Frame: Manufacturer standard with bedding slots. 4. Load Capacity: 28,000 lbs, minimum. 5. Color: Selected by architect from manufacturers full range, including safety yellow or blue. 6. Lock: Quarter turn paddle type lock. 7. Tools & Accessories: a. Manhole Hook: Manufacturer standard. 1) Quantity: (2) two. b. Lock Paddle Wrench: Manufacturer standard. 15-039-00 CCSNH Project # MCC15-03CM ACCESS DOORS AND PANELS Page 2 of 2 Manchester Community College Advanced HVAC & Electrical Technology Building 8. 18 May 2016 Addendum 1 - Section 08 31 00 1) Quantity: (2) two. Surface Texture/Design: Anti-Skid/Slip Resistant, ADA Compliant. Dry and wet tested per ASTM C-1028. a. Static Coefficient of Friction (SCOF): 0.6 or greater. PART 3 EXECUTION 3.01 EXAMINATION A. Verify that rough openings for door and frame are correctly sized and located. B. Door locations that may physically or visually conflict with adjacent construction or building features shall be brought to the attention of the Architect prior to 'roughing-in'. Doors installed in locations objectionable to the Architect shall be removed, patched, and relocated at no additional cost to the Owner. 3.02 INSTALLATION A. Install units in accordance with manufacturer's instructions. B. Install frames plumb and level in openings. Secure rigidly in place. C. Position units to provide convenient access to the concealed work requiring access. D. Floor Units shall be placed plumb and flush to top of finish flooring. Cast base within concrete floor slab per manufacturer’s instructions. E D. Adjust hardware and panels after installation for proper operation. F E. Door lock keys shall be labeled and turned over to the Owner per Project Close-out requirements. END OF SECTION 15-039-00 CCSNH Project # MCC15-03CM ACCESS DOORS AND PANELS Page 3 of 2 Manchester Community College Advanced HVAC & Electrical Technology Building Addendum 1 – 18 May 2016 Section 10 56 13 SECTION 10 56 13 METAL STORAGE SHELVING PART 1 GENERAL 1.01 SECTION INCLUDES A. Metal storage shelving. B. Shelving accessories. C. Enclosures and doors. 1.02 RELATED REQUIREMENTS A. Section 06 10 54 - Wood Blocking & Curbing: Blocking in walls for anchoring. B. Section 09 21 16 - Gypsum Board Assemblies: CFMF for anchoring of shelving units. 1.03 REFERENCE STANDARDS A. ANSI MH28.1 - American National Standard for the Design, Testing, Utilization and Application of Industrial Grade Steel Shelving - Specifications; 1997. B. ASCE 7 - Minimum Design Loads for Buildings and Other Structures; American Society of Civil Engineers; 2011. 1.04 SUBMITTALS A. See Section 01 30 00 - Administrative Requirements, for submittal procedures. B. Product Data: Manufacturer's data sheets on each product to be used, including: 1. Rated uniform shelf loads. 2. Details of shelving assemblies, including reinforcement. 3. Accessories. C. Test Reports: Provide independent agency test reports documenting compliance with specified structural requirements. 1. In lieu of test reports, detailed drawings stamped and sealed by a Professional Engineer licensed in the State in which the Project is located will be acceptable. D. Shop Drawings: Indicate location, type, and layout of shelving, including lengths, heights, and aisle layout, and relationship to adjacent construction. 1. Indicate methods of achieving specified anchoring requirements. E. Selection Samples: For each finish product specified, color chips representing manufacturer's full range of available colors and finishes. F. Warranty: Submit manufacturer warranty and ensure that forms have been completed in Owner's name and registered with manufacturer. 1.05 QUALITY ASSURANCE A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section, with not less than three years of documented experience. 1.06 DELIVERY, STORAGE, AND HANDLING A. Inspect for dents, scratches, or other damage. Replace damaged units. B. Store in manufacturer's unopened packaging until ready for installation. C. Store under cover and elevated above grade. 1.07 WARRANTY A. See Section 01 78 00 - Closeout Submittals, for additional warranty requirements. B. Provide one year manufacturer warranty covering defects of manufacturing and workmanship and rust and corrosion. 15-039-00 CCSNH Project # MCC15-03CM METAL STORAGE SHELVING Page 1 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building Addendum 1 – 18 May 2016 Section 10 56 13 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Four Post Shelving: 1. Hallowell, Div. of List Industries, Inc. 2. Penco Products, Inc. 3. SpaceSaver Corporation. 4. Substitutions: See Section 01 60 00 - Product Requirements. 2.02 SHELVING - GENERAL A. See drawings for layout and sizes. B. Shelving: Provide products tested to comply with ANSI MH28.1 for design criteria, lateral stability, shelf connections, and shelf capacity. C. Seismic Design: Design for Seismic Class D, in accordance with ASCE 7, Section 9. D. Anchors: Provide anchoring hardware to secure each shelving unit to floor and wall. 1. Provide hardware of type recommended by manufacturer for substrate. 2.03 FOUR POST SHELVING A. Four Post Shelving: Steel post-and-beam type with sway bracing, shelving brackets, shelving surfaces, and accessories as specified. 1. Unit Width: 78 inches, center to center of posts. 2. Shelf Capacity: Rated uniform load of 100 psf, minimum, tested in accordance with ANSI MH28.1. 3. Shelf Deflection: 1/4 inch in 36 inches, maximum, under rated uniform load. 4. Adjustability of Shelving: Continuous along length of post. 5. Shelf Depth: 36 inches, minimum. 6. Shelf Height: a. (3) Three Units: 96 inches. b. (3) Three Units: 144 inches. 7. Shelves per Unit: As indicated on drawings. 8. Finish: Galvanized. 9. Number of Units: As indicated on drawings. B. Posts and Beams: Formed sheet members; perforations may be exposed on face of members. 1. Metal Thickness: 13 gage, 0.0897 inch. 2. Post Shape: Tee intermediate posts, angle end posts forming corners. 3. Post Face Width: 2 inches, maximum. 4. Connecting Hardware: Manufacturer's standard. 5. Post Bases: Flat steel foot plate, with manufacturer’s recommended adjustable leveling device. C. Bracing: Formed sheet members. 1. Back Sway Bracing: Either strap; at back of each unit. 2. Side Sway Bracing: Strap type; at each side of each unit. 3. Strap Sway Bracing: One strap installed diagonally, 16 gage, 0.0598 inch; welded, riveted, or bolted to uprights. D. Shelves: Formed sheet, finished on all surfaces. 1. Metal Thickness: 13 gage, 0.0897 inch. 2. Provide raised edge lip on all shelves; height 2 inches. 3. Shelf Connection to Posts: Manufacturer's standard. 2.04 ACCESSORIES A. Label Holders: Steel, attached to front face of shelf. 1. Size: 2-1/4 by 3/4 inches. 2. Finish: Manufacturer’s standard. 15-039-00 CCSNH Project # MCC15-03CM METAL STORAGE SHELVING Page 2 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building 3. Addendum 1 – 18 May 2016 Section 10 56 13 Mounting: Slide-on. B. Enclosure and Doors at Shelving Units: Steel mesh enclosure with sliding doors. 1. Enclosure: 2 inches x 2 inches welded wire mesh securely welded to manufacturer standard frames and stiffeners. a. Application: Sides, back, front and top enclosure of all shelving specified per the Section. b. Size/Configuration: 1) Perimeter: See Drawings. 2) Height: Full height of shelving unit. Floor to ceiling. 2. Enclosure Thickness: 10 gauge. 3. Enclosure Doors: Manufacturer standard. a. Size: See Drawings. b. Manufacturer standard partition lock front (SF-1) with standard back (SB-1). c. Lock Cylinder: See Section 08 71 00. 4. Accessories, brackets and fasteners: Manufacturer standard required for a complete system including floor anchors. 5. Finish: Powder Coat. a. Color: Selected by Architect from manufacturer stock colors. 6 5. Products: RapidWire Enclosure & Doors by WireCrafters. 7 6. Substitutions: See Section 01 60 00 - Product Requirements. C. Independent Enclosure and Doors: Steel mesh enclosure with hinged doors. 1. Enclosure: 1 inch x 2 inches welded wire mesh securely welded to manufacturer standard frames and stiffeners. a. Application: Room #224 HVAC 101 b. Size/Configuration: 1) Perimeter: See Drawings. 2) Height: 10 feet. 2. Enclosure Thickness: 10 gauge. 3. Enclosure Doors: Manufacturer standard. a. Size: See Drawings. b. Manufacturer standard partition lock front (SF-1) with lever handle back (SB-4). c. Lock Cylinder: See Section 08 71 00. 4. Posts and Base Plates: 2 inch x 2 inch x 14 gauge steel tubing with 2 inch x 7 inch x 1/4 inch steel base plates. Posts and base plates shall be factory welded. Factory drilled for anchoring hardware. 5. Accessories, brackets and fasteners: Manufacturer standard required for a complete system including floor anchors. 6. Finish: Powder Coat. a. Color: Selected by Architect from manufacturer stock colors. 7. Products: Style 840 Enclosure & Doors by WireCrafters. 8. Substitutions: See Section 01 60 00 - Product Requirements. PART 3 EXECUTION 3.01 EXAMINATION A. Verify that substrate is level and that clearances are as specified. B. Do not begin installation until substrates have been properly prepared. C. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding. 3.02 PREPARATION A. Clean surfaces thoroughly prior to installation. 15-039-00 CCSNH Project # MCC15-03CM METAL STORAGE SHELVING Page 3 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building B. Addendum 1 – 18 May 2016 Section 10 56 13 Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions. 3.03 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Anchor and reinforce as specified, as indicated on drawings, and as recommended by manufacturer. C. Install shelving with shelf surfaces level and vertical supports plumb; adjust feet and bases as required. D. Out-Of-Square Tolerance - Four Post Shelving: Maximum of 1/8 inch difference in distance between bottom shelf and canopy top, measured along any post in any direction. 3.04 PROTECTION A. Protect installed products until completion of project. B. Touch-up, repair or replace damaged products before Substantial Completion. END OF SECTION 15-039-00 CCSNH Project # MCC15-03CM METAL STORAGE SHELVING Page 4 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building 18 May 2016 Section 26 00 00 – ADDENDUM 1 PART 2 PRODUCTS 2.25 MEDIUM-VOLTAGE CABLE A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Cables: a. American Insulated Wire Corp.; Leviton Manufacturing Co. b. BICC Brand-Rex Company. c. Carol Cable Co., Inc. d. Kerite Co. (The); Hubbell Inc. e. Okonite Co. (The) f. Pirelli Cable Corp.; Power Cable Division. g. Rome Cable Corp. h. Southwire Company. 2. Cable Splicing and Terminating Products and Accessories: a. Elastimold. b. Engineered Products Co. c. G&W Electric Co. d. Mac Products, Inc. e. MP Husky Corp. f. Raychem Corp.; Energy Division. g. RTE Components; Cooper Power Systems, Inc. h. Scott Fetzer Co.; Adalet-PLM Subsidiary. i. Thomas & Betts Corp. j. 3M Company; Electrical Products Division. B. Cables 1. Type: MV90. 2. Conductor: Copper. 3. Conductor Stranding: Class B. 4. Insulation: Cross-linked polyethylene complying with AEIC CS 5. a. Voltage Rating: 15 kV. b. Insulation Thickness: 133 percent insulation level. c. Circuit Identification: Color-coded tape (black, red, blue) under the metallic shielding. 5. Jacket: Cross-linked polyethylene. C. Splice Kits 1. Connectors: IEEE 404, compression type, as recommended by cable or splicing kit manufacturer for the application. 2. Splicing Products: As recommended in writing by splicing kit manufacturer for specific sizes, ratings, and configurations of cable conductors and splices specified. Include all components required for complete splice, with detailed instructions. a. Taped splice kit. b. Combination tape and cold-shrink rubber sleeve kit with re-jacketing by castepoxy-resin encasement or other waterproof, abrasion-resistant material. c. Heat-shrink splicing kit of uniform, cross-section, polymeric construction with outer heat-shrink jacket. d. Pre-molded, cold-shrink rubber, in-line splicing kit. e. Pre-molded EPDM splicing body kit with cable joint sealed by interference fit of mating parts and cable. D. Solid Terminations 15-039-00 CCSNH Project # MCC15-03CM MEDIUM-VOLTAGE CABLE Page 1 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building E. F. G. H. 18 May 2016 Section 26 00 00 – ADDENDUM 1 1. Conductor Terminations: Comply with IEEE 48, as indicated. Insulation class is equivalent to that of cable. Terminations for shielded cables include a shield ground strap. a. Class 1 Termination for Shielded Cable: Modular type, furnished as a kit, with stress-relief tube; multiple, molded-silicone rubber, insulator modules; shield ground strap; and compression-type connector. 2. Termination for Non-shielded Cable: Kit with compression-type connector. Include silicone-rubber tape, cold-shrink rubber sleeve, or heat-shrink plastic-sleeve moisture seal for end of insulation whether or not supplied with kits. Separable Insulated Connectors 1. Separable Insulated Connectors: Modular system complying with IEEE 386. Disconnecting, single-pole, cable terminators and matching, stationary, plug-in, deadfront terminals designed for cable voltage and for sealing against moisture. 2. Terminations at Distribution Points: Modular type, consisting of terminators installed on cables and modular, dead-front, terminal junctions for interconnecting cables. 3. Dead-Break Cable Terminators: Elbow-type unit with 600-A continuous-current rating, designed for de-energized disconnecting and connecting; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled. 4. Dead-Front Terminal Junctions: Modular bracket-mounted groups of dead-front stationary terminals that mate and match with above cable terminators. 2-, 3-, or 4terminal units as indicated, with fully rated, insulated, watertight conductor connection between terminals. Grounding lug and manufacturer's standard accessory stands, stainless-steel mounting brackets, and attaching hardware. a. Portable Feedthrough Accessory: 2-terminal, dead-front junction arranged for removable mounting on accessory stand of stationary terminal junction. b. Grounding Kit: Jumpered elbows, portable feedthrough accessory units, protective caps, test rods suitable for concurrently grounding 3 phases of feeders, and carrying case. c. Standoff Insulator: Portable, single dead-front terminal for removable mounting on accessory stand of stationary terminal junction. Insulators suitable for fully insulated isolation of energized cable elbow terminator. 5. Tool Set: Shotgun hot stick with energized terminal indicator, fault-indicator test tool, and carrying case. Arc-Proofing Materials 1. Tape for First Course on Metal Objects: 10-mil- (250-micron-) thick, corrosionprotective, moisture-resistant, PVC pipe-wrapping tape. 2. Arc-Proofing Tape: Fireproofing tape, flexible, conformable, intumescent to 0.3 inch thick, compatible with cable jacket. 3. Glass-Cloth Tape: Pressure-sensitive adhesive type, 1/2 inch wide. Conduits Seals 1. All spare, unused conduits shall be sealed with a water tight seal. 2. All conduits in use shall be sealed with a water tight seal utilizing appropriate Raychem RDSS (Rayflate duct sealing system) at both ends. Source Quality Control 1. Test and inspect cables according to NEMA WC 7 (ICEA S-66-524) and NEMA WC 8 (ICEA S-68-516) before shipping. 15-039-00 CCSNH Project # MCC15-03CM MEDIUM-VOLTAGE CABLE Page 2 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building 18 May 2016 Section 26 00 00 – ADDENDUM 1 PART 3 INSTALLATION 3.28 INSTALLATION OF MEDIUM-VOLTAGE CABLES A. Examine raceways to receive medium-voltage cables for compliance with requirements for installation tolerances and other conditions affecting performance of cables. Do not proceed with installation until unsatisfactory conditions have been corrected. B. INSTALLATION 1. Install cables as indicated, according to manufacturer's written instructions and IEEE 576. 2. Pull Conductors: Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values. 3. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceways. Do not use rope hitches for pulling attachment to cable. 4. Install exposed cables, parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible. 5. Support cables according to Division 26 Section "Raceway Support Systems." 6. Install direct-buried cables on leveled and tamped 3-inch bed of clean sand at bottom of trench. Separate cables crossing other cables or piping from those items by a minimum of 4 inches of tamped earth. Install permanent markers at ends of cable runs, changes in direction, and buried splices. 7. Install "buried cable" warning tape 12 inches above cables. 8. In manholes, handholes, pull boxes, junction boxes, and cable vaults, train cables around walls by the longest route from entry to exit and support cables at intervals adequate to prevent sag. 9. Install splices at pull points and elsewhere as indicated; use standard kits. Comply with kit manufacturer's written instructions. 10. Install terminations at ends of conductors and seal multiconductor cable ends with standard kits. Comply with kit manufacturer's written instructions and with classes of terminations indicated. 11. Install separable insulated-connector components where indicated according to manufacturer's written instructions. a. Quantities: Provide the following quantities of components: 1) Protective Cap: Install at each terminal junction, one on each terminal to which no feeder is indicated to be connected. 2) Portable Feedthrough Accessory: 3. 3) Standoff Insulator: 3. 12. Arc Proofing: Arc proof medium-voltage cable at locations not protected by conduit, cable tray, direct burial, or termination materials, unless otherwise indicated. Apply as follows and as recommended by manufacturer of arc-proofing tape: a. Clean cable sheath. b. Wrap metallic cable components with 10-mil (250-micron) pipe-wrapping tape. c. Smooth surface contours with electrical insulation putty. d. Apply arc-proofing tape in one half-lapped layer with coated side toward cable. e. Band arc-proofing tape with 1-inch- wide bands of half-lapped, adhesive, glass-cloth tape 2 inches o.c. 13. Seal around cables passing through fire-rated elements according to Division 7 Section "Firestopping." 14. Fault Indicators: Install fault indicators on each phase where indicated. 15-039-00 CCSNH Project # MCC15-03CM MEDIUM-VOLTAGE CABLE Page 3 of 4 Manchester Community College Advanced HVAC & Electrical Technology Building 18 May 2016 Section 26 00 00 – ADDENDUM 1 15. Ground shields of shielded cable at terminations, splices, and separable insulated connectors. Ground metal bodies of terminators, splices, cable and separable insulatedconnector fittings, and hardware according to manufacturer's written instructions. 16. Identify cables according to Division 26 Section "Electrical Identification." A. Field Quality Control 1. Testing: On installation of wires and cables and before electrical circuitry has been energized, demonstrate product capability and compliance with requirements. 2. Procedures: Perform each visual and mechanical inspection and electrical test stated in NETA ATS, Section 7.3.1. Certify compliance with test parameters. A polarization index equal to or less than 1.25 on new installations shall be considered a failure of the test. a. Correct malfunctioning conductors and cables at Project site, where possible, and retest to demonstrate compliance; otherwise, remove and replace with new units and retest. b. Submit test results immediately upon completion to the Owner and Engineer prior to energizing the circuit. c. Pending approval of the Owner, energize cable within 48 hours of acceptance test. 2. Confirm electric phasing between all existing cables, new cables and equipment with an approved electrical testing device. Phasing must be done in the presence of Owner representation before switching to the electrical grid. The contractor shall fully demonstrate all operations of the switchgear in the presence of Owner representation. 3. END OF SECTION 15-039-00 CCSNH Project # MCC15-03CM MEDIUM-VOLTAGE CABLE Page 4 of 4 5/18/16 SKC - 01 5/18/16 SKC - 02 5/18/16 SKC - 03 5/18/16 SKC - 04 5/18/16 SKC - 05 5/18/16 SKC - 06 5/18/16 SKC - 07 5/18/16 SKC - 08 5/18/16 SKC - 09 07 90 05 - SEALANT 08 43 13 - ALUM STOREFRONT FRAMING 06 10 00 - WD SHIM 07 90 05 - SEALANT & BACKER 1 03 30 00 - CONC SLAB-ON-GRADE (S) 2 REVISION TO J7/A0.5 3" = 1'-0" 4 216B 4' - 0" CLEAR 1 F5 2' - 11 3/8" 1 ADD-1 CORRIDOR 200 3 1 2 1 64 X202 S13 4 1 S27 B S23 C1 A6.3 213 7' - 6 5/8" 321A 4 C11 215A 1 ALIGN W/ FRAME 216B 11' - 2" 1' - 11 3/8" 3.4 7' - 7 3/8" ADD-1 F5 UP TO MEZZANINE G9 A5.1 VESTIBULE 214 F5 X200 1 1 1' - 1 1/2" TO F.O. STUD REVISION TO A1.1 1/8" = 1'-0" Aluminum Framing Clarifications 1 Boston | Manchester | Portland www.LBPA.com Manchester Community College PROJECT: Advanced HVAC & Electrical Technology Building PR NO: MCC15-03CM SCALE: As indicated DATE: 05/18/2016 ADD-1 SKA-001 AUTOMATIC VENT 6 FT. 2" (TYP) 20 FT. DWYER SERIES SF-100 2" FLOW INDICATOR (TYP 3) 6 FT. 2" (TYP) BLUE-WHITE MODEL F-42050LN INLINE FLOW METER HWP-5 DRAIN VALVE WITH THREADED HOSE CONNECTION (TYP) TACO 4900 VORTECH AIR SEP. TRIPLE DUTY VALVE AMTROL EX-30 EXPANSION TANK PRV 1/2" CW TO BACKFLOW PREVENTER (PLUMBING CONTRATOR SUPPLIED) 11/17/05 LAB PUMP STATION SCHEMATIC 1 SKM-01 NO SCALE 238219-02 ADDENUDM #1 - REF M902 NTS Advanced HVAC & Electrical Technology Building PUMP STATION DETAIL Project number Date Drawn by Checked by 150114.01 05/18/16 CW CW Scale SKM-01 NTS 5/16/2016 11:23:30 AM GENERAL NOTES 1. MECHANICAL WORK IS INDICATED DIAGRAMMATIC. EXACT LOCATIONS OF ALL COMPONENTS ARE TO BE DETERMINED IN THE FIELD (SPACING SUBJECT TO ARCHITECT'S REVIEW AND APPROVAL) TO AVOID CONFLICT WITH OTHER TRADES AND EXISTING SITE CONDITIONS. 2. THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THE SITE TO IDENTIFY EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT THE WORK OF THIS SECTION. REPORT IN WRITING TO THE ARCHITECT CONDITIONS WHICH MIGHT ADVERSELY AFFECT WORK. NO EXTRA PAYMENT WILL BE PROVIDED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY AN EXPERIENCED OBSERVER. 3. WORK REQUIRING INTERRUPTION OF BUILDING SERVICES SHALL BE CAREFULLY REVIEWED AND COORDINATED WITH THE OWNER TO MINIMIZE FREQUENCY AND DURATION OF SERVICE INTERRUPTIONS. 4. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION OF CEILING GRID, DIFFUSERS, AND GRILLES. 5. ALL INSTALLATIONS SHALL PERMIT AND PROVIDE ACCESSIBILITY FOR SERVICE AND REPLACEMENT OF ALL NEW EQUIPMENT AND EXISTING EQUIPMENT IMPACTED BY THIS WORK. 6. COORDINATE ALL OPENINGS IN FLOORS WITH STRUCTURAL DRAWINGS AND GENERAL CONTRACTOR. 7. COORDINATE ALL ROOF OPENINGS WITH ARCHITECT AND STRUCTURAL ENGINEER. 8. REFER TO STRUCTURAL FRAMING PLANS FOR EXACT LOCATION OF ALL ROOF MOUNTED EQUIPMENT. 9. ALL MECHANICAL EQUIPMENT, PIPING, AND DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF GOVERNING LOCAL, STATE, AND FEDERAL SEISMIC CODES. PARTICULAR ATTENTION SHALL BE MADE TO VIBRATION ISOLATION, ANCHORING, AND BALANCING REQUIREMENTS. 1 10. INSTALL SMOKE DETECTORS, FURNISHED AND WIRED BY DIVISION 26 00 00, IN DUCTS WHERE SHOWN ON DRAWINGS. 11. ALL DUCTWORK SHALL BE INSTALLED IN ACCORDANCE WITH CODES AND STANDARDS SET FORTH IN NFPA, SMACNA, AND ASHRAE FOR LOW PRESSURE DUCTWORK SYSTEMS. 12. ALL EXPOSED DUCTWORK SHALL BE PAINTED TO MATCH CEILING. REFER TO ARCHITECTURAL DRAWINGS. 13. PROVIDE MANUAL VOLUME DAMPERS AT ALL BRANCH DUCTS FOR AIR BALANCING. 14. ALL SHEET METAL PLENUMS AT OUTSIDE AIR LOUVERS SHALL BE INSULATED WITH RIGID INSULATION, AS PER SPECIFICATIONS. 15. RUN-OUTS TO RETURN AND EXHAUST REGISTERS, OR GRILLES ABOVE GYP BOARD CEILINGS, SHALL BE RIGID DUCTED. NO FLEXIBLE DUCT WORK SHALL BE ALLOWED ON RETURN OR EXHAUST REGISTERS. 16. ALL DUCTS, PIPES, AND EQUIPMENT SHALL BE INDEPENDENTLY SUPPORTED FROM THE BUILDING STRUCTURE WITH PROPER ALLOWANCES FOR CONTRACTION, EXPANSION, AND VIBRATION ELIMINATION. 17. PROVIDE 12"x10" ACCESS PANELS AT ALL BASEBOARD CONTROL VALVES. COORDINATE EXACT LOCATIONS WITH GENERAL CONTRACTOR. 18. PROVIDE COPPER 3/4" RUN-OUTS TO HOT WATER REHEAT COILS, CABINET HEATERS AND UNIT HEATERS UNLESS NOTED OTHERWISE. 19. PROVIDE SWING JOINTS AT ALL BRANCH CONNECTIONS TO HYDRONIC EQUIPMENT. 20. ROOM THERMOSTATS SHALL BE MOUNTED 4'-0" ABOVE FINISHED FLOOR UNLESS OTHERWISE SHOWN OR DIRECTED. COORDINATE LOCATIONS WITH ARCHITECTURAL WALL PROTECTIONS. 21. COORDINATE EXACT LOCATION OF UNIT HEATERS WITHIN ELECTRIC ROOMS WITH ELECTRICAL CONTRACTOR. 22. REFER TO SPECIFICATIONS FOR TYPE OF VALVE TO BE USED. VALVES ARE SHOWN ON PLANS FOR PLACEMENT ONLY. 23. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR FREE AREA REQUIRED. 24. ALL DIFFUSER, REGISTER, AND GRILLE SIZES INDICATED ON FLOOR PLANS ARE NECK SIZE REQUIRED. 25. ALL PIPING IS TO BE SLOPED A MINIMUM OF 1/4" PER HUNDRED FEET IN THE DIRECTION OF DRAINAGE. 26. NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED ON THIS PROJECT. 27. COORDINATE ENTIRE INSTALLATION WITH THE WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR INSTALLATIONS. ADDEMDUM #1; REF M000 NTS Advanced HVAC & Electrical Technology Building No. Description Reference drawing Date LEGEND REVISIONS Project number Date Drawn by Checked by 150114.01 05/18/16 CW CW SKM-02 Scale NTS STORM PIPE FIBERGLASS INSULATION TYPICAL HYDROCOIL http://www.hydrocoilpower.com/1home.html CONTACT RICH rich@hydrocoil.com REGARDING CONNECTION TO STORM PIPING. HYDROCOIL DETAIL NO SCALE 226029-01 1 Advanced HVAC & Electrical Technology Building HYDROCOIL DETAIL Project number Date Drawn by Checked by 150114.01 05/18/16 ZTR TRB Scale SKP-01 NTS 5/16/2016 10:53:32 AM 6 R4 R4 CLASSROOM 110 6 R4 R4 6 6 6 R4 R4 6 R4 PHS-700 LR1 R4 6 LC 6 R4 P201D 6 R4 6 6 P201D 8 8 P201D P201D 8 6 EBU 6 6 SCM-2000 R4 6 6 R4 6 6 1 SC5D PLC LAB 109 EX1 S2 LP411 - 8 S2 8 EBU SC5D 8 S4 S4 S4 S4 ALC 8 7 EBU ALC P161D 8 SC5D ETEC MOTORS 1 103 8 EBU 8 8 E JJ ELEV. ELEV ST EBU 7 LC TEL/DATA 113 7 OS LC 7 R4L S4 7 EBU 7 S4 7 7 7 7 R4L S4 7 EBU EBU MEN 114 7 7 S4 2B LP411 - 12 SCM-2000 F 8 CORRIDOR 100 CORRIDOR 100 8 8 MTS1 LH MT S1 EBU 8 8 EBU 8 EBU 8 8 P201D SCM-2000 OS 8 P201D 8 P201D 8 P201D 8 P201D 8 ALC V V 8 8 P41D 8 P201D OS EBU 6 P41D R4 ALC PC ALC R4 ALC R4 G FACULTY OFFICE 107 EBU 8 1 WOMEN 115 R4L R4L 7 STORAGE 116 7 7 S4 7 D 1 3 4 LOWER LEVEL LIGHTING Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-01 1/8" = 1'-0" 5/16/2016 5:02:08 PM E EBU 11 V V ALC 11 LW1 9 ALC 11 ALC V 11 11 V 11 1 V 11 ALC P41D EBU 9 PHS-700 PC V 11 11 EBU V 11 LP411 - 11 11 V 11 V 11 V 11 LW1 9 P41D 9 ALC 1 D 9 P41D 9 V 11 1 EX1 11 9 P41D V 11 P41D 9 LW1 9 9 C P41D 5 6 GROUND LEVEL LIGHTING Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-02 1/8" = 1'-0" 5/16/2016 5:02:10 PM 11 EBU 1 9 9 EBU 9 11 ALC SC5D P41D 9 P41D 9 SWM-1200 OS P41D 9 9 ALC AHU LAB 213 CORRIDOR 200 EX1 9 EBU EBU R4 1 9 9 9 R4 OS SWM-1200 B 9 OEBU 9 5 6 GROUND LEVEL LIGHTING Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-03 1/8" = 1'-0" 5/16/2016 5:02:10 PM V V 4 4 V 4 V 4 C V V 3 3 3 V V V V 4 EBU LP411 - 4 EBU V 4 3 V 4 4 SEE SHEET E601 DETAIL 6 FOR TYPICAL COMMERCIAL LAB ELARGED CEILING PLAN 1 1 EX1 1 1 BUILDING MECHANICAL ROOM 321 1 ST B 1 ST EBU 1 1 1 ST 1 ST 1 1 A PC PHS-800 4 5 UPPER LEVEL LGIHTING PLAN Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-04 1/8" = 1'-0" 5/16/2016 5:02:11 PM GROUND ROD (TYP) 1 TV CC CR 43 WP 4 4/0 BARE COPPER (TYP) D211 SP D221 P221 D211 P212 5 P412 - 19,21,23 EPO CU-1 TV FOR D211 4 1 P214 - 22,24 CCTV MD 360 P412 - 13,15,17 WP ACCU-2 P412 - 25,27,29 4 AHU-2 D TV SP 4 COMMERCIAL LAB 204 CT-1 WAP DS P412 - 14,16,18 1 1" SCHED 40 PVC FOR E-PHONE P211 - 4 WP 11 H-1 1 C TV 3 4 P211 - 3 P412 - 20,22,24 3 FOR D211 1 43 EPO CCTV MD 360 P412 42 CCTV 4 P412 - 1,3,5 SP 42 TV P213B - 52 ERU-1 1 TV 12 STAND ALONE ADA ADO 52 1 4 DR EL CR CORRIDOR 200 EPO AHU LAB 213 P412 - 2,4,6 P412 - 26,28,30 P214 - 18 5 Advanced HVAC & Electrical Technology Building 6 GROUND LEVEL POWER AND LOW VOLTAGE Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-05 1/8" = 1'-0" 5/16/2016 5:02:12 PM EPO P212 - 3 42 42 42 P213B - 41 1 FOR P411 P213B - 42 41 WAP CR SP P211 - 2 EPO TV 1 CORRIDOR 200 ATC 5 4 P213B - 52 P214 - 13 J 12 P411A - 19,21,23 B-4 P411A - 20,22,24 P411B - 7,9,11 P211 15KVA CWP-3 HWP-1 P411A - 25,27,29 J CWP-4 P214-11 41 41 P411A - 26,28,30 HWP-2 EPO CWP-1 STAND ALONE ADA ADO J HP-24 44 CCTV HWP-4 B-3 MD 360 LP411 P411A - 13,15,17 P411A P211 - 1 P411A - 7,9,11 CWP-2 TV P413 CHWP-3 CRAC-1 P411A - 14,16,18 MSB P213B CHWP-1 J HWP-3 P411A - 1,3,5 P411B - 2,4,6 P213A CHWP-4 P411A - 2,4,6 CH-1 P214 CHWP-2 LCP1 P411A - 8,10,12 4 TV CH-2 CRAC-2 45KVA P411A - 37,39,41HWP-5 MAIN ELECTRIC ROOM P411B - 8,10,12 P411A - 32,34,36 44 215 P411A - 38,40,42 225KVA 5 P213B - 44 4 GROUND BAR P211 - 5 TV ADA ADO B EL DS MAIN DIST P411B ACCU-4 1" SCHED 40 PVC CONDUIT FOR BOLLARDS P411B - 13,15,17 52 1 4/0 BARE COPPER TO COUNTERPOISE 3 Advanced HVAC & Electrical Technology Building P214 - 18 MD 360 CCTV A REFER TO DUCTBANK SECTION B-B ON 1 DRAWING E001 4 GROUND LEVEL POWER AND LOW VOLTAGE Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-06 1/8" = 1'-0" 5/16/2016 5:02:14 PM VRF CONTROLLER 50 J MEN 201 CR WOMEN 202 SP D211 P214 - 26,28 BC-1 EPO FOR D211 SP EPO J 1 D212 45KVA FOR D212 1 ETEC STORAGE 205 RESIDENTIAL LAB 211 D P212 - 17 17 J J P212 - 9 J 17 P212 - 5 P212 - 11 P212 - 6 SP REF P212 - 7 RANGE P212 - 10 J J SP P212 - 8 FURNACE SUMP PUMP WELL PUMP J ON DEMAND WATER HEATER RECIRC PUMP ON DEMAND WATER HEATER RADIANT FLOOR P212 - 14 J J COMMERCIAL LAB 204 P212 - 15 J C J 3 Advanced HVAC & Electrical Technology Building 4 GROUND LEVEL POWER AND LOW VOLTAGE Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-07 1/8" = 1'-0" 5/16/2016 5:02:16 PM P221 - 2 RESIDENTIAL LAB 311 P221 - 17 P214 - 14 17 ATC 45 REF P221 - 7 P221 - 8 J J D SP J 1 SEE SHEET E601 DETAIL 4 FOR BATHROOM LAYOUT P221 - 9 C P221 - 19 P221 - 18 18 18 19 2 C 1 SEE SHEET E601 DETAILS 1, 2, 3 AND 6 FOR TYPICAL COMMERCIAL LAB CUBICLE LAYOUT OPTIONS EPO SEE SHEET E601 DETAIL 5 FOR UTILITY/PORCH LAYOUT 1 4 Advanced HVAC & Electrical Technology Building 5 UPPER LVEL POWER AND LOW VOLTAGE Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-08 1/8" = 1'-0" 5/16/2016 5:02:17 PM 1 F E 1 1 XFMR FUSED DISCONNECT MOUNTED TO UNISTRUT D 6 ROOF POWER AND LOW VOLTAGE Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-09 1/8" = 1'-0" 5/16/2016 5:02:18 PM F 1 E 1 1 1 1 P413 - 14,16,18 60AS 60AF D 49 JJ 49 RTU-2 1 C 3 ROOF POWER AND LOW VOLTAGE Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-10 1/8" = 1'-0" 5/16/2016 5:02:18 PM B 1 1 EF-1 48 JJ 48 1 P214 - 4 M M EF-2 1 P214 - 3 A 3 4 ROOF POWER AND LOW VOLTAGE Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-11 1/8" = 1'-0" 5/16/2016 5:02:19 PM ELECTRICAL SCHEDULES Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-12 5/16/2016 5:02:19 PM SPACE SPACE FACP FIRE ALARM BEACON PENDANT LIGHT FIXTURE RECEPTACLES DOOR HOLD SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE Circuit Description *TYPICAL OF 24 PANELS CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Location: Space RR Supply From: Mounting: Surface Enclosure: Type 1 A (KVA) Trip Poles 0A 1 0 kVA 0... 0A 1 0A 1 0A 1 0 kVA 0... 0A 1 ----0 kVA 0... ------0 kVA 0... ------0 kVA 0... ------0 kVA 0... ------0 kVA 0... ----0... 0... 0... 0... 0... 0... 0... 0... 0... 0... 0... 0... 0... 0... B (KVA) 0... 0 kVA 0... 0 kVA 0... 0 kVA 0... 0 kVA 0... 0 kVA 0... 0 kVA 0... 0 kVA C (KVA) Volts: 120/208 Wye Phases: 3 Wires: 4 Branch Panel: LEARNING PANEL Poles 1 1 1 1 1 ----------------Trip 0A 0A 0A 0A 0A ----------------- Circuit Description EXIT SIGN SECURITY PANEL CONTRUCTION LIGHT AUTOMATIC TEMP CONTROL CARD READER SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE A.I.C. Rating: Mains Type: MCB Mains Rating: 100 A MCB Rating: 100 A CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 GROUND ROD 0" '20 #4/0 BARE COPPER (TYP) N* MI EXOTHERMIC WELD CONNECTION (TYP) 1#4/0 BARE TYPICAL COUNTER POISE DETAIL NO SCALE 26.8006 1 COUNTERPOISE DETAIL Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-13 N.T.S. 5/16/2016 5:02:20 PM F H V V FS TS F F S TYPICAL SPRINKLER RISER STACK DUCT SMOKE DETECTOR F S ER D CONTINUED ON SKETCH SKE-15 V S NORMAL ELECTRIC CLOSET ELEVATOR RECALL NEW FIRE ALARM TERMINAL CABINET CM CM SM DENOTES TO ADDITIONAL DEVICES (TYPICAL) TYPICAL FLOOR PS V F H V V FS TS F F S D TYPICAL SPRINKLER RISER STACK DUCT SMOKE DETECTOR F S ER S NORMAL ELECTRIC CLOSET ELEVATOR RECALL DENOTES TO ADDITIONAL DEVICES (TYPICAL) NEW FIRE ALARM CONTROL PANEL MCC CAMPUS FIRE ALARM CONNECTION GROUND LEVEL 1 CONTINUED ON SKETCH SKE-15 1 CM CM SM PS MUNICIPAL FIRE ALARM CONNECTION FIRE ALARM RISER DIAGRAM SCALE: N.T.S. FIRE ALARM RISER DIAGRAM Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-14 N.T.S. 5/16/2016 5:02:20 PM CONTINUED ON SKETCH SKE-14 F F S F S ER S V V V TS FS H F D NORMAL ELECTRIC CLOSET TYPICAL SPRINKLER RISER STACK DUCT SMOKE DETECTOR DENOTES TO ADDITIONAL DEVICES (TYPICAL) ELEVATOR RECALL CONTINUED ON SKETCH SKE-14 TYPICAL FLOOR F S F S ER F S V V TS FS 1 V H F D NORMAL ELECTRIC CLOSET ELEVATOR RECALL TYPICAL SPRINKLER RISER STACK DUCT SMOKE DETECTOR DENOTES TO ADDITIONAL DEVICES (TYPICAL) GROUND LEVEL 1 FIRE ALARM RISER DIAGRAM SCALE: N.T.S. FIRE ALARM RISER DIAGRAM Advanced HVAC & Electrical Technology Building Project number Date Drawn by Checked by 150114.01 05/18/16 RJG ASK Scale SKE-15 N.T.S. 5/16/2016 5:02:20 PM POWER KEYED NOTES POWER PLAN NOTES 1. CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO ROUGH IN. 1 2. CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY. EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND SHALL BE NOTED ON THE CONTRACTORS AS-BUILT DRAWINGS. 2 3. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND OPTIONS. 4. Boston | Manchester | Portland www.LBPA.com NOT USED. PROVIDE 2#12,1#12G IN 1" CONDUIT TO 20A CIRCUIT BREAKER IN PANEL P214, CIRCUIT #30 FOR EMERGENCY BLUE LIGHT PHONE. CONDUIT SHALL BE ROUTED THROUGH BUILDING AND TRANSITION TO DIRECT BURIED (SCHEDULE 40) CONDUIT OUTSIDE OF BUILDING. COORDINATE EXACT REQUIREMENTS WITH ARCHITECT AND CAMPUS SECURITY. PROVIDE 1" CONDUIT WITH PULL STRING FOR DATA WIRE. 1 OIL CURB REFER TO NOTE 11 2/0 BARE COPPER TO COUNTERPOISE 1 83" COORDINATE EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION DRAWINGS. 1'-0" 1'-0" 10 " CONCRETE SLAB WITH 3/4" CONTINUOUS CHAMFER A 3'-0" GROUND PIGTAIL (MINIMUM) S G G 10 CONDUITS MAXIMUM D G 22 8 G 1'-0" 22 8 GH SI T SEE DETAIL (4) 4" (2 ACTIVE, 2 SPARE) GALVANIZED STEEL 36" RADIUS 90° SWEEP (TYPICAL) CONDUIT L MH D 0 23 D 230 IN E OF D S (6) EXISTING 5" SCHEDULE 40 PVC CONDUIT UNDERNEATH ROADWAY 3'-0" GROUND PIGTAIL (MINIMUM) 1" CONDUIT, COORDINATE EXACT REQUIREMENTS WITH CAMPUS SECURITY 22 8 1-1/4"C. FOR PAD MOUNTED METERING. TO TELCO GROUND IF AVAILABLE 82" B 1 UGE &C 'C-C' E001 NEW XFMR, REFER TO DETAIL ON THIS SHEET S UGE &C B INE AS L 4" G TING EXIS B OH W T UGE&C E RD RD 'A-A' E001 2 S WS 1 O V S S S H Y D S O UGF VC 5 P DR3 8" S P IP E S S S D 6" PLAN VIEW EXISTING PARKING LOT D D D EXISTING LIGHT POLE GROUND WIRE (TYPICAL) VISE TYPE CONNECTOR (TYPICAL) GROUND PAD, SEE DETAIL (TYPICAL) D CUTTING OF EXISTING HAND G HOLE WILL BE REQUIRED FOR CONNECTION TO DUCT BANK 'B-B' ON THIS SHEET S G E IMAT ROX ARE APP P " S 2-2 UITS D CON 'B-B' E001 G APPROXIMATE LOCATION OF EXISTING HANDHOLE. FIELD VERIFY EXACT LOCATION. SPLICE NEW AND EXISTING 1 CABLES; CORECBAS NECESSARY 7.6 6 =22 4 .5 FOR USE OFRINIMVDUCT BANK 'C-C'. 2 2 .=2 C 3/4" DIAMETER X 8' GALVANIZED STEEL GROUND ROD WITH GROUND CLAMP, REFER TO DETAIL. (TYPICAL FOR 2) APPROXIMATE LOCATION OF EXISTING HANDHOLE. FIELD VERIFY EXACT LOCATION D 23 0 OX R B AKE BRE H O UGF 4 TING EX IS ED 1 POS PRO SS 3 LO T 0 NE GAIN NET GROUND ROD SPACED 20' APART (TYP) G UGE UGE EO C 1/0 AWG COPPER S D T/ UG Y D D LINE TION ATER NSTRUC E W O IMAT ER C ROX UND AP P LY T REN CUR 2/0 19 STRAND BARE SOFT DRAWN COPPER GROUND GRID 1'-9" BELOW GRADE UG T/ D 16 1'-0" 30" VA N UG E OHW TB M 6 TING EX IS ED 2 POS 4 PRO S LO S 0 NET GAIN NET UGE&C W OOHF O HW UGE 25" E P I OH W IC SERV GAS UGE&C E /D UG T 8" EXISTING LIGHT POLE UGE&C T GH SI EXISTING LIGHT POLE ACCESS 1'-0" 1'-0" OF GAS R E MET P" BUM ED- 8" FRONT EMERGENCY BLUE LIGHT PHONE E LIN "SPE SECONDARY KNOCKOUT PRIMARY KNOCKO UT EXISTING LIGHT POLE G LL .4 0 DWA HEA =217 OUT INV. EO P 1 23 0 15" 1'-0" 10 " CONCRETE SLAB WITH 3/4" CONTINUOUS CHAMFER D 6" D GROUND CLAMP (TYPICAL) 1" D 10" S D W Y D UGFO LINE S ATER E W IMAT ROX AP P H D W 24" S D D CP W 1 12" EXISTING DUCTBANK WITH SPARE CONDUITS. ADDITIONAL DUCT BANK MAY BE REQUIRED. S D W COMPOSITE BASE SILTY SAND MIX 2" D W D COPPER GROUND GRID 1'-0" BELOW GRADE (TYPICAL) UGFO G D (4) 4" (2 ACTIVE, 2 SPARE) GALVANIZED STEEL 36" RADIUS 90° SWEEP (TYPICAL) CONDUIT GEOTEXTILE FABRIC S TRANSFORMER PAD DETAIL NOTES 1, PRIMARY GRAVEL SECONDARY SECTION VIEW INSTALL CONDUITS AS SHOWN PLANS AND DUCT BANK DETAILS, BEFORE SLAB IS POURED. USE 36" RADIUS BEND, GALVANIZED STEEL RIGID STEEL CONDUIT SWEEPS AND RISER, WITH COUPLINGS, NIPPLES AND BUSHINGS AS REQUIRED. BENDS FOR PRIMARY CABLES SHALL BE GALVANIZED STEEL. TERMINATIONS AND BUSHINGS SHALL BE INSTALLED AFTER THE TRANSFORMER IS PLACED, AND BEFORE THE CABLES ARE PULLED. "C" TYPE COMPRESSI ON CONNECTO R W G 19 CB 3 227 .2 RIM= 2 1.11 2 N=2 2 INV.I 221.0 = T U INV.O S D EXISTING DUCTBANK WITH SPARE CONDUIT. PROVIDE NEW FIBER OPTIC CABLE D 12 "D I I 12"D D 18 CB 7 226.1 2 RIM= 21.9 2 = N INV.I 1.87 2 2 UT= INV.O D D G G GRAVEL AND SAND SHALL BE PLACED AS SHOWN IN DETAIL. THE GRAVEL, BEING THOROUGHLY COMPACTED, AND THE SAND THOROUGHLY WETTED, JUST BEFORE PLACING THE CONCRETE. 4. CONCRETE TO HAVE A MINIMUM STRENGTH OF 5000 PSI AFTER 28 DAYS. AIR ENTRAINMENT TO BE 6% +/- 1%. ALL EXPOSED EDGES TO HAVE A 3/4" CHAMFER. MATERIALS AND WORKMANSHIP SHALL CONFORM TO ACI-318. 5. REINFORCING RODS TO BE #5 AT 10" ON CENTER, TOP AND BOTTOM EACH WAY, GRADE 60 AND SHALL CONFORM TO ASTM. STANDARD A-615 OF LATEST DATA. REINFORCING RODS TO BE LOCATED A MINIMUM OF 2" CLEARANCE FROM FACE OF CONCRETE. 6. ALL OPENINGS SHALL HAVE ADDITIONAL REBAR REINFORCEMENT OF 1 #5 EACH CORNER, MID- DEPTH. 7. LIFTING ANCHORS SHALL BE INSTALLED WITH APPROPRIATE DAYTON LIFTING ANCHORS OR EQUIVALENT. 8. UPON COMPLETION OF THE SLAB, AND THE INSTALLATION OF CONDUIT, FILL THE OPEN AREA AROUND THE CONDUITS WITH EXPANDING FOAM, CONCRETE AND GROUT AROUND THE CONDUIT TO SEAL THIS AREA. 9. TRANSFORMER TO BE FURNISHED AND INSTALLED BY THE UTILITY COMPANY. 10. INSTALLATION OF CONDUITS AND GROUND GRID BY THE ELECTRICAL CONTRACTOR. CONCRETE, GRAVEL AND SAND INSTALLATION TO BE BY THE GENERAL CONTRACTOR. 11. VERIFY OIL CURB AND BOLLARD REQUIREMENTS WITH THE UTILITY COMPANY PRIOR TO CONSTRUCTION OF TRANSFORMER PAD 12. BOLLARDS SHALL BE PROVIDED PER UTILITY COMPANY REQUIREMENTS. D D D D D TO EXISTING IT ROOM IN ROOM 224 S G D D 1 P30 9 CB 240.1 RIM= 35.2± 2 .= V IN 232.6 = P SUM D D D 1 E001 1066 Front Street, Manchester, New Hampshire, 03102 3. G D W D 12"SDR 35 PVC D LINE GROUND CLAMP #2/0 19 STRAND BARE SOFT DRAWN COPPER (TYPICAL) 3/4" DIAMETER X 8' GALVANIZED STEEL GROUND ROD F NO. 1 4 E001 ADDENDUM 1 DATE 05/18/2016 CONNECTION & GROUNDING DETAILS G THREE PHASE TRANSFORMER (15KV PRIMARY, 750-2500KVA) PAD DETAIL (BASED ON NATIONAL GRID) WITH OIL CONTAINMENT CURB ELECTRICAL SITE PLAN 1" = 40'-0" DESCRIPTION N S S 11 3 CB 2 34.5 RIM= 27.59 2 INV.= 12 CB 2 232.8 RIM= 27.2 2 2 .= V IN APPROXIMATE LOCATION OF EXISTING HANDHOLE. FIELD VERIFY EXACT LOCATION. E GROUND CLAMP 12" S G S INSTALL #2/0 19 STRAND BARE SOFT DRAWN COPPER WIRE LOOP 12" BELOW GRADE. BOND TO ALL EXPOSED METALLIC CONDUIT AND LEAVE 3'-0" OF WIRE ABOVE PAD FOR GROUNDING TRANSFORMER AT TWO OPPOSITE POINTS IN THE CABLE CONDUIT OPENINGS. INSTALL TWO 8" COPPERWELD (3/4") GROUND RODS AND APPROVED CONNECTORS BELOW GROUND. LEAVE GROUND GRID EXPOSED UNTIL INSPECTED BY THE UTILITY COMPANY. CONNECTIONS TO GROUND GRID TO BE MADE AS FOUND IN DETAILS, EXCEPT THAT EXOTHERMIC WELDING ("CADDWELD") SHALL BE AN ACCEPTABLE ALTERNATE TO COMPRESSION BOLTED CONNECTIONS. Advanced HVAC & Electrical Technology Building SEE DETAIL 12" G 2. ATER E W IMAT ROX AP P Lavallee|Brensinger Architects G D 12"R D D D D SAND FINISHED GRADE D S 1 1/2" CRUSHED ROCK,18" DEPTH 26.0013 NONE TRANSFORMER PAD DETAIL 12" = 1'-0" H FINISHED GRADE/PAVEMENT C:\2015 Revit\150114 - MCCNH Lab Building - Local (v2015) - TXP.rvt PROVIDE #4 REBAR IF DUCTBANK IS LOCATED UNDER ROADWAY M 12" RED (PER SHOP DRAWINGS) WARNING TAPE SHALL RUN THE LENGTH OF DUCTBANK, LOCATED 12"B.F.G. (TYPICAL) P 1 30" MIN COMPACT NATIVE BACKFILL VOID OF OBJECTS OVER TWO INCHES IN DIAMETER AND VOID OF DECOMPOSED MATERIAL. 6" MIN P P P P P SP CONCRETE ENCASEMENT SHALL BE 3 INCHES MINIMUM ALL AROUND CONDUITS UNDISTURBED EARTH OR COMPACTED FILL 7.5" 7.5" 7.5" 37.5" 7.5" FA 4" PVC POWER T CONDUIT FOR PRIMARY FEEDERS 4" PVC POWER SP CONDUIT FOR SECONDARY FEEDERS 2" PVC CONDUIT FOR OUTGOING TELEPHONE SERVICE 2" PVC CONDUIT FOR INCOMING FIRE ALARM SERVICE 4" POWER EMERGENCY FEEDERS 2" PVC CONDUIT FOR C GENERATOR CONTROL WIRING CONDUIT NOTES: E FO 4" SPARE WITH PULLSTRING 2. 4" PVC CONDUIT FOR OUTGOING FIBER OPTIC 1. THE RACEWAY PROVIDED FOR THE SECONDARY FEEDERS BETWEEN THE MAIN BUILDING TRANSFORMER AND THE SWITCHBOARD SHALL BE AS RIGID STEEL ELBOWS WITH ONLY STRAIGHT PORTIONS OF UNDERSLAB RACEWAY ALLOWED TO BE PVC RACEWAY. 2. IT IS ASSUMED PRIMARY CABLES CONSIST OF 4#1 MEDIUM VOLTAGE CABLES. ELECTRICAL CONTRACTOR MUST CONFIRM PRIMARY FEEDER GAUGE. PLASTIC SPACERS 1 1 1. 5/16/2016 5:04:26 PM 26.0028 2 3 6. 7 NONE 4 5 30" MIN 6" MIN BACKFILL MAY BE MADE WITH EXCAVATED MATERIAL OR COMPARABLE, UNLESS MATERIAL IS DEEMED UNSUITABLE BY ENGINEER. BACKFILL SHALL BE FREE OF FROZEN LUMPS, ROCKS, DEBRIS AND RUBBISH. ORGANIC MATERIAL SHALL NOT BE USED AS BACKFILL. BACKFILL SHALL BE 6-INCH LAYER AND THOROUGHLY COMPACTED. 4. A SUITABLE PULLING STRING, CAPABLE OF 200 POUNDS OF PULL, MUST BE INSTALLED IN THE CONDUIT BEFORE UTILITY COMPANY IS NOTIFIED TO INSTALL CABLE. THE STRING SHOULD BE BLOWN INTO THE CONDUIT AFTER THE RUN IS ASSEMBLED TO AVOID BONDING THE STRING TO THE CONDUIT. 5. UTILITY COMPANY MUST BE GIVEN THE OPPORTUNITY TO INSPECT THE CONDUIT PRIOR TO BACKFILL. THE CONTRACTOR IS RESPONSIBLE FOR ALL REPAIRS SHOULD UTILITY COMPANY BE UNABLE TO INSTALL ITS CABLE IN A SUITABLE MANNER. 8. 1 ALL 90 DEGREE SWEEPS WILL BE MADE WITH RIGID GALVANIZED STEEL WITH A MINIMUM RADIUS OF 36 INCHES FOR PRIMARY AND 24 INCHES FOR SECONDARY CABLES. 12" RED (PER SHOP DRAWINGS) WARNING TAPE SHALL RUN THE LENGTH OF DUCTBANK, LOCATED 12"B.F.G. (TYPICAL) 3. SEE RISER DIAGRAM FOR CABLE TRAY REQUIREMENTS CONCRETE ENCASED POWER DUCTBANK SECTION "A-A" (6) 4" CONDUITS ALL CONDUIT IS TO BE SCHEDULE 40 PVC, ELECTRICAL GRADE, GRAY IN COLOR AND INSTALLED PER MANUFACTURER'S RECOMMENDATIONS. A 10 FOOT HORIZONTAL SECTION OF RIGID STEEL CONDUIT WILL BE REQUIRED AT EACH SWEEP. ALL JOINTS ARE TO BE WATERTIGHT. FINISHED GRADE/PAVEMENT PROVIDE #4 REBAR IF DUCTBANK IS LOCATED UNDER ROADWAY ALL CONDUIT INSTALLATIONS MUST CONFORM TO THE CURRENT EDITION OF THE NATIONAL ELECTRIC SAFETY CODE, STATE AND LOCAL CODES AND ORDINANCES, AND WHERE APPLICABLE, THE NATIONAL ELECTRIC CODE. FA FA T SP FO FINISHED GRADE/PAVEMENT PROVIDE #4 REBAR IF DUCTBANK IS LOCATED UNDER ROADWAY CONTENT: 12" RED (PER SHOP DRAWINGS) WARNING TAPE SHALL RUN THE LENGTH OF DUCTBANK, LOCATED 12"B.F.G. (TYPICAL) 30" MIN COMPACT NATIVE BACKFILL VOID OF OBJECTS OVER TWO INCHES IN DIAMETER AND VOID OF DECOMPOSED MATERIAL. 6" MIN M COMPACT NATIVE BACKFILL VOID OF OBJECTS OVER TWO INCHES IN DIAMETER AND VOID OF DECOMPOSED MATERIAL. SP 6" CLEAN SAND SP I 6" CLEAN SAND UNDISTURBED EARTH OR COMPACTED FILL UNDISTURBED EARTH OR COMPACTED FILL 7.5" 7.5" 7.5" 37.5" 7.5" PLASTIC SPACERS 7.5" 7.5" 22.5" 7.5" PLASTIC SPACERS 26.0028 POWER DUCTBANK SECTION "C-C" NONE POWER DUCTBANK SECTION "B-B" 40' 26.0028 20' 1 0 GRAPHIC SCALE 40' 80' NONE THE EMPTY POSITION IN THE COMBINATION POWER-TELE/DATA DUCTBANK SHALL REMAIN EMPTY TO ENSURE SEPARATION BETWEEN POWER AND TELE/DATA CONDUITS SCALE: 1" = 40' - 0" DUCTBANK WILL BE PITCHED AND RUN DEEP BELOW FINISHED GRADE FROM THE MANHOLE TO THE TRANSFORMER PAD. 6 7 120' J 8 9 10 11 12 13 14 FOR ADDITIONAL INFORMATION, REFER TO PROJECT MANUAL. DUCTBANK INSTALLATION NOTES CONDUIT DENOTATIONS: ELECTRICAL SITE PLAN DRAWN BY: RJG PROJECT NO: 150114.01 DATE: 04/22/16 REVISED: SCALE: 1"=40'-0" E001 Project Phase BIDDING DOCUMENTS BY LAVALLEE/BRENSINGER PROFESSIONAL ASSOCIATION. ALL RIGHTS RESERVED. NO REPRODUCTION WITHOUT PERMISSION. 200AS 125AF RTU-1 200AS 125AF 200AS 125AF 75KVA XFMR Boston | Manchester | Portland www.LBPA.com 75KVA XFMR ROOF DRY TYPE TRANSFORMER SCHEDULE 8 D222 150A MCB 120/208 T4 30 T3 KVA P221 100A MCB 120/208 D221 250A MCB 120/208 1 9 20 60AS 50AF 1 2ND FLOOR MAIN SWITCHBOARD "MSB" 2,000 AMP 480/277 VOLT M 3 PHASE 4 WIRE SPACE DMU 480-120V 1600A 3P TO ETHERNET CONNECTION 125A 3P 50A 3P 125A 3P 125A 3P 350A 3P 50A 3P 800A 3P 1 30A 3P SPD 125A 3P 60A 3P 125A 3P 200A 3P 200A 3P 150A 3P SPACE 1 9 G GROUND BUS 400AS 350AF 60AS 50AF T3 1 30 PAD MOUNTED TRANSFORMER 11 1 N NEUTRAL BUS P211 60A MCB 120/208 208 VOLT (4) OVERCURRENT 480V FEEDER (3 PHASE, 3 WIRE, WITH GROUND) 120/208V FEEDER (3 PHASE, 4 WIRE, WITH GROUND) GROUNDING (5) 15A-3P 30A-3P 3#12 & 1#12G.-3/4"C. 4#10 & 1#8G.-3/4"C. 1#8 - 3/4"C 42 30A-3P 60A-3P 3#10 & 1#10G.-3/4"C. 4#4 & 1#8G.-1-1/4"C. 1#8 - 3/4"C 36 83 50A-3P 100A-3P 3#6 & 1#10G.-3/4"C. 4#1 & 1#6G.-1 1/2"C. 1#6 - 3/4"C 45 54 125 70A-3P 150A-3P 3#4 & 1#8G.-1"C. 4#1/0 & 1#6G.-2"C. 1#6 - 3/4"C T5 75 90 208 125A-3P 250A-3P 3#1 & 1#6G.-1-1/4"C. 4#250 KCMIL & 1#2G.-2-1/2"C. 1#2 - 3/4"C T6 112.5 135 313 200A-3P 400A-3P 3#3/0 & 1#6G.-2"C. 4#600 KCMIL & 1#1/0G.-3-1/2"C. 1#1/0 - 3/4"C. T7 150 181 417 250A-3P 500A-3P 3#250 KCMIL & 1#4G.-2-1/2"C. 8#250 KCMIL & 2#1/0G. (2)-2-1/2"C. 1#2 - 3/4"C T8 225 270 625 350A-3P 800A-3P 3#500 KCMIL & 1#3G.-2 1/2"C. 8#600 KCMIL & 2#3/0G. (2)-3-1/2"C. 1#1/0 - 3/4"C T9 300 361 834 500A-3P 1000A-3P 6#250 KCMIL & 2#1G. (2)-2-1/2"C. 12#400 KCMIL & 3#3/0G. (3)-3"C. 1#1/0 - 3/4"C T10 500 600 1400 800A-3P 1600A-3P 6#600 KCMIL & 2#1/0G. (2)-3"C. 16#600 KCMIL & 4#300 KCMIL G. (4)-3-1/2"C. 1#3/0 -3/4"C. KVA T1 9 11 25 T2 15 18 T3 30 T4 P411B P411A 800A 800A MLO MCB 277/480 277/480 T2 15 KVA 225 KVA 30 KVA 200AS 150AF 75 KVA T5 8 P212 100A MCB 120/208 16 P213B P213A 800A 800A MLO MCB 120/208 120/208 D212 150A MCB 120/208 CH-2 1 T8 LP411 60A MCB 277/480 P214 250A MCB 120/208 P413 400A MCB 277/480 BOND AND GROUND TRANSFORMER PER NEC ARTICLE 250.30. 2. CONNECT TRANSFORMER GROUNDING ELECTRODE CONDUCTOR TO NEAREST GROUNDING ELECTRODE (BUILDING STEEL, GROUND ROD, OR METAL WATER PIPE). 3. ALL CONDUCTOR SIZES ARE FOR COPPER CONDUCTORS NEC TABLE 310.15.(B).(16)(2014); 60-DEGREE C UP TO 100A; 75 DEGREE C OVER 100A. 4. SECONDARY OVERCURRENT PROTECTION SHALL BE LOCATED WITHIN TEN (10) FEET OF THE TRANSFORMER SECONDARY TERMINALS EITHER IN A PANELBOARD (MAIN BREAKER) OR A INDIVIDUALLY MOUNTED CIRCUIT BREAKER. 5. TRANSFORMER BONDING JUMPER AND GROUNDING ELECTRODE CONDUCTOR PER TABLE 250.66. 6. 600KCMIL CONDUCTORS AND LARGER SHALL BE PROVIDED WITH MAC ADAPTERS AS REQUIRED TO COORDINATE WITH BREAKER LUG SIZES. 7. CONDUIT SIZES ARE FOR COPPER CONDUCTORS WITH THWN-2 INSULATION IN EMT PER NEC TABLE C1 IN ANNEX C. CH-1 1 200AS 125AF 1. MCC CAMPUS DISTRIBUTION LOOP 200AS 125AF 16 CIRCUIT BREAKER 1 CONDUCTORS C D211 250A MCB 120/208 P412 350A MCB 277/480 120 VOLT & 277 VOLT 1PH, 2W. CIRCUITS 30A-1P 2#10 & 1#10G - 3/4"C. 40A-1P 2#8 & 1#10G - 3/4"C. 50A-1P 2#6 & 1#10G - 3/4"C. 60A-1P 2#4 & 1#10G - 3/4"C. 208 VOLT & 480 VOLT 1PH, 2W. CIRCUITS (5) SETS OF (4#500KCMIL FEEDERS) IN 4" CONDUIT. PROVIDE (1) ADDITIONAL CONDUIT WITH PULL STRING AS SPARE. 1 1 BRANCH CIRCUIT SIZE NOTES: 1. ALL CONDUCTOR SIZES ARE FOR COPPER CONDUCTORS NEC TABLE 310.15.(B).(16) (2011); 60-DEGREE C UP TO 100A; 75 DEGREE C OVER 100A. 2. CONDUIT SIZES ARE FOR COPPER CONDUCTORS WITH THWN-2 INSULATION IN EMT PER NEC TABLE C1 IN ANNEX C. LOWER FLOOR E400 B BRANCH CIRCUIT SCHEDULE GROUND FLOOR MH A TRANSFORMER NOTES: 100% RATED MAIN CIRCUIT BREAKER REFER TO COUNTERPOISE DETAIL ON DRAWING E600 PRIMARY SECONDARY 480 VOLT AMPS AMPS OVERCURRENT SIZE 3. CONDUIT AND CABLE SIZES SHALL BE PER TABLE ABOVE, UNLESS NOTED OTHERWISE ON THE FLOOR PLANS AND DRAWINGS. 4. SEE SPECIFICATIONS FOR ACCEPTABLE CONDUCTOR TYPES. 20A-2P/2W 2#12 & 1#12G - 3/4"C. 30A-2P/2W 2#10 & 1#10G - 3/4"C. 40A-2P/2W 2#8 & 1#10G - 3/4"C. 50A-2P/2W 2#6 & 1#10G - 3/4"C. 60A-2P/2W 2#4 & 1#10G - 3/4"C. D Lavallee|Brensinger Architects 208 VOLT & 480 VOLT 3PH, 3W. CIRCUITS 20A-3P/3W 3#12 & 1#12G - 3/4"C. 30A-3P/3W 3#10 & 1#10G - 3/4"C. 40A-3P/3W 3#8 & 1#10G - 3/4"C. 50A-3P/3W 3#6 & 1#10G - 3/4"C. 60A-3P/3W 3#4 & 1#10G - 3/4"C. Advanced HVAC & Electrical Technology Building E RISER DIAGRAM 12" = 1'-0" COPPER FEEDER SCHEDULE FEEDER SYMBOL TO ADDITIONAL ECUs (AS NEEDED) 1 CONDUCTORS (3-PHASE, 3-WIRE) WITH GROUND RACEWAY SIZE CONDUIT ENCELIUM GREENBUS CHANNELS 8 PER ECU/MAX 100 NODES EACH (TYP) TYPICAL GREENBUS LAYOUT WALL MOUNT DIMMING ZONE CONTROLLER (TYP.) WALL MOUNT 3-ZONE CONTROLLER (TYP.) 3 5 CAT 5 ALC G4 ECU #1 No use r ser vicea ble p arts inside . Con tact OSRAM for servic e. PSU EXTERNAL POWER SUPPLY 100-240VAC/50-60Hz/1.8A CH 8 CH 7 CH 6 24V DC Output CH 5 FIXTURE (TYP.) Do Not D iscon nect From Power CH 4 GreenBus II CH 3 CH 2 CH 1 24V DC Input USB 2.0 ALC Ethernet 10/100BaseTx Class 2 SC3D PCDM PS PHOTO SENSOR (TYP.) ZC3 OCCUPANCY SENSOR (TYP.) 9 AREA LIGHTING CONTROLLER (ALC) DIMMED/SWITCHED ZONE (TYP.) 11 INCANDESCENT FIXTURES OR LED LINE VOLTAGE DIMMING (TYP.) 3#1 & 1#8G. 3#1 & 1#6G. 3#1/0 & 1#6G. PHASE CUT DIMMING MODULE (TYP.) 15 SSU 3#2/0 & 1#6G. 17 3#3/0 & 1#6G. 19 TYPICAL ENCELIUM BLOCK RISER * A SINGLE ECU, USE CROSSOVER CABLE TO SSU PORT 2 3#4/0 & 1#4G. 3#250 KCMIL & 1#4G. 23 3#350 KCMIL & 1#4G. 3#500 KCMIL & 1#3G. 25 ENCELIUM GREENBUS CHANNELS 6 PER ECU/MAX 75 NODES EACH (TYP) UP TO 100 NODES 26 (DEVICE DEPENDANT) 27 3#600 KCMIL & 1#3G. 6#250 KCMIL & 2#2G. LUMINAIRE CONTROL MODULE (LCM) PSU EXTERNAL POWER SUPPLY 100-240VAC/50-60Hz/1.8A CH 8 CH 7 CH 6 24V DC Output CH 5 Do Not D iscon nect From Power CH 4 GreenBus II CH 3 CH 2 CH 1 24V DC Input USB 2.0 Ethernet 10/100BaseTx CONTROL LINES 20AMP LOAD CONTROL LINES C:\2015 Revit\150114 - MCCNH Lab Building - Local (v2015) - TXP.rvt 4#2/0 & 1#6G. 2" 4#3/0 & 1#6G. 2" 4#4/0 & 1#4G. 2 1/2" 4#250 KCMIL & 1#4G. 2-1/2" 4#350 KCMIL & 1#4G. 3" 4#500 KCMIL & 1#3G. 4" 4#600 KCMIL & 1#3G. 4" 8#250 KCMIL & 2#2G. (2)2-1/2" 175 200 G 225 250 300 350 4" 400 (2)2-1/2" 500 H (2)3" 30 LINEVOLTAGE (SUPPLIED TO FIXTURE) MAX: 300W @ 120-347V SENSOR INPUT MODULE (SIM) Scene 2 ALC TO SECURE LAN PORT FOR CUSTOMER/CLIENT LIGHTING CONTROL ACCESS * REQUIRES STATIC IP ADDRESS * REQUIRES USB PORT TO NETWORK ADAPTOR LINEVOLTAGE (SUPPLIED TO FIXTURE) MAX: 300W @ 120-347V PHASE CUT DIMMING MODULE (PCDM) (TYP.) Scene 3 31 33 LOW VOLTAGE WALL STATIONS (TYP.) 0-10V DIMMING BALLAST OCCUPANCY SENSOR (TYP.) LINEVOLTAGE (SUPPLIED TO FIXTURE) MAX: 450W @ 120V MAX: 277W @ 277V 0-10V DIMMING BALLAST 8#350 KCMIL & 2#1G. (2)3" 12#300 KCMIL & 3#1/0G. (3)3" 12#400 KCMIL & 3#2/0G. (3)3" 12#600 KCMIL & 3#3/0G. (3)4" 16#600 KCMIL & 4#4/0G. (4)4" 600 CONTENT: 35 PHOTO SENSOR (TYP.) (PORTS IN FRONT) 9#400 KCMIL & 3#2/0G. 9#600 KCMIL & 3#3/0G. 37 12#600 KCMIL & 4#4/0G. 38 800 (3)3" 1000 (3)4" 36 ALC CAN SUPPORT UP TO THIRTY-TWO (32) BALLASTS CONNECTED IN PARALLEL. INCANDESCENT OPTIONAL: MAXIMUM TWO (2) BALLASTS CONNECTED IN PARALLEL. FIXTURES OR LED LINE VOLTAGE DIMMING (TYP.) AREA LIGHTING CONTROLLER (ALC) ETHERNET SWITCH (3)3" 34 0-10V DIMMING BALLAST SSU 9#300 KCMIL & 3#1/0G. 32 0-10V DIMMING BALLAST 120 VAC/60Hz/10W NON-EMERGENCY CIRCUIT 2" Scene 1 Class 2 120 VAC/60 Hz/200W NON-EMERGENCY CIRCUIT 120 VAC/60 Hz/300W EMERGENCY CIRCUIT (PREFERRED) NON-EMERGENCY CIRCUIT ACCEPTABLE 6#350 KCMIL & 2#1G. 1200 (4)4" 1600 FEEDER SIZE NOTES: LUMINAIRE CONTROL MODULE (LCM, TYP.) * A SINGLE ECU, USE CROSSOVER CABLE TO SSU PORT 2 1. ALL CONDUCTOR SIZES ARE FOR COPPER CONDUCTORS NEC TABLE 310.15.(B).(16)(2011); 60-DEGREE C UP TO 100A; 75 DEGREE C OVER 100A. 2. CONDUIT SIZES ARE FOR COPPER CONDUCTORS WITH THWN-2 INSULATION IN EMT PER NEC TABLE C1 IN ANNEX C. 3. 600KCMIL FEEDERS SHALL BE PROVIDED WITH MAC ADAPTERS AS REQUIRED TO COORDINATE WITH BREAKER LUG SIZES. 4. SEE SPECIFICATIONS FOR ACCEPTABLE CONDUCTOR TYPES. I TYPICAL ENCELIUM WIRING RISER GRAPHIC SCALE 5/16/2016 5:04:28 PM 8' 2 E400 4' ENCELIUM RISER DIAGRAM 12" = 1'-0" 0 8' 16' 24' SCALE: 1/8" = 1' - 0" J 1 2 3 4 5 6 7 8 9 10 11 05/18/2016 150 4#1/0 & 1#6G. 12 13 14 FOR ADDITIONAL INFORMATION, REFER TO PROJECT MANUAL. CAT 5 No use r ser vicea ble p arts inside . Con tact OSRAM for servic e. 29 AREA LIGHTING CONTROLLER (ALC) ADDENDUM 1 DATE 4" 28 G4 ECU #1 1 125 DESCRIPTION 3" 24 TYP. ENCELIUM WIRING RISER (GB2) 1-1/2" NO. 2 1/2" 22 TO ADDITIONAL ECUs (AS NEEDED) 4#1 & 1#6G. 100 2 1/2" 20 21 1 1/2" F 2" 18 (PORTS IN FRONT) 120 VAC/60Hz/10W NON-EMERGENCY CIRCUIT 4#1 & 1#8G. 90 2" 16 CAT 5 ETHERNET SWITCH 1 1/2" 2" 14 120 VAC/60 Hz/300W EMERGENCY CIRCUIT (PREFERRED) NON-EMERGENCY CIRCUIT ACCEPTABLE 4#2 & 1#8G. 1 1/2" 12 13 1 1/4" 1 1/2" 10 AREA LIGHTING CONTROLLER (ALC) SWITCHED ZONE (TYP.) 4#3 & 1#8G. 80 1 1/4" 3#2 & 1#8G. 8 CAT 5 120 VAC/60 Hz/200W NON-EMERGENCY CIRCUIT TO SECURE LAN PORT FOR CUSTOMER/CLIENT LIGHTING CONTROL ACCESS * REQUIRES STATIC IP ADDRESS * REQUIRES USB PORT TO NETWORK ADAPTOR 7 1066 Front Street, Manchester, New Hampshire, 03102 1 1/4" 3#3 & 1#8G. 6 (DEVICE DEPENDANT) NOMINAL AMPERE RATING 70 1 1/4" 4#4 & 1#8G. 4 UP TO 100 NODES RACEWAY SIZE CONDUIT 1 1/4" 3#4 & 1#8G. 2 PHASE CUT DIMMING MODULE (PCDM) (TYP.) CONDUCTORS (3-PHASE, 4-WIRE) WITH GROUND N TYP. ENCELIUM COMPONENT RISER SHOWING G4 ECU ELECTRICAL POWER RISER DIAGRAM DRAWN BY: RJG PROJECT NO: 150114.01 DATE: 04/22/16 REVISED: SCALE: 1/8" = 1'-0" E400 Project Phase BIDDING DOCUMENTS BY LAVALLEE/BRENSINGER PROFESSIONAL ASSOCIATION. ALL RIGHTS RESERVED. NO REPRODUCTION WITHOUT PERMISSION.