Weidmuller Diode Modules

advertisement
I n t ro d u c t i o n — D i o d e M o d u l e s f o r R e d u n d a n c y
Redundancy, Load Sharing,
Increased Power Delivery
Weidmuller’s diode modules are designed
to enhance the ConnectPower series of
DC power supplies and provide a more
reliable Power Delivery Solution. They are
cost effective products that enable redundancy as well as load sharing between
power supplies, thus extending the useful
life of the power supply.
It is important to keep in mind that before
paralleling power supplies, their output
voltage must be calibrated to be within
±50mV of each other, and the parallel
connection must be positioned as close
as possible to the load.
Diode modules can increase the reliability
of a Power Delivery Solution by preventing current feedbacks between paralleled
power supplies.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
I n t ro d u c t i o n — D i o d e M o d u l e s f o r R e d u n d a n c y
Parallel Connection for Increased Power Delivery
24VDC/20Amp
10Amp Power Supply
10Amp Power Supply
OUT
+V
+V
-V
-V
230VAC
230VAC
115VAC
115VAC
8710620000
CP DM 10
8708680000
CP SNT 250W 24V 10A
Input
24V=2x10A
Output
24V=20A
8708680000
CP SNT 250W 24V 10A
DC OK
L
N
• The amount of power needed is
provided by two power supplies
combined in parallel
PE
12
11
14
+V
DC OK
+V
-V
E1
-V
-V
-V
E2
L
N
PE
12
11
14
+V
+V
-V
-V
IN
24VDC/10Amp
24VDC/10Amp
• Diode modules provide galvanic
isolation between power supplies
Provide Uninterrupted DC Power with Redundancy and Fault Indication
(this example supplying 7A to load)
Diode Module
24VDC/7Amp
10Amp Power Supply
10Amp Power Supply
• Use status relays for remote alarm
indication
OUT
+V
+V
-V
-V
230VAC
230VAC
115VAC
115VAC
8708680000
CP SNT 250W 24V 10A
8710620000
CP DM 10
Input
24V=2x10A
Output
24V=20A
8708680000
CP SNT 250W 24V 10A
DC OK
L
N
PE
12
11
14
+V
DC OK
+V
-V
-V
E1
-V
-V
E2
L
N
PE
12
11
14
+V
+V
-V
-V
IN
24VDC/3.5Amp
24VDC/3.5Amp
Status Relays (Change-Over-Contact)
e.g. to PLC, IPC or Fieldbus
Status Relays (Change-Over-Contact)
e.g. to PLC, IPC or Fieldbus
• The amount of power needed is
provided by two power supplies
combined in parallel
Increase DC Power Delivery to Control Systems
(this example supplying 14A to load)
Diode Module
24VDC/14Amp
10Amp Power Supply
10Amp Power Supply
OUT
+V
+V
-V
-V
230VAC
230VAC
115VAC
115VAC
8708680000
CP SNT 250W 24V 10A
8710620000
CP DM 10
Input
24V=2x10A
Output
24V=20A
8708680000
CP SNT 250W 24V 10A
DC OK
L
N
• Use status relays for remote alarm
indication
PE
12
11
14
+V
DC OK
+V
-V
E1
-V
-V
-V
E2
L
N
PE
12
11
14
+V
+V
-V
-V
IN
24VDC/7Amp
24VDC/7Amp
Status Relays (Change-Over-Contact)
e.g. to PLC, IPC or Fieldbus
Status Relays (Change-Over-Contact)
e.g. to PLC, IPC or Fieldbus
• Under normal operating conditions,
the critical load is provided by both
the 10A and 3A power supply
Guarantee DC Power to Critical Loads
(this example supplying 3A to critical load)
24VDC/3Amp
10Amp Power Supply
24VDC/10Amp
Critical Loads
OUT
+V
+V
-V
-V
Diode Module
24VDC/10Amp
230VAC
• If the larger power supply fails,
the critical load will continue to be
maintained by the 3A power supply
115VAC
8708680000
CP SNT 250W 24V 10A
8710620000
CP DM 10
Input
24V=2x10A
Output
24V=20A
Status Relays (Change-Over Contact)
e.g. to PLC, IPC or Fieldbus
DC OK
L
N
PE
12
11
14
+V
+V
-V
E1
-V
-V
-V
E2
• This ensures uninterrupted power to
the critical load
IN
Non-critical Loads
24VDC/10Amp
Status Relays (Change-Over Contact)
e.g. to PLC, IPC or Fieldbus
12 11 10
V+ V+ V- V-
DC OK
8703660000
CP SNT 70A 24V 3A
24Amp Power Supply
24VDC/3Amp
L
N
PE
Note: Two power supplies in parallel must be calibrated to within ± 50 mv
of each other.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Diode Modules for Redundancy
CP DM 10
10A per Input Diode Module
CP DM 20
20A per Input Diode Module
Approvals:
% \
Derating Curve
3/5/10/20A
Schematic
Output load / ambient temperature
Schematic
+V
120
-V
+V
-V
Load (%)
100
80
60
40
20
E1
0
-10
0
10
20
30
40
50
60
70
E2 -V
E1
E2 -V
Ambient temperature (°C)
Type
CP DM 10
Ordering Data
Technical Data
Input
Input voltage
Input current
Output
Output voltage
Output current
General Specifications
Temperature
Operating
Storage
Efficiency under max. load
Mount onto mounting rail
Mounting position
Mounting
Weight
Dimensions (L x W x H)
Type of Connection
Clamping area input (nominal / min. / max.)
Clamping area output (nominal / min. / max.)
Indication signals
Voltage
Alarm
Fault Relay
Other
Terminations
Voltage
Current
Configuration
Set point
Voltage drop input-output
Fan
Input/output
Alarm contact
Qty.
1
Order No.
8710620000
Type
CP DM 20
Qty.
1
40 VDC max.
10 A per input max.
40 VDC max.
20 A per input max.
Vin - 0.5 typ.
Vin - 0.5 typ.
20 A max.
40 A max.
-10°C…+55°C (+14°F…+131°F)
-20°C…+85°C (-4°F…+185°F)
-10°C…+55°C (+14°F…+131°F)
-20°C…+85°C (-4°F…+185°F)
approx. 95.5% at 24 VDC
Mounting rail TS35 to DIN 50022
Horizontal
approx. 95% at 24 VDC
Mounting rail TS35 to DIN 50022
Horizontal
Clearance: side 2 4 cm; above/below 2 10 cm
approx. 0.15 kg (0.33 lbs.)
Clearance: side 2 4 cm; above/below 2 10 cm
approx. 0.5 kg (1.1 lbs.)
125.0 x 55.5 mm x 110.0 (4.92 x 2.19 x 4.33 in.)
Screw
125.0 x 55.5 mm x 110.0 (4.92 x 2.19 x 4.33 in.)
Screw
4 / 0.13 / 6 mm2 (12 / 26 / 10 AWG)
4 / 0.13 / 6 mm2 (12 / 26 / 10 AWG)
4 / 0.13 / 6 mm2 (12 / 26 / 10 AWG)
None
10.0 / 0.32 / 16.0 mm2 (8 / 22 / 6 AWG)
None
None
None
None
None
None
None
0.5 V typ.
None
None
None
None
None
0.5 V typ.
None
N/A
N/A
N/A
N/A
% \
% \
Order No.
8768650000
Approvals/Certifications
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
Diode Modules for Redundancy
CP DM 30 (SP-RS-RED./PARR.30A)
15A per Input Diode Module
Ordering Data
Type
RSD-40A
20A per Input or 40A Input per Unit
Diode Module with Status Indication
Order No.
Type
Order No.
CP DM 30 with voltage sensing and fault relay
998739
RSD-40A (20 A per input max.) (2 x 20)
7940005219
CP DM 30 without voltage sensing
998786
RSD-40A (40 A input per unit max.,
2 units required) (1 x 40)
7940005218
Technical Data
Input
Input voltage
Input current
Output voltage
Output current
Output
General Specifications
Temperature
Operating
Storage
14-24 VDC
24 VDC nominal
15 A per input max.
24 VDC
30A Maximum
20 A per input max. / 40 A (7940005218)
24 VDC
40 A Maximum
0°C…+50°C (32°F…+122°F)
0°C…+40°C (32°F…+104°F) ambient
(40°C rise (104°F) above ambient at 30 A)
-20°C…+85°C (-4°F…+185°F)
Efficiency under max. load
Mount onto mounting rail
95%
TS32 or TS35 mm DIN rails
95%
TS32 or TS35 mm DIN rails
Mounting position
Mounting
Horizontal
Clearance: side 2 4 cm; above/below 2 10 cm
Horizontal
Clearance: side 2 4 cm; above/below 2 10 cm
Weight
Dimensions (L x W x H)
226.8 g (0.5 lbs.)
70 x 110 x 90 mm (2.75 x 4.33 x 3.5 in.)
317.5 g (0.7 lbs.)
109.2 x 109.2 x 99 mm (4.3 x 4.3 x 3.9 in.)
Type of Connection
Screw
Screw
Clamping area input (nominal / min. / max.)
Clamping area output (nominal / min. / max.)
Indication signals
4 / 0.32 / 16 mm2 (12 / 22 / 6 AWG)
4 / 0.32 / 16 mm2 (12 / 22 / 6 AWG)
None for 998786
Actual voltage for 998739
1.5 / 0.32 / 16 mm2 (14 / 22 / 6 AWG)
1.5 / 0.32 / 16 mm2 (14 / 22 / 6 AWG)
“AN.1” = input 1 (2 x 20 A version)
“AN.2” = input 2 (2 x 20 A version)
“AN.1” = “AN.2” = input voltage (1 x 40 A version)
“CATH” = output voltage
Voltage
Alarm
Fault Relay
Other
Terminations
Voltage
Current
Configuration
Set point
Voltage drop input-output
Fan
Input/output
Alarm contact
0-10 VDC = 0°C…+100°C (32°F…+212°F)
15 VDC Max. output (150°C [302°F])
24 VDC under normal operating conditions
0 VDC if heatsink temperature exceeds 90°C (194°F)
N/A
N/A
None
125 VAC Maximum
6 A Maximum
1 Form C / SPDT
14-24 VDC, ± 5% typ.
0.38 V typ.
None
N/A
N/A
0.40 V typ.
Turns on when heatsink temperature exceeds 60°C (140°F)
Proportional control (fan speed increases as heatsink
2.5 mm2 (26…14 AWG)
26…12 AWG
temperature increases–fully on at 80°C [176°F])
13 mm2 (22…6 AWG)
26…14 AWG
UL recognized, a
cULus Listed
Approvals/Certifications
RSD-40A Schematics
7940005218
7940005219
OUT 1
OUT 2
OUT 3
OUT 4
IN 1
IN 2
Alarm
& Fan
Control
OUT 1
OUT 2
OUT 3
OUT 4
IN 1
IN 2
AN.1
AN.1
AN.2
AN.2
CATH
CATH
Deg. C
(0-10 VDC = 0-100°C)
Alarm
(0V = Deg. C > 90°C)
COM (0V)
Alarm
& Fan
Control
Deg. C
(0-10 VDC = 0-100°C)
Alarm
(0V = Deg. C > 90°C)
COM (0V)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com