Ü INDEX SECTION 1 1.1.1 1.2.1 1.3.1 1.4.1 INTRODUCTION Welcome Registration Form Terms of Usage Disclaimer SECTION 2 2.1.1 2.2.1 2.3.1 2.4.1 PADMOUNTED SWITCHGEAR / FUSEGEAR Padmounted Fuse Gear (Deadfront), Model SFGD Padmounted Switchgear (Deadfront), Model SPD Padmounted Switchgear (Livefront), Model SPL, (2/4 Circuit) Padmounted Switchgear (Livefront), Model SSGL, (6 Circuit) SECTION 3 3.1.1 3.2.1 PADMOUNTED PRIMARY METERING GEAR Padmounted Primary Metering (Deadfront), Models SPMD and SPMG Padmounted Primary Metering (Livefront), Model SPML SECTION 4 4.1.1 4.2.1 4.3.1 PADMOUNTED CABLE TERMINATING GEAR Padmounted Cable Switching Gear (Deadfront), Model SCSD Cable Terminating Gear, Models STEN, STEI, STMV, STEC1 and STEC2 Padmounted Telephone Cable Splicing Enclosures, Model SECL (Future Release) SECTION 5 5.1.1 5.2.1 5.3.1 5.4.1 5.5.1 5.6.1 CAPACITOR BANKS / POWER FACTOR CORRECTION Padmounted Capacitor Banks (Deadfront and Livefront), Models SCBD and SCBL Metal-Enclosed Capacitor Banks, Model SCBM, Types M1 and M2 Metal-Enclosed Multi-Step Capacitor Banks, Model SCBM, Types S1 and S2 Metal-Enclosed Harmonic Filter Capacitor Banks, Model SCBM, Type H1 (Future Release) Surge Capacitor Banks (Future Release) RTXTM RT and FR Active Power Factor Correction (Future Release) SECTION 6 6.1.1 6.2.1 6.3.1 6.4.1 6.5.1 6.6.1 6.7.1 SWITCHGEAR / PARALLELING SWITCHGEAR Metal-Enclosed Switchgear, Model SMEG Metal-Enclosed Wall-Hung Switch/Fuse Enclosures, Model SWHG Metal-Clad and Metal-Enclosed/Clad Switchgear, Models SMCG and SMECG Paralleling / Generator Control Switchgear (Future Release) DGXTM Distributed Generation Transfer Switchgear (Future Release) Utility Power Container Switchgear (Future Release) Utility Inter-Tie / Paralleling (Future Release) SECTION 7 7.1.1 7.2.1 7.3.1 7.4.1 7.5.1 7.6.1 REFERENCES Shallbetter Product Codes and Descriptions Terms and Conditions Glossaries (Future Release) Contacting Shallbetter Inc. Warranty Statement ANSI / IEEE Device Numbers © 2002 Shallbetter Inc. www.shallbetter.com 1.0.0 Ü Û INDEX Ü WELCOME to SHALLBETTER INC.’s PRODUCT CATALOG Welcome: Thank you for reviewing Shallbetter Inc.’s Product Catalog that contains our fine line of equipment for the following applications: n n n n n Power Generation Power Reliability Power Quality Power Distribution Power Transmission and Distribution — T & D Registration: If this catalog is registered in your name already — Thank you! New users — please take a moment to fill-out the registration form on next page and return it to Shallbetter (see “Contact Shallbetter” section). This will allow us to provide you with product updates, catalog revisions, and new information as they become available. Questions / Comments / Issues: Your feedback regarding this catalog, or any other questions that you may have, are extremely important to us. Please contact your authorized Shallbetter factory representative or Shallbetter directly (see “Contact Shallbetter” section). Catalog Doc. Number SICO1028A © 2002 Shallbetter Inc. www.shallbetter.com 1.1.1 Û INDEX Ü Û INDEX Ü DOCUMENT REGISTRATION FORM Document Information: Document Name: Product Catalog Today’s Date: ____/____/____ Document Number: Registered To: Salutation: p Mr. p Mrs. p Ms. First Name: ______________________ Title: ______________________ Address 1: ______________________ City: ______________________ State: ______________________ Telephone: ______________________ E-Mail: ______________________ SICO1028A Last Name: _______________________ Company: _______________________ Address 2: _______________________ Zip Code: Fax: _______________________ _______________________ Type of Company: p Consultant p End User p OEM p Distributor p Dealer p System Packager p GenSet Manufacturer p Utility p IPP p Other __________________________________________________ Products / Applications of interest: p Distribution Switchgear p Paralleling Switchgear p Power Quality p T & D p Padmount Gear p Metering p Controls p Other ____________________________ Registered By: p Customer or p Rep p Shallbetter Area Manager First Name: ___________________ Last Name: ___________________ Company: ___________________ Phone #: ___________________ p Other Shallbetter Thank You! © 2002 Shallbetter Inc. www.shallbetter.com 1.2.1 Û INDEX Ü Û INDEX Ü TERMS of USAGE This catalog and the information contained within is the exclusive copyright material of: Shallbetter Inc. 2050 South Oakwood Road Oshkosh, WI 54904-6308 or the appropriate copyright owner of documents as indicated. Your usage of the contents of this catalog in any format or media is conditional upon your acceptance of the following terms. If you do not accept the terms, refrain from using any of the contents, documents and/or information. Any unauthorized duplication or reproduction of this material without the express written consent of Shallbetter Inc. is strictly prohibited under penalty of law. All information, documents, graphics, white papers, brochures, software, etc. (collectively referred to as "documents") located in this catalog in any form or media format are copyrighted © by the applicable companies as indicated on the documents. Documents are the intellectual property of their creators and all rights are reserved by the appropriate companies unless noted otherwise. You are permitted to view the documents for conducting your normal course of business however all copyright notices shall remain intact. You may not re-distribute the documents in any way that may conflict with the copyright laws and notices. You may not use the documents in competition with, or to reverse engineer, the products or services of Shallbetter Inc. The documents are provided "as is". Documents are considered to be recommended guidelines. Documents may contain errors or omissions, and Shallbetter Inc., their employees, and other companies creating the documents, do not make any warranty, express or implied, or assume any legal liability or responsibility for the correctness, accuracy, completeness, or usefulness of the documents or any information that they contain. Shallbetter Inc. reserves the right to change the specifications in their respective documents or their contents from time to time without notice. © 2002 Shallbetter Inc. www.shallbetter.com 1.3.1 Û INDEX Ü Û INDEX Ü DISCLAIMER The following companies have granted permission to Shallbetter Inc. to reproduce printed material or reference trade names, trademarks or company logos and are referenced on the pages following their companies name. ABB - Asea Brown Boveri, Inc., Florence, South Carolina 29501 ............................................................................. Versa-Rupter .............................................................................................................................................................. 6.1.4 6.3.4 Cooper - Cooper Industries, Pittsburgh, Pennsylvania 15230 .................................................................................. NX .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. NXC .............................................................................................................................................................. 6.1.4 6.3.4 2.1.2 2.1.6 2.1.7 2.2.2 2.2.6 2.3.2 2.4.2 6.1.2 6.3.2 Cutler-Hammer - Cutler-Hammer, Pittsburgh, Pennsylvania 15220 .......................................................................... .............................................................................................................................................................. CL .............................................................................................................................................................. .............................................................................................................................................................. CLE .............................................................................................................................................................. .............................................................................................................................................................. RBA .............................................................................................................................................................. .............................................................................................................................................................. GE - General Electric Company, Fairfield, Connecticut 06430-5163......................................................................... .............................................................................................................................................................. EJ .............................................................................................................................................................. .............................................................................................................................................................. ........................................................................................................................................................ .............................................................................................................................................................. EJO .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. .............................................................................................................................................................. JKM-95 .............................................................................................................................................................. JVM-95 .............................................................................................................................................................. 6.1.4 6.3.4 6.1.2 6.3.2 6.1.2 6.3.2 6.1.2 6.3.2 6.1.4 6.3.4 2.1.2 2.2.2 6.1.2 6.3.2 2.1.2 2.2.2 6.1.2 6.3.2 3.1.7 3.1.7 Gould Shawmut - Gould Shawmut, Newburyport, Massachusetts 01950 ............................................................... Joslyn - Joslyn Hi-Voltage Corporation, Cleveland, Ohio 44105 6.1.4 © 2002 Shallbetter Inc. www.shallbetter.com 1.4.1 Û INDEX Ü Û INDEX Ü Kearney - Kearney, Atlanta, Georgia 30359 Type Q ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. Powercon - Powercon Corp, Severn, Maryland 21144 ............................................................................................... ............................................................................................................................................................. Raychem - Raychem Corporation, Menlo Park, California 94025 ............................................................................ S&C - S&C Electric Company, Chicago, Illinois 60626 .............................................................................................. ............................................................................................................................................................. SM .............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. .......................................................................................................................................................... SML ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. ............................................................................................................................................................. Square D - Square D, Smyrna, Tennessee, 37167....................................................................................................... ............................................................................................................................................................. 3M - 3M Electrical Products Division, Austin, Texas 78769 ...................................................................................... 1.4.2 2.1.2 2.2.2 2.3.2 2.4.2 6.1.2 6.3.2 6.1.4 6.3.4 2.4.5 6.1.4 6.3.4 2.1.2 2.2.2 2.3.2 2.4.2 6.1.2 6.3.2 2.1.2 2.2.2 2.3.2 6.1.2 6.3.2 6.1.4 6.3.4 2.4.5 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Single and Three Phase. Current-Limiting and Power Fuses. Application: Shallbetter model SFGD Padmounted Fusegear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electrical Code requirements. The Shallbetter SFGD Padmounted Fuse Gear is ideal for sectionalizing cables that require fused taps for single phase and three phase loads where group-operated switching (Shallbetter model SPL,SPD, SSGD, or SSGL switchgear) is not desired. This padmounted equipment may be operated as single phase, load-break switchgear utilizing the elbows for switching or it can be utilized in conjunction with conventional padmounted switchgear with group-operated switches (Shallbetter model SPL,SPD, SSGD, or SSGL switchgear). For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 2.1.1 Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Single and Three Phase. Current-Limiting and Power Fuses. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. 2.1.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Single and Three Phase. Current-Limiting and Power Fuses. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous Current (Load) ______/______ kV o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other _____kV, _______kV BIL o 200 amp o 600 amp o 200 amp o 600 amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o 5052-H32 Aluminum Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: ___________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Fuse Compartment Barriers: o 3/16", Glass Reinforced Polyester, (Standard). o 1/4", Clear Polycarbonate (Lexan), Replaces 3/16" Glass Reinforced Polyester Compartment Barriers. Fuse Extenders: o 15 kV, Code 4 to Code 6 o 15 kV, Code 5 to Code 6 o 25 kV, Code 6 to Code 9 o o o o o o o o Louvers for enclosure ventilation. Insulating "No-Drip" Compound. Applied to the inside surface of the enclosure roof to prevent condensation. Base Undercoating. Applied to the bottom 2" of the enclosure. REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. Note: Replace compartment barriers. Rodent Plate. Seals base of enclosure, (Fuse side only). Ground Bails. (Located on the deadfront). Interface Bushing Well Inserts (200 amp only). Specials: © 2002 Shallbetter Inc. www.shallbetter.com 2.1.3 Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Single Phase - Current Limiting Fuses. l l l l l For 5 kV applications, use 15 kV table. For fuse selection, refer to Catalog Number Selection Sheet, (Page 2.1.2) or consult factory for assistance. H1 and H2 dimensions are typical of NX clip style fusing (Code 6). Fuse extenders are required for code 4 and 5 fuses. For special configurations and sizes, consult factory. 2.1.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Three Phase - Current Limiting Fuses. l l l l l For 5 kV applications, use 15 kV table. For fuse selection, refer to Catalog Number Selection Sheet, (Page 2.1.2) or consult factory for assistance. H1 and H2 dimensions are typical of NX clip style fusing (Code 6). Fuse extenders are required for code 4 and 5 fuses. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 2.1.5 Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Single Phase - Power Fuses. l l l For 5 kV applications, use 15 kV table. For fuse selection, refer to Catalog Number Selection Sheet, (page 2.1.2) or consult factory for assistance. For special configurations and sizes consult factory. 2.1.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED FUSEGEAR (DEADFRONT) Model SFGD, 5-35 kV. Three Phase - Power Fuses. l l l For 5 kV applications, use 15 kV table. For fuse selection, refer to Catalog Number Selection Sheet, (page 2.1.2) or consult factory for assistance. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 2.1.7 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 2.1.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD, 2/4 Circuit, 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Application: Shallbetter Inc. model SPD Padmounted Switchgear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electrical Code requirements. The Shallbetter SPD Padmounted Switchgear is intended for use as underground cable protection, distribution transformer protection, and fused or non-fused sectionalizing and switching where three phase, load-break switching is desired. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 2.2.1 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD, 2/4 Circuit 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current-Limiting and Power Fuses. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. 2.2.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD, 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current-Limiting and Power Fuses. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) ____/____ kV o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL Continuous Current (Line) o o o o Continuous Current (Load) 200 600 200 600 amp amp amp amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel Exterior/A60 Galvanneal Steel Interior o 304L Stainless Steel Exterior and Interior Paint Finish: o Green Munsell No.,7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other:__________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155 Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Base Spacer : ____”H. o A60, Galvanneal Steel construction o 304L, Stainless Steel construction o Base Adapter to fix existing pad, consult factory. o Cable Support Rails. o Fault Indicator Provisions. o Base Undercoating. Applied to the bottom 2” of the enclosure. o Key Interlocks: o Prevents paralleling of source switches, (Models SPD6, SPD9, SPD10, SPD11, SPD13A). o Prevents opening fuse doors when source switches are closed, (Models SPD5, SPD6, SPD7, SPD9, SPD 11, SPD12). o Prevents paralleling of source switches and opening fuse doors when source switches are closed, (Models SPD6, SPD9, SPD11). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 2.2.3 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD, 2/4 Circuit 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Top Unit: Model SPD5, 15kV. Bottom Unit: Model SPD9, 15 kV. 2.2.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD, 2/4 Circuit 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Circuit Diagram Model/Style kV H W D WGT 15 44 41 66.75 800 lb 25 50 46 81.75 1025 lb 15 44 41 52.75 750 lb 25 50 46 62.25 950 lb 15 44 41 66.75 975 lb 25 50 46 81.75 1125 lb 15 44 75 66.75 1525 lb 25 50 84 81.75 1775 lb 15 44 75 66.75 1550 lb 25 50 84 81.75 1825 lb SPD3 SPD4 SPD5 SPD6 SPD7 Continued on page 2.2.6 © 2002 Shallbetter Inc. www.shallbetter.com 2.2.5 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (DEADFRONT) Model SPD 2/4 Circuit, 5-25 kV. 200 and 600 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Circuit Diagram Model/Style kV H W D WGT 15 44 75 66.75 1650 lb 25 50 84 81.75 1925 lb 15 44 75 72.75 1775 lb 25 50 84 88.25 1975 lb 15 44 75 72.75 1850 lb 25 50 84 88.25 2075 lb 15 44 75 66.75 1725 lb 25 50 84 81.75 1950 lb 15 44 75 72.75 1725 lb 25 50 84 88.25 1925 lb SPD9 SPD10 SPD11 SPD12 SPD13A l For special configurations and sizes, (i.e.; more than four compartments, metering, or higher amperage) consult factory. 2.2.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Application: Shallbetter Inc. model SPL Padmounted Switchgear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electrical Code requirements. The Shallbetter SPL Padmounted Switchgear is intended for use as underground cable protection, distribution transformer protection, and fused or nonfused sectionalizing and switching where three phase, load-break switching is desired. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 2.3.1 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Catalog Number Selection Sheet. To be used in conjunction with Factory Sheet. 15 25 35 2.3.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Factory Check Sheet. To be used in conjunction with Catalog Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous Current (Load) ____/____ kV o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 200 amp o 600 amp o 1200 amp o 200 amp o 600 amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other:__________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Base Spacer :____ ”H. o A60, Galvanneal Steel construction o 304L, Stainless Steel construction o Base Adapter to fix existing pad, consult factory. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. o Cable Support Rails. o Terminal Adapters. Allows “piggybacking” of cables in switch and bus compartments. o Fault Indicator Provisions. o Base Undercoating. Applied to the bottom 2” of the enclosure. o Concentric Ground. Connects front and rear ground bus. Key Interlocks: o Prevents paralleling of source switches, (Model SPL6, SPL9, SPL10, SPL11, SPL13, SPL14, SPL19). o Prevents opening fuse doors when source switches are closed, (Models SPL5, SPL6, SPL7, SPL8, SPL9, SPL11, SPL12, SPL14, SPL19). o Prevents paralleling of source switches and opening fuse doors when source switches are closed, (Models SPL6, SPL9, SPL11, SPL14, SPL19). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 2.3.3 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Top Unit: Model SPL5, 15kV. Bottom Unit: Model SPL9, 15 kV. 2.3.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Circuit Diagram Style KV H W D WGT 15 44 34.87 39.50 725 lb 25 55 43 54.50 1000 lb 15 44 34.87 39.50 600 lb 25 55 43 54.50 725 lb 15 44 34.87 49.50 900 lb 25 55 43 63.00 1200 lb 15 44 67 60.00 1625 lb 25 55 82 74.50 2025 lb 15 44 67 60.00 1550 lb 25 55 82 74.50 1950 lb 15 44 67 60.00 1500 lb 25 55 82 74.50 1950 lb 15 44 67 60.00 1700 lb 25 55 82 74.50 2100 lb SPL3 SPL4 SPL5 SPL6 SPL7 SPL8 SPL9 Continued on page 2.3.6 © 2002 Shallbetter Inc. www.shallbetter.com 2.3.5 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Circuit Diagram Model/Style kV H W D WGT 15 44 67 60 1875 lb 25 55 82 74.50 2325 lb 15 44 67 60 1775 lb 25 55 82 74.50 2225 lb 15 44 67 60 1600 lb 25 55 82 74.50 2000 lb 15 44 67 60 1675 lb 25 55 82 74.50 2125 lb 15 44 67 60.00 1600 lb 25 55 82 74.50 2050 lb 15 44 67 60.00 1775 lb SPL10 SPL11 SPL12 SPL13 SPL14 SPL19 Consult Factory l l For 5 kV applications, use 15 kV table. For special configurations, sizes, 35 kV and 1200 ampere configurations, consult factory. 2.3.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit 5-35 kV. Custom Designs - 35 kV. l Customer specified Livefront Switchgear, 600 ampere, 35 kV, 150 kV BIL, with 600 AMP switches, current limiting fuses, lightning arresters, and fault indicator provisions. © 2002 Shallbetter Inc. www.shallbetter.com 2.3.7 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SPL, 2/4 Circuit, 5-35 kV. Custom Designs - 1200 Ampere. Customer specified Livefront Switchgear Unit, 1200 ampere, 15 kV, 95 kV BIL, with 1200 AMP switches and lightning arresters. l 2.3.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Application: Shallbetter Inc. model SSGL Padmounted Switchgear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electrical Code requirements. The Shallbetter SSGL Padmounted Switchgear is ideal for multi-circuit applications when installing numerous padmounted switches is required, but not desired. This space saving, flexible design can incorporate primary metering, tie switches and higher amperages into complete padmounted units where conventional padmounted switchgear designs do not apply. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 2.4.1 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Catalog Number Selection Sheet. 2.4.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. Current Limiting and Power Fuses. Factory Check Sheet. To be used in conjunction with catalog Number selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous Current (Load) ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV Bil o 25 kV, 125 kV BIL o 200 amp o 600 amp o 1200 amp (consult factory) o 200 amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: _______________________ 3-Point latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Base Spacer.___ ”H. o A60, Galvanneal Steel construction o 304L, Stainless Steel construction o Base Adapter to fix existing pad, consult factory. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. o Cable Support Rails. o Terminal Adapters. Allows “piggybacking” of cables in switch and bus compartments. o Fault Indicator Provisions. o Base Undercoating. Applied to the bottom 2” of the enclosure. o Concentric Ground. Connects front and rear ground bus. o Key Interlocks, (Consult Factory). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 2.4.3 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Metering. 2.4.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Metering. Circuit Diagram Style KV H W D WGT 15 68 108 86 725 lb SSGL6600 25 15 CONSULT FACTO RY 68 108 86 600 lb SSGL6651 25 15 CONSULT FACTO RY 68 102 86 900 lb SSGL6642 25 15 CONSULT FACTO RY 68 102 86 1625 lb SSGL6633 25 15 CONSULT FACTO RY 68 102 86 1550 lb SSGL6624 25 CONSULT FACTO RY Continued on page 2.4.6 © 2002 Shallbetter Inc. www.shallbetter.com 2.4.5 Û INDEX Ü Û INDEX Ü PADMOUNTED SWITCHGEAR (LIVEFRONT) Model SSGL, 6 Circuit, 5-25 kV. 200, 600 and 1200 Ampere, Three Phase, Three-Pole Loadbreak Switching. 200 Ampere Power Fusing. 100 Ampere Current Limiting Fusing. Metering. Circuit Diagram Model/Style kV H W D WGT 15 68 102 86 1875 lb SSGL6615 25 15 CONSULT FACTO RY 68 102 86 1775 lb SSGL645 25 15 CONSULT FACTO RY 68 102 86 1600 lb SSGL6332 25 15 CONSULT FACTO RY 68 102 86 1675 lb SSGL6413-M 25 15 CONSULT FACTO RY 68 102 86 1600 lb SSGL6422-M 25 l l l CONSULT FACTO RY For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. For 1200 amperes, consult factory. 2.4.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Models SPMD and SPMG, 5-35 kV. 200 and 600 Ampere. Single and Three Phase, Fused/Nonfused. Application: Shallbetter Inc. models SPMD and SPMG Padmounted Primary Metering Gear is constructed in accordance with the latest applicable industry standards and the local and/or National Electrical Code requirements. The Shallbetter SPMD and SPMG Padmounted Primary Metering Gear is intended for use where the service is fed underground and the revenue metering is measured at the primary voltage rate. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 3.1.1 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Models SPMD and SPMG, 5-35 kV. 200 and 600 Ampere. Single and Three Phase, Fused/Nonfused. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. 3.1.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Models SPMD and SPMG, 5-35 kV. 200 and 600 Ampere. Single and Three Phase, Fused/Nonfused. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous (Load) o o o o o o o o ____/____ kV 15 kV, 95 kV BIL 25 kV, 125 kV BIL 35 kV, 150 kV BIL Other ___ kV, ___kV BIL 200 amp 600 amp 200 amp 600 amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o 5052-H32 Aluminum Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: ____________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. manufactured to meet or exceed A.N.S.I. C57.12.28 for padmount Equipment Enclosure Integrity. o Max-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Metering Compartment Barriers, (Model SPMD only): o 3/16”, Glass Reinforced Polyester, (standard) o 1/4, Clear Polycarbonate (Lexan), Replaces 3/16” Glass Reinforced Polyester Compartment Barriers. Instrument Transformers: o Current Transformers: Manufacturer: ____, Model: ____, Type: ____, kV: ____, Ratio: ____. o Potential Transformers: Manufacturer: ____, Model: ____Type: ____, kV: ____, Ratio: ____. o Meter Socket: Manufacturer: ____, Model: ____, Type: ____. o Louvers for enclosure ventilation. o Insulation “No-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base undercoating. Applied to the bottom 2” of the enclosure. o REA Deadfront Barriers. Barriers inside the enclosure door from each compartment, secured by recessed penta-head bolt. Note: Replaces compartment barriers, (Models SPMD only). o Rodent Plate. Seals base of enclosure, Metering Compartment side only, (Model SPMD only). o Ground Bails. (Located on the Deadfront, Model SPMD only). o Interface Bushing Well Inserts (200 amp only). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 3.1.3 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Model SPMD, 5-35 kV. 200 and 600 Ampere. Single and Three Phase, Fused/Nonfused. H2 H1 l l l For 5 kV applications, use 15 kV table. Units available as enclosures only (customers supplied and installed component) or as complete units from the factory. For single phase units, special configurations and sizes, consult factory. 3.1.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Model SPMG, 5-15 kV. 200 Ampere Max. Single and Three Phase, 15 kV Max. l l l l l For 5 kV applications, use 15 kV table. Utilizes General Electric JKM-95 and JVM-95 Instrument Transformers. Units available as enclosure only (customer supplied and installed components) or as complete units from the factory. For special configurations and sizes, consult factory. Not available above 15 kV. © 2002 Shallbetter Inc. www.shallbetter.com 3.1.5 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Model SPMD, Fused, 5-35 kV. Custom Designs. l l Customer specified Fused Deadfront Primary Metering Unit, 200 ampere elbow connected, 15 kV, 95 kV BIL, with S&C SML-20-fuse mountings, metering compartment, special instrument transformer mounting, and secondary wiring conduit and provisions for test blocks and meter sockets in an isolated compartment. For other custom designs, consult factory. 3.1.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (DEADFRONT) Model SPMD, Fused, 5-35 kV. Custom Designs. l l Customer specified Fused Deadfront Primary Metering Unit, 200 ampere elbow connected, 15 kV, 95 kV BIL, with S&C SML-4Z fuse mounting. For other custom designs, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 3.1.7 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 3.1.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. 200-3000 Ampere. Single and Three Phase. Application: Shallbetter Inc. model SPML Padmounted Primary Metering Gear is constructed in accordance with the latest applicable industry standards and the local and/or National Electrical Code requirements. The Shallbetter SPML Padmounted Primary Metering Gear is intended for use where the service is fed underground and the revenue metering is measured at the primary voltage rate. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 3.2.1 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. 200-300 Ampere. Single and Three Phase. Catalog Number Selection Sheet. 3.2.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. 200-3000 Ampere. Single and Three Phase. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous Current (Load) ____/____ kV o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other ____ kV, ____ kV BIL ____ amp ____ amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o 5052-H32 Aluminum Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: ________________________ 3-Point Latch type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Metering Compartment Barriers, (Model SPMD only): o 3/16”, Glass Reinforced Polyester, (standard) o 1/4”, Clear Polycarbonate (Lexan), Replaces 3/16” Glass Reinforced Polyester Compartment Barriers. Instrument Transformers: o Current Transformers: Manufacturer: ____, Model: ____, Type: ____, kV: ____, Ratio: ____. o Potential Transformers: Manufacturer: ____, Model: ____, Type: ____, kV: ____, Ratio: ____. o Meter Socket: Manufacturer: ____, Model: ____, Type: ____. o Louvers for enclosure Ventilation. o Insulating “No-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. Note: Replaces compartment barriers. o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 3.2.3 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. 200-3000 Ampere. Single and Three Phase. Circuit Diagram l l l Model/Style SPML-315 SPML-325 SPML-335 kV 15 25 35 H 48 48 W 72 72 D H1 H2 54 22.000 30.000 54 22.000 30.000 Consult Factory WGT 1100 lb 1100 lb For 5 kV applications, use 15 kV table. Units available as enclosures only (customer supplied and installed components) or as complete units from the factory. For single phase units, special configurations and sizes, consult factory. 3.2.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. 200-3000 Ampere. Single and Three Phase, 15 kV, 3000 Ampere Max. Circuit Diagram l l l Style KV H W D WGT SPM L-315-T-LVCT 15 54 72 54 1050 lb For 5 kV applications, use 15 kV table. Utilizes low voltage current transformers, 3000 ampere max. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 3.2.5 Û INDEX Ü Û INDEX Ü PADMOUNTED PRIMARY METERING GEAR (LIVEFRONT) Model SPML, 5-35 kV. Custom Designs. l l Customer specific Livefront Primary Metering Unit, 600 ampere with special terminations, 15 kV, 96 kV BIL. For custom designs, consult factory. 3.2.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CABLE SWITCHING GEAR (DEADFRONT) Model SCSD. 5-35 kV. 200 and 600 Ampere, - Nonfused. Single and Three Phase. Application: Shallbetter Inc. model SCSD Padmounted Cable Switching Gear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electric Code requirements. The Shallbetter SCSD Padmounted Cable Switching Gear is ideal for sectionalizing cables that require nonfused taps for single phase and three phase loads where group-operated switching (Shallbetter model SPL, SPD, SSGD or SSGL switchgear) is not desired. This padmounted equipment may be operated as single phase, loadbreak switchgear utilizing the elbows for switching or it can be utilized in conjunction with conventional padmounted switchgear with group-operated switches (Shallbetter model SPL, SPD, SSGD or SSGL switchgear). For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 4.1.1 Û INDEX Ü Û INDEX Ü PADMOUNTED CABLE SWITCHING GEAR (DEADFRONT) Model SCSD, 5-35 kV. 200 and 600 Ampere, - Nonfused. Single and Three Phase. Catalog Number Selection Sheet. 4.1.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CABLE SWITCHING GEAR (DEADFRONT) Model SCSD, 5-35 kV. 200 and 600 Ampere, - Nonfused. Single and Three Phase. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Continuous Current (Load) ____/____ kV o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____kV, ____kV BIL o 200 amp o 600 amp o 200 amp o 600 amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o 5052-H32 Aluminum Paint finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: _______________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Bus Compartment Barriers: o 3/16” Glass Reinforced polyester, (standard) o 1/4”, Clear Polycarbonate (Lexan), Replaces 3/16” Glass reinforced Polyester Compartment Barriers. o Louvers for enclosure ventilation. o Insulation “No-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. Note: Replaces compartment barriers. o Rodent Plate. Seals base of enclosure, bus compartment side only. o Ground Bails. (Located in the deadfront). o Interface Bushing Well Inserts (200 amp only). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 4.1.3 Û INDEX Ü Û INDEX Ü PADMOUNTED CABLE SWITCHING GEAR (DEADFRONT) Model SCSD, 5-35 kV. 200 and 600 Ampere, - Nonfused. Single and Three Phase. 36 36 l l For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. 4.1.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CABLE SWITCHING GEAR (DEADFRONT) Model SCSD, 5-35 kV. 200 and 600 Ampere, - Nonfused. Single and Three Phase. SCSD-3153 48 SCSD-3253 48 SCSD-3353 SCSD-3154 60 SCSD-3254 60 SCSD-3354 SCSD-3155 72 SCSD-3255 72 SCSD-3355 SCSD-3156 84 SCSD-3256 84 SCSD-3356 l l For 5 kV applications, use 15 kV table. For special configurations and sized, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 4.1.5 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 4.1.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Models STEN, STEI, STEC1, STEC2, STMV. Application: Shallbetter Inc. Cable Terminating Gear is constructed in accordance with the latest applicable industry standards and the governing local and/or National Electrical Code requirements. The Shallbetter line of Cable Terminating Gear is intended for use as a junction point between transformer secondaries and switchgear or as a split point for feeding multi-services. For complete specifications, please contact your authorized Shallbetter factory representative. © 2002 Shallbetter Inc. www.shallbetter.com 4.2.1 Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Models STEN, STEI, STEC1, STEC2, STMV, 600 Volt./5-35 kV. Catalog Number Selection Sheet. 4.2.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Models STEN/STEI, STEC1/STEC2, 600 Volt./5-35 kV. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current ____/____ kV o 600 Volt, 10 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____ kV, ____ kV BIL o 200 amp o 400 amp o 600 amp o 1000 amp o 1200 amp o 1600 amp o o o o o o 2000 2500 3000 4000 5000 6000 amp amp amp amp amp amp ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o 5052-H32 Aluminum Bus Material: o Aluminum, Tin Plated, (0 - 3.000 amp only) o Copper, Silver Plated Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 o Other: _____________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C57.12.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Instrumental transformers, (Model STEI only): o Current Transformers: Manufacturer: ____, Model: ____, Type: ____, kV: ____, Ratio: ____. o Potential Transformers: Manufacturer: ____, Model: ____, Type: ____, kV: ____, Ratio: ____. o Meter Socket, (Model STEI only): Manufacturer: ____, Model: ____, Type: ____. o Meter, (Model STEI only): Manufacturer: ____, Model: ____, Type: ____. o Connectors: Manufacturer: ____, Model: ____, Type: ____, Wire range: ____. o Threaded Inserts on Bus Bar. o Ground Bus. o Louvers for enclosure ventilation. o Insulating “No-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. Note: Replaces compartment barriers, (Model STMV). o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 4.2.3 Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Models STEN/STEI, Padmounted, 600 Volt. Single and Three Phase, 400-6000 Ampere. l l For options including meter sockets, meters and factory wiring, consult factory. For special configurations and sizes, consult factory. 4.2.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Model STEC1, Padmounted, 600 Volt. Single Phase, 400-4000 Ampere. The model STEC1 Padmounted Cable Terminating Gear is rated for 400-4000 amps as a standard design. The lug bar is universally rated to 4000 amps. © 2002 Shallbetter Inc. www.shallbetter.com 4.2.5 Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Model STEC2, Wall Mounted, 600 Volt. Three Phase, 400-4000 Ampere. The model STEC2 Padmounted Cable Terminating Gear is rated for 400-4000 amps as a standard design. The lug bar is universally rated to 4000 amps. 4.2.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü CABLE TERMINATING GEAR Model STMV, Padmounted, 5-35 kV. Single and Three Phase, 1200 Ampere Max. l l l For 25 kV or 35 kV applications, consult factory. For amperage in excess of 1200 ampere, consult factory. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 4.2.7 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 4.2.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED TELEPHONE CABLE SPLICING ENCLOSURE Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 4.3.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 4.3.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (LIVEFRONT and DEADFRONT) Models SCBL and SCBD, 5-35 kV. 2400 kVAr Max. Application: Shallbetter Inc. models SCBL and SCBD Padmounted Capacitor Banks are constructed in accordance with the latest applicable industry standards and the governing local and/or National Electric Code requirements. The Shallbetter Padmounted Capacitor Banks are intended for use on underground distribution systems where the need for reactive power compensation and/or voltage support exists. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 5.1.1 Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (LIVEFRONT and DEADFRONT) Models SCBD and SCBL, 5-35 kV. 2400 kVAr Max. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. 5.1.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (LIVEFRONT and DEADFRONT) Models SCBD and SCBL, 5-35 kV. 2400 kVAr Max. Types P1, P2, P3 and P4. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Main switching Device Fuse rating: Main Fuses Capacitor Fuses kVAR Rating (TOTAL) ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____kV, ____ kV BIL 200A or 600A ____ amp, Type: Oil, Vacuum ____ amp, Type: ____, Voltage: ____ kV ____ amp, Type: ____, Voltage: ____ kV _________ kVAR ENCLOSURE: Material: o A60 Galvanneal Steel o 304L Stainless Steel o Aluminum 5052-H32 Paint Finish: o o o o 3-Point Latch Type: o Green Munsell No., 7GY 3.29/1.5 Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54 Other: ______________________ Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C5712.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Bushing Wells and/or Bushings, (Model SCBD only): o Bushing Wells: 200 amp o Bushings: 600 amp Equipment Compartment Barriers: o 3/16”, Glass Reinforced Polyester, (standard) o 1/4”, Clear Polycarbonate (Lexan). Replaces 3/16” Glass Reinforced Polyester Compartment Barriers. o Ground Switch. Group operated, external operating handle. o Ground Options: o Ground Bails o Ground Bosses, 1/2-13 UNC. Qty: ____, Location: ____________. o Louvers for enclosure ventilation. o Insulation “Non-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o REA Deadfront Barriers. Barriers inside the enclosure door for each compartment, secured by recessed penta-head bolt. Note: Replaces compartment barriers. o Control Options: o Control Power Transformer: o Specials: © 2002 Shallbetter Inc. www.shallbetter.com 5.1.3 Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (LIVEFRONT) Model SCBL, Livefront, 5-35 kV. Type P1. Circuit Diagram Model/Type kV H W D WGT 15 60 60 60 1050 lb 25 Consult Factory 35 Consult Factory SCBL-P1 l l For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. 5.1.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (DEADFRONT) Model SCBD, Deadfront, 5-35 kV. Type P2. Circuit Diagram Model/Type kV H W D WGT 15 60 60 60 1150 lb 25 Consult Factory 35 Consult Factory SCBD-P2 l l For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 5.1.5 Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (LIVEFRONT) Model SCBL, Livefront, 5-35 kV. Type P3. Circuit Diagram Model/Type kV H W D WGT 15 60 60 60 1175 lb 25 Consult Factory 35 Consult Factory SCBL-P3 l l For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. 5.1.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PADMOUNTED CAPACITOR BANKS (DEADFRONT) Model SCBD, Deadfront, 5-35 kV. Type P4. Circuit Diagram Model/Type kV H W D WGT 15 60 60 60 1275 lb 25 Consult Factory 35 Consult Factory SCBD-P4 l l For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 5.1.7 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 5.1.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Types M1 and M2. Internally or Externally Fused Capacitors. Application: Shallbetter Inc. model SCBM Metal-Enclosed Capacitor Banks are constructed in accordance with the latest applicable industry standards and the governing local and/or National Electric Code requirements. The Shallbetter Metal-Enclosed Capacitor Banks are intended for use on underground distribution systems where the need for reactive power compensation and/or voltage support exists. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 5.2.1 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Types M1 and M2. Internally or Externally Fused Capacitors. Catalog Number Selection Sheet. 5.2.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Types M1 and M2. Internally or Externally Fused Capacitors. Factory Check Sheet. RATINGS: Nominal System Voltage/ Maximum design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Main Disconnect Switching Device Capacitor Switching Device Fuse Ratings: Main Fuses Capacitor Fuses kVAR Rating (Total) To be used in conjunction with Catalog Number Selection Sheet. ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____ kV, ____ kV BIL ____ amp ____ amp, ____kV, ____kV BIL ____ amp, ____ kV, ____ kV BIL ____ amp, Type: ____, Voltage: ____ kV ____ amp, Type: ____, Voltage: ____ kV _________ kVAR Enclosure Type: o Indoor o Outdoor Material: o A60 Galvanneal Steel o 304L Stainless Steel o Aluminum 5052-H32 Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54, (standard) o Other: _______________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C5712.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 o Forced air ventilation. (Based on heat-rise calculations.) o Strip Heaters. o Ground Options: o Ground Bails. o Ground Bosses, 1/2-13 UNC. Qty: ____, Location: __________________. o Insulating “Non-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. (Applied to the bottom 2” of the enclosure). o Specials: (Factory Check Sheet continued on page 5.2.4) © 2002 Shallbetter Inc. www.shallbetter.com 5.2.3 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Types M1 and M2. Internally or Externally Fused Capacitors. Factory Check Sheet (continued). Main Disconnect Section, (standard 15 kV size: 102 H x 40 W x 60 D): o Disconnecting Switches: ____ amp., ____ kV, Type: ____, Manufacturer: ________. o 600 amperes, Non-loadbreak Elbow Terminators. o Main Fusing: ____ amp., ____ kV, Type: ____, Manufacturer: ________. o Surge Arresters: ____ kV, Type: ____, Manufacturer: ________. Capacitor Switching Section, (standard 15 kV size: 102 H x 68 W x 60 D): o Vacuum Circuit Breaker, (special sizing required, consult factory): ____ amp., ____kV, Type: ____, Manufacturer: _________. o Vacuum Contactor, (15 kV applications max): ____ amp., ____ kV, Type: ____, Manufacturer: ________. o Vacuum Switch: ____ amp., ____ kV, Type: ____, Manufacturer: ____. o Oil Switch: ____ amp., ____ kV, Type: ____, Manufacturer: ____. o Other: ____ amp., ____ kV, Type: ____, Manufacturer: ____. Reactors: o Air Core: ____ uH, ____ amp. Manufacturer (if other than Shallbetter:) ________. o Iron Core: ____ uH, ____ amp., Manufacturer: ________. (Special sizing may be required, consult factory). o Ground Switches: o Ground Options: o Control Power Transformer: o Specials: Capacitor Section. Section Type: o Internally fused Capacitors. o Externally fused Capacitors. o 4 Capacitors per phase, (standard 15 kV size: 102 H x 44 W x 60 D). o 6 Capacitors per phase, (standard 15 kV size: 102 H x 60 W x 60 D). Note: When selecting Capacitor section type for Type M2 Capacitor Banks, the section type must be the same front and rear to maintain the same front and rear alignment. Capacitors: ____ kVAR, ____ kV, ____ BIL, Manufacturer: ________. Capacitor Fusing: ____ amp., ____ kV, Type: ____, Manufacturer: ________. l l l l For 5 kV applications, use 15 kV sizing. For 25 kV and 35 kV sizes, consult factory. For internally fused capacitor designs, please consult factory. For special configurations and sizes, consult factory. 5.2.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Type M1. Internally or Externally Fused Capacitors. © 2002 Shallbetter Inc. www.shallbetter.com 5.2.5 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Type M1. Internally or Externally Fused Capacitors. The Capacitor Bank illustrations on pages 5.2.5-5.2.8 are shown as examples. The unit illustrated on page 5.2.5 and 5.2.6 includes the following: Main Disconnect Section/600 AMP, Group operated switch. Capacitor Switching Section/Vacuum Switch, Shallbetter Current-Limiting Reactors, Shallbetter 4 Pole Ground Switch. Capacitor Section, 18 Can Rack: Capacitor Fuses and Capacitors. Refer to Selection Guide for specific applications. 5.2.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Type M2. Internally or Externally Fused Capacitors. © 2002 Shallbetter Inc. www.shallbetter.com 5.2.7 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED CAPACITOR BANKS Model SCBM, 5-35 kV. Type M2. Internally or Externally Fused Capacitors. The Capacitor Bank illustrations on pages 5.2.5-5.2.8 are shown as examples. The unit illustrated on page 5.2.7 and 5.2.8 includes the following: Main Disconnect Section: 1 - 600 AMP, group operated switch. Front Capacitor Switching Section: 1 - Vacuum Switch, 3 - Shallbetter Current-Limiting Reactors, 1 - Shallbetter 4 Pole Ground Switch. Front Capacitor Section, 18 Can Rack: Capacitor Fuses and Capacitors. Rear Capacitor Switching section: 1 - Vacuum Switch, 3 - Shallbetter Current-Limiting Reactors, 1 - Shallbetter 4 Pole Ground Switch. Rear Capacitor Section, 18 Can Rack: Capacitor Fuses and Capacitors. Refer to Selection Guide for specific applications. 5.2.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Types S1 and S2. Internally and Externally Fused Capacitors. Application: Shallbetter Inc. model SCBM Multi-Step Capacitor Banks are constructed in accordance with the latest applicable industry standards and the governing local and/or National Electric Code requirements. The Shallbetter Multi-Step Capacitor Banks are intended for use on underground distribution systems where the need for reactive power compensation and/or voltage support exists. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 5.3.1 Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Types S1 and S2. Internally and Externally Fused Capacitors. Catalog Number Selection Sheet. 5.3.2 To be used in conjunction with Factory Check Sheet. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Types S1 and S2. Internally and Externally Fused Capacitors. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum design Voltage Basic Insulation Level (BIL) Continuous Current (Line) Main Disconnect Switching Device Capacitor Switching Device Fuse Ratings: Main Fuses Capacitor Fuses kVAR Rating (Total) ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____ kV, ____ kV BIL ____ amp ____ amp, ____kV, ____kV BIL ____ amp, ____ kV, ____ kV BIL ____ amp, Type: ____, Voltage: ____ kV ____ amp, Type: ____, Voltage: ____ kV _________ kVAR Enclosure Type: o Indoor o Outdoor Material: o A60 Galvanneal Steel o 304L Stainless Steel o Aluminum 5052-H32 Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54, (standard) o Other: _______________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C5712.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 o Ground Options: o Ground Bails o Ground Bosses, 1/2-13 UNC. Qty: ____, Location: __________________. o Forced air ventilation. (Based on heat-rise calculations.) o Strip Heaters. o Insulating “Non-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o Specials: (Factory Check Sheet continued on page 5.3.4) © 2002 Shallbetter Inc. www.shallbetter.com 5.3.3 Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Types S1 and S2. Internally and Externally Fused Capacitors. Factory Check Sheet (continued). Main Disconnect Section, (standard 15 kV size: 102 H x 40 W x 60 D): o Disconnecting Switches: ____ amp., ____ kV, Type: ____, Manufacturer: ________. o 600 amperes, Non-loadbreak Elbow Terminators. o Main Fusing: ____ amp., ____ kV, Type: ____, Manufacturer: ________. o Surge Arresters: ____ kV, Type: ____, Manufacturer: ________. Capacitor Switching Section, (standard 15 kV size: 102 H x 68 W x 60 D): Section Type: o 1 Capacitor per phase, (standard 15 kV size: 102 H x 60 W x 60 D). o 2 Capacitors per phase, (standard 15 kV size: 102 H x 80 W x 60 D). Note: When selecting Capacitor section type for Type S2 Capacitor Banks, the section type must be the same front and rear to maintain front and rear alignment. Capacitor Switching: o Single pole vacuum switches, 200 amp. on 15 kV, 95 kV BIL systems or 200 amp. on 25 kV, 125 kV BIL applied on grounded wye systems. o Three pole vacuum switch, 200 amp. on 15 kV, 95 kV BIL systems or 200 amp. on 25 kV, 125 kV BIL applied on grounded wye systems. o Single pole oil switches, 200 amp. on 15 kV, 95 kV BIL or 25 kV, 125 kV BIL systems or 60 amp. on 35 kV, 125 kV BIL applied on grounded wye systems. o Three pole oil switches, 200 amp. on 15 kV, 95 kV BIL or 25 kV, 125 kV BIL systems or 60 amp. on 35 kV, 125 kV BIL applied on grounded wye systems. o Vacuum contactor, 450 amp., on 5 kV (max 15 kV), 60 kV BIL systems. o Other: ____ amp., ____ kV, Type: ____, Manufacturer: ________. Reactors: o Air Core: ____ uH, ____ amp. Manufacturer (if other than Shallbetter:) ________. o Iron Core: ____ uH, ____ amp., Manufacturer: ________. (Special sizing may be required, consult factory). o Ground Switches: o Ground Options: o Control Power Transformer: o Specials: l l l For 5 kV applications, use 15 kV sizing. For 25 kV and 35 kV, consult factory. For special configurations and sizes, consult factory. 5.3.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Type S1. Internally and Externally Fused Capacitors. © 2002 Shallbetter Inc. www.shallbetter.com 5.3.5 Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Type S1. Internally and Externally Fused Capacitors. The Capacitor Bank illustrations on pages 5.3.5 and 5.3.6 are shown as examples. This illustration includes the following: Main Disconnect Section:1- 600 AMP, Group operated switch. Capacitor Section; 2 Capacitors per phase, 3- Vacuum Switches, 3- Shallbetter Current-Limiting Reactors, 1Shallbetter 4 Pole Ground Switch, and Capacitor Fuses. Capacitor Section: 1 Capacitor per phase; 3- Vacuum Switches, Shallbetter Current-Limiting Reactors, 1Shallbetter 4 Pole Ground Switch, and Capacitor Fuses. For specific applications, refer to the Selection Guide. 5.3.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM. 5-35 kV. Type S2. Internally and Externally Fused Capacitors. Continued on page 5.3.8 © 2002 Shallbetter Inc. www.shallbetter.com 5.3.7 Û INDEX Ü Û INDEX Ü MULTI-STEP CAPACITOR BANKS Model SCBM, 5-35 kV. Type M2. Internally and Externally Fused Capacitors. The Capacitor Bank illustrations on pages 5.3.7 and 5.3.8 are shown as examples. This illustration includes the following: Main Disconnect Section:1- 600 AMP, Group operated switch. SMG - Capacitor Section: 2- Capacitors per phase;3- Vacuum Switches, 3 - Shallbetter Current-Limiting Reactors, 1 - Shallbetter 4 Pole Ground Switch, and Capacitor Fuses. SMG - Capacitor Section: 1- Capacitor per phase; 3- Vacuum Switches, 3- Shallbetter Current-Limiting Reactors, Shallbetter 4 Pole Ground Switch, and Capacitor Fuses. For specific applications, refer to Selection Guide. 5.3.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED HARMONIC FILTER CAPACITOR BANKS Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 5.4.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 5.4.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü SURGE CAPACITOR BANKS Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 5.5.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 5.5.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü RTXTM ACTIVE PF CORRECTION Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 5.6.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 5.6.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. 1200 Ampere Max, Loadbreak. 4000 Ampere Max, Non-Loadbreak. Applications: The Shallbetter Inc. model SMEG Metal-Enclosed Switchgear is constructed in accordance with the latest industry standards and the governing local and/or National Electric Code requirements. The Shallbetter SMEG Metal-Enclosed Switchgear is intended for use on power distribution systems for transformer protection, isolation/sectionalizing or service entrance/power distribution at medium voltage where three phase (group-operated) switching is desired/required. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.1 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. 1200 Ampere Max, Loadbreak. 4000 Ampere Max, Non-Loadbreak. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. Figure Selection Guides 6-A, 6-B and 6-C. 6.1.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. 1200 Ampere Max, Loadbreak. 4000 Ampere Max, Non-Loadbreak. Factory Check Sheet. To be used in conjunction with Factory Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum Design Voltage Basic Insulation Level (BIL) ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o 35 kV, 150 kV BIL o Other: ____ kV, ____ kV BIL Continuous Current (Line) ____ amp Main Disconnect Switching Device ____ amp, ____kV, ____kV BIL Fuse Rating ____ amp, Type: ____, Voltage: ____ kV Enclosure Type: Indoor: o Nema 1 o Nema 2 o ______ Outdoor: o Nema 3 o Nema 3R o Nema 12 o Nema 4 o Nema 4X o _______ Material: o A60 Galvanneal Steel o 304L Stainless Steel Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54, (standard) o Other: _______________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C5712.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Rear Access, (optional): o Hinged, rear doors with padlocking handle. o Bolted, lift off panels. Ground Options: o Ground Bails o Ground Bosses, 1/2-13 UNC. Qty: ____, Location: __________________. o Insulating “Non-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Base Undercoating. Applied to the bottom 2” of the enclosure. o Specials: Factory Check Sheet continued on page 6.1.4 © 2002 Shallbetter Inc. www.shallbetter.com 6.1.3 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. 1200 Ampere Max, Loadbreak. 4000 Ampere Max, Non-Loadbreak. Factory Check Sheet (continued). Standard Component Options Switches l l l l l l l o ABB Cutler-Hammer Powercon S&C Square D Cleveland Price Cooper ___________ Fusing l l l l l o Miscellaneous l Cycloaliphatic Insulators l Glass Polyester l Insulators l Polycrete Insulators l Porcelain Insulators o _____________ Cooper Cutler-Hammer General Electric Gould-Shawmut S&C ____________ Options o o o o o U.L. Label, (5 and 15 kV)(Consult Factory) C.S.A. Label Key Interlocks Insulated Bus Mimic Bus o o o o Capacitors ______ kVAR Neoprene Door Gasketing Provisions for Future Extensions Braided Flex Connectors (Transformer Disconnect Only) o Protective Inner Barrier, (Standard on Fig. 5, 8, 12, 13, 14 and 15). Other models, barrier is optional unless otherwise stated. o Metal-Screen o NEMA Type GPO-3, Glass Reinforced Polyester o Clear Polycarbonate o o o o Rear Access: Hinged Rear Panels with Padlocking Handles Bolted Lift-off Panels with Padlocking Provisions Padlockable Switch Handle Cover o o o o o o o o o o o Space Heaters * Roof top Bushings Pot Head Terminators Surge Arresters Interior Lighting Duplex Outlets Control Power Instrumentation Packages Automatic Bus Transfer Schemes Motor Operator or Solenoid Trip Terminating Hardware o Non-Loadbreak Switching: o 2000 amp o 3000 amp o 4000 amp o o o o o o Walk-in Sheltered Aisle: Non-Insulated Insulated Heat AC Interior Walls Sheeted * Space Heaters are provided standard with outdoor equipment. 6.1.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Selection Guide. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.5 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Selection Guide. Figure 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Description Empty Entrance Pull Sectio n, S ide Access - Top or Bottom Feed. Transitio n Sectio n - Bussed , Cable or Flex Connected . Bussed Entrance Sectio n, Front Access - Top or Bottom Feed. Entrance Section, Non-Fused Switch - Top or Bottom Feed. Entrance Section, Fused Switch - Top or Bottom Feed. Entrance Section, Metered - Top or Bottom Feed. Distribution Sectio n, Non-Fused Switch. Distribution Sectio n, Fused Switch. Metering Section. Tie Section - Switched. Distribution Sectio n, Fused. Switch and Fuse Section - Top Entrance/Bottom Exit or Bottom Switch and Fuse Section - Top Entrance/Top Exit or Bottom Switch and Fuse, Metering Sectio n - Top Entrance/Top Exit or Bottom Entrance/Bottom Exit. Fused Non-Fuse - Top Entrance/Top, Botto m, or Side Exit. Corner Sectio n. Dimension Table A. A. B. B. B. B. B. B. Consult factory B. B. B. C. C. D. Per Requirements DIMENSION TABLE Rating KV Design BIL 5 60 15 95 25 125 35 150 35 200 Table A H 94 94 126 126 162 W 24 24 36 40 40 Table B D 44 44 60 72 96 H 94 94 126 126 162 W 40 40 48 60 78 Table C D 44 44 60 72 96 H 94 94 126 126 162 W 40 40 48 60 78 Table D D 54 54 72 84 110 H W D 94 80 54 94 80 54 Consult Factory Consult Factory Consult Factory Dimensions reflect indoor units. Add 3” to height (H) on outdoor units. l For special configurations and sizes, consult factory. 6.1.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Units shown are: Top: Figure 12: 15 kV, switch and fuse section - top entrance/bottom exit, outdoor. Bottom: Figure: 13 and 2:, 15 kV, switch and fuse section - bottom entrance/top, bottom, or side exit outdoor. l l l Refer to Selection Guide for specific applications. For 5 kV applications, use 15 kV table. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.7 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG 5-35 kV. Units shown from left: Figure 4: 15 kV, entrance section non-fused switch - bottom feed, outdoor. Figure 9: 15 kV, metering section, outdoor. Figure 8: 15 kV, fused switch distribution section, outdoor. l For specific applications, refer to Section Guide. l For 5 kV applications, use 15 kV table. l For special configurations and sizes, consult factory. 6.1.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Transformer Disconnects. (Transformer, primary selector switch): Figure 15: 15 kV, switch only and switch/fuse section - top entrance,top, bottom, or side exit, outdoor. Figure 2: 15 kV, transition section, outdoor. l l For specific applications, refer to Section Guide. For 5 kV applications, use 15 kV table. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.9 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 2000 ampere, 5 kV, distribution section fused switch with incoming terminations - Bottom entrance/bottom exit, and 2 - Distribution section fused switch, bottom exit with electrically operated switches and ground fault protection, indoor. l For custom designs, consult factory. 6.1.10 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 600 ampere, 15 kV, indoor construction. Figure 13: Switch and fuse section, bottom entrance/bottom exit with electrically operated vacuum interrupter switch, over-current protection, and pothead terminators. l For custom designs, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.11 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 600 ampere, 15 kV outdoor construction. Figure 15: Non-fused selector switch - top entrance/top exit with mimic bus, metering,and control compartment. l For custom designs, consult factory. 6.1.12 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 600 ampere, 5 kV outdoor stainless steel construction (NEMA 4X). Figure 12: Switch and fuse section - top entrance/bottom exit, door in door construction. l For custom designs, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.13 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 400 ampere, 5 kV, motor contactor - top entrance/bottom exit with metering, protection and controls, outdoor, (similar to NEMA 4). l For custom designs, consult factory. 6.1.14 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR Model SMEG, 5-35 kV. Custom Designs. Unit shown is: Customer specified 600 ampere, 35 kV, distribution section fused switch with incoming terminations - Bottom entrance/bottom exit, and 2 - Distribution section fused switch, bottom exit with electrically operated switches and ground fault protection, indoor. l For custom designs, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.1.15 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.1.16 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR (WALL-HUNG) Model SWHG, 5-25 kV. 600 Ampere Max. Applications: General and specialized switching of electric power systems. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 6.2.1 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR (WALL-HUNG) Model SWHG, 5-25 kV. 600 Ampere Max. Catalog Number Selection Sheet. To be used in conjunction with Factory Check Sheet. 6.2.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR (WALL-HUNG)) Model SWHG, 5-25 kV. 600 Ampere Max. Factory Check Sheet. To be used in conjunction with Catalog Number Selection Sheet. RATINGS: Nominal System Voltage/ Maximum design Voltage Basic Insulation Level (BIL) ____/____ kV o 5 kV, 60 kV BIL o 15 kV, 95 kV BIL o 25 kV, 125 kV BIL o Other: ____ kV, ____ kV BIL Continuous Current (Line) ____ amp Main Disconnect Switching Device ____ amp, ____kV, ____kV BIL Capacitor Switching Device ____ amp, ____ kV, ____ kV BIL, Type: o Oil. o Vacuum Fuse Ratings: ____ amp, ____ kV, Type: ________, Voltage: ____ Enclosure Type: o Indoor o Outdoor Material: o A60 Galvanneal Steel o 304L Stainless Steel Paint Finish: o Green Munsell No., 7GY 3.29/1.5 o Gray (ANSI 70). Munsell No., 5BG 7.0/0.4 o Gray (ANSI 61). Munsell No., 8.3G 6.10/0.54, (standard) o Other: _______________________________ 3-Point Latch Type: o Penta-Head Bolt and shielded padlockable shackle, Shallbetter #70155. Manufactured to meet or exceed A.N.S.I. C5712.28 for Padmount Equipment Enclosure Integrity. o Hex-Head Bolt and shielded padlockable shackle, Shallbetter #70156 o Padlocking Handle, Shallbetter #70153 Ground Options: o Ground Bails o Ground Bosses, 1/2-13 UNC. Qty: ________, Location: ___________ o Strip Heaters o Insulating “Non-Drip” Compound. Applied to the inside surface of the enclosure roof to prevent condensation. o Specials: (Factory Check Sheet Continued on page 6.2.4) © 2002 Shallbetter Inc. www.shallbetter.com 6.2.3 Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR (WALL-HUNG) Model SWHG, 5-25 kV. 600 Ampere Max. Factory Check Sheet (continued). Standard Component Options Switches l l l l l ABB Cutler-Hammer Powercon S&C Square D Fusing l l l l Miscellaneous l l l l Cooper Cutler-Hammer General Electric S&C Porcelain Insulators Glass Polyester Insulators Cycloaliphatic Insulators Polycrete Insulators Options o o o Key Interlocks Insulated Bus Mimic Bus Protective Inner Barrier, (Metal-Screen is standard on Model suffix MSF). Other models Metal-Screen is optional unless otherwise stated. o NEMA Type GPO-3, Glass Reinforced Polyester o Clear Polycarbonate o o o o o o o o o Space Heaters * Roof Top Bushings Surge Arresters Interior Lighting Instrumentation Packages Motor Operator or Solenoid Trip Terminating Hardware Neoprene Door Gasketing Padlockable Switch Handle Cover * Space heaters are provided standard with outdoor equipment. 6.2.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-ENCLOSED SWITCHGEAR (WALL-HUNG) Model SWHG, 5-25 kV. Selection Guide. Circuit Diagram l l Model/Style SWHG-30502MS SWHG-30506MS SWHG-31502MS SWHG-31506MS SWHG-30502MF SWHG-30506MF SWHG-31502MF SWHG-31506MF SWHG-30502MSF SWHG-30506MSF SWHG-31502MSF SWHG-31506MSF kV 5 5 15 15 5 5 15 15 5 5 15 15 Amperage 200 600 200 600 200 600 200 600 200 600 200 600 H W D WGT Consult Factory Consult Factory Consult Factory For 25 kV configurations and sizes, consult factory. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.2.5 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.2.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Models SMCG and SMECG, 5-35 kV. 3000 Ampere Max. Applications: The Shallbetter Inc. models SMCG and SMECG line of Metal-Clad and Metal Enclosed/Clad Gear is constructed in accordance with the latest applicable industry standards and governing and/or electric code requirements. The Shallbetter models SMCG and SMECG Switchgear is intended for use on power distribution systems for transformer protection, isolation/sectionalizing or service entrance/power distribution at medium voltage. Shallbetter’s flexibility in design allows the integration of switches and circuit breakers into standardized lineups of custom designed switchgear. For complete specifications, please contact your authorized Shallbetter representative. © 2002 Shallbetter Inc. www.shallbetter.com 6.3.1 Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Models SMCG and SMECG, 5-35 kV. 3000 Ampere Max. 6.3.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Models SMCG and SMECG, 5-35 kV. 3000 Ampere Max. “A” Compartment “B” Compartment l n u ¨ l Requires blank in "A" Compartment. n PT roll-out is in the mid position. PT or CPT roll-out is in the lower position. u PT roll-out is in the mid position. Fuse roll-out is in the lower position. o Fuse roll-out is in the lower position only. © 2002 Shallbetter Inc. www.shallbetter.com 6.3.3 Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Models SMCG and SMECG, 5-35 kV. Options Sheet. Features l l l l l l l l l l l l l l l l 11 Gauge, Galvanneal Steel All Weld Construction C4x5.4 Channel Base Hinged Compartment Doors Paint Finish Meets/Exceeds ANSI C57 12.28 Copper or Aluminum Bus Continuous Ground Bus Lifting and Handling Provisions Non-Corrosive Nameplate Modular Breaker Cells Isolated Through Bus Open Door Retainers Padlockable Switch Operator Handle Space Heaters* 14 Gauge, Type SIS, Control Wiring Interfaces with Shallbetter Metal-Enclosed Switchgear Standard Component Options Circuit Breakers l l l l l ABB General Electric Siemens Square D Cutler Hammer Relaying l l l l l ABB Basler General Electric Schweitzer Customer Specified Miscellaneous l l l Porcelain Insulators Cycloaliphatic Insulators Polycrete Insulators Options o o o o o o o o o o o o o Stainless Steel or Aluminum Construction Screened Tamperproof Louvers Insulated Bus. ** Coal Tar Epoxy Base Coating No-Drip Inner Roof Coating Mimic Bus ANSI Specification 3 Point Penta-Head Bolt Latching, (Outdoor only) Walk-In Sheltered Aisle Space Heaters * Roof Top Bushings Pot Head Terminators Surge Arresters Interior/Exterior Lighting o o o o o o o o o o o o Duplex Outlets Control Power Instrumentation Packages Automatic Bus Transfer Schemes Neoprene Door Gasketing Provisions for Future Extensions Climate Control Packages Rear Access Bolted Lift-off Panels with Padlocking Provisions Hinged Rear Panels with Padlocking Handles U.L. Label, (5 and 15 kV) (Consult Factory) Other Special Options Available * Space heaters are provided standard with outdoor equipment. ** Insulated bus standard with ANSI class Metal-Clad Switchgear. 6.3.4 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Models SMCG and SMECG, 5-35 kV. Standard Side Views. Dimension shown for standard side views are 15 kV rated enclosures. © 2002 Shallbetter Inc. www.shallbetter.com 6.3.5 Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Model SMECG, 5-35 kV. Unit shown from left to right: Figure 4: 15 kV, entrance section - bottom feed, outdoor. Figure 8: 15 kV, distribution section, fused switch, outdoor. Metal-Clad Section, compartment A with special metering and compartment B with 1200 ampere. Breaker compartment. l l l l Refer to Section Guide for specific applications for Metal-Enclosed Switchgear. For 5 kV applications, use 15 kV table. For 15 through 35 kV applications, consult factory. For special configurations and sizes, consult factory. 6.3.6 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Model SMECG, 5-35 kV. Unit shown from left to right is: Figure 4: 35 kV, entrance section - top feed with top-hat, outdoor. Figure 6: 35 kV, metering section. Figure 6: 35 kV, metering section. Metal-Clad Section, compartment A with special metering and compartment B with 1200 ampere. Breaker compartment. Metal-Clad Section, compartment A with special metering and compartment B with 1200 ampere. Breaker compartment. l l l l Refer to Section Guide for specific applications for Metal-Enclosed Switchgear. For 5 kV applications, use 15 kV table. For 15 through 35 kV applications, consult factory. For special configurations and sizes, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.3.7 Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Model SMECG, 5-35 kV. Custom Designs. 6.3.8 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü METAL-CLAD AND METAL-ENCLOSED HYBRID SWITCHGEAR Model SMECG, 5-35 kV. Custom Designs. Unit shown on pages 6.3.8 and 6.3.9 is outdoor hybrid Metal-Enclosed/Metal-Clad Switchgear. Facing the front from left to right is: Figure 7: 15 kV, distribution section, non-fused switch. Metal-Clad section, compartment A with potential transformers. Compartment B with 1200 ampere. Breaker, over-current and ground fault protection. Section is terminated with roof and supplied with surge protection. l l For specific applications for Metal-Enclosed Switchgear, refer to the Selection Guide. For custom designs, consult factory. © 2002 Shallbetter Inc. www.shallbetter.com 6.3.9 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.3.10 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PARALLELING SWITCHGEAR Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 6.4.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.4.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü DGXTM DISTRIBUTED GENERATION TRANSFER SWITCHGEAR Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 6.5.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.5.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü UTILITY POWER CONTAINER SWITCHGEAR Under development. Will be included in a future release. © 2002 Shallbetter Inc. www.shallbetter.com 6.6.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.6.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü UTILITY INTER-TIE / PARALLELING Under development. Will be included in a future release. © 2002 Shallbetter Inc. www.shallbetter.com 6.7.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 6.7.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü PRODUCT CODES and DESCRIPTIONS CODES DESCRIPTIONS SFGD Padmount Fusegear Deadfront SFGL Padmount Fusegear Livefront SPD Padmount Switchgear Deadfront SPL Padmount Switchgear Livefront SSGD Padmount Switchgear Deadfront 6 Bay SSGL Padmount Switchgear Livefront 6 Bay SPMD Padmount Primary Metering Deadfront SPMG Padmount Primary Metering Deadfront with GE Xfmr SPML Padmount Primary Metering Livefront SCSD Padmount Cable Switching Enclosure Deadfront SSED Padmount Sectionalizer Enclosure STEN Padmount Termination Enclosure 600V w/o CTs STEI Padmount Termination Enclosure 600V with CTs STMV Padmount Termination Enclosure 5-35 kV SECL Padmount Telephone Cable Splicing Enclosure SCBD Padmount Capacitor Bank Deadfront SCBL Padmount Capacitor Bank Livefront SCBM-M1 Metal-enclosed Capacitor Bank with Single Side Access SCBM-M2 Metal-enclosed Capacitor Bank with Double Side Access SCBM-S1 Multi-step Capacitor Bank with Single Side Access SCBM-S2 Multi-step Capacitor Bank with Double Side Access RTX SMEG SMEG/SMCG RTXTM Active Power Factor Correction Metal-enclosed Switchgear Metal-enclosed / Metal-clad Switchgear SWHG Metal-encloded Wall Hung Switch / Fuse Enclosure SMCG Metal-clad Switchgear LVSG Low Voltage Switchgear LVPS Low Voltage Paralleling Switchgear MVPS Medium Voltage Paralleling Switchgear SPCP Paralleling Control Panel SDFS Low Voltage Deadfront Switchboard DGX DGXTM Distributed Generation Transfer Switchgear MISC Miscellaneous © 2002 Shallbetter Inc. www.shallbetter.com 7.1.1 Û INDEX Ü Û INDEX Ü This page is intentionally left blank. 7.1.2 © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü TERMS and CONDITIONS The following Conditions of Sale shall govern the sale of any equipment, apparatus, process, services, or other product, hereafter referred to as "product". APPLICABLE TERMS AND CONDITIONS Shallbetter Inc. (hereafter referred to as Shallbetter) hereby gives notice of its objection to any different or additional terms and conditions. This sale is expressly conditional on Purchasers' assent to the terms and conditions stated below. If not previously given, Purchasers' acceptance of product is conclusive as to this assent. Unless different or additional terms and conditions are stated or referred to in the Shallbetter proposal, in which event such different or additional terms and conditions shall be exclusive as to the particular subject covered, the terms and conditions stated below apply, and such terms and conditions supersede any prior or contemporaneous agreements or correspondence between the parties. QUOTATIONS Each quotation is valid for 30 days from its date unless otherwise stated in the quotation. PRICES Prices stated on sellers acknowledgment for orders, or items or quantities thereon, for which the release for manufacturing is no later than 90 days after customer receives final drawings, are not subject to upward or downward adjustments. Minimum Order charge is $250.00. TAXES The price does not include any Federal, state or local property, license, privilege, sales, use, excise, gross receipts or other like taxes which may now or hereafter be applicable. Payment by Shallbetter of any such taxes shall be for the account of the customer. TERMS OF PAYMENT 1. Payment terms are net 30 days from date of invoice. 2. If, in the judgment of Shallbetter the financial condition of Purchaser at any time prior to delivery does not justify the terms of payment specified, then Shallbetter may require payment in advance or cancel any outstanding order, whereupon Shallbetter shall be entitled to receive cancellation charges per Table A. If delivery is delayed by Purchaser, payment shall become due on the date Shallbetter is prepared to make delivery. Delays in delivery or non-conformities in any installments shall not relieve Purchaser of its obligation to accept and pay for remaining installments. 3. If Payments are not made when due, Purchaser shall pay, in addition to the overdue payment, a late charge equal to the lesser of 1½% per month or the highest applicable rate allowed by law on all such overdue amounts. DELIVERY Unless otherwise specified, all products are shipped F.O.B. point of shipment, regardless of transportation costs being "allowed", "prepaid" or "collect". SHIPPING SCHEDULES Shipping dates are approximate and are based on receipt of complete information with the order. If drawing approval is required, drawings must be returned on schedule to maintain estimated shipping date. Change in shipping date due to vendor delays, production interruption or changes by the customer shall not hold Shallbetter responsible for penalties, back charges or incurred cost. DRAWING APPROVAL AND CHANGES Unless mutually agreed upon, Shallbetter requires approval of submittal drawings. Such review, comment and/or approval must be received by Shallbetter prior to commencing with manufacturing. Customer agrees to release for manufacturing all equipment no later than 60 days after receipt of final corrected drawings for approval. Purchaser's failure to comply with this requirement could result in delays in performance and increased costs. Where Purchaser's specifications are not sufficiently detailed, Shallbetter reserves the right to design the product in line with, in Shallbetter's judgment, good commercial practice. If at any time, the Purchaser makes changes to the contract design as covered in the project specifications, the contract shall be subject to renegotiation of the price terms and delivery to reasonably cover any additional costs and commitments occasioned by the change. SHIPMENT DAMAGE Except in the event of F.O.B. destination shipments, Shallbetter will not participate in any settlement of claims for concealed or other shipment damage. When shipment has been made on an F.O.B. destination basis, the Purchaser must unpack immediately and, if damage is discovered, must: 1. Not move the product from the point of examination. 2. Retain shipping container and packing material. 3. Notify the carrier of any apparent damage in writing on carrier's delivery receipt and request the carrier to make an inspection. 4. Notify the Shallbetter location from which shipment originated within 72 hours of delivery. 5. Send Shallbetter a copy of the carrier's inspection report. FORCE MAJEURE Shallbetter shall not be liable for failure to perform or for delay in performance due to, any cause beyond its reasonable control, or fire, flood, strike or other labor difficulty, act of God, natural disasters, act of governmental authority or of the Purchaser, riot, act of war, terrorism, vandalism, criminal activities by others, embargo, fuel or energy shortage, car shortage, faulty castings or forgings, wrecks or delay in transportation, or inability to obtain necessary labor, materials or manufacturing facilities from usual sources. In the event of delay © 2002 Shallbetter Inc. www.shallbetter.com 7.2.1 Û INDEX Ü Û INDEX Ü in performance due to any such cause, the date of delivery or time for completion will be extended by a period of time reasonably necessary to overcome the effect of such delay. PENALTY CLAUSES / LIQUIDATED DAMAGES Shallbetter will not accept any penalty or liquidated damage clauses of any kind, written or implied, or any liability arising from such clauses, unless specifically approved in writing by a duly authorized officer of the company. INSPECTION AND ACCEPTANCE Purchaser has a reasonable time after receipt of the product to inspect and reject or accept the product. In any event acceptance will be deemed to have occurred no later than 30 days after shipment. TITLE / RISK of LOSS The product sold shall remain the property of Shallbetter and shall remain personal property until fully paid for in full, and the Purchaser agrees to perform all acts, which may be necessary to perfect and assure retention of title to such product by Shallbetter. Risk of loss of the product, or any part of same, shall pass to the Purchaser upon delivery of such product or part at the designated delivery (F.O.B.) point. TERMINATION BY PURCHASER Any order of contract may be terminated by the Purchaser only by written notice and upon payment of reasonable and proper termination charges, including but not limited to all costs identified to the order or contract which have been incurred up to the date of notice of termination, unless mutually agreed upon. The buyer agrees to remit to Shallbetter the full amount for any and all expenses incurred prior to written receipt of cancellation in accordance with the following Table A. Payment shall be made within 30 days from date of invoice. CANCELLATION BY SHALLBETTER Shallbetter shall have the right to cancel at any time by written notice for any material breach of the contract by the Purchaser. RETURN GOODS 1. Prior written authorization is absolutely required before Return Merchandise will be accepted. 2. Buyer is responsible for prepaying freight charges. 3. Equipment will not be accepted unless adherence to cancellation clause has been met. 4. Shallbetter reserves the right to specify the receiving point of all Return Merchandise regardless of original shipping point. SUSPENSION BY PURCHASER Any orders held or delayed or rescheduled at the request of the Purchaser will be subject to the prices and conditions of sale in effect at the time of the release of the hold or the reschedule. Any such order held, delayed or rescheduled 7.2.2 beyond a reasonable period of time will be treated as a Purchaser termination. (Refer to Table A) DELAYED SHIPMENT When products are ready for shipment and shipment cannot be made because of reasons beyond Shallbetter control, Shallbetter shall submit an invoice for such product payable upon receipt thereof and shall, upon written notice to the Purchaser, store such products. Storage charges will be on a negotiated basis. TABLE A: CANCELLATION / RETURN GOODS n Order Entered - 5% n Drawings Completed - 10% n Drawings Approved/ Material Ordered - 25% n Production in Process - 75% n Equipment Complete - 100% LIMITED WARRANTY** Unless otherwise mutually agreed upon, Shallbetter Inc. (the manufacturer) warrants this product to the original purchaser against defects in materials and workmanship for a period of 18 months after shipment or 12 months after energization, which ever comes first. This warranty does not cover, and the manufacturer shall not be liable for damages arising from any product installed or used for a purpose other than that which it is intended or in a manner inconsistent with any instructions, local codes, and/or national electrical codes regarding its installation or use. In order to obtain performance of this warranty, the purchaser must return the product prepaid along with the proof of manufacture by Shallbetter, to the manufacturer, Attn. Warranty Department. Thereafter, the manufacturer shall replace or repair the product if it is defective. Sub Components that fail within the specified warranty period shall be repaired or replaced upon mutual agreement between Shallbetter and the original purchaser. Shallbetter will expedite repair or replacement of the failed component with like components. Shallbetter has no control of independent suppliers and will not be liable for incidental charges incurred due to component failure. Upon receipt of the replaced component, the original purchaser is requested to return the failed component to Shallbetter. Failure to return faulty components to Shallbetter within 60 days of replaced component receipt will result in invoicing for components supplied. Analysis of returned failed components will be conducted by Shallbetter and/or independent sources to determine failure mode. If the component failed due to damage, and the damage is not Shallbetter related, the end user is liable for parts and related costs incurred to repair unit. Damage immediately voids any warranty provisions implied or stated by this policy. All implied warranties, including all implied warranties of merchantability or fitness for a particular purpose, are limited to one year from the date of purchase.* * Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. **from original doc. number SICO1030A © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX Ü Û INDEX Ü GLOSSARIES Under development. Will be included in a future release © 2002 Shallbetter Inc. www.shallbetter.com 7.3.1 Û INDEX Ü Û INDEX Ü CONTACTING SHALLBETTER INC. Shallbetter Inc. hq: 2050 South Oakwood Road Oshkosh, WI 54904-6308 ph: ph: fx: e-m: 920.232.8888 800.843.0051 920.232.8977 info@shallbetter.com web: www.shallbetter.com © 2002 Shallbetter Inc. www.shallbetter.com 7.4.1 Û INDEX Ü Û INDEX Ü LIMITED WARRANTY STATEMENT Unless otherwise mutually agreed upon, Shallbetter Inc. (the manufacturer) warrants this product to the original purchaser against defects in materials and workmanship for a period of 18 months after shipment or 12 months after energization, which ever comes first. This warranty does not cover, and the manufacturer shall not be liable for damages arising from any product installed or used for a purpose other than that which it is intended or in a manner inconsistent with any instructions, local codes, and/or national electrical codes regarding its installation or use. In order to obtain performance of this warranty, the purchaser must return the product prepaid along with the proof of manufacture by Shallbetter, to the manufacturer, Attn. Warranty Department. Thereafter, the manufacturer shall replace or repair the product if it is defective. Sub Components that fail within the specified warranty period shall be repaired or replaced upon mutual agreement between Shallbetter and the original purchaser. Shallbetter will expedite repair or replacement of the failed component with like components. Shallbetter has no control of independent suppliers and will not be liable for incidental charges incurred due to component failure. Upon receipt of the replaced component, the original purchaser is requested to return the failed component to Shallbetter. Failure to return faulty components to Shallbetter within 60 days of replaced component receipt will result in invoicing for components supplied. Analysis of returned failed components will be conducted by Shallbetter and/or independent sources to determine failure mode. If the component failed due to damage, and the damage is not Shallbetter related, the end user is liable for parts and related costs incurred to repair unit. Damage immediately voids any warranty provisions implied or stated by this policy. All implied warranties, including all implied warranties of merchantability or fitness for a particular purpose, are limited to one year from the date of purchase.* *Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. from original doc. number SICO1029A © 2002 Shallbetter Inc. www.shallbetter.com 7.5.1 Û INDEX Ü Û INDEX Ü ANSI / IEEE DEVICE NUMBERS The devices used in system protection are referred to by numbers, with suffix letters when necessary, according to the functions they perform. This system is used as a numbering standard throughout the power industry in electrical diagrams, instruction manuals and specifications. This is a partial list of the device numbers commonly used. For a complete listing, refer to ANSI/IEEE C37.2. DEVICE # FUNCTION 21 DISTANCE RELAY - Functions when the circuit impedance, or a component of impedance, increases or decreases beyond predetermined limits. 25 SYNC-CHECK RELAY - Functions when two ac circuits are within desired limits of frequency, phase angle and voltage to permit the paralleling of these two circuits. 25A AUTOMATIC SYNCHRONIZING RELAY - Acts to bring two ac circuits within desired limits of frequency, phase angle and voltage then initiates the paralleling of these two circuits. 27 27N UNDERVOLTAGE RELAY - Functions on a given value of undervoltage. GROUND FAULT UNDERVOLTAGE RELAY - Functions on a given value of third harmonic undervoltage. 32 POWER RELAY - Functions on a desired value of power flow in a given direction. 37 UNDERCURRENT RELAY - Functions on a given value of undercurrent. 40 LOSS OF FIELD RELAY - Functions on a given value of dc field current. 41 FIELD BREAKER - A device used to apply and remove the field excitation of a machine. MANUAL SELECTOR SWITCH - Used to control circuit operation. 43 46 PHASE BALANCE CURRENT RELAY - Functions on a given degree of unbalance between the polyphase currents. 46N NEGATIVE SEQUENCE OVERCURRENT - Functions when the polyphase currents contain negative sequence components above a given value. 47 PHASE SEQUENCE VOLTAGE RELAY - Functions on a given value of polyphase voltage in the desired phase sequence. 47N NEGATIVE SEQUENCE VOLTAGE RELAY -Functions on a given value of the negative sequence component of the polyphsae voltage. 49 TEMPERATURE RELAY - Functions when the temperature of a machine, transformer or other load carrying winding exceeds a given value. 50 INSTANTANEOUS OVERCURRENT RELAY - Functions without intentional time delay when the current exceeds a given value. 5OBF BREAKER FAILURE RELAY - Functions when current continues to flow after the monitored breaker should have interrupted a fault. 51 TIME OVERCURRENT RELAY - Functions with a definite or inverse time characteristic when the current exceeds a given value. © 2002 Shallbetter Inc. www.shallbetter.com 7.6.1 Û INDEX Ü Û INDEX DEVICE # 51/27C VOLTAGE CONTROLLED TIME OVERCURRENT RELAY - A time overcurrent relay which is enabled by an undervoltage function. 51/27R VOLTAGE RESTRAINED TIME OVERCURRENT RELAY - A time overcurrent relay whose pickup is adjusted by an undervoltage function. 52 AC CIRCUIT BREAKER - A device used to close and interrupt an ac power circuit. 55 POWER FACTOR RELAY - Functions when the power factor falls below a given value. 59 OVERVOLTAGE RELAY - Functions as a given value of overvoltage. 59N 7.6.2 FUNCTION GROUND FAULT OVERVOLTAGE RELAY - Functions on a given value of overvoltage at the fundamental frequency. 59/81 VOLTS PER HERTZ OVEREXCITATION RELAY - Functions when the voltage to frequency ratio exceeds predetermined limits. 60 VOLTAGE BALANCE RELAY - Functions on a quantitative voltage difference between two circuits. 64 GROUND DETECTOR RELAY - Functions on the failure of the insulation of a machine or other apparatus. Used only for normally ungrounded circuits. 65 GOVERNOR - Functions to control the mechanical power output of a generator prime mover. 67 DIRECTIONAL OVERCURRENT RELAY - Functions on a given value of current flowing in a predetermined direction. 74 ALARM RELAY - Functions to provide an alarm. 79 RECLOSING RELAY - Functions to control the automatic reclosing and lockout of an ac circuit breaker. 81 FREQUENCY RELAY - Functions on a given value of frequency either under or over the normal system frequency. 86 LOCKOUT RELAY - An electrically tripped, hand reset, relay that functions to shut down and hold equipment out of service. 87 DIFFERENTIAL RELAY - Functions on a quantitative difference of two currents. 90 VOLTAGE REGULATOR - Functions to regulate the voltage between certain limits for machines. © 2002 Shallbetter Inc. www.shallbetter.com Û INDEX