FEDERAL SIGNAL UPS UNINTERRUPTIBLE POWER SUPPLY OWNERS MANUAL IMPORTANT SAVE THESE INSTRUCTIONS PLEASE READ THIS MANUAL BEFORE USING EQUIPMENT PUBLISHED DECEMBER, 2003 ALL RIGHTS RESERVED: REPRODUCTION WITHOUT PERMISSION IS PROHIBITED REVISION : 1 PART # 109916 FEDERAL SIGNAL UPS TABLE OF CONTENTS PAGE INTRODUCTION 1.1 1. GENERAL DESCRIPTION General Benefits of Owning and Using the UPS Using Your Ups - How It Works 2. SPECIFICATIONS 1.1 - 1.2 1.3 1.4 - 1.5 2.1 - 2.2 3. SIZING THE UPS Installation Considerations 3.1 4. INSTALLATION, SET-UP AND START-UP Receiving your UPS Removing the UPS from the Pallet Cabinet Dimensions, Access and Clearances Installation and Wiring AC Input Breaker, Wiring and Amperage Matrix Set-Up and Start-Up Procedures Applying Power Changing Input Power AC Input and Output Wiring 3.5K, and 5 K AC Input and Output Wiring 7.5K Battery Installation Customer Satisfaction Checklist 5. COMMUNICATIONS (Also See Options) 4.1 4.2 4.3 – 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 5.1 - 5.4 6. PRODUCT SUPPORT SERVICES Warranty Validation Form 6.1 FEDERAL SIGNAL UPS TABLE OF CONTENTS PAGE 7. MAINTENANCE PROCEDURE General Maintenance Complete Maintenance Check UPS Function Test UPS Generator Test Performance Checklist 7.1 7.1 7.2 7.2 7.3 8. TROUBLE SHOOTING General Trouble Shooting Guide System Circuit Diagram 9. PARTS LISTS 8.1 8.2 9.1 10. OPTIONS WITH INSTALLATION INSTRUCTIONS Plugs, Receptacles and Distribution Panels Bypass Switches Other Options Remote Emergency Power Off Push Button Monophone Automatic Phone Dialer Remote Annunciator 4X Communication Port Expander 2X Communication Port Expander UPS Component Locations and Options Installation Diagram 10.1 10.2 10.3 10.3 10.3 10.3 10.3 10.3 10.4 FEDERAL SIGNAL UPS INTRODUCTION The Federal Signal UPS is a single phase, continuous duty, line interactive, single conversion Uninterruptible Power System (UPS) designed to supply reliable, clean, regulated power for critical loads. An efficient ferroresonant transformer, microprocessor controlled solid state pulse width modulation inverter and long lasting battery pack provide immunity to all line disturbances and power interruptions with no break in AC output power. When using the UPS you are assured the integrity of your systems will not be corrupted. GENERAL OPERATION The synchronous inverter produces a true uninterrupted output in any mode of operation. A self-diagnostic monitoring alarm system keeps operators continuously advised of the system status. A RS232 ASCII Communications port is standard and allows a computer or LAN System to communicate with the UPS. The communications have many features including: - Monitoring - Input voltage, output voltage, battery voltage, output current, percent load, watts, KVA, power factor, frequency, number of outages, number of overloads, UPS on. - Alarms - Low battery warning, on battery, overload, low output, high output, check battery, frequency fault, overtemp. - Set Points - You may customize the operation of the UPS for your special requirements. - Auto Shutdown - Warns users of limited battery time and performs an orderly unattended shutdown. - Alarm Contacts - UPS on, AC power failure, low battery, alarm, remote emergency power off. CONSERVATIVELY RATED The UPS is conservatively rated for non-linear loads with crest factors as high as 3:1 and 0.7 power factors. FUZZY LOGIC AND ENVIRONMENTAL ADAPTIVE CONTROL Fuzzy Logic is used to self-adjust to the incoming power and deliver exact output power to your systems without wasting valuable battery time even during brownouts. Soft utility lines and engine generators produce severe input voltage distortion that cause UPS detection circuits to misjudge real power failures. Environmental Adaptive Control eliminates this problem by capturing the input voltage waveform and using artificial intelligence to make detection decisions. This again preserves valuable battery time. NORMAL OPERATION The UPS is comprised of a microprocessor controlled PWM static inverter; highly filtered current and voltage limited precision battery charger, diagnostic display and output power distribution. Under normal operating conditions, the critical load is supported by AC power, filtered and regulated through a ferro-resonant transformer. When AC power is present the battery charger maintains a ripple free float charge on the batteries. Page 1.1 EMERGENCY OPERATION Upon failure of commercial AC power, battery power is converted by the PWM inverter and filtered through the on-line power purification system. There is no interruption of regulated and conditioned power to the critical load upon failure or restoration of the commercial AC power. The entire UPS operates from the front panel with status signals available through a bi-directional RS232 port. Battery sensory circuits warn you if your batteries are in need of attention and disconnect the batteries when discharge reaches a critical level. BATTERY AND CHARGER The battery packs are pre-wired, pre-tested and are contained within the inverter cabinet. They are sealed no maintenance recombinant lead acid batteries. Run time may be extended by adding Battery Extensions. External battery cabinets are pre-wired and pre-tested, hook-up ready and match the inverter cabinet. Precision controlled to 1%, highly filtered, current limited and voltage regulated battery charger sustains float charge on the battery continuously affording maximum, battery life. PROTECTION INPUT - Integrally mounted molded case AC and DC circuit breaker protects against abnormal current overloads and provides a convenient means of disconnecting utility or DC power. OUTPUT - Ferro-resonant transformer, provides inherent overload protection. Output fuses or circuit breakers are also utilized for added protection. Page 1.2 BENEFITS OF OWNING AND USING THE UPS * Environmental Adaptive Control * True On-Line Protection * Power Factor Correction * Line Harmonic Filtering * Small Physical Size * Simple and Inexpensive Installation * Highly Efficient * Quiet Operation * Low BTU Output * Microprocessor Control and Diagnostics * Automatic Synchronized Retransfer * Multiple Input and Output Voltage Selection * Casters Provide Simple Relocation and Installation * Priced to be Affordable * 200,000 Hour MTBF Transformer * Extremely High Surge Capability * 3:1 Crest Factor for Non Linear Loads * Simple Operation * Early Power Warning Communication for Unattended Computer Shutdowns * Full RS232 Communication of Operating Parameters * Input and DC Thermal Magnetic Circuit Breakers * Nation Wide Customer Support Service Page 1.3 USING YOUR UPS - HOW IT WORKS 1 FRONT VIEW OF UPS 2 3 4 5 6 1. Input Volts- LED on indicates unit is monitoring the input voltage via the digital display. This function is activated by pushing the display select button. 2. Output Volts- LED on indicates unit is monitoring the output voltage via the digital display. This function is activated by pushing the display select button. 3. Percent Load- LED on indicates unit is monitoring the output load capacity relative to maximum watts via the digital display. This function is activated by pushing the display. 4. Percent Battery- LED on indicates unit is monitoring the battery charger when UPS is on utility power. Note: When UPS is on battery power the Percent Battery monitors actual battery time left via the digital display. This function is activated by pushing the display select button. 5. Display Select- This pushbutton selects one of four monitor functions mentioned above and displays the results on the digital display. Also used for manual restart after rundown. 6. Digital Display- Three-digit display monitoring the four functions mentioned above. This display monitors one function at a time and is selected by the “Display Select” pushbutton. 7. System On- LED on indicates the correct AC input voltage is present. The units AC and DC circuit breakers must be on. LED will remain on when unit is on battery power. 7 8 9 10 12 11 13 8. System On Battery- LED on indicates the UPS is on battery power accompanied by an audible alarm. The UPS may switch to battery power even when it appears there are not power outages. The reason is that the UPS detects input sags and surges and does not necessarily require a total power loss to switch to battery power. The UPS will remain on battery power for a few seconds after normal AC power is restored. 9. Low Battery- LED on indicates batteries are low and a total UPS shutdown is immanent unless AC power returns. This alarm set point is user selectable via the communications port (see communications section) to turn on at a pre-determined percentage of battery time remaining. Percentage is selectable from 10 % to 90% of battery remaining. 10. Alarm- LED on is accompanied by an audible alarm. For a number of alarm functions (see communications section). Alarm will clear automatically once the alarm condition is resolved. 11. Battery Circuit Breaker- Connects or disconnects the battery pack. 12. AC Circuit Breaker- Connects or disconnects the AC utility power. 13. Stack Pack – Battery compartment. Page 1.4 USING YOUR UPS - HOW IT WORKS REAR VIEW OF UPS 1 2 5 1. Mode selection switch: Position 4- Audible Alarm-on/off. Causes of alarm -Loss of AC power -Low battery warning -Frequency Fault -Check Battery -Shorted SCR -Low battery shutdown 3 Position 3- Automatic Restart- on/off. (On = Auto Start) -The UPS will automatically restart When facility power is restored following a power down caused by a low battery condition. All other power down conditions will require a manual restart. 4 6 9 Position 2- Slew Rate Fast-on/off. -For use with unstable line or generators. *Only 1 position (1) or (2) must be on at one time. Do not change with UPS on. 7 Position 1- Normal Slew Rate-on/off. -This is preset by the factory and need not be changed unless the UPS will be operated with rapid input frequency variations, such as gas driven engine generators. 8 2. J1 communication port. 3. Input voltage selection switch. Preset at the factory. (See changing input power section before changing this switch). -Low Output -High Output -Overload - Overtemp 4. Specification Tag: KVA Input Voltage Input Current 5. 6. 7. 8. 9. Output Voltage Output Current Cooling Fan Input / Output Access Plate Input / Output Terminal Block Stack Pack – Battery compartment Input Conduit Hole Page 1.5 SPECIFICATIONS INPUT OUTPUT KVA RATINGS 120 or 208 or 240 VAC at 50 or 60 Hz Other voltages available Sine wave voltage: Maximum 3% Harmonic distortion, any single harmonic Output is rated for computer-type loads with switch mode power supplies. Operating rating: +10*% to -30% under a typical load; +10% to -15% at full load at 60Hz: 120VAC: 120/208 VAC:120/240 VAC Frequency range: ± 2.5Hz Power factor: self correcting to >0.95 (approaching unity) at 50Hz 220VAC: 110/220VAC Extended Emergency back up available. Crest factor: 3.5:1 Reflected Input harmonics: <3% THD (total harmonic distortion) K factor: 30 or better Spike Attenuation: 3000:1 Power factor: 0.7 switch mode rated Harmonic attenuation: load generated harmonics are attenuated 400% at the input Line regulation: typically better than ±3% Load regulation: typically better than ±3% Note: Efficiency ratings for 3.5 KVA - 5 KVA is 89%, ratings for 7.5 KVA is 91%. Note: Audible noise full load for 3.5 KVA - 5 KVA is 50 dBA, audible noise for 7.5 KVA is 51 dBA. Federal Signal Model Number System U35-30-120-S KVA Size Battery back-up time in Minutes Input Voltage Cabinet Style Page 2.1 BATTERY TIME, CABINET DIMENSIONS, AND WEIGHT FS MODEL # BACK UP TIME (MINUTES) DIMENSIONS WEIGHT U35-30-120-S U35-60-120-S U35-30-120-R U35-60-120-R U35-30-208-S U35-60-208-S U35-30-208-R U35-60-208-R U35-30-240-S U35-60-240-S U35-30-240-R U35-60-240-R U50-30-120-S U50-60-120-S U50-60-120-R U50-60-120-R U50-30-208-S U50-60-208-S U50-30-208-R U50-60-208-R U50-30-240-S U50-60-240-S U50-30-240-R U50-60-240-R U75-30-120-S U75-60-120-S U75-30-120-R U75-60-120-R U75-30-208-S U75-60-208-S U75-30-208-R U75-60-208-R U75-30-240-S U75-60-240-S U75-30-240-R U75-60-240-R 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 30 60 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 19” x 29.81” x 36.44” 19” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 19” x 29.81” x 36.44” 19” x 29.81” x 36.44” 15” x 29.81” x 36.44” 15” x 29.81” x 36.44” 19” x 29.81” x 36.44” 19” x 29.81” x 36.44” 15” x 29.81” x 42.44” 15” x 29.81” x 42.44” 19” x 29.81” x 42.44” 23” x 29.81” x 42.44” 15” x 29.81” x 42.44” 15” x 29.81” x 42.44” 15” x 29.81” x 42.44” 23” x 29.81” x 42.44” 15” x 29.81” x 42.44” 15” x 29.81” x 42.44” 19” x 29.81” x 42.44” 23” x 29.81” x 42.44” 462 587 462 587 462 587 462 587 462 587 462 587 553 707 553 707 553 707 553 707 553 707 553 707 857 1151 857 1151 857 1151 857 1151 857 1151 857 1151 Page 2.2 SPECIFICATIONS BATTERY COMMUNICATIONS INTERFACE Runtime listed at full and half load for each model number with extended runtimes available beyond this standard Status and alarm port: Used for network protection and unattended, automatic shutdown for all LAN/WAN systems such as Novell, LAN Manager, OS/2 and others including UNIX and ZENIX operating systems. Type: sealed, maintenance-free, gas recombinant, selfventing, suspended electrolyte with no gel contaminant Charger: 3 amp, two stage, temperature compensated, not to exceed 25% of the amp hour rating Full duplex ASCII, RS/232 Serial port; this port provides over 50 operating, diagnostic and performance characteristics. Recharge time: typically 3 hours to full charge ENVIRONMENTAL Buss voltage: 48 volts dc, 3.5 – 5 KVA; float 2.27 vdc - final 1.75 vpc, 96 volts dc 7.5 KVA Isolation: NEC article 250 -5d; complies with this standard that specifies a separately derived power source Factory tested with specific inverter before shipping Operating temperature: 0 (32) to 40 (105) degrees Celsius (F) without derating in any mode Projected life: 5 years service Capacity: batteries are sized with the inverter to support the load at rated KVA with a 0.7 power factor PERFORMANCE Storage temperature: -20 to 50 degrees Celsius Relative humidity: 95% non-condensing Elevation: 5,000 feet, 1500 meters Overload capacity: 125% for ten minutes MTBF Surge Capability: 150% of rated output without need of static bypass Total system - 100,000 hours MIL Spec standard 217E Frequency stability: ± 0.2 Hz Transformer - 200,000 hours Inner winding capacitance: 0.01 pico farads (primary to secondary coupling) Mean time to repair - less than one hour Common mode: 120 dB (106 : 1 ground noise attenuation) (-3 dB at 1 kHz; -20 dB per decade) SAFETY Reactive power correction: load at .6 pF corrected to > .95 at input (automatically self-correcting) UL Listed 1778 standard for UPS equipment CSA certified Fuzzy Rangingtm Human-like decision making to optimize useable input line voltage without use of batteries. Range without battery consumption to 61% of nominal input voltage. FCC article 15, section J, Class A means it will not interfere with any other electronic device, including your computer or phone. DISPLAY MONITORS AND DIAGNOSITCS AGENCIES Digital, 3 digit, bright LED providing system parameters: IEEE 587 category B guide for surge suppression, exceeds by 33% • Input Voltage • Percent of Load • Percent of Battery Charger • Output Voltage • Percent of Battery Capacity LED indicators providing system status: System On (Green) System On Battery (Yellow) Low Battery Warning (Red) The following are accessible through the J1 port: • Low Output • Over temperature • Output Shutdown • High Output • Shorted SCR Shutdown • Inverter On • Overload • Low Battery Shutdown • Low Battery • Frequency Fault • Weak Battery • Remote/Emergency Power Off Shutdown Audible Alarm: • Switch Selectable • ANSI/IEEE C62.41 and .45 category A and B FAA - G - 201e power factor specifications CBEMA and ANSI C84.1 - exceeds specifications and recommendations IEEE 519 Federal Signal reserves the right to change specifications and design without notice as part of our policy of continual improvement of products and technology. Page 2.3 SIZING THE UPS When sizing the UPS, be sure to take into consideration all loads and circuits the UPS is to supply. A good way to insure that the UPS is sized properly is to use the following guide lines. - List each piece of equipment, include Model, Voltage, Current and KVA. - Gather the data by reading the spec plate of the equipment you plan on backing up. Make sure your equipment's input voltage matches the UPS output voltage. - Consult the vendor of the computer equipment to supply you with the information you need. - Add up the total KVA of the equipment and make sure it does not exceed the UPS KVA rating. INSTALLATION CONSIDERATIONS Prior to installing the UPS be sure to take into consideration the site you have selected. UPS systems produce heat and therefore require ventilation as well as accessibility. Consider these factors. - Ventilation - Input Source Voltage - Size of the UPS - Receiving Facilities - Weight Load - Available Single Phase KVA - Noise Requirements - Room Temperature - Audible - Distance of Inverter to Critical Load - Clearances - Accessibility - Excessively Long Power Runs - Proper Ground Techniques - Generator Applications - Distribution of Power - Communications (i.e. Early Power Warning Feature) - Remote Emergency Power Off (REPO) - Monitors - Extended Battery Run Times - Options Page 3.1 RECEIVING THE UPS *** INSPECTION, PLACEMENT, INSTALLATION, SET-UP *** AND START-UP SHOULD BE PERFORMED BY QUALIFIED PERSONNEL *** WARNING *** HIGH VOLTAGE EXISTS, CAUTION MUST BE TAKEN WHEN WORKING NEAR THE BATTERY TERMINALS. POWER IS SUPPLIED BY MORE THAN ONE SOURCE. MAKE SURE BOTH AC AND DC CIRCUIT BREAKERS ARE OFF BEFORE INSTALLING OR SERVICING THE UPS INSPECTION Upon receipt of your UPS visually inspect the unit for shipping damage. If shipping damage has occurred the purchaser should promptly notify the carrier and file a claim with the carrier. Federal Signal should be notified if the damages may impair the operation of the unit. Call 1-708-534-4756 Note: Be sure to remove the cover and inspect inside the unit for shipping damage. STORAGE If it is necessary to store the unit be sure to place it in a clean dry area. It is advisable to protect the unit by replacing it in the original container. For extended storage the battery must be charged for 24 hours every 6 months. This is accomplished by hooking up and turning the UPS on. Make sure proper ventilation is available anytime the UPS is on. PLACEMENT The portability of the system allows the unit to be rolled into a convenient location. The minimum spacing required for service, ventilation, and accessibility to the circuit breakers is (2) two feet at the left, rear and front side of the cabinet. If flexible conduit is used for input power and distribution, the rear clearance can be reduced to ten inches. Allowance must be made in the length of the cable so that the unit can be rolled out forward for service. Page 4.1 THE FEDERAL SIGNAL UPS REMOVING THE UPS FROM THE PALLET TOOLS REQUIRED. 1/2” Wrench Hammer STEPS TO REMOVE THE CABINET 1. 2. 3. 4. 5. Check to make sure the casters are locked. Remove the bolts holding the brackets to the skid with a 1/2” Wrench. Remove the brackets With a hammer, knock out one end of the skid as shown below. Unlock the casters and carefully roll the unit down the ramp. Page 4.2 THE FEDERAL SIGNAL UPS CABINET DIMENSIONS, ACCESS AND CLEARANCES Page 4.3 THE FEDERAL SIGNAL UPS CABINET DIMENSIONS, ACCESS AND CLEARANCES Page 4.4 THE FEDERAL SIGNAL UPS CABINET DIMENSIONS, ACCESS AND CLEARANCES Page 4.5 THE FEDERAL SIGNAL UPS CABINET DIMENSIONS, ACCESS AND CLEARANCES Page 4.6 THE FEDERAL SIGNAL UPS CABINET DIMENSIONS, ACCESS AND CLEARANCES Page 4.7 THE FEDERAL SIGNAL UPS INSTALLATION AND WIRING TOOLS REQUIRED AND INSTALLATION CHECKLIST _______ Flat Head and Phillips Head Screw Driver _______ The AC input breaker, wiring and amperage matrix defines the proper AC breaker size for the appropriate KVA. Refer only to the matrix for the service panel AC breaker size. The UPS comes standard with terminals for hard wire installation. For Input Wiring, Refer To the Section "AC Input Breaker, Wiring and Ampereage Matrix” Page 4.9. _______ All 208/240 VAC UPS systems will operate without the neutral wire at the input of the system, however, the neutral wire is required when bypassing the system without the use of the VPXT (Voltage and Phase Correction Transformer) option. _______ Do not attempt to change the plug supplied with the equipment. Federal Signal offers receptacle/plug converters that will allow you to match most standard receptacles. _______ All the UPS requires a ground wire. The ground wire should be the same size as the input feed wires. The ground that feeds the UPS should be of good integrity and dedicated to the UPS. The run should be as short as possible. Conduit cannot be used for the grounding of the circuit. Reference: NEC 250-5 and 250-6 _______ Systems using the VPXT option, do not require the neutral from the AC source panel. The VPXT recreates the neutral and generates a new neutral ground bond in accordance with the National Electric Code. _______ The System is designed to operate on the primary power you select. Verify that the available power source meets the voltage and current requirements. Under no circumstances should the primary not conform to the UPS operating voltage you have selected. _______ If this voltage is not correct for your application refer to section "Changing Input Voltage." Page 4.12. _______ The input plug is 120 or 240 volts unless tagged for 208 volts. Page 4.8 THE FEDERAL SIGNAL UPS AC INPUT BREAKER, WIRING AND AMPERAGE MATRIX KVA KW AC LINE VOLTAGE SERVICE PANEL AC BREAKER NO. OF INPUT WIRES REG. OUTPUT VOLTAGE OUTPUT CURRENT 3.5 3.5 3.5 5 5 5 7.5 7.5 7.5 2.5 2.5 2.5 3.5 3.5 3.5 5.3 5.3 5.3 120 208 240 120 208 240 120 208 240 40 25 20 50 30 30 80 50 50 3W 4W 4W 3W 4W 4W 3W 4W 4W 120 / 240 120 / 240 120 / 240 120 / 240 120 / 240 120 / 240 120 / 240 120 / 240 120 / 240 29 16.8 14.6 41.7 24 20.8 62 36 31 NOTE: Output currents at 120 volts (from 3.5K to 7.5K) are derived from the addition of two line to neutral loads. Page 4.9 THE FEDERAL SIGNAL UPS SET-UP AND START-UP PROCEDURES *** DO NOT ATTEMPT TO OPERATE THE *** UNIT UNTIL THE FOLLOWING STEPS HAVE BEEN COMPLETED _______ Prior to turning on the power and starting the UPS, it is very important to check out the mode in which you intend to operate the system. _______ All operating parameters are factory set to standard operating modes. _______ Selector switch S1 and S2 at the rear of the UPS allows you to change the mode operation that best suits your specific needs. SELECTOR SWITCH S1 (DIP SWITCH SELECTING) Operating Mode Position 1 - Slew Rate Normal (factory set to normal). Do not change switch with UPS on. *Position 2 -Slew Rate Fast - This selection is typically used when the UPS must follow a rapidly changing input frequency. I.E.....engine generators. Do not change switch with UPS on. NOTE: Only one switch must be on at a time for Positions #1 and #2.. Position 3 - Manual or Automatic Restart - (Automatic Restart - following a power down caused by depleting the battery power, the UPS will automatically start upon restoration of utility power). This selection can be changed with the UPS on. Manual restart requires pushbutton at front of unit to be reset. ON = Auto Restart, OFF = Manual Restart. Position 4 - Audible Alarm - (Off to silence audible alarm). This selection can be changed with the UPS on. * DEFAULT SELECTOR SWITCH S2 (DIP SWITCH SELECTING) Input Voltage Do not change this setting without changing or verifying that the input wiring matches the input voltage selection. (See Changing Input Voltage on Page 4.12). Page 4.10 THE FEDERAL SIGNAL UPS APPLYING POWER _______ Re-install all panels that may have been removed during installation. _______ Verify the input voltage matches the UPS input volts and the UPS output voltage matches your equipment’s input voltage. _______ Turn off all loads attached to the UPS. _______ Using the line cord and plug supplied, plug in the UPS or for hardwire installation turn on the input service breaker. NOTE: Batteries require charging for 6 to 8 hours. Backup time is reduced until batteries are fully charged. _______ Turn on the battery and utility breaker. There will be a few seconds delay as the unit comes on. The digital display and "System On" LED will illuminate. Scroll to the "Output Volts" function and make sure the output voltage is correct. _______ Verify the output voltage on the UPS matches the load requirement. Do not plug your equipment in if output voltage is out of spec, contact factory. _______ Simulate a power loss by turning off the UTILITY BREAKER ONLY, located on the front of the UPS. An "Audible Alarm" will sound and the following LED's will illuminate. - System On - System on Battery - Alarm _______ While on inverter, verify the output voltage on the UPS matches the load requirement while on batteries. Do not plug your equipment in if output voltage is out of spec, contact factory. _______ Turn on the Utility breaker and the UPS will return to utility power. _______ With the UPS running and “System On” LED illuminated, turn on the output circuit breakers and loads. _______ Some loads start hard and may cause the UPS to display a temporary overload. This is normal and in no way damage the UPS. _______ If the overload (typically to much equipment connected to the UPS) persists and is in excess of 150% the UPS will shut off within one minute. If the unit is overloaded , some equipment will have to be removed or the UPS must be expanded. Call Customer Support for any questions during start up at 1-708-534-4756. Page 4.11 THE FEDERAL SIGNAL UPS CHANGING INPUT VOLTAGE CAUTION: HIGH VOLTAGES - ONLY QUALIFIED ELECTRICIANS SHOULD SERVICE. _______ Turn off all power (open AC and DC breaker on the front of the unit) and unplug the UPS prior to performing the following steps. _______ Locate the input terminal strip through the rear access of the UPS. _______ The illustrations on Page 4.13 and 4.14 display the method in which the wiring at the input terminal must be connected for your selected voltage. *** IMPORTANT *** _______ Selector Switch 2, at the rear of the UPS, must match the input voltage selection. * No transformer tap is provided in standard unit. Consult factory for applications of this voltage. *** CAUTION *** When using bypass switches, changing the input voltage may negate the bypass function. Be sure that the input and output of the UPS are the same. Contact the Customer Support Department at Federal Signal at 1-708-534-4756 if you have any questions. Page 4.12 THE FEDERAL SIGNAL UPS AC INPUT AND OUTPUT WIRING FOR 3.5 KVA AND 5 KVA Note: To change output voltage a pre-wired output connector and receptacle panel is required. Contact factory. *** WARNING *** CAUTION RISK OF ELECTRICAL SHOCK. THE UPS RECEIVES POWER FROM MORE THAN ONE SOURCE. BE SURE BOTH UTILITY AND BATTERY CIRCUIT BREAKERS ARE IN THE OFF POSITION BEFORE SERVICING Page 4.13 THE FEDERAL SIGNAL UPS AC INPUT AND OUTPUT WIRING FOR 7.5 KVA *** WARNING *** CAUTION RISK OF ELECTRICAL SHOCK. THE UPS RECEIVES POWER FROM MORE THAN ONE SOURCE. BE SURE BOTH UTILITY AND BATTERY CIRCUIT BREAKERS ARE IN THE OFF POSITION BEFORE SERVICING. Page 4.14 THE FEDERAL SIGNAL UPS BATTERY INSTALLATION **** WARNING **** CAUTION RISK OF ELECTRICAL SHOCK. THE UPS RECEIVES POWER FROM MORE THAN ONE SOURCE. BE SURE BOTH UTILITY AND BATTERY CIRCUIT BREAKERS ARE IN THE OFF POSITION BEFORE SERVICING. KVA 3.5 5 7.5 DC/BUS 48 48 96 Page 4.15 FEDERAL SIGNAL UPS CUSTOMER SATISFACTION CHECKLIST The employees at Federal Signal strive to produce and maintain quality UPS’s. All facets from installation through to operation are reviewed so that the unit is the easiest to install and operate. We listen to our customers suggestions and recommendations. This insures that you receive equipment with the most current technology and functionality. We value your suggestions and recommendations. Please take the time to fill out the following form. Your comments allow Federal Signal to better serve you. SATISFACTORY TO POOR How was the unit upon arrival? Was the installation simple? Was the start-up simple? Do you find the UPS easy to operate? Is the information clear and concise? Does the UPS meet your expectations? Do you feel the UPS has enough capacity to fulfill your growth needs? Are the ergonomics of the UPS satisfactory? How was the communications with the factory or the representative? 1 2 _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ 3 _____ _____ _____ _____ _____ _____ _____ _____ _____ 4 _____ _____ _____ _____ _____ _____ _____ _____ _____ CIRCLE ONE Did the UPS solve a previous power problem? Do you have future applications? Do you have any other UPS needs? Is the UPS located in a computer room? Is the UPS maintained under a service contract? Would you like information on our Customer Support Plan? Would you recommend Controlled Power to others? Yes Yes Yes Yes Yes Yes Yes or or or or or or or No No No No No No No What type and model of equipment is the UPS supporting? __________________________________________________________________________________________ __________________________________________________________________________________________ Comments __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________ Complete and return to: Federal Signal Integrated Systems Group 2645 Federal Signal Drive University Park, IL 60466 Phone 1-708-534-4756 Page 4.16 COMMUNICATIONS The UPS provides complete diagnostic and operating status. The signals are available through a DB 25 Pin Female connector labeled J1 on the rear of the unit. Three methods can be used to communicate with the UPS: - Direct connect to a terminal. - Direct connect to a PC that is operating as a terminal emulator or a communication software that will emulate a terminal. - Modem operation. Once the communication link is established, system set points, system parameters, system status and memory modification is attainable. Any system status change will automatically cause the UPS to send an alert warning signal. The signal sent is "?". User software can be written to identify this signal and initiate automatic unattended action. J1 PORT - DB25 PIN FUNCTION Pin # 1 2 3 6 7 8 11 14 18 Name UPS On (Battery Operation) Receive Data Transmit Data + 12 VDC Supply Signal Ground UPS On (Ready) Low Battery Alarm (Shutdown Pending) General Alarm Remote Emergency Power Off 20 21 23 + 12 VDC Supply -12 VDC Supply Remote Emergency Power Off 25 12, 13 Signal to ground Bypass On Description Closes when on battery operation. RS/232 RS/232 Limited to 1 ma Communication signal ground. Closes when UPS output power is present. Closes when low battery. Closes on alarm condition. Contact closure with reference to ground shuts unit down. Limited to 1 ma Limited to 1 ma Positive DC input w/reference to ground shuts unit down. Communication signal ground. Closes when switch is on Bypass Pins 8, 1, 11 and 14 are normally open cold contacts that change state as described. The contacts are referenced to pins 7 or 25 which is chassis ground. Contact Rating: AC/DC 24 volts .5 amps. Pins 12 and 13 are totally isolated cold contacts rated: AC/DC 24 volts .5 amp. Pin 23 requires a high input limited to 20 VDC with respect to pin 7 and 25 or the +12 VDC signal at pin 6 may be utilized with an external contact. RS232 TECHNICAL SPECIFICATION SUMMARY Connector Format Baud Rate Parity Duplex Delimiters Flow Control 25 Pin, Type D, Female ASCII 8 Bit, One Start Bit, One Stop Bit Default 1200 None Full Carriage Return per Block XON / XOFF Page 5.1 COMMUNICATIONS CON'T SYSTEM PARAMETERS To attain System Parameters and Status send the lower case "s" to the UPS from the terminal. Description AC Volts In AC Volts Out Battery Volts AC Amps Out Percent of Full Load Watts Out Volts Amps Out Power Factor Incoming Line Frequency Outages Overloads Response Sample Display Explanation Input Voltage = 240 The voltage the UPS is receiving. Output Voltage = 240 The voltage the UPS is delivering to the load. Battery Voltage (%) = 98 Percent of full charge of the battery. Output Current = 2.4 Amperage the load draws from the UPS. Load (%) = 90 The percentage of total capacity that the load is using. KW = .54 The total real power the UPS is delivering to the load. KVA = .77 The total apparent power the UPS is delivering to the load. Power Factors = 0.70 The power factor of the computer load (KW/KVA). Frequency = 60.0 Displays input frequency when on line, output frequency when on inverter. Number of Outages = xx The number of outages recorded from the last clear function. Number of Overloads = xx The number of overloads from the last clear function. Status Description Synchronization Sample Display Synchronization UPS On Low Battery Warning UPS On Low Battery Warning On Battery On Inverter Overload Alarm Overload Alarm Low Output Low Output High Output High Output Weak Battery Weak Battery Frequency Fault Frequency Fault Over temp Warning Over temp Warning Shorted SCR Shutdown Low Battery Shutdown Output Shutdown Shorted SCR Shutdown Low Battery Shutdown Output Shutdown Explanation When the UPS is in sync with the line frequency. When the UPS is producing an output voltage. When the battery level reaches the preset value of alarm condition. When the UPS is supplying output power from the batteries. When the UPS is supplying more power than its rated capacity. When the output voltage goes lower than the preset alarm condition. When the output voltage exceeds the preset alarm condition. When the batteries discharge rate is greater than normal. When the fault exceeds the preset range of the alarm conditions. When the UPS temperature reaches a critical level. Shutdown 2 minutes after warning. When the power electronic switch is shorted. When the batteries are depleted the UPS shuts off. If selected, the UPS will shutdown when the output exceeds set points. Page 5.2 COMMUNICATIONS CON'T SYSTEM SET POINTS To attain System Set Points send the lower case "p" to the UPS from the terminal. Note: This allows monitoring of system set points only. To modify set points see page 5.4. Description Minimum AC Start Voltage Maximum AC Start Voltage Low Output Alarm Set Point High Output Alarm Set Point Low Battery Warning Set Point High Battery Warning Set Point Low Frequency Alarm Set Point High Frequency Alarm Set Point Over Temperature Set Point Nominal Input Voltage Response Sample Display Password min AC start = 204 Required max AC start = 264 Required low output = 210 Required high output = 264 Required low battery (%) = 040 high battery (%) = 105 low frequency = 59 Required No Access high frequency = 61 Required over temperature = 160 input nominal = 240 No Access Nominal Output Voltage output nominal = 240 Required Maximum KVA Rating Low Line Switch Point Note: If using Fuzzy Logic enter as shown. High Line Switch Point output KVA = 5000 sag switch point (%) = 85. Fuzzy logic = 00. surge switch point (%) = 110 Required Required Low Line Sample Accumulation Buffer sensitivity (1-2) = 1 Required Frequency Accumulation Buffer frequency delay (2-9) = 8 Required Power Grid Stability Check transfer delay (sec) = 10 No Access System ID Number system ID = units 8 digit serial #. output shutdown enable (1/0) = 0 Required System Shutdown Enable Required Required Required Required Explanation Minimum AC voltage required before the UPS will start. If the input voltage exceeds this value, the UPS will not start. Alarm or shutdown if the output voltage dips to this set value. Alarm or shutdown if the output voltage reaches this set value. Percent of battery capacity alarm set value. Manufacturer set point for diagnostics and charger control. Alarm or shutdown if the output frequency dips to this set value. Alarm or shutdown if the output frequency reaches this set value. Manufacturer set point. Nominal input voltage. Switch set points are calculated from this value. Nominal output voltage. Value from which other calculations are derived. Maximum KVA rating of the UPS. Percent below nominal AC input when the UPS will switch to battery operation. Percent above nominal AC input when the UPS will switch to battery operation. Averaging factor for low line voltage. 1 = least averaging (greater sensitivity). Number of AC cycles required to be out of set frequency range prior to switching to inverter mode. Amount of time in seconds the UPS will wait before accepting the AC input. System identification serial number. If enable set = 1, the UPS will shutdown when alarm set points are exceeded. 0 = audible alarm only. Page 5.3 COMMUNICATIONS CON'T There are alarm and operation set points that will alter the behavior of the UPS. It is not recommended that these be modified without a complete understanding of the function. For added security, a password will be required to continue into the memory modification group. * Consult Customer Support at 1-708-534-4756 prior to modifying set points. To enter into the memory modification group send the lower case "m" from the terminal to the UPS. The response will be: PASSWORD= (consult factory) Upon entering the correct password, one line item will be displayed, i.e., Min AC Start = 204 Min AC Start = * If the value is to remain unchanged press ENTER or else type the new value. To end the process type the lower case "e". Other interactive signals can be sent that will place the UPS in the inverter operation mode and/or shut the UPS down. The following functions require the password. Testing the UPS inverter send SHIFT I. This will cause the UPS to run on battery power for a few seconds and then return to normal. To remotely shutdown the UPS from the communication link send SHIFT D. You cannot restart the UPS from the communication line. To clear the log send lower case "c". SYSTEM SET POINTS - FACTORY PRESET LEVELS Description Value Entered w/Nominal Input Voltage = 120 Value Entered w/Nominal Input Voltage = 208 = 177 = 229 = 208 Same = 182 = 229 Same Value Entered w/Nominal Input Voltage = 240 = 204 = 264 = 240 Same = 210 = 264 Same Minimum AC Start Voltage Maximum AC Start Voltage Nominal Input Voltage Nominal Output Voltage Low Output Alarm Set Points High Output Alarm Set Points Low Line Switch Point. Note: Fuzzy Logic is entered as shown. High Line Switch Point Low Battery Warning Set Point Low Output Frequency Alarm Set Point High Output Frequency Alarm Set Point Low Line Sample Accumulation Set Point Frequency Accumulation Buffer System Shutdown Enable Maximum KVA Rating = 102 = 132 = 120 Refer to units spec tag. = 105 = 132 Low Line Switch % = 85. Fuzzy Logic = 00. % = 110 % = 040 =059 Same Same Same Same Same Same = 061 Same Same Available (1-2) = 1 Same Same Available (2-9) = 8 Audible Only = 0 Enter Actual KVA Rating – See units spec tag. Same Same Same Same Same Same Page 5.4 FEDERAL SIGNAL UPS WARRANTY ***Warranty void unless this form is completed and returned to *** Federal Signal Federal Signal warrants that the UPS and its components will remain free from defects in material and workmanship for the period of 18 months from the date of delivery and agrees to replace, F.O.B. it's factory, any part which fault through defect in material or workmanship during such period. This Warranty applies only to the original purchaser who must properly register the product within (10) days of receipt. 1. The Warranty shall be effective only if and so long as the system is installed and operated in the manner specified in this manual which accompanied the UPS and operated within the ratings on the nameplate of the system. 2. The Warranty shall be void if any alteration is made to the system or any of its components are altered by anyone other than an authorized Federal Signal Power Service Personnel without the written permission of Federal Signal. 3. The Warranty shall be effective provided the purchaser pays the cost of transporting the questionable component to and from the Federal Signal factory at his own expense. The cost of installation of the defective component is the responsibility of the purchaser. Factory servicemen are not included in this warranty. If the component fault has been caused by misuse or abnormal conditions in the judgment of Federal Signal, after inspection at our plant, the customer will be charged for repairs based on parts and labor required. 4. This Warranty is in lieu of all other warranties, expressed or implied. Federal Signal neither assumes nor authorizes any person to assume for it, any liability other than that specifically set forth in this Warranty. Except for its obligations, Federal Signal assumes no responsibility for consequential or other damages resulting from defects in or failure of the system or any component. System #_______________________________ Model #____________________________________ Date___________________________ Application__________________________________________ Company___________________________________________________________________________ Address____________________________________________________________________________ City/State/Zip________________________________________________________________________ Contact______________________________________ Phone #_______________________________ Start-Up Organization_________________________________________________________________ Please complete and return to : Federal Signal Integrated Systems Group 2645 Federal Signal Drive University Park, IL 60466 Phone 1-708-534-4756 Page 6.1 THE FEDERAL SIGNAL UPS MAINTENANCE PROCEDURE WARNING: ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD MAINTAIN THIS EQUIPMENT. *** DANGER HIGH VOLTAGE *** GENERAL MAINTENANCE The best preventive maintenance is to operate the UPS in a clean environment with proper ventilation and no restrictions on air intakes and cooling fan outputs. Battery connections should be tightened annually by qualified electrical personnel. Batteries should be replaced every 5 years. The UPS should be checked monthly on battery operation. Take precautions to have computers in a mode that could tolerate a shut down. To simulate a utility power loss, simply turn off the AC circuit breaker located on the UPS. Observe the battery display. A properly functioning system will show 90 - 100% on the battery display and should decrement slowly. COMPLETE MAINTENANCE CHECK PREPARATION A shutdown period must be scheduled to perform maintenance unless the system is equipped with a "Maintenance Bypass" switch. A computer load should be available to test the UPS with a loss of power simulation. EQUIPMENT Digital multimeter, wire brush or other cleaning device (for battery connections), insulated tools (for battery connections) and safety glasses. SYSTEM OPERATION 1. With power on, check display functions of unit for proper operation. 2. Turn AC and DC breakers off. VISUAL INSPECTION 1. Remove top panel. 2. Remove any load from units output. 3. Check for burnt, frayed, broken or loose connections. Look closely in the following areas: Inverter components, power semi-conductors, input, output connections, circuit breakers, transformer connections, capacitors, fans, bypass switch and electronic circuit boards. 4. Correct any loose connections, replace any physically burned or broken components. Use extreme care when replacing components to assure correct installation. NOTE: Note check off all items on the Performance Checklist. Page 7.1 BATTERY CHECKS *** WARNING DANGER HIGH VOLTAGE *** Batteries have high voltage present. Accidental shorts may cause severe arching, burning or battery explosion wear eye protection and use insulated tools when servicing batteries. Remove all jewelry. NOTE: Never mix batteries with a different brand or size. Never mix old and new batteries. Dispose of batteries properly. Do not open, mutilate or dispose in a fire. 1. Visually inspect all battery connections,. If there is any sign of corrosion - disconnect that battery and clean with wire brush. Tighten all other battery connections. Make sure batteries are not swollen or cracked. If they are, contact factory. 2. Turn AC and DC breakers on. Let unit run for a minute. 3. Verify battery float voltage in table A after following these steps. Place DC voltmeter on millivolt scale and measure across resistor R5 on switch mode board #406242 This signal limits at 75 millivolts when batteries require a full charge. If this condition exists allow batteries to charge until signal is 15 millivolts or less. 4. Place voltmeter across K1 connector on switch mode board wires V2 (common) and V1. Adjust P2 float voltage as shown in Table A. TABLE A UNIT SIZE 3.5 - 5 KVA 7.5 KVA NUMBER OF BATTERIES 4 8 FLOAT VOLTAGE 54.5 VDC 109 VDC 5. Turn AC input breaker off only, unit should invert. Note the percentage of battery time remaining. The rate at which the batteries decrease is related to the actual load on the output and battery backup time. If back-up time is extremely short, contact factory. 6. Complete a NO LOAD INVERTER test and record readings on Performance Checklist. 7. Turn AC breaker on, unit will return to line power, complete a NO LOAD ON LINE test and record readings on Performance Checklist. 8. Check any emergency power off devices and any options - bypass switch, REPO, remote monitor, computer interface, etc..... 9. Test unit ON LINE with load and record readings on Performance Checklist. 10. Invert unit with loads and record readings on Performance Checklist. NOTE: Observe the percentage of battery time remaining. The rate at which the display decreases is related to output load and battery back-up time. If battery back-up time is very short, contact factory. GENERATOR TEST 1. If generator is backing the UPS, check to be sure the UPS operates properly with the generator. A. Check generator operation with no load. Unit should switch to inverter when generator kicks on. After a minute or so the UPS should switch back to normal mode and run off the generator. Record UPS output voltage on Performance Checklist. B. Check generator with customers loads. Follow same steps stated above and record readings on Performance Checklist. Page 7.2 THE UPS PERFORMANCE CHECKLIST COMPANY:____________________________ MODEL #:_________________ SERIAL :________________ DATE:______________________ 1. Comments or problems with UPS ___________________________________________________________ 2. Display functions_________________________ Cooling Fans (3)_________________________ 3. Electrically wired properly i.e.. Bypass switch, breakers, ground ______________________ 4. Verify input and output voltage. Compare with spec tag _________________________ 5. Test any emergency shutoff devices _____________________________________ 6. Check tightness of electrical connections - Bypass switch ____________ Input connections __________ Output connections __________ Heatsink assembly __________ Main battery connector __________ Circuit board connections _________ Resonant capacitors __________ Battery connections __________ Fan Motor _________ 7. UPS environment clean and dust free Yes ______ No ______ 8. Charger output voltage __________ VDC Charger current shunt __________ Milli VDC 9. NO LOAD ON LINE AVAILABLE LOAD ON LINE Input voltage ________ VAC Output voltage L1 to L2 __________ VAC L1 to N ________ VAC L2 to N ________ VAC L3 to N ________ VAC L1 to L2 ________ VAC 10. INVERTER NO LOAD TEST INVERTER FULL LOAD TEST Output voltage L1 to L2 ________ VAC L1 to N ________ VAC L2 to N ________ VAC L1 to L3 _______ VAC L3 to N ________ VAC 11. BATTERY VOLTAGE 1. 2. 3 4. 5. 6. 7. 8. 9. 10. 11. 12. Input voltage ________ VAC Output Voltage L1 to L2 ________VAC L1 to L3 ________ VAC Input Current ________ Amps Output Current _______ Amps Output voltage L1 to L2 ________ VAC L1 to N ________ L2 to N ________ VAC L3 to N ________ L1 to L3 ________ VAC Output Current _____________ Amps (Record actual voltage of each battery) No Load With Load No Load With Load No Load With Load ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ __________ 14. Generator check A. No load on GEN-Output =_______VAC. B. Invert on GEN-Output = _______ VAC. Does UPS return to normal when on generator ______ yes ______ no. Page 7.3 THE UPS GENERAL TROUBLE SHOOTING GUIDE PROBLEM NO OUTPUT WHEN UTILITY POWER FAILS UPS SHUTS OFF OR OVERTEMPS PROBABLE CAUSE A. DEFECTIVE CONTROL CIRCUITS B. DEFECTIVE BATTERY OR ASSOCIATED WIRING C. UNIT IN BY PASS MODE D. DC BREAKER TRIPPED E. BATTERIES WEAK A. CONTACT FACTORY B. CHECK WIRING AND TEST BATTERIES REFER TO MAINTENANCE PROCEDURES C. CHECK BY PASS SWITCH D. RESET DC BREAKER E. ALLOW BATTERIES TO CHARGE 24 HOURS AND TEST UPS A. AIR INTAKE BLOCKED B. EXHAUST FANS BLOCKED A. CLEAN INTAKES B. CHECK FOR PROPER CLEARANCE, CLEAN EXHAUST C. REPLACE DEFECTIVE FANS D. CHECK OPERATING SPECIFICATIONS E. VERIFY OUTPUT RATINGS C. DEFECTIVE FANS D. ROOM TEMPERATURE TO HOT E. UNIT OVERLOADED NO OUTPUT AT START UP A. OUTPUT BREAKER OPEN OR OUTPUT FUSE OPEN B. WRONG INPUT VOLTAGE C. NO INPUT VOLTAGE D. DEFECTIVE BATTERY E. F. G. H. UPS WILL NOT RETURN TO UTILITY POWER SHORTED OUTPUT DEFECTIVE INVERTER COMPONENTS DEFECTIVE CONTROL CIRCUITS AC OR DC BREAKER OFF A. INPUT VOLTAGE OR FREQUENCY OUT OF SPEC (GENERATOR APPLICATION) B. DEFECTIVE CONTROL CIRCUITS C. INADEQUATE SOURCE D. AC BREAKER TRIPPED SHORT BATTERY BACK UP TIME A. BATTERY DISCONNECTED B. BATTERY NOT CHARGING C. OPEN CHARGER FUSE D. DEFECTIVE BATTERY E. BATTERY NOT CHARGED F. UNIT OVERLOADED UPS ALARMS OCCASIONALLY A. NORMAL B. INTERMITTENT ALARM UNIT OPERATES BUT DROPS LOAD SOLUTION A. COMMUNICATIONS ERROR B. OUTPUT BREAKER TRIPPED OR FUSE OPEN C. UNIT OVERLOADED A. CHECK BREAKER OPERATION AND TEST OR REPLACE FUSE B. VERIFY INPUT VOLTAGE AND SELECTOR SWITCH SW2 C. VERIFY SOURCE FEEDING THE UPS D. TEST BATTERIES REFER TO MAINTENANCE PROCEDURES E. DISCONNECT OUTPUTS AND RESTART UNIT F. CONTACT FACTORY G. CONTACT FACTORY H. TURN ON BOTH AC AND DC BREAKERS A. VERIFY INPUT SPECS, SELECT DIFFERENT SLEW RATE (REFER TO SET UP PROCEDURES IN INSTALLATION SECTION) B. CONTACT FACTORY C. VERIFY SOURCE FEEDING UPS IS ADEQUATE D. RESET AC BREAKER A. CHECK BATTERY CONNECTIONS (REFER TO MAINTENANCE PROCEDURES) B. CHECK BATTERY FLOAT VOLTAGE REFER TO MAINTENANCE PROCEDURES C. CHECK FUSE F1 ON CHARGER BOARD D. TEST BATTERIES REFER TO MAINTENANCE PROCEDURES E. ALLOW BATTERIES TO CHARGE 24 HOURS F. CHECK % LOAD DISPLAY AND REDUCE LOAD A. UPS IS PROTECTING YOUR EQUIPMENT FROM MOMENTARY SAGS AND SURGES B. MONITOR TYPE AND FREQUENCY OF ALARM, TAKE ACTION ON PARTICULAR ALARM. A. CHECK INTERFACE CABLES FOR CONTINUITY TEST COMMUNICATION SIGNALS B. RESET OUTPUT BREAKER AND TEST OUTPUT FUSE C. CHECK % LOAD DISPLAY AND REDUCE LOAD NOTE; The UPS has two shutdown levels, the first one releases the load, and the second shutdown will disable the internal circuitry after a period of time, before the batteries get too low. If this situation occurs, both breakers on the UPS must be opened for a couple minutes and then closed, at which point the unit should power up. Page 8.1 Page 8.2 3.5 - 7.5 KVA PARTS LIST PRINTED CIRCUIT BOARDS PART NUMBER IS-415336 IS-406242 IS-28056 IS-28556 IS-28295 IS-28917 DESCRIPTION Control Board Power Supply Snubber Board Display Board E.M.I. Filter Board SCR DV/DT Board all units all units all units all units all units all units Transistor Diode SKKT 81/04 Diode DD-89N-12K Relay (solid state) all units all units all units all units INVERTER COMPONENTS IS-19183 IS-19884 IS-104561 IS-104562 MISCELLANEOUS (FUSES, CAPACITORS, ETC...) IS-103391 IS-16120 IS-19188 IS-13576 IS-16123 IS-18271 IS-13577 IS-13695 IS-109218 IS-104435 IS-13319 IS-18385 IS-18386 Capacitor, DC Input Capacitor Capacitor, DC Ferro Capacitor Ferro Capacitor Ferro Capacitor Ferro Capacitor Fan Motor High Speed Fan Motor Caster Thermal Sensor Fuse, 1A Fuse, 3/4A 3.5K - 5K all units 7.5K all units all units all units all units all units all units all units all units all units all units. Page 9.1 PLUGS, RECEPTACLES AND DISTRIBUTION PANELS CAUTION: RISK OF ELECTRICAL SHOCK. THE UPS RECEIVES POWER FROM MORE THAN ONE SOURCE. BE SURE BOTH UTILITY AND BATTERY CIRCUIT BREAKERS ARE IN THE OFF POSITION BEFORE SERVICING. The following is a list of receptacles available that may be configured onto a distribution panel and plugged into the output of your UPS. Input plugs are also available in these configurations. INSTALLATION CHANGING POWER DISTRIBUTION PANELS ________Refer to figure ________Turn off both utility and battery breaker. ________Unplug all items supplying power to the UPS and battery. ________Remove the four screws that hold the output distribution panel in place. ________Unplug the output connector and disconnect the green ground wire from the ground lug. ________Replace the patch panel with new patch panel. ________Be sure to re-install the ground wire. ________Re-attach all panels. ________Apply power and verify output receptacles have proper voltage before plugging in critical loads. Page 10.1 . BYPASS SWITCHES IMBB Internal make before break switch. This switch bypasses battery backup capability of the UPS, but still utilizes the power purification transformer to provide clean power to your computers in the event of a battery or inverter failure. CAUTION: This is not a "Maintenance" bypass switch. The UPS must be completely shutdown to perform service on the UPS. You may operate this switch with no interruption to critical loads. WARNING: Do not operate this switch while on battery power. Page 10.2 OTHER OPTIONS REMOTE EMERGENCY POWER OFF PUSH-BUTTON This option allows you to completely disable the UPS, which is required by many local safety codes. The pushbutton may mount near an entrance or exit and comes standard with 50 feet of cable terminated with a 4 pin connector. The 4 pin connector is used in conjunction with a DB25 gender changer that plugs into the UPS. (See Page 10.4 for installation diagram.) MONOPHONE AUTOMATIC PHONE DIALER Monitors when UPS is on battery power, when the batteries are low and the room temperature. Each of these conditions will automatically dial up to four preprogrammed phone numbers and delivers a voice synthesized warning message. The monophone will continue to call until the message is acknowledged. Warning features may be added which are - moisture detection, unauthorized access and alarms pertinent to heating and cooling systems. The "call in" feature allows you to call in from any outside telephone. You receive a report on monitored conditions and may listen for unusual sounds in the room. It is recommended to plug the monophone into the UPS so you are assured the monophone is working during power outages. The monophone has it's own battery and may be plugged into any 120 volt AC outlet, but the battery is not rechargeable and must be replaced annually. This option comes with 50 feet of cable terminated with a DB25 connector and a 10 foot telephone cord. NOTE: All auxiliary conditions are contact closure inputs. (See Page 10.4 for installation diagram.) REMOTE ANNUNCIATOR This option provides a remote emergency power off push button and remotely monitors the UPS status with incandescent bulbs. The monitor function includes UPS On, System on Battery, Impending Shutdown, and ByPass Active. The option comes with 50 feet of cable terminated with a DB25 connector and a 24 volt power supply that plugs into the output of the UPS. (See Page 10.4 for installation diagram.) NOTE: If a 4X port expander is used the 24 volt power supply is not required. Remote annunciator may be connected directly to 4X expander. 4X COMMUNICATIONS PORT EXPANDER This option allows communication to the UPS by up to four separate peripherals. All ports are isolated eliminating mixed ground problems or incompatibility of signal style. The 4X Expander must be plugged into the UPS and comes with a interconnecting cable for the J1 port on the UPS. (See Page 10.4 for installation diagram.) 2X COMMUNICATIONS PORT EXPANDER (Option # 103934) This option allows communication to the UPS by up to two separate peripherals. The option has one male DB25 connector and two female DB25 connectors one foot long. Note: There is NO isolation between the two female connectors. Page 10.3 UPS COMPONENT LOCATIONS AND OPTIONS INSTALLATION DIAGRAM Page 10.4