Installation and Maintenance Manual OM 1149-2 Group: WSHP Document PN: 910154675 Date: July 2014 MicroTech® IIISmartSource™ Unit Controller with I/O Expansion Module for Single and Two Stage Water Source Heat Pumps Models GS Models GT I/O Expansion Module MicroTech III SmartSource Unit Controller People and ideas you can trust.™ Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Fan Speed Selector Switch . . . . . . . . . . . . . . . . . . . . 20 MicroTech III Unit Controller . . . . . . . . . . . . . . . . . . . . 4 Fan Performance – Constant CFM Type ECM Motor 21 Control Boards Terminals and Connectors Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 I/O Expansion Module Faults and Fan Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 I/O Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . 5 Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 BACnet Communication Module . . . . . . . . . . . . . . . . 5 Waterside Economizer . . . . . . . . . . . . . . . . . . . . . . . 23 LonWorks Communication Module . . . . . . . . . . . . . 5 SmartSource Dehumidification . . . . . . . . . . . . . . . . . 23 MicroTech III Unit Controller & I/O Expansion Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Hot Gas Reheat Smart Dehumidification . . . . . . . . . 23 Replacing a MicroTech III Circuit Board: . . . . . . . . . . 7 Humidistat Controlled Dehumidification . . . . . . . . . . 25 Simplified Dehumidification . . . . . . . . . . . . . . . . . . . 24 Initial Power-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Pre start check list: . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 General Use and Information . . . . . . . . . . . . . . . . . . . 8 Dehumidification Only . . . . . . . . . . . . . . . . . . . . . . . 26 Appendix B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 MicroTech III Unit Controller with LonWorks® Communication Module . . . . . . . . . . . . . . . . . . . . . . 27 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Control Inputs (HP, LP, SLTS, COF, U, E, O) . . . . . . 10 Control Outputs {A and IV/PR (H8)} . . . . . . . . . . . . . 10 Unoccupied Operation – Stand Alone Thermostat Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 MicroTech III Controller with an Optional BACnet® Communication Module . . . . . . . . . . . . . . . . . . . . . . 28 Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . 29 115V, 1Ph – Model WGS, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) (See page 30 for Service & Disconnect Wiring) . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Thermostat Inputs (G, Y1, Y2, W1, and W2) . . . . . . . 11 Additional Fault Modes . . . . . . . . . . . . . . . . . . . . . . . 12 Brownout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 265V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) (See page 32 for Service & Disconnect Wiring) . . . . . . . . . . . . 31 Remote Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . 12 High / Low Pressure Faults (HP/LP) . . . . . . . . . . . . 13 Low Suction Temperature Fault Heating . . . . . . . . . 13 208-230V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, Desuperheater, 115V Loop Pumps & 20kW Electric Heat) (See page 34 for Service & Disconnect Wiring) . 33 Low Suction Temperature Fault Cooling . . . . . . . . . 13 Condensate Overflow . . . . . . . . . . . . . . . . . . . . . . . . 14 Fan Operation During Most Modes, Faults and Shutdowns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Faults and Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 208-230V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 5kW Electric Heat) (See page 36 for Service & Disconnect Wiring) . . . . . . . . . . . . . . . . . . 35 Troubleshooting the Water Source Heat Pump Unit 17 Microtech® III Unit Controller Interface to External Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 460V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 20kW Electric Heat) (See page 38 for Service & Disconnect Wiring) . . . . . . . . . . . . . . . . . . 37 Operation and Maintenance of I/O Expansion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Initial Power up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Thermostat Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Appendix C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Controller Comparison . . . . . . . . . . . . . . . . . . . . . . . 39 Electric Heat Controls . . . . . . . . . . . . . . . . . . . . . . . . 19 Supplemental Electric Heat Control . . . . . . . . . . . . . 19 Boilerless Heat Control . . . . . . . . . . . . . . . . . . . . . . 20 Compressor Heating Source Selection . . . . . . . . . . 20 Hydronic Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 OM 1149-2 2 www.DaikinApplied.com Introduction This installation and operation manual covers the MicroTech® III unit controller for Daikin G-Series Water Source Heat Pumps. For information on LonWorks® or BACnet® communication modules and other ancillary components, see: ■■ IM 952 - Multiple Unit Control Panel (MUCP) for use with MicroTech III Unit Controller and Mark IV Unit Controller. ■■ IM 955 - MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors. ■■ IM 956 - Temperature Sensors for Units with MicroTech III Unit Controller and LonWorks Communication Module. ■■ IM 927 - MicroTech III Water Source Heat Pump LonWorks Communication Module. ■■ IM 928 - MicroTech III Water Source Heat Pump Unit Controller BACnet MS/TP Communication Module. ■■ IM 933 - LonWorks Plug-In Software for use with MicroTech III Unit Controller - LonWorks Communication Module. www.DaikinApplied.com 3 OM 1149-2 MicroTech III Unit Controller Control Boards Terminals and Connectors Descriptions Table 1: MicroTech III Unit Controller Terminals & Descriptions H1 – 1 24 24 VAC Power Input H7 – 2 No Connection H1 – 2 C 24 VAC common H7 – 3 Red LED Output H2 – 1 SL1 Fan Main Required Output – Switched L1 H7 – 4 Green LED Output Blank Terminal H7 – 5 Yellow LED Output Fan Main Required Output – Neutral H7 – 6 H2 – 2 H2 – 3 N H3 – 1 HP1-1 Comp High Pressure Switch (HP1) Input Terminal 1 H8 – 1 H3 – 2 HP1-2 Comp High Pressure Switch (HP1) Input Terminal 2 H8 – 2 Isolation Valve/Pump Request Relay N/C H4 – 1 1 Discharge Air Temp Sensor – Common H8 – 3 24 VAC Common H4 – 2 Discharge Air Temp Sensor – Signal H9 – 1 H4 – 3 Leaving Water Temp Sensor – Common H9 – 2 H4 – 4 Leaving Water Temp Sensor – Signal TB1 – 1 1 Room Sensor – Status LED Output TB1 – 2 2 Room Sensor – Fan Mode & Unit Mode Switches H5 – 2 TB1 – 3 3 Room Sensor – Setpoint Adjust Potentiometer H5 – 3 TB1 – 4 4 Room Sensor – Room Temp Sensor & Tenant Override H5 – 4 TB1 – 5 5 Room Sensor – DC Signal Common H5 – 5 TB2 – 1 R 24 VAC H5 – 6 TB2 – 2 A Thermostat – Alarm Output TB2 – 3 W2 Thermostat – Heat Stage #2 (W2) Input H5 – 8 TB2 – 4 W1 Thermostat – Heat Stage #1 (W1) Input H5 – 9 TB2 – 5 Y2 Thermostat – Cool Stage #2 (Y2) Input H5 – 10 TB2 – 6 Y1 Thermostat – Cool Stage #1 (Y1) Input H5 – 11 TB2 – 7 G Thermostat – Fan Input H5 – 1 1 Connections to I/O Expansion Board H5 – 7 H5 – 12 Red-Green-Yellow LED Common 1 1 Isolation Valve/Pump Request Relay N/O Room Temp Sensor & Tenant Override – Signal Room Temp Sensor & Tenant Override – Common TB2 – 8 O Thermostat – Heat Stage #3 (W3) Input Condensate Overflow Signal Input TB2 – 9 C 24 VAC Common H6 – 2 Compressor Suction Temp Sensor (LT1) – Common TB3 – 1 E Emergency Shutdown Input H6 – 3 Compressor Suction Temp Sensor (LT1) – Signal TB3 – 2 U Unoccupied Input H6 – 4 Compressor Low Pressure Switch (LP1) – Source Voltage L1 – 1 L1 - 1 Line Voltage Terminal 1 H6 – 5 Compressor Low Pressure Switch (LP1) – Signal L1 – 2 L1 - 2 Line Voltage Terminal 2 H6 – 6 Reversing Valve – Common L1 – 3 L1 - 3 Line Voltage Terminal 3 H6 – 7 Reversing Valve – Output N1 N1 Neutral Terminal 1 No Connection N2 N2 Neutral Terminal 2 N3 N3 Neutral Terminal 3 H6 – 1 H7 – 1 1 1 OM 1149-2 4 www.DaikinApplied.com MicroTech III Unit Controller I/O Expansion Module BACnet Communication Module Table 2: I/O Expansion Module Connectors/Terminals Table 3: BACnet Communication Module Connectors/ Terminals H1 – 1 1 H1 – 2 P4 – 1 H1 – 3 P4 – 2 + 5 VDC H1 – 4 P4 – 3 SPI SELECT (SPI Select To Communications Board) H1 – 5 P4 – 4 SPI CLK (Master Clock) H1 – 6 P4 – 5 SPI RCV (MOSI) P4 – 6 SPI XMIT (MISO) H1 – 8 P4 – 7 SRDY OUT (SPI Ready To Baseboard) H1 – 9 P4 – 8 H1 – 10 P3 – 1 H1 – 11 P3 – 2 Network Signal – H1 – 12 P3 – 3 REF P3 – 4 Shield Connections to Main Board H1 – 7 H2 – 1 1 H2 – 2 24 VAC Common 1 Ext. 24 VAC Common In H3 – 3 HGR / Waterside Economizer Output – N/O H3 – 4 Ext. 24 VAC Common H3 – 5 ECM Fan Motor Variable Speed Signal Output H3 – 6 ECM Fan Motor Variable Speed Signal – Common 1 H4 – 2 H5 – 1 Network Signal + Table 4: LON Communication Module Connectors/ Terminals CN_SPI – 1 Entering Water Temp Sensor – Signal Entering Water Temp Sensor – Common 1 No Connection H5 – 2 No Connection H5 – 3 Red LED Output H5 – 4 Green LED Output H5 – 5 Yellow LED Output H5 – 6 Red-Green-Yellow LED Common Fan Speed Table Row Select – Signal H7 – 2 Fan Speed Table Row Select – Common H7 – 3 Thermostat – Heat Stage #4 (W4) Input – Signal H7 – 4 + 5 VDC CN_SPI – 3 SPI_SELECT1_0 (SPI Select To CommunicationsBoard) CN_SPI – 4 SPI_CLK_0 (Master Clock) CN_SPI – 5 SPI_RX_0 (MOSI) CN_SPI – 6 SPI_TX_0 (MISO) CN_SPI – 7 SREADY_0 (SPI Ready To Baseboard) TB1 – 1 H6 – 2 HP2-2 Comp High Capacity High Press Sw (HP2) Input Terminal 2 H7 – 1 CN_SPI GND CN_SPI – 2 CN_SPI – 8 H6 – 1 HP2-1 Comp High Capacity High Press Sw (HP2) Input Terminal 1 H8 – 1 No Connection P3 LonWorks Communication Module Ext. 24 VAC In H3 – 2 H4 – 1 GND No Connection H2 – 3 H3 – 1 Auxiliary Heat Stage #2 Output – N/O P4 No Connection TB1 Network Signal A TB1 – 2 Network Signal B TB1 – 3 REF Auxiliary 24 VAC Out 1 Compressor – High Capacity Output – N/O H8 – 2 24 VAC Common H8 – 3 No Connection H8 – 4 Auxiliary Heat Stage #1 / Hydronic Heat Output N/O (24 VAC) H8 – 5 24 VAC Common TB1 – 1 1 Humidistat Signal Input TB1 – 2 2 Thermostat - Heat Stage #4 (W4) Input – Signal www.DaikinApplied.com 5 OM 1149-2 MicroTech III Unit Controller MicroTech III Unit Controller & I/O Expansion Module Connections Figure 1: MicroTech III Unit Controller & I/O Expansion Module Connectors Descriptions OM 1149-2 6 www.DaikinApplied.com MicroTech III Unit Controller Initial Power-Up CAUTION Pre start check list: The MicroTech III circuit board incorporates static sensitive devices. A static charge from touching the device can damage the electronic components. To help prevent damage during service, use static discharge wrist straps.Static discharge wrist straps are grounded to the heat pump chassis through a 1 Mohm resistor. A random start delay time between 300 and 360 seconds is generated at power up. Figure 2: Location of Configuration Jumpers on the Base Board Controller Replacing a MicroTech III Circuit Board: 1. Connect wrist strap to unit. 2. Remove faulty board and place on static protected surface. 3. Remove replacement board from static protected bag. Note: Do not touch circuit board; hold by edges. 4. Holding board in grounded hand, install board in unit. 5. Insert faulty board in empty static bag for return. Table 5: I/O expansion module jumper settings Jumper Description JP1 Mode JP2 Fan operation JP3 (See Warning) Options Open for normal operation mode Shorted for service/test operation mode Freeze Protection JP4 Freeze Fault Protection JP5 Set point adjustment range only applies to network controls with a room temperature sensor JP6 Room control type JP7 Compressor heating source JP8 I/O expansion module Open for continuous fan operation, when not in unoccupied mode. Shorted for cycling fan operation Open for water freeze protection Shorted for systems with anti-freeze protection (15°F (9°C) Open for none Shorted to enable freeze fault protection based on Leaving Water Temperature (LWT) Open for adjustment range of -5.0° to +5.0° F Shorted for 55° to 95° F adjustment range Open for thermostatic room control Shorted for room temperature sensor control, MicroTech III only. Open to enable compressor heating Shorted to disable compressor heating Open when I/O expansion module is not needed Shorted when I/O expansion module is required WARNING Proper antifreeze/water solution is required to minimize the potential of fluid freeze-up. Jumper JP3 is factory set for water freeze protection with the jumper open. Operation at fluid temperatures below 32°F with anti-freeze protection requires JP3 to be field configured for the jumper closed. If unit is employing a fresh water system (no anti-freeze protection), it is extremely important that JP3 jumper setting remains in the open position (factory default setting) in order to shut down the unit at the appropriate water temperature to protect your heat pump from freezing. Failure to do so can result in unit damage and fluid leaks.” www.DaikinApplied.com 7 OM 1149-2 MicroTech III Unit Controller General Use and Information The Microtech III SmartSource unit controller is a water source heat pump control platform used to control the heat pump in all modes of operation, including variable speed fans, two stage compressors, loop pumps, economizers, reversing valves, and all components used to control conditioned space temperature and humidity. By adding communications cards, (LonWorks or BACnet) network integration is possible. The controller can be used with thermostat control or wall sensor control. All MicroTech III unit controller inputs must be operated by dry contacts powered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate MicroTech III unit controller inputs. No outside power sources may be used to operate MicroTech III. All units must be properly grounded per local code requirements. See the Installation and Maintenance bulletin specific to your Water Source Heat Pump. Occupied Operation The board will be in occupied mode if the unoccupied terminal (U) is not shorted to ground. Board LED Status – Occupied Yellow Green Red Off On Off Operating Modes ■■ Start-up – The unit will not operate until all the inputs and safety controls are checked for normal conditions. ■■ Cooling mode – On an initial call for cooling, the fan will energize at its “fan only” setting, the pump request will engergize, the 45 second proof of flow timer will start, compressor minimum off, and random startup timers are expired, the compressor and fan will start at the stage 1 cooling settings. If room setpoint conditions are not satisfied, the fan will operate at the stage 2 cooling settings. When the room setpoint conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off once room setpoint conditions are satisfied. ■■ Dehumidification modes – There are four dehumidification modes of operation; 1. Smart Dehumidification with Hot Gas Reheat 2. Simplified Dehumidification 3. Humidistat Controlled Dehumidification 4. Dehumidification Only See "SmartSource Dehumidification" on page 23 for details. OM 1149-2 ■■ Smart Dehumidification – Uses hot gas reheat, a humidistat, a 2-stage thermostat and air flow management for precise humidity control. When the cooling and heating temperature setpoint is satisfied and there is a call for dehumidification, maximum dehumidification is initiated by energizing the fan at its “fan only” setting, energizing the pump request, starting the 45 second proof-of-flow timer, energizing the hot gas reheat solenoid valve, energizing the compressor at maximum cooling, and energizing the fan at the dehumidification setting. When the room humidity conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off, once room humidity conditions are satisfied. ■■ Simplified Dehumidification – Uses a 3-stage thermostat and air flow management to optimize unit capacity and fan speed for maximum latent capacity while decreasing room humidity levels. On a call for cooling, the fan will energize at its “fan only” setting, the pump request will energize, the 45 second flow timer will start, after the flow, compressor minimum off, and random startup timers are expired, the compressor will start at stage 1 cooling and the fan will energize at its dehumidification setting. If the room setpoint temperature is still not satisfied, the fan will be energized at the stage 1 cooling settings. If the room setpoint temperature is still not satisfied, the compressor and fan will operate at the stage 2 cooling settings. When the room temperature conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off, once room setpoint conditions are satisfied. ■■ Humidistat Controlled Dehumidification – Uses a humidistat and 2-stage thermostat to control room humidity levels. On a call for dehumidification, the fan will energize at its “fan only” setting, the pump request will energize, the 45 second flow timer will start, after the flow, compressor minimum off, and random startup timers are expired, the compressor will start at stage 1 cooling and the fan will energize at its dehumidification setting. If the room setpoint temperature is not satisfied, the fan will be energized at the stage 1 cooling settings. If the room setpoint temperature is still not satisfied, the compressor and fan will operate at the stage 2 cooling settings. When the room temperature and humidity conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off once room setpoint conditions are satisfied. 8 www.DaikinApplied.com MicroTech III Unit Controller ■■ Dehumidification Only – Uses a humidistat in the cooling only mode. On a call for dehumidification, the fan will energize at its “fan only” setting, the pump request will energize, the 45 second flow timer will start, after the flow, compressor minimum off, and random startup timers are expired, the compressor will start at stage 1 cooling and the fan will energize at its dehumidification setting. Room temperature conditions are not monitored or maintained. The unit only responds to a call for dehumidification. When the room humidity conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off once room setpoint conditions are satisfied. and the fan will operate at its electric heat setting. For units equipped with 2 stages of electric heat, if room setpoint conditions are still not satisfied, the second stage of electric heat will be energized and the fan will continue to operate at its electric heat setting. When the room setpoint conditions are satisfied, electric heat will be de-energized allowing the compressor to remain on if necessary to maintain room setpoint conditions. The fan will operate according to its “fan only” setting when enabled, for continuous fan operation. If fan cycling is enabled, the fan will turn off once room setpoint conditions are satisfied. ■■ Primary Electric Heat mode – On an initial call for heating, stage 1 electric heat will be energized and the fan will start at its electric heat setting. For units equipped with 2 stages of electric heat, if room setpoint conditions are not satisfied, the second stage of electric heat will be energized and the fan will continue to operate at its electric heat setting. When the room setpoint conditions are satisfied, electric heat will be de-energized and the fan will continue to operate at its “fan only” setting when enabled, for continuous fan operation. If fan cycling is enabled, the fan will turn off after 30 seconds once room setpoint conditions are satisfied. ■■ Heating mode – On an initial call for heating, the fan will energize at its "fan only" setting, the pump request will energize, the 45 second flow timer will start, after the flow, compressor minimum off, and random startup timers are expired, the compressor and fan will start at stage 1 heating settings; the reversing valve shall energize 5 seconds after the compressor turns on. If room setpoint conditions are not satisfied, the fan will operate at stage 2 heating settings. When the room setpoint conditions are satisfied, the compressor will shut off and the fan will operate according to its “fan only” setting when enabled for continuous fan operation. If fan cycling is enabled, the fan will turn off, once room setpoint conditions are satisfied. ■■ Emergency Electric Heat mode – A 24v control signal from the thermostat will initiate a call for stage 1 or stage 2 electric heat. The compressor will not operate and the fan will start at its electric heat setting. ■■ Hydronic Heat Mode – The hydronic heating option provides control of a two position valve connected to a hot water coil when loop water temperature is warm enough for hydronic heating. Loop water temperature is sensed by a factory installed entering water temperature sensor located on the inlet water line. Hydronic heat circuit shall be independent and substitute the use of the compressor driven refrigeration circuit. Hydronic heating set point allowed range is 70°F to 158°F, with a 70°F default value. ■■ Boilerless Electric Heat mode – When the entering water temperature is below setpoint, the compressor will not be allowed to operate. On an initial call for heating, stage 1 electric heat will be energized and the fan will start at its electric heat setting. For units equipped with 2 stages of electric heat, if room setpoint conditions are not satisfied, the second stage of electric heat will be energized and the fan will continue to operate at its electric heat setting. When the room setpoint conditions are satisfied, electric heat will be de-energized and the fan will continue to operate at its “fan only” setting when enabled, for continuous fan operation. If fan cycling is enabled, the fan will turn off after 30 seconds once room setpoint conditions are satisfied. ■■ Occupied Mode – The MicroTech III SmartSource unit controller will manage occupied and unoccupied modes of operation. The occupancy mode can be established by a BACnet or LonWorks communication signal, from a room sensor equipped with “Occupied/Unoccupied” mode functions, or a thermostat equipped with an “Occupied/Unoccupied” mode switch. When in the occupied mode, the unit will be controlled to its occupied setpoint conditions. The occupancy state will be displayed on sensors equipped with “Occupied/Unoccupied” mode functions and annunciation capabilities. ■■ Supplemental Electric Heat mode – On an initial call for heating, the fan will energize at its “fan only” setting, the pump request will energize, the 45 second flow timer will start. After the flow, compressor minimum off, and random startup timers are expired, the compressor and fan will start at stage 1 heating settings; the reversing valve shall energize 5 seconds after the compressor turns on. If room setpoint conditions are not satisfied, the fan will operate at stage 2 heating settings. If room setpoint conditions are still not satisfied, the compressor will continue to operate and stage 1 electric heat will be energized www.DaikinApplied.com ■■ Unoccupied Mode – When operating in the unoccupied mode, the unit will be controlled to its unoccupied setpoint conditions and the fan will cycle according to a call for cooling, dehumidification or heating. A simple “grounded” signal between 9 OM 1149-2 MicroTech III Unit Controller ■■ terminals U and C on the MicroTech III SmartSource unit controller will place the unit into the unoccupied mode for night setback operation. The occupancy state will be displayed on sensors equipped with “Occupied/Unoccupied” mode functions and annunciation capabilities. ■■ Override Mode – A momentary (4 to 9 seconds) press of the “Override” button on the thermostat or room sensor during the unoccupied mode will cause the unit to operate in the occupied mode for two hours, for after-hours heating, cooling or dehumidification. “OVERRIDE” will be displayed on sensors equipped with override button and annunciation capabilities. ■■ “Energy Save” Bypass Mode – BACnet or LonWorks units can receive a signal from the Building Automation System (BAS) to initiate the energy savings mode. This mode is typically initiated by the BAS with smart grid technologies to save energy. The savings is driven by reducing peak electrical demand for the building. Once initiated, the MicroTech III SmartSource unit controller will reset its effective setpoint to minimize the stage of compressor operation. “E-SAVE” will be displayed on sensors equipped with bypass mode annunciation capabilities. ■■ Motorized Water Valve or Pump Start – When there is a call for cooling, dehumidification or heating, the MicroTech III SmartSource unit controller will energize its IV/PR (H8) terminal to open the motorized water valve or start the loop pump 45 seconds prior to starting the compressor. The IV/ PR (H8) terminal may be “daisy chained” between 200 units. Control Inputs (HP, LP, SLTS, COF, U, E, O) The control inputs are High Pressure (HP), Low Pressure (LP), Suction Line Temperature Sensor (SLTS), Condensate Overflow (COF), Unoccupied (U), and Remote Shutdown (E). The control inputs are in normal states during occupied mode. The state of each control in occupied mode during normal operation is as follows: ■■ High Pressure (HP): Normally closed switch that opens on a high refrigerant pressure condition. Control will generate a high pressure fault and disables the compressor output when the switch is open. ■■ Low Pressure (LP): Normally closed switch that opens on a low refrigerant pressure condition. Control will generate a low pressure fault when the switch is open. Suction Line Temperature Sensor (SLTS): temperature sensor on the suction line. ■■ Condensate Overflow (COF): senses condensate level in condensate pan. Control will generate a fault when condensate level is too high. ■■ Remote Shutdown (E): Grounding this terminal forces the control to shutdown the unit. Control Outputs {A and IV/PR (H8)} The control outputs are Alarm Fault (A) and Isolation Valve / Pump Request {IV/PR (H8)}. The operation of the control outputs during occupied mode is as follows: ■■ The thermostat alarm output will be energized when there are fault conditions presently active. Without any fault conditions active, the alarm output shall be de-energized. ■■ Isolation Valve / Pump Request {IV/PR (H8)}: is selectable to be energized when the compressor is off (normally closed), or when the compressor is on (normally open), by moving the wire lead to the appropriate terminal. Figure 3: H8 Terminals on MicroTech III Board ■■ Reversing Valve: 24V signal that is energized upon a call for heat mode. ■■ Compressor Relay: Line or low voltage output used to control compressor. (On/Off) Fan Operation The G terminal controls continuous fan operation. The fan runs continuously when the G terminal is energized. When the G terminal is de-energized, the fan cycles with the compressor. Cooling Mode The Y1 terminal controls the Cooling Mode of operation. When the Y1 terminal is energized (24VAC), the following occurs: 1. The fan energizes. 2. The IV/PR (H8) control output de-energizes or energizes depending on the H8 terminal wiring (refer to "MicroTech III Unit Controller Terminals & Descriptions" on page 4 & "MicroTech III Unit Controller & I/O Expansion Module Connectors Descriptions" on page 6). 3. The compressor energizes after 45 seconds. 4. The reversing valve de-energizes 5 seconds after the compressor turns on. When the Y1 terminal is de-energized, the following occurs: 1. The compressor de-energizes. ■■ Unoccupied (U): Grounding this terminal puts the control into unoccupied mode. OM 1149-2 10www.DaikinApplied.com MicroTech III Unit Controller 2. The IV/PR (H8) control output energizes or deenergizes depending on the H8 terminal wiring (refer to "MicroTech III Unit Controller Terminals & Descriptions" on page 4 & "MicroTech III Unit Controller & I/O Expansion Module Connectors Descriptions" on page 6). 3. The fan de-energizes, unless the G terminal is energized (24VAC). Note: To prevent compressor cycling and all compressors from starting up together after loss of power, the required minimum on/off time default is 300 seconds. This may cause the compressor time delay to be longer than indicated above. Heating Mode The W1 terminal controls the occupied Heating Mode of operation. When the W1 terminal is energized, the following occurs: 1. The fan energizes. 2. The IV/PR (H8) control output de-energizes or energizes depending on the H8 terminal wiring (refer to "MicroTech III Unit Controller Terminals & Descriptions" on page 4 & "MicroTech III Unit Controller & I/O Expansion Module Connectors Descriptions" on page 6). Note: To prevent compressor cycling, the required minimum on/off time default is 300 seconds. This may cause the compressor time delay to be longer than indicated above. Unoccupied Operation – Stand Alone Thermostat Control The board will be in unoccupied mode if the unoccupied terminal (U) is grounded. Board LED Status – Unoccupied Yellow Green Red On On Off Thermostat Inputs (G, Y1, Y2, W1, and W2) The only thermostat inputs used during unoccupied operation are Y2 and W2, which when energized will activate Cooling Mode or Heating Mode respectively. Inputs G, Y1 and W1 have no effect during unoccupied mode. Figure 4: Terminal "U" - Grounded for Unoccupied 3. The compressor energizes after 45 seconds. 4. The reversing valve energizes 5 seconds after the compressor turns on. When the W1 terminal is de-energized, the following occurs: 1. The compressor de-energizes. 2. The IV/PR (H8) control output energizes or deenergizes depending on H8 terminal wiring (refer to "MicroTech III Unit Controller Terminals & Descriptions" on page 4 & "MicroTech III Unit Controller & I/O Expansion Module Connectors Descriptions" on page 6). 3. The fan de-energizes, unless the G terminal is energized. www.DaikinApplied.com11 OM 1149-2 MicroTech III Unit Controller Additional Fault Modes Figure 5: Terminal "E" - Grounded for Remote Shutdown Brownout Board LED Status – Brownout Yellow Green Red Off Flash Off Brownout condition is provided to protect the water source heat pump’s motor electrical damage due to low voltage conditions. The MicroTech III unit controller is designed to monitor the 24VAC power supply to the board. If the line voltage supplied to the water source heat pump drops, the 24VAC supply to the control board will also drop. When the line voltage supplied to the unit drops below approximately 80% of the unit nameplate rated value, the controller goes into brownout condition. The controller remains in brownout condition until line voltage returns to approximately 90% of the unit nameplate value. When in brownout condition, thermostat and control inputs have no affect upon unit operation. Remote shutdown and brownout conditions have the same level of priority. See Table 8 on page 16. When the unit is in brownout condition the following occurs: 1. The compressor de-energizes. 2. The fan de-energizes. 3. Fault terminal (A) energizes (fault). A to R will be used to indicate an alarm signal. When in remote shutdown (E terminal grounded), thermostat and control inputs have no affect upon unit operation. No faults or modes have higher priority than remote shutdown. Remote shutdown and brownout condition have the same level of priority. See Table 8 on page 16. When the unit is in remote shutdown mode, the following occurs: 1. The compressor de-energizes (if enabled). 2. The fan de-energizes (if enabled). 3. Fault terminal (A) will remain de-energizes because emergency shutdown is a "mode". A to C will be used to indicate normal operation. When the E terminal is no longer grounded the unit will automatically return to normal operation. Note: The remote shutdown input (E) will suspend unit operation. Disconnect power when servicing the unit/controller. When the line voltage supplied to the unit returns to acceptable levels (~90% of nameplate) the controller returns to the current mode. Remote Shutdown Board LED Status – Remote Shutdown Yellow Green Red Off Flash Off When the E terminal is grounded, the MicroTech III unit controller enters remote shutdown mode. Remote shutdown is provided so that when properly connected to a building automation system, remote switch, etc., the E terminal can be used to shut down the water source heat pump. OM 1149-2 12www.DaikinApplied.com MicroTech III Unit Controller High / Low Pressure Faults (HP/LP) Normally closed high and low refrigerant pressure switches help protect the water source heat pump from excessively high or low refrigerant pressures. The MicroTech III unit controller monitors these switches individually. If the compressor is running and the HP circuit is open, the controller enters a pressure fault mode. If the LP circuit is open after a time delay (default of 30 seconds, adjustable if a communication module is present) the controller enters a low pressure fault mode. Board LED Status – High/Low Pressure Faults Pressure Yellow Green Red HP Off Off Flash LP Off Off Solid See Table 8 on page 16. When the unit is in high or low pressure fault modes the following occurs: 1. The compressor de-energizes. 2. The IV/PR(H8) output will change state. (On to Off / Off to On). 3. The fan de-energizes. 4. The fault terminal (A) energizes (fault). A to R will be used to indicate an alarm signal. High Pressure/Low Pressure Reset After the HP circuit is closed, the unit does not return to normal operation until the alarm is manually reset. The unit is locked out in this manner until the unit can be serviced. The alarm is reset by a short interruption of unit power, by holding down the tenant override button for more than 10 seconds, or via the Building Automation System (BAS). Low Suction Temperature Fault Heating 1. The control will attempt to recover from a low suction temperature condition by defrosting water heat exchanger (coaxial coil). 2. See the Defrost Process below for details. Low Suction Temperature Fault Cooling 1. When the suction line temperature falls below 28° F disable the compressor output only. 2. The fan will continue to run drawing warmer air over the air heat exchanger. 3. When the suction line temperature increases by Low Temp Protect Diff (the default is 8° F) degrees. 4. The compressor is available for cooling if the Compressor Minimum Off timer has expired. 5. Mark the occurrence of the fault. Board LED Status – Low Suction Line Temperature Fault Yellow Green Red Flash Off Off Defrost Sequence of Operation: 1. Immediately turn off the compressor if operating in the cooling or dehumidification modes. 2. The reversing valve output is de-activated, placing the reversing valve in the cooling mode and moving warm refrigerant to the coax coil. 3. Fan speed is not changed, however “Heat Stage #1” speed is used if the fan is presently off. 4. If the compressor was on at the beginning of the defrost process, then start the 60 second fixed defrost timer. 5. Wait for the defrost timer to expire. 6. If the alarm condition has cleared: • Return to normal operation. 7. If the alarm condition remains active: • Compressor High Capacity is turned off • Compressor is immediately turned off, ignoring the Compressor Minimum ON timer • Compressor is disabled for heating and cooling • Electric heating can be used if it is available • Fan and pump remain available for operation www.DaikinApplied.com13 OM 1149-2 MicroTech III Unit Controller Heating Mode When the suction line temperature falls below 28°F on standard equipment (6.5°F on Geothermal) the low temperature fault generates the following: • The reversing valve de-energizes. The compressor and fan continue to operate in cooling mode for 60 seconds, which results in a defrost mode. This defrosts any ice that may have accumulated in the water-to-refrigerant coil, because of a lack of condenser water flow in heat mode. • In heat mode the low temperature fault is subject to Intelligent Reset. • The fault terminal (A) energizes while the unit is in defrost mode. It will stay energized until the temperature recovers to 36°F for standard equipment (14.5°F for geothermal). A to R will be used to indicate an alarm signal. The previous operation of heating or cooling determines how the low suction temp alarm must be reset. • The fan and pump remain available for operation. Cooling Mode When the suction line temperature falls below 28°F standard equipment (28°F geothermal) in cool mode the: • Compressor de-energizes. • The fan and pump remain available for operation. • Alarm output energizes. • When the suction line temperature recovers to 36°F standard equipment (14.5°F on geothermal) the low temperature fault continues and the compressor will be locked out. Fan Only Mode When the suction line temperature falls below 28°F standard equipment (28°F geothermal) in cool mode the: • The fan and pump remain available for operation. • Alarm output energizes. The previous operation of heating or cooling determines how the low suction temp alarm must be reset. OM 1149-2 Condensate Overflow Board LED Status – Condensate Overflow Yellow Green Red On Off Off The MicroTech III unit controller's condensate sensor is designed to detect excessively high condensate water levels in the drain pan. When high condensate water levels are detected during cooling or dehumidification modes, the controller enters into condensate fault mode. The fan operates at fan only speed during the condensate overflow fault mode. Some faults and modes have higher priority than condensate overflow mode. See Table 8 on page 16. When the unit senses a condensate overflow fault while in cooling mode the following occurs: 1. The compressor de-energizes. 2. The fault terminal (A) energizes (fault). A to R will be used to indicate an alarm signal. When condensate levels return to normal, the controller will automatically return to normal operation. Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset some lockouts generated by highpressure and/or low-temperature faults. When the MicroTech III unit controller is locked out due to one of these faults, and the cause of the fault condition has been cleared, energizing the O-terminal for 11 seconds or more forces the MicroTech III unit controller to clear the lockout. Cycling unit power also clears a lockout if the conditions causing the fault have been alleviated. Intelligent Reset (See "Fault Recovery and Reset" on page 15) The Intelligent Reset feature helps to minimize nuisance trips of automatic lockouts caused by low-temperature faults. This feature clears faults the first two times they occur within a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours. 14www.DaikinApplied.com MicroTech III Unit Controller Table 6: Fault Recovery and Reset Auto Recovery Tenant Override Button Reset Network Reset IO Expansion Communication Fail Yes No No Invalid Jumper Configuration No No No Low Voltage Brownout Yes No Yes All Sensor Failures No No Yes Compressor High Pressure No Yes Yes Compressor Low Pressure No Yes Yes Compressor Low Suction Temp or Freeze Fault Detect (Heat & Cool) Yes1 Yes Yes Compressor Low Suction Temp or Freeze Fault Detect (Dehumidification) Yes Yes Yes Condensate Overflow Yes No Yes Low Entering Water Temp. Yes No No EEPROM Corrupted No No No Waterside Economizer Low Temp. Cutout Yes No No Fault Description Note: 1 Indicates auto recover is subject to intelligent alarm reset. Alarm auto recovers on first two occurrences, locked out on third within 24 hour period. See “Intelligent Alarm Resetting” section on the previous page for further details. Tenant Override Note: It is recommended that the "All MicroTech III unit controller inputs must be operated by dry contacts powered by the control board’s power terminals. No solid state devices (Triacs) may be used to operate MicroTech III unit controller inputs. No outside power sources may be used to operate MicroTech III. All units must be properly grounded per local code requirements. See the Installation and Maintenance bulletin specific to your Water Source Heat Pump." and "Unoccupied Operation – Stand Alone Thermostat Control" on page 11 section should be reviewed prior to this section. www.DaikinApplied.com15 The MicroTech III unit controller enters tenant override mode when the Tenant Override (TO) terminal is grounded for 4-10 seconds during a period when the Water Source Heat Pump is in unoccupied mode. Tenant override allows a tenant, returning to the controlled space after the unit has been placed in unoccupied mode, to activate the tenant override input and place the unit into occupied mode. Any remote button or switch with momentary dry contacts can be used for this purpose. During the 2-hour tenant override period all the thermostat inputs will be used, (see "Occupied Operation" on page 8) for unit operation. If the U terminal is still grounded after the 2-hour time limit, the unit will return to unoccupied mode. Refer to "Unoccupied Operation – Stand Alone Thermostat Control" on page 11. OM 1149-2 MicroTech III Unit Controller Fan Operation During Most Modes, Faults and Shutdowns The MicroTech III unit controller allows fan operation during most modes, faults and shutdowns to facilitate maximum space comfort and control. However, the fan does not operate during brownout or emergency shutdown condition. During most modes, faults, or shutdowns the fan will operate normally: Operation with the High Speed Jumper • The MicroTech III unit controller includes a highspeed jumper terminal labeled JP1 to speed system check out and trouble-shooting. See Figure 2 on page 7 for JP1 location. Table 7: Room Sensor Status LED LED On Time (Sec) LED Off Time (Sec) Operating Mode 0.5 0.5 Alarm Condition or Network “Wink” Operation Active 0.0 Continually Bypass Mode is Active 0.5 5.5 Unoccupied Mode 5.5 0.5 Standby Mode Continually 0.0 Occupied Mode Faults and Modes Table 8: Priority Level of Faults and Modes Priority Level Mode or Fault 1 I/O Expansion Communication Fail 2 Invalid Configuration 3 Low Voltage Brownout Note: This jumper is intended for factory unit testing and should only be used by trained service technicians as several timing functions are reduced to speed system check out. • Disconnect power to the unit when installing or removing the high-speed jumper. 4 Emergency Shutdown Mode 5 Compressor High Pressure • The high speed jumper should only be used for a short period of time for testing of the unit’s operation by a trained service technician. The jumper must be removed for normal unit operation. 10 Room Temp Sensor Fail 11 Entering Water Temp Sensor Fail 12 Leaving Water Temp Sensor Fail 13 Condensate Overflow • If the jumper is left on after system check out, the unit may be damaged. 14 Low Entering Water Temp 15 Serial EEPROM Corrupted 16 Waterside Economizer Low Temp Cutout 17 Service Test Mode 6 Compressor Low Pressure 7 Compressor Suction Temp Sensor Fail 8 Freeze Fault 9 Compressor Low Suction Temp Table 9: MicroTech III Unit Controller Status LED's Description Type Yellow Green Red IO Expansion Communication Fail Invalid Jumper Configuration Fault ON Flash Flash Fault Flash Flash OFF Low Voltage Brownout Fault OFF Flash OFF Emergency Shutdown Mode OFF Flash OFF Compressor High Pressure Fault OFF OFF Flash Compressor Low Pressure Fault OFF OFF ON Compressor Suction Temp Sensor Fail Fault Flash Flash ON Freeze Fault Detect Fault Flash OFF Flash Compressor Low Suction Temp Fault Flash OFF OFF Room Temp Sensor Fail (Room Sensor Control Only) Fault Flash Flash ON Leaving Water Temp Sensor Fail (Freeze Fault Protect) Fault Flash Flash ON Condensate Overflow (Cooling & Dehumidification Modes) Fault ON OFF OFF Serial EEPROM Corrupted Fault ON ON ON Waterside Economizer Low Temp Cutout (WSE Control & Call for Cooling) Mode Flash ON Flash Service Test Mode Enabled Mode Flash Flash Flash Unoccupied Mode Mode ON ON OFF Occupied, Bypass, Standby, or Tenant Override Modes Mode OFF ON OFF OM 1149-2 16www.DaikinApplied.com MicroTech III Unit Controller Troubleshooting the Water Source Heat Pump Unit Figure 6: Troubleshooting Guide - Unit Operation Low voltage, check power supply voltage Fuse may be blown, circuit breaker is open Wire may be loose or broken. Replace or tighten wires Check wiring - loose or broken and check for faulty connection Check relays and contacts, also capacitor and wiring Check high pressure switch, low pressure switch and low temperature switch to see if unit is cycling on the safety Unit control, check thermostat for correct wiring or faulty thermostat Check capacitor Neither fan, nor compressor runs and all LED lights are off Compressor runs in short cycle Fan operates, compressor does not Unit Check wiring - loose or broken and check for bad connection High or Low pressure lockout A. Cool mode, check water flow B. Heating mode, check air flow C. Check reversing valve for proper valve position Check compressor overload make sure it is closed Check to see if the reversing valve is not hung up and is operating correctly Check compressor to ground, or for internal short to ground Check condensate overflow switch in cool mode of operation Compressor winding may be open. Check continuity with ohm meter Check thermostat for proper location Compressor attempts to start but does not Insufficient cooling or heating Check compressor wiring for defective wiring or loose connection Check for defective compressor internal windings with ohm meter Check thermostat for improper location Check for faulty compressor capacitor Check blower assembly for dirt or faulty fan motor capacity Check for lock rotor amp draw Check for low refrigerant charge Check for proper air flow filter could be dirty Check amp draw on blower assembly Check for proper water flow and delta T (°F) www.DaikinApplied.com17 OM 1149-2 MicroTech III Unit Controller Microtech® III Unit Controller Interface to External Equipment • • • • The MicroTech III unit controller’s thermostat input terminals may be directly interfaced with any standard or night setback thermostat that uses mechanical dry contacts. Power cannot be supplied from the water source heat pump for electronic thermostats that require a separate power supply for their internal operation except those provided by Daikin. Only thermostats offered by Daikin are proven to operate properly with the MicroTech III unit controller. Daikin makes no guarantees about any other thermostat or control device interfaced by the end user with the MicroTech III unit controller. Appendix A Operation and Maintenance of I/O Expansion Module Introduction Care must be used to isolate all external power sources from the MicroTech III unit controller to prevent ground loops and other unpredictable electrical problems. Only dry mechanical contacts should be used to operate or interface with the MicroTech III unit controller’s thermostat and or control inputs. Use mechanical relays to isolate two power systems when external equipment with its own power supply is used to interface with or control the MicroTech III unit controller’s thermostat and or control inputs. For example, if you have a Building Automation System (BAS), controller, etc., and you wish to use a digital output from the building automation system or controller that is internally powered, then you must use an additional mechanical relay (not supplied by Daikin) to isolate the MicroTech III unit controller. The I/O Communication Module is an expansion of the main board and provides extra functionality to the MicroTech III control system. • The MicroTech III unit controller in combination with the I/O Expansion Module will be the standard control system for SmartSource Water Source Heat Pumps. Due to the nature of triacs and other solid state devices, triacs cannot be directly used to operate the MicroTech III’s unit controller’s thermostat or control inputs. To interface triacs or other solid state switching devices to the MicroTech III unit controller inputs, separate them from the board using mechanical relays. To do this, use the triac or solid state device to drive a mechanical relay (not supplied by Daikin), then use the mechanical relay’s dry contacts to drive the desired MicroTech III unit controller input. • Boilerless & Supplemental Auxiliary Heating Options The MicroTech III unit controller’s valve or pump request terminal {IV/PR (H8)} is an output signal to external devices to allow water flow as required by the heat pump. The IV/PR (H8) terminal follows compressor operation inversely if connected to the normally open terminal and simultaneously when connected to the normally closed terminal. The IV/PR (H8) terminal can be used as a signal to an external pump or valve to enable flow to the unit. The compressor start is delayed for 30 seconds after the IV/PR (H8) output is energized. Adding an I/O Expansion Module (with an interconnect cable) to the main controller allows: • Compressor High Capacity On/Off Control • Variable Speed Fan Control • Water Side Economizer Control • Active Hot Gas/Reheat (HGR), or Low Capacity Dehumidification Options • The fourth thermostat Heating Stage (W4) Input • Hydronic Heating Control The I/O Expansion Module has an independent LED annunciator to identify operational fault conditions. Initial Power up Figure 7: I/O Expansion Board Configuration Jumper Terminals I/O expansion module configuration jumper terminals Table 10: IV/PR(H8) Terminal and Compressor Operation IV/PR(H8) Compressor On Normally Open 24 VAC 0 VAC Normally Closed 0 VAC 24 VAC OM 1149-2 Compressor Off 18www.DaikinApplied.com MicroTech III Unit Controller Table 11: I/O Expansion Module Jumper Settings I/O Expansion Description Jumper(s) Setting Not Used JP1 JP1 = Open Not Used JP2 JP2 = Open JP3 = Open JP4 = Open Secondary Heating Options JP3 & JP4 JP5 & JP6 None JP3 = Shorted JP4 = Open Supplemental Electric Heat JP3 = Open JP4 = Shorted Boilerless Electric Heat JP3 = Shorted JP4 = Shorted Hydronic Heat JP5 = Open JP6 = Open Dehumidification Options / Waterside Economizer Model None JP5 = Shorted JP6 = Open Hot Gas/Water Reheat (HGR) JP5 = Open JP6 = Shorted Waterside Economizer Not Used JP7 JP7 = Open Compressor Capacity Option JP8 JP8 = Open JP8 = Shorted Single-Stage Capacity Dual-Stage Capacity Operation Thermostat Inputs Waterside Economizer/ Dehumidification • The Waterside Economizer/Dehumidification input (TB1-1), when energized from the thermostat, enables Waterside Economizer or Dehumidificaiton operation depending on jumper configuration. W4 • The W4 (TB1-2) terminal enables the second stage of electric heat. Electric Heat Controls Supplemental Electric Heat Control The supplemental electric heating option provides additional stages of heating that can be used in conjunction with compressor heating, or exclusively if the compressor is not available for heating. General Rules: • Supplemental electric heater and the compressor may operate simultaneously. • Minimum Compressor ON and OFF timers do not apply to electric heat control. www.DaikinApplied.com19 Operation: Fan Main Output: will turn ON and the Fan PWM signal will be at “Auxiliary Heat” duty cycle when: • Any auxiliary heat output is energized. • For 30 fixed seconds after all auxiliary heat outputs have been de-activated. Electric Heat Outputs: are allowed to energize when either condition exists: • Inter-Stage ON timer must be expired. • Compressor is not available for heating. When Compressor is Available: • Auxiliary Heat Stage #1 output energizes upon activation of Heating – Stage #3. • Auxiliary Heat Stage #2 output energizes upon activation of Heating – Stage #4. When Compressor is Unavailable: • Auxiliary Heat Stage #1 output energizes upon activation of “Heating – Stage #1. • Auxiliary Heat Stage #2 output energizes upon activation of Heating – Stage #4. OM 1149-2 MicroTech III Unit Controller Boilerless Heat Control Operation: • For geothermal applications the heater turns on when the entering water temperature is less than setpoint (default 28°F). • When Entering Water Temperature (EWT) rises above the hydronic heating on setpoint: • Turns on the heater when the entering water temperature is less than setpoint (default is 55°F), the temperature set point is adjustable through the network. The Auxiliary Heat Stage #1 (H8-4) output on the I/O expansion board is used to open the hydronic heating valve. • Hydronic heating setpoint allowed range is 70°F to 158°F, with a 70°F default value. Note: In both cases the compressor is shut down. • Compressor will be locked out of heating Compressor Heating Source Selection • (compressor minimum on timer applies). Compressor heating source selection provides a method to disable the compressor operation when in the heating mode. Baseboard JP7 configuration jumper operation: • Open: Enables compressor operation in the heating mode. • Shorted: Disables compressor operation in the heating mode. When compressor operation is disabled in the heating mode and electric heat is available: • Auxiliary Heat Stage #1: output energizes upon activation of the “Heating – Stage #1”. • Auxiliary Heat Stage #2: output energizes upon activation of the “Heating – Stage #4”. When compressor operation is disabled in the heating mode and electric heat is unavailable: • The unit will not provide any form of heating. • If hydronic heating is required: the pump request output is activated; the “wait for flow” timer is canceled because the EWT is adequate for hydronic heating; the hydronic heating output shall energize; and the fan will turn on 30 seconds after the hydronic heating output has been energized. • The fan speed signal is based on the highest active heating stage (#1 or #2) Fan Speed Selector Switch A 4-position fan speed selector switch located in the control box allows CFM settings to be field adjustable. Fan speed control optimizes unit fan speed based on thermostat/room sensor inputs. The fan speed switch allows for manually setting an optimal fan speed specific to the application requirements. Each position on the fan speed switch represents settings 1-4. See Table 12 and Table 13 on page 21 for a list of fan speed selector switch settngs. Figure 8: 4-position fan speed selector switch Hydronic Heat General: The hydronic heating option provides control of a two position valve connected to a hot water coil when loop water temperature is warm enough for hydronic heating. • Loop water temperature is sensed by a factory installed entering water temperature sensor located on the inlet water line. • Hydronic heat circuit shall be independent and substitute the use of the compressor driven refrigeration circuit. OM 1149-2 20www.DaikinApplied.com MicroTech III Unit Controller Table 12: Fan speed selector switch settings (2-ton unit example) CFM Setting Stage 1 Heat Stage 2 Heat Stage 1 Cool Stage 2 Cool Fan Only Dehumidification Electric Heat Setting 4 (High) 800 900 800 900 600 600 900 Setting 3 (Standard) 700 800 700 800 600 600 900 Setting 2 (Medium) 600 700 600 700 4560 600 900 Setting 1 (Low) 6 00 600 600 600 450 600 900 Fan Performance – Constant CFM Type ECM Motor Table 13: Single stage units with constant CFM type ECM motor Unit Size 015 019 024 030 036 042 048 060 070 Setting Maximum ESP (in. wg.)2 1Low CFM Heat 1High CFM Heat 1Low CFM Cool 1High CFM Cool Fan Only Dehumidification Electric Heat Setting 4 (High) .70 500 560 500 560 375 375 560 Setting 3 (Standard) .70 440 500 440 500 375 375 560 Setting 2 (Medium) .70 375 440 375 440 280 375 560 Setting 1 (Low) .70 375 375 375 375 280 375 560 Setting 4 (High) .70 600 675 600 675 450 450 675 Setting 3 (Standard) .70 525 600 525 600 450 450 675 Setting 2 (Medium) .70 450 525 450 525 340 450 675 Setting 1 (Low) .70 450 450 450 450 340 450 675 Setting 4 (High) .70 800 900 800 900 600 600 900 Setting 3 (Standard) .70 700 800 700 800 600 600 900 Setting 2 (Medium) .70 600 700 600 700 450 600 900 Setting 1 (Low) .70 600 600 600 600 450 600 900 Setting 4 (High) .70 1000 1125 1000 1125 750 750 1125 Setting 3 (Standard) .70 875 1000 875 1000 750 750 1125 Setting 2 (Medium) .70 750 875 750 875 560 750 1125 Setting 1 (Low) .70 750 750 750 750 560 750 1125 Setting 4 (High) .70 1250 1400 1250 1400 940 938 1400 Setting 3 (Standard) .70 1090 1250 1090 1250 940 938 1400 Setting 2 (Medium) .70 940 1090 940 1090 700 938 1400 Setting 1 (Low) .70 940 940 940 940 700 938 1400 Setting 4 (High) .70 1400 1575 1400 1575 1050 1050 1575 Setting 3 (Standard) .70 1225 1400 1225 1400 1050 1050 1575 Setting 2 (Medium) .70 1050 1225 1050 1225 785 1050 1575 Setting 1 (Low) .70 1050 1050 1050 1050 785 1050 1575 Setting 4 (High) .70 1600 1800 1600 1800 1200 1200 1800 Setting 3 (Standard) .70 1400 1600 1400 1600 1200 1200 1800 Setting 2 (Medium) .70 1200 1400 1200 1400 900 1200 1800 Setting 1 (Low) .70 1200 1200 1200 1200 900 1200 1800 Setting 4 (High) .70 2000 2250 2000 2250 1500 1500 2250 Setting 3 (Standard) .70 1750 2000 1750 2000 1500 1500 2250 Setting 2 (Medium) .70 1500 1750 1500 1750 1120 1500 2250 Setting 1 (Low) .70 1500 1500 1500 1500 1120 1500 2250 Setting 4 (High) .70 2160 2400 2160 2400 1710 1710 2400 Setting 3 (Standard) .70 1920 2160 1920 2160 1710 1710 2400 Setting 2 (Medium) .70 1710 1920 1710 1920 1330 1710 2400 Setting 1 (Low) .70 1710 1710 1710 1710 1330 1710 2400 Notes: 1 The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as High CFM fan performance. 2 Applications up to 1.0" ESP (in. wg.) are possible. However, increased fan noise should be anticipated and appropriate noise attenuation should be considered. www.DaikinApplied.com21 OM 1149-2 MicroTech III Unit Controller I/O Expansion Module Faults and Fan Operating Modes Table 14: I/O Expansion Module LED & Fault Outputs Type Yellow Green Red Baseboard Communication Fail Description Fault Flash OFF Flash Entering Water Temp Sensor Fail (Boilerless Electric Heat or Waterside Economizer Only or Hydronic Heat) Fault ON OFF Flash Low Entering Water Temperature (No Display On Boilerless Electric Heat) Fault OFF ON Flash Fan is OFF Mode OFF ON OFF Fan Running at Low Speed (0 to 33%) Duty Cycle Mode OFF Flash OFF Fan Running at Medium Speed (34 to 66%) Duty Cycle Mode ON Flash OFF Fan Running at High Speed (67 to 100%) Duty Cycle Mode Flash Flash OFF Note: Mode / Faults are listed in order of priority. Table 15: I/O Expansion Module Connectors and Descriptions H1 – 1 1 H4 – 1 1 Entering Water Temp Sensor – Signal H1 – 2 H4 – 2 H1 – 3 H5 – 1 H1 – 4 H5 – 2 No Connection H1 – 5 H5 – 3 Red LED Output H1 – 6 H5 – 4 Green LED Output H5 – 5 Yellow LED Output H1 – 8 H5 – 6 Red-Green-Yellow LED Common H1 – 9 H6 – 1 HP2-1 Comp High Capacity High Press Sw (HP2) Input Terminal 1 H1 – 10 H6 – 2 HP2-2 Comp High Capacity High Press Sw (HP2) Input Terminal 2 H1 – 11 H7 – 1 Fan Speed Table Row Select – Signal H1 – 12 H7 – 2 Fan Speed Table Row Select – Common Auxiliary Heat Stage #2 Output – N/O H7 – 3 Thermostat – Heat Stage #4 (W4) Input – Signal H2 – 2 No Connection H7 – 4 Auxiliary 24 VAC Out H2 – 3 24 VAC Common H8 – 1 Ext. 24 VAC In H8 – 2 24 VAC Common H3 – 2 Ext. 24 VAC Common In H8 – 3 No Connection H3 – 3 HGR / Waterside Economizer Output – N/O H8 – 4 Auxiliary Heat Stage #1 / Hydronic Heat Output N/O (24 VAC) H3 – 4 Ext. 24 VAC Common H8 – 5 H3 – 5 ECM Fan Motor Variable Speed Signal Output TB1 – 1 1 Humidistat Signal Input H3 – 6 ECM Fan Motor Variable Speed Signal – Common TB1 – 2 2 Thermostat - Heat Stage #4 (W4) Input – Signal Connections to Main Board H1 – 7 H2 – 1 H3 – 1 1 1 OM 1149-2 Entering Water Temp Sensor – Common 1 1 No Connection Compressor – High Capacity Output – N/O 24 VAC Common 22www.DaikinApplied.com MicroTech III Unit Controller Unit Options ■■ Wiring: Waterside Economizer Control • Digitally adjustable room temperature sensor (Part No. 910121754) • Thermostat (Part No. 910121746 or 910121748)/ Sensor (Part No. 667720401) Combination: Waterside Economizer • The Microtech III controls the waterside economizer. Upon a call for economizer operation via TB1-1, the output to the 3-way diverting valve and the fan motor are energized, allowing water flow through the economizer coil and fan operation. Figure 9: Model GT thermostat and sensor combination hot gas reheat smart dehumidification wiring diagram Model GT Unit Thermostat R R24VAC C CCommon G GFan Y1 Y1 Cool Stage 1 Y2 Y2 Cool Stage 2 Humidistat TB-1 R 24VAC DHDehumid SmartSource Dehumidification ■■ Hot Gas Reheat Smart Dehumidification ■■ Simplified Dehumidification ■■ Humidistat Controlled Dehumidification ■■ Dehumidification Only Hot Gas Reheat Smart Dehumidification Figure 10: Model GS thermostat and sensor combination hot gas reheat smart dehumidification wiring diagram ■■ Application: By utilizing the factory installed hot gas reheat and smart air flow management; dehumidifiation can be achieved in applications where precise humidity control is required. ■■ Items Required: Model GS Unit Thermostat R R24VAC C CCommon G GFan Y1 Y1 Cool Stage 1 Humidistat TB-1 R 24VAC DHDehumid • Unit with Hot Gas Reheat option • Humidistat and a Thermostat OR Digitally Adjustable Wall Sensor ■■ Unit Control Settings: • I/O Expansion Module Jumper Settings: • JP5 = Shorted • JP6 = Open Figure 11: SmartSource MicroTech III board to digital room temperature sensor wiring MicroTech III Board SmartSource Board I/O Expansion Module Base Board Terminal Block Label TB2-1 TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB3-1 TB3-2 TB1-1 Description 24VAC Unit Status Output Fan & Unit Mode Setpoint Adjust Room Temp Sensor & Tenant Override DC Signal Common Emergency Shutdown Input Unoccupied Input Dehumidification Input Terminal Label R 1 2 3 4 5 E U 1 Typical Wiring R (24VAC) 1 (ST) 2 (FM) 3 (SP) 4 (UTS) 5 (GND) 6 (FC) E U Description 24VAC Unit Status Output Fan & Unit Mode Setpoint Adjust Room Temp Sensor & Tenant Override DC Signal Common Fan Speed Select - Fan Coil Version Only Emergency Shutdown Unoccupied Sensor DH Dehumidification Terminal Label Digitally Adjustable Room Temperature Sensor (Part No. 910121754) www.DaikinApplied.com23 OM 1149-2 MicroTech III Unit Controller ■■ Operation: ■■ Wiring: A call for heating or cooling has a higher priority than a call for dehumidification. Dehumidification is allowed only if the room temperature is satisfied. If the controller detects the need for heating or cooling, or if the Humidistat is no longer calling for dehumidification, dehumidification mode will be suspended. Dehumidification mode will enable the 3-way hot gas bypass valve, sending hot superheated refrigerant to the hot gas reheat coil while running the compressor at full load and the fan at dehumidification speed. Note: See Fan Performance section in catalog for unit size specific fan speeds. Figure 12: Model GT unit and thermostat simplified dehumidification wiring diagram Model GT Unit R C G TB-1 Y1 Y2 Thermostat R24VAC CCommon GFan Y1 Cool Stage 1 Y2 Cool Stage 2 Y3 Cool Stage 3 Simplified Dehumidification Figure 13: Model GS unit and thermostat simplified dehumidification wiring diagram By utilizing a basic thermostat and configuring the Microtech III unit controller for this mode of operation, the WSHP will provide maximum latent capacity by optimizing blower fan speeds resulting in decreased humidity levels in the conditioned space. ■■ Items Required: Model GS Unit R C G TB-1 Y1 ■■ Application: • Model GT = 3 stage thermostat • Model GS = 2 stage thermostat Note: This feature is not available if unit is controlled by wall sensor ■■ Unit Control Settings: • I/O Expansion Module Jumper Settings: • JP5 = Shorted • JP6 = Open Thermostat R24VAC CCommon GFan Y1 Cool Stage 1 Y2 Cool Stage 2 ■■ Operation: Unit will run at maximum compressor capacity with low CFM to maximize latent capacity. Example: A 2-stage model GT, unit size 026, wired for Simplified Dehumidifcation: • Upon a call for Y1, TB1-1 on the unit control board will be energized, allowing the compressor to operate at full load and the fan to operate at 600 CFM. • Upon a call for Y2, Y1 on the unit control board will be energized, allowing the compressor to operate at part load and the fan to operate at 700 CFM. (Factory default fan speed setting #3) • Upon a call for Y3, Y2 on the unit control board will be energized, allowing the compressor to operate at full load and the fan to operate at 800 CFM. (Factory default fan speed setting #3) OM 1149-2 24www.DaikinApplied.com MicroTech III Unit Controller Humidistat Controlled Dehumidification Figure 14: Model GT thermostat and humidistat combination - humidistat controlled dehumidification wiring diagram ■■ Application: Model GT Unit Thermostat R R24VAC C CCommon G GFan Y1 Y1 Cool Stage 1 Y2 Y2 Cool Stage 2 Humidistat TB-1 R 24VAC DHDehumid Similar to the simplified dehumidification option, this option also maximizes latent capacity by using a humidistat and thermostat. This option allows the room thermostat to control sensible cooling, while the independent humidistat controls room humidity levels ■■ Items Required: • Humidistat combined with a... • Model GT = 3 stage thermostat • Model GS = 2 stage thermostat OR • I/O Expansion Module Jumper Setting: • JP5=Shorted • JP6=Open Note: This feature is not available if unit is controlled by wall sensor ■■ Unit Control Settings: • I/O Expansion Module Jumper Settings: • JP5=Shorted • JP6=Open Figure 15: Model GS thermostat and humidistat combination - humidistat controlled dehumidification wiring diagram Model GS Unit Thermostat R R24VAC C CCommon G GFan Y1 Y1 Cool Stage 1 Humidistat TB-1 R 24VAC DHDehumid ■■ Wiring: • Thermostat/Sensor combination: • Field supplied sensor Figure 16: SmartSource MicroTech III board & I/O expansion module to field supplied room temperature sensor wiring MicroTech III Board SmartSource Board I/O Expansion Module Base Board TB1-1 TB1-2 Description 24VAC Unit Status Output Fan & Unit Mode Humidistat Source Voltage (24VAC) Terminal Label R 1 2 3 4 5 E U 1 Terminal Label X X X Description Dehumidification Output TB3-2 Dehumidification Input TB3-1 Unoccupied Input TB1-5 Emergency Shutdown Input TB1-4 DC Signal Common TB1-3 DC Signal Common TB1-2 Room Temp Sensor, 10K Ohm ATP Curve Z or equivalent TB1-1 Room Temp Sensor & Tenant Override TB2-1 Setpoint Adjust Terminal Block Label Typical Wiring www.DaikinApplied.com25 Dehumidification Source Voltage Sensor X Field Supplied Room Temperature Sensor OM 1149-2 MicroTech III Unit Controller ■■ Operation: ■■ Wiring: Unit will run at maximum compressor capacity with low CFM to maximize latent capacity. Example: A 2-stage model GT, unit size 026, wired for Humidistat Controlled Dehumidification: • Upon a call for dehumidificaion, TB1-1 on the unit control board will be energized by the humidistat, allowing the compressor to operate at full load and the fan to operate at 600 CFM. • Upon a call for stage 1 cooling, Y1 on the unit control board will be energized from Y1 on the thermostat, allowing the compressor to operate at part load and the fan to operate at 700 CFM. (Factory default fan speed setting #3) • Upon a call for stage 2 cooling, Y2 on the unit control board will be energized from Y2 on the themostat, allowing the compressor to operate at full load and the fan to operate at 800 CFM. (Factory default fan speed setting #3) Note: See Fan Performance section in catalog for unit size specific fan speeds. Figure 17: Model GS & GT unit and humidistatdehumidification only wiring diagram Dehumidification Only ■■ Application: Model GS & GT Unit Humidistat R R24VAC C DHDehumid G TB1-1 ■■ Operation: Upon a call for dehumidification, the unit will run in cool stage 1 compressor capacity and cool stage 1 fan speed. Example: A 2-stage model GT, unit size 026, wired for Dehumidification Only: • Upon a call for dehumidification from the humidistat, TB1-1 on the unit control board will be energized, allowing the compressor to operate at full load and the fan to operate at 600 CFM. Note: See Fan Performance section in catalog for unit size specific fan speeds. In applications where only dehumidification is needed, the humidistat can be wired to TB1-1 on the Microtech III unit controller, allowing the WSHP unit to operate in dehumidification mode only. The unit will only respond to a call for dehumidification. ■■ Items Required: • Humidistat ■■ Unit Control Settings: • I/O Expansion Module Jumper Settings: • JP5=Shorted • JP6=Open OM 1149-2 26www.DaikinApplied.com MicroTech III Unit Controller Appendix B MicroTech III Unit Controller with LonWorks® Communication Module For installation and operation information on LonWorks Communication Module and other ancillary control components, see: • IM 927 - MicroTech III Water Source Heat Pump LonWorks Communication Module. • IM 933 - LonMaker Integration Plug-in Tool: For use with the MicroTech III Unit Controller. MicroTech III Unit Controller with LonWorks Communication Module orchestrates the following unit operations: • Enable heating and cooling to maintain setpoint based on a room sensor • IM 955 - MicroTech III Wall Sensor for use with Microtech III Unit Controller • Enable fan and compressor operation Each Daikin water source heat pump can be equipped with a LonWorks communication module that is LonMark 3.4 certified to meet the LonMark Space Comfort Control (SCC) profile for heat pumps. The controller is microprocessor-based and is designed to communicate over a LonWorks network. With the optional factory or field-installed communication module. The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the Water Source Heat Pump. The unit controller monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS to provide network control of the Water Source Heat Pump. • Monitors room and discharge air temperatures Figure 18: LonWorks Communication Module • Monitors all equipment protection controls • Monitors leaving water temperature • Relays status of all vital unit functions The MicroTech III unit controller with an optional communication module includes: • Return Air Temperature sensor (RAT)(field-installed) • Discharge Air Temperature sensor (DAT)(fieldinstalled) • Leaving Water Temperature sensor (LWT) Note: Refer to IM 956-X for details to install (RAT) & (DAT) sensors. CAUTION When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly. The MicroTech III unit controller with communication module includes a unit-mounted return air, discharge air and leaving water temperature sensor. Wall mounted temperature sensors include setpoint adjustment and tenant override. The user has the capability of substituting the wall sensor with a duct-mounted return air sensor. www.DaikinApplied.com27 The communication module provides access to setpoints for operational control Available wall sensors include: • Room sensor with LED status and tenant override button • Room sensor with LED status, tenant override button, and ±5°F setpoint adjustment • Room sensor with LED status, tenant override button, 55° to 95°F setpoint adjustment OM 1149-2 MicroTech III Unit Controller MicroTech III Controller with an Optional BACnet® Communication Module MicroTech III Unit Controller with BACnet MS/TP Communication Module orchestrates the following unit operations: • Enable heating and cooling to maintain setpoint based on a room sensor • Enable fan and compressor operation For installation and operation information on MicroTech III unit controller and other ancillary components, see: • IM 928 - MicroTech III Water Source Heat Pump BACnet Communication Module • IM 955 - MicroTech III Wall Sensor For use with Microtech III Unit Controller Daikin water source heat pumps are available with an optional BACnet MS/TP communication module that is designed to communicate over a BACnet MS/ TP communications network to a building automation system (BAS). It can be factory or field-installed. The unit controller is programmed and tested with all the logic required to monitor and control the unit. An optional wall sensor may be used with the communication module to provide limited local control of the water source heat pump. The unit controller monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS, to provide network control of the water source heat pump. The module makes operational data and commands available on a communications network using BACnet objects and properties: • The network cable is a shielded twisted-pair cable • Network communications run up to 76.8 Kbps • DIP switches on the controller enable the MS/TP MAC address to be set in the range 0-127 • Four green status LEDs on the communication module indicate communication activity on the MS/TP communication network and with the unit controller Figure 19: MicroTech III BACnet MS/TP Snap-in Communication Module OM 1149-2 • Monitors all equipment protection controls • Monitors room and discharge air temperatures • Monitors leaving water temperature • Relays status of all vital unit functions The MicroTech III unit controller with an optional communication module includes: • Return Air Temperature sensor (RAT)(field-installed) • Discharge Air Temperature sensor (DAT)(fieldinstalled) • Leaving Water Temperature sensor (LWT) Note: Refer to IM 956-X for details to install (RAT) & (DAT) sensors. CAUTION When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly. The communication module provides access to setpoints for operational control Available wall sensors include: • Room sensor with LED status and tenant override button • Room sensor with LED status, tenant override button, and ±5°F setpoint adjustment • Room sensor with LED status, tenant override button, 55° to 95°F setpoint adjustment 28www.DaikinApplied.com Typical Wiring Diagrams 115V, 1Ph – Model WGS, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) (See page 30 for Service & Disconnect Wiring) www.DaikinApplied.com29 OM 1149-2 Typical Wiring Diagrams Service & Disconnect Wiring - 115V, 1Ph – Model WGS, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) OM 1149-2 30www.DaikinApplied.com Typical Wiring Diagrams 265V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) (See page 32 for Service & Disconnect Wiring) www.DaikinApplied.com31 OM 1149-2 Typical Wiring Diagrams Service & Disconnect Wiring - 265V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Hot Gas Reheat) OM 1149-2 32www.DaikinApplied.com Typical Wiring Diagrams 208-230V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, Desuperheater, 115V Loop Pumps & 20kW Electric Heat) (See page 34 for Service & Disconnect Wiring) www.DaikinApplied.com33 OM 1149-2 Typical Wiring Diagrams Service & Disconnect Wiring - 208-230V, 1Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, Desuperheater, 115V Loop Pumps & 20kW Electric Heat) OM 1149-2 34www.DaikinApplied.com Typical Wiring Diagrams 208-230V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 5kW Electric Heat) (See page 36 for Service & Disconnect Wiring) www.DaikinApplied.com35 OM 1149-2 Typical Wiring Diagrams Service & Disconnect Wiring - 208-230V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 5kW Electric Heat) OM 1149-2 36www.DaikinApplied.com Typical Wiring Diagrams 460V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 20kW Electric Heat) (See page 38 for Service & Disconnect Wiring) www.DaikinApplied.com37 OM 1149-2 Typical Wiring Diagrams Service & Disconnect Wiring - 460V, 3Ph – Model WGS-WGT, MicroTech III SmartSource Unit Controller with BACnet Communication Module (Waterside Economizer, 230V Loop Pumps & 20kW Electric Heat) OM 1149-2 38www.DaikinApplied.com Appendix C Controller Comparison Note: The Mark IV, MicroTech 2000, Alerton and MicroTech III boards are NOT interchangeable. Table 16: Control Boards and Features ● = Applies Mark IV MicroTech 2000 – = Does not apply Alerton MicroTech III DC Power ● – – – AC Power ● ● ● ● Terminal Connection 1/4″ Push-on ● – – – Features IDC Connection – ● ● ● Fault Indicators ● ● – ● Thermostatic Controls ● – – ● Room Sensor – ● ● ● LONmark Capable – ● – ● LonWorks Capable – ● – – BACnet Capable(1) Motorized Valve Capability – – ● ● – ● ● ● Short Cycle Protection & Random Start ● ● ● ● Unoccupied Mode ● ● ● ● Override Mode ● ● ● ● Pump Restart ● ● ● ● Loadshed ● ● ● – Brownout Protection ● ● ● ● Unit Shutdown ● ● ● ● Condensate Overflow Protection ● ● ● ● Remote Reset(1) ● – – ● Intelligent Reset(1) – – – ● Dual Circuit Capability ● ● ● ● Adjustable Set Points Through Software – ● ● ● Adjustable Fan Speed – – – ● Electric Heat Availability – – – ● Service Tools Needed at Start up – ● ● ● Dipswitch Settings – – ● – Programmable Front-end Settings – ● – ● Switching Line Voltage ● – – ● Note: (1) Alerton BACnet requires Alerton service tools for commissioning (1) Alerton dipswitch settings must be configured during commissioning (1) See Remote Reset and Intelligent Reset information under section: Additional Operating Modes www.DaikinApplied.com39 OM 1149-2 Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com. Aftermarket Services To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com. Products manufactured in an ISO Certified Facility. OM 1149-2 ©2014 Daikin Applied (7/14) | (800) 432–1342 | www.DaikinApplied.com