Metasys Integrator

advertisement
Application Note
Issue Date May 25, 2004
APPLICATION NOTE
Metasys Integrator® GE Power Application
lntroduction
3
Application Details
3
Component Requirements
6
Vendor Contact Information
10
Design Considerations
11
Cable Connections
13
Cable Pinouts
13
Metasys Integrator Unit Setup
15
Point Mapping Tables
19
Epic MicroVersaTrip System
19
GE Power Leader Meter—485 PIM
21
Power Leader MicroVersaTrip—485 PIM
23
Power Leader Electronic Power Meter—485 PIM, Power Leader Modbus
Concentrator, Daisy-chained Devices
25
GE Power Leader Meter—Power Leader Modbus Concentrator
27
GE Power Leader Spectra MVT— Power Leader Modbus Concentrator
29
GE Power Leader Enhanced MVT— Power Leader Modbus Concentrator
31
Multilin Power Quality Meter—Daisy-chained Devices
33
GE MDP—Daisy-chained Devices
37
EPM3720 Power Meter—Daisy-chained Devices
40
EPM3710 Power Meter—Daisy-chained Devices
44
EPM5300P Power Meter—Daisy-chained Devices
46
EPM7300 Power Meter—Daisy-chained Devices
47
EPM9650Q Power Meter—Daisy-chained Devices
49
© 2004 Johnson Controls, Inc.
Code No. LIT-6295291
1
www.johnsoncontrols.com
Metasys Network Setup
50
Mapping to a CS Object
50
Custom Integration
51
2 Metasys Integrator—Metasys Integrator GE Power Application
lntroduction
This document explains Metasys Integrator® GE power applications,
which include:
•
Epic MicroVersaTrip™ Field Programming Unit (FPU) used on
GE switch gear and switch boards
•
GE Power Leader™ products
•
GE Power Leader Modbus Concentrator
•
Multilin™ Power Quality Meter (PQM)
•
GE MDP
•
EPM3720 Power Meter
•
EPM3710 Power Meter
•
EPM5300P Power Meter
•
EPM7300 Power Meter
•
EPM9650Q Power Meter
Use this document with the Metasys Integrator unit technical bulletins
For information on vendor equipment, see GE documentation (obtainable
from a GE representative), or call 1-800-437-3765.
Application
Details
Metasys Integrator unit allows GE® equipment to become an integral part
of the Metasys® and Metasys Companion Networks. Once the GE Epic
MicroVersaTrip System, GE Power Leader Network, Multilin Power
Quality Meter, GE MDP, or EPM3720/3710/5300P/7300/9650Q Power
Meter is connected to a Metasys or Companion Network via the
Metasys Integrator unit, its data is available to the full complement
of Metasys Building Automation System (BAS) features, including
Change-of-State (COS) monitoring, alarm notification, trend, and
totalization.
The Epic MicroVersaTrip System, an early generation GE power
monitoring system, consists of one Field Programming Unit (FPU) and up
to 30 Breaker Programmers. The FPU acts as an interface between GE trip
units and non-GE devices (such as Metasys Integrator unit). Metasys
Integrator unit allows status information and commands to be transmitted
between the FPU and programmers and the Metasys or Companion
Networks. Each Metasys Integrator vendor port can connect to one GE
FPU.
Metasys Integrator—Metasys Integrator GE Power Application 3
The GE Power Leader Network can be comprised of two methods to
integrate their Commnet devices into a Modbus network:
•
Networks utilizing GE Product Interface Module (PIM) to convert
GE Commnet devices (i.e., MicroVersaTrip PM units, Power Leader
Meters, etc.) to Modbus
•
Networks utilizing GE Power Leader Modbus Concentrator
•
Networks utilizing standard Modbus RTU protocol
The GE Power Leader Network consists of the Commnet Network and an
interface device. The interface device can be either the 485 Product
Interface Module (PIM) or the GE Power Leader Modbus Concentrator.
The 485 PIM handles communication between the Metasys Integrator unit
and the GE devices. The GE Power Leader Network consists of one
485 PIM and up to nine Commnet Power Leader devices (see Figure 2).
The 485 PIM is a non-standard Modbus RTU protocol device and cannot
be on the same 485 network as other standard Modbus devices.
The GE Power Leader Modbus® Concentrator handles communication
between Metasys Integrator unit and the GE Commnet devices. Since
Modbus RTU protocol is used for communication to the GE Power Leader
Modbus Concentrator, the same Metasys Integrator port can be connected
to a 485 Modbus network. This network consists of one or more Power
Leader Modbus Concentrator devices, and daisy-chained devices such as
the PQM and the EPM3720/3710/5300P/7300/9650Q—as well as other
standard Modbus RTU protocol devices—up to a total number of
32 devices.
The Multilin Power Quality Meter (PQM), MDP,
EPM3720/3710/5300P/7300/9650Q Power Meter, and Power Leader EPM
(with Modbus Communication Option) communicate via an RS-485 Port.
This requires the use of the Multilin RS-232 to RS-485 Converter to
facilitate communication between the RS-232 vendor ports on
Metasys Integrator unit and the RS-485 port on the daisy-chained device.
Standard Modbus RTU protocol is used. Up to 32 daisy-chained devices
can then be connected in a daisy chain configuration.
Figure 1 shows GE Epic MicroVersaTrip System and Metasys system
integration. Figure 2 shows the GE Power Leader Network and Metasys
system Companion integration. Figure 3 shows
EPM3720/3710/5300P/7300/9650Q Power Meter and Metasys system
integration. All these integrations apply to both Metasys and Metasys
Companion systems.
4 Metasys Integrator—Metasys Integrator GE Power Application
N1 LAN
Breaker
Breaker
Breaker
Programmer Programmer Programmer
Standard NCU
RS-232
Metasys
Integrator
GE
FPU
Epic MicroVersaTrip System
UNT
N2 Bus
GE1
Figure 1: GE and Metasys System Integration
Panel Unit
M3 Workstation
RS-232 RS-232 to RS-485
Converter
RS-485
485 PIM
(Product
Interface
Module)
Metasys
Integrator
Commnet Network
MicroVersaTrip
PM Units
UNT
Power Leader
Meter
Electronic Power
Meter
N2 Bus
Note: A PC version and converter may be substituted for the Panel unit.
gecomp
Figure 2: GE and Metasys Companion Integration
Metasys Integrator—Metasys Integrator GE Power Application 5
N1 LAN
RS-232 to RS-485
Converter
RS-485
485 PIM
(Protocol Interface
Module)
Commnet Network
RS-232
Standard NCU
Port A
PLM
Port B
Metasys
Integrator
UNT
EPM
RS-232
MicroVersaTrip
PM Units
RS-232 to RS-485
Converter
RS-485
PLM
N2 Bus
EPM
3710
EPM
3720
Power
Leader
EPM
EPM
5300P
EPM
7300
EPM
9650Q
Power
Leader
EPM
PQM
Power
Leader
MVT
EPM3720
GE Concentrator
Figure 3: EPM3720/3710/5300P/7300/9650Q Power Meter
and Metasys System Integration
Component
Requirements
Epic
MicroVersaTrip
System
To integrate the GE Epic MicroVersaTrip System, you need the following:
•
properly installed GE FPU and Breaker Programmers
•
RS-232 cable (for connecting the GE FPU to Metasys Integrator unit)
•
Metasys Integrator unit
•
N2 Bus (for connecting Metasys Integrator unit to the Metasys or
Companion Network)
•
portable PC for downloading vendor communication tables
(.VCT files) and network setup information, and for running
diagnostics
•
cable for connecting portable PC to Metasys Integrator unit
6 Metasys Integrator—Metasys Integrator GE Power Application
•
Power Leader
System—485 PIM
the correct vendor communication table (.VCT file) to download into
Metasys Integrator unit (supplied on diskette)
To integrate the GE Power Leader Network using the 485 PIM, you need
the following:
•
properly installed GE 485 PIM and 1-9 Power Leader devices
- Power Leader Meter
- Power Leader Spectra MVT
- Power Leader MVT PM Trip Units
- Power Leader EPM (with Commnet Communication Option)
Note: The GE Operator Interface cannot be used in conjunction with
Metasys Integrator unit.
Power Leader
System—
Power Leader
Modbus
Concentrator
•
RS-232 to RS-485 Multilin converter, Revision D
•
RS-232 cable (for connecting the converter to Metasys Integrator
unit)
•
RS-485 cable (for connecting the 485 PIM to the converter)
•
Metasys Integrator unit
•
N2 Bus (for connecting Metasys Integrator unit to the Metasys or
Companion Network)
•
portable PC for downloading vendor communication tables
(.VCT files) and network setup information, and for running
diagnostics
•
cable for connecting portable PC to Metasys Integrator unit
•
the correct vendor communication table (.VCT file) to download into
Metasys Integrator unit (supplied on diskette)
To integrate the Power Leader Network using the Power Leader Modbus
Concentrator, you need the following:
•
properly installed GE Power Leader Modbus Concentrator
- Power Leader Meter
- Power Leader Spectra MVT
- Power Leader Enhanced MVT PM ‘C’
- Power Leader Enhanced MVT PM ‘D’
- Power Leader EPM (with Commnet Communication Option)
•
RS-232 to RS-485 Multilin converter, Revision D
•
RS-232 cable (for connecting the converter to Metasys Integrator
unit)
Metasys Integrator—Metasys Integrator GE Power Application 7
Daisy-chained
Devices
•
RS-485 cable (for connecting the Power Leader Modbus Concentrator
to the converter)
•
Metasys Integrator unit
•
N2 Bus (for connecting Metasys Integrator unit to the Metasys or
Companion Network)
•
portable PC for downloading vendor communication tables
(.VCT files) and network setup information, and for running
diagnostics
•
cable for connecting portable PC to Metasys Integrator unit
•
the correct vendor communication table (.VCT file) to download into
Metasys Integrator unit (supplied on diskette)
To integrate daisy-chained devices, you need the following:
•
properly installed daisy-chained device
- Multilin Power Quality Meter
- GE MDP (w/ Modbus Communication Option)
- EPM3720, EPM3710, EPM5300P, EPM7300, or EPM9650Q
Power Meter (set up for Modbus Communication)
- Power Leader EPM (w/ Modbus Communication Option)
•
Multilin RS-232 to RS-485 converter, Revision D
•
RS-232 cable for connecting the converter to Metasys Integrator unit
•
RS-485 2-wire, shielded cable (for connecting the converter to
daisy-chained devices)
•
Metasys Integrator unit
•
N2 Bus (for connecting Metasys Integrator unit to the Metasys or
Companion Network)
•
portable PC for downloading vendor communication tables
(.VCT files) and network setup information into Metasys Integrator
unit, and for running diagnostics
•
cable for connecting portable PC to Metasys Integrator unit
•
the correct vendor communication table (.VCT file) to download into
Metasys Integrator unit (supplied on Metasys Integrator unit diskette)
This document describes the RS-232 cable and the vendor communication
tables. GE documentation describes their equipment. The remaining
components are described in the Metasys Integrator unit technical
bulletins.
8 Metasys Integrator—Metasys Integrator GE Power Application
Metasys Release
Requirements
Metasys
Companion
Release
Requirements
Vendor
Component
Requirements
To integrate the Epic MicroVersaTrip system, GE Power Leader Network,
Multilin PQM, GE MDP, or EPM3720/3710/5300P/7300/9650Q Power
Meter into the Metasys Network, you need:
•
Metasys Operator Workstation (OWS) software Release 9.0 or later
•
Metasys Integrator unit firmware Release 9.0 or later
•
Metasys Integrator unit software Release 9.3 or later
To integrate the Epic MicroVersaTrip system, GE Power Leader Network,
Multilin PQM, GE MDP, or EPM3720/3710/5300P/7300/9650Q Power
Meter into the Metasys Companion Network, you need:
•
Metasys Companion Release 6.0 or later
•
Metasys Integrator unit firmware Release 9.0 or later
•
Metasys Integrator unit software Release 9.3 or later
Integration between Metasys Integrator unit and GE has been tested with
the Power Leader system described in Tables 1 and 2, the
EPM3720/3710/5300P/7300/9650Q Power Meter described in Table 3,
and the Multilin converter described in Table 4 (see the Design
Considerations section). The Multilin converter is the only converter
approved for use with the Power Leader System and is available from GE
Multilin (see the Vendor Contact Information section).
Integration has also been tested with:
•
Epic MicroVersaTrip System Revision 2.3 connected to AKD-8
switch gear (Catalog No. TFPU2)
Table 1: Power Leader System Software Revision Numbers-485 PIM
Power Leader Product
Software Revision
Power Leader Power Leader Meter
2.0
Power Leader Spectra MicroVersaTrip PM
5.16
Power Leader MicroVersaTrip PM (4 Button)
1.02
Power Leader Enhanced MicroVersaTrip PM (5 Button)
4.13
Power Leader Electronic Power Meter
Power Leader 485 Interface Module (Catalog No. PLPIM485G01)
3.06/2.19
2.00
Metasys Integrator—Metasys Integrator GE Power Application 9
Table 2: Power Leader System Software Revision Numbers—
Power Leader Modbus Concentrator
GE Product
Software Revision
Power Leader Meter
2.0
Power Leader Spectra MVT
5.16
Power Leader Enhanced MVT PM ‘C’
4.13
Power Leader Enhanced MVT PM ‘D’
4.13
Power Leader EPM (w/ Commnet Communication Option)
1.06
Power Leader Modbus Concentrator (Main Firmware)
Power Leader Modbus Concentrator (Segment Firmware)
2.2
2.11/2.12
Table 3: GE Daisy-chained Devices Software Revision Numbers
GE Product
GE Multilin PQM
GE MDP (w/ Modbus Communication Option)
Software Revision
3.10
2.0/3.3/3.4
EPM3710 Power Meter (Catalog No. PLPML10CG04-08)
3.0.1.1-B/4.0.0.0-B
EPM3720 Power Meter (Catalog No. PLPML20CG01-05)
V05B1502
EPM5300P Power Meter
EPM7300 Power Meter
EPM9560Q Power Meter
Power Leader EPM (w/ Modbus Communication Option)
3.6
V277
COM55/DSP18
2.0/3.3
Changes to this equipment or integration of GE products not discussed in
this document requires additional software development and testing. For
information on integrating other products, refer to the Custom Integration
section of this technical bulletin.
Vendor Contact
Information
GE Electrical Distribution Control
41 Woodford Ave.
Plainville, CT 06062
Customer Service
Phone: (888) 437-3765 (888-GE-RESOLV)
GE Multilin
215 Anderson Avenue
Markham, Ontario Canada L6E 1B3
Phone: (905) 294-6222
www.geindustrial.com
10 Metasys Integrator—Metasys Integrator GE Power Application
Design
Considerations
When integrating GE equipment, consider the following:
•
Make sure GE equipment is set up and running properly before
integrating with Metasys or Companion. (The GE representative is
responsible for operation of GE equipment.)
•
RS-232 cable distance between Metasys Integrator unit and the GE
equipment can be a maximum of 50 feet.
•
For the Epic MicroVersaTrip, make sure the equipment’s baud rate is
set to 9600. (The GE representative is responsible for setting the baud
rate.)
•
For the Power Leader System, make sure the 485 PIM’s baud rate is
set at 4800. (The GE representative is responsible for setting the baud
rate.)
•
For the Power Leader system, the Multilin converter DIP switches
need to be set for data controller, direct, and 4800 or 19200 baud, as
shown in Table 4.
•
The GE Concentrator and all GE Modbus daisy-chained devices must
be configured for 19200 baud.
•
The EPM3720/3710/5300P/7300/9650Q Power Meter must be set to
the Modbus protocol to communicate with the Metasys Integrator
unit.
•
Up to 32 daisy-chained devices per RS-485 network.
•
The MDP requires an Internal RS-485 communications card.
•
If you need to monitor energy usage in gigawatt hours, set the
EPM3720/3710 PM Modbus register size to 32 bits; otherwise, set it
to 16 bits. Configure the Metasys Integrator unit using the
appropriate 16 or 32-bit application.
•
For the EPM3720/3710 Power Meter, invalid objects must be set to
YES.
•
The password must be set to zero (0) for the EPM3720/3710 Power
Meter.
Metasys Integrator—Metasys Integrator GE Power Application 11
Table 4: Settings for DIP Switches in the Multilin Converter
DIP Switches
Switch 1
Set to Data Controlled*
Switch 2
Set to Direct*
Switch 3—485 PIM
Set to 4800
Switch 3—Power Leader Modbus
Concentrator
Set to 19200
* Factory Default
12 Metasys Integrator—Metasys Integrator GE Power Application
1
2
3
4
5
6
on
off
on
off
n/a
n/a
on
off
on
off
n/a
n/a
off
off
off
on
off
off
off
off
off
off
off
on
Cable Connections
Cable Pinouts
GE FPU
Use the following cable pinouts for the RS-232 connection between
Metasys Integrator unit and the GE FPU:
Vendor Port A or B
on Metasys Integrator
RS-232 Port
on GE FPU
DB-9 Female
Signal
DB-25 Female
Pin
Pin
Signal
2
3
7
TD
RD
GND
RS-232
RD
TD
GND
2
3
5
(50 ft. maximum)
GE2
Figure 4: Cable Pinouts—FPU
Multilin Converter
(RS-232 to RS-485)
Use the following cable pinouts for the RS-232 connection between
Metasys Integrator unit and the Multilin Converter:
Vendor Port A or B
on Metasys Integrator
RS-232 Connector on
Multilin Converter
DB-9 Female
Signal
DB-9 Male
Pin
Pin
Signal
2
3
7
5
RD
TD
RTS
GND
RS-232
RD
TD
RTS
GND
2
3
7
5
(50 ft. maximum)
gemulti
Figure 5: Metasys Integrator Unit to Multilin Converter Cable
Pinouts
Metasys Integrator—Metasys Integrator GE Power Application 13
Use the following cable pinouts for the RS-485 connection between the
Multilin Converter and the Power Leader or daisy-chained devices. The
shield of the Modbus cable should be connected at the PIM end only.
Multilin
Converter
+
-
RS-485
Power Leader or
Daisy-chained Device
A+
BSHL
GND
gepldc
Figure 6: Multilin Converter to Power Leader or Daisy-chained
Devices Cable Pinouts
Power Quality
Meter
Use the following cable pinouts for the RS-485 connection between the
Multilin Converter and the Power Quality Meter:
Multilin
Converter
+
-
PQM COM 1
(Terminal No.)
RS-485
+ (48)
(47)
COM (46)
GND
multipqm
Figure 7: Multilin Converter to PQM Cable Pinouts
GE MDP
Use the following cable pinouts for the RS-485 connection between the
Multilin Converter and the GE MDP:
Multilin
Converter
RS-485
+
GND
MDP
+
N/C
mdp2
Figure 8: Multilin Converter to GE MDP Cable Pinouts
14 Metasys Integrator—Metasys Integrator GE Power Application
Metasys Integrator Unit Setup
To set up Metasys Integrator unit, use a portable PC connected to the
Metasys Integrator Terminal Port. Metasys Integrator unit setup involves:
•
downloading the correct vendor communication table (.VCT file)
•
setting up the ports
•
setting up the network addressing
Tables 5-8 provide information specific to the GE application. For
detailed procedures, see the Metasys Integrator unit technical bulletins.
Table 5: Metasys Integrator Unit Setup—Epic MicroVersaTrip
System
Vendor Communication Table (.VCT File)
Epic MicroVersaTrip
GE_EPIC.VCT
Port Setup--Epic MicroVersaTrip System
Baud Rate
9600
Word Length
8
Stop Bits
1
Parity
None
Interface
RS-232
Network Setup--Epic MicroVersaTrip System
Vendor Address
2 to 5 character alphanumeric breaker
address (for example, MAIN)
Timeout Value
4000 ms
Poll Delay
1000 ms
Retry
10
Performance Guide
Approximate Scan Time
(For a single N2 address)
Epic MicroVersaTrip
40 seconds
Metasys Integrator—Metasys Integrator GE Power Application 15
Table 6: Metasys Integrator Unit Setup—485 PIM
Vendor Communication Table (.VCT File)
Power Leader Meter
GE_PLM.VCT
Power Leader MicroVersaTrip
GE_MVT.VCT
•
Spectra MicroVersaTrip
•
MicroVersa Trip
•
Enhanced MicroVersaTrip
Power Leader Electronic Power Meter
GE_EPM.VCT
Port Setup--Power Leader System
Baud Rate
4800
Word Length
8
Stop Bits
1
Parity
None
Interface
RS-485
Network Setup--Power Leader System
Vendor Address
Device address
(must be in range 256-502)
Timeout Value
4000 ms
Poll Delay
100 ms
Retry
5
Performance Guide
Approximate Scan Time
(For a single N2 address)
Power Leader Meter
Power Leader MicroVersaTrip
•
Spectra MicroVersaTrip
•
MicroVersaTrip
•
Enhanced MicroVersaTrip
Power Leader Electronic Power
Meter
16 Metasys Integrator—Metasys Integrator GE Power Application
14 seconds
8 seconds
14 seconds
Table 7: Metasys Integrator Unit Setup—Power Leader Modbus
Concentrator
Vendor Communication Table (.VCT File)
Power Leader Meter
GEC_PLM.VCT
Power Leader Spectra MVT
GEC_MVT.VCT
Power Leader Enhanced MVT
GEC_EMVT.VCT
Power Leader Electronic Power
Meter
GEC_EPM.VCT
Port Setup—Power Leader System
Baud Rate
19200
Word Length
8
Stop Bits
1
Parity
None
Interface
RS-485
Network Setup—Power Leader System
Vendor Address
Modbus address = (Commnet address - 267)
For example, if the Commnet address = 397,
enter 130 as the vendor address.
Timeout Value
1500 ms
Poll Delay
220 ms
Retry
3
Performance Guide
Approximate Scan Time
(For a single N2 address)
Power Leader Meter
Power Leader Spectra MVT
Power Leader Enhanced MVT
Power Leader Electronic Power
Meter
1 second
1 second
1 second
1 second
Metasys Integrator—Metasys Integrator GE Power Application 17
Table 8: Metasys Integrator Unit Setup—Daisy-chained Devices
Vendor Communication Table (.VCT File)
Multilin Power Quality Meter
GE MDP
EPM3720 Power Meter
EPM3710 Power Meter
EPM5300P Power Meter
EPM7300 Power Meter
EPM9650Q Power Meter
Power Leader Electronic Power Meter
(w/ Modbus Communication Option)
GE_PQM.VCT
GE_MDP.VCT
P3720M16.VCT
P3720M32.VCT
P3710M16.VCT
P3710M32.VCT
GE_5300.VCT
GE_7300.VCT
GE_9650.VCT
GEC_EPM.VCT
Port Setup—Multilin Power Quality Meter, GE MDP,
EPM3720/3710/5300P/7300/9650Q and Power Leader EPM (w/Modbus
Communication Option)
Baud Rate
19200
Word Length
Stop Bits
8
1
Parity
Interface
None
RS-485
Network Setup—Multilin Power Quality Meter
Vendor Address
Modbus Communication Address (1-255)
Timeout Value
Poll Delay
Retry
800 ms
55 ms
3
Network Setup—GE MDP
Vendor Address
1-32
Timeout Value
Poll Delay
Retry
2200 ms
220 ms
3
Network Setup-- EPM3720/3710/5300P/7300/9650Q Power Meter
Vendor Address
1-247
Timeout Value
Poll Delay
Retry
2000 ms
110 ms
3
Network Setup—Power Leader EPM (w/ Modbus Communication Option)
Vendor Address
EPM direct address = 0 through 254
Timeout Value
Poll Delay
Retry
3000 ms
220 ms
3
Performance Guide
Approximate Scan Time
(For a single N2 address)
Multilin Power Quality Meter
GE MDP
EPM3720/3710/7300 Power Meter
EPM5300P/9650Q Power Meter
Power Leader Electronic Power Meter
18 Metasys Integrator—Metasys Integrator GE Power Application
2 seconds
3 seconds
1 second
2 seconds
1 second
Point Mapping Tables
Epic
MicroVersaTrip
System
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
The following tables (one for each application) show the points available
for mapping in the GE devices.
Table 9: Epic MicroVersaTrip System
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kVAR
kVA
kVA
kVA
#
#
#
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Voltage, Phase A to Neutral
RMS Voltage, Phase B to Neutral
RMS Voltage, Phase C to Neutral
RMS Voltage, Phase A to B
RMS Voltage, Phase B to C
RMS Voltage, Phase C to A
Real Power
Reactive Power
Total Power - a
Total Power - b
Total Power - c
Power Factor - a
Power Factor - b
Power Factor - c
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
1
2
Breaker State
Ground Fault Trip
Long Time Trip
Short Time Trip
Long Time Pickup Trip
Instantaneous Trip
Under Voltage
Voltage Unbalance
Current Unbalance
Power Reversal
0=open, 1=close
0=ok, 1=trip
0=ok, 1=trip
0=ok, 1=trip
0=ok, 1=trip
0=ok, 1=trip
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 19
NPT1
(Cont.)
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
kWh
kW
kW
Hz
kW
%
%
%
kW
Energy Reading
Demand Reading
Peak Demand Reading
Frequency
Peak Capacity
Under Voltage Setpoint
Current Unbalance Setpoint
Voltage Unbalance Setpoint
Power Reversal Setpoint
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
3
4
5
6
7
8
9
10
1
2
ADC Protection Self Test Fail
RAM Protection Self Test Fail
ROM Protection Self Test Fail
RVM Protection Self Test Fail
ADC Metering Self Test Fail
RAM Metering Self Test Fail
ROM Metering Self Test Fail
RVM Metering Self Test Fail
INT Metering Self Test Fail
IPC Failure
Network Point Type
Network Point Address
20 Metasys Integrator—Metasys Integrator GE Power Application
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
0=ok,
1=fail
1=fail
1=fail
1=fail
1=fail
1=fail
1=fail
1=fail
1=fail
1=fail
GE Power
Leader Meter—
485 PIM
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the Apparent
Power, Phase B
point is AI17.
Table 10: GE Power Leader Meter—485 PIM
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kVAR
kW
kVAR
kW
kVAR
kVA
kVA
kVA
kVA
#
#
#
#
kWh
MWh
kVARh
Mvarh
Amps
Amps
Amps
Amps
Amps
Amps
kW
kW
Hz
%
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Voltage, Phase A to Neutral
RMS Voltage, Phase B to Neutral
RMS Voltage, Phase C to Neutral
RMS Voltage, Phase A to B
RMS Voltage, Phase B to C
RMS Voltage, Phase C to A
Real Power, Phase A
Reactive Power, Phase A
Real Power, Phase B
Reactive Power, Phase B
Real Power, Phase C
Reactive Factor, Phase C
Apparent Power, Phase A
Apparent Power, Phase B
Apparent Power, Phase C
Total Apparent Power
1
2
*
Power Factor, Phase A*
Power Factor, Phase B*
A negative value
Power Factor, Phase C*
indicates lag.
Total Power Factor*
Energy (KWH)
Energy (MWh)
Reactive Energy (kVARh)
Reactive Energy (Mvarh)
Current Demand, Phase A
Current Demand, Phase B
Current Demand, Phase C
Peak RMS Current, Phase A
Peak RMS Current, Phase B
Peak RMS Current, Phase C
Watt Demand
Peak Watt Demand
Frequency
Total Current Harmonic Distortion
Potential Transformer Ratio (secondary is 120V)
Current Transformer Ratio (secondary is 5A)
Network Point Type
Network Point Address
If the system is in a delta connection, these will be only one power factor value;
that value will be shown in point AI23 (Total Power Factor).
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 21
NPT1
(Cont.)
NPA2
BO
1
2
3
BO
BO
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
BD
BD
1
2
3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
1
2
Unit
Description
Clear Energy and VAR Hour3
Clear Peak Watt Demand3
Clear Peak Current (A, B, C)3
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
kW
Sec
kW
Sec
%
Sec
Min
Code
Code
0=n/a, 1=clear
0=n/a, 1=clear
0=n/a, 1=clear
Current Unbalance Trip Setpoint
Current Unbalance Trip Time Delay
Current Unbalance Alarm Setpoint
Current Unbalance Alarm Time Delay
Voltage Unbalance Trip Setpoint
Voltage Unbalance Trip Time Delay
Voltage Unbalance Alarm Setpoint
Voltage Unbalance Alarm Time Delay
Over Voltage Trip Setpoint
Over Voltage Trip Time Delay
Over Voltage Alarm Setpoint
Over Voltage Alarm Time Delay
Under Voltage Trip Setpoint
Under Voltage Trip Time Delay
Under Voltage Alarm Setpoint
Under Voltage Alarm Time Delay
Power Reversal Trip Setpoint
Power Reversal Trip Time Delay
Power Reversal Alarm Setpoint
Power Reversal Alarm Time Delay
Over Current Relay Alarm Setpoint
Over Current Relay Alarm Time Delay
Demand Time Period
Event Type
Event Identifier
Device Open/Close
Hardware Failure
0=ok,
0=ok,
1=close
1=fail
Network Point Type
Network Point Address
Do not map these points to Companion BO points. If you map these points to
Metasys system BO objects, disbale Auto Restore in the BO object’s Definition or
Focus window.
22 Metasys Integrator—Metasys Integrator GE Power Application
Power Leader
MicroVersaTrip
—485 PIM
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the Frequency
point is AI17.
Table 11: GE Power Leader MicroVersaTrip—485 PIM
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Amps
Amps
Amps
Amps
Volt
Volt
Volt
kW
kVAR
kW
kVAR
kW
kVAR
kW
kWh
MWh
Hz
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Current, Phase N
RMS Voltage, Phase A to Neutral
RMS Voltage, Phase B to Neutral
RMS Voltage, Phase C to Neutral
Filtered Real Power, Phase A
Filtered Reactive Power, Phase A
Filtered Real Power, Phase B
Filtered Reactive Power, Phase B
Filtered Real Power, Phase C
Filtered Reactive Power, Phase C
Three Phase Power (Demand)
Energy (kWh)
Energy (MWh)
Frequency
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
2
Current Unbalance Trip
Under Voltage Trip
Voltage Unbalance Trip
Power Reversal Trip
Instantaneous Trip
Short Time Trip
Long Time Trip
Ground Fault Trip
Breaker Position Closed
Breaker Short Time Pickup
Breaker Long Time Pickup
Breaker Ground Fault Pickup
Over Voltage Trip Condition
Breaker Opened Remotely
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=open,
1=closed
0=off,
1=on
0=off,
1=on
0=off,
1=on
0=normal, 1=trip
0=not remote,
1=remote
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 23
NPT1
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
%
Sec
%
Sec
%
Sec
%
Sec
kW
Sec
%
Sec
%
Code
15
16
%
Code
17
18
%
Code
Current Unbalance Setpoint
Current Unbalance Time Delay
Voltage Unbalance Setpoint
Voltage Unbalance Time Delay
Over Voltage Setpoint
Over Voltage Time Delay
Under Voltage Setpoint
Under Voltage Time Delay
Power Reversal Setpoint
Power Reversal Time Delay
Long Time Pickup
Long Time Delay
Short Time Pickup
Short Time Delay 0=off,
3=in 3,
18=out 2,
Ground Fault Pickup
Ground Fault Delay 0=off,
3=in 3,
18=out 2,
Instantaneous Pickup
Fault Phase ID
0=N,
ADF
ADF
ADF
ADF
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1=in 1,
2=in 2
4=in 4,
17=out 1
19=out 3, 20=out 4
1=in 1,
2=in 2
4=in 4,
17=out 1
19=out 3, 20=out 4
1=A, 2=B,3=C
ADC Failure in Ground Unit
RAM Failure in Ground Unit
ROM Failure in Ground Unit
NVM Failure in Ground Unit
ADC Failure in Protection Board
RAM Failure in Protection Board
ROM Failure in Protection Board
NVM Failure in Protection Board
ADC Failure on Metering Board
RAM Failure on Metering Board
ROM Failure on Metering Board
NVM Failure on Metering Board
INT Failure on Metering Board
IPC Failure on Metering Board
Medium Voltage Grnd Flt Unit
Network Point Type
Network Point Address
24 Metasys Integrator—Metasys Integrator GE Power Application
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=disconnected,
1=connected
Power Leader
Electronic
Power Meter—
485 PIM, Power
Leader Modbus
Concentrator,
Daisy-chained
Devices
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the Apparent
Power, Phase B
point is AI20.
Table 12: GE Power Leader Electronic Power Meter—485 PIM,
Power Leader Modbus Concentrator, and Daisy-chained Devices
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Amps
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
kVA
kVA
kVA
kVA
#
#
#
#
kWh
MWh
kVARh
kVARh
kVAH
Amps
Amps
Amps
kW
kVAR
kVAR
kVA
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Current, Phase N
Voltage Line, Phase A to Neutral
Voltage Line, Phase B to Neutral
Voltage Line, Phase C to Neutral
Voltage Line, Phase A to B
Voltage Line, Phase B to C
Voltage Line, Phase C to A
Real Power, Phase A
Real Power, Phase B
Real Power, Phase C
Real Power Total of All Phases
Reactive Power, Phase A
Reactive Power, Phase B
Reactive Power, Phase C
Reactive Power Total of All Phases (pos=lag, neg=lead)
Apparent Power, Phase A
Apparent Power, Phase B
Apparent Power, Phase C
Apparent Power Total of All Phases
Power Factor, Phase A
Power Factor, Phase B
Power Factor, Phase C
Power Factor Total of All Phases
Energy Total of All Phases (kWh)
Energy Total of All Phases (MWh)
Reactive Energy Total of All Phases (lag)
Reactive Energy Total of All Phases (lead)
Apparent Energy Total of All Phases
Current Demand, Phase A
Current Demand, Phase B
Current Demand, Phase C
Real Power Demand Total of All Phases
Reactive Power Demand Total of All Phases (lag)
Reactive Power Demand Total of All Phases (lead)
Apparent Power Demand Total of All Phases
1
2
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 25
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
39
40
41
42
43
44
45
46
47
48
Amps
Amps
Amps
kW
kVAR
kVAR
kVA
Hz
Current Maximum, Phase A
Current Maximum, Phase B
Current Maximum, Phase C
Real Power Maximum Total of All Phases
Reactive Power Maximum Total of All Phases (lag)
Reactive Power Maximum Total of All Phases (lead
Apparent Power Maximum Total of All Phases
Frequency Phase A
Potential Transformer Ratio
Current Transformer Ratio
ADF
ADF
ADF
1
2
3
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
3
4
5
6
7
8
9
10
11
1
2
Code
Number of Resets
Number of Power Failures
Voltage Phase Loss Errors
1=Phase A to N, Voltage Lost
2=Phase B to N, Voltage Lost
3=Phase A to N and B to N, Voltage Lost
4=Phase C to N, Voltage Lost
5=Phase A to N and C to N, Voltage Lost
6=Phase B to N and C to N, Voltage Lost
7=Phase A to N, B to N, and C to N, Voltage Lost
Meter Error: All Energy Lost
Meter Error: Comm Error
Meter Error: Energy Data Lost (up to 12 hrs)
Power Factor Lead/Lag Qualifier, Phase A 0=lagging
Power Factor Lead/Lag Qualifier, Phase B 1=leading
Power Factor Lead/Lag Qualifier, Phase C
Power Factor Lead/Lag Qualifier, All Phases
Demand Reset Occurred
0=n/a, 1=occurred
Energy Reset Occurred
0=n/a, 1=occurred
Meter Initialize Occurred
0=n/a, 1=occurred
Errors Clear Occurred
0=n/a, 1=occurred
Network Point Type
Network Point Address
26 Metasys Integrator—Metasys Integrator GE Power Application
GE Power
Leader Meter—
Power Leader
Modbus
Concentrator
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
Table 13: GE Power Leader Meter Points—Power Leader Modbus
Concentrator
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
BO
BO
BO
1
2
3
1
2
3
Unit
Description
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
kVA
kVA
kVA
kVA
#
kW
kW
kWh
MWh
kVARh
Hz
%
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
Current Maximum Phase A
Current Maximum Phase B
Current Maximum Phase C
Current Phase A Demand
Current Phase B Demand
Current Phase C Demand
RMS Voltage Line-Neutral, Phase A-N
RMS Voltage Line-Neutral, Phase B-N
RMS Voltage Line-Neutral, Phase C-N
RMS Voltage Line-Line, Phase A-B
RMS Voltage Line-Line, Phase B-C
RMS Voltage Line-Line, Phase C-A
KW Phase A
kW Phase B
kW Phase C
kW Total Power
kVAR Phase A
kVAR Phase B
kVAR Phase C
kVAR Total Reactive Power
kVA Phase A
kVA Phase B
kVA Phase C
kVA Total Apparent Power
Total Power Factor
Watt Demand
Peak Power Demand
kWh Energy
MWh Energy
Reactive Energy
Frequency
Harmonic Distortion
Clear Energy/VAR Hour3
Clear Peak Watt Demand3
Clear Peak Current3
0=n/a
0=n/a
0=n/a
1=clear
1=clear
1=clear
Network Point Type
Network Point Address
Do not map these points to Companion BO points. If you map these points to Metasys
system BO objects, disbale Auto Restore in the BO object’s Definition or Focus window.
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 27
NPT1
(Cont.)
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
%
Sec
kW
Sec
kW
Sec
%
Sec
Min
Current Unbalance Trip Setpoint
Current Unbalance Trip Time Delay
Current Unbalance Alarm Setpoint
Current Unbalance Alarm Time Delay
Voltage Unbalance Trip Setpoint
Voltage Unbalance Trip Time Delay
Voltage Unbalance Alarm Setpoint
Voltage Unbalance Alarm Time Delay
Over Voltage Trip Setpoint
Over Voltage Trip Time Delay
Over Voltage Alarm Setpoint
Over Voltage Alarm Time Delay
Under Voltage Trip Setpoint
Under Voltage Trip Time Delay
Under Voltage Alarm Setpoint
Under Voltage Alarm Time Delay
Power Reversal Trip Setpoint
Power Reversal Trip Time Delay
Power Reversal Alarm Setpoint
Power Reversal Alarm Time Delay
Over Current Relay Alarm
Over Current Relay Alarm Time Delay
Demand Time Period
1
2
Network Point Type
Network Point Address
28 Metasys Integrator—Metasys Integrator GE Power Application
GE Power
Leader Spectra
MVT—
Power Leader
Modbus
Concentrator
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
Table 14: GE Power Leader Spectra MVT—Power Leader Modbus
Concentrator
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
kVA
kVA
kVA
kVA
#
Hz
kWh
MWh
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Voltage Line-Neutral, Phase A-N
RMS Voltage Line-Neutral, Phase B-N
RMS Voltage Line-Neutral,
RMS Voltage Line-Line, Phase A-B
RMS Voltage Line-Line, Phase B-C
RMS Voltage Line-Line, Phase C-A
Real Power, Phase A
Real Power, Phase B
Real Power, Phase C
Total Real Power
Reactive Power, Phase A
Reactive Power, Phase B
Reactive Power, Phase C
Total Reactive Power
Apparent Power, Phase A
Apparent Power, Phase B
Apparent Power, Phase C
Total Apparent Power
Power Factor
Frequency
kWh Energy
MWh Energy
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
2
Current Unbalance Trip
Under Voltage Trip
Voltage Unbalance Trip
Power Reversal Trip
Instantaneous Trip
Short Time Trip
Long Time Trip
Ground Fault Trip
Breaker Position Closed
Breaker Short Time Pickup
Breaker Long Time Pickup
Breaker Ground Fault Pickup
Over Voltage Trip Condition
Breaker Opened Remotely
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=normal, 1=trip
0=open, 1=closed
0=off,
1=on
0=off,
1=on
0=off,
1=on
0=normal, 1=trip
0=no,
1=yes
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 29
NPT1
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
%
Sec
%
Sec
%
Sec
%
Sec
kW
Sec
%
Sec
%
Code
ADF
ADF
15
16
%
Code
ADF
ADF
17
18
%
Code
Current Unbalance Setpoint
Current Unbalance Time Delay
Voltage Unbalance Setpoint
Voltage Unbalance Time Delay
Over Voltage Setpoint
Over Voltage Time Delay
Under Voltage Setpoint
Under Voltage Time Delay
Power Reversal Setpoint
Power Reversal Time Delay
Long Time Pickup
Long Time Delay
Short Time Pickup
Short Time Delay 0=off,
3=in 3,
18=out 2,
Ground Fault Pickup
Ground Fault Delay 0=off,
3=in 3,
18=out 2,
Instantaneous Pickup
Fault Phase ID
0=N,
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
1=in 1,
4=in 4,
19=out 3,
2=in 2
17=out 1
20=out 4
1=in 1,
4=in 4,
19=out 3,
2=in 2
17=out 1
20=out 4
1=A,
2=B,
ADC Failure in Ground Unit
RAM Failure in Ground Unit
ROM Failure in Ground Unit
NVM Failure in Ground Unit
ADC Failure in Protection Board
RAM Failure in Protection Board
ROM Failure in Protection Board
NVM Failure in Protection Board
ADC Failure on Metering Board
RAM Failure on Metering Board
ROM Failure on Metering Board
NVM Failure on Metering Board
INT Failure on Metering Board
IPC Failure on Metering Board
Medium Voltage Grnd Flt Unit
Network Point Type
Network Point Address
30 Metasys Integrator—Metasys Integrator GE Power Application
3=C
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=normal, 1=fail
0=disconnected,
1=connected
GE Power
Leader
Enhanced
MVT—
Power Leader
Modbus
Concentrator
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
Table 15: GE Power Leader Enhanced MVT (-C) and (-D) PM
Points—Power Leader Modbus Concentrator
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Amps
Amps
Amps
Amps
Volt
Volt
Volt
Volt
Volt
Volt
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
kVA
kVA
kVA
kVA
kWh
MWh
kW
kW
#
Hz
RMS Current, Phase A
RMS Current, Phase B
RMS Current, Phase C
RMS Current, Phase N
RMS Voltage Line-Neutral, Phase A-N
RMS Voltage Line-Neutral, Phase B-N
RMS Voltage Line-Neutral, Phase C-N
RMS Voltage Line-Line, Phase A-B
RMS Voltage Line-Line, Phase B-C
RMS Voltage Line-Line, Phase C-A
Real Power, Phase A
Real Power, Phase B
Real Power, Phase C
Total Real Power
Reactive Power, Phase A
Reactive Power, Phase B
Reactive Power, Phase C
Total Reactive Power
Apparent Power, Phase A
Apparent Power, Phase B
Apparent Power, Phase C
Total Apparent Power
kWh Energy
MWh Energy
Power Demand
Peak Power Demand
Power Factor
Frequency
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
1
2
Current Unbalance Trip
Under Voltage Trip
Voltage Unbalance Trip
Power Reversal Trip
Instantaneous Trip Condition
Short Time Trip Condition
Long Time Trip Condition
Ground Fault Trip Condition
Breaker Position Closed
Breaker Short Time Pickup
0=normal,
0=normal,
0=normal,
0=normal,
0=normal,
0=normal,
0=normal,
0=normal,
0=open,
0=off,
1=trip
1=trip
1=trip
1=trip
1=trip
1=trip
1=trip
1=trip
1=closed
1=on
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 31
NPT1
NPA2
BI
BI
BI
BI
11
12
13
14
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
%
Sec
%
Sec
%
Sec
%
Sec
kW
Sec
%
Sec
%
Code
ADF
ADF
15
16
%
Code
ADF
17
%
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
Unit
Description
Breaker Long Time Pickup
Breaker Ground Fault Pickup
Over Voltage Trip Condition
Breaker Opened Remotely
Current Unbalance Setpoint
Current Unbalance Time Delay
Voltage Unbalance Setpoint
Voltage Unbalance Time Delay
Over Voltage Setpoint
Over Voltage Time Delay
Under Voltage Setpoint
Under Voltage Time Delay
Power Reversal Setpoint
Power Reversal Time Delay
Long Time Pickup
Long Time Delay
Short Time Pickup
Short Time Delay 0=off,
3=in 3,
18=out 2,
Ground Fault Pickup
Ground Fault Delay 0=off,
3=in 3,
18=out 2,
Instantaneous Pickup
0=off,
1=on
0=off,
1=on
0=normal, 1=trip
0=not remote,
1=remote
1=in 1,
4=in 4,
19=out 3,
2=in 2
17=out 1
20=out 4
1=in 1,
4=in 4,
19=out 3,
2=in 2
17=out 1
20=out 4
ADC Failure in Ground Unit
RAM Failure in Ground Unit
ROM Failure in Ground Unit
NVM Failure in Ground Unit
ADC Failure in Protection Board
RAM Failure in Protection Board
ROM Failure in Protection Board
NVM Failure in Protection Board
ADC Failure on Metering Board
RAM Failure on Metering Board
ROM Failure on Metering Board
NVM Failure on Metering Board
INT Failure on Metering Board
IPC Failure on Metering Board
Medium Voltage Grnd Flt Unit
Network Point Type
Network Point Address
32 Metasys Integrator—Metasys Integrator GE Power Application
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=ok, 1=fail
0=disconnected,
1=connected
Multilin Power
Quality Meter—
Daisy-chained
Devices
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
Table 16: Multilin Power Quality Meter—Daisy-chained Devices
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
BI
1
AO
1
BO
BO
BO
BO
BO
BO
BO
1
2
3
4
5
6
7
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
Unit
Description
Amps
Amps
Amps
Amps
Amps
%
Volt
Hz
kW
kVAR
kVA
#
kWh
kWh
kVARh
kVARh
kVAh
Amps
Amps
Amps
Amps
kW
kVAR
kVA
Phase A Current
Phase B Current
Phase C Current
Average Current
Neutral Current
Current Unbalance
Average Phase Voltage
Frequency
3-Phase Real Power
3-Phase Reactive Power
3-Phase Apparent Power
3-Phase Power Factor*
3-Phase Positive Real Energy Used
3-Phase Negative Real Energy Used
3-Phase Positive Reactive Energy Used
3-Phase Negative Reactive Energy Used
3-Phase Apparent Energy Used
Phase A Current Demand
Phase B Current Demand
Phase C Current Demand
Neutral Current Demand
3-Phase Real Power Demand
3-Phase Reactive Power Demand
3-Phase Apparent Power Demand
Cents
Energy Cost Per kWh
Alarm Present
Reset Latched Alarms
Alarm Relay Operation
Alarm Relay Activation
Clear Energy Values
Clear Max Demand Values
Clear Min/Max Power/Frequency Values*
Clear Max Current Values
Volt
Volt
Volt
Volt
Volt
0=normal, 1=alarm
(0.01-500.0)
0=n/a, 1=reset
0=non-fs, 1=failsf
0=unlatc, 1=latch
0=n/a, 1=clear
0=n/a, 1=clear
0=n/a, 1=clear
0=n/a, 1=clear
Voltage Phase A to Neutral
Voltage Phase B to Neutral
Voltage Phase C to Neutral
Voltage Phase A to B
Voltage Phase B to C
1 Network Point Type
2 Network Point Address
*
A negative power factor indicates lead; a positive power factor indicates lag.
** PQM firmware revisions later than 65C do not clear Min/Max Frequency Values using this
point.
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 33
NPA2
NPT1
(Cont.)
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Volt
Volt
%
kW
kVAR
kVA
#
kW
kVAR
kVA
#
kW
kVAR
kVA
#
kW
kVAR
kVA
kWh
Cents
Cents
Hz
Hz
Amps
Amps
Amps
Amps
%
%
%
%
%
%
%
%
%
%
#
Voltage, Phase C to A
Average Line Voltage
Voltage Unbalance
Phase A Real Power
Phase A Reactive Power
Phase A Apparent Power
Phase A Power Factor*
Phase B Real Power
Phase B Reactive Power
Phase B Apparent Power
Phase B Power Factor*
Phase C Real Power
Phase C Reactive Power
Phase C Apparent Power
Phase C Power Factor*
3-Phase Real Power—Maximum
3-Phase Reactive Power—Maximum
3-Phase Apparent Power—Maximum
3-Phase Energy Used in Last 24 Hours
3-Phase Energy Cost Since Reset
3-Phase Energy Cost Per Day
Frequency Minimum
Frequency Maximum
Phase A Current—Maximum
Phase B Current—Maximum
Phase C Current—Maximum
Neutral Current—Maximum
Phase A Current THD
Phase B Current THD
Phase C Current THD
Neutral Current THD
Voltage Phase A to Neutral THD
Voltage Phase B to Neutral THD
Voltage Phase C to Neutral THD
Voltage Phase A to B THD
Voltage Phase B to C THD
Voltage Phase C to A THD
Main Software Version Code
ADI
ADI
1
2
#
#
Multilin Product Device Code
Hardware Version Code
1
2
*
(1=A, 2=B, … , 26=Z)
Network Point Type
Network Point Address
A negative power factor indicates lead; a positive power factor indicates lag.
Continued on next page . . .
34 Metasys Integrator—Metasys Integrator GE Power Application
NPA2
NPT1
(Cont.)
Unit
Description
Active Alarm Flags
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
BD
1
2
Phase Undercurrent
Phase Overcurrent
Neutral Overcurrent
Current Unbalance
Undervoltage
Overvoltage
Voltage Unbalance
Voltage Phase Reversal
Underfrequency
Overfrequency
Power Factor Lead 1
Power Factor Lead 2
Power Factor Lag 1
Power Factor Lag 2
Positive Real Power
Negative Real Power
Positive Reactive Power
Negative Reactive Power
Positive Real Power Demand
Negative Real Power Demand
Positive Reactive Power Demand
Negative Reactive Power Demand
Apparent Power Demand
Phase A Current Demand
Phase B Current Demand
Phase C Current Demand
Neutral Current Demand
Current THD
Voltage THD
Internal Fault
Switch A
Switch B
Switch C
Switch D
Serial COM1 Failure
Serial COM2 Failure
Pulse Input 1
Pulse Input 2
Pulse Input 3
Pulse Input 4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 35
NPA2
NPT1
(Cont.)
BD
BD
BD
BD
BD
BD
BD
BD
1
2
Unit
41
42
43
44
45
46
47
48
Description
Totalized Pulse Input
Analog Input Main
Analog Input Alt
Data Log 1
Data Log 2
Parameters Not Set
Clock Not Set
Time
Network Point Type
Network Point Address
36 Metasys Integrator—Metasys Integrator GE Power Application
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
0=ok, 1=alarm
GE MDP—
Daisy-chained
Devices
To obtain the
hardware reference
for mapping points to
a CS object (via the
software model),
combine the Network
Point Type (NPT)
and Network Point
Address (NPA). For
example, the
hardware reference
for the RMS Current,
Phase A point is AI1.
Table 17: GE MDP Points—Daisy-chained Devices
NPT1 NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Sec
Code
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
11
12
13
14
15
16
17
18
19
20
Sec
Code
Current Phase A
Current Phase B
Current Phase C
Current Ground
Trip Current Phase A
Trip Current Phase B
Trip Current Phase C
Trip Current Ground
Trip Time
Relay Hardware Status
00h=Relay is okay
01h=Relay not responding to read
02h=Relay not responding to write
03h=Relay reports an error in command
04h=Fatal error in Relay
Phase A Current in Multiples of Tap
Phase B Current in Multiples of Tap
Phase C Current in Multiples of Tap
Ground Current in Multiples of Tap
Phase A Trip Current in Multiples of Tap
Phase B Trip Current in Multiples of Tap
Phase C Trip Current in Multiples of Tap
Ground Trip Current in Multiples of Tap
Trip Time (converted from ASCII)
Phase Curve Selection
00h=Not used
01h=Long Time Inverse
02h=Very Inverse
03h=Extremely Inverse
04h=Inverse
Phase Definite Time
Ground Curve Selection
00h=Not used
01h=Long Time Inverse
02h=Very Inverse
03h=Extremely Inverse
04h=Inverse
Ground Definite Time
Ground Time Dial
Ground IOC Delay
Ground TOC Pickup
Ground IOC Pickup
Phase Time Dial
Phase IOC Delay
Phase TOC Pickup
Phase IOC Pickup
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
21
22
Sec
23
24
25
26
27
28
29
30
31
Sec
Sec
Amps
TOCx
Sec
Sec
Amps
TOCx
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 37
NPA2
NPT1
(Cont.)
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
Unit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Description
LED Status Ready
LED Status Ready Phase A
LED Status Ready Phase B
LED Status Ready Phase C
LED Status Ready Ground
LED Status TOC Trip
LED Status IOC Trip
LED Status Pickup
HDW Status Breaker
HDW Status Ext Input, Block Gnd
HDW Status Ext Input, Block IOC
HDW Status Settings Status
HDW Status Relay
Breaker Status
Output Selection
Ground Time Dial Sw 1
Ground Time Dial Sw 2
Ground Time Dial Sw 3
Ground Time Dial Sw 4
Ground Time Dial Sw 5
Ground IOC Delay Sw 1
Ground IOC Delay Sw 2
Ground IOC Delay Sw 3
Ground IOC Delay Sw 4
Ground IOC Delay Sw 5
Ground TOC Pickup Sw 1
Ground TOC Pickup Sw 2
Ground TOC Pickup Sw 3
Ground TOC Pickup Sw 4
Ground TOC Pickup Sw 5
Ground IOC Pickup Sw 1
Ground IOC Pickup Sw 2
Ground IOC Pickup Sw 3
Ground IOC Pickup Sw 4
Ground IOC Pickup Sw 5
Phase Time Dial Sw 1
Phase Time Dial Sw 2
Phase Time Dial Sw 3
Phase Time Dial Sw 4
Phase Time Dial Sw 5
Network Point Type
Network Point Address
Continued on next page . . .
38 Metasys Integrator—Metasys Integrator GE Power Application
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=A, 1=B
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
NPA2
NPT1
(Cont.)
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
Unit
Description
Phase IOC Delay Sw 1
Phase IOC Delay Sw 2
Phase IOC Delay Sw 3
Phase IOC Delay Sw 4
Phase IOC Delay Sw 5
Phase TOC Pickup Sw 1
Phase TOC Pickup Sw 2
Phase TOC Pickup Sw 3
Phase TOC Pickup Sw 4
Phase TOC Pickup Sw 5
Phase IOC Pickup Sw 1
Phase IOC Pickup Sw 2
Phase IOC Pickup Sw 3
Phase IOC Pickup Sw 4
Phase IOC Pickup Sw 5
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
0=off, 1=on
Network Point Type
Network Point Address
Metasys Integrator—Metasys Integrator GE Power Application 39
EPM3720
Power Meter—
Daisy-chained
Devices
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine the
Network Point Type
(NPT) and Network
Point Address (NPA).
For example, the
hardware reference
for the Average
Current is AI1.
Table 18: EPM3720 Power Meter Points—Daisy-chained Devices
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
BO
BO
1
2
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
Unit
Description
ARMS
kWRMS
kVA
kVRMS
VAux
ARMS
%
%
VRMS
VRMS
%
Hz
Average Current
Total Kilowatts
kVA Total
kVAR Total
Voltage Aux
Neutral Current (I4)
Voltage Imbalance
Current Imbalance
Average LN Voltage
Voltage LL average
Power Factor Total
Frequency at Va
Reset All Minimum/Maximum Values3
Reset All k/MW, k/Mvar, k/MVA hours3
kWh
MWh
kWh
MWh
kWh
MWh
kWh
MWh
kVARh
Mvarh
kVARh
Mvarh
kVARh
Mvarh
kVARh
Mvarh
kVAh
MVAh
kVAh
MVAh
0=n/a 1=reset
0=n/a 1=reset
kWh Import
MWh Import
kWh Export
MWh Export
kWh Total
MWh Total
kWh Net
MWh Net
kVARh Import
Mvarh Import
kVARh Export
Mvarh Export
kVARh Total
Mvarh Total
kVARh Net
Mvarh Net
kVAh Import
MVAh Import
kVAh Export
MVAh Export
Network Point Type
Network Point Address
Do not map these points to Companion BO points. If you map these points to Metasys
system BO objects, disbale Auto Restore in the BO object’s Definition or Focus window.
Continued on next page . . .
40 Metasys Integrator—Metasys Integrator GE Power Application
NPT1
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
kVAh
MVAh
kVAh
MVAh
kW
kW
kW
kW
kVAR
kVAR
kVAR
kVAR
kVAh Total
MVAh Total
kVAh Net
MVAh Net
Minimum Kilowatts, Phase A
Minimum Kilowatts, Phase B
Minimum Kilowatts, Phase C
Minimum Kilowatts Total
Minimum kVAR Phase A
Minimum kVAR Phase B
Minimum kVAR Phase C
Minimum kVAR Total
Minimum Power Factor, Phase A
Minimum Power Factor, Phase B
Minimum Power Factor, Phase C
Minimum Power Factor Total
Minimum kVA, Phase A
Minimum kVA, Phase B
Minimum kVA, Phase C
Minimum kVA, Total
Minimum Frequency
Minimum Phase A Voltage K-Factor
Minimum Phase B Voltage K-Factor
Minimum Phase C Voltage K-Factor
Minimum Auxiliary Voltage K-Factor
Minimum Phase A Current K-Factor
Minimum Phase B Current K-Factor
Minimum Phase C Current K-Factor
Minimum Neutral Current K-Factor
Minimum Phase A Voltage Total Harmonic Distortion
Minimum Phase B Voltage Total Harmonic Distortion
Minimum Phase C Voltage Total Harmonic Distortion
Minimum Auxiliary Voltage Total Harmonic Distortion
Minimum Phase A Current Total Harmonic Distortion
Minimum Phase B Current Total Harmonic Distortion
Minimum Phase C Current Total Harmonic Distortion
Minimum Neutral Current Total Harmonic Distortion
Maximum Kilowatts, Phase A
Maximum Kilowatts, Phase B
Maximum Kilowatts, Phase C
1
2
kVA
kVA
kVA
kVA
Hz
%
%
%
%
%
%
%
%
kW
kW
kW
Network Point Type
Network Point Address
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 41
NPT1
(Cont.)
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
kW
kVAR
kVAR
kVAR
kVAR
Maximum Kilowatts Total
Maximum kVAR, Phase A
Maximum kVAR, Phase B
Maximum kVAR, Phase C
Maximum kVAR Total
Maximum Power Factor, Phase A
Maximum Power Factor, Phase B
Maximum Power Factor, Phase C
Maximum Power Factor Total
Maximum kVA, Phase A
Maximum kVA, Phase A
Maximum kVA, Phase A
Maximum kVA, Phase A
Maximum Frequency
Maximum Phase A Voltage K Factor
Maximum Phase B Voltage K Factor
Maximum Phase C Voltage K Factor
Maximum Auxiliary Voltage K Factor
Maximum Phase A Current K Factor
Maximum Phase B Current K Factor
Maximum Phase C Current K Factor
Maximum Neutral Current K Factor
Maximum Phase A Voltage Total Harmonic Distortion
Maximum Phase B Voltage Total Harmonic Distortion
Maximum Phase C Voltage Total Harmonic Distortion
Maximum Auxiliary Voltage Total Harmonic Distortion
Maximum Phase A Current Total Harmonic Distortion
Maximum Phase B Current Total Harmonic Distortion
Maximum Phase C Current Total Harmonic Distortion
Maximum Neutral Current Total Harmonic Distortion
Voltage at Phase A
Voltage at Phase B
Voltage at Phase C
Voltage at Phase AB
Voltage at Phase BC
Voltage at Phase CA
Current at Phase A
Current at Phase B
Current at Phase C
1
2
kVA
kVA
kVA
kVA
Hz
%
%
%
%
%
%
%
%
VRMS
VRMS
VRMS
VRMS
VRMS
VRMS
ARMS
ARMS
ARMS
Network Point Type
Network Point Address
Continued on next page . . .
42 Metasys Integrator—Metasys Integrator GE Power Application
NPT1
(Cont.)
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
kWRMS
kWRMS
kWRMS
kVRRMS
kVRRMS
kVRRMS
Kilowatts at Phase A
Kilowatts at Phase B
Kilowatts at Phase C
kVAR at Phase A
kVAR at Phase B
kVAR at Phase C
Power Factor at Phase A
Power Factor at Phase B
Power Factor at Phase C
KVA at Phase A
KVA at Phase B
KVA at Phase C
Phase A Voltage K-Factor
Phase B Voltage K-Factor
Phase C Voltage K-Factor
Aux Voltage K-Factor
Phase A Current K-Factor
Phase B Current K-Factor
Phase C Current K-Factor
Neutral Current K-Factor
Phase A Voltage Total Harmonic Distortion
Phase B Voltage Total Harmonic Distortion
Phase C Voltage Total Harmonic Distortion
Aux Voltage Total Harmonic Distortion
Phase A Current Total Harmonic Distortion
Phase B Current Total Harmonic Distortion
Phase C Current Total Harmonic Distortion
Neutral Current Total Harmonic Distortion
1
2
kVA
kVA
kVA
%
%
%
%
%
%
%
%
Network Point Type
Network Point Address
Metasys Integrator—Metasys Integrator GE Power Application 43
EPM3710
Power Meter—
Daisy-chained
Devices
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine the
Network Point Type
(NPT) and Network
Point Address (NPA).
For example, the
hardware reference
for the Average
Current is AI1.
Table 19: EPM3710 Power Meter Points—Daisy-chained Devices
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
BO
BO
BO
BO
BO
1
2
3
4
5
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
Unit
Description
ARMS
kW
kVA
kVAR
Volt
Amps
Volt
Volt
#
Hz
kW
#
Average Current
Total Kilowatts
kVA Total
kVAR Total
Voltage Aux
Neutral Current (I4)
Average LN Voltage
Voltage LL Average
Power Factor Total
Frequency at Va
kW Total Demand
Real Time Polarity
Reset All Minimum/Maximum Values3
Reset Hour Counters3
Relay 1
Relay 2
Relay 3
kWh
MWh
kWh
MWh
kWh
MWh
kVARh
Mvarh
kVARh
Mvarh
kVARh
Mvarh
kW
kVAR
%
kVA
0=n/a
0=n/a
1=reset
1=reset
kWh Import
MWh Import
kWh Export
MWh Export
kWh Total
MWh Total
kVARh Import
Mvarh Import
kVARh Export
Mvarh Export
kVARh Total
Mvarh Total
Minimum kW Total
Minimum kVAR Total
Minimum Power Factor Total
Minimum kVA Total
Network Point Type
Network Point Address
Do not map these points to Companion BO points. If you map these points to Metasys
system BO objects, disbale Auto Restore in the BO object’s Definition or Focus window.
Continued on next page . . .
44 Metasys Integrator—Metasys Integrator GE Power Application
NPT1
NPA2
Unit
Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Hz
kW
kVAR
#
kVA
Hz
Volt
Volt
Volt
Volt
Volt
Volt
Amps
Amps
Amps
kW
kW
kW
kVAR
kVAR
kVAR
kVA
kVA
kVA
Minimum Frequency
Maximum kW Total
Maximum kVAR Total
Maximum Power Factor Total
Maximum kVA Total
Maximum Frequency
Voltage at Phase A
Voltage at Phase B
Voltage at Phase C
Voltage at Phase AB
Voltage at Phase BC
Voltage at Phase CA
Current at Phase A
Current at Phase B
Current at Phase C
Kilowatts at Phase A
Kilowatts at Phase B
Kilowatts at Phase C
kVAR at Phase A
kVAR at Phase B
kVAR at Phase C
kVA at Phase A
kVA at Phase B
kVA at Phase C
1
2
Network Point Type
Network Point Address
Metasys Integrator—Metasys Integrator GE Power Application 45
EPM5300P
Power Meter—
Daisy-chained
Devices
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine the
Network Point Type
(NPT) and Network
Point Address
(NPA). For example,
the hardware
reference for the
Frequency is AI15.
Table 20: EPM5300P Power Meter Points—Daisy-chained Devices
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Unit
Description
Volt
Volt
Volt
Volt
Volt
Volt
Amps
Amps
Amps
Amps
Watts
Vars
VA
PF
Hz
Watts
Watts
Watts
Vars
Vars
Vars
VA
VA
VA
PF
PF
PF
Volt
Volt
Volt
Amps
Amps
Amps
Phase AN Voltage
Phase BN Voltage
Phase CN Voltage
Phase AB Voltage
Phase BC Voltage
Phase CA Voltage
Phase A Current
Phase B Current
Phase C Current
Neutral Current
Real Power
Reactive Power
Apparent Power
Power Factor
Frequency
Real Power Phase A
Real Power Phase B
Real Power Phase C
Reactive Power Phase A
Reactive Power Phase B
Reactive Power Phase C
Apparent Power Phase A
Apparent Power Phase B
Apparent Power Phase C
Power Factor Phase A
Power Factor Phase B
Power Factor Phase C
KF Voltage Phase A
KF Voltage Phase B
KF Voltage Phase C
KF Amps Phase A
KF Amps Phase B
KF Amps Phase C
Network Point Type
Network Point Address
46 Metasys Integrator—Metasys Integrator GE Power Application
EPM7300 Power
Meter—
Daisy-chained
Devices
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine the
Network Point Type
(NPT) and Network
Point Address
(NPA). For example,
the hardware
reference for the
Frequency is AI6.
Table 21: EPM7300 Power Meter Points—Daisy-chained Devices
NPT1 NPA2
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
BO
BO
1
2
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
Unit
Description
VRMS
VRMS
kVA
%
%
Hz
Voltage LN Average
Voltage LL Average
Average Current
Voltage Unbalance
Current Unbalance
Frequency
Real Time Polarity
kW Total Demand
kVAR Total
kVA Total
Power Factor Signed Average
KWh Total
kW
kVAR
kVA
%
kWh
Reset Minimum/Maximum Values3
Energy3
Volt
Volt
Volt
Volt
Volt
Volt
Amps
Amps
Amps
kW
kW
kW
kVAR
kVAR
kVAR
kVA
kVA
kVA
+/-%
+/-%
+/-%
kW
kVAR
kVA
0 = n/a,
0 = n/a,
1 = reset
1 = reset
Voltage at Phase A
Voltage at Phase B
Voltage at Phase C
Voltage at Phase AB
Voltage at Phase BC
Voltage at Phase CA
Current at Phase A
Current at Phase B
Current at Phase C
kW at Phase A
kW at Phase B
kW at Phase C
kVAR at Phase A
kVAR at Phase B
kVAR at Phase C
kVA at Phase A
kVA at Phase B
kVA at Phase C
Power Factor Signed A
Power Factor Signed B
Power Factor Signed C
kW Total to Date
kVAR Total to Date
kVA Total to Date
Network Point Type
Network Point Address
Do not map these points to Companion BO points. If you map these points to Metasys
system BO objects, disable Auto Restore in the BO object’s Definition or Focus window.
Continued on next page . . .
Metasys Integrator—Metasys Integrator GE Power Application 47
NPT1 NPA2
(Cont.)
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
Unit
Description
KW
KVAR
kVA
Volt
Amps
KW
KVAR
kVA
Hz
%
%
Hz
kWh
kWh
kWh
kVARh
kVARh
kVARh
kVARh
kVAh
kW Total to Date Maximum
kVAR Total to Date Maximum
kVA Total to Date Maximum
Voltage LN Average Frequency
Current Average Maximum
kW Total Maximum
kVAR Total Maximum
kVA Total Maximum
Frequency Maximum
Voltage LN Average Minimum
Current Average Minimum
Frequency Minimum
kWh Import
kWh Export
kWh Net
kVARh Import
kVARh Export
kVARh Total
kVARh Net
kVAh Total
Network Point Type
Network Point Address
48 Metasys Integrator—Metasys Integrator GE Power Application
EPM9650Q
Power Meter—
Daisy-chained
Devices
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine the
Network Point Type
(NPT) and Network
Point Address
(NPA). For example,
the hardware
reference for the
Frequency is AI24.
Table 22: EPM9650Q Power Meter Points—Daisy-chained Devices
NPT1
NPA2
Unit
Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
Volt
Volt
Volt
Volt
Amps
Amps
Amps
Amps
Volt
Volt
Volt
VA
VA
VA
VA
VAR
VAR
VAR
VAR
Watts
Watts
Watts
Watts
Hz
PF
PF
PF
PF
Volt
Volt
Volt
Volt
Pct
Pct
Pct
Pct
Pct
Pct
Volt
Volt
Volt
Amps
Amps
Amps
Volt
Volt
Volt
Phase A-N Voltage
Phase B-N Voltage
Phase C-N Voltage
Auxiliary Voltage
Phase A Current
Phase B Current
Phase C Current
Measured Neutral Current
Phase A-B Voltage
Phase B-C Voltage
Phase C-A Voltage
Phase A kVA
Phase B kVA
Phase C kVA
Three Phase VA
Phase A kVAR
Phase B kVAR
Phase C kVAR
Three Phase VAR
Phase A Watts
Phase B Watts
Phase C Watts
Three Phase Watts
Frequency
Phase A Power Factor
Phase B Power Factor
Phase C Power Factor
Three Phase Power Factor
Ph A-N Volts to Aux Volts Ph Angle
Phase A-N / Phase A-B Voltage THD
Phase B-N / Phase B-C Voltage THD
Phase C-N / Phase C-A Voltage THD
Phase A Current THD
Phase B Current THD
Phase C Current THD
Phase A Current K-Factor
Phase B Current K-Factor
Phase C Current K-Factor
Phase Angle Phase A-N Voltage
Phase Angle Phase B-N Voltage
Phase Angle Phase C-N Voltage
Phase Angle Phase A Current
Phase Angle Phase B Current
Phase Angle Phase C Current
Phase Angle Phase A-B Voltage
Phase Angle Phase B-C Voltage
Phase Angle Phase C-A Voltage
1
2
Network Point Type
Network Point Address
Metasys Integrator—Metasys Integrator GE Power Application 49
Metasys Network Setup
Metasys Network Setup is described in the Metasys Integrator unit
technical bulletins. This section contains details specific to the GE
applications.
Mapping to a
CS Object
Table 23: Software Model and CS Object Details
Application
Software Model
Display Attribute
(on Models diskette)
(recommended)
NT Command
Attribute*
(recommended)
Epic MicroVersaTrip FPU
GE_EPIC.DDL
BI1
Breaker State
ADF6
Under Voltage
Setpoint
GE PLM
GE_PLM.DDL
GE MVT
GE_MVT.DDL
GE EPM
GE_EPM.DDL
AI24
Energy
BI9
Breaker Open/Close
AI27
Energy
ADF1
Current Setpoint
ADF1
Current Setpoint
ADF1
Current Setpoint
AI1
Current Phase A
AI1
Current Phase A
AI1
Current Phase A
AI1
Current Phase A
ADF1
Current Setpoint
ADF1
Current Setpoint
ADF1
Current Setpoint
ADF1
Current Setpoint
GE FPU
485 PIM
Power Leader Modbus Concentrator
GE PLM
GEC_PLM.DDL
GE Spectra MVT
GEC_MVT.DDL
GE EMVT -C and -D
GEC_EMVT.DDL
GE EPM
GEC_EPM
Daisy-chained Devices
AI4
AO1
Average Current
Energy Cost Per kWh
GE_MDP.DDL
AI1
N/A
GE MDP
Current Phase A
AI2
PML_3720.DDL
AI1
EPM3720
Total Kilowatts
Average Phase
Current
BO1
PML_3710.DDL
AI1
EPM3710
Clear kWh
Average Phase
Current
GE_5300.DDL
AI11
AI11
EPM5300P
Real Power
Real Power
GE_7300.DDL
AI1
BO2
EPM7300
Average Voltage LN
Clear kW Hours
GE_9650.DDL
AI23
AI23
EPM9650Q
Three Phase Watts
Three Phase Watts
*
The NT Command attribute must be defined; it cannot be null. However, since the points
are not commandable, you cannot command the attribute.
GE PQM
GE_PQM.DDL
50 Metasys Integrator—Metasys Integrator GE Power Application
Custom Integration
For information on integrating products that are not discussed in this
document, first refer to the Metasys Compatible Products online list of
released connectivity products. If this list does not provide the information
you require, consider using the Systems Integration Services (SIS)
Request Custom Engineered Solutions process to request a custom
contract from the System Integration Team.
Access both the Metasys Compatible Products and the Request Custom
Engineered Solutions process from The Advisor by performing the
following steps:
1. Click on the Products Focus link, located at the top of The Advisor
home page.
2. Under Products, click on the Systems Integration Services link.
3. For the searchable database, click on Metasys Compatible Products.
4. Select Metasys Compatible Products Database.
5. Click Online Search Tool.
6. After the search is completed, return to the Systems Integration
Services home page as instructed in Steps 1-2.
7. Select Custom Engineered Solutions to view the process used for
requesting all types of SIS engineered solutions and services.
8. Select Requesting an Engineered Solution or Service.
9. Click Online Request Page.
If you need further assistance, contact the Johnson Controls Field Support
Center.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
www.johnsoncontrols.com
Software Release 9.3
Published in U.S.A.
Metasys Integrator—Metasys Integrator GE Power Application 51
Download