SES ONE-LINE DIAGRAM

advertisement
SES
STATUS= NEW
BUS RATING = 800A
VOLTAGE = 120/208V
# POLES=
NEMA RATING = 3R
MOUNTING= FREESTANDING
AIC RATING = 42K
LOCATION= EXTERIOR
1
NEW PAD-MOUNT
TRANSFORMER
KEYED NOTES:
100AF
100AS
3P
42K AIC
M
3
800AF
800AT
3P GFPE
42K AIC
NEW
PULL SECTION
TV
SS
N
G
300AF
300AT
3P
42K AIC
200AF
200AT
3P
42K AIC
200AF
200AT
3P
42K AIC
200AF
200AT
3P
42K AIC
150AF
150AT
3P
42K AIC
200AF
200AT
3P
42K AIC
200AF
SPACE
1
PROVIDE 4" HIGH CONCRETE PAD FOR EXTERIOR
MOUNTED SERVICE ENTRANCE SECTION. PAD
SHALL EXTEND 3' BEYOND THE LEADING EDGE OF
THE NEW SES, AND EXTEND 6" ON EACH SIDE OF
THE SES.
2
(3)-4"C WITH PULLSTRING FOR SECONDARY
CABLES (CABLES FURNISHED AND INSTALLED BY
SALT RIVER PROJECT). MINIMUM BURIAL DEPTH
SHALL BE 36" BELOW FINISHED GRADE.
3
NEW UTILITY PAD-MOUNT TRANSFORMER
COORDINATE EXACT LOCATION WITH SALT RIVER
PROJECT. CONTRACTOR SHALL PROVIDE
TRANSFORMER PAD AND GROUNDING PER
SALT RIVER PROJECT INSTALLATION STANDARDS.
4
REFER TO GROUNDING DETAIL THIS SHEET
5
3"C EA WITH (4)-#350KCMIL CU., (1)-#2CU. GND.
6
2"C WITH (4)-#1/0CU., (1)-#6CU. GND.
7
1 1/2"C WITH (4)-#1CU., (1)-#6CU. GND.
8
2 1/2"C WITH (4)-#3/0CU., (1)-#4CU. GND.
9
TRANSIENT VOLTAGE SURGE SUPPRESSOR, EQUAL
TO CURRENT TECHNOLOGY #SEL200-3GY-L3.
10
(3)-3"C WITH PULLSTRING FOR PRIMARY
CABLES (CABLES FURNISHED AND INSTALLED
BY SALT RIVER PROJECT). MINIMUM BURIAL
DEPTH SHALL BE 48" BELOW FINISHED GRADE.
9
4
TO UTILITY POINT
OF CONNECTION.
VERIFY LOCATION WITH
UTILITY PRIOR TO INSTALLATION.
MODIFY AS REQUIRED.
10
2
TRANSFORMER
GROUNDING
5
Diesel
Generator
80KW
120/208V
3 phase, 4 wire, with
weatherproof enclosure
SERVICE S.C. INFO:
8
G E
5
ENTRANCE SECTIONS PER PUBLISHED SRP
STANDARDS IS 42,000 AIC.
NEUTRAL
BUS
STATUS= NEW
STATUS= NEW
STATUS= NEW
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 200A
AICRATING = 42K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION= 1ST FLR. ELEC. RM.
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 200A
AICRATING = 42K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION= 1ST FLR. ELEC. RM.
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 200A
AICRATING = 42K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION= 1ST FLR. ELEC. RM.
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 200A
AICRATING = 42K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION= 2ND FLR. ELEC. RM
REFER TO SHEET E902 FOR
ADDITIONAL INFORMATION
- 1
4
STATUS=
NEW
BUS RATING = 400A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
MAIN TYPE = M.C.B.
MAIN RATING = 300A
AICRATING = 42K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION=
6
STATUS= NEW
5
#2/0CU. MAIN BONDING
JUMPER PER 2005 NEC
250-28(D).
PV METER
PV
INVERTER
'ELP1'-37
BLOCK HEATER
0 3
6
#4CU. GROUNDING CONDUCTOR
TO CONCRETE ENCASED ELECTRODE
(UFER) PER 2005 NEC 250-66(B)
#1/0CU. BOND TO METAL
PIPING (GAS, SPRINKLER, PNEUMATIC
PER 2005 NEC 250-104(B)
PV DISC. SWITCH
M
5
LOCATION = EXTERIOR
SWITCHBOARD
#6CU. GROUNDING ELECTRODE CONDUCTOR
PER NEC 250-66(A)
STATUS= NEW
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 150A
AICRATING = 22K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION=
#2/0CU. BOND TO METAL
UNDERGROUND WATER PIPE PER
2005 NEC 250-52(A)(1)
PROVIDE ADDITIONAL GROUND
ROD(S) AS REQUIRED BY
NEC 250-56.
#2/0CU. BOND TO METAL
FRAME OF BUILDING PER
2005 NEC 250-52(A)(2)
8
AMP RATING = 400A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SKID MOUNTED
NEMA RATING = 3R
# POLES= 3P
NEUTRAL TYPE= SOLID
BYPASS ISOLATION = N
TRANSITION = OPEN
AIC RATING = 42K AIC
BATTERY CHARGER
'ELP2'-39
GROUND
BUS
8
300A/3P
MAXIMUM AVAILABLE FAULT CURRENT ON (1) SES
#2/0CU. BOND TO EQUIPMENT
ENCLOSURE PER 2005 NEC 250-102(D)
8
6' MIN.
STATUS= NEW
BUS RATING = 225A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= SURFACE
NEMA RATING = 1
MAIN TYPE = M.L.O.
UPSTREAM MAIN = 150A
AICRATING = 22K AIC
MANUFACTURER=
PANEL STYLE=
LOCATION=
STATUS= NEW
MANUFACTURER=
SWBD SERIES =
UTILITY= SALT RIVER PROJECT
CCT
NO.
LOAD
CODE
BUS RATING = 800A
VOLTAGE = 120/208V
SYSTEM=
MOUNTING= FREE-STANDING
NEMA RATING = 3R
E.U.S.E.R.C.= YES
FEED TYPE = BOTTOM
LOAD
DESCRIPTION
BKR
SIZE
8
1
8
Panel 'ELP1'
300/3
8
3/4"x10'-0" LONG GROUND
ROD. 8'-0" MINIMUM SHALL
BE IN DIRECT CONTACT WITH
THE EARTH
8
200/3
SES ONE-LINE DIAGRAM
8
NEW
200/3
8
200/3
8
8
9.18
200/3
8
BKR
SIZE
LOAD
DESCRIPTION
LOAD
CODE
CCT
NO
200A
SPACE
2
150/3
PV SYSTEM
4
100A
SPACE
6
9.76
8.96
9.48
9.48
12.32
14.20
14.20
18.04
Panel 'LP4'
LOAD
(KVA)
7.06
8
14.20
13.36
8
9
GROUND BUS (COPPER) = YES
NEUTRAL BUS (COPPER) = YES
TERMINATIONS =
# SECTIONS= 1
BUS EXTENSION PROVISIONS = YES
25.46
9.18
14.20
Panel 'LP3'
BUS MATERIAL= COPPER
23.80
12.32
8
7
20.10
23.80
8.96
Panel 'LP2'
8
SCALE: NONE
20.10
PHASE PHASE
B
C
9.76
8
5
PHASE
A
7.06
Panel 'LP1'
8
#6CU. GROUNDING ELECTRODE
CONDUCTOR TO GROUND ROD
PROVIDE AN EXOTHERMIC CONNECTION
TO THE ROD
LOAD
(KVA)
25.46
8
3
MAIN RATING= 800A
MAIN TYPE= M.C.B.
AIC RATING = 42K
HORIZONTAL BUSSING= YES
FULLY RATED
VERTICAL BUSSING= FULL HEIGHT
VERTICAL BUSSING= YES
FULLY RATED
13.36
18.04
17.17
10
17.17
21.20
21.20
0.00
11
12
0.00
0.00
0.00
13
14
0.00
0.00
FEED THRU LOADS/PHASE (WHERE APPLICABLE)
PEAK DEMAND PER 220-87 (WHERE APPLICABLE)/.80*1.25
0.00
PHASE TOTALS (KVA/Phase)
DEMAND LOADS MAY VARY FROM CONNECTED
FAULT CURRENT CALCULATIONS
LOADS BECAUSE OF CODE DIVERSITIES.
68.36
Connected KVA
Demand KVA
0.00
73.83
0.00
82.10
623
224.29
227.67
CIRCUIT NUMBERING BY POLE POSITION
CIRCUIT BREAKERS FEEDING A/C EQUIPMENT
632
Connected AMPS
Demand AMPS
SHALL BE "HACR" RATED.
ALL BREAKERS SHALL BE FULLY RATED
THE FOLLOWING CALCULATIONS ARE BASED ONT THE "POINT-BY-POINT" METHOD WHERE:
M= 1/(1+f)
Isc = Isc x M
f = 1.73 x L x I
CxE
XFMR:
IP(sca)= IP(sca)x Vp x%Z
100,000xKVA
IS(sca)= Vp x M x IS(sca)
Vs
(ALL CALCULATIONS UTILIZE COPPER CONDUCTORS)
Source
Fault
Point
1
2
3
4
5
6
7
8
9
Panel /
Transformer
SES
PANEL LP1
PANEL LP2
PANEL LP3
PANEL LP4
ATS
PANEL ELP1
PANEL ELP2
PANEL ELP3
(Fault
Source I
Point)
(amps)
1
1
1
1
1
6
7
7
42,000
42,000
42,000
42,000
42,000
42,000
36,401
26,002
26,002
X'FMR
Conduit
Type
NM
NM
NM
NM
NM
NM
M
M
Wire/Bus Size
1
1
1
1
1
1
1
1
Set(s)
Set(s)
Set(s)
Set(s)
Set(s)
Set(s)
Set(s)
Set(s)
of
of
of
of
of
of
of
of
'C' value
3/0
3/0
3/0
3/0
350 KCML
350 KCML
1/0
1
13923
13923
13923
13923
22736
22736
8924
7292
E (volts)
208
208
208
208
208
208
208
208
L (length)
20
23
25
65
10
30
6
45
KVA
X'FMR
Z
f
0.502
0.578
0.628
1.633
0.154
0.400
0.146
1.336
M
0.67
0.63
0.61
0.38
0.87
0.71
0.87
0.43
Isc
42,000
27,956
26,620
25,799
15,953
36,401
26,002
22,697
11,130
Load Code
0
1
2
3
4
5
6
7
9
10
11
12
13
Load Summaries
Lighting - Non-Continuous
Lighting -Continuous
Receptacles
Special Loads
Connected KVA
Factor
Demand KVA
0.00
1.00
0.00
14.84
1.25
18.55
16.36
0.81
13.18
87.33
1.00
87.33
Motors
Kitchen (Commercial)
Heating
Cooling
Computer Outlets
Exterior Lighting
16.96
1.00
16.96
0.00
0.65
0.00
6.40
1.00
0.00
45.40
1.00
45.40
0.00
1.00
0.00
6.10
1.25
7.63
Miscellaneous - Continuous
Modular Furniture Outlets
Peak Demand per 220-87
30.90
1.25
38.63
0.00
1.00
0.00
0.00
1.00
0.00
Subtotals
Largest Motor
224.29
Total KVA
Phase (A)
Phase (B)
Phase (C)
569.23
614.80
683.64
Per Table 220.56
Larger of the two loads per NEC 220-60
Larger of the two loads per NEC 220-60
227.67
0.00
224.29
Phase amps
0.25
0.00
227.67
Spare Capacity (Amps)
Spare Capacity Load (%)
168
21%
2