OmniReach Multi-Fiber Service Terminal (MST) Connector

advertisement
ADCP-96-045 ISSUE 1 June 2005
OmniReachTM Multi-Fiber
Service Terminal (MST) Connector
Replacement Instructions
INTRODUCTION
This publication provides instructions for replacing an SC connector installed on the
distribution side of the Optitap connector installed in the OmniReach Multi-Fiber Service
Terminal (MST). The MST enclosure is available in 2, 4, 6, 8 and 12 port configurations. This
publication shows the MST 8-port configuration as an example. Refer to these instructions
when replacing a connector in any of the various configurations.
1
2
USE A 3/8 INCH NUT DRIVER OR A STANDARD 3/8 INCH CAM WRENCH TO LOOSEN THE 10-32
CAPTIVE SCREWS ON THE COVER OF THE MST (DO NOT REMOVE SCREWS). DO NOT LOOSEN THE
SCREWS ON THE CABLE CLAMP.
3/8-INCH NUT DRIVER
REMOVE MST-8 FROM ENCLOSURE AND LAY ON FLAT SURFACE WITH COVER
FACING UP (HOUSING AND OptiTap CONNECTORS FACING DOWN).
COVER
HOUSING
10-32 SCREWS (12)
!
COVER
CAUTION: DO NOT LOOSEN
CABLE CLAMP SCREWS
CABLE CLAMP
OPTITAP
CONNECTOR (8)
HOUSING
OPTITAP CONNECTORS
CABLE CLAMP
4
MULTI-FIBER
SERVICE TERMINAL (MST)
3
REFER TO THIS STEP FOR PORT DESIGNATIONS AND FOR
ROUTING FIBER.
1
REMOVE COVER AND SET ASIDE.
2
B
A
CAPTIVE SCREWS, NOT REMOVABLE
PORT
RADIUS LIMITER
DESIGNATIONS (1-5)
PORT DESIGNATIONS
(A-H)
D
3
C
F
4
H
E
5
RADIUS LIMITERS
FIBER
A
1
4
BLACK
B
1
4
RED
C
2
4
WHITE
D
2
4
SLATE
E
1
3
BROWN
F
1
3
GREEN
G
2
3
ORANGE
H
2
3
BLUE
G
NOTE:
Danger:
!
1320652 REV A
Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look
into the ends of any optical fiber. Do not look directly into the optical adapters of the
adapter packs. Exposure to invisible laser radiation may result. A protective cap or hood MUST
be immediately placed over any radiating adapter or optical fiber connector to avoid the
potential of dangerous amounts of radiation exposure. This practice also prevents dirt
particles from entering the connector and adapter.
RADIUS LIMITER ARE LABELED 1 THROUGH 5,
PORT DESIGNATIONS ARE LABELED A THROUGH H.
20624-A
ADC TELECOMMUNICATIONS, INC
PO BOX 1101, MINNEAPOLIS, MN 55440-1101, USA
ATTN: TECHNICAL ASSISTANCE CENTER: 1-800-366-3891, EXT: 73475
WWW.ADC.COM
© 2005, ADC Telecommunications, Inc.
ADCP-96-045 ISSUE 1 June 2005
5
LOCATE CONNECTOR TO BE REPLACED. POSITION TIP OF A
SMALL FLAT HEAD SCREWDRIVER INTO GROOVE OF CONNECTOR
AND CAREFULLY PRY CONNECTOR LOOSE FROM ADAPTER. DO
NOT PULL ON BOOT OF FIBER OR DAMAGE MAY OCCUR TO FIBER.
6
IF NECESSARY, UNWIND THE CONNECTOR AND SUFFICIENT AMOUNT OF FIBER
FROM THE OTHER FIBERS.
7
CUT THE END OF THE CONNECTOR OFF AND REPLACE PER LOCAL
PRACTICE. IF SPLICING IN A PIGTAIL, MAKE SURE TO CUT FIBER
WHERE SPLICE WILL FIT INTO A STRAIGHT LOCATION OF THE TRAY.
NOTE:
UNWIND FIBER FROM
OTHER FIBERS,
IF NECESSARY
SPLICE REPLACEMENT
CONNECTOR PER LOCAL PRACTICE
NOTE:
CUT FIBER
THIS EXAMPLE SHOWS THE FAULTY
CONNECTOR INSTALLED IN PORT D.
GROOVE IN CONNECTOR
D
CONNECTOR TO BE
REPLACED
CUT FIBER
STRAIGHT LOCATIONS
FOR SPLICE
8
RE-ROUTE FIBER AROUND RADIUS LIMITERS TAKING OUT ANY SLACK IN FIBER. PLUG CONNECTOR
BACK INTO ADAPTER. MAKE SURE CONNECTOR SNAPS INTO ADAPTER. REFER TO TABLE
AS REFERENCE FOR ROUTING FIBER.
MAKE SURE CONNECTOR
SNAPS INTO ADAPTER
PORT
RADIUS LIMITERS
FIBER
A
1
4
BLACK
B
1
4
RED
C
2
4
WHITE
D
2
4
SLATE
E
1
3
BROWN
F
1
3
GREEN
G
2
3
ORANGE
H
2
3
9
PLACE COVER BACK ON HOUSING MAKING SURE THERE ARE NO FIBERS EXTENDING BEYOND EDGE OF HOUSING. TORQUE
SCREWS TO 15-POUND-INCHES FOLLOWING TORQUE SEQUENCE SHOWN ON THE COVER. AFTER TORQUING SCREWS IN
POSTIONS 13 AND 14, RE-TORQUE SCREWS IN POSITIONS 10 AND 12.
9
!
11
TORQUE SEQUENCE
5
1
CAUTION: OBSERVE TORQUE
REQUIREMENTS WHEN TIGHTENING
NUTS AND BOLTS. DO NOT OVER
TIGHTEN HEX NUTS AND HEX BOLTS OR
DAMAGE MAY OCCUR TO EQUIPMENT.
4
14
8
12
BLUE
10
TORQUE TO 15 POUND-INCHES
7
3
2
6
13
RE-ROUTE FIBER AROUND RADIUS LIMITERS
TAKING UP ANY LOOSE SLACK. REFER TO TABLE
AS REFERENCE FOR ROUTING FIBERS.
1320652 REV A
TORQUE WRENCH
20625-A
© 2005, ADC Telecommunications, Inc.
Download