National Electrical Grounding Research Project Technical Report August 30, 2007 Prepared by: Travis Lindsey Travis Lindsey Consulting Services Inc. Prepared for: The Fire Protection Research Foundation 1 Batterymarch Park Quincy, MA 02169-7471 Foreword The use of electricity has long been recognized as a potential hazard to people and property. When an electrical system fails, the result can cause accidental electrocution, fire, causality, and equipment damage. The concept of circuit grounding for electrical systems was one of the more hotly contested topics in the early history of electrification. In the early 1890’s, the New York Board of Fire Underwriters had condemned the practice of grounding the neutral as a dangerous practice. The Edison utility companies, on the other hand, found just cause to ground their supply systems, even as others thought the utilities were doing this just to save copper and money at the cost of an increased fire risk. The great debate continued for over a decade, but in 1903 the National Electrical Code (NEC®) was revised to recommend that certain circuits be grounded, and finally in the 1913 NEC® a mandatory circuit grounding requirement was included for these circuits. [1] One of the most common ways to ground a wiring system has been to use the building’s metal water piping as a grounding electrode. The early Codes permitted water-piping systems of 3 ohms or less to ground to be used as an electrode, which was usually the case if the metal water pipe extended several feet into the ground. In 1923, the NEC® first mentioned driven rod or pipe electrodes. The 1925 NEC® further referred to these driven electrodes as “artificial” electrodes, and required them to be at least 8 feet long, with minimum diameters of ½ in. for a rod and ¾ in. for pipe. It also noted that if only one of these artificial electrodes had a resistance of greater than 25 ohms to ground, then two artificial electrodes had to be provided, spaced at least six feet apart. In subsequent years, and in recognition of the increased use of non-metallic water pipe, requirements were added to the NEC® to supplement the water-pipe electrode with an additional electrode or electrodes. [1] The practice of grounding (earthing) electrical systems to buried electrodes has been recognized for decades by the National Fire Protection Association (NFPA) and other safety standards development organizations as the recommended method to safeguard against people and property becoming the accidental electrical connection to the earth. There is ample evidence that accidental contact with earth can cause stray voltages, and dangerous errant current flows. The electrical system’s grounding electrode provides the system with a predetermined, and calculable path, to channel away dangerous currents, and reduce electrical hazards. In the absence of an effective grounding electrode, the stray voltages or path of any ground currents often must be determined forensically after an accident has occurred, by site survey, computations, and subjective opinion. Today, the NEC® recognizes electrical system grounding as an effective means to limit the voltage imposed by lighting, line surges, or unintentional contact with higher-voltage lines, as that will stabilize the voltage to earth during normal operation. The NEC does not include requirements for or the instruments to be used in testing the performance of the grounding electrode, thus, many default conditions could exist with simply two electrodes. In some soil conditions, two electrodes may produce a resistance to earth far in excess of 25 ohms, and that would still be acceptable. ii There are many unknowns in predicting how each of the many types of electrodes may perform their intended purpose of providing proper electrical grounding. Factors which may relate to performance of the electrode include: earth resistivity, earth chemistry, earth moisture, earth temperature, electrode resistance, weather or seasonal changes in the moisture of the earth, the current carrying capability of the electrode in earth, corrosion, material comprising the electrode, and mass of the electrode. The repeatability and reproducibility of the measurement of several of these factors can often not be accounted for to any great extent. The longevity of an electrode is another issue that cannot be easily addressed in installation codes or performance standards. Electrodes are rarely re-tested after installation, and rarely replaced or augmented. Electrodes may be damaged by lightning, direct impressed currents, corrosion or mechanical means. This report includes basic information which can be used by professionals who design, construct and install grounding systems and components, and for those who develop codes, standards or specifications. Those who work with grounding should understand that the grounding electrode resistance to earth can fluctuate. The resistance can fluctuate with the seasonal variations of soil temperature and moisture. In addition, the inherent conductivity of the soil can vary between different locations due to the natural chemical makeup and physical characteristics. This report documents the variation of grounding electrode earth resistance at different geographic locations and explores the effects of several of the dominant variables over a period of ten years. The data in this report including the electrode resistance, ancillary experiment results, soil characteristics and the corrosion data shown in Appendix 11.3, provides important information for designers, manufacturers and regulatory officials on the performance of grounding electrodes and components. iii TABLE OF CONTENTS 1. INTRODUCTION 1.1. Background/Chronology 1.2. Objectives 1.3. Scope 2. TEST SITES 3. ELECTRODE TEST SAMPLES 3.1. Electrode Legend 3.2. Electrode Details 4. EXPERIMENTS and METHOD 4.1. Sample Preparation 4.2. Installation and Exhumation 4.3. Electrode Resistance 4.4. DC Active Experiments 4.5. Dissimilar Metals Passive Experiments 4.6. Earth Resistivity 4.7. Soil Moisture 4.8. Soil Temperature 4.9. Passive Metal Corrosion 5. INSTRUMENTATION 5.1. Earth Testers 5.2. Multi-Meters 5.3. DC Current Probe 5.4. Thermocouple Thermometer 5.5. Moisture Meter 6. RESULTS 6.1. Electrode Resistance 6.1.1. Percentage of Readings Exceeding Certain Values 6.1.2. Resistance of Individual Electrodes at all Sites 6.1.3. Vertical and Horizontal Electrode Resistance- Las Vegas Sites 6.1.4. Vertical and Horizontal Electrode Resistance- National Sites 6.1.5. Comparison of Electrode Resistance 6.2. Ancillary Experiments 6.2.1. DC1 and DC2 Results 6.2.2. Dissimilar Metals Results 6.2.3. Benign Corrosion Experiments 6.3. Soil Characteristics 6.3.1. Earth Resistivity 6.3.2. Earth Resistivity versus Resistance for Selected Electrodes 6.3.3. Soil Temperature 6.3.4. Earth Resistivity and Soil Temperature 6.3.5. Soil Moisture 6.4. Corrosion Results 7. SUMMARY 8. AREAS of FURTHER STUDY 9. LIST OF FIGURES 10. CITATIONS iv pg. 1 pg. 2 pg. 4 pg. 4 pg. 5 pg. 6 pg. 6 pg. 10 pg. 18 pg. 18 pg. 18 pg. 19 pg. 19 pg. 20 pg. 20 pg. 20 pg. 20 pg. 20 pg. 22 pg. 22 pg. 22 pg. 22 pg. 22 pg. 22 pg. 24 pg. 25 pg. 25 pg. 29 pg. 34 pg. 47 pg. 56 pg. 83 pg. 83 pg. 92 pg. 96 pg. 97 pg. 97 pg. 98 pg. 100 pg. 105 pg. 109 pg. 114 pg. 117 pg. 120 pg. 122 pg. 125 11. APPENDICES (on CD) 11.1 Electrode Graphs Las Vegas 11.2 Electrode Graphs National 11.3 Corrosion Report 11.4 Exhumation Reports 11.5 Soils Reports 11.6 National Sites Construction Plans 11.7 Las Vegas Sites Construction Plans v 1 INTRODUCTION The practice of connecting electrical systems to earth using grounding electrodes has historically been the preferred means to safeguard against results of accidental contact of electrical power to earth. Previous research by the National Association of Corrosion Engineers Task Group T-4A3, “Methods and Materials for Grounding” (1966) and Naval Civil Engineering Laboratory, Technical Report R660, “Field Testing of Electrical Grounding Rods” (1970) indicated some degree of variability in the performance of commonly used types of grounding electrodes. In 1995, the National Electrical Grounding Research Project (NEGRP) was created by the Fire Protection Research Foundation (FPRF) to study this issue, and a technical advisory committee (TAC) was formed. The purpose of the TAC was to develop the scope, implement the site installations, make critical decisions during the term of the project, and insure that annual and final reports were issued. The project, which was managed by FPRF, evaluated many types of grounding electrodes in differing geographies to provide comparative results for a broad range of conditions, and to study electrodes over extended periods of time. This involved recording periodic measurements of electrode performances, and recording of soil conditions over the period of the study. Some features of the project included electrode resistance, earth resistivity, earth temperature, earth moisture, and effects of direct current on electrodes. After being buried for extended periods, some electrodes at selected sites were exhumed for corrosion analysis, and observation. Throughout the term of the project, the FPRF issued ten annual data collection reports beginning in 1995. (Available from FPRF) This report and its appendices includes background, data, results, summaries, and areas for further study. 1 1.1 Background/Chronology The research project was initiated as an effort to identify, and provide resolution for issues related to electrical grounding. In 1990, the Southern Nevada Chapter of the International Association of Electrical Inspectors (IAEI /SNC) initiated a study of buried grounding electrodes. Materials, labor, instrumentation, and maintenance needed for the IAEI study were donated by individuals, members at large, and by manufacturer participants whose products were included in the study. The scope of the study initially encompassed five test sites in the Las Vegas Valley, the last of these being installed in 1992. Each site contained sets of approximately 18 different types of buried grounding electrodes. Layout and electrode selection was similar for each site to facilitate direct comparison of data. Measurements were taken bi-monthly. The program included grounding electrodes which were not connected to a power source (passive electrodes), electrodes connected to a DC supply (active electrodes), and evaluation of bare conductor electrodes to evaluate the effects of dissimilar metals (passive electrodes), located in close proximity, in the same soil. One of each electrode type was installed in the Las Vegas sites. Some sample electrodes were encased in concrete and other materials during installation. Stranded copper 6 AWG conductors were installed from the electrodes to a terminal junction box, where data was collected. To test the effectiveness of connections, most of the electrodes were equipped with ERICO® Cadweld tm exothermically welded connectors, Burndy ® bolted type connectors, and some were additionally equipped with Burndy ® Hyground tm compression type connectors. In an effort to provide consistency of results, permanent test pins for electrode resistance and soil resistivity measurements were installed at predetermined locations on each site. In the following years, (1993- 1994) data were collected and reviewed for unusual characteristics. Some of these data from the study showed that there was a large diversity in results when comparing similar electrodes in different test site locations. These data were the subject of papers presented at IEEE conferences, [2] and articles presented to industry. Industry professionals interested in advancing the study including the Copper Development Association (CDA®), and the International Facility Management Association, recommended an expansion of the project to include other geographic locations around the country, noting that the diversity of performance seen in the Nevada study may not be isolated to the Las Vegas geography. During 1994, the governing committee (IAEI/SNC) for the Nevada study predicted difficulty in the prospective management for a proposed larger study and recognized a need to select a proctor for governance to maintain propriety. To provide independent oversight and review for the study, the Committee sought assistance from several university and research institutions. Initial contact was made with the Fire Protection Research Foundation in 1994. In 1995, FPRF formulated the first phase of the National Electrical Grounding Research Project (NEGRP). This project began by soliciting potential sponsors interested in funding a more comprehensive project with the objective of addressing the noted diversity by 2 installing electrodes in a number of test sites around the U.S. (termed the National sites in this report). Because soil temperature and moisture sensors were planned for the National sites, in 1995, sensors were also installed in the Las Vegas sites, in an effort to provide for data collection with consistency, Several sponsors elected to participate, which initiated Phase 1 of the NEGRP. A Technical Advisory Committee (TAC) was created, and during 1996 the planning of the expansion of Phase two was underway. During the Phase 1 deliberations, the original IAEI/ SNC Las Vegas sites were incorporated into the project by the TAC. Sites were selected from lands made available by the sponsors. Chief among the selection process was the requirement for data collection, and availability of site management. Phase two of this project which began in 1995, was originally planned to span five and one- half years, including start-up, and demobilization. Phase two of the project included the construction of five National sites at various locations in the U.S. including Illinois, Texas, California, Virginia and New York. 3 1.2 Objectives The primary objectives of the National Electrical Grounding Research Project were to: • • • • • Evaluate the performance, over time, of buried grounding electrodes. Provide information to regulators to use in enforcement of existing regulations. Provide information to standards development organizations for use in improving codes and standards. Provide information to industry that could be used to improve grounding system design and installation. Provide information to industry that could be used to develop new types of grounding electrodes. 1.3 Scope The scope of this project included ten test sites, five of which were in the Las Vegas Valley and five of which were in the National test sites. The test sites are shown in Table 1. Included in the project were 15 to 18 different types of passive and active direct current (DC) electrodes per site. Measurements included electrode resistance, soil temperature, soil moisture and earth resistivity. The project began in 1992 and ended in 2007. Some limitations of the project included the following. • • • • • Adequate funding to perform all initially desired scientific analyses of the samples. Personnel changes in management, staff, TAC membership, and within the ranks of the site managers. Some sites, specifically in Las Vegas, experienced encroachment of building construction. This resulted in earlier than anticipated exhumation. Funding prevented the TAC from hiring an archeologist to exhume the samples. Several of the TAC members personally did the exhumation and made every effort to ensure the samples were not damaged. Several limitations occurred during the DC experiments, including interruption of power, and required changes in instrumentation. 4 2 TEST SITES Test sites for this project included plots of land, representing different soil conditions which were selected in various locations to install buried grounding electrodes and conduct the specified experiments. The following sites shown in Table 1 were selected. Sites 1-5 were in the Las Vegas, Nevada area, and sites 6-10 were considered the National sites. Table 1 - Sites Legend SITE PA-1 LM-2 BA-3 PE-4 CH-5 LOCATION Pawnee Las Vegas, NV Central Lone Mountain Las Vegas, NV North Balboa Henderson, NV (LV) South Pecos Las Vegas, NV North Charleston Las Vegas, NV East INSTALL DATE REMOVE DATE SOIL CONDITIONS May-92 03 Water table ranging from 10 to 20 ft. generally clayey silt Jun-92 04 Normally dry, silty, sandy clays Aug-92 01 Normally dry, rock and gravel Dec-92 04 Normally dry , silt and sand to 6 ft., silty clays 6 to 11 ft. Dec-92 NA Normally dry, sand, and gravel, surface froth VA-6 Staunton, VA Jun-97 NA Sand, and silt to a depth of approximately 6 feet, silty clays 6 to 11 ft. TX-7 Dallas, TX Jun-98 NA Normally dry, sandy soil to a depth of 5 to 6 ft. increasingly stiff sandstone to 11 ft. NY-8 Hibernia, NY Sep-98 06 Water table at 10 ft to 11 ft. gravel, sand and clays with occasional cobbles to 11 ft. depth IL-9 Northbrook, IL Illinois Sep-98 NA Periodically covered with rainwater runoff, contains silts and clays to a depth of 11 ft. CA-10 Moffet Field, Mountain View, CA Jan-02 NA Normally dry, sand, silt with inorganic and organic clays 5 3 ELECTRODE TEST SAMPLES 3.1 Electrode Legend Tables 2 through 5 identify the electrode by material, installation parameters, length, fill surrounding the electrode, and orientation in the test site. Table 2 - Electrode Types A through K Electrode ID Material A No. 2 AWG stranded copper wire No. 4 uncoated steel reinforcing bar Centered in 12 in. of sand at 36 in. below grade measured to the conductor. 50 ft Orientation * H Fill or V Sand H Within, and near the bottom of a concrete foundation consisting of 12 in. by 12in. of 2500 psi concrete. The top of the concrete was located 6 in. below grade. 20 ft. Concrete H C No. 4 solid copper wire Centered in 6 in. by 6 in. of ERICO ® Ground Enhancement Material, (GEM tm) located at 20 in., to the bottom of the concrete. 25 ft GEM tm H D No. 4 solid copper wire Centered in 6 in. by 6in. of 2500 psi concrete. located at 20 in. to the bottom of the concrete. This electrode is designed to represent the thickened edge of post tensioned concrete construction. 25 ft Concrete H E Copper Bonded Steel Rod 5/8 in. diameter, centered in a 9 in. diameter, 9 ft. deep boring in earth, encased in ERICO ® (GEM tm ) backfill. 8 ft. GEM tm V F Copper Bonded Steel Rod 5/8 in. diameter, installed horizontally centered in a trench, encased in ERICO® (GEM tm) backfill, 24 in. to the bottom of the (GEM tm ) backfill material. 8 ft. GEM tm H G Copper Bonded Steel Rod 5/8 in. diameter, directly buried in a trench 36 in deep. 8 ft. None H H Copper bonded steel rod 5/8 in. diameter, driven vertically in earth. 8 ft., None V I galvanized steel rod 3/4 in. diameter, driven vertically in earth. 10 ft., None V J galvanized steel rod 3/4 in. diameter 10 ft. directly buried at a depth of 36 in. 10 ft Soil H K Copper grounding “pole” plate For Las Vegas sites 30 in. depth., T&B® Blackburntm Model PBH, .025 in. thickness 7 in. wide by 7 3/8 in. long, with connection capable of up to No.4 AWG Stranded wire For National sites, 36in. depth, T&B® Blackburntm GP-114, 14 in. diameter, .025 in. thickness. NA Soil na. B ELECTRODE LEGEND Installation Parameters * Orientation H- Horizontal V- Vertical 6 Length ft. Table 3 - Electrode Types L through V Electrode ID Material L M Lyncole® XITtm, copper Tube Steel, and Concrete N No. 4 AWG solid copper wire O No. 4 AWG solid copper wire P Wood pole with copper grounding pole plate to 6 AWG solid copper wire Copper Bonded Steel Rod Q ELECTRODE LEGEND Installation Parameters Length ft. Orientation Fill H o r V V Vertical chemically charged electrode assembly in an 11 ft. deep, 9 in. diameter boring. 10 Lynconite II Arrangement designed to represent a light pole base with six ea., 2 ft. long No. 4 reinforcing steel vertical, tied with 3 ea., No. 2 steel horizontal hoops separated 12 in., vertically in a 2 ft., deep 36 in. diameter excavation, encased in 2500 psi concrete, 20 ft. of wire rolled into a coil approximately 18 in. diameter, installed in a 2 ft. round by 2 ft. deep excavation in concrete 2500 psi. NA Concrete 20 Coil Concrete 20 Coil GEM tm 20 ft. of wire rolled into a coil approximately 18 in. in diameter, installed in a 2 ft., round by 2 ft., deep excavation encased in ERICO Ground Enhancement Material ™. Approximately 18 in. diameter, with Blackburn GP114 copper grounding pole plate attached at bottom using No. 6 AWG solid copper wire wrapped in a spiral for 6 ft., at approximately 6 in. spacing between wraps. n a. 8 Soil 1/2 in. diameter, rod installed horizontally, directly buried at 30 in. depth. 8 Soil H R LEC® Chemrod Vertically charged electrode assembly in an 11 ft. deep 9 in. diameter boring encased in Ground Augmentation Fill (GAF tm). 10 GAF tm With Earth V S Lyncole® XITtm Horizontal chemically charged electrode assembly installed at a depth of 36 in. 10 Lynconite II H T Galvanized steel water pipe 3/4 in. diameter galvanized (water) pipe, driven vertically in earth. 8 None V V 4/0 AWG- 7 strand copper wire 4/0 AWG- 7 strand bare copper cable, directly buried horizontally 36 in. deep. 20 Soil H * Orientation H- Horizontal V- Vertical 7 Table 4 - Electrode Types W through AE Electrode ID Material ELECTRODE LEGEND Installation Parameters Length ft. Orientation Fill Mortar H or V V 8 None V LEC® Chemrod tm charged electrode assembly installed at a depth of 36 in., encased in GAFtm backfill. Wire Mesh consisting of No. 6 copper plated steel on 4 in. centers measuring 2 ft. wide. 10 GAF tm With Earth H 8 Soil H Copper Tube ERICO® Horizontal Model Chemical Electrode. 10 GEM tm H AB Copper Tube Harger® Vertical Model Chemical Electrode. 11 Ultrafilltm V AC Copper Tube ERICO® Vertical Model Chemical Electrode. 10 GEM tm V AD Copper Tube Lyncole® Vertical Model Sectional Chemical. Electrode 10 Lynconite II V AE Copper Tube Lyncole® Horizontal Model Sectional Chemical Electrode. 10 Lynconite II H DC1 Rod DC1A,B, and C are 5/8 in. copper bonded steel rod. 8 None V DC2 Pipe DC2A, B, and C are ¾ in. by 8 ft. galvanized steel pipe. 8 None V DM Rod and Pipe DM1A, 2A,and 3A are 5/8 in. copper bonded steel rods. DM1B, 2B,and 3B are ¾ in.Galvanized Steel pipe. 8 None V W Assembly of copper bonded rods Dominion Virginia Power Co., ground cage, (proprietary)using multiple 8 ft. long, 5/8 in. diameter copper bonded rods installed in a mortar backfill. NA X Stainless steel rod 5/8 in. diameter stainless steel ground rod driven vertically in earth. Y LEC® Chemrod Z Copper plated steel mesh AA * Orientation H- Horizontal V- Vertical 8 8 V For the benign corrosion experiments, the following electrodes in Table 5, were installed without connections or conductors for resistance measurements. A limited corrosion analysis was done on these samples. Table 5 - Electrode Types 1A through 2C Electrode ID Material ELECTRODE LEGEND Installation Parameters 1A Copper Wire 4/0 AWG, 7 strand bare copper wire, installed at a depth of 36 in. 20 Orientation Fill H or V GEM tm H 2A Copper Wire 500 kcmil copper wire, installed at a depth of 36 in. 20 GEM tm H 1B Copper Wire 4/0 AWG, 7 strand bare copper wire, installed at a depth of 36 in. 20 Soil H 2B Copper Wire 500 kcmil copper wire, installed at a depth of 36 in. 20 Soil H 1C Copper Wire 4/0 AWG, 7 strand bare copper wire, installed at a depth of 36 in. 20 Lynconite II (Bentonite) H 2C Copper Wire 500 kcmil copper wire, installed at a depth of 36 in. 20 Lynconite II (Bentonite) H Orientation H- Horizontal V- Vertical 9 Length ft. 3.2 Electrode Details Figures 1 through 12 are included to provide a visual representation for informational purposes, and may not be a complete representation of installed conditions. CAD drawings of these illustrations are provided in Appendix 11.6 and 11.7. Figure 1 – Las Vegas Pullbox , Type M, N and R Electrodes Figure 2 - Types A, F and Q Electrodes 10 Figure 3 - Electrode Types E, H, L, S, K and P Figure 4 - Electrode Type B Concrete Encased Electrode The electrode in Figure 4 is representative of the electrode specified in NEC 250.52 (A)(3) [3]. 11 Figure 5 - Electrode Types H, T and X Figure 6 - Electrode Type V 12 Figure 7 - Electrode Type W Figure 8 - Electrode Type Y 13 Figure 9 - Electrode Type Z Figure 10 - Electrode Type AA 14 Figure 11 - Electrode Type AB Figure 12 - Electrode Type AC 15 Figure 13 - Direct Current Experiment DC2 (DC1 Similar) Figure 14 - Dissimilar Metals Experiment DM 16 Figure 15 – Electrodes, CDA- 1A, 1B, 2A, 2B, 3A and 3B 17 4 EXPERIMENTS AND METHOD The testing conducted on the static electrodes included electrode resistance, earth resistivity, soil moisture, and soil temperature. 4.1 Sample Preparation Prior to installation, the electrode samples were given a distinct sample number that was stamped directly into the sample. In some cases, the samples were also identified with a polymeric tag. All connectors used in the experiment were initially weighed using a calibrated scale. It was anticipated during the planning stage of the project that the weight of each connector would be compared before installation and after exhumation in an effort to determine the effects of corrosion by loss of material to the soil on each of the connectors used. Due to site limitations, weighing of the connectors was not carried out at the end of the experiment. The bolt-on, crimp type, and welded connectors were installed on the electrodes using the manufacturers recommended installation procedures. The recommended torque, crimp tool and die, and welding procedures were used. A site plan was developed by the TAC. The plan included trenching details, sample layouts, sample numbering, junction box location, and other detail and specifications. The plans are shown in Appendix 11.6, and 11.7. It should be noted that some differences occur between the plans and actual installation. Since every site had different conditions for installations (ie. size, terrain) the plan shown in the appendix varied from site to site based on installation decisions made by the site manager. No as-built site drawings were prepared. 4.2 Installation and Exhumation The electrodes were installed using earth moving equipment including backhoe, trenching machines, and hydraulic augers. Other chief equipment used included cement mixers, electrical generators, pneumatic hammers and selected hand tools. Installation was accomplished by firstly opening the trenching, digging holes for samples, positioning the samples, installing 6 AWG conductors in plastic conduits, laying conduits in trenches with termination at the electrode samples, and at junction box connections where resistance readings were taken. Driven rods and pipes were installed using pneumatic hammers. Conductors terminated at a connector on the electrode and at the junction box. The conductors were protected in the plastic conduit. Specific samples were then backfilled with their required backfill material including mortar, concrete, GEM tm, GAF tm, Ultrafill tm, Lynconite II, bentonite, or natural earth. Once this was done, all other samples and trenches were backfilled with native soil. None of the chemically charged electrodes in any of the sites were re-charged during the term of the project. All of the Las Vegas sites and the New York site were exhumed. Exhumation was done generally with a backhoe. Care was taken in every case to exhume a sample without destroying the electrode or the connection. Once a sample was exhumed, the bulk of the backfill material was removed by hand. Mortar and concrete were removed mechanically using hammers and jackhammers. Short lengths of 6 AWG conductors were left intact in 18 the connectors. Following this, the samples were cleaned with nylon brushes, clearly identified, and wrapped in plastic for storage. 4.3 Electrode Resistance The value of resistance to earth for each connection to each electrode was recorded during data collection, using the IEEE 81-1983 [4], Fall of Potential Method. Each electrode had an additional length of conductor from the junction box to the electrode under test. Various distances for test pin spacing were evaluated for the optimum distances for testing. Each electrode under test had a 6 AWG conductor permanently attached to it from the terminal box to allow for periodic measurements, the additional resistance was considered insignificant. This additional lead length was no more than 100 feet long. For the Fall of Potential resistance measurements, various distances for test pin spacing were evaluated for the optimum spacing, contributing to a small degree of variability in readings. For the five Las Vegas sites, a remote test pin distance of 100 ft. was used with the electrical current pin at 62 ft. from the termination box. The remote pin location of 100 ft. was determined to be sufficient to eliminate variability in readings due to location of the electrode. For the National sites, because of the larger footprint of the sites, the remote current electrode was located a distance of 200ft. with the potential electrode located 124 ft. from the terminal box. 4.4 DC Active Experiments The direct current experiments (DC1 and DC2) were developed as a method to evaluate the properties associated with damage to existing rod and pipe electrodes. In the National sites, there were two DC pods; DC1, and DC2. These experiments consisted of three driven rods in the DC1 pod, or pipes DC2 pod. Each pod was in a triangular formation with a rod or pipe located in the center of the pod that served as the negative terminal conductor. As shown in Figure 11, the surrounding electrodes were connected together using 6 AWG stranded copper conductors, and to the positive terminal conductor of a 12V@ 20 mA, DC power supply. The center rod or pipe was then connected to the negative terminal of the power supply across a standard (corrosion process 0.1 ohm) resistor. This method of connection has the effect of applying most of the (destructive force) current across the earth, and on the center rod or pipe. Permanent power was provided by means of a 120V power supply, and in two cases a solar photovoltaic array supplied the DC power. Time was recorded from hour meters located within test terminal enclosures. The design utilized three grounding rods or pipes spaced equally apart with a 5-milliamp DC current flowing through each of them. The fourth ground rod or pipe served as the negative (center rod in the pod) initially having 15 milliamps DC current flowing though it. The initial design was based on the concept that the negative would carry the summation of the currents flowing in each of the three outer electrodes. The current flowing in any of the outer electrodes should change based upon change of resistance mainly due to corrosion. Measuring DC currents for the DC and the dissimilar metals experiments was accomplished using either the direct connection to a portable meter capable of displaying 19 current in milliamperes, or by using a clamp-on style DC current probe in conjunction with a voltmeter. 4.5 Dissimilar Metals The Dissimilar Metals Experiment included six electrodes arranged in three sets of two. The purpose of this experiment was to develop data that could show changes of resistance, mainly caused by dissimilar metals in an earth coupled cell, which could possibly produce current flow. Figure 12 illustrates the experiment and shows the grounding electrode samples used. This experiment in the National sites was designed to identify electrical currents, and resulting corrosion of electrodes consistent with the currents measured across an earth coupled cell (galvanic corrosion). The cell consisted of a single 8 ft. long copper bonded steel ground rod, and a single ¾ in. diameter galvanized steel pipe spaced 6-1/2 ft. apart, in the earth and connected together using a standard (corrosion process .01 ohm) resistor. The resulting DC current between the two electrodes was measured. The test samples DM1A, DM2A and DM3A were 5/8” x 8’ copper bonded ground rod and the DM1B, DM2B and DM3B samples were ¾” x 8’ galvanized steel pipe. The descriptions of the electrodes are shown in Figure 12. There is 6 1/2 ft. between the copper bonded ground rod and the paired galvanized steel pipe ground rod. The experiment included the measurement of current flow through each paired grounding electrode circuit. A precision 0.01 ohm resistor was used in the circuit to standardize current measurement. 4.6 Earth Resistivity Earth resistivity was established for 10 ft. and 20 ft. test pin spacing using the IEEE 811983, Four Point Method for each data collection exercise. [2] The resulting ohm-meter resistance values were converted and recorded in ohm-cm. Per IEEE 81-1983 this method gives approximately the average resistivity of the soil to the depth represented by the probe spacing. 4.7 Soil Moisture Soil moisture was recorded using a specialized moisture meter with buried sensor blocks at depths of 126 in. 78 in., and 30 in. for each site. In this report, soil moisture is shown in Delmhorst ® units. These units are defined by the Delmhorst® KS-D1 instrument. 4.8 Soil Temperature Soil temperature was recorded using thermocouple thermometers connected to Type K thermocouple sensors buried at depths of 126 in., 78 in., and 30 in. at each site. 4.9 Passive Metal Corrosion Adjunct to this research project was a corrosion experiment with six grounding electrodes. These grounding electrodes were not connected to a power supply or any termination. 20 The experiment is shown in Figure 13. Samples 1A, 2A, and 3A consisted of 20 ft. of 4/0 stranded bare copper conductor and Sample 1B, 2B, and 3B consisted of 20 ft. of 500KCMIL stranded bare copper conductor. Samples 1A and 1B were backfilled with GEM tm, Samples 2A, 2B were backfilled in earth, and Samples 3A and 3B were backfilled in Bentonite. This was a long-term corrosion experiment of copper grounding electrodes in various backfills. There were no monthly resistance measurements conducted. Any corrosion observed after exhumation was assumed to be caused by the corrosive effects of the backfill and surrounding earth. 21 5 INSTRUMENTATION The following calibrated instruments were used for data collection. 5.1 Earth Testers Models used include: AVO / Megger- Det 2/2 AEMC- 4500 LEM - GEO Biddle Null Balance AEMC 3720 Clamp Earth Tester - Used in conjunction with the AEMC 4500 as a verification for the site manager. A standard four terminal instrument [2] was used to perform tests for resistance to earth, fall of potential testing, and earth resistivity testing. 5.2 Multi-Meters Fluke 87 or equal AC/DC volts, ohm, milliamps Multi-meters were used as a means to perform various routine tests such as continuity, current, and voltage measurements for portable equipment requiring the temporary connection of test leads, and general maintenance of wire, and terminations associated with experiments. 5.3 DC Current Probe AEMC K110 The DC current probe is a clamp-on style sensor. When connected to a volt-meter, and clamped around a wire carrying small DC currents, it is capable of producing measurable voltages which are then converted to a value of DC current. 5.4 Thermocouple Thermometer Omega HH-25KF or similar Used for measuring earth temperature requiring direct connection using a standard plug for Type K thermocouples. 5.5 Moisture Meter Delmhorst KSD1 22 Soil moisture measurements were made at each of the Las Vegas and National sites using the Delmhorst moisture measuring system. The system consisted of two chief parts: gypsum soil block sensors, and the measuring instrument - Model KS-D1 moisture meter. The gypsum served as a buffer against the effects that salts may have on the soils conductivity. The blocks were buried at soil depths of 30, 78, and 128 in. The blocks absorb or release moisture into the soil, until their moisture content reaches equilibrium with the moisture content of the surrounding soil. When the meter is connected to the block, current flows between two current probes and the electrical resistance of the block is measure. The meter is calibrated to relate moisture content with electrical resistance. 23 6 RESULTS Information in this section was derived from the specific data shown in the appendices. Some data include readings for each of the three connector types (bolt-on, crimp type, welded), but most data includes the results for only one connector type when the data were similar. The data is organized as follows. • • • • Electrode Resistance o Percentage of Readings Exceeding Resistance of Certain Values o Resistance of Individual Electrodes at All Sites o Vertical and Horizontal Electrode Resistance o Comparison of Electrode Resistance Ancillary Experiments o DC1 and DC2 Results o Dissimilar Metals Results o Benign Corrosion Experiments Soil Characteristics o Earth Resistivity o Soil Temperature o Soil Moisture Corrosion Results 24 6.1 Electrode Resistance 6.1.1 Percentage of Readings Exceeding Resistance of Certain Values Tables 6 through 9 are based on average resistance values over the term of the project. The Tables indicate percentage of readings which exceeded the specified values of 25, 50, 100, and 250 ohms respectively. Table 6 - Percentage of Readings Exceeding 25 ohms Of the 18 electrodes in the Balboa test site, 14 of these exceeded 25 ohms for 90% or more of the readings; electrode Types E, L and R were the exception. Similarly, for electrodes in the New York test site, 100% of the readings exceeded 25 ohms for 13 of the 15 electrodes in the site; the exceptions being electrodes Type L and R. It is noted that the percentage of readings for electrode Type B, (NEC Section 250.52) [2] exceeded 25 ohms for 74% or more of the readings in four of the 10 test sites. Electrode Type K readings exceeded 25 ohms for 75% or more of the readings at nine of the 10 test sites with Texas readings exceeding 25 ohms for 21% of the readings. 25 The Illinois site had the least number of electrodes with readings exceeding 25 ohms. Electrodes H and K having 11% and 79% respectively that exceeded 25 ohms. This could be due to generally wet soil conditions based upon site location in a drainage field. Table 7 - Percentage of Electrodes Exceeding 50 ohms In the New York, site 10 of 15 electrodes exceeded 50 ohms more than 50% of the time. In the Balboa site, nine of 16 electrodes exceeded 50 ohms 50% of the time, as compared to the Illinois site where no electrodes exceed 50 ohms except for the K electrode (18%). Although the Las Vegas Pecos and Balboa sites, were in the same geographical area the results differed greatly. In the Balboa site, nine of 18 electrodes exceeded 50 ohms more than 50% of the time, whereas, in the Pecos site only the K electrode exceeded 50 ohms 50% of the time. Any electrode which exceeded 50 ohms exceeded the NEC 25 ohm requirement by a factor of two. 26 Table 8 - Percentage of Electrodes Exceeding 100 ohms As expected, there were fewer electrodes exceeding the 100 ohm value than those shown in the previous tables. The results showed that only one electrode in each of the Illinois and Texas sites exceeded 100 ohms. In Illinois, 3% of the readings for the K electrode exceeded 100 ohms and in Texas, 7% of the readings for the X electrode exceeded 100 ohms. In the Las Vegas sites, only the B, I, L, and S electrodes had readings less than 100 ohms. The K electrode for all sites had the worst results. Over the term of the project in the New York site, three of the 15 electrode readings measured 100 ohms or greater for at least 95% of the readings. In the Balboa site, two of the electrodes exceeded 100 ohms for at least 95% of the readings. Any electrode exceeding 100 ohms, also exceeded the NEC 25 ohm requirement by a factor of four. 27 Table 9 - Percentage of Electrodes Exceeding 250 ohms As with the results for readings exceeding 25, 50, and 100 ohms, the K electrode also exhibited the worst performance when evaluated against 250 ohms. If the data for the K electrode in the above Table was eliminated, then none of the electrodes in the Las Vegas Pecos, or Charleston sites would have any values exceeding 250 ohms. Any electrode which exceeded 250 ohms exceeded the NEC 25 ohms requirement by a factor of ten. 28 6.1.2 Resistance of Individual Electrodes at All Sites 6.1.2.3 Illinois Site Resistance Experiments In the Illinois site, there were 15 different electrodes evaluated for resistance, with three samples of each buried in the site. Of the 15 types, there were five electrodes that had a trend of decreasing resistance over time. Ten of the 15 electrodes had an increasing trend. For the Illinois as well as other sites, the slope of the trendlines was not calculated, nonetheless, inferences can be made by the reader regarding this trend continuing over time beyond the conclusion of this experiment. It is assumed that those electrodes that had decreasing trendlines would not actually reach a zero resistance value. For those electrodes with increasing trendlines, it is not known whether or not any specific trend would continue at the same slope for the service life beyond the period of this experiment, however, this trendline could be used for predicting performance, and also for comparing one electrode to another. Northbrook, IL All Electrodes 100 B1 E1 F1 G1 H1 K1 L1 R1 S1 T1 V1 W1 X1 Y1 Z1 Ohms 75 50 25 10/25/06 6/14/06 2/15/06 6/22/05 10/19/05 2/22/05 10/29/04 6/23/04 2/18/04 10/8/03 6/13/03 2/19/03 10/17/02 6/17/02 2/18/02 6/26/01 10/22/01 2/19/01 6/19/00 10/11/00 2/15/00 10/15/99 6/18/99 2/18/99 10/8/98 0 Figure 16- Illinois Electrodes Resistance The data for all electrodes in the Illinois site is shown in the above Figure 16. All electrodes except for the K1 and H1 had resistance readings for the tenure of the experiment less than 25 ohms. 29 6.1.2.3 Texas Site Resistance Experiments In the Texas site, there were 15 different electrodes evaluated for resistance, with three samples of each buried in the site. Of the 15 types, there were three electrodes that had a trend of decreasing resistance over time. Twelve of the 15 electrodes had an increasing trend. Dallas, TX All Electrodes 100 B1 E1 F1 G1 H1 K1 L1 R1 S1 T1 V1 W1 X3 Y1 Z1 Ohms 75 50 25 11/22/06 5//06 8/29/06 2//06 8/29/05 11/28/05 5/31/05 2/28/05 8//2004 11//2004 5//2004 2//2004 8/19/03 11/25/03 5/22/03 2/18/03 8/26/02 11/25/02 5/28/02 2/25/02 8/28/01 11/26/01 5/31/01 2/26/01 8/28/00 11/20/00 5/31/00 2/24/00 8//1999 11/22/99 5/21/99 1/29/99 7/30/98 10/30/98 0 Figure 17– Texas Electrodes Resistance The data for all electrodes in the Texas site is shown in Figure 15. All electrodes except for the type B, F, G, K, and V electrodes had resistance readings for the period of the experiment less than 25 ohms. It is noted that the type V electrode, exceeded 25 ohms only over a narrow period of approximately three months over the tenure of the experiment. 30 6.1.2.3 California Site Resistance Experiments In the California site, there were 18 different electrodes evaluated for resistance, with three samples of each buried in the site. Of the 18 types, all electrode types showed increasing resistance over time. Of all the National sites, the California site had the shortest period of time from which resistance readings were taken. In addition, the California site included additional electrodes not present in the other National sites. These electrodes were types AA, AB, AC, AD and AE and there were three of each present in the site. Moffett Field, CA All Electrodes 175.0 B1 E1 F1 G1 H1 K1 L1 S1 T1 V1 W1 X1 Z1 AA1 AB1 AC1 AD1 AE1 150.0 125.0 Ohms 100.0 75.0 50.0 25.0 12/26/06 9//06 11/16/06 5//06 7/7/06 3//06 1//06 9/1/2005 11/4/2005 5//2005 7/6/2005 3//2005 1//2005 9//2004 11//2004 7//2004 5//2004 3//2004 1//2004 9//2003 11//2003 7//2003 5//2003 3//2003 1//2003 9/1/2002 11/1/2002 7/1/2002 3//2002 5/1/2002 1/30/2002 0.0 Figure 18 - California Electrodes Resistance The data for all electrodes in the California site is shown in Figure 18. All electrodes except for the type B, F, G, K, T, V, Z and AB electrodes had resistance readings for the tenure of the experiment less than 25 ohms. Even though some electrodes for the tenure of the test had readings less than 25 ohms, all electrodes showed an increasing trend of resistance. 31 6.1.2.4 Virginia Site Resistance Experiments In the Virginia, site there were 15 different electrodes evaluated for resistance, with three samples of each buried in the site. Of the 15 types, there were four electrodes that had a trend of decreasing resistance over time. Eleven of the 15 electrodes had an increasing trend. Staunton, VA All Electrodes 450 400 B1 E1 F1 G1 H1 K1 L1 R1 S1 T1 V1 W1 X1 Y1 Z1 350 Ohms 300 250 200 150 100 50 7//06 11/28/06 3/3/06 7/28/05 11/18/05 3/24/05 10/28/04 7/29/04 11//04 3/19/04 3//03 7/3/03 7/12/02 11/26/02 3/29/02 11/7/01 7/23/01 3/29/01 11/14/00 3/9/00 7/11/00 11/30/99 7/29/99 11//99 3/25/99 7/10/98 3/26/98 11/24/97 0 Figure 19 - Virginia Electrodes Resistance The data for all electrodes in the Virginia site is shown in Figure 19. The type E and R electrodes had resistance readings for the tenure of the experiment less than 25 ohms. 32 6.1.2.5 New York Site Resistance Experiments In the New York site, there were 15 different electrodes evaluated for resistance, with three samples of each buried in the site. Of the 15 types, there was only one electrode, the B electrode, that had a trend of decreasing resistance over time. Cenhud Hibernia NY All Electrodes 900 800 B1 E1 F1 G1 H1 K1 L1 R1 S1 T1 V1 W1 X1 Y1 Z1 700 Ohms 600 500 400 300 200 100 5/1406 3//2006 12//2005 9/1/2005 3//2005 6/9/2005 9//2004 12//2004 6//2004 3//2004 9//2003 12//2003 6//2003 3//2003 9//2002 12//2002 6//2002 3//2002 9//2001 12//2001 3//2001 6/20/2001 9/20/2000 12/13/2000 6/15/2000 9//99 03/22/00 9/27/1999 6/18/1999 3/19/1999 9/24/1998 12/29/1998 0 Figure 20 - New York Electrodes Resistance In most cases, the electrodes resistance greatly exceeded 25 ohms. As was expected the K electrodes had high resistance readings. The best results were with the L and R electrodes, however, some of their readings exceeded 25 ohms with an increasing trend line. 33 6.1.3 Vertical and Horizontal Electrodes - Las Vegas Sites The following Figures 19 through 28 and their associated data in Tables 10 through 19, show the relationship between resistance and time of the vertical and horizontal rod electrodes. The vertical electrodes (H) shown in red exhibited lower resistance values than did the horizontal electrodes (G) shown in blue for every Las Vegas site. The horizontal electrodes were installed at 36 in. depth to evaluate installations where rock bottom is encountered, as referenced in NEC Section 250 53(G). Vertical electrodes were driven to a depth of approximately 8 ft. Las Vegas, NV Balboa G vs. H 600 500 G H Linear (G) Linear (H) 300 200 100 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 0 9/19/1991 Ohms 400 Figure 21 - Balboa Test Site Graph Electrode Type G and H 34 Table 10 - Balboa Test Site Data for Electrode Type G and H The vertical electrode Type H, exhibited consistently lower resistance levels than Type G, horizontal. Additionally the data showed that the average resistance over time of the vertical electrodes was much less than the horizontal electrodes. It is noted, however, that none of the vertical electrodes met the NEC requirement of 25 ohms. 35 Las Vegas, NV Charleston G vs. H 500 450 400 350 Ohms 300 G H Linear (G) Linear (H) 250 200 150 100 50 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 22 - Charleston Test Site Graph for Electrode Type G and H Table 11 - Charleston Test Site Data for Electrode Type G and H The vertical electrode Type H exhibited consistently lower resistance levels than Type G, horizontal. Additionally the data showed that the average resistance over time of the vertical electrodes was much less than the horizontal electrodes. Three of the average resistance readings for the Type H electrode exceeded the NEC requirement of a maximum 25 ohms. 36 Las Vegas, NV Lone Mountain G vs. H 280 240 200 160 Ohms G H Linear (G) Linear (H) 120 80 40 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 23 - Lone Mountain Test Site Graph for Electrode Type G and H Table 12 - Lone Mountain Test Site Data for Electrode Type G and H Lone Mountain had similar results to the Balboa and Charleston sites. In all cases, the vertical rods met the NEC requirement of 25 ohms. In all cases except one, the horizontal rods did not meet the requirement. 37 Las Vegas, NV Pecos G vs. H 140 120 100 80 Ohms G H Linear (G) Linear (H) 60 40 20 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 24 - Pecos Test Site Graph for Electrode Type G and H Table 13 - Pecos Test Site Data for Electrode Type G and H Some Type G electrode readings were not included due to damage during excavation. Once again, the data showed that the vertical rods had lower average resistance than the horizontal rods. All of the vertical rods meet the NEC 25 ohm requirement, but this cannot be said for the horizontal rods. Seventy percent of the average resistance readings for horizontal electrodes did not meet the NEC 25 ohm requirement. 38 Las Vegas, NV Pawnee G vs. H 25 20 15 Ohms G H Linear (G) Linear (H) 10 5 1/14/2004 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 25 - Pawnee Test Site Graph for Electrode Type G and H Table 14 - Pawnee Test Site Data for Electrode Type G and H The results showed that for both types of rods, the NEC requirement of 25 ohms was met. These results could be attributed to lower earth resistivity than is present at Balboa, Charleston, Lone Mountain and Pecos sites. 39 Las Vegas, NV Balboa I vs. J 400 350 300 Ohms 250 I J Linear (J) Linear (I) 200 150 100 50 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 26 - Balboa Test Site Graph for Electrode Type I and J Table 15 - Balboa Test Site Data for Electrode Type I and J The vertical electrode Type I exhibited consistently lower resistance levels than Type J, horizontal. Additionally, the data showed that the average resistance over time of the vertical electrodes was much less than the horizontal electrodes. Regarding the average resistance readings, in all cases except for one, all electrodes either vertical or horizontal did not meet the NEC 25 ohm requirement. 40 Las Vegas, NV Charleston I vs. J 140 120 100 80 Ohms I J Linear (J) Linear (I) 60 40 20 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 27 - Charleston Test Site Graph for Electrode Type I and J Table 16 - Charleston Test Site Data for Electrode Type I and J Some of vertical electrodes showed low average resistance readings, whereas others exceeded the NEC requirement. In all cases the average resistance readings for the horizontal electrodes exceeded those of the vertical electrodes. This data clearly showed once again, that resistance readings are dependent upon positioning in soil. This could be due to a number of factors including soil moisture, soil compaction and possibly temperature. 41 Las Vegas, NV Lone Mountain I vs J 25 20 15 Ohms I1 J1 Linear (J1) Linear (I1) 10 5 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 28 - Lone Mountain Test Site Graph for Electrode Type I and J Table 17 - Lone Mountain Test Site Data for Electrode Type I and J The results showed that for both types of rods, the NEC 25 ohm requirement was met. For the average resistance readings, in all cases the vertical electrodes had average resistances less than or equal to resistances of horizontal electrodes. 42 Las Vegas, NV Pecos I vs J 25 20 15 Ohms I1 J1 Linear (J1) Linear (I1) 10 5 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 9/19/1991 0 Figure 29 - Pecos Test Site Graph for Electrode Type I and J The results showed that for both types of rods, the NEC 25 ohm requirement was met. For the average resistance readings, in 18 of 20 cases the vertical electrodes had average resistances less than or equal to resistances of horizontal electrodes. 43 Table 18 - Pecos Test Site Data for Electrode Type I and J 44 Las Vegas, NV Pawnee I vs J 14 12 8 I J Linear (J) Linear (I) 6 4 2 1/14/2004 9/1/2002 4/19/2001 12/6/1999 7/24/1998 3/11/1997 10/28/1995 6/15/1994 1/31/1993 0 9/19/1991 Resistance (Ohms) 10 Figure 30 - Pawnee Test Site Graph for Electrode Type I and J 45 Table 19 - Pawnee Test Site Data for Electrode Type I and J As compared to other Las Vegas sites, the Pawnee site exhibited resistance readings well below the NEC requirement in all cases. Unlike other sites, Pawnee soil consistency was mostly clayey sand, which could explain the low level of earth resistivity. 46 6.1.4 Vertical and Horizontal Electrodes – National Sites The following Figures 31 through 35 and their associated data in Tables 20 through 24 show the relationship between resistance and time for the vertical and horizontal rod electrodes in the National sites. The variant results for the Illinois site could be attributed to the relatively high water table and standing water occurring many weeks during the year. This is the only National site where average resistance values were less for the horizontal electrodes than for vertical electrodes. Unlike the vertical electrodes, there were no specific readings exceeding 25 ohms for their horizontal counterpart. For the horizontal electrode, the average resistance values met the 25 ohm requirement. The vertical electrode (H) shown in red exhibited lower resistance values than did the horizontal electrode (G) shown in blue. For the National sites, the horizontal electrodes were installed at a 36 in. depth to evaluate installations where rock bottom is encountered, as referenced in NEC Section 250 53(G). Vertical electrodes were driven to a depth of approximately 8 ft. Northbrook, IL G- Horizontal vs H- Vertical 40 35 30 G1 H1 Linear (G1) Linear (H1) 20 15 10 5 8/23/06 12/12/06 4/18/06 12/22/05 8/16/05 4/18/05 12/29/04 8/16/04 4/28/04 8/18/03 12/18/03 4/23/03 8/16/02 12/12/02 4/15/02 12/18/01 6/26/01 2/19/01 6/19/00 10/11/00 2/15/00 6/18/99 10/15/99 2/18/99 0 10/8/98 Ohms 25 Figure 31 – Illinois Test Site Graph for Electrode Type G and H 47 Table 20 – Illinois Test Site Data for Electrode Type G and H National Electrical Grounding Research Project Location: Northbrook, IL Test Site: UL Read Date 10/8/98 11/6/98 1/18/99 2/18/99 3/17/99 4/13/99 5/21/99 6/18/99 7/16/99 8/11/99 9/30/99 10/15/99 11/10/99 12/20/99 1/18/00 2/15/00 3/8/00 4/14/00 5/15/00 6/19/00 7/17/00 8/16/00 9/13/00 10/11/00 11/22/00 12/20/00 1/10/01 2/19/01 3/20/01 4/18/01 5/16/01 6/26/01 9/27/01 10/22/01 11/7/01 12/18/01 1/22/02 2/18/02 3/12/02 4/15/02 5/15/02 6/17/02 7/15/02 8/16/02 9/17/02 10/17/02 11/13/02 12/12/02 1/28/03 2/19/03 3/14/03 4/23/03 5/19/03 6/13/03 7/18/03 8/18/03 9/16/03 10/8/03 11/20/03 12/18/03 1/14/04 2/18/04 Resistance (Ohms) Horizontal Rods Vertical Rods G1 G2 G3 H1 H2 7 7 6 8 9 7 7 6 7 7 9 9 9 9 10 9 8 8 9 9 9 9 8 9 9 7 7 7 8 9 7 6 7 7 8 6 5 6 7 9 7 7 7 9 17 12 9 9 9 11 6 6 6 8 9 6 6 6 8 9 10 9 8 9 10 7 8 8 8 9 8 8 9 9 10 8 8 9 10 10 7 7 8 9 9 7 7 8 9 9 6 6 7 9 9 6 6 6 8 8 5 6 6 8 11 6 6 6 13 17 5 6 6 13 10 6 7 7 9 8 7 8 8 9 8 7 9 8 9 9 7 8 8 9 9 8 7 8 10 10 7 7 8 10 10 6 6 7 9 9 6 6 6 9 9 5 6 6 9 16 5 7 6 10 9 5 7 7 9 9 6 7 7 9 10 6 7 8 10 11 7 8 9 17 22 6 7 8 11 12 6 6 8 10 12 5 6 7 10 11 5 6 7 9 11 5 5 6 9 13 5 6 7 22 26 5 6 7 21 27 5 5 7 20 21 5 6 7 14 21 6 7 8 23 23 5 6 8 10 14 6 8 11 14 18 6 7 9 14 22 5 6 9 13 22 4 5 6 11 14 4 5 6 9 12 4 5 6 9 20 3 4 5 13 18 4 5 6 23 26 4 5 6 28 31 5 6 7 32 28 4 6 7 12 13 6 7 8 11 12 5 6 8 11 12 5 6 8 12 15 48 Soil Resistivity (Ohm-cm at 10 ft.) H3 9 7 10 9 10 9 9 12 18 26 10 9 10 9 9 9 9 9 8 7 7 7 7 7 8 8 8 9 9 8 8 8 7 7 8 8 9 9 9 9 8 8 8 9 8 7 8 9 10 11 23 9 8 8 7 8 9 9 8 9 9 6 Read Date 2938 2505 2647 3152 3164 3168 2953 2719 2490 2562 2566 2589 2601 2804 3068 3210 3275 3083 2984 2712 2455 2321 2375 2313 2432 2681 2934 3007 3202 3171 2984 2662 2509 2358 2482 2597 2815 3175 3187 3175 3018 2777 2570 2601 2811 2348 2478 2696 2991 3298 3451 3497 3087 2842 2693 2436 2543 2670 2746 2762 3141 3305 3294 10/8/98 11/6/98 1/18/99 2/18/99 3/17/99 4/13/99 5/21/99 6/18/99 7/16/99 8/11/99 9/30/99 10/15/99 11/10/99 12/20/99 1/18/00 2/15/00 3/8/00 4/14/00 5/15/00 6/19/00 7/17/00 8/16/00 9/13/00 10/11/00 11/22/00 12/20/00 1/10/01 2/19/01 3/20/01 4/18/01 5/16/01 6/26/01 9/27/01 10/22/01 11/7/01 12/18/01 1/22/02 2/18/02 3/12/02 4/15/02 5/15/02 6/17/02 7/15/02 8/16/02 9/17/02 10/17/02 11/13/02 12/12/02 1/28/03 2/19/03 3/14/03 4/23/03 5/19/03 6/13/03 7/18/03 8/18/03 9/16/03 10/8/03 11/20/03 12/18/03 1/14/04 2/18/04 Average Resistance (Ohms) G H 6 9 7 7 9 9 8 9 9 9 7 9 7 8 6 9 7 15 10 15 6 9 6 9 9 10 8 9 8 9 8 10 7 9 7 9 6 9 6 8 6 9 6 12 6 10 7 8 8 8 8 9 8 9 8 10 7 10 6 9 6 9 6 11 6 9 6 8 7 9 7 10 8 16 7 11 7 10 6 10 6 9 5 10 6 19 6 19 6 16 6 14 7 18 6 11 8 14 7 16 7 19 5 11 5 10 5 12 4 13 5 19 5 23 6 23 6 11 7 11 6 11 6 11 Dallas, TX G- Horizontal vs H- Vertical 75 50 Ohms G1 H1 Linear (G1) Linear (H1) 25 7/30/2006 7/30/2005 7/30/2004 7/30/2003 7/30/2002 7/30/2001 7/30/2000 7/30/1999 7/30/1998 0 Figure 32 – Texas Test Site Graph for Electrode Type G and H At the Texas site, in every case, the average resistance values of the horizontal and vertical electrodes met the 25 ohm requirement of NEC Section 250.52(G). For the horizontal electrodes there were many specific readings that exceeded 25 ohms. No readings exceeded 25 ohms for the duration of the test for the vertical electrodes. 49 Table 21 – Texas Test Site Data for Electrode Type G and H National Electrical Grounding Research Project Location: Test Site: Dallas,Texas Megger Read Date 7/30/1998 8/17/1998 9/30/1998 10/30/1998 11/30/1998 12/16/1998 1/29/1999 3/23/1999 4/26/1999 5/21/1999 6/29/1999 7/30/1999 9/20/1999 10/25/1999 11/22/1999 12/22/1999 1/24/2000 2/24/2000 03/28/00 4/18/2000 5/31/2000 6/26/2000 7/30/1999 8/28/2000 9/29/2000 10/26/2000 11/20/2000 12/28/2000 1/26/2001 2/26/2001 3/13/2001 5/31/2001 6/20/2001 7/31/2001 8/28/2001 9/20/2001 10/16/2001 11/26/2001 12/28/2001 1/28/2002 2/25/2002 3/28/2002 4/25/2002 5/28/2002 6/24/2002 7/30/2002 8/26/2002 9/23/2002 11/25/2002 12/18/2002 1/29/2003 2/18/2003 3/24/2003 4/28/2003 5/22/2003 6/30/2003 8/19/2003 9/22/2003 10/28/2003 11/25/2003 12/15/2003 2/28/2005 3/22/2005 4/25/2005 5/31/2005 6/28/2005 G1 46 64 50 6 6 6 62 8 9 12 17 20 29 36 39 15 5 14 12 10 17 12 20 29 34 36 15 14 12 10 8 16 19 26 26 16 22 29 17 19 16 15 13 16 21 24 25 27 5 15 15 15 13 15 17 14 23 22 29 31 35 12 13 15 18 21 Resistance (Ohms) Horizontal Rods G2 G3 H1 77 94 8 66 102 8 53 97 7 7 6 5 7 6 5 7 7 5 69 79 8 9 9 5 14 11 6 19 13 5 18 18 6 25 24 8 50 38 10 65 46 11 76 48 11 16 15 7 17 16 7 18 18 6 11 15 6 11 14 5 14 14 5 11 12 5 25 24 8 34 31 12 41 36 13 49 35 9 14 15 7 14 17 7 13 15 7 12 14 7 9 12 7 16 17 6 19 18 6 26 21 9 25 19 8 9 9 5 15 13 6 21 15 7 17 15 7 19 18 7 17 17 7 16 16 7 15 15 6 18 16 7 21 18 9 22 21 9 25 22 10 28 24 10 16 16 8 16 16 7 17 17 6 16 17 6 15 16 6 18 21 7 19 23 7 14 13 5 23 22 8 22 19 7 30 24 8 33 25 7 39 28 7 14 12 5 15 12 5 16 13 6 20 15 7 22 17 10 Vertical Rods H2 8 8 6 5 5 5 8 5 6 5 6 9 11 12 12 6 6 6 5 5 5 5 9 16 16 12 6 6 6 6 5 6 7 9 8 5 6 6 6 7 6 6 6 7 8 9 9 9 6 6 7 7 7 8 7 6 9 8 9 9 9 7 8 9 9 14 50 Soil Resistivity (Ohm-cm at 10 ft.) H3 10 9 7 5 5 5 10 5 6 5 6 9 11 12 12 6 6 6 6 5 5 5 9 11 12 10 6 6 6 6 5 6 7 10 9 5 5 6 6 6 6 6 6 6 8 9 9 10 6 6 6 6 6 7 7 5 10 8 9 8 8 5 6 7 7 11 3983 4021 3926 3753 3677 2739 2857 2819 3014 3661 3646 4079 4079 4577 3221 3252 3037 2746 2585 3106 2309 3646 3868 4175 3849 2758 3081 3026 2945 2781 3244 3631 3673 3661 2237 1735 3386 2869 3024 3079 2907 3083 3321 3849 3926 3887 3926 2804 2754 2972 2915 2934 3799 3577 2819 2662 2815 3707 3359 3416 1563 3018 3700 3148 3887 Read Date 7/30/98 8/17/98 9/30/98 10/30/98 11/30/98 12/16/98 1/29/99 3/23/99 4/26/99 5/21/99 6/29/99 7/30/99 9/20/99 10/25/99 11/22/99 12/22/99 1/24/00 02/24/00 03/28/00 04/18/00 05/31/00 06/26/00 07/30/99 08/28/00 09/29/00 10/26/00 11/20/00 12/28/00 1/26/01 2/26/01 3/13/01 5/31/01 6/20/01 7/31/01 8/28/01 9/20/01 10/16/01 11/26/01 12/28/01 1/28/02 2/25/02 3/28/02 4/25/02 5/28/02 6/24/02 7/30/02 8/26/02 9/23/02 11/25/02 12/18/02 1/29/03 2/18/03 3/24/03 4/28/03 5/22/03 6/30/03 8/19/03 9/22/03 10/28/03 11/25/03 12/15/03 2/28/05 3/22/05 4/25/05 5/31/05 6/28/05 Average Resistance (Ohms) G H 72 8 77 8 67 7 6 5 6 5 7 5 70 8 8 5 11 6 15 5 18 6 23 9 39 11 49 12 54 12 16 7 13 6 16 6 13 6 12 5 15 5 12 5 23 9 31 13 37 14 40 10 15 6 15 6 13 6 12 6 10 6 16 6 19 7 24 9 23 8 11 5 17 5 22 6 16 6 19 7 17 6 16 6 14 6 17 7 20 8 22 9 24 9 27 10 12 7 15 6 16 6 16 6 15 6 18 7 20 7 14 5 22 9 21 8 28 9 30 8 34 8 13 6 14 6 15 7 18 8 20 12 Figure 33 – California Test Site Graph for Electrode Type G and H Figure 31 California test site graph for electrode type G and H was purposely omitted to due lack of data. Table 22 – California Test Site Data for Electrode Type G and H National Electrical Grounding Research Project Location: Test Site: Moffett Field, CA. NASA Read Date 6/13/2003 2/5/2005 7/6/2005 8/4/2005 9/1/2005 11/4/2005 6/2/2006 7/7/2006 10/2/2006 11/16/2006 12/4/2006 12/26/2006 G1 27 33.4 30 33.7 39.5 57.9 31 30.5 48.3 64.7 73.3 80.9 Resistance (Ohms) Horizontal Rods Vertical Rods G2 G3 H1 H2 3.8 3.5 14.1 14.2 4.09 4.02 12.61 14.33 4.39 4.48 20.2 23 4.39 4.67 20.8 23 4.4 4.6 22.1 23.3 4.69 5 23.7 24.3 4.29 4.48 19.8 23.1 4.31 4.41 20.4 23.4 4.46 4.89 22 20 4.72 5.28 22 20.5 4.81 5.89 20.6 20.1 4.96 5.91 19.53 19.77 51 H3 22.7 25.4 31.8 32.3 32.6 31.9 31.9 31.6 30.9 32 31.6 33.1 Soil Resistivity (Ohm-cm at 10 ft.) Read Date 517 781 3677 3868 4577 3160 3621 3753 3037 3374 1792 1666 6/5/1993 12/29/1993 6/23/1994 12/27/1994 6/10/1995 12/21/1995 6/29/1996 12/29/1996 6/28/1997 12/13/1997 12/4/2006 6/28/1998 Average Resistance (Ohms) G H 11 17 14 17 13 25 14 25 16 26 23 27 13 25 13 25 19 24 25 25 28 10 31 24 Staunton, VA G- Horizontal vs H- Vertical 200 175 150 Ohms 125 G1 H1 Linear (G1) Linear (H1) 100 75 50 25 8/6/06 1/18/06 9/28/05 5/20/05 12/4/04 7/29/04 3/19/04 9/11/03 5/8/03 12/16/02 9/23/02 4/22/02 8/15/01 12/20/01 3/29/01 11/14/00 3/9/00 7/11/00 7/29/99 11/30/99 3/25/99 10/23/98 5/15/98 11/24/97 0 Figure 34 – Virginia Test Site Graph for Electrode Type G and H At the Virginia site, only one electrode of types G and H met the NEC requirement, and that electrode was H3. The average resistance for the horizontal electrodes was more than 100 percent greater than the average resistance for all vertical electrodes. The average resistance values over time for the vertical rods, was relatively consistent for the duration of the test. The trendline shows decreasing values for both types of electrodes during the term of the experiment. 52 Table 23 – Virginia Test Site Data for Electrode Type G and H National Electrical Grounding Research Project Location: Staunton, VA Test Site: Dominion Virginia Power Co. Read Date 11/24/97 12/19/97 1/26/98 3/26/98 5/15/98 7/10/98 8/14/98 9/11/98 10/23/98 12/4/99 1/12/99 2/10/99 3/25/99 4/22/99 5/27/99 6/30/99 7/29/99 8/26/99 10/7/99 10/26/99 11/30/99 12/1/99 2/8/00 3/9/00 4/5/00 5/31/00 6/8/00 7/11/00 8/15/00 9/12/00 10/4/00 11/14/00 12/27/00 1/9/01 2/7/01 3/29/01 4/24/01 6/12/01 7/23/01 8/15/01 9/19/01 10/3/01 11/7/01 12/20/01 1/25/02 2/18/02 3/29/02 4/22/02 5/16/02 6/13/02 7/12/02 9/23/02 9/23/02 10/23/02 11/26/02 12/16/02 1/16/03 2/25/03 4/3/03 5/8/03 6/4/03 7/3/03 8/31/03 9/11/03 10/30/03 12/4/03 G1 30.2 34.9 14.2 41.1 35.2 65.3 120.8 138.0 161.3 186.2 61.1 50.7 41.9 53.6 111 168 170 140 38 47 70 55 65 57 52 44 94 79 91 42 42 88 73 77 66 60 55 73 122 71 146 162 190 186 194 192 77 47 51 97 155 177 195 123 52 50 66 56 55 56 34 50 74 65 62 59 Resistance (Ohms) Horizontal Rods G2 G3 H1 35.5 31.6 24.7 45.2 35.5 27.1 14.8 14.1 28.8 54.0 42.2 29.9 47.1 39.5 28.5 71.3 52.9 31.1 104.0 69.7 34.2 110.0 71.8 29.9 120.4 80.0 28.5 156.2 98.6 34.7 98.4 68.9 29.7 86.4 60.2 30.8 73.7 53.1 28.9 81.5 59.2 29.7 108 67 31 134 85 34 129 80 31 104 79 35 59 40 23 71 49 23 88 61 24 78 57 26 88 66 28 77 57 28 71 52 26 63 44 25 94 64 28 86 58 29 90 59 25 64 43 29 64 43 27 103 67 26 93 67 28 98 72 29 92 66 28 85 60 28 76 53 28 84 54 25 107 72 28 99 67 26 135 82 27 146 88 27 166 98 28 175 104 28 188 111 30 176 106 29 101 63 26 61 39 24 75 49 23 96 63 26 135 80 27 145 85 28 154 88 26 111 72 23 69 50 23 72 50 24 97 65 26 77 58 28 81 54 27 77 51 26 46 32 25 62 42 26 83 55 27 80 56 27 87 65 26 87 62 26 Vertical Rods H2 25.5 27.9 29.1 31.1 30.4 33.6 38.9 37.5 39.7 49.0 40.9 38.3 35.3 35.7 36 44 45 49 28 28 29 31 34 34 32 30 33 37 34 35 32 31 34 36 36 35 34 31 39 38 43 45 49 51 55 55 45 36 34 34 40 46 46 44 33 34 36 38 35 34 31 31 30 29 31 32 53 H3 21.6 23.5 24.6 26.7 26.4 28.6 31.7 27.9 26.6 32.2 25.1 27.0 25.2 26.2 27 31 30 34 20 20 21 22 24 24 23 22 24 26 22 27 25 23 23 24 24 24 24 21 25 22 25 25 26 27 28 28 24 21 21 22 25 27 26 24 20 22 24 25 24 24 23 23 22 22 22 22 Soil Resistivity (Ohm-cm at 10 ft.) Read Date 9,958 10,437 10,073 9,728 19,533 10,207 11701 11,701 10,647 10,647 10,647 10,667 11,145 11,318 11,222 8,464 8,675 9,020 9,518 10302.7 10168.65 9766.5 9421.8 9747.35 9651.6 10647.4 9192 9038.8 9287.75 9900.55 10302.7 10436.75 10206.95 9881.4 9249.45 9575 9268.6 9517.55 9785.65 9938.85 10743.15 11758.1 11490 10360.15 9172.85 8923.9 8847.3 10149.5 9670.75 9651.6 9709.05 8617.5 9172.85 9747.35 10436.75 9919.7 9881.4 9230.3 9096.25 8847.3 8560.05 8962.2 9383.5 10838.9 11/24/97 12/19/97 1/26/98 3/26/98 5/15/98 7/10/98 8/14/98 9/11/98 10/23/98 12/4/99 1/12/99 2/10/99 3/25/99 4/22/99 5/27/99 6/30/99 7/29/99 8/26/99 10/7/99 10/26/99 11/30/99 12/1/99 2/8/00 3/9/00 4/5/00 5/31/00 6/8/00 7/11/00 8/15/00 9/12/00 10/4/00 11/14/00 12/27/00 1/9/01 2/7/01 3/29/01 4/24/01 6/12/01 7/23/01 8/15/01 9/19/01 10/3/01 11/7/01 12/20/01 1/25/02 2/18/02 3/29/02 4/22/02 5/16/02 6/13/02 7/12/02 9/23/02 9/23/02 10/23/02 11/26/02 12/16/02 1/16/03 2/25/03 4/3/03 5/8/03 6/4/03 7/3/03 8/31/03 9/11/03 10/30/03 12/4/03 Average Resistance (Ohms) G H 32 24 39 26 14 28 46 29 41 28 63 31 98 35 107 32 121 32 147 39 76 32 66 32 56 30 65 31 95 31 129 36 126 35 108 40 46 23 55 24 73 25 64 26 73 29 63 28 58 27 50 26 84 29 75 30 80 27 50 30 50 28 86 27 78 28 82 29 75 30 68 29 61 29 71 26 100 31 79 29 121 32 132 32 152 34 155 36 164 38 158 37 81 31 49 27 58 26 86 27 123 31 136 34 146 33 102 31 57 25 57 27 76 29 63 30 63 28 61 28 37 26 52 27 71 26 67 26 71 26 70 27 /99 54 5/1406 3/23/2006 6/9/2005 6/20/2001 4/19/2001 1//2001 11/16/2000 9/20/2000 7/19/2000 5/26/2000 03/22/00 9/ 10/19/1999 8/16/1999 6/18/1999 4/15/1999 2/19/1999 12/29/1998 10/23/1998 Ohms Hibernia, NY G- Horizontal vs H- Vertical 400 350 300 250 200 G1 H1 Linear (G1) Linear (H1) 150 100 50 0 Figure 35 – New York Test Site Graph for Electrode Type G and H Table 24 – New York Test Site Data for Electrode Type G and H National Electrical Grounding Research Project Location: Test Site: Hibernia, NY CENHUD Read Date 9/24/1998 10/23/1998 11/20/1998 12/29/1998 1/21/1999 2/19/1999 3/19/1999 4/15/1999 5/27/1999 6/18/1999 7/16/1999 8/16/1999 9/27/1999 10/19/1999 11/19/1999 9/ /99 2/15/2000 03/22/00 4/19/2000 5/26/2000 6/15/2000 7/19/2000 8/18/2000 9/20/2000 10/17/2000 11/16/2000 12/13/2000 1//2001 2/15/2001 4/19/2001 5/16/2001 6/20/2001 7/19/2001 6/9/2005 1/20/2006 3/23/2006 4/28/2006 5/1406 G1 681 95 138 173 136 133 111 143 104 164 164 265 83 112 154 124 173 139 155 114 108 216 103 114 190 165 261 256 213 180 228 194 234 250 164 240 135 152 Resistance (Ohms) Horizontal Rods G2 G3 443 291 81 80 116 104 141 129 109 102 107 100 96 98 126 135 89 99 128 147 125 130 173 167 68 64 104 110 135 144 114 138 145 146 120 122 142 147 97 97 93 93 161 173 88 88 97 95 166 162 136 127 222 223 215 207 172 180 163 171 197 216 151 156 162 169 187 178 142 140 214 224 148 152 135 141 H1 111 102 118 134 140 137 142 136 114 122 116 118 108 115 130 139 157 155 143 124 119 123 109 110 125 130 151 162 162 156 151 130 124 140 155 171 155 144 Vertical Rods H2 118 104 119 136 143 137 142 139 115 121 113 116 105 113 126 134 150 151 142 123 117 122 109 108 122 127 145 157 156 153 152 132 125 152 158 81 530 153 Soil Resistivity (Ohm-cm at 10 ft.) H3 124 109 124 142 147 141 147 143 118 126 116 123 110 117 133 140 156 154 145 124 119 125 110 109 126 130 151 161 162 157 154 131 125 155 160 184 405 155 Read Date 19916 18575 21237 22407 22349 23229 23172 21831 18575 17427 17158 18288 16086 17235 19093 19686 22406 21142 20222 17503 16948 16737 15378 16086 18020 18729 21237 23037 24014 21574 20299 18193 17081 17886 18499 29491 19035 20108 9/24/1998 10/23/1998 11/20/1998 12/29/1998 1/21/1999 2/19/1999 3/19/1999 4/15/1999 5/27/1999 6/18/1999 7/16/1999 8/16/1999 9/27/1999 10/19/1999 11/19/1999 9/ /99 2/15/2000 03/22/00 4/19/2000 5/26/2000 6/15/2000 7/19/2000 8/18/2000 9/20/2000 10/17/2000 11/16/2000 12/13/2000 1//2001 2/15/2001 4/19/2001 5/16/2001 6/20/2001 7/19/2001 6/9/2005 1/20/2006 3/23/2006 4/28/2006 5/1406 Average Resistance (Ohms) G H 472 118 85 105 119 120 148 137 116 143 114 138 101 144 135 139 97 116 146 123 140 115 202 119 72 108 109 115 144 130 125 138 155 154 127 154 148 143 103 124 98 118 184 123 93 109 102 109 173 124 142 129 235 149 226 160 188 160 171 155 214 152 167 131 188 125 205 149 149 158 226 145 145 363 143 151 As compared to earth resistivity readings in other sites, Hibernia, NY, was consistently greater on average than any of the other sites. Neither the horizontal nor the vertical rods had average resistance values that met the NEC Section 250.53(G), 25 ohm requirement. The average resistance values for the vertical rods over time were relatively consistent for the duration of the test. The trendlines for the both vertical and horizontal electrodes showed an increasing trend. 55 6.1.5 Comparison of Electrode Resistance Table 25 shows the electrode comparisons that were made at the Las Vegas, National, and at all sites combined. The Type K (plate) electrode differs in diameter for the National sites and Las Vegas Sites, thus graphs for each are shown. The objective of this section was to show how the electrode resistance varied from site to site. By charting the yearly mean of the electrode resistance with one data point, ignoring the monthly variations, the average trend or influence each test location has on an electrode can be more easily evaluated. Site Location Las Vegas All Las Vegas Las Vegas All All All All Las Vegas Las Vegas National Las Vegas All Table 25 - Electrode Comparison Legend Electrode Type Site Location A Las Vegas B Las Vegas C Las Vegas D Las Vegas E Las Vegas F All G National H National I National J National K National K National L National 56 Electrode Type M N O P Q R S T V W X Y Z LAS VEGAS SITES A- ELECTRODES COMPARISON 80 70 60 Ohms 50 BA-A1 PA-A1 LM-A1 PE-A1 CH-A1 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 36 - Type A Electrode Comparison The comparison shows that the Pawnee A electrode had lower yearly mean resistance over time than other type A electrodes. 57 All Sites B- Electrodes Comparison 80 70 60 IL-B1 VA-B1 TX-B1 NY-B1 CA-B1 BA-B1 PA-B1 LM-B1 PE-B1 CH-B1 Ohms 50 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 37 - Type B Electrode Comparison The B electrode was installed in all sites. B electrodes in the Illinois, Pawnee, Lone Mountain, Pecos and Charleston all had resistance readings less than 20 ohms when evaluated with their yearly mean resistance calculated for the term of the project. 58 LAS VEGAS SITES C- ELECTRODES COMPARISON 200 180 160 140 Ohms 120 BA-C1 PA-C1 LM-C1 PE-C1 CH-C1 100 80 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 38 - Type C Electrode Comparison The data showed a spike in mean resistance during the fourth and sixth year at the Pawnee site, and there was also a spike in resistance during the seventh year at the Balboa site. This could be caused by loose connections or corroded conductor. The C electrodes in the Lone Mountain and Pecos sites had resistance readings less than 20 ohms when evaluated with their yearly mean resistance calculated for the term of the project. 59 LAS VEGAS SITES D- ELECTRODES COMPARISON 140 120 100 BA-D1 PA-D1 LM-D1 PE-D1 CH-D1 Ohms 80 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 39 - Type D Electrode Comparison Three sites had resistance readings that were relatively flat during the term of the experiment; those were Balboa, Lone Mountain and Pawnee. Greater variability with higher resistance readings occurred at the Charleston site. The D electrodes in the Lone Mountain and Pawnee sites had resistance readings less than 20 ohms when evaluated with their yearly mean resistance calculated for the term of the project. 60 All Sites E- Electrodes Comparison 60 50 IL-E1 VA-E1 TX-E1 NY-E1 CA-E1 BA-E1 PA-E1 LM-E1 PE-E1 CH-E1 Ohms 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 40- Type E Electrode Comparison The E electrode in all sites except in New York, had relatively consistent yearly mean resistance readings for the term of the experiment. Except for New York, all mean yearly data points for this electrode were less than 25 ohms. 61 All Sites F- Electrodes Comparison 200 180 160 IL-F1 VA-F1 TX-F1 NY-F1 CA-F1 BA-F1 PA-F1 LM-F1 PE-F1 CH-F1 140 Ohms 120 100 80 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 41 - Type F Electrode Comparison Very few readings were made at the California site to make any inferences on that data. In addition, there was nearly a four-year break in data collection for the F electrode in the New York site. The data showed that the majority of F electrodes had relative consistent yearly mean resistance plots during the term of the experiment. 62 All Sites G- Electrodes Comparison 450 400 350 IL-G1 VA-G1 TX-G1 NY-G1 CA-G1 BA-G1 PA-G1 LM-G1 PE-G1 CH-G1 Ohms 300 250 200 150 100 50 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 42 - Type G Electrode Comparison The graphs showing the highest resistance yearly mean readings were the New York and Balboa sites. The lowest resistance readings for these sites occurred in the second year at about 140 ohms. The variability of the electrodes in the Virginia and Lone Mountain sites were similar, and were mostly above 50 ohms. All other electrodes, except for those at the Charleston site, had mean yearly resistance readings below 50 ohms for the term of the experiment. 63 All Sites H- Electrodes Comparison 180 160 140 IL-H1 VA-H1 TX-H1 NY-H1 CA-H1 BA-H1 PA-H1 LM-H1 PE-H1 CH-H1 Ohms 120 100 80 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 43 - Type H Electrode Comparison Once again, there was a break in the data collection for the New York site. Nonetheless, the highest mean yearly resistance readings were at the New York site. The H electrode in the Balboa site showed an increasing trend during the experiment. Other electrodes showed this trend, but were not so pronounced. Except for the H electrode in the Balboa and New York sites, all other electrodes during the term of the project were below yearly mean readings of approximately 30 ohms. 64 LAS VEGAS SITES I- ELECTRODES COMPARISON 50 40 30 Ohms BA-I1 PA-I1 LM-I1 PE-I1 CH-I1 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 44 - Type I Electrode Comparison The I electrodes in every Las Vegas site showed relatively little variability in mean yearly readings during the term of the experiment. Only the electrode in Balboa was greater than 10 ohms, but it was less than 40 ohms during the term of the experiment. 65 LAS VEGAS SITES J- ELECTRODES COMPARISON 275 250 225 200 Ohms 175 BA-J1 PA-J1 LM-J1 PE-J1 CH-J1 150 125 100 75 50 25 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 45 - Type J Electrode Comparison The graph clearly showed that the J electrode in the Balboa site had the highest mean yearly resistance readings and the greatest variability. All other electrodes showed a decreasing or relatively flat trend over time. 66 National Sites K- Electrodes Comparison 700 600 500 IL-K1 VA-K1 TX-K1 NY-K1 CA-K1 Ohms 400 300 200 100 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 46 - Type K Electrode Comparison National Sites The K electrodes in all sites had the highest resistance readings. Based on this, the graphs also showed high mean yearly readings through the term of the experiment. This is especially so with the K electrodes in the Virginia, New York, and California sites. 67 LAS VEGAS SITES K- ELECTRODES COMPARISON 600 550 500 450 400 BA-K2 PA-K2 LM-K2 PE-K2 CH-K2 Ohms 350 300 250 200 150 100 50 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 47 - Type K Electrode Comparison Las Vegas Sites The K electrodes in all Las Vegas sites had the highest resistance readings. Based on this, the graphs also show high mean yearly readings through the term of the experiment, except for the Pawnee site. The Pawnee K electrode, however, does show an increasing trend in resistance over time. 68 All Sites L- Electrodes Comparison 70 60 IL-L1 VA-L1 TX-L1 NY-L1 CA-L1 BA-L1 PA-L1 LM-L1 PE-L1 CH-L1 50 Ohms 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 48 - Type L Electrode Comparison In all sites except for Virginia, the L electrode had resistance readings of less than approximately 40 ohms for the term of the experiment, averaging below 25 ohms for nine out of ten years. The L electrode in the Virginia site had a steep positive slope for the mean yearly resistance reading from year 9-10. As compared to other L electrodes, the electrodes in the Illinois, Texas, California, Pawnee, and Pecos sites had low mean yearly resistance readings. 69 LAS VEGAS SITES M- ELECTRODES COMPARISON 110 100 90 80 Ohms 70 BA-M1 PA-M1 LM-M1 PE-M1 CH-M1 60 50 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 49 - Type M Electrode Comparison The M electrode in the Balboa site clearly had the highest mean yearly readings during the term of the experiment. The best results were with the Pawnee site. Most electrodes showed an increasing trend in resistance. 70 LAS VEGAS SITES N- ELECTRODES COMPARISON 100 90 80 70 Ohms 60 BA-N1 PA-N1 LM-N1 PE-N1 CH-N1 50 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 50 - Type N Electrode Comparison The N electrode in the Balboa site had the highest mean yearly readings during the experiment. The best results were with the electrode in the Lone Mountain, Pawnee and Charleston sites. 71 LAS VEGAS SITES O- ELECTRODES COMPARISON 80 70 60 Ohms 50 BA-O1 PA-O1 LM-O2 PE-O1 CH-O1 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 51 - Type O Electrode Comparison Once again, the electrode in the Balboa site had the highest mean yearly readings. Somewhat similar results for the N electrode were obtained for the O electrodes - the worst case was in the Balboa site, and the best cases were with the Lone Mountain, Pawnee and Charleston sites. 72 LAS VEGAS SITES P- ELECTRODES COMPARISON 100 90 80 70 Ohms 60 BA-P1 PA-P1 LM-P1 PE-P1 CH-P1 50 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 52 - Type P Electrode Comparison Again, for the electrodes in the Las Vegas sites, the P electrode in the Balboa site was the worst case. All other sites had resistance readings less than 40 ohms through the term of the experiment. 73 LAS VEGAS SITES Q- ELECTRODES COMPARISON 300 275 250 225 200 BA-Q1 PA-Q1 LM-Q1 PE-Q1 CH-Q1 Ohms 175 150 125 100 75 50 25 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 53 - Type Q Electrode Comparison For the Q electrode, the Balboa site had the highest resistance readings. The Lone Mountain, Pecos and Pawnee sites showed a sharp decrease in mean resistance from year one to year two. In contrast, the Q electrode in the Charleston site showed a sharp increase during that same time period. 74 All Sites R- Electrodes Comparison 40 35 30 Ohms 25 IL-R1 VA-R1 TX-R1 NY-R1 CA-R1 BA-R1 20 15 10 5 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 54 - Type R Electrode Comparison The R electrode was present only in the sites shown in the graph legend. There was approximately a four-year break in data collection from the New York site. Nonetheless, the limited data shows that the mean yearly resistance readings were greatest at the New York site. The R electrodes in the Texas and Illinois sites had very low mean yearly resistance readings. 75 All Sites S- Electrodes Comparison 120 100 Ohms 80 IL-S1 VA-S1 TX-S1 NY-S1 CA-S1 PA-S1 PE-S1 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 55 - Type S Electrode Comparison Except for the New York site, the S electrodes in all other sites showed relatively low and consistent mean yearly readings for the term of the experiment. 76 National Sites T- Electrodes Comparison 120 100 Ohms 80 IL-T1 VA-T1 TX-T1 NY-T1 CA-T1 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 56 - Type T Electrode Comparison The results for the T electrode were very similar to the results for the S electrodes in the National sites. The chief difference was that the T electrode had slightly higher readings than the S electrode. 77 National Sites V- Electrodes Comparison 160 140 120 Ohms 100 IL-V1 VA-V1 TX-V1 NY-V1 CA-V1 80 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 57 - Type V Electrode Comparison Once again, for the National sites, the highest mean yearly resistance readings were with the New York site. The lowest readings were with the Illinois site, which showed consistency throughout the term of the experiment. 78 National Sites W- Electrodes Comparison 45 40 35 Ohms 30 IL-W1 VA-W1 TX-W1 NY-W1 CA-W1 25 20 15 10 5 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 58 - Type W Electrode Comparison Once again, for the National sites, the highest mean yearly resistance readings were with the New York site. The lowest readings were with the Illinois site, which showed consistency throughout the term of the experiment. 79 National Sites X- Electrodes Comparison For Year 7 and 8, TX- X1and X2 Exceed 3000 Ohms 120 100 Ohms 80 IL-X1 VA-X1 TX-X3 NY-X1 CA-X1 60 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 59 - Type X Electrode Comparison The X1 and the X2 electrodes in the Texas site readings exceeded 3000 ohms in year seven and eight of the experiment. The Figure above plots electrode X3 which remained low for the term of the experiment. The X1 electrode in the California and Illinois sites were less than 20 ohms for the mean yearly resistance readings. 80 National Sites Y- Electrodes Comparison 100 80 60 Ohms IL-Y1 VA-Y1 TX-Y1 NY-Y1 40 20 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 60 - Type Y Electrode Comparison The Y electrode was not installed in the California site. Again, the New York site had the highest readings, followed by Virginia, Texas, and Illinois. 81 National Sites Z- Electrodes Comparison 90 80 70 Ohms 60 IL-Z1 VA-Z1 TX-Z1 NY-Z1 CA-Z1 50 40 30 20 10 0 Year Year Year Year Year Year Year Year Year Year 1 2 3 4 5 6 7 8 9 10 Years of Service Figure 61 - Type Z Electrode Comparison The Z electrodes had similar results to other electrodes in the National sites. That is, the highest mean yearly readings were with the New York site, followed by Virginia, California, Texas, and Illinois. 6.2 Ancillary Experiments 82 The ancillary experiments included: a) DC Active, b) Dissimilar Metals, and c) Benign Corrosion experiments. 6.2.1 DC1 and DC2 Results Northbrook, IL Direct Currrent Experiment DC1 7 6 Milliamps 5 4 DC1A DC1B DC1C 3 2 1 12/12/06 7/26/06 10/25/06 4/18/06 1/19/06 7/15/05 10/19/05 4/18/05 1/25/05 8/16/04 11/23/04 5/26/04 2/18/04 10/8/03 7/18/03 4/23/03 1/28/03 7/15/02 10/17/02 4/15/02 1/22/02 7//01 10/22/01 4/18/01 1/10/01 7/17/00 10/11/00 4/14/00 1/18/00 7/16/99 10/15/99 4/13/99 1/18/99 10/8/98 0 Figure 62 - Illinois DC1 Experiment The results for the DC1 pod showed that the current in all three electrodes were relatively similar over the term of the experiment. All electrodes showed a decrease in current in about the sixth year of the experiment, and a continuing progressive decrease through the eighth year. The decrease in current is possibly due to either corrosion and/or a loosening of the connection means and separation between the soil and the rod itself. 83 Northbrook, IL Direct Currrent Experiment DC2 40 35 30 Milliamps 25 DC2A DC2B DC2C 20 15 10 5 10/8/98 1/18/99 4/13/99 7/16/99 10/15/99 1/18/00 4/14/00 7/17/00 10/11/00 1/10/01 4/18/01 7//01 10/22/01 1/22/02 4/15/02 7/15/02 10/17/02 1/28/03 4/23/03 7/18/03 10/8/03 2/18/04 5/26/04 8/16/04 11/23/04 1/25/05 4/18/05 7/15/05 10/19/05 1/19/06 4/18/06 7/26/06 10/25/06 12/12/06 0 Figure 63 - Illinois DC2 Experiment Unlike the results for the DC1 pod, the electrodes in the DC2 pod did not show a specific decrease in DC current at a specific period in time. It was determined that at about the second year of the experiment the polarity in the DC2 pod was reversed. This means that electrode material was not being lost to the surrounding soil. Except for one abnormality during the end of the third year, the current for the three electrodes in the DC2 pod were similar. 84 Dallas, TX Direct Current Experiment DC1 12 10 Milliamps 8 DC1A DC1B DC1C 6 4 2 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 7//03 11/25/03 3/24/03 7/30/02 11/25/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 11/22/99 7/30/99 3/23/99 7/30/98 11/30/98 0 Figure 64 - Texas DC1 Experiment Except for some abnormalities, the results for the DC1 pod showed that the current in all three electrodes were relatively similar over the term of the experiment. All electrodes showed a decrease in current in about the fourth year of the experiment and remained at a relatively low level for the remaining term of the experiment. As with the Illinois site, the results for the DC1 pod showed that the current in all three electrodes were relatively similar over the term of the experiment. The decrease in current is possibly due to one or more of the following factors: corrosion; loosening of the connection means; and separation between the soil and the rod itself. 85 Dallas TX Direct Current Experiment DC2 12 10 Milliamps 8 DC2A DC2B DC2C 6 4 2 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 7//03 11/25/03 3/24/03 7/30/02 11/25/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 11/22/99 7/30/99 3/23/99 7/30/98 11/30/98 0 Figure 65 - Texas DC2 Experiment The results showed that the three electrodes in the DC2 pod did not reach a low current level until late 2005. Once again, the overall decrease in current indicated that there was an increase in resistance due to a number of contributing factors, one of which could be corrosion. 86 Moffett Field, CA Direct Current Experiment DC1 30 25 Milliamps 20 DC1A DC1B DC1C 15 10 5 12/26/06 10/2/06 7/7/06 4//06 1//06 10//05 7/6/05 4//05 1//05 10//2004 7//2004 4//2004 10//03 1//2004 7//03 4//03 1//03 10//02 7//02 4//02 1/28/02 0 Figure 66 - California DC1 Experiment Unlike the other National sites, little data was collected from the California site. Based on this it was difficult to draw any specific conclusion. The figures for both DC pods are included for reference. Moffett Field, CA Direct Current Experiment DC2 7 6 4 DC2A DC2B DC2C 3 2 1 Figure 67 - California DC2 Experiment 87 12/26/06 10/2/06 7/7/06 4//06 1//06 10//05 7/6/05 4//05 1//05 10//2004 7//2004 4//2004 1//2004 10//03 7//03 4//03 1//03 10//02 7//02 4//02 0 1/28/02 Milliamps 5 Staunton, VA Direct Current Experiment DC1 10 Milliamps 8 6 DC1A DC1B DC1C 4 2 12//06 9//06 5/24/06 1/18/06 9/28/05 5/20/05 9//04 1/ /2005 1//06 5/21/04 9/11/03 5/8/03 1/16/03 9/23/02 5/16/02 1/25/02 5//01 9/19/01 1/9/01 9/12/00 1//00 5/31/00 10/7/99 5/27/99 9//98 1/12/99 5/15/98 1/26/98 0 Figure 68 - Virginia DC1 Experiment Except for one abnormality in mid 2000, the results for the DC1 pod showed that the current in all three electrodes was relatively similar up until the sixth year of the experiment. At this time the DC1 electrode measured little or no current. This indicated that the DC1A electrode had a high resistance, which could be due to a number of factors, including corrosion. 88 Staunton, VA Direct Current Experiment DC2 10 Milliamps 8 6 DC2A DC2B DC2C 4 2 12//06 9//06 5/24/06 1/18/06 9/28/05 5/20/05 9//06 1/ /2005 1//06 5/21/04 9/11/03 5/8/03 1/16/03 9/23/02 5/16/02 1/25/02 5//01 9/19/01 1/9/01 9/12/00 5/31/00 1//00 10/7/99 5/27/99 9//98 1/12/99 5/15/98 1/26/98 0 Figure 69 - Virginia DC2 Experiment The results for the DC2 experiment showed very similar results for all electrodes in the pod. These results were consistent during the term of the experiment. The graph seems to show that this experiment needs to be conducted for a longer period of time to result in a current drop due to an increase in resistance from corrosive effects. 89 Hibernia, NY Direct Current Experiment DC1 10 Milliamps 8 6 DC1A DC1B DC1C 4 2 4//06 8//05 12//05 4//05 8//04 12//04 4//04 8//03 12//03 4//03 8//02 12//02 4//02 8//01 12//01 5/16/01 1/15/01 09/20/00 1//00 05/26/00 9/27/1999 5/27/1999 1/21/1999 9/24/1998 0 Figure 70 - New York DC1 Experiment The New York site experiment was active for the first two and one-half years, and inactive for the following three and one-half years. Except for DC1A, the results for the DC1 pod showed that the current in all three electrodes was relatively similar up until mid 2000. All electrodes showed a decrease in current at about the end of the second year of the experiment, and decreased through the remaining term of the experiment. This was not true, however, for the DC1A electrode which showed an increase in current after the second year. 90 Hibernia, NY Direct Current Experiment DC2 10 Milliamps 8 6 DC2A DC2B DC2C 4 2 4//06 8//05 12//05 4//05 8//04 12//04 4//04 8//03 12//03 4//03 8//02 12//02 4//02 8//01 12//01 5/16/01 1/15/01 09/20/00 1//00 05/26/00 9/27/1999 5/27/1999 1/21/1999 9/24/1998 0 Figure 71 - New York DC2 Experiment The results for the DC2 pod had similar readings to the DC1 pod for the term of the experiment. A marked decrease in current took place two years into the experiment, and the data showed that all three electrodes had minimal current at about two and one-half years into the experiment. The data indicated that the direct current had a pronounced effect on the resistance of the electrode to earth. 91 6.2.2 Dissimilar Metals Results 6.2.2.1 Illinois DM Experiments The Dissimilar Metals (DM) Experiment included six electrodes arranged in three sets of two. The purpose of this experiment was to develop data that could show changes of resistance, mainly caused by dissimilar metals in an earth coupled cell that could possibly produce current flow and lead to corrosion. Figure 70 illustrates the experiment and shows the grounding electrode samples used. DM1A, DM2A, DM3A are 5/8” x 8’ copper bonded ground rod and DM1B, DM2B, DM3B are ¾” x 8’ galvanized steel pipe. There is 6-1/2 ft. between the copper bonded ground rod and the paired galvanized steel pipe ground rod. The experiment included the measurement of current flow through each paired grounding electrode circuit. A precision 0.01 ohm resistor was used in the circuit to standardize current measurement. Northbrook, IL Dissimilar Metals Experiment 6 5 Milliamps 4 DM1 DM2 DM3 Linear (DM1) Linear (DM2) Linear (DM3) 3 2 1 10/8/98 1/18/99 4/13/99 7/16/99 10/15/99 1/18/00 4/14/00 7/17/00 10/11/00 1/10/01 4/18/01 7//01 10/22/01 1/22/02 4/15/02 7/15/02 10/17/02 1/28/03 4/23/03 7/18/03 10/8/03 2/18/04 5/26/04 8/16/04 11/23/04 1/25/05 4/18/05 7/15/05 10/19/05 1/19/06 4/18/06 7/26/06 10/25/06 12/12/06 0 Figure 72 - Illinois Dissimilar Metals Experiments Figure 69 shows the trendlines for the three sets of DM electrodes. In all cases, the trend shows a decrease in current over time, which would indicate an increase of resistance between the electrodes and earth. 92 Dallas TX Dissimilar Metals Experiments 6 5 Milliamps 4 DM1 DM2 DM3 Linear (DM1) Linear (DM2) Linear (DM3) 3 2 1 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 7//03 11/25/03 3/24/03 7/30/02 11/25/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 7/30/99 11/22/99 3/23/99 11/30/98 7/30/98 0 Figure 73 - Texas Dissimilar Metals Experiments The current readings over time are relatively similar for each of the electrodes. The trend, however, showed two electrodes decreasing with one electrode increasing. This increase may be due to one relatively high reading measured in early 2006. 93 Moffett Field, CA Dissimilar Metals Experiments 70 60 Milliamps 50 40 DM1 DM2 DM3 30 20 10 12/26/06 10/2/06 7/7/06 4//06 1//06 10//05 7/6/05 4//05 1//05 10//2004 7//2004 4//2004 10//03 1//2004 7//03 4//03 1//03 10//02 7//02 4//02 1/28/02 0 Figure 74 - California Dissimilar Metals Experiments Relatively few data points for this experiment were taken at the California site. The figure for the DM electrodes is included for reference. 94 Staunton, VA Dissimilar Metals Experiments 10 8 DM1 DM2 DM3 Linear (DM1) Linear (DM2) Linear (DM3) Milliamps 6 4 2 9//06 12//06 5/24/06 1/18/06 9/28/05 5/20/05 9//06 1/ /2005 1//06 5/21/04 5/8/03 9/11/03 1/16/03 9/23/02 5/16/02 1/25/02 5//01 9/19/01 1/9/01 9/12/00 1//00 5/31/00 10/7/99 5/27/99 9//98 1/12/99 5/15/98 1/26/98 0 Figure 75 - Virginia Dissimilar Metals Experiments Figure 73 shows trendlines for the three sets of electrodes. In two of three cases, the trend shows a decrease in current over time, which would indicate an increase of resistance between the electrodes and earth. In the one case (DM1) the trend is nearly flat. 95 Hibernia, NY Dissimilar Metals Experiments 4 Milliamps 3 DM1 DM2 DM3 Linear (DM1) Linear (DM2) Linear (DM3) 2 1 4//06 8//05 12//05 4//05 12//04 8//04 4//04 12//03 8//03 4//03 12//02 8//02 4//02 8//01 12//01 5/16/01 1/15/01 09/20/00 1//00 05/26/00 9/27/1999 5/27/1999 1/21/1999 9/24/1998 0 Figure 76 - New York Dissimilar Metals Experiments For the term of the experiment, the trendlines for all electrodes are decreasing. This indicated a decrease in current which results in an increase in resistance between earth and the electrode. 6.2.3 Benign Corrosion Experiments The Copper Development Association (CDA®), sponsored an adjunct corrosion experiment that consisted of using 4/0 AWG and 500 KCM bare copper conductors installed directly in earth, Bentonite or GEM tm backfill materials. Samples of these conductors from the New York site were exhumed for corrosion analysis, and these results are shown in Section 5.5 of the, “Condition Report of Grounding Electrodes after Underground Burial at Las Vegas Nevada and Poughkeepsie, NY”, (Corrosion Report). See Appendix 11.3. 96 6.3 Soil Characteristics 6.3.1 Earth Resistivity Earth resistivity (IEEE 81-1983 [4]) is a key factor that can determine the resistance of grounding electrodes. A set of readings taken with various probe spacings gives a set of resistivities which, when plotted against spacing, indicates whether there are distinct layers of different soil or rock and gives an idea of their respective resistivities and depth. Earth resistivity varied by location as shown in Table 26. Recorded resistivity values for the National and the Las Vegas test sites ranged from 517 to 23,363 ohm-cm, and 77 to 31,597 ohm-cm respectively. To properly predict the performance of electrodes, earth resistivity values must be obtained. Standardized testing methods, such as those referenced in IEEE 81-1983 [4], should be used to determine these values. Table 26 - Earth Resistivity for All Sites 10 Year Data Earth Resistivity 10 ft. Spacing MIN AVE MAX 2313 2821 3497 IL 1563 3319 4577 TX 517 2763 4577 CA 153 2527 9000 LM 77 1362 9575 PA 708 2084 9575 CH 766 1734 12868 PE 7603 9930 19533 VA 15378 19527 24014 NY 3217 8736 31597 BA Earth Resistivity 20 ft. Spacing MIN AVE MAX 1896 2098 2306 IL 1655 3242 8158 TX 460 2118 9000 CH 766 4638 9506 CA 613 3158 9958 LM 575 2079 13175 PE 306 1651 14056 PA 8235 10269 15090 VA 11011 20409 23363 NY 1915 11474 25278 BA Data in Table 26 are arranged in ascending order using the maximum values. 97 6.3.2 Earth Resistivity versus Resistance for Selected Electrodes Soil classification reports were provided for each of the Las Vegas sites, and are included in Appendix 11.5. In tables 27 through 31, comparisons of electrode resistance were made to earth resistivity. Pawnee represented a low value of earth resistivity and Balboa represents the highest value. A limited analysis was conducted to determine whether or not there would be significant differences in resistance of horizontal versus vertical electrodes. This analysis included electrodes in the Pawnee, Pecos, Lone Mountain, Charleston and Balboa Las Vegas sites. The results showed that the average electrode resistance in all cases except for one, the horizontal electrodes had higher average resistance readings than the vertical types. Tables 27 through 31, show average electrode resistance values as compared to average soils resistivity values. Table 27 - Pawnee Resistance Compared to Earth Resistivity Table 28 - Pecos Resistance Compared to Earth Resistivity 98 Table 29 - Lone Mountain Resistance Compared to Earth Resistivity Table 30 - Charleston Resistance Compared to Earth Resistivity Table 31 Balboa Resistance Compared to Earth Resistivity 99 6.3.3 Soil Temperature With the exception of the Charleston site, all sites had soil temperatures taken at depths of 30 in., 78 in., and 126 in. Northbrook IL Soil Temperature 80 70 60 Deg F. 50 T1 -126 Inches T2 -78 Inches T3 -30 Inches 40 30 20 10 10/8/98 1/18/99 4/13/99 7/16/99 10/15/99 1/18/00 4/14/00 7/17/00 10/11/00 1/10/01 4/18/01 7//01 10/22/01 1/22/02 4/15/02 7/15/02 10/17/02 1/28/03 4/23/03 7/18/03 10/8/03 2/18/04 5/26/04 8/16/04 11/23/04 1/25/05 4/18/05 7/15/05 10/19/05 1/19/06 4/18/06 7/26/06 10/25/06 12/12/06 0 Figure 77 - Illinois Soil Temperature The greatest range of temperatures measured was with the T3 sensor, located at a 30 in. depth. This range was approximately 35 to 71 degrees F. As expected, the smallest range in temperature occurred with the T1 sensor at 126 in. below the surface. The range was approximately 44 to 59 degrees F. As expected, there was less fluctuation in soil temperature as soil depth increased. Also as expected, the graph shows a shift in the maximum and minimum temperatures recorded by any specific sensor over time. 100 Dallas, TX Soil Temperature 120 100 Deg F. 80 T1 -126 Inches T2 -78 Inches T3 -30 Inches 60 40 20 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 7//03 11/25/03 3/24/03 7/30/02 11/25/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 7/30/99 11/22/99 3/23/99 7/30/98 11/30/98 0 Figure 78 - Texas Soil Temperature The greatest range of temperatures measured was with the T3 sensor, located at a 30 in. depth. This range was approximately 48 to 83 degrees F. As expected, the smallest range in temperature occurred with the T1 sensor at 126 in. below the surface. Except for the abnormality in mid 1998, the range was approximately 59 to 72 degrees F. As expected, there was less fluctuation in soil temperature as soil depth increased. Also as expected, the graph showed a shift in the maximum and minimum temperatures recorded by any specific sensor over time. Also as expected, all three sensors recorded the lowest temperatures during the winter months and the highest temperatures in the summer months. 101 Moffett Field, CA Soil Temperature 90 80 70 Deg F. 60 50 T1 -126 Inches T2 -78 Inches T3 -30 Inches 40 30 20 10 12/26/06 10/2/06 7/7/06 4//06 1//06 10//05 7/6/05 4//05 1//05 10//2004 7//2004 4//2004 1//2004 10//03 7//03 4//03 1//03 10//02 7//02 4//02 1/28/02 0 Figure 79 - California Soil Temperature The greatest range of temperatures measured was with the T3 sensor, located at a 30 in. depth. This range was approximately 55 to 78 degrees F. As expected, the smallest range in temperature occurred with the T1 sensor at 126 in. below the surface. Also as expected, there was less fluctuation in soil temperature as soil depth increased. 102 Staunton, VA Soil Temperature 80 70 60 Deg F 50 T1 -126 Inches T2 -78 Inches T3 -30 Inches 40 30 20 10 10/23/02 7/12/02 4/22/02 1/25/02 10/3/01 7/23/01 4/24/01 1/9/01 10/4/00 7/11/00 4/5/00 1//00 7/29/99 10/26/99 4/22/99 1/12/99 10/23/98 7/10/98 04//98 1/26/98 0 Figure 80 - Virginia Soil Temperature Reliable temperature data for the Virginia site was only captured through 2002. The greatest range of temperatures measured was with the T3 sensor, located at a 30 in. depth. This range was approximately 42 to 71 degrees F. The smallest overall range in temperature occurred with the T1 sensor at 126 in. below the surface. As expected, there was less fluctuation in soil temperature as soil depth increased. 103 Hibernia, NY Soil Temperature 80 70 60 Deg F. 50 T1 -126 Inches T2 -78 Inches T3 -30 Inches 40 30 20 10 4//06 8//05 12//05 4//05 8//04 12//04 4//04 8//03 12//03 4//03 8//02 12//02 4//02 8//01 12//01 5/16/01 1/15/01 09/20/00 1//00 05/26/00 9/27/1999 5/27/1999 1/21/1999 9/24/1998 0 Figure 81 - New York Soil Temperature The greatest range of temperatures measured was with the T3 sensor, located at a 30 in. depth. This range was approximately 35 to 67 degrees F. As expected, the smallest range in temperature occurred with the T1 sensor at 126 in. below the surface. The range was approximately 43 to 59 degrees F. As expected, there was less fluctuation in soil temperature as soil depth increased. Also as expected, the graph shows a shift in the maximum and minimum temperatures recorded by any specific sensor over time. 104 6.3.4 Earth Resistivity and Soil Temperature Northbrook, IL Earth Resistivity and Soil Temperature 3497 3298 2451 45.1 F 43 F 6/27/04 5/27/04 4/27/04 3/27/04 2/27/04 Soil Temp ° F 1/27/04 12/27/03 11/27/03 9/27/03 10/27/03 8/27/03 7/27/03 5/27/03 4/27/03 3/27/03 2/27/03 1/27/03 12/27/02 11/27/02 9/27/02 10/27/02 8/27/02 7/27/02 6/27/02 5/27/02 4/27/02 3/27/02 2/27/02 1/27/02 12/27/01 11/27/01 9/27/01 10/27/01 6/27/03 Resistivity Ohm-cm 41.4 F Figure 82 - Illinois Earth Resistivity and Soils Temperature The data compares the earth resistivity and soil temperature taken at the 126 in. depth. As expected in most cases, the graph showed an inverse relationship between earth resistivity and soil temperature. 105 Dallas TX Earth Resistivity and Soil Temperature 3925 3887 3926 69.2 70.1 67.7 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 11/25/03 7//03 3/24/03 11/25/02 7/30/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 11/22/99 7/30/99 3/23/99 7/30/98 11/30/98 Ohm-cm Temp ° F Figure 83 - Texas Earth Resistivity and Soils Temperature Unlike the Illinois site, there was not a clear inverse relationship between earth resistivity and soil temperature for the Texas site. With some data over the term of the experiment there was an inverse relationship, but at other times (e.g. 7/30/99) there was a direct relationship between resistivity and temperature. It is speculated that these results were based upon relatively large fluctuations in soil moisture content. 106 Staunton, VA Earth Resistivity and Soil Temperature 9//06 5/24/06 1/18/06 9/28/05 5/20/05 9//06 1/ /2005 5/21/04 1//06 9/11/03 5/8/03 1/16/03 9/23/02 5/16/02 1/25/02 5//01 Soil Temp ° F 9/19/01 1/9/01 9/12/00 5/31/00 1//00 10/7/99 5/27/99 9//98 1/12/99 5/15/98 1/26/98 Resistivity Ohm-cm Figure 84 - Virginia Earth Resistivity and Soils Temperature The data compares the earth resistivity and soil temperature taken at the 126 in. depth. As expected in most cases, the graph showed an inverse relationship between earth resistivity and soil temperature. 107 Hibernia, NY Earth Resistivity and Soil Temperature 24014 23037 21237 49.2 45.5 2//06 5/14/06 8//05 11//05 5//05 2//05 8//04 11//04 5//04 2//04 8//03 11//03 5//03 2//03 8//02 5//02 2//02 8//01 11//01 3//01 6/20/01 12/13/00 09/20/00 06/15/00 /99 9/ 03/22/00 9/27/1999 6/18/1999 3/19/1999 9/24/1998 12/29/1998 11//02 Earth Resistivity ohm-cm Soil Temp ° F 43.3 Figure 85 - New York Earth Resistivity and Soils Temperature As was done with the data for other sites, the data compares the earth resistivity and soil temperature taken at the 126 in. depth. As expected in most cases, the graph showed an inverse relationship between earth resistivity and soil temperature. 108 6.3.5 Soil Moisture A higher Delmhorst unit represents a greater moisture content and a lower resistance. Northbrook IL Soil Moisture 120 100 Delmhorst Units 80 M1 -126 Inches M2 -78 Inches M3 -30 Inches 60 40 20 6/14/06 10/25/06 2/15/06 10/19/05 6/22/05 2/22/05 7/12/04 11/23/04 3/19/04 10/8/03 6/13/03 2/19/03 6/17/02 10/17/02 2/18/02 6/26/01 10/22/01 2/19/01 6/19/00 10/11/00 2/15/00 6/18/99 10/15/99 2/18/99 10/8/98 0 Figure 86 - Illinois Soil Moisture The data for all three sensors at each level showed relative consistency throughout the term of the experiment regarding soil moisture. Some abnormalities in data exist, but this was for relatively short periods of time. 109 Dallas, TX Soil Moisture 140 120 Delmhorst Units 100 80 M1 -126 Inches M2 -78 Inches M3 -30 Inches 60 40 20 11/22/06 3//06 7/12/06 7/29/05 11/28/05 3/22/05 7/ /2004 11/ /2004 3/ /2004 7//03 11/25/03 3/24/03 7/30/02 11/25/02 3/28/02 7/31/01 11/26/01 3/13/01 11/20/00 07/30/99 03/28/00 7/30/99 11/22/99 3/23/99 7/30/98 11/30/98 0 Figure 87 - Texas Soil Moisture The data for all three sensors at each level showed large swings in soil moisture content during the term of the experiment. The range was approximately 1 to 118 Delmhorst units. The M2 and M3 sensors recorded relative consistent soil moisture, beginning with about the third year into the experiment. 110 Moffett Field, CA Soil Moisture 120 100 Delmhorst Units 80 M1 -126 Inches M2 -78 Inches M3 -30 Inches 60 40 20 12/26/06 7/7/06 10/2/06 4//06 1//06 10//05 7/6/05 4//05 1//05 10//2004 7//2004 4//2004 1//2004 7//03 10//03 4//03 1//03 10//02 7//02 4//02 1/28/02 0 Figure 88 - California Soil Moisture The limited data for all three sensors at each level showed at least one swing in soil moisture content during the term of the experiment. Beginning in the last year of the experiment, the three sensors began to show relatively constant soil moisture, with the sensor at the deepest level, M1, showing the greatest Delmhorst units. 111 Staunton, VA Soil Moisture 120 100 Delmhorst Units 80 M1 -126 Inches M2 -78 Inches M3 -30 Inches 60 40 20 10/23/02 7/12/02 4/22/02 1/25/02 10/3/01 7/23/01 4/24/01 1/9/01 10/4/00 7/11/00 4/5/00 1//00 10/26/99 7/29/99 4/22/99 1/12/99 10/23/98 7/10/98 04//98 1/26/98 0 Figure 89 - Virginia Soil Moisture The results of the data showed periods of moist soil conditions at approximately 95 Delmhorst units, followed by periods of drier soil conditions. Fluctuations were recorded with sensors at all depths. The greatest fluctuations were with the M2, and M3 sensors. The smallest range in soil moisture fluctuation was with the M1 sensor at the 126 in. level. 112 Hibernia, NY Soil Moisture 120 100 Delmhorst Units 80 M1 -126 Inches M2 -78 Inches M3 -30 Inches 60 40 20 4//06 8//05 12//05 4//05 8//04 12//04 4//04 8//03 12//03 4//03 8//02 12//02 4//02 8//01 12//01 5/16/01 1/15/01 09/20/00 05/26/00 1//00 9/27/1999 5/27/1999 1/21/1999 9/24/1998 0 Figure 90 – New York Soil Moisture Until one and one-half years into the experiment, the soil moisture readings at every depth were relatively consistent. The M3 sensor showed a sharp decrease in Delmhorst units in about April 2000, and remained relatively consistent through mid 2001. There was a break in data collection from mid 2001 through mid 2005. 113 6.4 Corrosion Results When this project began, it was anticipated that all sample electrodes in every site would be exhumed and then evaluated for corrosion. Based upon this, the samples including their three wire connectors were weighed prior to installation in the National sites. Weight is an important physical characteristic of the sample electrodes and their connectors, to be judged by a corrosion analysis. As the project progressed, it became apparent that due to a number of reasons including lack of complete funding, full exhumation and corrosion analysis of all electrodes in every National site would not be possible. In addition, difficulty was encountered with some of the sites due to unanticipated changes including the lack of site access authorization for exhumation. Nonetheless, a corrosion analysis was conducted on selected exhumed electrodes from New York and from three of the five Las Vegas sites; Balboa, Lone Mountain and Pecos. Corrosion and Materials Consultancy Inc., was contracted by FPRF to conduct a corrosion analysis on the exhumed samples. The complete report is shown in Appendix 11.3. A summary of the corrosion report by Corrosion and Materials Consultancy Inc. follows. Grounding electrodes were examined following underground soil exposure testing at sites near Las Vegas, NV and Poughkeepsie, NY. Specifically, the test samples were examined after about 9 to 11 years, (Las Vegas) and following 8 years and 8 months, (Poughkeepsie). The Las Vegas samples were exhumed from four sites (Balboa, Lone Mountain, Pecos, and Pawnee) between May, 2001 and April, 2004. The samples from Poughkeepsie, were exhumed in May, 2006. The corrosion report describes the general condition of the buried grounding electrodes, notably the extent of corrosion degradation or damage following the approximately ten year burial period. Given the geometry of electrode assemblies and the three connectors installed thereon, it was not possible to fully quantify the material performance. Thus, the majority of the findings were based upon visual appearances supported by selective metallurgical testing. The corrosion condition of the grounding electrode assemblies was reviewed according to the visual appearance and metallurgical condition of the materials. The metallurgical testing conducted in this program was performed to assess the extent of corrosion damage confined to the metal substrate. This could include general or localized pitting, metal thinning, cracked or fractured metals, internal pits, de-alloying and intergranular attack. Conventional optical microscopy and selective electron microscopy were used to better describe the nature and extent of corrosion displayed by representative grounding electrodes after about 10 years burial in soil. A corrosion rating (CR) was allocated in an attempt to better define the extent and nature of the corrosion condition of the various grounding electrodes based upon the visual and metallurgical assessments that were performed. This approach should be of value regarding the potential for corrosion in any particular type of grounding electrode. The CR rating shown in Table 32 was not intended as a ranking of one electrode type over another. 114 Table 32 – Corrosion Ratings Corrosion rating (CR ) 0 none 1 slight 2 moderate X heavy Features No visible corrosion products or pitted metal Superficial occurrences of corrosion - not over all surfaces Moderate build up of products; some protrusions; local pitting Significant build-up of products over all; metal section loss The three types of connectors were exposed to the same underground soil conditions as the grounding electrodes for the same periods of time. The grounding electrodes were connected using 6 AWG insulated stranded copper conductor to the pull box – the central place for termination of connectors. Exothermic connections were connected to the top end of the electrodes; compression and bolted connectors were generally connected approximately 3-in. apart down from the exothermic connectors. Most connections retained their integrity during the complete test period. Corrosion was manifested as rust or green corrosion products on the exothermic connections and on the steel or copper connectors, respectively. The connectors performed under static conditions, and were not exposed to high-fault current. The study demonstrated that many of the grounding electrodes tested at the Las Vegas, NV sites performed well in the silt, sand, clay-like soils that can generally be regarded as corrosive-to-highly corrosive. The effects of corrosion at the Poughkeepsie, NY site were generally less extensive. The copper-bonded grounding electrodes were generally better ranked from a corrosion viewpoint by contrast to the galvanized rods (Las Vegas, NV) or pipes (Poughkeepsie, NY) that displayed more extensive corrosion (rusting). The corrosion report includes a discussion of the effect of the soil environment on corrosion. The report concludes that soil properties are only guides and should be considered against other factors when choosing appropriate grounding electrodes. For all National and Las Vegas sites, a soil analysis was conducted on either a soil sampling from core boring or soil “grab” sample. Based upon funding limitations for the corrosion analysis, the soil chemistry correlation to electrode performance was not conducted. In summary, the majority of the grounding electrode materials performed well over the approximately ten year soil exposure tests. Notable exceptions included: • • • • The loss of zinc on galvanized steel ground rods, which resulted in excessive steel corrosion. Copper-bonded steel ground rods showed minimal corrosion. The exposed steel at the uncoated end of the copper-bonded ground rods showed evidence of corrosion (rust) over a distance (typically) of about 1-1.5 inches. Certain of the grounding electrodes filled with chlorides and encased in Lynconite II or Bentonite clay corroded at the tip end and around the weep holes, by contrast to others that displayed minimal corrosion. Certain of the grounding electrodes – encased horizontally – in coke based ground enhancement material (GEM tm) corroded along the entire length by 115 • contrast to others – enclosed vertically – in coke based GEM tm that showed minimal corrosion. Failed connectors in general were damaged during the exhumation processes, where connecting wires were occasionally pulled free of the connectors. Exothermic connections placed at the ends of the ground rods were particularly vulnerable to mechanical damage. There was generally insignificant corrosion of the steel or copper fasteners. 116 7. SUMMARY The data and observations documented under this research project support the following findings. 7.1 In evaluating the data for all electrodes in all National sites, the electrodes as a group in the Illinois site appeared to have the lowest resistance readings, whereas, the New York site had the highest readings, with the majority of readings in New York not meeting the 25 ohm requirement of NEC Section 250.52. In a comparison of all electrodes in each National site, the best results were with the E, L and R electrodes. Other electrodes that did relatively well were the, S, W and X electrodes. For most sites, the K and G electrodes were poor performers. 7.2 A limited analysis of the horizontal versus the vertical rod type electrodes for the Las Vegas sites showed that the vertical electrodes had lower resistance values than their horizontal counterparts. This was also a similar case for all the National sites except for Illinois. Variations in earth resistivity and other factors did not appear alter this relationship. 7.3 Yearly mean electrode resistance readings were compared in the Las Vegas, National, and all sites combined. For the Las Vegas sites, in almost every case for every electrode, the Balboa site had the highest yearly mean readings, whereas the Pawnee site had the lowest values. For the National sites, the yearly mean readings for all electrodes were highest in the New York site, and lowest in the Illinois and Texas sites. The B, E, F, G, H and L electrodes were included in all sites. 7.4 As expected, the worst case results were with the New York and Balboa sites, whereas, the best-case results were generally with the Illinois, Pawnee, and Texas sites. Electrode resistance values are required to be lower than 25 ohms for individual rod, pipe and plate electrodes to meet NEC 250.56 [3] requirement. Concrete encased electrodes per NEC 250.52 [3] are not required to be lower than the 25 ohm value and may be installed without testing. The concrete encased electrode, (Type B) exceeded the 25 ohm value in the Texas, Virginia and New York sites, for the majority of readings. 7.5 Distinct patterns can be seen in data for many of the sites. These patterns appear to be sympathetic to seasonal variations. It is apparent in comparisons of data from many sites that an inverse relationship exists between earth resistivity and soil temperature. According to the Soares Book on Grounding [5], soil temperatures vary inversely with relative earth resistivity. Knowledge of this factor could be useful in determining the suitability of an electrode. 7.6 The resistance reading for the National sites showed that Illinois had only two electrodes that exceeded 25 ohms during the term of the study. This could be due to the Illinois site being located in moist soil conditions. Most of the electrodes in the Dallas site for the term of the study were less than 25 ohms. The difference in resistance readings between the sites can be attributed to soil chemistry, moisture, resistivity, and other mechanical conditions. The data can be used to make inferences for appropriate electrodes for use in similar locations. 117 7.7 The DC experiments were designed to evaluate the effects of corrosion due to the presence of direct currents. With many of the DC electrodes in the National sites, the data showed a sharp decrease in current with time. It is assumed that this decrease is due to the corrosive effects of the DC current possibly resulting in progressively higher resistance levels between the electrode and earth ground. 7.8 The purpose of the dissimilar metals experiment was to evaluate the corrosion of electrodes caused by different metals (Zn, Cu) installed in close proximity to one another. Data was developed showing changes of resistance, mainly caused by dissimilar metals in an earth-coupled cell that could possibly produce a direct current flow and lead to accelerated corrosion. In most cases, the trendline showed a decrease in current over time, which indicates an increase of resistance between electrodes and earth due to corrosion caused by DC current from dissimilar metals located in an electrolyte (earth). 7.9 The results for the CDA® sponsored benign corrosion experiment showed that the 4/0 AWG and 500 KCM bare copper conductors backfilled with earth, Bentonite or GEM tm , received a CR of no worse than 0/1- slight superficial occurrences of corrosion, not over all surfaces. 7.10 To properly predict the performance of electrodes, earth resistivity values were obtained. Standardized testing methods such as those referenced in IEEE 81-1983 [4] were used to determine these values. Care was taken to ensure reliability and reproducibility of readings. Even though this was done there were a few abnormalities in the data. Nonetheless, the data for most sites show reliability through the term of the project, except for California which showed some variability. It is known that brackish water exists below the surface of the California site. Earth resistivity varied by location. Resistivity values for the National sites ranged from 517 to 24,014 ohm-cm. In the Las Vegas sites, the range was 30 ohm-cm to 31,597 ohm-cm. Data support the concept that a direct relationship exists between earth resistivity and electrode resistance. 7.11 Soil temperature measurements were taken at three different depths. Reliability was shown by the data in all sites since there was less fluctuation in soil temperature as depth increased. The purpose for the soil temperature measurements was to compare this information to earth resistivity. As was expected in most cases, the data showed an inverse relationship. This information could be used by installers of grounding electrode systems to predict performance during seasonal changes. 7.12 Project data indicated that moist soil does not necessarily ensure low earth resistivity or low electrode resistance values. All National sites were in different geographic locations, and, therefore, subjected to different local weather climates and soils content. Soil moisture values for the Virginia and New York sites indicate mostly wet soil for the majority of readings while average resistivity values were in the range of 9,817 and 20,424 ohm-cm for 10 ft. spacing respectively. Electrode resistance average values were in the range of 39.6 ohms in Virginia to 94.6 ohms in New York. 7.13 An independent corrosion analysis of some exhumed grounding electrodes was conducted. The analysis indicated that the majority of the grounding electrode 118 materials performed well over the approximately ten year exposure test except for the following: a) loss of zinc on galvanized steel rods resulted in excessive corrosion, b) copper-bonded steel ground rods showed minimal corrosion, however, the exposed steel at the unplated end of the ground rod was particularly vulnerable to corrosion although the average loss was minimal, c) some electrodes filled with salts and encased in Bentonite corroded at the end of the electrode and around the weep holes by contrast to others that displayed minimal corrosion, d) vertical electrodes in GEM tm displayed minimal corrosion in contrast to their horizontal counterparts, and e) there was generally insignificant corrosion of the three types of connectors, mechanical, compression, and exothermic, during the term of the study. 119 8. AREAS OF FURTHER STUDY 8.1 Comparison of Data to Theoretical Models - The data from this project could be used to compare the values obtained using mathematical modeling found in other published sources (IEEE and proprietary models). 8.2 Second Generations Study, DC and DM Re-examined - In the DC experiments, a declining trend in current was present in much of the data. It was apparent that after a period of time the current flow in many cases was reduced to zero, or near zero levels. This reduction in current flow is assumed to be caused by corrosion deposits at the electrode or connector, however, there may be other causes. One implication of this decreasing current could be that corrosion, meaning loss of electrode material to the soil due to ionic transport, will occur on rod or pipe grounding electrodes as a result of being subjected to prolonged low level DC currents in the grounding system, such as those produced by small household DC power supplies. Further work could study the corrosive effects of DC current by providing needed insight into the function and interaction of soils and electrodes relative to small DC levels. The DM experiments were passive (non-powered). The current for these experiments had a tendency to become lower as time progressed in similar fashion to the active DC experiments. Experiments could be designed to further examine the corrosive effects due to dissimilar metals and current flow in soil. Electrode resistance was typically not measured during DC or DM testing, and should be considered for future experimentation. 8.3 Controlled Soils: Temperature versus Earth Resistivity - During the course of the experiment, it was observed that the soils temperature affected the earth resistivity inversely. When soil temperature decreased it caused earth resistivity to increase. The degree of increase varied in all sites, possibly due to geographic location, varying moisture levels and soil chemistry. A further study could seek to eliminate some of the variables by controlling the moisture and soil chemistry while examining only the effect of temperature. 8.4 Controlled Soils: Moisture versus Earth Resistivity - Similar to and in conjunction with controlled temperature experiments, an evaluation of the effects of soil moisture could be designed to examine the primary effect of soil moisture on earth resistivity where the moisture levels are controlled and can be set to known variables. 8.5 Controlled Soils Chemistry – Laboratory experiments which control and vary temperature and moisture of soil could produce indicators for the performance of grounding electrodes. Varying the chemistry of soils may similarly provide insight into performance of electrodes, but in a broad scope the examination of soils chemistry may provide a greater insight into their corrosive effects on various types of electrodes and connectors. Further work could also seek to evaluate the soil chemistry, and its effects on earth resistivity. Experiments which require measuring the effects of corrosion require long-term exposure, and in many cases multiple samples, some of which could remain for the duration of the experiment and some which could be removed and examined during the course of the experiment. 120 8.6 Horizontal versus Vertical Electrodes – In this report comparisons were made of some vertical rod and pipe electrodes installed in vertical and horizontal orientations. Further work on orientation could re-examine the performance relationships of different orientations of electrodes in the study. 8.7 Data Analysis - The raw data could be further studied in a number of ways, including further comparisons, statistical confidence and uncertainty. 121 9. LIST OF FIGURES and TABLES Table 1. Sites Legend Table 2. Electrode Types A through K Table 3. Electrode Types L through V Table 4. Electrode e Types W through AE Table 5. Electrode Types 1A through 2C Figure 1. Las Vegas Pullbox , Type M, N and R Electrodes Figure 2. Types A, F and Q Electrodes Figure 3. Electrode Types E, H, L, K and P Figure 4. Electrode Type B Concrete Encased Electrode Figure 5. Electrode Types H, T and X Figure 6. Electrode Type V Figure 7. Electrode Type W Figure 8. Electrode Type Y Figure 9. Electrode Type Z Figure 10. Electrode Type AA Figure 11. Electrode Type AB Figure 12. Electrode Type AC Figure 13. Direct Current Experiment DC2 (DC1 Similar) Figure 14. Dissimilar Metals Experiment DM Figure 15. Electrodes CDA 1A, 1B, 2A, 2B, 3A and 3B Table 6. Percentage of Readings Exceeding 25 ohms Table 7. Percentage of Electrodes Exceeding 50 ohms Table 8. Percentage of Electrodes Exceeding 100 ohms Table 9. Percentage of Electrodes Exceeding 250 ohms Figure 16. Illinois Electrodes Resistance Figure 17.Texas Electrodes Resistance Figure 18. California Electrodes Resistance Figure 19. Virginia Electrodes Resistance Figure 20. New York Electrodes Resistance Figure 21.Balboa Test Site Graph Electrode Type G and H Table 10. Balboa Test Site Data for Electrode Type G and H Figure 22. Charleston Test Site Graph for Electrode Type G and H Table 11. Charleston Test Site Data for Electrode Type G and H Figure 23. Lone Mountain Test Site Graph for Electrode Type G and H Table 12. Lone Mountain Test Site Data for Electrode Type G and H Figure 24. Pecos Test Site Graph for Electrode Type G and H Table 13. Pecos Test Site Data for Electrode Type G and H Figure 25. Pawnee Test Site Graph for Electrode Type G and H Table 14. Pawnee Test Site Data for Electrode Type G and H Figure 26. Balboa Test Site Graph for Electrode Type I and J Table 15. Balboa Test Site Data for Electrode Type I and J Figure 27. Charleston Test Site Graph for Electrode Type I and J Table 16. Charleston Test Site Data for Electrode Type I and J Figure 28. Lone Mountain Test Site Graph for Electrode Type I and J Table 17. Lone Mountain Test Site Data for Electrode Type I and J Figure 29. Pecos Test Site Graph for Electrode Type I and J Table 18. Pecos Test Site Data for Electrode Type I and J Figure 30. Pawnee Test Site Graph for Electrode Type I and J Table 19. Pawnee Test Site Data for Electrode Type I and J 122 pg. 5 pg. 6 pg. 7 pg. 8 pg. 9 pg. 10 pg. 10 pg. 11 pg. 11 pg. 12 pg. 12 pg. 13 pg. 13 pg. 14 pg. 14 pg. 15 pg. 15 pg. 16 pg. 16 pg. 17 pg. 25 pg. 26 pg. 27 pg. 28 pg. 29 pg. 30 pg. 31 pg. 32 pg. 33 pg. 34 pg. 35 pg. 36 pg. 36 pg. 37 pg. 37 pg. 38 pg. 38 pg. 39 pg. 39 pg. 40 pg. 40 pg. 41 pg. 41 pg. 42 pg. 42 pg. 43 pg. 44 pg. 45 pg. 46 Figure 31. Illinois Test Site Graph for Electrode Type G and H Table 20.Illinois Test Site Data for Electrode Type G and H Figure 32. Texas Test Site Graph for Electrode Type G and H Table 21. Texas Test Site Data for Electrode Type G and H Figure 33. California Test Site Graph for Electrode Type G and H Table 22. California Test Site Data for Electrode Type G and H Figure 34. Virginia Test Site Graph for Electrode Type G and H Table 23. Virginia Test Site Data for Electrode Type G and H Figure 35. New York Test Site Graph for Electrode Type G and H Table 24. New York Test Site Data for Electrode Type G and H Table 25. Electrode Comparison Legend Figure 36. Type A Electrode Comparison Figure 37. Type B Electrode Comparison Figure 38. Type C Electrode Comparison Figure 39. Type D Electrode Comparison Figure 40. Type E Electrode Comparison Figure 41. Type F Electrode Comparison Figure 42. Type G Electrode Comparison Figure 43. Type H Electrode Comparison Figure 44. Type I Electrode Comparison Figure 45. Type J Electrode Comparison Figure 46. Type K Electrode Comparison National Sites Figure 47. Type K Electrode Comparison Las Vegas Sites Figure 48. Type L Electrode Comparison Figure 49. Type M Electrode Comparison Figure 50. Type N Electrode Comparison Figure 51. Type O Electrode Comparison Figure 52. Type P Electrode Comparison Figure 53. Type Q Electrode Comparison Figure 54. Type R Electrode Comparison Figure 55. Type S Electrode Comparison Figure 56. Type T Electrode Comparison Figure 57. Type V Electrode Comparison Figure 58. Type W Electrode Comparison Figure 59. Type X Electrode Comparison Figure 60. Type Y Electrode Comparison Figure 61. Type Z Electrode Comparison Figure 62. Illinois DC1 Experiment Figure 63. Illinois DC2 Experiment Figure 64. Texas DC1 Experiment Figure 65. Texas DC2 Experiment Figure 66. California DC1 Experiment Figure 67. California DC2 Experiment Figure 68. Virginia DC1 Experiment Figure 69. Virginia DC 2 Experiment Figure 70. New York DC1 Experiment Figure 71. New York DC2 Experiment Figure 72. Illinois Dissimilar Metals Experiments Figure 73. Texas Dissimilar Metals Experiments Figure 74. California Dissimilar Metals Experiments Figure 75. Virginia Dissimilar Metals Experiments 123 pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. pg. 47 48 49 50 51 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 87 88 89 90 91 92 93 94 95 Figure 76. New York Dissimilar Metals Experiments Table 26. Earth Resistivity for All Sites Table 27. Pawnee Resistance Compared to Earth Resistivity Table 28. Pecos Resistance Compared to Earth Resistivity Table 29. Lone Mountain Resistance Compared to Earth Resistivity Table 30. Charleston Resistance Compared to Earth Resistivity Table 31. Balboa Resistance Compared to Earth Resistivity Figure 77. Illinois Soil Temperature Figure 78. Texas Soil Temperature Figure 79. California Soil Temperature Figure 80. Virginia Soil Temperature Figure 81. New York Soils Temperature Figure 82. Illinois Earth Resistivity and Soils Temperature Figure 83. Texas Earth Resistivity and Soils Temperature Figure 84. Virginia Earth Resistivity and Soils Temperature Figure 85. New York Earth Resistivity and Soils Temperature Figure 86. Illinois Soil Moisture Figure 87. Texas Soil Moisture Figure 88. California Soil Moisture Figure 89.Virginia Soil Moisture Figure 90. New York Soil Moisture Table 32. Corrosion Ratings 124 pg. 96 pg. 97 pg. 98 pg. 98 pg. 99 pg. 99 pg. 99 pg.100 pg.101 pg.102 pg.103 pg.104 pg.105 pg.106 pg.107 pg.108 pg.109 pg.110 pg.111 pg.112 pg.113 pg.115 10. CITATIONS [1] D. A. Dini, “Some History of Residential Wiring Practices in the U.S.,” The Fire Protection Research Foundation Aged Electrical Systems Research Application Synposium, Chicago, Illinois, October 18-19, 2006, pp. 4-20. [2] T. Lindsey, T. D.W. Zipse, T Krob, “Grounding/earthing electrode studies. I “,1994 IEEE Industrial, and Commercial Power Systems Technical Conference, Conference Record, Papers Presented at the 1994 Annual Meeting, 1994 IEEE Irvine, California, 1-5 May 1994 pp: 163 - 174 [3] National Fire Protection Association, Inc. National Electrical Code. 2005 Edition. Quincy, MA. [4] IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System, IEEE Standard 81-1993. [5] IAEI. Soares Book on Grounding, Eighth Edition. Richardson TX: IAEI, 2001. 125 11. APPENDICES 11.1. 11.2. 11.3. 11.4. 11.5. 11.6. 11.7. Electrode Graphs Las Vegas Electrode Graphs National Corrosion Report Exhumation Reports Soils Reports National Construction Plans- Example Las Vegas Construction Plans 126