ACTIVE LINE CONDITIONER Actively limits Harmonic Distortion

advertisement
ACTIVE LINE
CONDITIONER
H5
Actively limits Harmonic Distortion
• ≤ 5% TDD - Meets IEEE-519 1992
• Improves True Power Factor - Improves energy efficiency
• System applied - MCC & Switchboard
• Touchscreen display and Modbus RTU
Line Reactors • Harmonic Filters • EMC Filters • dv/dt Filters • Sinewave Filter
ACTIVE LINE
CONDITIONER
H5
Typical Problems, Superior Solutions with H5 Filters
Power quality had degraded over time due to the increased
use of non-linear loads. The IEEE-519 standard for harmonic
distortion was developed to address this problem. Utilities are
now mandating that this standard be followed.
Harmonics and Power Quality
Variable frequency drives and other types of non-linear loads
take the incoming power from the utility and modify it for more
efficient use within a wide range of applications. The conversion
process creates current and voltage distortion.
Unfiltered Application
300
Amps
200
100
0
-100
-200
-300
0
5
10
15
20
25
30
35
40
Time (ms)
Typical Non-Linear Load Waveform
without Filtering
The H5 Active Line Conditioner
The H5 actively monitors the load current, reacting to changes in
load almost instantaneously, while returning true power factor to
near unity:
• Virtual real time correction of the non-linear current
• Synchronization of the current and voltage waveforms
• Always attempting to achieve unity power
• Never allowing for leading power factor
Injection Current
300
Amps
200
100
0
-100
-200
-300
0
5
10
15
20
25
30
35
40
Time (ms)
Resulting Line Current Waveform
300
200
Amps
If non-linear loads represent a significant portion of the entire
installed load, this distortion begins to cause problems
throughout the electrical system:
• Transformer and distribution equipment overheating
• Random breaker tripping
• Sensitive equipment may fail completely
• Poor power factor
100
0
-100
-200
-300
0
5
10
15
20
25
Time (ms)
30
35
40
Meeting IEEE-519 Recommendations on Harmonics
The H5 active filter provides a cost effective, efficient solution
allowing the user to meet IEEE-519 requirements. Using
harmonic analysis software, TCI can help customers meet IEEE519. Typical applications include:
• Wastewater treatment plants
• Commercial buildings
• Hospitals
H5 Filters v. Other Harmonic Solutions
The H5 active filter can be a better overall system solution when
compared to large, expensive 18 pulse VFD’s or multiple passive
drive-applied filtering:
• Save money
• Save space
• Reduce energy losses
Bus-Applied Configuration for MCC or Switchboard
This bus-applied filter design can be directly connected to the
power bus in standard MCC and Switchboard configurations. As
with other bus-applied designs, impedance must be installed on
the load side of the H5 filter.
Part Numbering System
ALC
100
A
01
Product Specifications
H 20 00
• Meets IEEE-519 1992
H5 Series
Panel Current
Voltage Rating
A = 480V
Enclosure
00 = Open, 01 = UL Type 1
Package Option
H = HMI Interface Module Package
Circuit Breaker
01 = 65kA, 20 = 100kA
Custom Options
0 = Custom
• TDD Reduction to 5% or better
• Power Factor Correction: ≤ 98% Lagging
(programmable)
• Response Time: < 8 ms to step load changes
• Harmonic Cancellation to the 50th harmonic
• Additional filters can be added in parallel to
increase correction capability (up to 10)
• Over Current Protection: Molded Case Circuit
Breaker
CT’s can be applied on either Line or Load side
(contact factory for CT placement)
• ANSI C62.16 surge protection
Typical
Non-Linear
Load(s)
Source
• Modular design
• Voltage Ratings: 480V, 3-phase, 60Hz
• Operating Temperature:
50 & 100 A: 50° C version available
50 & 100 A: -20° C (-4° F) to 40° C (104° F)
175 & 225 A: -12° C (10° F) to 40° C (104° F)
H5
• Storage Temperature:
50 & 100 A: -20° C (-4° F) to 60° C (140° F)
175 & 225 A: -12° C (10° F) to 60° C (140° F)
• Maximum Humidity: 95%, non-condensing
OPEN
Selection Chart for Open Units
Part Number
Corrective
RMS
Current
Height x Width x Depth
Wt. (Ibs.)
ALC50A00H
ALC100A00H
ALC175A00H
ALC225A00H
50
100
175
225
56.00 x 17.00 x 14.18
56.00 x 17.00 x 14.18
71.42 x 34.50 x 18.10
71.42 x 34.50 x 18.10
285
285
659
659
Dimensions (Inches)
• Elevation: 1,000 meters (3,300 feet) Derating
necessary above 1,000 meters
• Enclosure Options: Open Chassis; NEMA 1
• Agency Approvals: UL and cUL Listed to UL508
NEMA 1
Selection Chart for Enclosed Units
Part Number
Corrective
RMS
Current
Height x Width x Depth
Wt. (Ibs.)
ALC50A01H
ALC100A01H
ALC175A01H
ALC225A01H
50
100
175
225
56.00 x 17.57 x 16.40
56.00 x 17.57 x 16.40
84.00 x 39.00 x 24.00
84.00 x 39.00 x 24.00
372
372
794
794
Dimensions (Inches)
•Communication options include Modbus RTU over
RS485 and Ethernet/IP
H5 Typical Applications
• Oil and Gas
• Water/Waste Water
• HVAC Systems
• Pulp & Paper
• Data Centers
• Chemical
• Mining & Mineral
• Distribution Center
Additional Power Quality Solutions:
KDR Line Reactor
• Prevents nuisance tripping
• Protects the source by lowering current distortion created by the drive
HG7 Passive Harmonic Filter
Part Number: 25379 Version 1.6
• Helps meet IEEE-519
• Reduces harmonic distortion to less than 7% TDD at full load
• Improves power factor
KRF EMI/RFI Filter
© Copyright 2011
• Filter EMI/RFI noise caused by power switching devices
• Meet FCC regulation 15, subpart 3
• Prevents interference with automated lighting circuits, security cameras, and other critical
electronics
V1k Motor Protection Output Filter
• Protects the motor from voltage spikes due to dv/dt (reflective wave)
• Helps stop motor insulation breakdown
• Protects cable runs (up to 3,000 feet) and reduces motor heating, noise and vibration
KMG Motor Protection Output Filter
• Protects the motor by converting the PWM waveform into a near sinusoidal wave
• Prevents voltage overshoots that cause early degradation of insulation systems in
motors, transformers, and cables
• Extends motor life by reducing operating temperature
TCI, LLC
www.transcoil.com
7878 North 86th Street
Milwaukee, WI 53224
USA
Toll Free: 800-824-8282
P:
414-357-4480
F:
414-357-4484
Please contact us about
specific products and services.
Line Reactors • Harmonic Filters • EMC Filters • dv/dt Filters • Sinewave Filters