model : jm40uc

advertisement
DIESEL GENSET
MODEL : JM40UC
40 kW / 50 kVA
Stand-by Power @ 60Hz
36 kW / 45 kVA
Prime Power @ 60Hz
Standard Features :
•
•
•
•
•
•
•
•
•
•
•
•
•
Engine (JOHN DEERE , 3029TF150 )
Engine EPA Carb Charge alternator 12 V , Meca
Alternator (MECC ALTE , ECO 32 3S/4 )
Single bearing alternator IP 21 , insulation class H
/H
Radiator 50°C [122°F]°C max. T° air inlet with
coolant cap
Skid and vibration isolators
Dry type air filter
Main line circuit breaker
Microprocessor control panel
12 V battery, rack and cable
Industrial silencer (loose)
User manual
CSA Certified
GENERATOR RATINGS :
Voltage
480/277
440/254
240/120
230/115
220/127
208/120
HZ Phase P.F Standby Amps Standby Ratings kW/kVA Prime Ratings kW/kVA
60
3
0.8
60
40 / 50
36 / 45
60
3
0.8
66
40 / 50
36 / 45
60
3
0.8
120
40 / 50
36 / 45
60
3
0.8
100
32 / 40(40 / 50*)
29 / 36(36 / 45*)
60
3
0.8
131
40 / 50
36 / 45
60
3
0.8
128
37 / 46
33 / 42
* Rating Available with the oversized alternator option
Stand-By ratings are available for the duration of any power outage. No overload capacity is specified at this ratings. Prime ratings are
available per BS 5514, DIN 6271, ISO-3046 and IEC 34-1 with 10% overload capacity one hour in twelve hours.
SDMO provides a full line of products with high quality
recognized engines and alternators.
Service and parts are available from SDMO distributors as a
single source of responsibility
avr.-03
1/5
Each and every units is factory tested. All generator sets are
also prototype tested.
Two years limited warranty , please refer to the conditions
terms . Five years extended are also available.
JM40UC - C
specifications and design liable to modifications without prior notice
DIESEL GENSET
MODEL : JM40UC
ENGINE DATA
Manufacturer / Model
Cylinder Arrangement
Displacement
Bore and Stroke
Compression ratio
Rated RPM
Piston Speed
Max. stand by Power at rated RPM
Frequency regulation, steady state
BMEP
Governor : type
Exhaust System
Fuel System
Oil System
JOHN DEERE 3029TF150 , 4-cycle, Turbo , N/A
3 XL
2.9L [177.0C.I.]
106mm [4.2in.] X 110mm [4.3in.]
17,8:1
1800 Rpm
6.6m/s [21.7ft./s]
44.5kW [60BHP]
+/-2, 5%
11.19bar [162psi]
Meca
Exhaust gas flow
Exhaust temperature
Max back pressure
138L/s [292cfm]
517°C [963°F]
625mm CE [25in. WG]
110% (Stand By power )
100% (of the Prime Power)
75% (of the Prime Power)
50% (of the Prime Power)
Total fuel flow
14.93L/h [3.9gal/hr]
13.11L/h [3.5gal/hr]
10.1L/h [2.7gal/hr]
6.91L/h [1.8gal/hr]
108L/h [28.5gal/hr]
Total oil capacity w/filters
Oil Pressure low idle
Oil Pressure rated RPM
Oil consumption 100% load
Oil capacity carter
6L [1.6gal]
1bar [14.5psi]
5bar [72.5psi]
0.01L/h [0.0gal/hr]
5.3L [1.4gal]
Heat rejection to exhaust
Radiated heat to ambiant
Heat rejection to coolant
43kW [2445Btu/mn]
5kW [284Btu/mn]
28kW [1592Btu/mn]
Thermal balance 10% load
Air intake
Max. intake restriction
Engine air flow
300mm CE [12in. WG]
138L/s [292cfm]
Radiator & engine capacity
Max water temperature
Outlet water temperature
Fan power
Fan air flow
Available restriction on air flow
Type of coolant
Thermostat
16.1L [4.3gal]
105°C [221°F]
93°C [199°F]
2 kW
2.34m3/s [4959cfm]
20mm CE [0.8in. WG]
Gencool
82-94 °C
Coolant System
Emissions
HC
CO
Nox
PM
avr.-03
0.41 gr/bhp/h
0.77 gr/bhp/h
6.12 gr/bhp/h
0.22 gr/bhp/h
2/5
JM40UC - C
specifications and design liable to modifications without prior notice
DIESEL GENSET
MODEL : JM40UC
ALTERNATOR SPECIFICATIONS
•
•
•
Compliance with NEMA MG21, UTE NF C51.111, VDE
0530, BS 4999, CSA standards.
Vacuum-impregnated windings with epoxy varnish.
IP21 drip proof.
ALTERNATOR DATA
Manufacturer / Type
Number of phase
Power factor (Cos Phi)
Altitude
Overspeed
Pole : number
Exciter type
Insulation : class, temperature rise
Voltage regulator
Sustained short circuit current
Total harmonics (TGH/THC)
Wave form : NEMA = TIF – TGH/THC
Wave form : CEI = FHT – TGH/THC
Bearing : number
Coupling
Voltage regulation 0 to 100% load
Recovery time (20% Volt dip) ms
SkVA with 90 % of nominal sustained voltage (at 0.4 PF)
MECC ALTE ECO 32 3S/4
3
0.8
1000
rpm
4
No
H /H
AVR
1
Direct
ms
N/A
OTHER ALTERNATOR DATA
Continuous nominal rating @ 40°C
Standby rating @ 27°C
Efficiencies @ 4/4 load
Air flow
Short circuit ratio;50 (Kcc)
Direct axis synchro reactance unsaturated (Xd)
Quadra axis synchro reactance unsaturated (Xq)
Open circuit time constant;50 (T’do)
Direct axis transient reactance saturated (X’d)
Short circuit transient time constant (T’d)
Direct axis subtransient reactance saturated (X’’d)
Subtransient time constant (T’’d)
Quadra axis subtransient reactance saturated (X’’q)
Zero sequence reactance unsaturated (Xo)
Negative sequence reactance saturated (X2)
Armature time constant (Ta)
No load excitation current (io)
Full load excitation current (ic)
Full load excitation voltage (uc)
Recovery time (Delta U = 20% transitoire)
Motor start (Delta = 20% perm. Or 50% trans.)
Transient dip (4/4 charge) – PF : 1.8 AR
No load losses
Heat rejection
avr.-03
48 kVA
52.8 kVA
88.8 %
14.5m3/s [30723.62cfm]
0.8
190 %
98 %
1.4 ms
14.3 %
61 ms
10 %
15 ms
30.6 %
2.7 %
21.5 %
31 ms
A
A
V
ms
kVA
%
kW
kW
3/5
JM40UC - C
specifications and design liable to modifications without prior notice
DIESEL GENSET
MODEL : JM40UC
M150 CONTROL PANEL
Manual starting Panel type M150
Standard features :
4 positions contact key ,AC voltmeter, AC ammeter, Emergency Stop Button,
Genset Breaker.
Engine shutdown :
Oil pressure, High water temperature.
Engine parameters :
Running timer.
Telys CONTROL PANEL
TELYS Microprocessor control panel Type S2500 to S5000 (depending of the breaker size).
Standard features :
AC voltmeter, AC ammeter, Frequency meter.
Engine shutdown :
Oil pressure, High water temperature, Low water level, Overspeed, Overcrank,
Emergency Stop Button.
Engine parameters :
Oil pressure, Water temperature, Fuel level, Running time meter, Battery voltage,
RS485 Communication for remote management (software is an option).
avr.-03
4/5
JM40UC - C
specifications and design liable to modifications without prior notice
DIESEL GENSET
MODEL : JM40UC
OPTIONS
Engine and Radiator
Isochronous governor
Heat shield protection
Oil drain extension
Heavy duty air filter
Lube oil drain pump
Radiator core guard
Battery charger
Block heater
Fuel
Day tank
Subbase fuel tanks UL
Water separator fuel filter
Alternator
Anti condensation heater
Enforced impregnation
Oversized alternator
Exhaust
Residential silencer
Critical silencer
Flexible exhaust conn.
Enclosure M107
Silent 71db @ 23 Ft (stby)
Control panel
NFPA 110 level 1
Paralleling system
Remote annunciator
Oil temperature shutdown
Key start panel
Literature
Parts
Maintenance
WEIGHT AND DIMENSIONS
Open model
Overall size l x w x h :
1520mm [60in] x 780mm [31in] x 1180mm [46in]
Weight :
780kg [1719lbs] Net 890kg [1962lbs] Gross
WEIGHT AND DIMENSIONS With optional Enclosure
Open model
Overall size l x w x h :
2100mm [83in] x 920mm [36in] x 1330mm [52in]
Weight :
1115kg [2457lbs] Net 1225kg [2700lbs] Gross
SDMO industries - Head Office - 12 rue de la Villeneuve - BP 241 - 29272 BREST cedex FRANCE - www.sdmo.com
avr.-03
5/5
JM40UC - C
specifications and design liable to modifications without prior notice