A70-38-0002 Rev P CFS Family TITLE PAGE Specifications Installation Procedures Wiring Diagrams Installation Checklist Maintenance Material Return Policy Part Number A70-00-5006 A70-00-5007 A70-00-5008 A70-00-5010 A70-00-5011 A70-00-5012 Model CFS-120/240-SP CFS-120/208-3Y CFS-277/480-3Y CFS-480-D CFS-120/240(208)-CPGD CFS-220/380-352 1 2 3 5 5 6 Description MOV 120kA, 4X plastic encl, Split Phase MOV 120kA, 4X plastic encl, Wye MOV 120kA, 4X plastic encl, Wye MOV 120kA, 4X plastic encl, Delta MOV 120kA, 4X plastic encl, CPGD MOV 120kA, 4X plastic encl, Wye All Models Protection Provided L-N; L-G; N-G; L-L Maximum Surge Current Dissipation per Phase* 120,000 Amps Maximum Load Current per Phase Unlimited Total System Response Time <1 Nanosecond Certified Category @ Test IEEE C62.41 & .45 Yes Life Cycle Testing Category C3, Operations (20,000 volts @ 1.2 x 50 µsec, 10,000 amps @ 8 x 20 µsec) <1000 Certified Category @ Test IEEE C62.41 & .45 Yes Operating Temperature Range -40º C to +85º C Operating Humidity (noncondensing) 5% to 95% Operating Altitude (feet) Up to 12,000 *8 x 20 µsec I wave per IEEE C62.41 1 A70-38-0002 Rev P The LEA International CFS FAMILY is intended for installation on AC power systems capable of delivering not more than 25,000 rms symmetrical amperes at rated voltage. Read the entire installation and maintenance manual before installing this surge protection device (SPD). Check to be certain that the voltage indicated by the model number on the front of the unit matches the AC nominal line voltage of your service. (Example: CFS-120/208-3Y) “120" is the line to neutral voltage; "208" is the line to line voltage; "3Y" indicates 3 phase, W(Y)E. The CFS FAMILY voltage rating must be the same as the incoming supply voltage. Contact LEA International’s field service department with any questions concerning the voltage configuration prior to system power on. **WARNING** Before installing the SPD, AC power must be OFF. Failure to do so could result in damage to the SPD as well as potential electrical shock hazard to personnel. INSTALLATION The CFS is to be mounted on the side or the bottom of the panel utilizing the ½” nipple provided through a ½” knockout in the panel. Secure the locking ring onto the ½” nipple and proceed. Where no knockout is available the unit can be wall mounted via the mounting tabs provided on the unit. Also, a flush mount option is available. GROUND Connect the green ground wire to the ground bus in panel. A #12 AWG green wire is provided with unit. NEUTRAL CONNECTION Connect the white neutral wire to the neutral bus in panel. A #12 AWG white wire is provided with unit. Keep the lead length as short as possible and avoid sharp bends to ensure optimum performance. PHASE CONDUCTOR CONNECTIONS Connect the black hot wires to the phase lugs. #12 AWG black wires are provided with unit. In addition, the unit can be connected to a breaker with a minimum current rating of 20 amps. Keep the lead length as short as possible and avoid sharp bends to ensure optimum performance. LEA International recommends a 20 amp breaker for the CFS units. TYPICAL WIRING METHOD The CFS FAMILY is connected in parallel with the power system to provide optimum protection. FINAL CHECK Check installation of the SPD as indicated by the provided layout/installation drawing and verification of proper connection and voltages. Apply external AC power to the SPD. The unit is now operational. All green indicator lamps should be illuminated. If not, contact LEA International’s customer service department at 1-800-882-9110. 2 A70-38-0002 Rev P The following section contains all layout/installation drawings found within the CFS FAMILY. Locate the appropriate drawing based on the model number of your system. MODEL Part Number Split Phase (-SP) A70-00-5006 3 Phase WYE (-3Y) A70-00-5007 A70-00-5008 A70-00-5012 3 A70-38-0002 Rev P CPGD (Hi-Leg Delta) A70-00-5011 3 Phase Delta (-D) A70-00-5010 4 A70-38-0002 Rev P For proper performance of the CFS FAMILY, the qualified installing electrician may use the following checklist to help in proper installation: YES NO □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ 1. The voltage of the SPD matches actual system voltage. 2. Ground resistance is less than 25 ohms. 3. All wiring conforms to the national electric code (NEC). 4. All conductors are in accordance with the appropriate layout/installation drawing. 5. All lead lengths are as short as possible. 6. The SPD is installed in parallel with the incoming phase conductors. 7. After installation, all lights are illuminated and the unit is functional. 8. All critical loads are protected by the SPD. additional SPD(s) may be required. If not, FOREWORD CFS FAMILY surge protection device (SPD) is designed for long life without the need for routine maintenance. The design is of a passive nature, with no degradation expected. LEA International’s TVSS system will fail only if an undefined over voltage (a RMS rise in system voltage in excess of the SPD rating) or a transient in excess of its maximum surge current is experienced. There are no moving parts. There are LED indicators visible on the outside of the enclosure, which indicate protection is intact. VISUAL INSPECTION Operational status of the SPD is verified by observing the status indicator lamps. All status lamps "ON" with input power applied indicates normal operation with all protection modes functioning. CFS units with status indicators not “ON” require replacement. 5 A70-38-0002 Rev P No product may be returned without the seller's prior written approval. Transportation charges are to be prepaid by the buyer. Returned item(s) are subject to the seller's inspection and acceptance. Seller may, at its discretion, replace any or all return items within a reasonable time after seller determines that returned item(s) are not in accordance here within; and in such an event, seller shall not be liable for any damage arising from the defective delivery or delay caused thereby. When authorized by the seller in writing, unused products may be returned to the seller, subject to service handling, restocking charges and rebuilding charges to "as new" condition. Call LEA International’s customer service department at 800.882.9110 for a return material authorization (RMA) number. No items will be accepted without a RMA number. Please have the following information on hand when calling for an RMA number: MODEL NUMBER FAILURE DESCRIPTION PART NUMBER INSTALLATION DATE PURCHASED DATE SYSTEM OPERATING VOLTAGE LEA JOB NUMBER 6