sEcTtoN 16140

advertisement
sEcTtoN 16140
WIRING DEVICES
PART
1
GENERAL
1.01 SUMMARY
A.
B.
1.02
1.
2.
3.
Related Sections:
The Contract Documents are a single integrated document, and as such all
Divisions and Sections apply. lt is the responsibility of the CONTRACTOR and
its subcontractors to review all sections to ensure a complete and coordinated
project.
1.
REFERENCES
A.
B.
C.
D.
1.03
Section includes requirements for:
Switches.
Receptacles.
Plates.
Referto Section 16050Undenryriters Laboratories lnc. (UL):
1.
2.
3.
4.
5.
20 - General use Snap Switches.
498 - Standard for Attachment Plugs and Receptacles.
514D - Cover Plates for Flush-Mounted Wiring Devices.
943 - Standard for Safety for Ground-Fault Circuit-lnterrupters.
1474 - Solid State Dimming Control.
National Electrical Manufacturers Association (NEMA):
WD1 - General color requirement for wiring devices.
ICS 5 - Control circuits and pilot devices.
OS1 - Device box, covers, and box supports.
WD6 - Wiring devices dimensional requirements.
1.
2.
3.
4.
FederalSpecification:
W-C 596.
W-S 896.
1.
2.
DEF¡NITIONS
A.
B.
Refer to Section 16050-
SpecificDefinitions:
GFCI: Ground Fault Circuit lnterrupter.
P-S: Pass and Seymour.
CWD: Cooper Wiring Devices.
T&B:Thomas and Betts.
1.
2.
3.
4.
APRIL 2O1O - FINAL
16140-1
X/Fort Worth/820541 O/Spec¡fi ôat¡ons/1 6140 (Final (cleana))
8205410
1.04
SYSTEM DESCRIPTION
A.
I.O5
SUBMITTALS
A.
B.
C.
1.06
Shop Drawings:
Engraving Schedule:
Furnish complete engraving schedule for engraved nameplates.
1.
a.
Refer to Sectíon 16050.
Wiring devices shall be UL listed and labeled.
Refer to Section 16050.
Refer to Section 16050.
WARRANW
A.
I.IO
1.
PROJECT OR SITE CONDITIONS
A.
1.09
Product Data:
Catalog cut sheets.
DELIVERY, STORAGE, AND HANDLING
A1.08
Furnish submittals in accordance with Sections 01300 and 16050.
QUALITY ASSURANCE
A.
B.
1.07
Switches, receptacles, and plates as indicated on the Drawings wired and operable
to form a complete system.
Refer to Section 16050.
SYSTEM START.UP
A.
Refer to Section 16050.
PART
2
PRODUCTS
2.01
MANUFACTURERS
A.
Switches:
General purpose toggle switches, one of the following or equal:
Part numbers are for brown switches:
1.
a.
1-pole 2-pde 3-wav
Hubbell HBL 122'l HBL 1222 HBL 1223
Leviton 1221-2 1222-2 '1223-2
cwD
4901
4902
4903
APRIL 2010 -
FINAL
pwJ/Carollo/Documents/ClienUTXFort
Worth/820541 0/Specifications/1
16140-2
61
40 (F¡nal (cleana))
4-wav
HBL 1224
1224-2
4904
8205A10
2.
3.
4.
Switches for NEMA 4 and NEMA 4X locations, one of the following or equal:
1-pole
2-pole
3-wav
4-wav
Hubbell
HBL 1281
HBL 1282
HBL 1283
HBL 1284
Cooper
Wiring
Devices
2291
2292
2293
2294
Switches for office areas, one of the following or equal:
1-pole
2-pole
3-wav
4-wav
Hubbell
HBL2121l
HBL2122l
HBL2123t
HBL2124t
CWD
5621-2
5622-2
5623-2
5624-2
Switches for photocells, one of the following or equaf:
Sinqle-pole. double-throw
5.
B.
Hubbell
HBL 1385
CWD
2226
Dimmer switches:
Rectangular design wíth LED light level indicators:
1) Lutron MAESTROTM MA-1000 controller for incandescent light.
2) Lutron MAESTROTM MALV-1000 controllerfor magnetic low-voltage
ights.
3) Lutron MAESTROTM MA-R remote for additíonalcontrol stations.
a.
Receptacles:
1. General purpose receptacles, one of the followíng or equal:
a. Part numbers are for brown receptacles.
2.
3.
Sinole
Duplex
GFCI
Weather
Resistant
GFCI
Hubbell
HBL5361
HBL5362
GF5362A
GFR5362SG
Leviton
5361
5362
6899
w7899-W
CWD
53618
53628
HGF2OB
WRVGF2OW
250 VAC receptacles, one of the following or equal:
Hubbell: H815462.
Cooper wiring devices: 54628.
480-Volt, 3-Phase receptacles:
30 Ampere:
Crouse-HindsARE3423.
Hubbell Hubbellock@ 21420.
a.
b.
a.
APRIL 2O1O - FINAL
pwJ/Carollo/Documents/Client/IX/Fort
1)
2)
16140-3
Worth/820541 0/Specifcaùons/'l 6'140 (Final (cleana))
8205410
b.
C.
3) RussellstolrM DF3404FRAB.
60 Ampere:
1) Crouse-HindsAREA6425.
2) Hubbell Hubbellock@ 26410 or 26420 with 26401 box and 26404
adapter.
3) RussellstolrMDF6404FRAB.
Plates:
1. General location, one of the following or equal:
a. Provide plates with number of gangs as required:
Standard
Office
P-S
2.
Switches Switches
SS1-N
5526
Duplex
SS8
WPH26
Wet or corrosive areas, one of the following or equal:
Outdoor
lndoor
Duplex
Corrosive
Locations
CA8-GH
3780-SC
Switcheg Receotacles Receptacles
Hubbell
T&B
P-S
2.02
GFCI
Receptacles Receptacles
1750
CCT
CAI-GL
CKMD
MANUFACTUREDUNITS
A.
Switches:
1. General:
a. 120-277 VAC.
b. 20 Ampere.
c. Specificationgrade.
d. Back and side wired unless othenryise indicated.
e. lntegralgroundingterminal.
f.
Totally enclosed:
1) Color-coded body with color corresponding to ampere rating.
g. Provide switches with the operator style and contact arrangement as
indicated on the Drawings and as required for proper operation.
h. Color:
1) lvory.
2. General purpose switches:
a. Toggle type.
3. Corrosive and wet areas requiring NEMA 4 or NEMA 4X enclosures:
a. Toggle switch.
b. Back and side wired.
4. Switches for office areasl
a. Rocker type.
b. Rectangular
5. Switches for use with photocell:
a. Maintained contact.
APRTL 2010
-
FINAL
16140-4
pwJ/Carolloi Documents/ClienUTX/Fort Worlh/820541 0/Specifications/1 6140 (Final (cleana))
8205A10
b.
c.
6.
Two circuit.
Three position:
1) Center off.
Dimmer switches shall be rectangular design wíth LED light level indicators:
a. Lutron MAESTROTM MA-1000 controller for incandescent light.
b. Lutron MAESTROTM MALV-1000 controller for magnetic low-voltage
lights.
c. Lutron MAESTROTM MA-R remote for additional control stations.
B.
Receptacles:
1. General purpose receptacles:
a. Single or duplex as indicated on the Drawings.
b. 125 VAC.
c. 20 Ampere or as indicated on the Drawings.
d. NEMA 5-20R configuration for 20 Ampere receptacles.
e. Other NEMA configurations as indicated on the Drawings.
f.
Specification grade.
g. Back wired.
h. One-piece mounting strap.
i. Color:
1) lvory.
2) Orange when powered by a UPS.
2. Ground Fault lnterrupter Receptacles (GFCI):
a. 125VAC.
b. 20 Ampere.
c. Trip level4-6 milliampere.
d. lndividual and feed through protection.
e. UL 943 and UL 498 listed.
f.
NEMA 5-20R configuration.
g. For damp or wet locations:
1) Weather Resistant, in accordance with UL 498.
3. 480 VAC receptacles:
a. 3-Pole, 4-wire grounding.
b. Ampere rating as indicated on the Drawings.
c. Spring door on receptacle.
d. Furnish one matching plug for each 480-volt power receptacle.
C.
Plates:
1. General location:
a. Type 302 or 304 stainless steel.
b. Brushed satin finish.
c. Minimum thickness: 0.032 inches.
d. Rectangular or square shape.
e. Engraving:
1) Engrave each plate with the following information:
a) Area served.
b) Circuit number.
2) Treat engraving to improve visibility and, except for stainless steel
plates, to prevent corrosion.
3) Characters shall be block letter pantograph engraved with a
minimum character height of 1/8-inch.
APRIL 2010 -
FTNAL
pwJ/Carollo/Documents/ClienUTXFort
16140-5
Worth/8205410/Specificalions/1 6'140 (Final (cleana))
8205410
t.
2.
3.
D.
Coordinate the number of gangs, number and type of openings with the
specific location.
Outdoor and wet areas requiring NEMA 4 or NEMA 4X enclosures:
a. General:
1) UL listed for wet locations.
2) Gasketed.
3) Die cast metal:
a) Match materialto box material.
b. Switches:
1) Lever-operated.
Corrosive Areas:
a. Neoprene.
b. Gasketed.
c- Weatherproof.
Data and communications jacks:
a. Process network jacks - panel/enclosure mounted:
1) Network jacks located in process areas shall have a NEMA 4 rating
(with closure cap).
2) Mounting of network jacks in control panels shall be accomprished
using bulkhead connectors and environmentalenclosure caps, which
are permanently attached to the bulkhead fitting.
3) Network jacks shall have RJ-45 connections on both sides of
connector (bulkhead pass through) allowing for direct connection to
the network switch and computer with standard patch cords. No
punch down PC board connections shall be allowed.
4) Manufactured by Woodhead Connectívity RJLNXX:
2. Process network jacks - conduit body mounted:
a. Network jacks located in process areas shall have a NEMA 4 rating (with
closure cap).
b. Mounting of network jacks in conduit bodies adapter (with Minifast
connector) shall be accomplished using conduit body insert and
environmental enclosure caps.
c. PC board connections are not to be allowed.
d. Furnish 10 RJ-45 to minifast connector patch cable 3 feet in length.
e. Manufactured by lnterlinkBT RSS series.
3. Network/phonejacks:
a. Network jacks located in computer rooms shall be installed per the
installation details in the drawings.
b. Standard Decora wall plates shall be used with QuickPort modules and
inserts.
c. Plugs shall be color coded as indicated in the installation details in the
Drawings.
d. Manufactured by Leviton Quickport seríes.
PART
3
3.OI
INSTALLATION
A.
EXECUTION
Refer to Section 16050.
APR| L 2010 -
FTNAL
pw://Carollo/Docurnents/ClienUTX/Fort Worlh/820541 0/Specilrcations/1
16140-6
6140 (F¡nat (cleena))
8205A10
3.02
B.
Mounting heights:
1. Process and production areas
a. Switches and receptacles 42 inches from finished floor to center of plate.
2. Offices and finíshed areas:
a. Switches: 42 inches from finished floor to center of plate.
b. Receptacles: 18 inches from finished floor to center of plate.
C.
Switches:
1. Over 300 Volts:
a. Where switches used in systems of more than 300 volts between
conductors, are to be ganged in outlet boxes, provide switches having no
exposed live parts or use barriers between the individual switches.
D.
Receptacles:
1. Provide GFCI receptacles as indicated on the Drawings.
a. Provide weather resistant GFCI receptacles in all wet or damp areas.
1) Refer to 16050.
2. Mountnon-weatherproofreceptaclesvertically:
a. Ground slot up.
3. Mountweatherproofreceptacles horizontally:
a. Neutral slot up.
4. 3-phase receptacles shall be consistent with respect to phase connection at
the receptacle terminals. Conect errors in phasing at the source and not the
receptacle.
E.
Ensure all plates make a firm sealwith wallfor recessed mounted devices:
1. Outside edges of plates parallel with building lines.
FIELD QUALIW CONTROL
A.
3.03
Refer to Section 16050.
DEMONSTRATION AND TRAINING
A.
B.
Referto Section 16050.
Demonstrate the following to the ENGINEER and OWNER:
1. Switching is per the Drawings.
2. All circuits conform to the panel schedules.
3. All ground fault receptacles operate at levels below or equal to OSHA
maximum allowable fault levels.
3.O4 PROTECTION
A.
\
Refer to Section 16050.
END OF SECTION
APRIL 2O1O - FINAL
16140-7
X/Fort Worth/8205410/Specif¡cations/1 6140 (Final (cleana))
8205410