Chapter 4 SFRA Testing Chapter 4 SFRA Testing 4.1 Introduction SFRA is able to detect a number of fault conditions, both mechanical and electrical. The main application of SFRA is to detect mechanical faults, for which some are detectable by SFRA only and some are useful to analyze both with SFRA and other methods for correlation. Electrical faults are often easy to detect using SFRA, but are also easily detectable by other methods. Examples of fault conditions that can be detected by SFRA: Mechanical faults: • Winding deformations (including hoop buckling). • Winding movement. • Partial collapse of winding • Core displacements • Broken or loosened winding or clamping structure Electrical faults: • Shorted turns or open circuit winding • Bad ground connection of the transformer tank. SFRA is often the only method that can detect axial movements of a winding. SFRA does also detect radial movements, which can be detected by leakage reactance tests (short-circuit impedance test) as well. It is useful to correlate the two methods to increase the precision of the result. This is also true for other, especially mechanical, faults. [16] 4.2 SFRA Test Procedure 4.2.1 Preparation: The Transformer to be tested must be completely isolated from the power system. This requires that all bushings of all windings be connected from any bus and insulators. This ensures that measurements are not adversely affected by interference. [46] 39 Chapter 4 SFRA Testing 4.2.2 Connections: Generally, an SFRA measurement is made from one terminal on the transformer (e.g. H1 (or U) or A) to another terminal (e.g. H2 (or V) or N) It is important to record all relevant information, which includes tap position, oil level and terminals grounded or shorted. Where previous test results exist, the best testing procedure is to repeat those tests, taking note of tap position, shorted or grounded bushings, and any details for specific tests. [46] 4.2.3 Types of Measurement: 4.2.3.1 Open Circuit An open circuit measurement is made from one end of a winding to another with all other terminals floating. For example, for a delta winding, connections would be H1 to H2 ( or U to V) and for a star winding, measurements are taken from HV terminals to neutral, such as X1 to X0 (or U to N) 4.2.3.2 Short Circuit A short circuit measurement is made with the same SFRA test lead connections as an open circuit measurement, but with the difference that another winding is short circuited. To ensure repeatability, the three voltage terminals on the shorted winding be shorted together. This would mean, for example, shorting X1 to X2, X2 to X3 and X3 to X1 (or U to V, V to W and W to U). This ensures that all three phases are similarly shorted to give a consistent impedance. Any neutral connections available for the shorted winding should not be included in the shorting process. [46] 4.2.4 Test Templates The test templates given here require performing open-circuit and short-circuit tests. A standard set of tests, recorded when a baseline is needed and there is no question of the transformer’s health, consists of a set of results taken only at extreme tap position. The LTC be in the extreme raise position. However, if the transformer is being tested for post-event reasons, such as fault, this should be done in the as-found LTC position. Note the tap positions on the test report and apply them during the start of each test. 40 Chapter 4 SFRA Testing The DETC position should not be moved for an SFRA test until all options are exhausted. For new transformers in the factory, use the nominal DETC position, unless otherwise specified by the end-user. Notes Leads. Table - 4.1 gives the recommended tests with position of the red lead and black lead clearly identified. Reversing these test leads may provide small variation in higher frequency response. Therefore, care should be taken for attaching test leads appropriately. Grounding. Good grounds are key to good high frequency responses. Make sure that grounds are not hampered by loose connections, paint, dirt or grease. LTC Position. Changing LTC will change SFRA response; LTC position should be recorded. DETC Position. Transformers in service occasionally have problems due to DETC movement. DETC position should not be altered for an SFRA test. The exception is in factory test on a new transformer, where it can be assumed that the DETC is in operating condition and tests can be performed on nominal tap. [46] ¾ Two-Winding Transformers Table 4.1 Two Winding Transformers – 9 Tests [46] 3Ø 3Ø 3Ø 3Ø Test Delta- Wye - Delta- Wye - # Wye Delta Delta Wye HV open Circuit (OC) Test 1 H1-H3 H1-H0 H1-H3 H1-H0 All Other Terminals Test 2 H2-H1 H2-H0 H2-H1 H2-H0 Floating Test 3 H3-H2 H3-H0 H3-H2 H3-H0 LV open Circuit (OC) Test 4 X1-X0 X1-X2 X1-X3 X1-X0 All Other Terminals Test 5 X2-X0 X2-X3 X2-X1 X2-X0 Floating Test 6 X3-X0 X3-X1 X3-X2 X3-X0 Short Circuit (SC) Test 7 H1-H3 H1-H0 H1-H3 H1-H0 H1-H2(H0) High (H) to Low (L) Test 8 H2-H1 H2-H0 H2-H1 H2-H0 Short Short [X1-X2-X3]* Test 9 H3-H2 H3-H0 H3-H2 H3-H0 X1-X2(X0) * Test Type 41 1Ø H1-H2(H0) X1-X2(X0) Chapter 4 SFRA Testing *Indicates short-circuit tests where the terminals are shorted together with three sets of jumpers, to provide symmetry (X1-X2, X2-X3, X3-X1) OR (Y1-Y2, Y2-Y3, Y3Y1). The neutral is not included for 3Ø wye connections but may be included for 1Ø test connections. ¾ Auto Transformers Table 4.2 Autotransformer without Tertiary or with Buried Tertiary – 9 Tests [46] Test Type Series Winding (OC) All Other Terminals Floating Common Winding (OC) All Other Terminals Floating Short Circuit (SC) High (H) to Low (L) * Short [X1-X2-X3] Test # 3Ø 1Ø Test 1 H1-X1 Test 2 H2-X2 Test 3 H3-X3 Test 4 X1-H0X0 Test 5 X2- H0X0 Test 6 X3- H0X0 Test 7 H1- H0X0 H1- H0X0 Test 8 H2- H0X0 Short Test 9 H3- H0X0 [X1-H0X0] * H1-X1 X1-H0X0 *Indicates short-circuit tests where the terminals are shorted together with three sets of jumpers, to provide symmetry (X1-X2, X2-X3, X3-X1) OR (Y1-Y2, Y2-Y3, Y3Y1). The neutral is not included for 3Ø wye connections but may be included for 1Ø test connections. 42 Chapter 4 SFRA Testing ¾ Three-Winding Transformers Table 4.3 Three- Winding Transformers, Part 1 – 18 Tests [46] 3Ø 3Ø 3Ø 3Ø Delta- Delta - Delta- Delta- Delta- Delta- Wye- Wye - Delta Wye Delta Wye Test 1 H1-H3 H1-H3 H1-H3 H1-H3 Test 2 H2-H1 H2-H1 H2-H1 H2-H1 Test 3 H3-H2 H3-H2 H3-H2 H3-H2 Test 4 X1-X3 X1-X3 X1-X0 X1-X0 Test 5 X2-X1 X2-X1 X2-X0 X2-X0 Test 6 X3-X2 X3-X2 X3-X0 X3-X0 Tert open Circuit (OC) Test 7 Y1-Y3 Y1-Y0 Y1-Y3 Y1-Y0 All Other Terminals Floating Test 8 Y2-Y1 Y2-Y0 Y2-Y1 Y2-Y0 Test 9 Y3-Y2 Y3-Y0 Y3-Y2 Y3-Y0 Short Circuit (SC) Test 10 H1-H3 H1-H3 H1-H3 H1-H3 H1-H0 High (H) to Low (L) Test 11 H2-H1 H2-H1 H2-H1 H2-H1 Short Short [X1-X2-X3]* Test 12 H3-H2 H3-H2 H3-H2 H3-H2 [X1-X2]* Short Circuit (SC) Test 13 H1-H3 H1-H3 H1-H3 H1-H3 H1-H0 High (H) to Tertiary (T) Test 14 H2-H1 H2-H1 H2-H1 H2-H1 Short Short [Y1-Y2-Y3]* Test 15 H3-H2 H3-H2 H3-H2 H3-H2 [Y1-Y2]* Short Circuit (SC) Test 16 X1-X3 X1-X3 X1-X0 X1-X0 X1-X0 Low (L) to Tertiary (T) Test 17 X2-X1 X2-X1 X2-X0 X2-X0 Short Short [Y1-Y2-Y3]* Test 18 X3-X2 X3-X2 X3-X0 X3-X0 [Y1-Y2]* Test Type HV open Circuit (OC) All Other Terminals Floating LV open Circuit (OC) All Other Terminals Floating Test # 1Ø H1-H2 (H1-H0) X1-X2 (X1-X0) Y1-Y2 (Y1-Y0) *Indicates short-circuit tests where the terminals are shorted together with three sets of jumpers, to provide symmetry (X1-X2, X2-X3, X3-X1) OR (Y1-Y2, Y2-Y3, Y3Y1). The neutral is not included for 3Ø wye connections but may be included for 1Ø test connections. 43 Chapter 4 SFRA Testing Table 4.4 Three- Winding Transformers, Part 2 – 18 Tests [46] Test Type Test # 3Ø 3Ø 3Ø 3Ø Wye- Wye- Wye- Wye- Wye- Wye- Wye Delta Delta-Wye Delta-Delta Test 1 H1-H0 H1-H0 H1-H0 H1-H0 Test 2 H2-H0 H2-H0 H2-H0 H2-H0 Test 3 H3-H0 H3-H0 H3-H0 H3-H0 Test 4 X1-X0 X1-X0 X1-X2 X1-X2 Test 5 X2-X0 X2-X0 X2-X3 X2-X3 Test 6 X3-X0 X3-X0 X3-X1 X3-X1 Tert open Circuit (OC) Test 7 Y1-Y0 Y1-Y2 Y1-Y0 Y1-Y2 All Other Terminals Floating Test 8 Y2-Y0 Y2-Y3 Y2-Y0 Y2-Y3 Test 9 Y3-Y0 Y3-Y1 Y3-Y0 Y3-Y1 Short Circuit (SC) Test 10 H1-H0 H1-H0 H1-H0 H1-H0 High (H) to Low (L) Test 11 H2-H0 H2-H0 H2-H0 H2-H0 Short [X1-X2-X3]* Test 12 H3-H0 H3-H0 H3-H0 H3-H0 Short Circuit (SC) Test 13 H1-H0 H1-H0 H1-H0 H1-H0 High (H) to Tertiary (T) Test 14 H2-H0 H2-H0 H2-H0 H2-H0 Short [Y1-Y2-Y3]* Test 15 H3-H0 H3-H0 H3-H0 H3-H0 Short Circuit (SC) Test 16 X1-X0 X1-X0 X1-X2 X1-X2 Low (L) to Tertiary (T) Test 17 X2-X0 X2-X0 X2-X3 X2-X3 Short [Y1-Y2-Y3]* Test 18 X3-X0 X3-X0 X3-X1 X3-X1 HV open Circuit (OC) All Other Terminals Floating LV open Circuit (OC) All Other Terminals Floating *Indicates short-circuit tests where the terminals are shorted together with three sets of jumpers, to provide symmetry (X1-X2, X2-X3, X3-X1) OR (Y1-Y2, Y2-Y3, Y3Y1). The neutral is not included for 3Ø wye connections but may be included for 1Ø test connections. 44 Chapter 4 SFRA Testing 4.2.5 Diagnostic Significance of Frequency Diagnostics of frequency ranges are discussed on two levels; per phase open circuit measurement and short circuit measurement. 4.2.5.1 Per Phase Open Circuit Measurement As the name implies, per phase measurement targets the individual phase of a winding. At low frequencies, the influence of capacitance is negligible, and the winding behaves as an inductor. Therefore, the attenuation and phase shift of the low frequency sinusoidal signals, passing through the winding, are determined by the inductive and resistive nature of the network. The inductive characteristics are determined by the magnetic circuit of the core, and the resistive characteristics are dominated by the resistance of the output measuring cable. As the frequency of the input signal increases, the capacitive effects begin to dominate and the phase angle quickly becomes close to +90 degrees in the region above 1 KHz. Now, the attenuation and phase shift of the high frequency sinusoidal signals passing through the windings are determined by inductive and capacitive nature of the network. However in the high frequency region, the inductive characteristics are determined by the leakage flux coupling, and capacitive characteristics are determined by the various capacitance elements associated with individual turns. The propagation characteristic of the winding becomes complex as a result of the many resonance frequencies found in the high frequency range. However, since the winding resonances become less dependent on the magnetic circuit of the core, the traces of the three phases converge and become quite similar. As the frequency increases even further over 100 KHz, the sinusoidal signals travel mostly outside the winding and reflect the other elements found in the transformer – e.g. leads, support insulation etc. The magnitude and the phase of the transfer function in that frequency region are influenced by the inductive-capacitive-resistive nature of these elements. 45 Chapter 4 SFRA Testing Although most of the low frequency magnitude responses exhibit a typical shape, there are no typical form responses in the high frequency region. These vary greatly with the design of the unit. 4.2.5.2 Short Circuit Measurement The aim of this measurement is to allow direct comparison between the three phases of a three phase transformer where no prior measurements exist. Taking a measurement on one winding with another winding short circuited removes the effect of the core at low frequencies. The resulting response is that for a large inductor with no core. The responses for all three phase should be similar at low frequencies. The theory behind the short circuit measurement is given below. Any two winding transformer can be modeled at low frequencies by a simple T model as shown in Fig. 4.1. Fig. 4.1 T Model of Transformer Winding The impedance of the winding is small, while the impedance of the core to ground is extremely high. This means that for any input signal, the response is dominated by the core. By adding a short to the LV side, the effect of the core is removed and the response is dominated by the windings, which are predominantly inductors at low frequency with an inductive roll off as frequency rises (Fig.4.2) 46 Chapter 4 SFRA Testing Fig. 4.2 T Model with LV Short All three phase of a transformer have similar winding inductances, which means their responses should be similar. [46] 4.3 Test Circuit and Connections To make an FRA measurement, a voltage (either a sweep frequency or an impulse signal) is supplied to a transformer terminal with respect to the tank. The voltage measured at the input terminal is used as the reference for the FRA calculation. A second parameter (response signal) is usually a voltage taken across the measurement impedance connected to a second transformer terminal with reference to the tank (it may also be a current measured at the input terminal or at some other grounded terminal). The FRA response amplitude is the ratio between the response signal (Vr) and the source voltage (Vs) as a function of the frequency (generally presented in dB). The following ‘standard’ method for connecting the terminals and the tank using extension leads is mainly used: • The input and reference coaxial cables are tapped together near the top of the bushing. A ground extension is run along the body of the bushing, down to the flange, to connect the cables shields to the tank. The same principle applies for the response cable. An alternative technique, referred to the ‘reverse’ method given below can also be used. • The input and reference coaxial cables are tapped together near the flange of the bushing. The cables shields are connected to the tank using a short lead. A lead 47 Chapter 4 SFRA Testing extension is run along the body of the bushing to connect the signal to the bushing terminal. The same principle applies for the response cable. [15] The following sections 4.3.1 to 4.3.4 describe the main FRA test types. 4.3.1 End-to-end (Fig. 4.3a, b) In the ‘end-to-end’ (or ‘end-to-end open’) test, the signal is applied to one end of each winding in turn, and the transmitted signal is measured at the other end. The magnetizing impedance of the transformer is the main parameter characterizing the low-frequency response (below first resonance) using this configuration. This test is the more commonly used because of its simplicity and the possibility to examine each winding separately. The end-to-end tests can be made with the source applied on the phase terminal or on the neutral terminal. In principle, both should give similar results but the FRA user should specify the test set-up used and keep that information along with test data since it will influence the results. 4.3.2 End-to-end short-circuit (Fig. 4.3c, d) This test is similar to the end-to-end measurement above, but with a winding on the same phase being short-circuited. Such measurements allow the influence of the core to be removed below about 10-20 kHz because the low-frequency response is characterized by the leakage inductance instead of the magnetizing inductance. The response at higher frequencies is similar to the one obtained using end-to-end measurement. The short-circuited winding can be floating or grounded. For three-phase transformers, there are two levels of variations, either per-phase or three-phase shortcircuit. Furthermore, the end-to end short-circuit tests can be made with the source applied on the phase terminal or on the neutral terminal. This test can be made if there is an interest in obtaining information related to the leakage impedance at low frequency, or removing uncertainties related to analysis of the core influence when residual magnetism is present. 48 Chapter 4 SFRA Testing 4.3.3 Capacitive inter-winding (Fig. 4.3e) The signal is applied to one end of a winding and the response is measured at one end of another winding on the same phase (not connected to the first one). By definition, this test is not possible between the series and common windings of autotransformers. The response using this configuration is dominated at low frequencies by the interwinding capacitance. 4.3.4 Inductive inter-winding (Fig. 4.3f) The signal is applied to a terminal on the HV side, and the response is measured on the corresponding terminal on the LV side, with the other end of both windings being grounded. The low-frequency range of this test is determined by the winding turns ratio. [15] 49 Chapter 4 SFRA Testing Fig. 4.3: FRA test types. [15] 4.4 Test Types The choice of the list of tests to perform should be adjusted depending on the purpose of the measurement. To obtain benchmark test values for future comparison or for general condition assessment, the four main FRA test types presented in section 4.3 should be performed. If the test involves a winding with regulation (tap winding) the measurements should be performed at maximum tap (with all the windings included in the measurement). If there are limitations on the time available to perform all the tests, it is recommended to perform only the end-to-end tests on all windings. Example: 3-phase transformer (Y-Δ) End-to-end (6 tests) • 3 tests on HV side • 3 tests on LV side End-to-end short-circuit (3 tests) • 3 tests on HV side (with corresponding LV shorted) Capacitive inter-winding (3 tests) 50 Chapter 4 SFRA Testing • 3 tests from HV to LV Inductive inter-winding (3 tests) • 3 tests from HV to LV If the FRA is performed to evaluate the windings before and after laboratory shortcircuits tests, again the number of tests might be an issue in order to minimize the test time. In this case, it is suggested to make the end-to-end short-circuit measurements on the HV windings to include the leakage reactance in the low-frequency measurements, and to perform the end-to-end open test on the LV side. In the example shown, it would represent six tests. For specific fault/defect analysis or general-condition assessment, the selection of test should be made depending on the information already available (known failure modes of a specific winding design, reference FRA measurement available, cause of the problem, etc.). [15] 4.5 Measurement connection and checks 4.5.1 Measurement connection and earthing Poor connections can cause significant measurement errors, attention shall be paid to the continuity of the main and earth connections. The continuity of the main and earth connections shall be checked at the instrument end of the coaxial cable before the measurement is made. In particular, connections to bolts or flanges shall be verified to ensure that there is a good connection to the winding or the test object tank. 4.5.2 Zero-check measurement If specified, a zero-check measurement shall be carried out as as additional measurement. Before measurements commence, all the measuring leads shall be connected to one of the highest voltage terminals and earthed using the normal method. A measurement is then made which will indicate the frequency response of the measurement circuit alone. The zero check measurement shall also be repeated on other voltage terminals if specified. 51 Chapter 4 SFRA Testing The zero-check measurement can provide useful information as to the highest frequency that can be relied upon for interpretation of the measurement. The zerocheck measurement is not a calibration check and no attempt should be made to remove any deviations seen in the zero-check measurement from the measurement results. 4.5.3 Repeatability check On completion of the standard measurements the measurement leads and earth connections shall be disconnected and then the first measurement shall be repeated and recorded. This check is necessary to evaluate the repeatability and useable diagnostic frequency range under the specific conditions of the measurement. [27] 4.6 Conclusion SFRA has been a key tool in the decision to scrap or reenergize a transformer. To get value from an SFRA test it is necessary to make sure that the measurements are credible, which requires good test technique and simple procedures; proper training is thus essential to control the measurement process. However special care must be taken both in application of the test to acceptable standards and in interpretation of the tests results to gain value from the tests themselves. 52