Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 PROTECTION PERFORMANCE OF LIGHTNING PROTECTION SYSTEMS UNDER SWITCHING SURGE VOLTAGES Z. Faydalı1, A. Ozdemir1*, S. lhan1 Separtment of Electrical Engineering, Istanbul Technical University, Maslak-Istanbul 34469, Turkey *Email: ozdemir@elk.itu.edu.tr 1 Abstract: Using (Franklin) Air Terminals to control and divert lightning discharges is still indispensable method after 200 years of usage. Still, there are several uncertainties regarding the discharge mechanism of the lightning phenomena that lead to variety of lightning protection systems. Early Streamer Emission (ESE) Air Terminals and Charge Transfer Systems (CTS) have evolved from these uncertainties. This study presents the experimental performance of CTS against ordinary Franklin Air Terminal based protection systems under the same electrogeometric conditions. Their comparative advantages and disadvantages are illustrated according to the results of corona emission current tests, comparative tests under the same electrogeometrical conditions and critical switching impulse flashover voltage tests. These tests are conducted at High Voltage Laboratory of Istanbul Technical University for several different electrode spacing at different DC polarization conditions. 1. There are still several uncertainties regarding the discharge mechanism of the lightning phenomena that lead to variety of lightning protection systems. Therefore, experimental and observational researches performed to solve the lightning protection problem are still ongoing [5]. INTRODUCTION Lightning protection systems are used to eliminate or minimize the direct and indirect effects of lightning strikes. The effects of lightning that were taken into consideration when designing a protection system were limited with fire and life risk at old times. However, technological developments and improved life standards require an expanded scope of protection. The objective of this paper is to compare and illustrate the advantages and disadvantages of the Charge Transfer Systems and ordinary Franklin Air Terminal based protection systems with respect to the results of several experimental studies; namely, critical flashover (CFO) voltage tests, comparative tests under the same electrogeometrical conditions and corona emission current tests. The tests are chosen similar those presented in previous studies in order to make fair comparisons. It is obvious that the comparisons and the derived conclusions are limited with the scope of the tests. The first commonly used Lightning Protection System (LPS) is the capturing rod (which is also known as Franklin rod named after Benjamin Franklin) which aims to capture the lightning and to direct it to the ground through the conductors and grounding system [1]. After long and detailed analysis of the protection system performances, Franklin rods have taken their final forms today. Their performances are improved by using them together with Faraday Cage structures [2]. 2. Early Streamer Emission (ESE) systems are later developed and are claimed to improve the capturing performance of ordinary Franklin rods by using different types of triggering mechanisms. It is claimed that the triggering mechanism increases the efficiency of lightning attraction and extends the range of protection [3]. However, scientific and technical basis of the system is open to some questions and they are still not accepted by most of the authorities. CRITICAL FLASHOVER VOLTAGE TESTS Charge transfer systems consist of multi point discharge paths assigned to neutralize the thundercloud and minimize the risk of charge transfer between the cloud and the earth [4]. The charges emitted by these multi point paths are also assumed to shield the area over the air terminal and to prevent lightning strike nearby objects and areas [5]. CFO voltage tests are performed in order to investigate and to compare the differences due to the emitted charges. Charge Transfer Systems (CTS) are one of the last approaches in Lightning Protection. Their operating principle is based on multi point discharges that are created by means of many sharp electrodes. By the charge created in opposite polarity to the charges in the thundercloud, the thundercloud is claimed to be neutralized and the specified region is prevented from direct lightning strikes [4]. Two types of CTSs and a Franklin rod (standard lightning rod) given in Figure 1 are tested. A plane electrode of 5m x 3.5m is used to simulate the cloud. Air terminals are installed at four different heights under the plane electrode; namely, 2 m, 3 m, 3.5 m and 4 m. The negative standard switching impulse test Pg. 1 Paper G-32 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 voltages (300/2500 µs) are applied between the plane electrode and the air terminals for all electrode configurations and spacing (Figure 2). The critical flashover voltages (CFO) of air terminals are determined by up-down method described in IEC 60060. (a) (b) 3. COMPERATIVE TESTS UNDER THE SAME ELECTROGEOMETRICAL CONDITIONS The three protective devices are subjected to comparative tests under the same electrogeometrical conditions. The aim of this test is to strengthen of the conclusions derived from flashover voltages as well as to derive final conclusions with the aim of supporting test results. Three protective devices are placed under a plane electrode of 3.5*5 m. They are placed symmetrically and equidistant from the centre of the plane electrode (Figure 3) to provide the same electrogeometrical conditions. 100 standard switching impulse voltages of negative polarity are applied to the plane electrode for each of three different electrode spacing. The test voltages are chosen to be higher than the CFO voltages of the protective systems. (c) Figure 1: Photographs of the air terminals tested. a – Franklin rod b – CTS 1 c – CTS 2 The CFO voltages of air terminals for all electrode spacing are shown in Table 1. A quick check of the table shows that there are not significant differences between the CFO voltages of the Franklin rod and of the CTS 2, while CFO voltages of CTS 1 are noticeably higher than those of the others’. Table 1: CFO voltages for switching impulse voltages. Figure 3: Positioning of the air terminals under the plane electrode. CFO (kVpeak) Electrode Franklin Spacing (m) CTS 1 CTS 2 rod 2 -838 -1036 -914 3 -1370 -1559 -1400 3.5 -1659 -1765 -1676 4 -1874 -2103 -1915 The tests are carried out for several test voltages. The results are approximately the same. Therefore, the results of only one test voltage is illustrated for each spacing in Table 2. Photographs of the flashovers are given in Figure 4. Table 2: Number of flashovers between the plane electrode and the protective systems. Number of Discharges Gap [m] / Applied Voltage [kVpeak] 2 / 1200 3 / 1750 4 / 2200 Franklin rod 86 92 87 CTS 2 14 8 13 CTS 1 0 0 0 Figure. 2: Negative switching impulse test voltage (300 / 2500 µs). Pg. 2 Paper G-32 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 (a) (a) (b) (b) Figure 4: Photographs of the comparative tests under the same electrogeometrical conditions. (a) Flashover to CTS 2 (b) Flashover to Franklin rod As it can easily be realized from the table, all the flashovers from the plane electrode occurred either to the CTS 2 or to the Franklin rod. The ratio of the discharges to CTS 2 and to Franklin rod does not significantly differ for different electrode spacing. 4. (c) CORONA EMISSION CURRENT TESTS Corona emission current is thought to block the formation of upward discharge by causing a delay for the attachment process of lightning [5]. Therefore, it is generally accepted as an index of the protective effectiveness of a CTS. (d) Standard switching impulse test voltages (300 / 2500 µs) of both the positive and the negative polarity are individually applied between the plane electrode and air termination system. The tests are repeated for several different amplitudes of the test voltages for 2 m, 3 m and 4 m electrode spacings. For the sake of higher accuracy, each test voltage is applied three times and their average is recorded as a result. The results are shown graphically in Figure 4. (e) The corona emission currents of CTS 1 and CTS 2 are found to be close to each other and also seem to be considerably higher than the emission currents recorded for Franklin rod. Pg. 3 Paper G-32 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 (f) The results of these tests can be stated as DC polarization has no significant effect on the number of discharges attracted by CTS 1. Figure 5: Corona Emission Currents for switching impulse voltages. (a) (b) (c) (d) (e) (f) 5. 3.1 Corona emission current tests with DC polarization Electrode spacing: 2 m, Polarity of voltage: + Electrode spacing: 2 m, Polarity of voltage: Electrode spacing: 3 m, Polarity of voltage: + Electrode spacing: 2 m, Polarity of voltage: Electrode spacing: 2 m, Polarity of voltage: + Electrode spacing: 2 m, Polarity of voltage: -) DC part of the test setup is used alone and corona emission currents are measured for 2 m, 3 m and 4 m of electrode spacings. DC voltages providing a constant electric field strength around 15 kV/m are applied between the plane electrode and the air terminals. The measured corona emission currents are in the order of µA and are smaller than one thousandth of the previous ones for switching impulses. Therefore, switching impulses superimposed on DC voltages are not used to perform another comparative test. TESTS WITH DC POLARIZATION Since there is a constant electric field between the cloud and the earth during the formation of real lightning phenomena, all the previous tests are repeated for DC polarization between the plane electrode and the air terminal. The value of the field strength is chosen in the range of 10 - 25 kV/m as in similar studies [5]. 6. CONCLUSIONS CFO voltage tests with DC polarization show that there are no significant differences between CFO voltages without DC polarization. Therefore they will not be reproduced here. In order to compare the protective performance of CTS systems and ordinary Franklin Air Terminal based protection systems several experiments have been conducted. 3.1 The results of the CFO voltage and comparative tests, with and without DC polarization, showed that CTS 1 provided better protection performance than the Franklin rod under the same electrogeometric conditions. However, CFO voltages of CTS1 are not much higher than of the Franklin rod to claim that CTS1 will effectively eliminate direct strikes on it. On the other hand, no distinction could be made for the Franklin rod and CTS 2 as they showed similar performances during the experiments. Comparative tests under electrogeometrical conditions the same 100 negative standard switching impulse voltages are applied to the plane electrode which is polarized with a DC voltage to provide a constant electric field of 17.5 kV/m. Flashovers to the three protection systems which are placed symmetrically under the plane electrode (Figure 3) are recorded for an electrode spacing of 2 m. (Table 3). Table 3: The number of discharges occurred for the air terminals. Since the corona emission currents of CTS 1 and CTS 2 were close to each other and were noticeably higher than of the Franklin rod, protection performance of CTS1 and CTS 2 were expected to be similar and also much better than of the Franklin rod. However, this contradicted with the results of previous CFO voltage test and comparative tests. This contradictory behavior of CTS 2 brought out two important facts: Number of Discharges Gap [m] / Applied Voltage [kVpeak] 2 m / 1200 kVpeak Franklin rod 56 CTS 2 44 CTS 1 0 Although the tests are also carried out for several different spacing as well as for several different test voltage magnitudes, only a representative one will be given here. Corona emission current was not a reliable index itself to determine the effectiveness of a LPS. CTSs based on the same technical and physical laws behaved differently at similar tests. It can be concluded from the test results that the charge transfer systems are not reliable protective systems from the point of eliminating the direct lightning strikes yet. In addition, their construction and shape affect their protection performance. If the number of discharges given for a spacing of 2 m and a test voltage of 1200 kVpeak is compared with the test results without DC polarization, at a first glance an increase in the number of strikes to CTS 2 can be seen. However, all the discharges are still shared between the Franklin rod and CTS 2. None of the test voltages have resulted a flashover to CTS1. An appropriate design that combines Franklin rods and CTS seems to provide better performance to protect a region against lightning. A CTS placed at an elevated Pg. 4 Paper G-32 ISBN 978-0-620-44584-9 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° position of the protective area will reduce the likelihood of direct lightning strikes onto the region. Additional Franklin rods installed at elevated positions surrounding the protective region captures the lightning strikes and therefore provides additional protection for the protective region. 7. ACKNOWLEDGMENTS The authors would like to thank to Fuat Kulunk High Voltage Laboratory staff for their patient supports during the tests. 8. REFERENCES [1] J.M. Tobias, “The basis of conventional lightning protection systems”, IEEE Transactions on Industry Applications, Volume 40, No. 4, July-Aug. 2004, pp. 958 – 962. [2] D.W. Zipse, “Lightning protection systems: advantages and disadvantages.” Petroleum and Chemical Industry Conference, Record of Conference Papers. The Institute of Electrical and Electronics Engineers Incorporated. Industry Applications Society, 40th Annual 13-15 Sept. 1993, pp.51 - 64. [3] R.J. Van Brunt, T.L. Nelson, K.L. Stricklett, “Early streamer emission lightning protection systems: An overview. IEEE Electrical Insulation Magazine, Volume 16, No. 1, Jan.Feb. 2000, pp. 5 – 24. [4] D.W. Zipse, “Lightning protection methods: an update and a discredited system vindicated”, IEEE Transactions on Industry Applications, Volume 37, No. 2, March-April 2001, pp. 407 – 414. [5] J.B. Lee, S.H. Myung, Y.G. Cho, S.H. Chang, , J.S. Kim, G.S. Kil, Experimental study on lightning protection performance of air terminals, International Conference on Power System Technology, 2002. Proceedings. PowerCon2002. Volume 4, 13-17 Oct. 2002, pp. 2222 - 2226. Pg. 5 Paper G-32