BITORON-12 MV indoor switchgears rated upto 2500A-31.5kA - 12kV Adaptation of New Standard IEC 62271-200 for Bitoron 12 Metalclad, arc resistant switchgears power is our business we keep you ahead ISO 9001 : 2008 Certified bitoron 12 the evaluative, arc resistant switchgear Safety at works: J switch- disconnector and earthing switch The load break switch is filled with SF6 gas, having exceptional isolating properties and arc extinguishing particularities. Optimal security is ensured by means of a " sealed for life " concept and seal tightness is always checked in the factory. The choice of an ideal operational speed allows a short arcing time. All non-ferrous components of the switch are free of halogen, resistant to the ultra violet and ozone, reinforced with fiberglass and manufactured according to the class UL 94 V0. By using a fuse combination, the load break switch will be completed with the fuse holders and a second earthing switch. Both earthing switches are mechanically linked and so they are opening and closing at the same time. When a fuse is blowing, switch off mechanism through a hitting bolt opens the three phases of the load break switch simultaneously. J SF6 / Vacuum Circuit breaker a compact modular circuit breaker & tested solution for both withdrawable & fixed installation 3.3 kV to 12 kV 630A to 2500A, 20-31.5 kA with metallic protection shutter on cradle racking in/out operation possible with the cubicle door closed conformity standards IEC 62271-1 : common specifications for high voltage switchgear and controlgear standards IEC 62271-100 : high voltage AC circuit breaker IEC 62271-200 : AC metal enclosed switchgear IEC 60529 : degree of protection operating safety as for switch-units, accidental over-pressures are eliminated by opening of the safety membrane. internal arc withstand of the cubicles All bitoron-12 switchboards comply with the five criteria relative to internal arc classification (IAC) as defined in IEC recommendation 62271-200. To ensure complete safety of people, any internal overpressure is directed upward the cubicles, towards the arc chamber. bitoron 12 02 ISO 9001 : 2008 Certified bitoron 12 MV switchgear assemblies 630-2500A, 16-25kA 3.3 to 12 kV system E bitoron-12 is an indoor metal-enclosed switchgear designed in conformity with IEC recommendations for the protection of life and property as well as easy of installation, operation and protecting the environment bitoron-12 meet all the following recommendations and specifications: J IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 B D Adaptations for compliance with national standards and corporate specifications are available as well. The switching devices are of the metalclad. Bitoron-12's design takes into account three categories of user's requirements: J reliability necessary for continuity of power supply J simple installation, operation and maintenance, J safety of operating personnel A Classification for bitoron-12 Service Continuity LSC2B Partitioning PM Accessibility Code AFLR Internal Arc 31.5 kA x 1s C J Loss of Service Continuity : LSC2B The main busbar and circuit-breaker/cable compartments are physically and electrically segregated. This is the category for equipment that enables access to the circuit-breaker/cables compartment with the main busbars energized. J Partition Metallic: PM This covers switchgears with continuous metallic partitions intended to be earthed, between opened accessible compartments and live parts of the main circuit. Metallic partitions or metallic parts of them shall be connected to the earthing point of the switchgear. J Accessibility Code: AFLR A: Accessibility type A restricted to authorized personnel only. Distance of indicators are 300 from the panel. Compartmented Switchgear to IEC 62271-200 A = Switching Compartment B = Busbar Compartment C = Cable Connection Compartment D = LV Compartment E = Arc Chamber (with pressure relief flap) General technical data bitoron-12 rated voltage kV 7.2 12 rated power-frequency withstand voltage, 1mn kV 20 28 rated lightning impulse withstand voltage kV 60 75 I (Test Current)=31.5 kA t (Internal arc duration)=1s In accordance to IEC 62271-200, internal arc classification IAC A FLR 31.5kA x 1s, our bitoron -12 switchgear offers maximum possible personal protection. frequency Hz 50/60 A 800-1250-2500 - switch-fuse unit A 800-1250 The bitoron-12 range is made up of modular units containing fixed and/or withdrawable metal-enclosed SF6 and/or vacuum switchgears : - SF6 circuit breaker A 630-1250-2500 - vacuum circuit breaker A 630-1250-2500 FLR: access from the front (F), from the sides (L) and from the rear (R). J Internal Arc: 31.5 kA x 1s J SF6 fused switch disconnector J SF6 circuit breakers J Vacuum circuit breakers J Contactor J Disconnector. bitoron 12 units are used for the medium voltage section in MV/LV transformer substations in public distribution systems and medium voltage consumer or distribution substations upto 12 kV. bitoron 12 rated current of busbars rated current of the short time withstand current of the : - switch fuse unit kA 25 25 - SF6 circuit breaker kA 20-25 - vacuum circuit breaker kA 20-31.5 rated short-circuit breaking current of the: - SF6 circuit breaker kA 20/25 - vacuum circuit breaker kA 25/31.5 auxiliary voltage V DC 24/48/110/220 AC 110/220 03 ISO 9001 : 2008 Certified Switchgear selections : bitoron 12W 3 Protection cubicle with drawout vacuum circuit breaker Application : Protection of feeders, transformers and MV- equipment Standard equipment - withdrawable circuit breaker interlocking between circuit breaker & cradle position makes operation safer; - current transformers - 4 racked in/out position contacts Options - voltage detector key interlock on load break switch key interlock on earthing switch no door interlock floor plans short circuit indicator sets of VT and double core CT metering (A, V, F, kwh, kVARh etc.) shunt trip close coil - cable supporting door interlock low voltage compartment trip coil- block of 4 O/C contacts - block auxiliary contacts on load - break switch block aux contacts on earthing switch motor operation : 24-48-110 V AC/DC press button control- distance control switching counter- automatic recloser under voltage release Operating voltages : 24-48-110V AC/DC & 220V AC Please consult us for other options and dimensions. Technical data : rated voltage kV rated current A 7.2 12 630-1250-2500 630-1250-2500 short time current (maximum) kA 25 25 short time current duration sec 1 1 operating sequence 0-3mn - CO - 3mn - CO 0-0.3s - CO - 3mn - CO 0-0.3s - CO -15s - CO cubicle dimensions: width mm 850 850 depth mm 1200/1500 1200/1500 height mm 2000 2000 height (with arc chamber) mm 2300 2300 bitoron 12 Common characteristics according to IEC 60 056 short-time withstand current IK for tk=3s (kA) rms Ik=Isc rated peak withstand current Ip peak(kA) Ip= 2.5 & 2.6 Ik rated short circuit making current peak(kA) = 2.5 & 2.6 Isc operating times opening ms < 50 breaking ms < 60 closing ms < 65 mechanical endurance class M2 no. of operations with maintenance 25000 electrical endurance class E2 no. of operations 25kA 100 capacitive current braking C1 class Specifications to be indicated for circuit breaker : - short circuit capacity - rated current - rated voltage - capacity to be secured 04 ISO 9001 : 2008 Certified Switchgear selections:bitoron 12V 3 Protection cubicle with SF6 Isolator & vacuum circuit breaker Application : Protection of feeders, transformers and MV- equipment Standard equipment Options - three phase load break switch according to IEC 62271-103 SF6 - insulation interlocked earthing switch - vacuum circuit breaker with integrated protection relay, current transformers & open release - voltage detector - key interlock on load break switch - key interlock on earthing switch - no door interlock - floor plans - short circuit indicator - sets of VT and double core CT - metering - shunt trip - close release - cable supporting - door interlock - low voltage compartment - block auxiliary contacts on load break switch - block auxiliary contacts on earthing switch - motor operation : 24-48-110V AC/DC - press button control - distance control - switching counter - automatic recloser - under voltage release operating voltages : 24-48-110V AC/DC & 220V AC Please consult us for other options and dimensions. Technical data : rated voltage kV 7.2 rated current A 630-1250 630-1250 short time current (maximum) kA 25 25 short time current duration sec 1 1 operating sequence 12 0-3mn - CO - 3mn - CO 0-0.3s - CO - 3mn - CO 0-0.3s - CO -15s - CO cubicle dimensions: width mm depth mm height mm 2000 2000 height (with arc chamber) mm 2300 2300 bitoron 12 850 850 1200/1500 1200/1500 Common characteristics according to IEC 60 056 short-time withstand current IK for tk=3s (kA) rms Ik=Isc rated peak withstand current Ip peak(kA) Ip= 2.5 & 2.6 Ik rated short circuit making current peak(kA) = 2.5 & 2.6 Isc operating times opening ms < 50 breaking ms < 60 closing ms < 65 mechanical endurance class M2 no. of operations with maintenance 25000 electrical endurance class E2 no. of operations 25kA 100 capacitive current braking C1 class Specifications to be indicated for circuit breaker : - short circuit capacity - rated current - rated voltage - capacity to be secured 05 ISO 9001 : 2008 Certified Switchgear selections : bitoron 12SF Transformer protection cubicle with SF6 insulated fused load break switch and interlocked earth switch Application : Transformer protection and MV- equipment protection Standard equipment - three phase fused load break switch according to IEC 62271-105 - earthing switch with interlock - socle for DIN HRC fuses - cable supporting - Options - block auxiliary contacts on load break switch - block auxiliary contacts on earthing switch - motor operation : 24-48-110 V AC/DC - press button control - distance control - sets of VT and/or CT - capacitive voltage detector key interlock on load break switch key interlock on earthing switch floor plans short circuit indicator DIN HRC fuses and/or spare fuses metering shunt trip close release 3pole fuse trip door interlock low voltage compartment switch off mechanism through hitting bolt operating voltages : 24-48-110 V AC/DC & 220V AC Please consult us for other options and dimensions. Fuse selection table Technical data : rated voltage kV rated current A 800-1250 short time current kA 25 short time current duration sec 7.2 12 mm 750 10 11 12 25A 20A 16A 10A 10A 31.5A 25A 16A 16A 16A 160 40A 31.5A 20A 16A 16A 200 50A 40A 25A 20A 20A 250 63A 50A 31.5A 25A 25A 315 75A 63A 40A 31.5A 31.5A 750 400 100A 75A 50A 40A 40A 500 100A 100A 63A 50A 50A 1 depth mm 1050/1475 1050/1475 height mm 2000 2000 height (with arc chamber) mm 2300 2300 bitoron 12 6 125 cubicle dimensions: width 5 100 800-1250 25 1 kVA/kV 630 75A 63A 63A 800 100A 75A 75A 1000 100A 100A 100A 06 ISO 9001 : 2008 Certified Switchgear selections : bitoron 12AF Transformer protection cubicle with Air insulated type fused load break switch and interlocked earth switch Application : Transformer protection and MV- equipment protection Standard equipment - three phase fused load break switch according to IEC 62271-105 - interlock earthing switch - socle for DIN HRC fuses - cable supporting - Options - block auxiliary contacts on load break switch - block auxiliary contacts on earthing switch - sets of VT and/or CT - capacitive voltage detector key interlock on load break switch key interlock on earthing switch floor plans short circuit indicator DIN HRC fuses and/or spare fuses metering 3 pole fuse trip door interlock low voltage compartment switch off mechanism through hitting bolt operating voltages : 24-48-110 V AC/DC & 220V AC Please consult us for other options and dimensions. Fuse selection table Technical data : rated voltage kV 7.2 rated current A 800-1250 short time current kA 25 short time current duration sec 1 12 800-1250 25 1 cubicle dimensions: width mm 850 850 depth mm 1200/1500 1200/1500 height mm 2000 2000 height (with arc chamber) mm 2300 2300 bitoron 12 kVA/kV 5 6 10 11 12 100 25A 20A 16A 10A 10A 125 31.5A 25A 16A 16A 16A 160 40A 31.5A 20A 16A 16A 200 50A 40A 25A 20A 20A 250 63A 50A 31.5A 25A 25A 315 75A 63A 40A 31.5A 31.5A 400 100A 75A 50A 40A 40A 500 100A 100A 63A 50A 50A 630 75A 63A 63A 800 100A 75A 75A 1000 100A 100A 100A 07 ISO 9001 : 2008 Certified Switchgear selections : bitoron 12A Incoming cubicle with load break switch and interlocked earth switch Application : Incoming cable connection, isolation etc Standard equipment - three phase load break switch according to IEC 62271-103, SF6 - insulation - interlocked earthing switch with making capacity upto 63kA - cable supporting - door interlock - low voltage compartment Options - capacitive voltage detector - key interlock on load break switch - key interlock on earthing switch - no door interlock - floor plans - short circuit indicator - block auxiliary contacts on load break switch - block auxiliary contacts on earthing switch - press button control - distance control Please consult us for other options and dimensions. Technical data : rated voltage kV 7.2 12 rated current A 800-1250 800-1250 short time current kA 25 25 short time current duration sec 1 1 width mm 850 850 depth mm 1200/1500 1200/1500 height mm 2000 2000 height (with arc chamber) mm 2300 2300 cubicle dimensions : bitoron 12 08 ISO 9001 : 2008 Certified Compact Indoor Current Transformers Design The primary is wound with pure heavy copper, to provide a maximum mechanical strength against short circuit currents. The secondary is evenly distributed on a very low losses core for best accuracy. The transformer is hot cast in an insulating resin under vacuum, to achieve a very compact unit. The base plate is supplied as a standard. A secondary cover is available upon request. Advantages The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimensions of these transformers are typically well adapted for their mounting in metal enclosed and metalclad cubicles. They can be fixed in any position and require no maintenance. Function These current measuring units provide two functions: - they insulate the high voltage power network from the low voltage metering circuit. - they supply a low voltage alternative signal proportional to the network current, and intented to supply meters, protection relays, measuring instruments, etc... Standards and tests the transformers are manufactured according to the required standard: IEC 60044-1 They can also be designed according to any customers specification. All the routine tests required by the relevant standard are performed on each unit. The results are noted in the report referred to the order. The type tests have been passed when qualifying each type of transformer, the reports are available upon request. Connection The secondary terminals supply a L.V. current to the measuring circuits. They must never be open- circuited. For each secondary winding, one terminal (one only) is to be grounded. The primary terminals are connected to the busbars, and properly tightened. A slot is provided near each M12 primary holes on to offer an anti- rotating option if necessary to the equipment connected. Rated tightening torques: Primary terminal (M12) : 35N.m Coupling primary (M8) : 12.4N.m Secondary terminal (M6) : 3N.m Typical ratings Insulation : 7.2 kV to 12 kV Frequency : 50Hz or 60Hz Short time current : max 500In upto 600A max 800In upto 1250A Permanent over current factor : 1.0 (over upon request) Primary current : SW447 & SW4412 upto 600A SW457 & SW4512 upto 1250A SW477& SW4712 upto 3000A Secondary current : 5A or 1A Number of cores : SW447 and SW45 : 1 or 2 SW47 : 1 to 3 (upon request) Accuracy metering : CI 0.2 to CI 3 relaying : CI 5P to CI 10P20 (IEC) special uses : CI X to B.S. standard bitoron 12 09 ISO 9001 : 2008 Certified Current transformers typical ratings upto 600A CT-MODEL Common characteristics: IEC standard : 60044-1 50 Hz No partial discharge according to standard Insulating class kV Cores number Rated primary A current Ipn Rated secondary current Isn Thermal current Short time current Precision classes core of measure Rating Precision classes core of protection Rating SW447-1 SW4412-1 SW447-2 SW4412-2 7.2 1 12 1 7.2 2 12 2 A from 10 upto 600A or 2X300A 5 or 1A from 10 upto 600A or 2X300A 5/5 or 1/1A lth ..XIn 100 Ipn upto 500In 100 Ipn upto 500In cl VA 0.2 10 cl VA 0.5 20 1 40 0.2 10 15 10 5P10/5P20/10P10 10 15 148 20.5 92.5 P1 H1 15 P2 H2 NAME PLATE COVER (OPTIONAL) 285 1 40 5P10/5P20/10P10 185 M12 0.5 20 0 250-2 67 27 98.5 SECONDARY TERMINALS 122 195 φ 12 12.5 SCREW M6-12 125 148 125 100 X1 X2 1S1 1S2 120 37.5 X1 S1 220 M8 M12 40 bitoron 12 HIGH RATIO X2 S2 120 PRIMARY TERMINALS DOUBLERATION LOW RATIO Y1 Y2 ANSI - CSA 2S1 2S2 IEC 15 RATED TIGHTENING TORQUE (W5%) Primary terminals (M12) : 35N.m coupling primary (M8) : 12.4N.m Secondary terminals (M6) : 3N.m 34 10 ISO 9001 : 2008 Certified Current transformers typical ratings upto 1250A CT-MODEL Common characteristics: IEC standard : 60044-1 50 Hz No partial discharge according to standard Insulating class kV Cores number Rated primary current Ipn A Rated secondary A current Isn Thermal current lth Short time current ..XIn Precision classes core of measure cl Rating VA Precision classes core of protection cl Rating VA SW457-1 SW4512-1 SW457-2 SW4512-2 7.2 1 12 1 7.2 2 12 2 upto 1250A 5 or 1A upto 1250A 5/5 or 1/1A 100 Ipn upto 800In 100 Ipn upto 800In 0.2 10 0.5 20 1 40 0.2 10 15 10 5P10/5P20/10P10 10 120 0 120 -2 15 178 104.5 P1 H1 1 40 5P10/5P20/10P10 209 M12 0.5 20 20.5 P2 H2 15 NAME PLATE Cover (Optional) 67 27 98.5 122 Secondary Terminals UP TO 600A φ 12 195 125 148 120 120 37.5 220 UP TO 300/600A 120 Arrester When Capacitor Divider M6-12 12.5 120 X2 S2 X3 S3 X1 S1 X2 S2 X3 S3 X1 S1 X2 S2 X4 S4 Ck ANSI - CSA IEC Ck Ck X1 X2 y1 y2 Ck 1S1 1S2 2S1 2S2 UP TO 1250A M12 X1 S1 M12 40 40 M8 15 32 32 y1 y2 z1 z2 x1 x2 1S1 1S2 2S1 2S2 3S1 3S2 ANSI - CSA IEC x3 y1 y2 y3 x1 x2 1S1 1S2 1S3 2S1 2S2 2S3 LOW RATIO bitoron 12 HIGH RATIO y1 y2 2S1 2S2 x1 x2 1S1 1S2 x1 S1 x2 S2 x3 S3 x4 S4 11 ISO 9001 : 2008 Certified Indoor Voltage transformers dry cast resin insulated up to 12 kV Design The primary and secondary windings are mounted on a very low losses core, hot cast in an insulating resin. The mounting base is supplied as a standard and is not to be dismounted. Advantages The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimensions of these transformers are typically well adapted for their mounting in metal enclosed and metalclad cubicles. They can be fixed in any position. These units compact and rugged, require no maintenance. Function Typical ratings These voltage measuring units provide two functions: Insulation 7.2kV to 12kV - they insulate the high voltage power network from the low voltage metering circuit. Frequency 50Hz or 60 Hz -they supply a low voltage alternative signal proportional to the network voltage, and intented to supply meters, protection relays, measuring instruments, etc... connection phase to ground Primary voltage Standards and Tests Accuracy The secondary terminals supply L.V. to the measuring circuits. They must never be short- circuited. to 11000 V 100/A3 V 100V, 110V 110/A3 V 220V metering : 15 VA CI 0.2 to 300 VA CI 1 1.5 x Un-30 sec for grounded neutral 1.9 x Un-30 sec for impedant neutral 1.9 x Un-8h for isolated neutral The core is connected to the base and so grounded (residual voltage winding 100/3 on request) Voltage factor for line to line and line to ground units: Line to ground: The H.V. primary terminal is connected to the bus bar directly or by mean of a high voltage fuse. H.V. 1.2 x Un -continuous Line to line: The two H.V. terminals are connected to the busbars directly or by mean of high voltage fuses. FUSE H.V. IEC da dn residual a1 voltage a2 n FUSE damping resistor connection residual voltage windings The L.V. primary terminal, located near the secondary terminals, must be grounded. The residual voltage winding is to be connected in open delta, closed by a resistor (typical value 100 ohms, 320W). One end of the delta must be grounded. They can also be designed according to any customers specification. All the routine tests required by the relevant standard are performed on each unit. the results are noted in the report referred to the order. The type tests have been passed when qualifying each type of transformer, the reports are available on request. bitoron 12 to 11000/A3 V Voltage factor for line to ground units: For each secondary winding, one terminal (one only) is to be grounded. B 6600 V relaying : 15 VA CI 3P to 100 VACI 5P Connection IEC A 6600/A3 V Secondary voltage The transformers are manufactured according to the required standard : IEC 60044-2 phase to phase Note: IEC A IEC A a a The purpose of the H.V. fuses is to isolate the busbars from the transformer if any incident occurs on it, and not to protect the transformer in case of an overload. Rated tightening torques : Primary terminal (M10) : 15Nm Secondary terminal (M5) : 2Nm Secondary terminal (M6) : 3Nm Ground terminal (M8) : 8Nm 12 ISO 9001 : 2008 Certified Voltage transformers Typical ratings of each unit IEC 60044-2 50 or 60 Hz Compact range Insul. BIL kV Max. Prim. kV Type Available Burdens (VA) Voltage 1 Secondary V 7.2 60 6600 12 75 11000/V3 11000 Thermal 2 Secondaries CL0.2 CL0.5 CL1.0 CL0.5 + CL0.5 V7P 15 50 100 15 15 Y12P 10 50 100 15 Y12G 30 100 200 V12G 30 100 200 Burden CL1 (VA) 30 30 250 15 40 40 250 40 40 80 80 400 50 50 100 100 600 Rated voltage factor : All units : 1.2 Un continuous Phase to ground units : 1.9 Un-30sec (8th upon request) Phase to ground VT : Residual Voltage winding 100/3 or 110/3 2A-8h upon request *60% ** 80% of burden with residual voltage winding 2A-8h Secondary voltage : 100, 110, 100/A3, 110/A3 V Other value upon request CL1 + H.V TERM. M10-20 + SCREW 145 110 A I Sealable Screw B I Name Plate Dia 16 for Cable 200 SADTEM M8 2 40 20 162 113 142 50 50 Secondary Terminals M5 105 4 HOLES DIAN11 bitoron 12 125 235 13 148 1a a b 1b 2a 2b 280 13 ISO 9001 : 2008 Certified Protection, control and monitoring A complete range of digital & microprocessor based protection and monitoring units are designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of a complete range but with simple and reliable solutions, suited to the following applications: M Protection of substations (incomers and feeders) M Protection of transformers M Protection of motors M Protection of busbars. Network and machine diagnosis Tripping current l1, l2, l3, lo Tripping context Unbalance ratio / negative sequence current li Phase angle jo, j1, j2, j3 Disturbance recording Thermal capacity used Waiting time after overload tripping Running hours counter / operating time Starting current and time start inhibit time delay, number of starts before inhibition Switchgear diagnosis Cumulative breaking current Trip circuit supervision Number of operations, operating time, charging time CT/VT supervision Control and monitoring Circuit breaker / contactor control (2) Logic discrimination Additional modules 8 temperature sensor outputs - MET 148 module 1 low level analog output - MSA141 module Logic inputs and outputs - MES108 module (4-wire) module RS485 interface - ACE949-2 (2-wire) or ACE959 (4 wire) module. Earth fault ANSI code : 50N/51N It picks-up when earth fault current reaches the set point. It is time delayed. The time delay may be definite (definite, DT) or IDMT (standard inverse, SIT very inverse VIT, extremely inverse EIT, ultra inverse UTT, RI). the protection comprises two units ; -IDMT or definite time low set unit, -Instantaneous or time-delayed, definite time high set unit IDMT protection IDMT protection operates in according with IEC 60255-3 and BS 142 standards t t to to v 38/49T Phase overcurrent ANSI code : 50/51 phase overcurrent protection is three-pole. It picks-up when one, two or three of the currents reaches the set point. It is time delayed. 1 1.2 10 20 1 1.2 I/Iso 10 20 I/Iso IDMT protection principle IDMT protection principle Definite time protection Is in the set point expressed in A and to> is the protection time delay Iso is the set point expressed In A and to> is the protection time delay t t to t v ANSI code 50/51 50N/51N 50BF 46 67 67N/67NC 32P 49RMS 37 48/51LR 66 27R 27 27S 59 59N 47 79 v Protection Phase overcurrent Earth fault, sensitive earth fault Breaker failure Negative sequence/ unbalance Directional phase overcurrent Directional earth fault Active overpower Thermal overload Phase undercurrent Locked rotor, excessive starting time Starts per hour Ruminant undervoltage Phase-to-phase undervoltage Phase-to-neutral undervoltage Phase-to-phase overvoltage Neutral voltage displacement Negative sequence overvoltage Recloser (4 cycles) Thermostat / Buchholz Temperature monitoring v Functions Is I Definite time protection principle Iso Io Definite time protection principle All other protections , metering & controls like differential transformer protections (87), distance (21) relay, temperatures alarm & trip, DC failure etc are available on request bitoron 12 14 ISO 9001 : 2008 Certified Multifunction Energy meters for billing CIRWATT is a family of multi-function energy meters capable of satisfying the most demanding requirements of energy measurement systems. Other features to highlight are quality, accuracy, security and reliability. Including new technology in its measuring circuitry has allowed CIRCUTOR to develop highly responsive new equipment and to include additional functions for the control and management of measuring. The CIRWATT family offers a complete range of electrical energy meters adapted to its type of applications. TYPES High accuracy, 4 quadrant measurement and advanced programming plus flexible communications for the most demanding of requirements. The best solution for large consumers: generation, substations and heavy industry. A balance between cost and benefits without compromising maximum quality. Ideal, both for industry and commercial buildings. CIRWATT D CIRWATT C CIRWATT A/B Latest generation domestic use energy meters. The last word in measurement, high performance and ease of reading. Anti-fraud protection included. APPLICATION Heavy Industry Substations Medium sized industry Light industry Commercial buildings Domestic use CIRWATT D CIRWATT C CIRWATT A/ B H.V. and M.V. L.V. APPLICATIONS The meter can be read remotely and several readings from different meters may be performed at the same time. This allows different CIRWATT energy meters to be connected via RS-485 and data to be received via a PC or from a central data system. Data may also be received via a Modem using an RS-485 converter to Ethernet TCP/IP, etc. bitoron 12 Remote reading 15 ISO 9001 : 2008 Certified Multifunction Energy meters for billing Heavy industry - CIRWATT D Technical features 402-D ( /5/1 A) 405-D ( /5/1 A) 410-T5-D ( /5, /1 A) Type 402-MTxA-xxD 405-MTxA-xxD 405-NTxA-xxD 405-QTxA-xxD 410-MTxA-xxD 410-NTxA-xxD 410-QTxA-xxD 4 4 4 0.2S 0,5S 1 0.5 1 2 M 3 x 63.5/110 V A.C. M 3 x 63.5/110 V A.C. N 3 x 127/220 V A.C. Q 3 x 230/400 V A.C. M 3 x 63,5/110 V A.C. N 3 x 127/220 V A.C. Q 3 x 230/400 V A.C. In (I b) /5 A /1 A /5 A /1 A /5 A /1 A Imax 10 A (2 A) Contracts Quadrants Active energy accuracy Reactive energy accuracy Rated voltages 10 A (2 A) 10 A (2 A) 3 3 3 Tariffs 9 9 9 Profiles 10 10 10 Regulated market Yes Yes Yes Free market Yes Yes Yes Consumers Type 1, 2, 3, 4 Type 2, 3, 4 Type 3, 4 Optical port Yes Yes Yes Port 1 RS-232 RS-232 RS-232 Port 2 RS-232 or RS-485 RS-232 or RS-485 RS-232 or RS-485 213 days 213 days 213 days 5 120 records 5 120 records 5 120 records Hourly load curve 2nd programmable curve CIRWATT D Nr. of bill summaries 64 64 64 Nr. of events 512 512 512 Medium sized industry Domestic use CIRWATT C 410-D1-C (Direct) 210-A (Direct) 210-B (Direct) 410-UTxA-xxC 410-UTxA-xxC 410-UD1A-xxC 410-UD1A-xxC 210-A 210-B Quadrants 2 2 2 2 Active energy accuracy 1 1 1 1 Type Reactive energy accuracy CIRWATT C 2 2 - - Multi-range 3x57.7/100 V up to 3x230/400 V A.C. Multi-range 3 x 57.7/100 V up to 3 x 230/400 V A.C. 127 V or 230 V A.C. 127 V or 230 V A.C. In (I b) 5A 10 A 10 A 10 A Imax 10 A 100 A 60 / 120 A 60 / 120 A 2 2 1 1 Rated voltages Contracts Tariffs 9 9 2 4 Profiles 10 10 4 4 Regulated market Yes Yes Yes Yes Free market Yes Yes Yes Yes Consumers Type 4 Type 4 Type 5 Type 5 Optical port Yes Yes Yes Yes Port 1 RS-232 or RS-485 RS-232 or RS-485 - RS-232 Port 2 No No - - 213 days 213 days - - Optional Optional - 365 days (30 min) Hourly load curve 2nd programmable curve CIRWATT A/B bitoron 12 CIRWATT A/B 410-T5-C ( /5, /1 A) Nr. of bill summaries 64 64 - 16 Nr. of events 512 512 64 64 16 Power is our business we keep you ahead Protection, automation, metering & measurement-PAMM is responsible for e3 (electrical energy efficiency) BACnet/IP TCP /IP OPEN 4100 EMS Native BACnet Controller OPEN 4100 EMS max. length each CAN-bus 5 km max. 198 IO modules max. 60 LSD-C, FBG 5 max. 192 IO 7-B, IO 7, GALAXY One, CORA OPEN 810 EMS max. CAN-bus length 5 km max. 32 IO modules max. 10 LSD-C, FBG 5 max. 32 IO 7-B, IO 7, GALAXY One, CORA BACnet MS/TP OPEN 600 EMS 32 integrated IOs max. CAN-bus length 5 km max. 5 IO modules max. 2 LSD-C, FBG 5 max. 5 IO 7-B, IO 7, GALAXY One, CORA OPEN SRU BACnet Single Room Controller OPEN SRU 16 integrated IOs C1 CAN C2 CAN RS232 DIT AU g 8 O 5 0 0 0 1 Sta IN G 9 E SS PROCPING M AP a d n GALAXY One BACnet / IP OPEN 600 EMS Native BACnet Controller OPEN 810 EMS Native BACnet Controller ls Suppl y Optim Volta is a t g e ion S O L U E ME TIO NT NS TUP 3,5” in ild o tr co n rd Ener gy I MP L M TCP/ IP CORA-B TUP 5,7” F ISDN RS232 Intelligent L ig ht i n g C on t r o l s 5 Bu ch roa pp OORRGAACNTISIOE N Modem Analog 6 high Efficien Motors cy RS 232 BASICline GSM 1 Complete solution for:> HVAC control > lighting control > parking management > high level integration (HLI) Terminal TCP/IP Controller sp e e d ble ria rives D Printer / Fax ps Va Modem(s) In German technology for intelligent buildings. c re cto a se Au r y o r d to m a t io n Fa s ces OPENweb Pro ING GPRS / UMTS Bluetooth Monitoring and Targeting Systems 7 Lam 2 10 M TA ON R G IT O R ETI & NG r IS r gy 4 Po w er n t M a na ge m e s S o l u t io n T R AI N as pe BMS Heat ined er mb C o n d P ow a T N Lo w En e 3 A complete system solution for Metering & Measurement:1. The meter can be read remotely & data can be received via a pc or from a central data system. 2. Prepayment solution using a recharging card. 3. Readings of different types of consumption at the same time (electricity, water & gas). 4. Power control with programmable CUTOFF RELAY & Communications with PLC is possible in Multifunction electronic energy meters. ent Syste m e g m a C n O W M E A MI T a REVI ME C1 CAN CAN RS232 KNX Building Management system (BMS) for:> commercial building > hotel > hospital > shopping mall > educational Institute USB BACnet MS/TP RS485 BACnet MS/TP RS485 BACnet MS/TP RS485 BACnet MS/TP RS485 BACnet MS/TP - RS485 Connection to external systems RS232 PLDx-24-BAC AI AI AI 0...10V PWDx-24-BAC AI RS232 AI AI -Bus 0...10V KNX TCP/IP BACnet/IP LON Home automation:> anti theft control > automatic gate control > access control > temperature control > lighting control ia re v all a /GPRS rk o M GS e netw l i b mo TCP/IP RS485 EBM Papst fan RS232 RS485 GRUNDFOS pump RS485 MODBUS further connections on request bitoron 12 17 ISO 9001 : 2008 Certified SM system analyzers Introduction SM Series analyzers are highly accurate measuring stations which control and supervise the main electrical parameters in three or four wire, single-phase and/or three-phase systems (in L.V. or M.V.) Measuring is in true effective value (TRMS), using three voltage inputs and neutral with external current transformer connection shaving ƒ/5A or ƒ/1A secondaries (current inputs are insulated in ITF types). Panel mounted equipment In addition to displaying and transmitting all measured or calculated electrical parameters through communications, SM analyzers include a meter function being able to store the systems consumed and generated energy within the SQMs internal memory without the need of an auxiliary power supply. SM system analyzers may include an hourly time slots, according to type, using a preset program. This system obtains a kWh total for each of the preset tariffs. These analyzers, like the single tariff analyzers, record active, inductive reactive, capacitive reactive and apparent power for each of the preset periods. The whole series has a built in power demand meter in which calculates integrated demand in a preset period. This sliding integration may be carried out for a selected parameter: three-phase current, three-phase active power, three-phase apparent power or current per phase. The expandable or modular equipment may be supplied with additional functions from a selected expansion card or from the type of SM selected. They have the option for analogue I/O (multi-converter function), digital I/O (central alarm function or impulse generation / kWh) which may be linked to any measured or calculated electrical parameter. Due to the large volume of information from each of the SM system analyzers, the equipment has communication output. Connection topology and system protocols are varied (RS-232, RS-485, RTB modem, GSM modem, Radio (Modbus RTU, Profi bus DP and Metasys N2) and Ethernet (Web or XML)). DIN rail mounted equipment bitoron 12 18 ISO 9001 : 2008 Certified SM system analyzers Three-phase system analyzers PANEL DIN RAIL 96 x 96 mm SM-96SP SM-NRG96 3 modules SM-96 SM-144 SMk SM-MINI 8 modules SM-BC3 SM-BD SM-BDM + MEASURING FEATURES - Single-phase + - + - O Phase-phase voltage O O O O O O O O True effective value (TRMS) O O O O O O O O O Quadrants 2 4 2 2 4 4 2 4 4 Power demand (Pd) O O O O O O O O Neutral current O O O O O O O O O Leakage current THD Measuring (V , A) O Harmonic decomposition Energy meter (kWh, kvarh C, kvarh L) O O O O O O O O O O O O O O O O O O O O O O O O O Multi-tariff Analogue inputs (0/4...20mA) O Analogue outputs (0/4...20mA) O Digital inputs O O O O O O O O O O O O O O O LCD LCD LED LED LED/LCD LCD LCD LCD LCD Screen saver O O O O O O Password protection O O O O O O O O O O O O O O O O O O O Digital outputs ASSEMBLY FEATURES Display COMMUNICATIONS FEATURES RS-232 RS-485 O O Ethernet O O O O O O O O COMMUNICATIONS PROTOCOL Modbus RTU O O O Profibus DP Johnson Controls XML (Ethernet types only) O O O O O Measured or calculated, according to type bitoron 12 19 ISO 9001 : 2008 Certified After 5 years of continuous Research, Development and Testing, ADEX R & D team has developed and validated quality performance of these range of products. Corporate Office : Baitul Abed 53 Purana Paltan (3rd Floor) Dhaka-1000, Bangladesh. Phone : +88 02 9559868, 9559826 Fax : +88 02 956 2705 e-mail : info@adexbd.com Sales Office : Shekh Centre 56 Purana Paltan (3rd Floor) Dhaka-1000, Bangladesh. Phone: +88 02 956 0626 Fax : +88 02 956 2705 e-mail : sales@adexbd.com Chittagong Office : bti Kanchan, Flat - A2, House# 25 Road# 2, O.R Nizam Road R/A GEC Circle, Chittagong – 4000 Tel : +88 031 651177 e-mail : adex_ctg@adexbd.com Khulna Office : 115/2ka, Ground Floor Sonadanga Thana Road Sonadanga, Khulna Mob : +88 01787 668677 e-mail : adex_khulna@adexbd.com Comilla Office: 32/ka, Tri-Ratno (3rd Floor) Islampur, Fousdari Chowmohoni Judge Court Road, Comilla Mob : +88 01713 436283 e-mail : adex_comilla@adexbd.com Bogra Office: House No. 02 (2nd Floor) Road# 01, Upashahor Bazar, Bogra Mob : +88 01777 790232 e-mail : adex_bogra@adexbd.com Sylhet Office: 7, Jalalabad R/A (Ground Floor) Darshandawri, Amborkhana Sylhet-3100 Mob : +88 01713 436288 e-mail : adex_sylhet@adexbd.com Web: www.adexbd.com creation by pulin | may, 15 | 4000 pcs ADEX E CNGINEERING ORPORATIONLLIMITED. IMITED.