21, rue d’Artois, F-75008 PARIS http : //www.cigre.org A2-307 CIGRE 2014 EXPERIENCE WITH THE FIRST 230 kV SHELL TYPE AUTOTRANSFORMER RETRO-FILLED WITH NATURAL ESTER ON MEXICAN GRID R. OCÓN * Industrias IEM R. MONTES Mexican Utility R. LIÑAN, A. GUZMÁN Instituto de Investigaciones Eléctricas MÉXICO SUMMARY The improvement of performance of power transformers is a permanent care for manufacturers and utilities since these constitute one of the most expensive and strategic components of electric power transmission and distribution systems. Alternative fluids such as natural and synthetic esters are increasingly being used for distribution and power transformers as a substitute of mineral oil. Some advantages are its higher fire and flash points and because are less harmful for the environment; also it was shown that these fluids can extend transformer insulation life. A research project was developed between Mexican utility, IIE (Electrical Research Institute) and transformer manufacturer in order to evaluate natural ester fluid performance in a 230 kV shell type autotransformer, installed in a strategically location on the Mexican grid. Autotransformer name plate data are: single phase, 25/33.33 MVA, 230/115/13.8 kV, shell type design. The autotransformer was original built in 1978, and retro-filled in 2011 with natural ester. The research project followed different stages, first a study of transformer retro-filled viability was carried out, including an analysis of dielectric and thermal autotransformer performance operating with natural ester; second the transformer condition was evaluated with field testing and then transformer was taken to manufacturer factory in order to replace bushings, gaskets, re-design oil preservation system and install on-line monitoring equipment. Full factory tests at 100% testing levels was performed on HV Laboratory, with the autotransformer filled first with mineral oil and then repeated retro-filled with natural ester, a comparison between test results was made in order to evaluate the new operation conditions of the autotransformer. Besides, considerable studies were conducted by IIE to investigate dielectric strength using various electrode configurations with uniform and non-uniform electrical fields, moisture sensitivity, partial discharge, bacterial growth, thermal and infrared characteristics, oxidation stability, material compatibility and temperature performance of the vegetable oil used. Finally after successful performance during factory testing, the autotransformer was shipped, installed and energized on April 2011; since then, it has been monitoring. On-line monitoring equipment includes optical fiber sensors located on winding leads and on load tap changer (OLTC), and on-line dissolved gas analysis (DGA). Also, field tests like FDS (Frequency Dielectric Spectroscopy), FRA (Frequency Response Analysis), infrared thermography and acoustic partial discharges, are routinely performed in order to evaluate actual autotransformer condition. * rocon@condumex.com.mx Stray gassing formation of ethane was observed during the first months of operation, which is the unexpected gas formation from some oils at relatively low temperatures in the 80 to 250°C range. This is attributed to the stray gassing of FR3™ which is the natural ester used on this autotransformer The paper presents field experience accumulated by the major Mexican utility over the last 2 years of successful autotransformer operation filled with vegetable oil as well as discussion of design aspect explained by the manufacturer and the IIE. Discussion about differences between dielectric test results with mineral and vegetable oil in the autotransformer (impulse and partial discharge tests) are also included on present paper. Main conclusion of this project is that natural esters represent a good alternative as a substitute of mineral oil on power transformers. KEYWORDS Natural ester, autotransformer, shell type, retro-filled, factory testing, vegetable oil. 1. INTRODUCTION The improvement of performance of power transformers is a permanent care for manufacturers and utilities since these constitute one of the most expensive and strategic components of electric power transmission and distribution systems. Alternative fluids such as natural and synthetic esters are increasingly being used for distribution and power transformers as a substitute of mineral oil [1]. Some advantages are its higher fire and flash points; a fire point greater than 300°C, as determined according to ASTM D92, classifies the liquid as a less-flammable liquid. These fluids are less harmful for the environment and it was shown that these fluids can extend transformer insulation life [2,6]. The main transformer oil functions are: as an electrical insulation, cooling media, to protect solid insulation, and as a diagnostic tool for routine evaluation of the condition of electrical equipment over its service life. Mineral oil has been used as an insulation system on transformers since the 1900s, because it’s good aging behavior, low viscosity and low cost. Since the end of 1970´s natural and synthetic esters which have higher flash and fire points than mineral oil, have been developed, and for 2010 over 200 power transformers up to 200 MVA and 242 kV, has been energized and operating filled and retro-filled with natural esters [1]. The main reasons for replacement mineral oils are its poor biodegradability and also the growing international demand for petroleum products, which could lead to serious shortages as soon as the mid-21 century [3]. In Mexico, during 2009, utility initiated a research project in order to evaluate and gain experience with the use of natural esters for high voltage and large power transformers. The project was carried out by IIE (Electrical Research Institute) in conjunction with a transformer manufacturer (Industrias IEM) which selected for retro-filled with vegetable oil, a 230 kV shell type auto-transformer installed at a strategically location on Mexican grid. Although, autotransformer retro-filled process could be done on site, the decision was to take the autotransformer to manufacturer factory; first because it was necessary to replace bushings, gaskets, re-design oil preservation system and to install on-line monitoring equipment, and second, because in this way a complete factory testing could be applied and a better comparison between testing results with the unit filled with mineral oil and then filled with vegetable oil could be done. Selected fluid for substituting mineral oil was FR3™ which is an environmentally friendly coolant made from edible seed oil. It is biodegradable and non-toxic and is classified as a natural ester fluid. A description of the stages and acquired experiences with this project is addresses on following paragraphs. 2. EVALUATION OF SELECTED AUTOTRANSFORMER Selected autotransformer nameplate characteristics are: 230/115/13.8 kV, shell type design, single phase, 60 Hz, 25/33.33 MVA, ONAN/ONAF, 55°C average winding rise, on load tap changer on HV for ± 10% of 230 kV, 900 kV BIL at high voltage, manufactured on 1978 and located on Irapuato II substation. Important considerations for transformer retro-filled process includes [10,11]: Review of material compatibility with new insulation fluid, evaluation of insulation system dielectric performance, evaluation of transformer thermal performance, consideration for no load an on load tap changer operation, consideration for change in capacitance, insulation power factor and insulation resistance due to fluid properties, consideration for forced oil pumps and oil preservation system. Also the use of dissolved gas analysis (DGA) tool for transformer diagnostic is quite different than for mineral oil, because different gas generation rates are produced for natural ester fluids [12]. The project followed different stages, first a study and evaluation of autotransformer retro-filled viability was carried out including material compatibility tests and a detailed analysis of dielectric and thermal autotransformer performance, operating with natural ester. 1 Material Compatibility Material compatibility tests followed manufacturer standards, taking samples of pressboard, paper, core steel, gaskets, etc., placing samples in vegetable oil and heat it up to 120 °C for at least 7 days. After this time period, oil properties changes were evaluated (interfacial tension, dielectric strength, power factor, etc.) as well as material mechanical properties, in order to evaluate material compatibility. From these test results a decision for changing all autotransformer gaskets was taken. Selected material for new gaskets was hydrogenated nitrile butadiene rubber (HNBR). Above results were also validated, testing same materials in accordance with ASTM D3455-02. Additionally, considerable studies were conducted by IIE to investigate dielectric strength and performance of the natural ester used [13]. For dielectric strength, various electrode configurations were used with uniform and non uniform electrical fields (see figure 1a). Experiments about moisture sensitivity, partial discharge, bacterial growth, thermal and infrared characteristics, oxidation stability and temperature performance of vegetable oil were made. These studies confirmed that FR3™ is a good alternative as a substitute of mineral oil on power transformers [13]. Figure 1b shows some results for dielectric strength as function of moisture in oil in accordance with ASTM test methods. (a) (b) Figure 1. (a) Comparison of vegetable and mineral oil dielectric strength for uniform and non uniform electrical fields; (b) Vegetable oil dielectric strength as a function of active water content in accordance with ASTM D877 and ASTM D1816. Dielectric Evaluation A typical insulation system normally used in liquid-immersed transformers shall contain solid materials for insulating the conductive parts and also a dielectric fluid for insulation and perform the heat transfer process. These insulation materials have to withstand electrical, mechanical, chemical, and thermal stresses for the expected life of the equipment. Natural esters have different dielectric properties than mineral oil [7]; specifically the permittivity (dielectric constant) is quite different for mineral oil and natural esters as well as various kraft insulation materials impregnated with these fluids. Inside transformers, the dielectric strength of a given gap is a function of the width of the gap [7,8]. Designer’s utilizes solid barriers to divide an oil gap into smaller gaps in order to allow a higher average stress [8]. Electrical stress is divided between solid and liquid insulation as a function of its dielectric constants. Also, apart from the electrical stress across the oil duct, a dielectric stress tangential to the surface of solid insulation (creep stress) is produced and has to be calculated and controlled by transformer designers. A detailed analysis and calculation of electrical field distribution in the autotransformer insulation system was made using the permittivity values for different operating conditions; filled with mineral oil and natural ester (see table 1). This calculation was performed using a commercial finite element (FE) program. On figure 2 equipotential lines for the main autotransformer high-low space are shown. The solid insulation barriers were considered and appropriated materials, sources and boundary conditions were selected for 900 kV BIL. Three cases were considered: a) conventional insulation, i.e. autotransformer filled with mineral oil, b) autotransformer filled with natural ester and solid insulation impregnated with mineral oil and c) autotransformer filled with natural ester and solid insulation impregnated with natural ester. 2 Figure 2. Equipotential lines on main high to low space for selected auto-transformer. Table 1. Permittivity values for different cases [7]. Material Mineral Oil Natural Ester Low Density pressboard (impregnated with M.O) High Density Pressboard (impregnated with M.O) Low Density pressboard (impregnated with N.E) High Density Pressboard (impregnated with N.E) Dielectric Constant (25 °C) 2.4 3.3 3.9 4.5 4.4 4.6 The stress distribution within the selected parts of the insulation system was calculated, and the dielectric strength of oil gaps was checked against “Weidmann Reference Curve - WRC”. This consisted in plotting the electric field along a chosen field line in the critically stressed area, calculation of the cumulative field Ecum(x) distribution, and comparison to the WRC that is expressed by the formula (1): Ecum(x) = 2.3·Eo/x0.37 [kV/mm] ----------------(1) A factor 2.3 is introduced to account for the impulse test conditions, and Eo=18 kV/mm corresponds to the paper coated electrodes. Safety margins confirmed that there was no dielectric problem for autotransformer filled with FR3™ fluid. A comparison for three different cases is shown on figure 3; a base line was plotted between series (HV winding) and common voltage windings and electrical field was calculated over it. As it is shown on figure 3, different values of dielectric constant, produces different distribution of electrical field between solid and liquid insulation. Better distribution of electric field, between solid and liquid insulation was found for case (b). Thermal Evaluation Thermal parameters of FR3™ such as its temperature dependent viscosity, thermal conductivity, specific heat and density were used in a cooling program in order to evaluated cooling performance with natural ester. The viscosity curve comparison with mineral oil is presented on figure 4. From these calculations, a maximum of 3-5 °C were found for calculated average winding rise differences, and this is mainly because the slower moving liquid compared with mineral oil. The results confirmed that there was not cooling problem and autotransformer could operate without modification of actual cooling equipment. With this calculation and based on actual ambient temperature conditions a re-design of the expansion tank and preservation system was made. The new preservation system included a rubber bag for avoiding contact between vegetable oil and surrounded air. This is very important due to oxidation characteristics of vegetable oils [11]. 3 Figure 3. Electric field distribution for modeled Figure 4. Curves of FR3™ and typical mineral oil cases; better condition is case (b) with transformer viscosity. filled with natural ester and solid insulation impregnated with mineral oil. 3. FIELD AND FACTORY TESTING Initial field testing included routine maintenance tests like DGA, turn ratio, insulation resistance, insulation power factor, and excitation current measurement. Also other tests like frequency response analysis (FRA) and frequency dielectric spectroscopy (FDS) were made. All testing results indicated a good condition of autotransformer, and then it was disassembled and shipped to manufacturer factory. Full factory tests at 100% testing levels, in accordance with IEEE standard [14] was performed on manufacturer HV Laboratory, with autotransformer filled first with mineral oil and then repeated with autotransformer retro-filled with vegetable oil. On load tap changer and bushings condition were also evaluated. After testing, all bushings were on good condition but because its age, all were replaced. On load tap changer (resistor type, located on high voltage winding) was in good condition but because it was not original designed for operation with vegetable oil, the decision was to leave it filled with mineral oil. A resume of some testing results are shown on table 2. Measured winding capacitances are larger for autotransformer filled with FR3™ as it was expected; due to the bigger value of dielectric constant. Insulation resistance are considerable less for auto-transformer filled with FR3™ than with mineral oil; this is because the natural properties of vegetable oil (lower resistivity). Winding Insulation power factors were very similar as well as polarization index. With respect to thermal performance; measured values matched well with calculation, and a maximum of 5 °C on average winding rise for tertiary and high voltage windings were obtained. The changes on autotransformer capacitances affect winding impulse voltage distribution; although the changes in the dielectric constant affect both the series capacitance and the ground capacitance of the windings, and the change on the ratio of these capacitances are not significant and the overall impulse voltage distribution is expected to be quite similar for transformer filled with mineral and vegetable oil [10]; on this specific case, for high voltage and neutral terminals, the measured full impulse waveforms were very similar; but for low voltage and tertiary terminals, measured impulse waveforms have appreciable differences, and voltages were oscillating in different way for autotransformer filled with mineral and vegetable oil. This is because on this specific shell type design, low voltage coils are closer to the core and low voltage winding ground capacitances was more affected than winding series capacitances. Figure 5 shows the full impulse waveforms comparison for both conditions. Although autotransformer passed successfully all dielectric testing, it is recommended to verify impulse voltage distribution for high voltage transformers that will be retro-filled. 4 Table 2. Test results for autotransformer, H =High voltage (series) windings, X = low voltage (common) winding, and Y= tertiary winding, T= ground. (a) (b) Figure 5. Full impulse voltage waveform for: a) high voltage terminal H1, b) low voltage terminal X1. During induce voltage test, partial discharge measurement was performed in accordance with IEEE standard [14]. For autotransformer filled with mineral oil a value of 275 pC was obtained after one hour test. For autotransformer retro-filled, a value of 700 pC was measured on similar testing conditions; it is suspected that different values are due to differences during drying process and/or due to streamer propagation differences, but at this time more research has to be done with this respect. On figure 6 a frequency response comparison between autotransformer filled with mineral and vegetable oil is presented. The curves are displaces between each other, mainly due to the differences of dielectric constant values for mineral and vegetable oil. 4. SHIPPING, INSTALLATION AND ENERGIZATION After successful performance during factory testing, autotransformer was shipped, installed and energized on April 2011. FR3 oil was shipped in a special tank-car sealed with nitrogen (5 PSI) for avoiding contact with oxygen. During final vacuum filling process the rate of filling was controlled 5 (around 1800 L/hr) to avoid bubbling formation and a waiting time before energization of around 36 hours was established. Temperature of fluid during filling process was around 50 °C. Monitoring equipments (DGA monitor and temperature fiber optical sensors) were also installed on autotransformer and calibrated. (a) (b) Figure 6. Autotransformer frequency response curves for: a) common winding and b) series winding. 5. ON SITE MONITORING On-line monitoring equipment, which includes fiber optical sensors, was located on winding leads and on load tap changer (LTC). Temperatures are continually measured. Periodic field tests like FDS (frequency dielectric spectroscopy), FRA (Frequency response analysis), infrared thermography (see figure 7) and acoustic partial discharges, are routinely performed in order to evaluate actual autotransformer condition. Stray gassing formation of ethane was observed during the first months of operation (see figure 8), which is the unexpected gas formation from some oils at relatively low temperatures in the 80 to 250°C range. This is attributed to the stray gassing of FR3™ which is the natural ester used on this autotransformer and these are not considered a fault or a concern with the autotransformer [15]. Figure 7. Autotransformer Infrared thermography and a view of auto-transformer on Irapuato II substation 6 Figure 8. Ethane gas concentration during first months of autotransformer operation; ethane stabilized at around 100 ppm after 15 days from energization. 6. CONCLUSIONS. Supervision and diagnostics of transformers are very important part of the strategic approach for risk analysis. On this specific research project, autotransformer has successfully operated since it was energized, and is continually monitoring. Experience obtained will be very useful for utility and manufacturers because it was demonstrated that natural esters represent a good alternative as a substitute of mineral oil on power transformers up to 230 KV; and in the near future a plan for retrofill existing, and to manufacture new, high voltage and large power transformer is expected. Since the development of alternative fluids for electrical applications began, researchers, producers, transformer manufacturers and utilities have been investigating the physical and electrical properties of vegetable oils. Vegetable oil-cellulose insulation aging rate extends the range of application beyond that of mineral oil-cellulose systems; this is one of the better advantages of using ester fluids. 7. ACKNOWLEDGEMENTS We would like to send our sincerely gratitude to all technical staff from utility, IIE, IEM and especially to Mr. Alvaro Cancino for their contributions for the present project. 8. BIBLIOGRAPHY [1] [2] [3] [4] [5] [6] [7] Working Group WG A2.35 CIGRE. “Experiences in Service with New insulating Liquids” Brochure 436. P. McShane, K.J. Rapp, J.L. Corkran “Aging of Paper Insulation in Natural Ester Dielectric Fluid”, IEEE/PES Transmission and Distribution Conference and Exposition, Oct 28-Nov 2, 2001. I. Fontana, “50 Years in the Development of Insulating Liquids”, IEEE Electrical Insulation Magazine, Vol. 29, No. 5. Sept/Oct 2013. IEEE Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers, 57.1472008, IEEE, 2008. M. Duval and R. Baldygam, “Stray gassing of FR3 oils in transformers in service,” in 76th Doble International Client Conference, 2009. IEEE Std C57.154™-2012, “IEEE Standard for the Design, Testing, and Application of LiquidImmersed Distribution, Power, and Regulating Transformers Using High-Temperature Insulation Systems and Operating at Elevated Temperatures”, 2012. T. A. Prevost, “Dielectric Properties of Natural Esters and their influence on Transformers Insulation System Design and Performance”, IEEE/PES Transmission and Distribution Conference and Exposition, 2005/2006. 7 [8] [9] [10] [11] [12] [13] [14] [15] Weidmann Electrical Technology Compendium, ver. 1.1 e/d, January 2004. D. Martin, D. Wang, P. Dyer,W.Darwin, R. James “ A Comparative Study of Dielectric Strenght of Ester Impregnated Cellulose For use in Large Power Transformers”, 2007 International Conference on Solid Dielectrics. Winchester, UK, July 8-13 July, 2007. S.P. Moore, “Some considerations for New and Retrofill applications of Natural Ester Fluids in Medium and Large Power Transformers”, IEEE/PES Transmission and Distribution Conference and Exposition, 2005/2006. H.R. Moore, “Requirements and Expectations of Natural Ester Fluids for Application in Power Transformers”, IEEE/PES Transmission and Distribution Conference and Exposition, 2005/2006. M., Duval, “The Duval Triangle for load tap Changer, non-mineral oils, and low temperature faults on transformers”, IEEE Electrical Insulation Magazine, Nov-Dec 2008, Vol 24, No. 6. A. Guzmán, F. Delgado, H. Lara. “Caracterización Dieléctrica de un Aceite Vegetal para la Sustitución de Aceite Mineral en Transformadores de Potencia”, IEEE – RVP-AI /2011, Acapulco, México, Julio 2011, TR09. IEEE Std C57.12.90-2010, “IEEE Standard test code for Liquid-Immersed Distribution, Power and Regulating Transformers”, October 2010. M. Duval, R. Baldyga, “Stray gassing of FR3 oils in Transformers in Service”, 2009 Doble Engineering Company -76th Annual International Doble Client Conference. 8