H:\Y04\Man\Y04man.wpd [PFP#381585155]

advertisement
TELEFRANG AB
Humidity & Temperature Sensor Y04
Y04 Block Diagram.
Gene
Description
ral
Y04 is a humidity and temperature sensor powered entirely from the two-wire
SIOX communication bus while Y04-1 uses a separate power supply.
Temperature is measured between -40,0 *C and +80,0 *C while relative
humidity is measured between 10 % and 95 %.
Both Y04 and Y04-1 contain a relative humidity sensor and an NTC resistor
(Negative Temperature Coefficient) used as temperature sensor. These
sensors are located at the tip of the module (to the right in the picture above).
The internal firmware presents the values read from these sensors with a
resolution of 0,1 *C and 0,1 %, respectively. The Y04-1 has a connector for an
additional NTC sensor and a relay output. The relay output is closed when no
power is supplied to the module.
Both modules include an internal PLC (Programmable Logic Controller) for
application specific programs. The PLC is described in an additional manual
called “SIOX Programmable Controller”.
The modules also contain a reed switch at the tip of the module that is used for
sequential addressing and default setting, see “Address setup”.
Care should be taken not to expose the module to liquid water since the
humidity sensor will be permanently affected by this, thus invalidating the
factory calibration.
H:\Y04\Man\Y04man.wpd/2007-06-05/YE
Y04-1
Block Diagram.
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p3
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p4
Installation and Startup
TABLE OF CONTENTS
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power Supply and connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Parameter Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
The SIOX modules should be interconnected through a two-wire, low capacitance
twisted pair. Shielded cables may be used, but unless a correct strategy for shield
grounding is adopted, it may prove to be of little benefit. Instead, the capacitance
between the shield and the bus wires will add to the total capacitive load on the
SIOX bus and decrease the maximum distance over which communication can be
carried out for a given bit rate. The total resistance of the bus should not be higher
than 2 * 50 (.
The module is preset at the factory to communicate at 4800 bits/s and the address
set to 1. General principles for the SIOX bus and communications are discussed
in a separate manual, the "SIOX System Description". Changes in operation modes
are brought about by Parameter Setup Strings communicated over the SIOX bus.
Magnetic Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Address setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Supply and connectors
Group Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Y04 is connected to the SIOX bus by an unpolarised 2-wire interface. The module
is powered from the SIOX bus and has no need for an external power supply.
SIOX Message Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Measurement Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Analogue Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Internal Temperature Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
External Temperature Gain / Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Humidity Gain / Offset (*) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dewpoint Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Relay Output (Y04-1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Y04-1 has eight screw terminals for 0,14 - 1,0 mm2 cable (see picture below). The
Relay switch can be controlled by the internal firmware or by the internal PLC, see
“Relay output”.
The NTC temperature sensor connected to the “External NTC” terminals should
have a nominal resistance of 10 k( at 25 *C and a B factor of 3900 for the internal
firmware to calculate the correct temperature from this sensor (for instance
Betatherm 10K3A1B) .
The SIOX communication terminals for Y04-1 are polarised so care should be
taken to connect the SIOX bus with the right polarity.
Y04-1 requires an external DC power supply with a voltage of 24 to 48 Volts.
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Y04-1
ors
Connect
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p5
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p6
Parameter Memory
Communications
The Y04 contains two types of memory: RAM for temporary storage for as long as
the module is connected to a power supply, and EEPROM for long-term storage
of working modes, parameters and initialization values after a power disconnect.
At power-up, the EEPROM variables are automatically copied to the RAM, and the
information is used to control the module. All EEPROM setup values may be
copied again if data = FFFF16 is written to the first parameter number 0/0/. This
initiates a full soft reset, without changing the value in the EEPROM for this
parameter.
Y04 communicates as a slave in normal SIOX buses using speeds from 300 to
19200 bits/second. To change communication speed, send a Setup String
command setting the station's EEPROM parameter 0/0/. Note, that the speed will not
change until after a power-down/power-up cycle has been carried out or a Soft
Reset (FFFF16) in this parameter.
By using String Mode commands any variable may be read or modified at any
time* either temporarily in RAM or permanently in EEPROM. In the latter case, the
corresponding RAM cell is modified as well. Information in controlling parameters
will immediately affect the function of the module.
* Parameters 5, 6, 7, $0/E and $0/F holds calibration data and are locked. They can
only be changed by setting the ‘Write All’ flag (bit 16 in parameter 0/). This is the
Most Significant bit in the parameter, refer to page 12.
Definitions of parameter contents.
(XXXX16)
Factory preset information for the parameter.
5555
One nibble (4bit), where the left bit is the most significant
bit and the right bit is the least significant bit.
5555 5555 5555 5555
One parameter (2byte)(16bit), where the left two nibbles
represents the most significant byte and the right the
least significant byte.
I
Only this bit is relevant for the described function.
5
This bit is used for other purposes.
This bit is equal to 0.
This bit is equal to 1.
If the current speed or address is unknown, use the Visual Setup PC program to
find and change the module. In worst case set the module to default (page 4) if the
module cannot be found following the procedure described below.
Parameter 0/0/: (0/70/0/16)
Soft Reset copies EEPROM to RAM.
0/ = Autobaud, 1200 - 19200 bits/second
5555 5555 5555
3 = 300 bits/second communication speed
5555 5555 5555
4 = 600 bits/second communication speed
5555 5555 5555
5 = 1200 bits/second communication speed
5555 5555 5555
6 = 2400 bits/second communication speed
5555 5555 5555
7 = 4800 bits/second communication speed
5555 5555 5555
8 = 9600 bits/second communication speed
5555 5555 5555
9 = 19200 bits/second communication speed
5555 5555 5555
Magnetic Switch
The module includes a reed switch which can be activated by placing a magnet on
the Y04 approximately 10 mm from the tip. If the switch is active when power is
applied to the SIOX bus and released within 3 seconds, the module enters a
“default” mode. The address is set to 63, the bit rate to 4800, PLC and any options
are disabled. In this way, an Y04 with unknown speed or address or colliding with
another module can be accessed and the correct settings entered.
Follow these steps to recover a “lost” module:
1. Disconnect power.
2. Apply a magnet to the tip of the module (closing an internal reed switch).
3. Reapply power and remove the magnet within 3 seconds. The module will now
communicate at 4800 bits/s on address 63 with the PLC and any options
disabled.
4. Check and reconfigure the module for proper operation.
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p7
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p8
Address setup
Group Address
Parameter 0/1 contains the module address in bits 14 - 9. Changing the address will
cause the module to occupy another address on the SIOX bus. Address 0/ is not
a valid address so setting the address to 0/ will revert the address to 63 (3F16).
Large SIOX systems may contain more than 63 modules. In this case an extra
group address character may be added to string setup messages to allow 63*63
modules. Y04 can be set to respond to a group address by setting the option x4xx
in parameter 0/2 and the Group address xx0/1 -xx3F in parameter 0/0/. The unit will
immediately readdress itself.
Parameter 0/1: (0/10/0/16)
0/1 - 3F = Module address
55IJ IJIJ 5555 5555
0/1 - 3F = Group address
5555 5555 55JI JIJI
(option x4xx in Parameter 2 must be set)
There are two ways of setting up the address in the internal EEPROM in the
module. If a module is connected to a SIOX bus which includes a master, typically
a PC or a SIOX operator terminal, this master can search for the module and, when
found, send a command to change the address. The typical PC program for this
is the Visual Setup for Y04: Y04setup.dff
Alternatively, a special Sequential Addressing command can be sent to a group
of already installed modules using the SIOX Sequential Addressing software*. If a
magnet is applied to the tip of a Y04 module (closing the internal reed-switch) when
it has received this command, the module accepts the command and saves the
included address in its EEPROM. The module then sends an acknowledge to the
master. The master now typically sends the addressing command again but now
with the next address in the chain, and the next module can be handled. Finally all
modules have received individual addresses regardless of their former set-ups and
the master stops sending Sequential Address commands. Should the chain be
incorrect, the whole sequence can be restarted.
Follow these steps:
1.
2.
3.
4.
5.
Start the software "SIOX Sequential Addressing tool".
Press F6 and make sure that the communication settings are correct.
Press start.
The start address can be changed by the "skip"-button
Now apply a magnet to the tip of the first Y04
(will have the first address) for a duration of approximately one second and then
remove it.
6. Continue with next module until all modules are configured.
* The addressing tool can be downloaded on our website.
SIOX Message Transfer
Two types of SIOX messages are accepted: Data Mode or String Setup Mode.
A Data Mode Communication is a minimum two-way communication between the
central and a module. Data Mode affects the seven least significant bits in
parameter 0/8 and the answer is the 14 least significant bits in parameter 0/9.
String Mode Communications use the same address as Data Mode but permit
access to all functions in the module.
Data Mode transfers are less reliable than String Mode, and in some cases a Data
Mode message could inadvertently change the relay state. Therefore, setting bit
14 in parameter 0/0/ inhibits any changes by Data Mode, although a correct answer
will still be returned.
Measurement Results
The results from the humidity and temperature measurements are stored in
parameter 38, 39 and 3A. The results are scaled by a factor of 10 e.g. a result
value of 213 (0/0/D516) in parameter 38 corresponds to a measured temperature of
21,3 *C.
Parameter 38: (0/0/0/0/16)
Measured Internal Temperature -40,0 *C to +80,0 *C,
IJIJ IJIJ IJIJ IJIJ
resolution in 0,1 *C.
Parameter 39: (0/0/0/0/16)
Measured Relative Humidity 0% to 100%, resolution in
IJIJ IJIJ IJIJ IJIJ
0,1% .
Parameter 3A: (0/0/0/0/16)
Valid only for Y04-1 with connected sensor
Measured External Temperature -40,0 *C to +80,0 *C,
IJIJ IJIJ IJIJ IJIJ
resolution in 0,1 *C. Please note that two choices of
sensor B value is supported. If Option Parameter 0/2
is set to x8xx then B=3900, otherwise B=3530.
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p9
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 10
Analogue Filter
External Temperature Gain / Offset (*)
Valid only for Y04-1. Filter for noise elimination of the external temperature sensor.
Sets the time-constant to between 1 s and 60 s in 7 steps.
These parameters permit offset and gain control for the external temperature NTC
sensor used in Y04-1. These values are factory calibrated and does not normally
need to be changed.
Parameter 0/3: (0/0/0/116)
0/1 = 1 second Analogue Filter Step
5555 5555 0/2 = 2 seconds Analogue Filter Step
5555 5555 0/3 = 4 seconds Analogue Filter Step
5555 5555 0/4 = 8 seconds Analogue Filter Step
5555 5555 0/5 = 16 seconds Analogue Filter Step
5555 5555 0/6 = 30 seconds Analogue Filter Step
5555 5555 0/7 = 60 seconds Analogue Filter Step
5555 5555 The result is stored in parameter 3A.
Parameter 0/6: (XXXX16)
80/0/1 - 80/FF Negative Temperature Gain
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ - 0/0/FF Positive Temperature Gain
Parameter 0/7: (XXXX16)
80/0/0/ - 0/0/0/0/ - 7FFF External Temperature Offset
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = No offset
Internal Temperature Offset (*)
Humidity Gain / Offset (*)
This parameter permit offset control of the internal temperature value, normally
expressed in tenths of *C. The Offset is added to the measured internal
temperature and the result is stored in parameter 38. It is typically used if a small
correction shall be made to the temperature value.
These parameters permit offsetting and scaling of the relative humidity value,
normally expressed in tenths of %. The Gain is multiplied with the measured
relative humidity and the Offset is then added to the product. Gain should normally
be set to 0/0/0/0/. Offset is used to fine trim the humidity value during calibration. The
result from these operations is stored in parameter 39.
The Offset uses 2:s complement representation, so an offset value of FFFF16
corresponds to a decimal value of -1 (-0.1 *C), FFFE16 corresponds to a decimal
value of -2 and so on. An offset value of 0/0/0/1 corresponds to 1, 0/0/0/2 to 2 and so
on. This gives an offset value range from -32768 to +32767 (80/0/0/ - 7FFF).
Gain = 10/0/0/16 corresponds to a multiplication by 1, 0/0/0/116 corresponds to a factor
of 1/4096 and FFFF16 is equal to a factor of 65535/4096 + *16. Default Offset and
Gain values = 0/0/0/0/ do not modify the temperature readout.
Parameter 0/5: (0/0/0/0/16)
80/0/0/ - 0/0/0/0/ - 7FFF
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = No offset
The Offset uses 2:s complement representation, see explanation in section
“Internal Temperature Offset”.
Internal Temperature Offset
Parameter 0/E: (0/0/0/0/16)
0/0/0/0/ - FFFF Humidity Gain
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = 10/0/0/ = Nominal gain adjustment (Gain = 1)
Parameter 0/F: (0/0/0/0/16)
FF0/0/ - 0/0/0/0/ - 0/0/FF Humidity Offset
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = No offset
* The gain and offset parameters for humidity and temperature are precalibrated
from factory and can only be changed if the most significant bit in parameter 0/0/ is
set (see page 12).
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 11
Dewpoint Calculation
The firmware calculates the dewpoint by measuring the internal temperature and
the relative humidity. The vapour pressure is then acquired from an internal table
using the measured temperature as input.
The dewpoint temperature is then calculated from this vapour pressure.
The “Internal dewpoint adjust” byte is then added to this temperature (with sign)
and the “External dewpoint adjust” byte is added to the external temperature
reading. If the internal temperature (with adjustment) is above 0 *C and the
external temperature (with adjustment) is below 0 *C, bit 1 in parameter 0/9 will be
set (Freezing hazard).
The two values in parameter 0/D use 2:s complement representation, see section
“Internal Temperature Offset” for a brief description.
Parameter 0/9: (0/0/0/0/16)
No dew point warning
5555 5555 5555 555
Dew point warning
5555 5555 5555 555
Parameter 0/D: (0/0/0/0/16)
Internal dewpoint adjust
IJIJ IJIJ 5555 5555
External dewpoint adjust
5555 5555 IJIJ IJIJ
Relay Output (Y04-1)
Bit 1 in parameter 0/8 controls the relay in Y04-1. When the bit is set, the relay
switch is open, and when it is zero the relay is closed. Bit 1 in parameter 0/A is a
user flag bit that enables control of the relay function by the firmware. If this bit is
set the internal firmware will use the relay to warn of a freezing hazard (when bit
1 in parameter 9 is set) by clearing bit 1 in parameter 8.
When bit 1 in parameter 0/A is set and a PLC program tries to use the relay, the
firmware and the PLC will compete for control of the relay. Care should be taken
to only enable firmware control of the relay when no PLC program is using the
relay.
Parameter 0/8: (0/0/0/0/16)
Relay active (relay contact open). Valid for Y04-1 only.
5555 5555 5555 555
Relay not active (relay contact closed)
5555 5555 5555 555
Parameter 0/A: (0/0/0/0/16)
Firmware relay activation allowed. Valid for Y04-1 only.
5555 5555 5555 555
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 12
Parameters
Parameter setup (16 bits / parameter):
Parameter 0/0/: (0/70/0/16)
(refer to page 6, 7)
Soft Reset copies EEPROM to RAM.
Enables writing to all parameters (‘Write All’)
555 5555 5555 5555
No output change allowed in Data Mode
555 5555 5555 5555
Enable Double Data Mode
555 5555 5555 5555
0/ = Autobaud, 1200 - 19200 bits/second
5555 5555 5555
3 = 300 bits/second communication speed
5555 5555 5555
4 = 600 bits/second communication speed
5555 5555 5555
5 = 1200 bits/second communication speed
5555 5555 5555
6 = 2400 bits/second communication speed
5555 5555 5555
7 = 4800 bits/second communication speed
5555 5555 5555
8 = 9600 bits/second communication speed
5555 5555 5555
9 = 19200 bits/second communication speed
5555 5555 5555
0/1 - 3F = Group address
5555 5555 55IJ IJIJ
Parameter 0/1: (0/10/0/16)
(refer to page 7)
0/1 - 3F = Module address
55IJ IJIJ 5555 5555
Parameter 0/2: (0/0/0/0/16)
Options reserved for customer specific functions
IJIJ 55IJ IJIJ IJIJ
External Temp. sensor B=3900, otherwise B=3530
5555 555 5555 5555
Group address allowed
5555 555 5555 5555
Parameter 0/3: (0/10/0/16)
(refer to page 9)
0/1 = 1 second Analogue Filter Step
5555 5 5555 5555
0/2 = 2 seconds Analogue Filter Step
5555 5 5555 5555
0/3 = 4 seconds Analogue Filter Step
5555 5 5555 5555
0/4 = 8 seconds Analogue Filter Step
5555 5 5555 5555
0/5 = 16 seconds Analogue Filter Step
5555 5 5555 5555
0/6 = 30 seconds Analogue Filter Step
5555 5 5555 5555
0/7 = 60 seconds Analogue Filter Step
5555 5 5555 5555
Parameter 0/4: (0/0/0/0/16)
Free for PLC use
IJIJ IJIJ IJIJ IJIJ
Parameter 0/5: (0/0/0/0/16)
(refer to page 9)
80/0/0/ - 0/0/0/0/ - 7FFF Internal Temperature Offset
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = No offset
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 13
Parameter 0/6: (XXXX16)
(refer to page 10)
External Temperature Scaling (calibration)
IJIJ IJIJ IJIJ IJIJ
80/0/1 - 80/FF Negative Temperature Gain
0/0/0/0/ - 0/0/FF Positive Temperature Gain
Parameter 0/7: (XXXX16)
(refer to page 10)
80/0/0/ - 0/0/0/0/ - 7FFF External Temperature Offset
IJIJ IJIJ IJIJ IJIJ
(calibration)
0/0/0/0/ = No offset
Parameter 0/8: (0/0/0/0/16)
(refer to page 11)
Relay active (relay contact open). Valid for Y04-1 only
5555 5555 5555 555
Relay not active (relay contact closed)
5555 5555 5555 555
Parameter 0/9: (0/0/0/0/16)
(refer to page 11)
No dew point warning. Valid for Y04-1 only
5555 5555 5555 555
Dew point warning
5555 5555 5555 555
Parameter 0/A: (0/0/0/0/16)
(refer to page 11)
Firmware relay activation allowed. Valid for Y04-1 only
5555 5555 5555 555
Parameter 0/B: (0/10/0/16)
(refer to page 9)
0/1 = 1 second Rh Analogue Filter Step
5555 5 5555 5555
0/2 = 2 seconds Rh Analogue Filter Step
5555 5 5555 5555
0/3 = 4 seconds Rh Analogue Filter Step
5555 5 5555 5555
0/4 = 8 seconds Rh Analogue Filter Step
5555 5 5555 5555
0/5 = 16 seconds Rh Analogue Filter Step
5555 5 5555 5555
0/6 = 30 seconds Rh Analogue Filter Step
5555 5 5555 5555
0/7 = 60 seconds Rh Analogue Filter Step
5555 5 5555 5555
Parameter 0/C: (0/0/0/0/16)
Internal functions. DO NOT MODIFY!
IJIJ IJIJ IJIJ IJIJ
Parameter 0/D: (0/0/0/0/16)
(refer to page 11)
Internal dewpoint adjust
IJIJ IJIJ 5555 5555
External dewpoint adjust
5555 5555 IJIJ IJIJ
Parameter 0/E: (0/0/0/0/16)
(refer to page 10)
0/0/0/0/ - FFFF Relative Humidity Gain
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = 10/0/0/ = Nominal gain adjustment (Gain = 1)
Parameter 0/F: (0/0/0/0/16)
(refer to page 10)
FF0/0/ - 0/0/0/0/ - 0/0/FF Relative Humidity Offset
IJIJ IJIJ IJIJ IJIJ
0/0/0/0/ = No offset
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 14
Parameter 10/: (0/0/0/0/16)
(refer to page 11)
PLC digital outputs mask.
55IJ IJIJ 5555 5555
Relay controlled by PLC
5555 555 5555 5555
Parameter 11: (0/0/0/0/16)
0/0/16 - 3F16 PLC program counter bank.
IJIJ IJIJ 5555 5555
0/0/16 - FF16 = PLC program counter.
5555 5555 IJIJ IJIJ
Parameter 12: (0/0/0/0/16)
0/0/16 - FF16 = PLC timer tick size.
IJIJ IJIJ 5555 5555
0/0/16 = 1/16 s (4B16 gives the same time as 0/0/ 16).
0/116 - FF16 = x, x / 1200 s.
EEPSH remapping of EEPROM active.
5555 5555 5J55 5555
Single step done.
5555 5555 55J5 5555
1 = PLC single step.
5555 5555 555J 5555
0/ = Continuous run.
0/0/0/2 = PLC stop.
5555 5555 5555 5JIJ
0/0/12 - 10/0/2 = PLC active task 1...4.
Parameter 13: (0/0/0/0/16)
Clear edge triggered Inputs (autoZ)
5555 J555 5555 5555
Communication ready.
5555 555J 5555 5555
PLC overflow flag L.
5555 5555 55J5 5555
PLC carry flag C.
5555 5555 555J 5555
PLC bit accumulator A.
5555 5555 5555 555J
Parameter 14: (000016)
PLC V accumulator, 80/0/0/16 - 7FFF16 = -32768 - +32767.
IJIJ IJIJ IJIJ IJIJ
Parameter 15: (000016)
PLC T timer, 0/0/0/0/ 16 - FFFF16. Tick rate is defined in
IJIJ IJIJ IJIJ IJIJ
parameter 12.
Parameter 16: (000016)
Real Time Clock, trim and 10 ms counter.
IJIJ IJIJ IJIJ IJIJ
Parameter 17: (000016)
RTC, seconds counter or PLC minutes + seconds.
IJIJ IJIJ IJIJ IJIJ
Parameter 18-37: (000016)
PLC data storage.
IJIJ IJIJ IJIJ IJIJ
Parameter 38: (0/0/0/0/16)
(refer to page 8)
Measured Internal Temperature -40,0 *C to +80,0 *C,
IJIJ IJIJ IJIJ IJIJ
resolution in 0,1 *C.
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
p 15
Parameter 39: (0/0/0/0/16)
(refer to page 8)
Measured Relative Humidity 0% to 100%, resolution in
IJIJ IJIJ IJIJ IJIJ
0,1% .
Parameter 3A: (0/0/0/0/16)
(refer to page 8)
Measured External Temperature -40,0 *C to +80,0 *C,
IJIJ IJIJ IJIJ IJIJ
resolution in 0,1 *C.
Parameter 3B: (0/0/0/0/16)
Measured Supply Voltage 10 V to 48 V,
IJIJ IJIJ IJIJ IJIJ
resolution in 0,1V.
Parameter 3C-3F: (0/0/0/0/16)
Reserved
IJIJ IJIJ IJIJ IJIJ
Parameter 40-41: (0/0/0/0/16)
Spy on external module, see manual “SIOX
IJIJ IJIJ IJIJ IJIJ
Programmable Controller”
Parameter 42-7F: (0/0/0/0/16)
Reserved, do not change
IJIJ IJIJ IJIJ IJIJ
Parameter 80-3FF: (0/0/0/0/16)
PLC program (EEPROM only)
IJIJ IJIJ IJIJ IJIJ
Min
15
15
Typ
24
24 / 48
1,2
21
0,3
-40,0
Max
35
56
19,2
+80,0
±1
10,0
±1
±2
15
95,0
±3
Unit
V
V
mA
mA
kbit/s
*C
*C
% rH
% rH
s
p 16
Environmental Specifications
Operating Temperature Range
Storage Temperature Range
Min
-40
-40
Mechanical Specifications
Case Size (Y04)
Case Size (Y04-1)
Weight (including 10m cable) (Y04)
Weight (Y04-1)
Assistance
on safety and technical matters is available from:
TELEFRANG AB
Varbergsgatan 8
S-412 65 GÖTEBORG
SWEDEN
Tel:
Fax:
E-mail:
Visual Setup Download:
Electrical Specifications (Tamb = 20 °C)
Bus voltage
Supply voltage (Y04-1)
Power Supply current (Y04, from 24V SIOX)
Power Supply current (Y04-1)
Communication speed
Temperature range
Temperature accuracy
Relative humidity range
Relative humidity accuracy
Response Time (90% of final value in a 95%
step change)
Y04 HUMIDITY AND TEMPERATURE SENSOR MODULE
+46 31 40 30 60
+46 31 40 20 25
info@telefrang.se
www.siox.com
Typ
Max
+80
+80
97,5 x 13 x 6,5
133 x 13 x 6,5
350
20
Unit
*C
*C
mm
mm
g
g
Download