R SL SERIES High Voltage Power Supply MODEL : SERIAL# : DATE : SPELLMAN HIGH VOLTAGE ELECTRONICS CORPORATION 475 Wireless Blvd. Hauppauge, New York, 11788 +1(631) 630-3000*FAX: +1(631) 435-1620* E-mail: sales@spellmanhv.com Website: www.spellmanhv.com SL SERIES MANUAL 118005-001 Rev N IMPORTANT SAFETY PRECAUTIONS SAFETY THIS POWER SUPPLY GENERATES VOLTAGES THAT ARE DANGEROUS AND MAY BE FATAL. OBSERVE EXTREME CAUTION WHEN WORKING WITH THIS EQUIPMENT. High voltage power supplies must always be grounded. Do not touch connections unless the equipment is off and the Capacitance of both the load and power supply is discharged. Allow five minutes for discharge of internal capacitance of the power supply. Do not ground yourself or work under wet or damp conditions. SERVICING SAFETY . Maintenance may require removing the instrument cover with the power on. Servicing should be done by qualified personnel aware of the electrical hazards. WARNING note in the text call attention to hazards in operation of these units that could lead to possible injury or death. CAUTION notes in the text indicate procedures to be followed to avoid possible damage to equipment. Copyright © 2000, Spellman High Voltage Electronics Corporation. All Rights Reserved. This information contained in this publication is derived in part from proprietary and patent data. This information has been prepared for the express purpose of assisting operating and maintenance personnel in the efficient use of the model described herein, and publication of this information does not convey any right to reproduce it or to use it for any purpose other than in connection with installation, operation, and maintenance of the equipment described. 118004-001 REV. B WICHTIGE SICHERHEITSHINWEISE SICHERHEIT DIESES HOCHSPANNUNGSNETZTEIL ERZEUGT LEBENSGEFÄHRLICHE HOCHSPANNUNG. SEIN SIE SEHR VORSICHTIG BEI DER ARBEIT MIT DIESEM GERÄT. Das Hochspannungsnetzteil muß immer geerdet sein. Berühren Sie die Stecker des Netzteiles nur, wenn das Gerät ausgeschaltet ist und die elektrischen Kapazitäten des Netzteiles und der angeschlossenen Last entladen sind. Die internen Kapazitäten des Hochspannungsnetzteiles benötigen ca. 5 Minuten, um sich zu entladen. Erden Sie sich nicht, und arbeiten Sie nicht in feuchter oder nasser Umgebung. SERVICESICHERHEIT Notwendige Reparaturen können es erforderlich machen, den Gehäusedeckel während des Betriebes zu entfernen. Reparaturen dürfen nur von qualifiziertem, eingewiesenem Personal ausgeführt werden. “WARNING” im folgenden Text weist auf gefährliche Operationen hin, die zu Verletzungen oder zum Tod führen können. “CAUTION” im folgenden Text weist auf Prozeduren hin, die genauestens befolgt werden müssen, um eventuelle Beschädigungen des Gerätes zu vermeiden. 118004-001 REV. B PRECAUTIONS IMPORTANTES POUR VOTRE SECURITE CONSIGNES DE SÉCURITÉ CETTE ALIMENTATION GÉNÈRE DES TENSIONS QUI SONT DANGEUREUSES ET PEUVENT ÊTRE FATALES. SOYEZ EXTRÊMENT VIGILANTS LORSQUE VOUS UTILISEZ CET ÉQUIPEMENT. Les alimentations haute tension doivent toujours être mises à la masse. Ne touchez pas les connectiques sans que l’équipement soit éteint et que la capacité à la fois de la charge et de l’alimentation soient déchargées. Prévoyez 5 minutes pour la décharge de la capacité interne de l’alimentation. Ne vous mettez pas à la masse, ou ne travaillez pas sous conditions mouillées ou humides. CONSIGNES DE SÉCURITÉ EN CAS DE REPARATION La maintenance peut nécessiter l’enlèvement du couvercle lorsque l’alimentation est encore allumée. Les réparations doivent être effectuées par une personne qualifiée et connaissant les risques électriques. Dans le manuel, les notes marquées « WARNING » attire l’attention sur les risques lors de la manipulation de ces équipements, qui peuvent entrainer de possibles blessures voire la mort. Dans le manuel, les notes marquées « CAUTION » indiquent les procédures qui doivent être suivies afin d’éviter d’éventuels dommages sur l’équipement. 118004-001 REV. B IMPORTANTI PRECAUZIONI DI SICUREZZA SICUREZZA QUESTO ALIMENTATORE GENERA TENSIONI CHE SONO PERICOLOSE E POTREBBERO ESSERE MORTALI. PONI ESTREMA CAUTELA QUANDO OPERI CON QUESO APPARECCHIO. Gli alimentatori ad alta tensione devono sempre essere collegati ad un impianto di terra. Non toccare le connessioni a meno che l’apparecchio sia stato spento e la capacità interna del carico e dell’alimentatore stesso siano scariche. Attendere cinque minuti per permettere la scarica della capacità interna dell’alimentatore ad alta tensione. Non mettere a terra il proprio corpo oppure operare in ambienti bagnati o saturi d’umidità. SICUREZZA NELLA MANUTENZIONE. Manutenzione potrebbe essere richiesta, rimuovendo la copertura con apparecchio acceso. La manutenzione deve essere svolta da personale qualificato, coscio dei rischi elettrici. Attenzione alle AVVERTENZE contenute nel manuale, che richiamano all’attenzione ai rischi quando si opera con tali unità e che potrebbero causare possibili ferite o morte. Le note di CAUTELA contenute nel manuale, indicano le procedure da seguire per evitare possibili danni all’apparecchio. 118004-001 REV. B Table of Contents PAGE 1. INTRODUCTION 1.1 Description of the SL Series ................................................................................1 1.2 Standard Features.................................................................................................2 1.2.1 Remote Operating Features ..................................................................2 1.2.2 System Status and Fault Diagnostic Display ........................................2 1.3 Options.................................................................................................................3 1.4 Interpreting the Model Number ...........................................................................4 2. INSPECTION & INSTALLATION 2.1 Initial Inspection ..................................................................................................5 2.2 Mechanical Installation........................................................................................5 3. OPERATING INSTRUCTIONS 3.1 Operation .............................................................................................................7 3.2 Standard Features.................................................................................................8 4. PRINCIPLES OF OPERATION 4.1 Chassis .................................................................................................................18 4.2 Line Rectification and Filtering...........................................................................18 4.3 Inverter.................................................................................................................19 4.4 High Voltage Transformer...................................................................................20 4.5 High Voltage Assembly.......................................................................................20 4.6 Control/Power PWB ............................................................................................20 4.7 Front Panel Assembly ..........................................................................................20 4.8 Options.................................................................................................................20 5. OPTIONS 5.1 Adjustable Overload Trip ....................................................................................21 5.2 220Vac Single Phase Input .................................................................................21 5.3 No Slow Start ......................................................................................................21 5.4 Non-Standard Slow Start .....................................................................................21 5.5 Extra Length Output Cable ..................................................................................21 5.6 Floating Ground ...................................................................................................21 5.7 Floating Ground Low Leakage ............................................................................22 5.8 Adjustable Power Trip/Constant Power Control .................................................22 SL SERIES MANUAL I 118006-001 REV V 5.9 Arc Trip Option ...................................................................................................22 5.10 Reversible Polarity Option...................................................................................22 5.10.1 Models from 1 kV to 8kV .........................................................................22 5.10.2 Models from 10kV to 130kV ....................................................................22 5.11 Instant On.............................................................................................................22 5.12 Bipolar Master/Slave Option ...............................................................................23 5.13 External Fault Relay Option ................................................................................23 5.14 Custom Design Models........................................................................................23 6. MAINTENANCE 6.1 Periodic Servicing................................................................................................28 6.2 Performance Test .................................................................................................28 6.3 High Voltage Dividers .........................................................................................28 7. REPLACEMENT PARTS 7.1 Replacement Parts................................................................................................29 7.2 Correspondence and Ordering Spare Parts ..........................................................29 8. FACTORY SERVICE 8.1 Warranty Repairs .................................................................................................30 8.2 Factory Service Procedures .................................................................................30 8.3 Ordering Options and Modifications ...................................................................30 8.4 Shipping Instructions ...........................................................................................30 SL SERIES MANUAL II 118006-001 REV V LIST OF FIGURES Figure 2.1 Figure 3.1 Figure 3.2A Figure 3.2B Figure 3.3 Figure 3.4 Figure 3.5 Figure 3.6 Figure 3.7 Figure 3.8 Figure 5.1 Figure 5.2 Figure 5.3 Figure 5.4 Figure 5.5 Figure 5.6 Figure 5.7 Figure 5.8 SL Series Dimensions .................................................................................6 SL Series Typical Operating Set Up...........................................................10 Wiring Diagram for Remote Programming via Voltage Source ................13 Wiring Diagram for Remote Programming via External Resistance..........13 Remote Monitor Test Point Designations...................................................14 Remote Control of High Voltage On and Off ............................................14 External Inhibit Interface Circuit................................................................15 External Interlock Interface Circuit ............................................................15 Remote High Voltage On and Remote High Voltage off Indicator Circuit.... 16 Remote Indicators Interface ............................................................................ 17 Floating Ground Interface Circuit................................................................... 24 Adjustable Power Remote Interface TB1 Only .............................................. 24 Polarity Reversal Procedure 1kV to 8kV (10W to 300W).............................. 25 Polarity Reversal Procedures, 10kV to 130kV (10W to 300W) ..................... 25 Polarity Reversal Procedures, 1kV to 8kV (600W to 1200W) ....................... 26 Polarity Reversal Procedures 10kV to 130kV (600W to 1200W) .................. 26 Instant On Option............................................................................................ 27 Bipolar Master/Slave Option ......................................................................27 LIST OF TABLES Table 1.1 Table 3.1 Table 3.2 Table 4.1 SL Options ..................................................................................................3 Rear Panel Interface 26 pin Terminal Block ..............................................11 Rear Panel Interface 25 pin Mini D ............................................................12 List of Main Assemblies .............................................................................19 APPENDIX A. SL SERIES MANUAL Specification Controls (Custom Models Only) III 118006-001 REV V Chapter 1 INTRODUCTION 1.1 Description of the SL Series T he SL Series of high voltage power supplies provides very well regulated, low ripple high voltage in a highly efficient, compact design. The improvements in size and performance over traditionally designed high voltage power supplies are due to the resonant topology and unique control circuitry of the SL design. A proprietary control system maintains high frequency over the operating output range. High frequency operation allows a dynamic response time of less than 5 milliseconds, and one of the lowest ripple specifications in the industry at this power level. The combination of proprietary control system and proprietary protection circuitry enables the supplies to operate under arcing and extreme transient conditions without damage or interruptions. The DC output voltage and current are continuously adjustable from zero to the maximum rating via two front panel ten-turn locking potentiometers. These high voltage power supplies have 0.005% load regulation, 0.005% line regulation, and 0.1% p-p ripple. The supplies operate from either a 115 or 220 Volt, single phase AC line. Other line voltages are available. Options are listed in Table 1.1 and are described in Section 5. Custom designed units to meet special needs are also available. SL SERIES MANUAL 1 118006-001 REV V 1.2 Standard Features The SL Series incorporates several standard features designed to optimize user satisfaction and safety. SLOW START: This feature provides a gradual increase in high voltage until the preset operating point is reached. The slow start time is factory set for 6 seconds. Other slow start times are available as an option. ARC DETECT / ARC QUENCH / ARC COUNT: These features allow the user to tailor the power supply to meet specific needs in dynamic load applications. If an arc occurs, the output is inhibited for approximately one second, then the output is ramped up to the preset level with the slow-start circuitry. See Chapter 3 for operating details and information for user customization of these features. INDICATOR LAMPS: LINE POWER, HIGH VOLTAGE OFF AND HIGH VOLTAGE ON indicators. OUTPUT CABLE: All models are provided with a ten foot shielded high voltage output cable. The cables are designed with a plug arrangement so that they can be easily removed from the mating receptacle located on the rear of the chassis. EXTERNAL INHIBIT: A control signal that will inhibit the high voltage output is provided on the external interface. A logic low, ground, will inhibit the high voltage output and a logic high, open, will restore the high voltage output to the preset level. “Dead Front” type indictors are provided to give the user complete indication of system operation and fault conditions. If a fault occurs, the power supply will revert to the POWER DOWN mode. This is indicated by both the HV ON and HV OFF lamps turning off. To reset, depress the HV OFF switch. REMOTE PROGRAMMING: Allows remote adjustment of the output voltage and current via an external voltage source. The output power is also remotely controllable when the CPC or APT option is ordered, TB1 only. VOLTAGE (CONTROL): Indicates the output voltage regulator circuit is maintaining voltage regulation. CURRENT (CONTROL): Indicates the output current regulator circuit is maintaining current regulation. POWER (CONTROL): Indicates the output power regulator circuit is maintaining power regulation (optional). HV INHIBIT: Indicates that the high voltage supply is being inhibited by either the EXTERNAL INHIBIT or internal protection circuitry. INTLK CLSD: Indicates the EXTERNAL INTERLOCK connections are in the closed position. This also indicates closure of internal power supply interlocks. REMOTE MONITOR: Allows remote monitoring of the output voltage and current. NOTE: Output power remote monitor is included with the CPC and APT options, TB1 only. SL SERIES MANUAL EXTERNAL INTERLOCK: Interlock connections are provided on the external interface on the rear of the chassis for connection to a safety switch. The unit will not operate unless the interlock circuit is closed. During high voltage operation, opening the interlock circuit will cause the High Voltage to shut off. This circuit should be used for safety interlock circuits. 1.2.2 System Status and Fault Diagnostic Display 1.2.1 Remote Operating Features REMOTE HIGH VOLTAGE CONTROL: Allows remote control of HIGH VOLTAGE ON and HIGH VOLTAGE OFF. Signals are also provided for remote indication of HV ON or HV OFF status. NOTE: The External Inhibit circuit should NOT be used for protection against injury or for safety interlock. See External Interlock for this type of safety control. INTERNAL FAULT PROTECTION: The SL Series continually monitors internal circuits critical to the proper operation of the power supply. In the event that one of these circuits does not function correctly, the fault detection circuit latches the appropriate fault on the front panel display and turns off the output and reverts the unit to the POWER DOWN mode. 2 118006-001 REV V INTKL OPEN: Indicates the EXTERNAL INTERLOCK connections are in the open position. This also indicates opening of internal power supply interlocks. 1.3 Options OVERVOLT: Indicates the overvoltage protection circuitry has caused the power supply to turn off. Overvoltage protection is internally set to 110% of the rated output voltage. OVERCURR: Indicates the output current has exceeded the programmed current trip level when the AOL (Adjustable Overload Trip) or the OL (Overload Trip) options are installed. OVERPOWER: Indicates the output power has exceeded the internally set level or the remote programmed level if the optional circuitry is installed. ARC: Indicates that an arc has occurred within the previous one second or that the ARC COUNT/TRIP has shutdown the power supply. RGLT ERR: Indicates a failure in the voltage, current or power regulation circuitry. This fault usually occurs when there is a lack of output power to maintain regulation. The options available are listed in Table 1.1. See Section 5 for more information on these options along with operating and set-up instructions. With few exceptions, these options and modifications can be retrofitted to your power supply at the factory in a short time. For price and retrofit arrangements, contact the Spellman Sales Department. AOL Adjustable Overload Trip (0-103%) OL Overload Trip (103%) APT Adjustable Power Trip AT Arc Trip FG Floating Ground FGLL Floating Ground, Low Leakage (10mA) CPC Constant Power Control SS(x) Non-Standard Slow Start NSS No Slow Start IO Instant ON LR Low Ripple (0.05% p-p) ( ) DPM4 Specify 220V or 100V or 200Vac Single Phase Input With Order. 4 1/2 Digit 1 Least Significant Digit Panel Mtr PN Reversible Polarity FPS Filament Power Supply LL (x) Extra Length Output Cable in Feet MS Bipolar Master/Slave C 3 1/2” High (2U) Cabinet For Multiple Units SL Slides EFR External Fault Relay BFP Blank Front Panel Table 1.1 SL Options SL SERIES MANUAL 3 118006-001 REV V 1.4 Interpreting the Model Number The model number of the power supply describes its capabilities. After the series name is: 1. 2. 3. 4. the maximum voltage (in KV). the polarity of the unit: positive (P), negative (N) or reversible (PN). the maximum output (in watts). the option codes for all options that are included. Custom units have an X number after the option codes. SL Series Name Maximum Voltage SL SERIES MANUAL 30 P 1200 / FG / X (#) Option Polarity Maximum Power 4 Custom “X” Number 118006-001 REV V Chapter 2 INSPECTION & INSTALLATION I nitial inspection and preliminary checkout procedures are recommended. For safe operation, please follow the step-by-step procedures described in Chapter 3, Operating Systems. Fill out and mail the Warranty Registration card accompanying the unit. Standard Spellman SL Series high voltage power supplies and components are covered by warranty. Custom and special order models (with an X suffix and the model number) are also covered by warranty. 2.1 Initial Inspection Inspect the package exterior for evidence of damage due to handling in transit. Notify the carrier and Spellman immediately if damage is evident. Do not destroy or remove any of the packing material used in a damaged shipment. 2.2 Mechanical Installation Units in the SL Series have front panel holes for standard EIA rack mounting. The rack must allow rear access for cable connections. Units are fully enclosed and are suitable for bench or table top operation. Standard unit dimensions are shown in Figure 2.1. It is strongly recommended to support the chassis by guides or slides. Slides are available for ease of servicing (SL option). After unpacking, inspect the panel and chassis for visible damage. SL SERIES MANUAL 5 118006-001 REV V 19.00 [482.60] 18.31 [465.14] 0.34 [8.73] 0.25 [6.35] TYP 90 90 10 80 20 80 30 70 30 70 40 VOLTAGE OVER VOLT CURRENT OVER CURR POWER OVER PWR 0 0 10 20 60 40 50 milliamperes 17.00 [431.83] IEC 320 INPUT CONNECTOR HV ON INTLK CLSD RGLT ERR INTLK OPEN ARC 60 50 kilovolts SPELLMAN I O 1 HV OFF HV INHIBIT OVER TEMP HIGH VOLTAGE OUTPUT CONNECTOR HIGH VOLTAGE TB1-I/O INTERFACE 1.72 [43.66] 2 3 4 5 6 7 8 9 TB2 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 J2 LINE INPUT J1 PART NO. MODEL: SERIAL NO: OUTPUT: INPUT: 0.23 [5.97] FRONT PANEL REAR PANEL 25 PIN MINI "D" 2 PIN TERMINAL BLOCK LOAD RETURN (CHASSIS GROUND) 26 PIN TERMINAL BLOCK FOR REMOTE CONTROL MONITORING REAR PANEL 25 PIN MINI "D" 10-300W 0.38 [9.52] 4 PLACES 0.25 [6.35] 4 PLACES 90 90 10 80 20 80 70 30 70 60 40 VOLTAGE OVER VOLT 0 0 10 20 30 3.45 [87.60] 60 40 CURRENT OVER CURR POWER OVER PWR INTLK CLSD RGLT ERR 50 50 milliamperes kilovolts INTLK OPEN ARC HV INHIBIT OVER TEMP HV ON HV OFF DANGER HIGH VOLTAGE TB1-I/O INTERFACE O I 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 3.00 [76.20] TYP LINE INPUT SPELLMAN TB2 1 HIGH VOLTAGE ELECTRONICS CORP PLAINVIEW, NY 11803 MADE IN USA 2 1-FLOATING GND (OPTIONAL) SPELLMAN 2-GND FRONT PANEL 0.23 [5.72] TYP PART NO. MODEL: SERIAL NO: OUTPUT: INPUT: REAR PANEL 14AWG LINE CODE 26 pin TB1 25 PIN MINI "D" JB1 I/O INTERFACE DANGER HIGH VOLTAGE LINE INPUT SPELLMAN TB2 1 HIGH VOLTAGE ELECTRONICS CORP PLAINVIEW, NY 11803 MADE IN USA 2 1-FLOATING GND (OPTIONAL) 2-GND PART NO. MODEL: SERIAL NO: OUTPUT: INPUT: 600-1200W "L" 1.66 [42.13] SIDE VIEW OF 10-300W OUTPUT VOLTAGE "KV" "L" 1 TO 70 19.00 80 TO 130 24.00 3.41 [86.59] SIDE VIEW OF 600-1200W Figure 2.1 - SL Dimension SL SERIES MANUAL 6 118006-001 REV V Chapter 3 OPERATING INSTRUCTIONS 10W-300W units are provided with IEC type line cable. 600W-1200W units are provided with a three conductor line cord. 3.1 Operation WARNING D) Attach the output cable to the load. THIS EQUIPMENT GENERATES DANGEROUS VOLTAGES THAT MAY BE FATAL. E) Plug the high-voltage output cable provided with the unit into the rear of the supply and hand tighten the knurled collar. PROPER GROUNDING OF ALL HIGH VOLTAGE EQUIPMENT IS ESSENTIAL. F) OPTIONS NOTE: See Section 5 for hook-up and operating instructions for the options on your unit. Custom models may also require set-up changes. WARNING BEFORE CONNECTING THE POWER SUPPLY TO THE AC LINE, FOLLOW THIS STEP BY STEP PROCEDURE. G) For initial turn-on, rotate the KILOVOLT control fully counter-clockwise to the zero voltage position. H) The input power cable may now be connected to the AC power line. DO NOT CONNECT THE POWER SUPPLY TO THE AC LINE UNTIL STEP H IS REACHED. I) Failure to follow these procedures may void the warranty. A) Insure that the Circuit Breaker is in the OFF position (0). B) Check the input voltage rating on the nameplate of the supply and make certain that this is the rating of the available power source. Spellman SL Series units operate on 115Vac (220Vac if 220Vac option is ordered), single phase unless ordered with a different input voltage. Switch the front panel circuit breaker to the ON position (1). (If the supply is to be turned off for an extensive period of time, the line cord should be disconnected). The light inside the circuit breaker should light up. The unit is now in the HIGH VOLTAGE OFF mode. The HIGH VOLTAGE OFF light should be lit. C) PROPER GROUNDING TECHNIQUES: The chassis of high voltage power supplies must be grounded, preferably to a water system ground using copper pipe or other earth ground using the ground stud B1 at the rear of the unit. See Figure 3.1 for a typical operating set-up. The return line from the load should be connected to the ground pin terminal block TB2-1, on the rear of the power supply. Using a separate external ground at the load is not recommended. SL SERIES MANUAL 7 118006-001 REV V CAUTION J) Depress and hold the HIGH VOLTAGE OFF switch. The front panel meters will now read the preset value of the KILOVOLT control dial and the MILLIAMPERES control dial. To preset the desired level of current and voltage during operation, hold in the HIGH VOLTAGE OFF switch and rotate the appropriate control dial while noting its corresponding meter reading. Release the HIGH VOLTAGE OFF switch. ALWAYS OPERATE THE UNIT WITH THE COVER ON. A fan maintains safe operating temperature in 600W1200W power supplies by drawing air over the circuit components. The cover must be on in order to direct the air flow over the areas that need cooling. In operation, the unit must be placed so that the air intake and the fan exhaust are clear of obstructions that might impede the flow of air. The 10W-300W units do not use forced air cooling. Simply maintain ambient temperature specifications. NOTE: No actual output is being produced at this stage. K) Depress the HIGH VOLTAGE ON switch. The light inside the switch should light up and the output will slow start to the preset level output voltage and/or output current. 3.2 Standard Features A note on remote interface circuitry and remote signal grounding. Whenever possible, electrical isolation should be provided when interfacing with any high voltage power supply. For power control signals such as EXTERNAL INTERLOCK, HIGH VOLTAGE OFF, AND HIGH VOLTAGE ON, isolated relay contacts should be used. For status signals and control signals such as HIGH VOLTAGE ON, HIGH VOLTAGE OFF, and EXTERNAL INHIBIT, etc., opto-isolation should be used. If possible, analog programming and monitoring signals should be isolated via analog isolation amplifiers. Spellman application engineers are available to assist in interface circuitry design. All interface cables should be properly shielded. All power supply signals should be referenced to the power supplies signal ground on the rea external interface. NOTE: The SL Series is equipped with a slow start circuit that ramps the output up to its maximum setting in approximately 6 seconds after the HIGH VOLTAGE ON switch is depressed. L) To terminate the generation of output power, depress the HIGH VOLTAGE OFF switch. In the HIGH VOLTAGE OFF mode the power supply’s fault and interface circuits are still active. M) To turn off the power supply, turn the circuit breaker to the off position (0). NOTE: If a power supply fault, or system monitoring fault occurs, the power supply will revert to the POWER DOWN mode. In this mode the output power will be turned off. The HV OFF lamp will be off. To reset, depress the HV OFF switch. WARNING AFTER TURNOFF, DO NOT HANDLE THE LOAD UNTIL THE CAPACITANCE HAS BEEN DISCHARGED! LOAD CAPACITANCE MAY BE DISCHARGED BY SHORTING TO GROUND. REMOTE PROGRAMMING: Allows remote adjustment of the output voltage and current via an external voltage source. (Output power is also remotely controllable with the CPC and APT options). In local control (front panel control), jumpers are installed on the external interface TB1 (or J5) in the rear of the chassis between TB-10 (J510) and TB1-11 (J5-11) for voltage control and between TB1-8 (J5-8) and TB1-9 (J5-9) for current control. For remote programming, the jumpers are removed and a positive voltage source, from 0V to 10V, is applied to the appropriate terminals. Programming signals should be referenced to TB1-1 (J5-1), signal ground. By adjusting the voltage source from 0V (zero output) to 10V (full rated output), the desired output can be selected. See Figure 3.2A on page 13 for the wiring diagram and specifications. WARNING THE VOLTMETER ON THE POWER SUPPLY FRONT PANEL DOES NOT READ THE OUTPUT VOLTAGE WHEN THE POWER IS TURNED OFF, EVEN IF A CHARGE STILL EXISTS ON THE LOAD. An alternate method of controlling the output remotely is by using external resistance, such as a potentiometer or a SL SERIES MANUAL 8 118006-001 REV V resistor network. For remote control the jumpers are removed and the desired register configuration installed. See Figure 3.2B on page 13 for the wiring diagram. REMOTE MONITOR: Test points are made available at the terminal block on the rear of the chassis for monitoring the voltage and current output. (Output power monitor is included with the CPC and APT option). The test points are always positive regardless of the output polarity where 0V to 10V equals 0 to 100% of the output 0.5%. Test points have an output impedance of 5K ohms. See Figure 3.3 on page 14 for the test point designation. REMOTE CONTROL: Remote control of the HIGH VOLTAGE ON and HIGH VOLTAGE OFF can be accomplished via the rear panel interface. HIGH VOLTAGE OFF and HIGH VOLTAGE ON can be controlled by momentary normally closed and normally open contacts respectively. See Figure 3.4 on page 14 for the recommended interface. EXTERNAL INHIBIT: Allows the user to inhibit the power supply output without switching HIGH VOLTAGE OFF control. This circuit can be used to generate fast slewing output waveforms or control of high voltage generation as in Laser and Capacitor discharge applications. The maximum inhibit rate should not exceed 5Hz. Consult the factory for higher repetition rates or high pulse load applications. See Figure 3.5 on 15 for the recommended interface circuit. the interlock circuit is closed. If the interlock is not being used, the jumper installed on the terminals before shipping must be in place. If the jumper is missing, or there is an opening between the interlock terminals, the unit’s high voltage inverter will be disabled. During high voltage operation, revert to the HIGH VOLTAGE OFF mode. Subsequent closing of the interlock circuit will NOT return the unit to the HIGH VOLTAGE ON mode. This must be accomplished by depressing the HIGH VOLTAGE ON switch. See Figure 3.6 on page 15 for the recommended interface circuit The ARC COUNT feature will allow the user to program the ARC fault parameters. The ARC indicator on the front panel will illuminate for approximately one second after each arc has occurred. The power supply can be programmed to trip the POWER DOWN mode if an arc occurs. WARNING The standard feature is programmed to trip the power supply if 8 arcs occur within a twenty second period. IT IS EXTREMELY DANGEROUS TO USE THIS INHIBIT CIRCUIT TO INHIBIT HIGH VOLTAGE GENERATION FOR THE PURPOSE OF SERVICING OR APPROACHING ANY AREA OR LOAD CONSIDERED UNSAFE DURING NORMAL USE. EXTERNAL INTERLOCK: Interlock connections are provided on the terminal block TB1-3 (J5-3) and TB1-4 (J5-4) on the rear of the chassis for connection to a safety switch. The unit will not operate unless SL SERIES MANUAL ARC DETECT / ARC QUENCH / ARC COUNT: The ARC DETECT circuit senses dynamic arcing or discharge conditions present at the output load. If an arc occurs, the output is inhibited for one second. After the one second period, the output is ramped up to the previous set level. This ramp is based on the standard six second slow start feature. The ARC DETECT ramp circuit may be disabled by removing CR32 on the Control/Power Pwb. Caution should be observed if this feature is disabled. Discharge rates of greater then 1Hz may cause excessive power dissipation in the power supply’s output limiting resistors. 9 REMOTE HIGH VOLTAGE ON & REMOTE HIGH VOLTAGE OFF: Signals are provided for remote monitoring of the HIGH VOLTAGE ON/OFF status. See Figure 3.7 on page 16 for recommended interface. REMOTE MODE INDICATORS: Signals are provided for remote indication of the control mode status, voltage control, current control, and power control. See Figure 3.8 on page 17 for the recommended interface. 118006-001 REV V It is recommended to connect the load return directly to Pin 1 of TB2 terminal block located on the rear of the high voltage power supply. Load Return 18AWG. Customer Supplied High Voltage Output 1 2 TB1-I/O INTERFACE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 For Remote Control Monitoring Input: 115Vac or 220Vac +/-10% 50/60 Hz, Specified at time of order TB2 High Voltage Load System Ground Cable Shielded High Voltage Output Cable Provided Figure 3.1 -- Typical Operating Setup NOTE: On standard units, TB2-1,-2 are connected to chassis ground internally. SL SERIES MANUAL 10 118006-001 REV V TB1 SIGNAL SIGNAL PARAMETERS 1 Power Supply Common Signal Ground 2 External Inhibit Ground = Inhibit, Open = HV ON 3 External Interlock +15V at Open, <15mA at Closed 4 External Interlock Return Return For Interlock 5 Current Monitor 0 to 10V = 0 to 100% Rated Output 6 kV Test Point 0 to 10V = 0 to 100% Rated Output 7 +10V Reference +10.24V, 1mA Max 8 Remote Current Program In 0 to 10V = 0 to 100% Rated Output 9 Local Current Program Out Front Panel Program Voltage 10 Remote Voltage Program In 0 to 10V = 0 to 100% Rated Output 11 Local Voltage Program Out Front Panel Program Voltage 12 Power Monitor (TB1 only) 0 to 10V = 0 to 100% Rated Power (Optional) 13 Remote Power Program In (TB1 only) 14 Local HV OFF Out +15V at Open, < 25mA at Closed. Connect to HV OFF For FP Operation 15 HV OFF 16 Remote HV ON +15V, 10mA Max = HV ON 17 Remote HV OFF Indicator 0 = HV ON, +15V, 10mA Max = HV OFF 18 Remote HV ON Indicator 0 = HV OFF, +15V, 10mA Max = HV ON 19 Remote Voltage Mode 20 Remote Current Mode 21 Remote Power Mode 22 Remote PS Fault 0 = Fault, +15V, 0.1 mA Max = No Fault 23 +15V Output +15V, 100mA Max 24 Power Supply Common Signal Ground 25 Spare Spare 26 Shield Return Chassis Ground Open Collector 50V Max, 10mA Max On = Active Table 3.1 - Rear Panel Interface 26 pin TB1 SL SERIES MANUAL 11 118006-001 REV V J5 SIGNAL SIGNAL PARAMETERS 1 Power Supply Common Signal Ground 2 External Inhibit Ground = Inhibit, Open = HV ON 3 External Interlock +15V at Open, <15mA at Closed 4 External Interlock Return Return For Interlock 5 Current Monitor 0 to 10V = 0 to 100% Rated Output 6 kV Test Point 0 to 10V = 0 to 100% Rated Output 7 +10V Reference +10.24V, 1mA Max 8 Remote Current Program In 0 to 10V = 0 to 100% Rated Output 9 Local Current Program Out Front Panel Program Voltage 10 Remote Voltage Program In 0 to 10V = 0 to 100% Rated Output 11 Local Voltage Program Out Front Panel Program Voltage 12 EFR (Common) Optional External Fault Relay 13 EFR (Normally Open) 14 Local HV Off Out +15V at Open, < 25mA at Closed. Connect to HV OFF For FP Operation 15 HV OFF 16 Remote HV ON +15V, 10mA Max = HV ON 17 Remote HV OFF Indicator 0 = HV ON, +15V, 10mA Max = HV OFF 18 Remote HV ON Indicator 0 = HV OFF, +15V, 10mA Max = HV ON 19 Remote Voltage Mode 20 Remote Current Mode 21 Remote Power Mode 22 Remote PS Fault 0 = Fault, +15V, 0.1 Ma Max = No Fault 23 +15V Output +15V, 100mA Max 24 Power Supply Common Signal Ground 25 Shield Return Chassis Ground Open Collector 50V Max, 10mA Max On = Active Table 3.2 - Rear Panel Interface 25 pin Mini D SL SERIES MANUAL 12 118006-001 REV V Voltage Source 0-10V = 0-100% of Rated Output It is recommended that analog signals be isolated TB1/J5 via isolation amplifiers. 1 All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply. 2 PS Common 3 4 5 V 6 Remote Current Program + 7 8 Remove jumpers for remote programing Remote Voltage Program V + Z in = 10M 9 10 Z in = 10M 11 Figure 3.2A -- Wiring Diagram for Remote Programming Via Voltage TB1/J5 Fully Counterclockwise = Zero Output Fully Clockwise = 100% of Rated Output 1 All cables should be shielded with the shields 2 being returned to the chassis ground of the High Voltage Power Supply. If connections to external potentiometers are excessively long (>10ft), motorized potentiometers are recommended. Remote Voltage Control 3 4 5 7 8 Remote Current Control 20k 6 Remove jumpers for remote programing 20k PS Common CW CW +10.32V 1mA max. Z in = 10M 9 10 Z in = 10M 11 Figure 3.2B -- Wiring Diagram for Remote Programming Via External SL SERIES MANUAL 13 118006-001 REV V It is recommended that analog signals be isolated via isolation amplifiers. All cables should be shielded with the shield being returned to the chassis ground of the high voltage power supply. TB1/J5 1 PS Common 2 M 3 4 Current Monitor M + + 5 Z out = 4.99k ohms 6 Voltage Monitor +/-0.1% Z out = 4.99k ohms +/-0.1% 7 Figure 3.3 -- Remote Monitor Test Point Designations S1 must be closed to enable HIGH VOLTAGE. Momentary closure of S2 will enable HIGH VOLTAGE ON. Opening S1 will disable HIGH VOLTAGE ON and switch the unit to the HIGH VOLTAGE OFF mode. It is recommended to use relay contacts for S1 and S2. Relays should be located as close as possible to the high voltage power supply. Coils should be driven from isolated sources. Signals are at 15Vdc, 25mA max., and are only to be used for contact closure. TB 1/J5 S1 S1 = Remote High Voltage Off 14 Remove jumper for remote high voltage control 15 S2 All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply. S2 = Remote High Voltage On 16 17 Figure 3.4 Remote Control Of High Voltage On and High Voltage Off Interface SL SERIES MANUAL 14 118006-001 REV V The transistor should be located as close as possible to the power supply All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply. TB1/J5 +15V 1 Transistor ON Inhibits High Voltage PS Common 2 2.2k 3 High Voltage Power Supply Internal inhibit circuitry. 4 Figure 3.5 -- External Inhibit Interface Circuit Relay contacts are recommended for S1. The relay should be located as close as possible to the power supply. Signals are at 15Vdc, 25mA max and are only to be used for contact closure. TB1/J5 1 External Safety Interlock Control 2 Remove jumper for remote external interlock 3 S1 4 S1 Open = Interlock Open S1 Closed = Interlock Closed 5 All cables should be shielded with the shields being returned to the chassis ground of the High Voltage Power Supply. Figure 3.6 -- External Interlock Interface SL SERIES MANUAL 15 118006-001 REV V 12Vdc lamps or relay coils may replace opto-couplers. Opto-couplers, lamps or relays should be located as close as possible to the high voltage power supply. All cables should be shielded with the shields being d to the chassis ground of the High Voltage Power Supply. returned TB1/J5 1 PS Common 2 3 General Purpose Opto-Coupler 4 5 To High Voltage OFF Indicator 6 7 8 General Purpose Opto-Coupler 9 To High Voltage ON Indicator 10 11 12 13 14 P/O High Voltage Power Supply 1/4 W 15 16 R Limit 17 R Limit 1/4 W 18 Signals are ~ 15Vdc, 10mA max. R Limit must be > 500 Figure 3.7 -- Remote High Voltage On and Remote High Voltage Off Indicator SL SERIES MANUAL 16 118006-001 REV V TB1/J5 23 +15V, 100mA max. Voltage Control Indicator R1 19 R2 20 R3 21 R limit 10mA max. Current Control Indicator 10mA max. Power Control Indicator R limit R limit 10mA max. R limit must be > 1kW R1-R3=680W 1/4W Figure 3.8 -- Remote Mode Indicators Interface SL SERIES MANUAL 17 118006-001 REV V Chapter 4 PRINCIPLES OF OPERATION The SL Series of high voltage power supplies utilizes sophisticated power conversion technology. A variety of analog, digital and power conversion techniques are used throughout. The intention of the Principles of Operation is to introduce the basic function blocks that comprise the SL power supply. For details on a specific circuit, consult Spellman’s Engineering Department. WARNING The energy levels used and generated by the power supply can be lethal! Do not attempt to operate the power supply unless the user has a sufficient knowledge of the dangers and hazards of working with high voltage. Do not attempt to approach or touch any internal or external circuits or components that are connected or have been connected to the power supply. Be certain to discharge any stored energy that may be present before and after the power supply is used. Consult IEEE recommended practices for safety in high voltage testing #510-1983. See Table 4.1 for a list of the main assemblies found in a typical SL power supply. Due to the many variations within the SL Series, drawing numbers may differ from unit to unit. The SL power supply is basically an AC to DC power converter. Within the power supply, conversions of AC to DC then to high frequency AC, then to high voltage DC take place. By reviewing further the sub-assemblies, a basic understanding of the process can be gained. 4.2 Line Rectification And Filtering 4.1 Chassis The SL is a compact, high efficiency, high voltage power supply. The power supply can supply up to 1200 watts of DC power. (Output power capability may be higher or lower depending upon the model ordered). Output voltages of up to 130kV can be generated. SL SERIES MANUAL Basic single phase rectification provides the DC voltage for the high frequency inverter. 18 118006-001 REV V ASSEMBLY TITLE ASSEMBLY DRAWING NO. SL Chassis (10W-300W) SL Chassis (600W-1200W) Control / Power PWB (to 300W) Control / Power PWB (600W-1200W) High Voltage Assy (to 300W) High Voltage Assy (600W-1200W) Front Panel PWB J5 TB1 403919-016 403917-001 403920-001 403918-001 404065-005 403911-001 404581-001 403935-TAB 403930-TAB 403931-TAB 403895-001 Table 4.1-List of Main Assemblies In general, the following variations can be ordered: 100Vac 10%, 50 to 60Hz, single phase. 115Vac 10%, 50 to 60Hz, single phase. 200Vac 10%, 50 to 60Hz, single phase. 220Vac 10%, 50 to 60Hz, single phase. SCHEMATIC DRAWING NO. J5 TB1 440643-003 440530-001 440643-004 440617-001 440570-002 440528-001 440687-002 440538-001 440533-001 440534-001 440525-001 energized to short the NTC or resistor limiters. This DC voltage is supplied to the high frequency inverter. The DC rails are connected to the high frequency rail capacitors. These capacitors are high frequency, low loss type, which provides the energy storage for the high frequency inverter. 4.3 Inverter Other input voltages can be accommodated. If the user is unsure of which input voltage option is supplied, check the serial tag on the rear of the power supply or consult Spellman’s Sales Department. The inverter is a series resonant, series/parallel loaded topology. A proprietary control scheme is used for regulating the power generated from the inverter. The switching devices are Mosfets up to 300W, and IGBT’s for power levels above 300W. These devices provide high frequency switching to control the resonant current flow. The typical resonant operating period is approximately 10 Seconds. The gate control for the switching devices is provided by the application circuitry located on the CONTROL/POWER PWB. The CONTROL/POWER PWB also provides circuitry for sensing shoot thru and overcurrent conditions in the inverter. Circuit protection is provided by a front panel circuit breaker. The circuit breaker is a fast acting magnetic trip type circuit breaker. The line input is connected directly to the line side of the circuit breaker whereas the load side is connected to the CONTROL/POWER PWB. The load side of the breaker is also connected to a step-down type line transformer. This transformer provides voltage for housekeeping and control circuit power. WARNING 4.4 High Voltage Transformer LINE VOLTAGE IS PRESENT WHENEVER THE POWER SUPPLY IS CONNECTED TO EXTERNAL LINE VOLTAGES. BE SURE TO DISCONNECT THE LINE CORD BEFORE OPENING THE UNIT. ALLOW 5 MINUTES FOR INTERNAL CAPACITANCE TO DISCHARGE BEFORE REMOVING ANY COVER. The output of the High Frequency Resonant Inverter is connected to the primary of the High Voltage Transformer. The High Voltage Transformer is a set up type. Typical secondary voltages are in the range of 1kV to 4.5kV depending upon the output voltage ratings. When the circuit breaker is ON, voltage is applied to an isolated diode rectifier bridge, which contains the rectifier diodes used for line voltage rectification. The output of this bridge rectifier is connected to a capacitor filter. Capacitors are initially charged through NTC type or resistive inrush limiters. For 150W and higher configurations, approximately 3 seconds after the circuit breaker is turned on, a relay is SL SERIES MANUAL 19 118006-001 REV V An arc sense circuit provides sensing, quench and indicator of arc conditions. Consult the operation manual for a detailed description of the arc sense control. 4.5 High Voltage Assembly The High Voltage Assembly will vary depending upon the model ordered. The circuitry typically consists of a full wave, full bridge, or full wave doubler for voltage outputs in the range of 1kV to 8kV. The higher voltage ranges utilize various parallel, series arrangements of a full wave voltage doubler. Current feedback from the high voltage rectifier is sent to sense resistors located on the High Voltage Assembly. Calibrated feedback is then sent to the applicable circuitry on the Control/Power Board. U12 and U13 circuits provide visual indication of the control mode, which is in operation. These signals are sent to the FRONT PANEL ASSEMBLY for front panel status indication. Output filtering is typically provided by an R-C type filter. Voltage feedback for regulation and monitoring is provided by a high bandwidth resistive/capacitive divider. Current feedback for regulation and monitoring is provided by a sense resistor connected at the low voltage end of the High Voltage Rectifier/Multiplier Circuit. The resonant control circuitry consists of a voltage to frequency and a voltage to pulse width converter. U17 generates all frequency and pulse width control signals. U16 provides specific control functions for the resonant control. 4.6 Control/Power PWB The majority of control circuits for power supply controls are located on the CONTROL/POWER PWB. +15VDC, 15VDC, and +10VDC is generated on the CONTROL/POWER PWB. High Voltage On/Off control is accomplished by K3, and its associated circuitry. Interlock control is provided by K4. Power supply inhibit circuits are provided by U22 and K3. System Fault control and Indication is provided by U19, U20 and U21, and associated circuitry. Diagnostic signals are latched and then sent to the FRONT PANEL ASSEMBLY for status indication. Voltage feedback from the high voltage divider is sent to the control board via a mass terminated ribbon cable. Gain adjustment is provided on the HV PWB. The KV feedback signal is sent to the front panel DVM and to the REAR PANEL TERMINAL BLOCK for remote monitoring. K2 provides switching between feedback and program signal for the front panel DVM’s. This allows the user to preset the desired output before energizing high voltage. 4.7 Front Panel Assembly Front Panel controls, meters and status indications are connected to the FRONT PANEL PWB. The FRONT PANEL PWB interfaces directly to the CONTROL/POWER PWB. 4.8 Options Due to the many variations of models and options provided in the SL Series, details of actual circuits used may differ slightly from the above descriptions. Consult Spellman’s Engineering Department for questions regarding the principles of operation for the SL Series. Program voltages are typically ramped up to set level by a slow start circuit. SL SERIES MANUAL 20 118006-001 REV V Chapter 5 OPTIONS T he options available for this power supply are described in this section. Interface diagrams are shown where required. Options are specified by including the option code in the model number as described in Section 1.5. 5.5 Extra Length Output Cable--LL(ft) Standard output cable is 10 feet of shielded high voltage cable. Other lengths may be specified in multiples of 10 feet. 5.1 Adjustable Overload Trip --AOL 5.6 Floating Ground--FG The overload trip protection feature rapidly shuts down the high voltage output when the current exceeds the limit set by the current control dial on the front panel. A fast acting circuit inhibits the generation of high voltage and reverts the unit to POWER DOWN mode, illuminating the OVER CURRENT indicator. When adjustable overload trip is provided, it replaces the standard current regulation feature. The floating ground option allows isolation of the power supply common from the chassis ground. TB2 located on the rear panel provides connection to the power supply common circuit and to the chassis ground. This signal can be used for a variety of applications. A typical application for FG is for connection of an external meter or circuit into the FG signal point. This circuit can monitor actual current flow at a low voltage level. See Figure 5.1 for typical connection to the floating ground terminal. 5.2 220Vac Single Phase Input--220 NOTE: On standard units, TB2-1 and TB2-2 are connected to the chassis grounded internally. Maximum floating ground voltage is 15V. Typically, the total leakage current of the floating terminal to the chassis terminal is less that 1A. It is important to realize there are two separate components to this leakage current. The first component is leakage current caused by the coupling of the 60Hz line magnetics to the power supply circuitry. This component can be measured when the power supply is ON and in the HIGH VOLTAGE OFF mode. The second component is the leakage current caused by the coupling of the HVDC circuits to the chassis. The component can be measured by first recording the leakage current in the HV OFF mode, and then recording the leakage at the desired HV setting. The difference between the two values is the HVDC leakage current. SL Series power supplies with the 220Vac input option will operate from an input voltage of 220Vac RMS 10%, 50 to 60Hz, single phase. 5.3 No Slow Start--NSS The no slow start option causes the output voltage of the power supply to rise (within 50 msec) to the rated voltage upon depressing the HIGH VOLTAGE ON switch. 5.4 Non-Standard Slow Start--SS(x) The non-standard slow start option allows the gradual rise time of the output voltage to be different from the standard of six seconds. To order the option place the time desired in seconds after the suffix letter, i.e. SS (10) denotes a 10 second rise time. SL SERIES MANUAL 21 118006-001 REV V 5.7 Floating Ground Low Leakage--FGLL 5.9 Arc Trip Option--AT When this option is ordered, the Arc Count circuit is set so the unit trips to Standby after 1 count. One of the applications for this option is for sensing a material breakdown under an applied high voltage. The Low Leakage floating ground option also provides isolation of the power supply common from the chassis ground with a maximum leakage current of 10nA. The typical connections are the same as for the regular Floating Ground Option described in Section 5.6. As stated above in the FG Option description, the FGLL leakage current is also comprised of two components. The 60Hz component is the same as the FG option (<1A). However, in the FGLL option the HVDC leakage current is less than 10 nanoAmps. 5.10 Reversible Polarity Option--PN 5.10.1 Models from 1 kV to 8kV For units from 1 kV to 8kV, the polarity may be reversed in the field by following the procedures shown in Figure 5.3. IMPORTANT 5.10.2 Models From 10Kv To 130Kv The power supply common must be connected to the chassis ground through a low impedance circuit. The power supply common is clamped to the chassis ground using a power zener diode. This diode is not intended to clamp under continuous operation. On higher current units the power dissipation within the zener diode can be excessive if allowed to clamp. When this option is ordered, a second multiplier is provided to permit the user to replace the existing multiplier with another of reverse polarity. See Figure 5.4 for a step by step procedure. 5.11 Instant On--IO When the Instant On Option is ordered, the High Voltage is enabled as soon as line voltage is applied when the circuit breaker is in the ON position. (See Figure 5.7) 5.8 Adjustable Power Trip/Constant Power Control To enable Instant On, keep the jumper between TB1-14 and TB1-15 attached. Connect an additional jumper from TB1-15 to TB1-16 as shown in Figure 5.7. (TB1 only)--APT/CPC CAUTION The power control options allow monitoring and control of the power supply output power. The APT option allows the user to remotely adjust the power limit for the power supply. If the power limit is exceeded, the unit will shut down with an OVERPOWER fault. The CPC option allows power regulation via an internal preset potentiometer, or a remote program source. When the unit is in power regulation, the POWER CONTROL status indicator will be illuminated. See Figure 5.2 for remote interface. SL SERIES MANUAL The Power Supply will generate programmed High Voltage whenever the circuit breaker is in the ON position, and line voltage is applied. 22 118006-001 REV V 5.12 Bipolar Master/Slave Option--MS The Bipolar Master/Slave option allows two supplies of the same voltage rating but opposite polarities to functions as a single tracking bipolar power supply. The positive supply is configured as the Master, the negative supply is configured as the Slave. This is accomplished by connecting the Voltage Test Point of the positive (Master) unit to the Voltage programming of the negative (Slave) unit. See Figure 5-8. The Master’s voltage programming signal will provide control of both power supplies from zero to rated output voltage. The negative polarity will track the positive polarity within 1% from 10% to full rated output. Performance specifications are governed by individual unit characteristics. The two units must be connected independently to their respective loads and ground. Arc (Shutdown): Arc sensing circuit has shut down the supply due to excessive arcing. Overpower: The power supply has exceeded the internally set power limit level, if such circuitry is installed. With the installation of the EFR option for TB1, if any of these faults occur, a relay will be activated to provide a remote indication that the power supply has reverted to the “power down” mode. The common, normally open and normally closed set of contacts are provided. Relay contacts are rated at 1A at 30Vdc or 0.5A at 48Vac. Connections on the rear panel Terminal Block (TB1) can be made as follows: 5.13 External Fault Relay Option EFR TB1-23 (J5-12) Relay Common TB1-24 (J5-NA) Normally Closed TB1-25 (J5-13) Normally Open Resetting the front panel and EFR relay is accomplished by depressing the green front panel HV OFF push-button switch, which reverts the power supply back to the “standby” mode. Removal and reapplication of the AC line input voltage will also reset any fault. The external fault relay option provides a set of customer accessible relay contacts that are controlled by the fault status circuitry of the applicable SL Series power supply. A standard SL power supply will revert to the “power down” mode with a visual front panel indication if any of the following fault conditions occur: The circuitry and components required for the EFR option are installed at the factory when this option is ordered. Overvoltage: Greater than 110% of maximum output voltage was produced by the power supply. 5.14 Custom Designed Models-X# Overcurrent: Greater than 104% of maximum output current was produced by the power supply or the AOL circuitry was activated. Units built to customer specification are assigned an X number by the factory. If this unit is an X model, a specification control sheet is added at the end of the test of this instruction manual. Overtemperature: Excessive temperature has been sensed within the chassis. Regulation Error: Lack of required output power to maintain regulation SL SERIES MANUAL Spellman welcomes the opportunity to customize units to fit your requirements or to develop new products for your applications. Contact the Spellman Sales Department with your needs. 23 118006-001 REV V Possible FG termination circuits To internal high voltage return circuits. 1 CR1 Pin 2 internally connected to power supply chassis. FG option units are shipped with external jumper. M 2 TB2 * IMPORTANT: Power dissipation in CR1 should not exceed 1/2W. This can be accomplished by keeping TB3-1 and TB3-2 voltage below Zener voltage. CR1 is for safety and transient protection only, and is not designed for continuous clamping. Zener voltage is 18V standard. Up to 50V is available. Consult factory. Figure 5.1 -- Floating Ground Interface Circuit TB1 1 2 Remove internal jumper, JP1 ON Control/Pwr PWB for remote Programing. (Jumper connects internal, pot, factory set at 103%of max power). 3 4 5 6 12 13 M + Remote Power Monitor 0-10V =0-100% power output Zout= 4.99k ohm0.1% Z in =10Mohm V Remote Power Program + 20K ohm min. Remote Power Programming potentiometer 7 Figure 5.2 -- Adjustable Power Remote Interface TB1 Only SL SERIES MANUAL 24 118006-001 REV V TABLE 1 SW1 AND SW2 SWITCH SETTINGS POLARITY SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW2-1 SW2-2 SW2-3 SW2-4 SW2-5 SW2-6 POSITIVE CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED OPEN OPEN OPEN OPEN OPEN OPEN NEGATIVE OPEN OPEN OPEN OPEN OPEN OPEN CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED 5 1 TURN UNIT OFF, UNPLUG LINE CORD FROM AC OUTLET AND WAIT FOR 5 MINUTES BEFORE PROCEEDING TO CHANGE THE POLARITY OF UNIT. 2 REMOVE COVER BY UNSCREWING AND REMOVING 11 SCREWS THAT MOUNT COVER TO CHASSIS AND FRONT PANEL. 3 REMOVE 4 SETS OF HARDWARE THAT HOLD THE LEXAN COVER TO THE HIGH VOLTAGE BOARD, AND REMOVE COVER. 4 SWAP BLACK AND WHITE WIRES BETWEEN J4 AND J5 AS FOLLOWS: FOR POSITIVE POLARITY: BLACK WIRE ON J4 AND WHITE WIRE ON J5. FOR NEGATIVE POLARITY: WHITE WIRE ON J4 AND BLACK WIRE ON J5. 5 SET SW1 AND SW2 DIP SWITCHES ACCORDING TO TABLE 1 6 CHANGE POSITION OF JP4 JUMPERS ON FRONT PANEL BOARD TO MATCH POLARITY OF UNIT, i.e 2 JUMPERS MUST BE ON "N" POSITIONS FOR NEGATIVE UNITS AND ON "P" POSITIONS FOR POSITIVE UNITS. 7 REINSTALL LEXAN COVER AND RELATED HARDWARE. REINSTALL POWER SUPPLY'S COVER AND ALL HARDWARE BEFORE TURNING UNIT ON. HIGH VOLTAGE BOARD 3 4 NOTE: POWER SUPPLIES THAT UTILIZE CONTROL BOARD P/N 450050-XXX DO NOT REQUIRE STEP 5. A A 10-300 Watt 1kV-8kV chassis 6 POSITIVE CONFIGURATION SHOWN PARTIAL VIEW A-A NOTE: JP4 NOT USED ON SUPPLIES EQUIPPED WITH BFP OPTION Figure 5.3-Polarity Reversal Procedure 10W to 300W, 1kV to 8kV Chassis 5 4 3 T U R N U N IT O F F , U N P L U G L IN E C O R D F R O M A C O U T L E T A N D W A IT F O R 5 M IN U T E S B E F O R E P R O C E E D IN G T O C H A N G E T H E P O L A R IT Y O F U N IT . 2 JB 2 JB 1 5 H IG H V O L T A G E M U L T IP L IE R 6 A A 1 R E M O V E C O V E R B Y U N S C R E W IN G A N D R E M O V IN G 1 1 S C R E W S T H A T M O U N T C O V E R T O C H A S S IS A N D F R O N T P A N E L . 2 U N P L U G H IG H V O L T A G E L E A D S F R O M A S S E M B L Y . 3 U N P L U G C A B L E F R O M J B 1 A N D R E M O V E C A B L E S H IE L D FRO M FASTO N TAB O N BO ARD . 4 U N PLU G C O N N EC TO R FR O M JB 2. 5 REM O VE 2 SC REW S TH AT HO LD TH E PO LYETH YLEN E ENC LO SUR E A N D 2 S C R E W S T H A T M O U N T T H E B O A R D T O T H E C H A S S IS 6 C A R E F U L L Y T IL T U P A N D S L ID E O U T M U L T IP L IE R . 7 IN S T A L L N E W M U L T IP L IE R B Y F O L L O W IN G S T E P S 6 T H R U 2 IN REVERSE. 8 C H A N G E P O S IT IO N O F J P 4 J U M P E R S O N F R O N T P A N E L B O A R D T O M A T C H P O L A R IT Y O F U N IT , i.e 2 J U M P E R S M U S T B E O N "N " P O S IT IO N S F O R N E G A T IV E U N IT S A N D O N "P " P O S IT IO N S F O R P O S IT IV E U N IT S . 9 IN S T A L L C O V E R A N D A L L H A R D W A R E B A C K B E F O R E T U R N IN G U N IT O N . 1 0 -3 0 0 W a tt 1 0 k V -1 3 0 k V c h a s s is 8 P O S IT IV E C O N F IG U R A T IO N SHOW N P A R T IA L V IE W A -A N O TE: JP4 N O T U SED O N S U P P L IE S E Q U IP P E D W IT H B F P O P T IO N F ig u re 5 .4 -P o la rity R e v e rs a l P ro c e d u re 1 0 W to 3 0 0 W , 1 0 k V to 1 3 0 k V C h a s s is SL SERIES MANUAL 25 118006-001 REV V E1 TB1 J4 TURN UNIT OFF, UNPLUG LINE CORD FROM AC OUTLET AND WAIT FOR 5 MINUTES BEFORE PROCEEDING TO CHANGE THE HIGH VOLTAGE MULTIPLIER. J1 CR4 JP12 JP13 J3 J2 JB1 C2E1 C2E1 L2 J3 JB2 E2 ASSY 404230REV.A Q3 L1 C1 J1 J4 1 REMOVE COVER BY UNSCREWING AND REMOVING 12 SCREWS THAT MOUNT COVER TO CHASSIS AND FRONT PANEL. E2 Q2 J2 C1 R26 G1 E1 2 E9 E2D G2 G1 E1 E14 E13 E11 E2D G2 E30 E28 E20 E27 2 REMOVE 4 SETS OF HARDWARE THAT HOLD THE LEXAN COVER TO THE HIGH VOLTAGE BOARD, AND REMOVE COVER. 3 JB5 3 SWAP BLACK AND WHITE WIRES BETWEEN J4 AND J5 AS FOLLOWS: FOR POSITIVE POLARITY: BLACK WIRE ON J4 AND WHITE WIRE ON J5. FOR NEGATIVE POLARITY: WHITE WIRE ON J4 AND BLACK WIRE ON J5. DANGER HIGH VOLTAGE OUTPUT VOLTAGE: OUTPUT POWER: OUTPUT CURRENT: POLARITY: SPECIAL FEATURES: 2 PART NO.: MODEL: JB7 SPELLMAN E38 HIGH VOLTAGE ELECTRONICS CORP PLAINVIEW, NY 11803 MADE IN USA JB8 E39 220V JB9 115V E37 115V T1 1 E36 4 REINSTALL LEXAN COVER AND RELATED HARDWARE. REINSTALL POWER SUPPLY'S COVER AND ALL HARDWARE BEFORE TURNING UNIT ON. E2 JB2 4 JB2 LINE 1 LOAD JB3 600 to 1200 Watt 1kV to 8kV chassis Figure 5.5 -- Polarity Reversal Procedures 600W to 1200W, 1kV to 8kV Chassis 5 6 4 3 TURN UNIT OFF, UNPLUG LINE CORD FROM AC OUTLET AND WAIT FOR 5 MINUTES BEFORE PROCEEDING TO CHANGE THE HIGH VOLTAGE MULTIPLIER. 2 REMOVE COVER BY UNSCREWING AND REMOVING 12 SCREWS THAT MOUNT COVER TO CHASSIS AND FRONT PANEL. 1 1 TB1 J4 E3 J1 JP12 JP13 J3 J2 REV. ASSY A 404129-001 JB1 E4 JB2 1 C2E1 1 4 JB3 J4 E2 C2E1 L2 REV. A 5 ASSY 403935SL 600W-1200W CONTROL/POWER BD S/S REV. A E2 E2 Q2 Q3 L1 C1 G1 E1 E9 C1 E2D G2 G1 E1 E14 E13 E11 E2D G2 3 UNPLUG HIGH VOLTAGE LEADS FROM ASSEMBLY. 4 UNPLUG CABLE FROM JB1 AND REMOVE CABLE SHIELD FROM FASTON TAB ON BOARD. 5 UNPLUG CONNECTOR FROM JB2. 6 REMOVE 2 SCREWS THAT HOLD THE POLYETHYLENE ENCLOSURE AND THE BOARD TO THE CHASSIS 7 CAREFULLY TILT UP AND SLIDE OUT MULTIPLIER. 8 INSTALL NEW MULTIPLIER BY FOLLOWING STEPS 6 THRU 2 IN REVERSE. 9 INSTALL COVER AND ALL HARDWARE BACK BEFORE TURNING UNIT ON. E30 E28 E20 E27 JB1 HIGH VOLTAGE MULTIPLIER JB5 7 E38 JB6 E39 220V JB7 115V E37 T1 115V 1 E36 E2 JB2 JB2 4 1 LINE LOAD JB3 600 to 1200 Watts 10kV to 120kV chassis Figure 5.6 -- Polarity Reversal Procedure 600W to1200W, 10kV to 120kV Chassis SL SERIES MANUAL 26 118006-001 REV V TB1/J5 14 Existing jumper 15 Jumper TB1 15 to 16 for Instant ON option Figure 5.7 -- Instant ON 16 17 POSITIVE (MASTER) SUPPLY P.S. Common kV Test Point OUT NEGATIVE (SLAVE) SUPPLY TB1/J5 TB1/J5 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 P.S. Common Remote Voltage Program IN * REMOVE JUMPER LINKING 10-11 INSTALLATION NOTE Keep Interconnecting Wires as Short as possible. Use of Twisted Wire Pair or Shielded/Coaxial wire is recommended. Figure 5.8 -- Bipolar/ Slave Option SL SERIES MANUAL 27 118006-001 REV V Chapter 6 MAINTENANCE T his section describes periodic performance testing procedures. servicing and 6.2 Performance Test WARNING WARNING HIGH VOLTAGE IS DANGEROUS. THIS POWER SUPPLY GENERATES VOLTAGES THAT ARE DANGEROUS AND MAY BE FATAL . OBSERVE EXTREME CAUTION WHEN WORKING WITH HIGH VOLTAGE. ONLY QUALIFIED PERSONNEL SHOULD PERFORM THESE TESTS. High voltage test procedures are described in Bulletin STP-783, Standard Test Procedures for High Voltage Power Supplies. Copies can be obtained from the Spellman Customer Service Department. Test equipment, including an oscilloscope, a high impedance voltmeter, and a high voltage divider such as the Spellman HVD100 or HVD-200, is needed for performance tests. All test components must be rated for operating voltage. 6.1 Periodic Servicing Approximately once a year (more often in high dust environments), disconnect the power to the unit and remove the top cover. Use compressed air to blow dust out of the inside of the unit. Avoid touching or handling the high voltage assembly. Be sure that the fan (600W1200W units only) is not obstructed and spins freely. The fan has sealed bearings and does not need lubrication. Be sure to replace the top cover before operating for proper cooling. SL SERIES MANUAL 6.3 High Voltage Dividers High voltage dividers for precise measurements of output voltage with an accuracy up to 0.1% are available. An HVD-100 is used for voltages up to 100KV. An HVD200 measures up to 200KV. The Spellman divider is designed for use with differential voltmeters or high impedance digital voltmeters. The high input impedance is ideal for measuring high voltage low current sources, which would be overloaded by traditional lower impedance dividers. 28 118006-001 REV V Chapter 7 REPLACEMENT PARTS 7.1 Replacement Parts 7.2 Correspondence and Ordering Spare Parts Contact the Spellman Customer Service Department for parts lists for specific models. Each power supply has an identification label on the rear of the chassis that bears its model and serial number. Parts and subassemblies for Spellman’s high voltage power supplies are available. It is recommended that only qualified personnel perform the repairs. High voltage is dangerous; even minor mistakes in repairs can have serious consequences. When requesting engineering or applications information, please state the model and serial number of the power supply. If specific components or circuit sections are involved in the inquiry, it is helpful to indicate the component symbol number(s) shown on the applicable schematic diagram. When requesting parts please give the model number and serial number of the power supply. When ordering spare parts, please specify the part number, the component function, and the model and serial number of the unit. SL SERIES MANUAL 29 118006-001 REV V Chapter 8 FACTORY SERVICE 8.3 8.1 Warranty Repairs During the Warranty period, Spellman will repair all units free of charge. The Warranty is void if the unit is worked on by other than Spellman personnel. See the Warranty in the rear of this manual for more information. Follow the return procedures described in Section 8.2. The customer shall pay for shipping to and from Spellman. Ordering Options and Modifications Many of the options listed in Chapter 5 can be retrofitted into Spellman’s power supplies by our factory. For prices and arrangements, contact the Spellman Sales Department. 8.4 Shipping Instructions All power supplies returned to Spellman must be sent shipping prepaid. Pack the units carefully and securely in a suitable container, preferably in the original container, if available. The power supply should be surrounded by at least four inches of shock absorbing material. Please return all associated materials, i.e. high voltage output cables, interconnection cables, etc., so that we can examine and test the entire system. 8.2 Factory Service Procedures Spellman has a well-equipped factory repair department. If a unit is returned to the factory for calibration or repair, a detailed description of the specific problem should be attached. For all units returned for repair, please obtain an authorization to ship from the Customer Service Department, either by phone or mail prior to shipping. When you call, please state the model and serial numbers, which are on the plate on the rear of the power supply, and the purchase order number for the repair. A Return Material Authorization Code Number (RMA Number) is needed for all returns. This RMA Number should be marked clearly on the outside of the shipping container. Packages received without an RMA Number will be returned to the customer. The Customer shall pay for shipping to and from Spellman. All correspondence and phone calls should be directed to: Spellman High Voltage Electronics Corp. 475 Wireless Boulevard Hauppauge, New York 11788 TEL: (631) 630-3000 FAX: (631) 435-1620 E-Mail: sales@Spellmanhv.com A preliminary estimate for repairs will be given by phone by Customer Service. A purchase order for this amount is requested upon issuance of the RMA Number. A more detailed estimate will be made when the power supply is received at the Spellman Repair Center. In the event that repair work is extensive, Spellman will call to seek additional authorization from your company before completing the repairs. SL SERIES MANUAL 30 118006-001 REV V To obtain information on Spellman’s product warranty please visit our website at: http://www.spellmanhv.com/en/About/Warranty.aspx