SES STATUS= NEW BUS RATING = 800A VOLTAGE = 120/208V # POLES= NEMA RATING = 3R MOUNTING= FREESTANDING AIC RATING = 42K LOCATION= EXTERIOR 1 NEW PAD-MOUNT TRANSFORMER KEYED NOTES: 100AF 100AS 3P 42K AIC M 3 800AF 800AT 3P GFPE 42K AIC NEW PULL SECTION TV SS N G 300AF 300AT 3P 42K AIC 200AF 200AT 3P 42K AIC 200AF 200AT 3P 42K AIC 200AF 200AT 3P 42K AIC 150AF 150AT 3P 42K AIC 200AF 200AT 3P 42K AIC 200AF SPACE 1 PROVIDE 4" HIGH CONCRETE PAD FOR EXTERIOR MOUNTED SERVICE ENTRANCE SECTION. PAD SHALL EXTEND 3' BEYOND THE LEADING EDGE OF THE NEW SES, AND EXTEND 6" ON EACH SIDE OF THE SES. 2 (3)-4"C WITH PULLSTRING FOR SECONDARY CABLES (CABLES FURNISHED AND INSTALLED BY SALT RIVER PROJECT). MINIMUM BURIAL DEPTH SHALL BE 36" BELOW FINISHED GRADE. 3 NEW UTILITY PAD-MOUNT TRANSFORMER COORDINATE EXACT LOCATION WITH SALT RIVER PROJECT. CONTRACTOR SHALL PROVIDE TRANSFORMER PAD AND GROUNDING PER SALT RIVER PROJECT INSTALLATION STANDARDS. 4 REFER TO GROUNDING DETAIL THIS SHEET 5 3"C EA WITH (4)-#350KCMIL CU., (1)-#2CU. GND. 6 2"C WITH (4)-#1/0CU., (1)-#6CU. GND. 7 1 1/2"C WITH (4)-#1CU., (1)-#6CU. GND. 8 2 1/2"C WITH (4)-#3/0CU., (1)-#4CU. GND. 9 TRANSIENT VOLTAGE SURGE SUPPRESSOR, EQUAL TO CURRENT TECHNOLOGY #SEL200-3GY-L3. 10 (3)-3"C WITH PULLSTRING FOR PRIMARY CABLES (CABLES FURNISHED AND INSTALLED BY SALT RIVER PROJECT). MINIMUM BURIAL DEPTH SHALL BE 48" BELOW FINISHED GRADE. 9 4 TO UTILITY POINT OF CONNECTION. VERIFY LOCATION WITH UTILITY PRIOR TO INSTALLATION. MODIFY AS REQUIRED. 10 2 TRANSFORMER GROUNDING 5 Diesel Generator 80KW 120/208V 3 phase, 4 wire, with weatherproof enclosure SERVICE S.C. INFO: 8 G E 5 ENTRANCE SECTIONS PER PUBLISHED SRP STANDARDS IS 42,000 AIC. NEUTRAL BUS STATUS= NEW STATUS= NEW STATUS= NEW BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 MAIN TYPE = M.L.O. UPSTREAM MAIN = 200A AICRATING = 42K AIC MANUFACTURER= PANEL STYLE= LOCATION= 1ST FLR. ELEC. RM. MAIN TYPE = M.L.O. UPSTREAM MAIN = 200A AICRATING = 42K AIC MANUFACTURER= PANEL STYLE= LOCATION= 1ST FLR. ELEC. RM. MAIN TYPE = M.L.O. UPSTREAM MAIN = 200A AICRATING = 42K AIC MANUFACTURER= PANEL STYLE= LOCATION= 1ST FLR. ELEC. RM. MAIN TYPE = M.L.O. UPSTREAM MAIN = 200A AICRATING = 42K AIC MANUFACTURER= PANEL STYLE= LOCATION= 2ND FLR. ELEC. RM REFER TO SHEET E902 FOR ADDITIONAL INFORMATION - 1 4 STATUS= NEW BUS RATING = 400A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 MAIN TYPE = M.C.B. MAIN RATING = 300A AICRATING = 42K AIC MANUFACTURER= PANEL STYLE= LOCATION= 6 STATUS= NEW 5 #2/0CU. MAIN BONDING JUMPER PER 2005 NEC 250-28(D). PV METER PV INVERTER 'ELP1'-37 BLOCK HEATER 0 3 6 #4CU. GROUNDING CONDUCTOR TO CONCRETE ENCASED ELECTRODE (UFER) PER 2005 NEC 250-66(B) #1/0CU. BOND TO METAL PIPING (GAS, SPRINKLER, PNEUMATIC PER 2005 NEC 250-104(B) PV DISC. SWITCH M 5 LOCATION = EXTERIOR SWITCHBOARD #6CU. GROUNDING ELECTRODE CONDUCTOR PER NEC 250-66(A) STATUS= NEW BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 MAIN TYPE = M.L.O. UPSTREAM MAIN = 150A AICRATING = 22K AIC MANUFACTURER= PANEL STYLE= LOCATION= #2/0CU. BOND TO METAL UNDERGROUND WATER PIPE PER 2005 NEC 250-52(A)(1) PROVIDE ADDITIONAL GROUND ROD(S) AS REQUIRED BY NEC 250-56. #2/0CU. BOND TO METAL FRAME OF BUILDING PER 2005 NEC 250-52(A)(2) 8 AMP RATING = 400A VOLTAGE = 120/208V SYSTEM= MOUNTING= SKID MOUNTED NEMA RATING = 3R # POLES= 3P NEUTRAL TYPE= SOLID BYPASS ISOLATION = N TRANSITION = OPEN AIC RATING = 42K AIC BATTERY CHARGER 'ELP2'-39 GROUND BUS 8 300A/3P MAXIMUM AVAILABLE FAULT CURRENT ON (1) SES #2/0CU. BOND TO EQUIPMENT ENCLOSURE PER 2005 NEC 250-102(D) 8 6' MIN. STATUS= NEW BUS RATING = 225A VOLTAGE = 120/208V SYSTEM= MOUNTING= SURFACE NEMA RATING = 1 MAIN TYPE = M.L.O. UPSTREAM MAIN = 150A AICRATING = 22K AIC MANUFACTURER= PANEL STYLE= LOCATION= STATUS= NEW MANUFACTURER= SWBD SERIES = UTILITY= SALT RIVER PROJECT CCT NO. LOAD CODE BUS RATING = 800A VOLTAGE = 120/208V SYSTEM= MOUNTING= FREE-STANDING NEMA RATING = 3R E.U.S.E.R.C.= YES FEED TYPE = BOTTOM LOAD DESCRIPTION BKR SIZE 8 1 8 Panel 'ELP1' 300/3 8 3/4"x10'-0" LONG GROUND ROD. 8'-0" MINIMUM SHALL BE IN DIRECT CONTACT WITH THE EARTH 8 200/3 SES ONE-LINE DIAGRAM 8 NEW 200/3 8 200/3 8 8 9.18 200/3 8 BKR SIZE LOAD DESCRIPTION LOAD CODE CCT NO 200A SPACE 2 150/3 PV SYSTEM 4 100A SPACE 6 9.76 8.96 9.48 9.48 12.32 14.20 14.20 18.04 Panel 'LP4' LOAD (KVA) 7.06 8 14.20 13.36 8 9 GROUND BUS (COPPER) = YES NEUTRAL BUS (COPPER) = YES TERMINATIONS = # SECTIONS= 1 BUS EXTENSION PROVISIONS = YES 25.46 9.18 14.20 Panel 'LP3' BUS MATERIAL= COPPER 23.80 12.32 8 7 20.10 23.80 8.96 Panel 'LP2' 8 SCALE: NONE 20.10 PHASE PHASE B C 9.76 8 5 PHASE A 7.06 Panel 'LP1' 8 #6CU. GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD PROVIDE AN EXOTHERMIC CONNECTION TO THE ROD LOAD (KVA) 25.46 8 3 MAIN RATING= 800A MAIN TYPE= M.C.B. AIC RATING = 42K HORIZONTAL BUSSING= YES FULLY RATED VERTICAL BUSSING= FULL HEIGHT VERTICAL BUSSING= YES FULLY RATED 13.36 18.04 17.17 10 17.17 21.20 21.20 0.00 11 12 0.00 0.00 0.00 13 14 0.00 0.00 FEED THRU LOADS/PHASE (WHERE APPLICABLE) PEAK DEMAND PER 220-87 (WHERE APPLICABLE)/.80*1.25 0.00 PHASE TOTALS (KVA/Phase) DEMAND LOADS MAY VARY FROM CONNECTED FAULT CURRENT CALCULATIONS LOADS BECAUSE OF CODE DIVERSITIES. 68.36 Connected KVA Demand KVA 0.00 73.83 0.00 82.10 623 224.29 227.67 CIRCUIT NUMBERING BY POLE POSITION CIRCUIT BREAKERS FEEDING A/C EQUIPMENT 632 Connected AMPS Demand AMPS SHALL BE "HACR" RATED. ALL BREAKERS SHALL BE FULLY RATED THE FOLLOWING CALCULATIONS ARE BASED ONT THE "POINT-BY-POINT" METHOD WHERE: M= 1/(1+f) Isc = Isc x M f = 1.73 x L x I CxE XFMR: IP(sca)= IP(sca)x Vp x%Z 100,000xKVA IS(sca)= Vp x M x IS(sca) Vs (ALL CALCULATIONS UTILIZE COPPER CONDUCTORS) Source Fault Point 1 2 3 4 5 6 7 8 9 Panel / Transformer SES PANEL LP1 PANEL LP2 PANEL LP3 PANEL LP4 ATS PANEL ELP1 PANEL ELP2 PANEL ELP3 (Fault Source I Point) (amps) 1 1 1 1 1 6 7 7 42,000 42,000 42,000 42,000 42,000 42,000 36,401 26,002 26,002 X'FMR Conduit Type NM NM NM NM NM NM M M Wire/Bus Size 1 1 1 1 1 1 1 1 Set(s) Set(s) Set(s) Set(s) Set(s) Set(s) Set(s) Set(s) of of of of of of of of 'C' value 3/0 3/0 3/0 3/0 350 KCML 350 KCML 1/0 1 13923 13923 13923 13923 22736 22736 8924 7292 E (volts) 208 208 208 208 208 208 208 208 L (length) 20 23 25 65 10 30 6 45 KVA X'FMR Z f 0.502 0.578 0.628 1.633 0.154 0.400 0.146 1.336 M 0.67 0.63 0.61 0.38 0.87 0.71 0.87 0.43 Isc 42,000 27,956 26,620 25,799 15,953 36,401 26,002 22,697 11,130 Load Code 0 1 2 3 4 5 6 7 9 10 11 12 13 Load Summaries Lighting - Non-Continuous Lighting -Continuous Receptacles Special Loads Connected KVA Factor Demand KVA 0.00 1.00 0.00 14.84 1.25 18.55 16.36 0.81 13.18 87.33 1.00 87.33 Motors Kitchen (Commercial) Heating Cooling Computer Outlets Exterior Lighting 16.96 1.00 16.96 0.00 0.65 0.00 6.40 1.00 0.00 45.40 1.00 45.40 0.00 1.00 0.00 6.10 1.25 7.63 Miscellaneous - Continuous Modular Furniture Outlets Peak Demand per 220-87 30.90 1.25 38.63 0.00 1.00 0.00 0.00 1.00 0.00 Subtotals Largest Motor 224.29 Total KVA Phase (A) Phase (B) Phase (C) 569.23 614.80 683.64 Per Table 220.56 Larger of the two loads per NEC 220-60 Larger of the two loads per NEC 220-60 227.67 0.00 224.29 Phase amps 0.25 0.00 227.67 Spare Capacity (Amps) Spare Capacity Load (%) 168 21% 2