GENESIS R70/R80/R90 OPERATOR’S MANUAL This guide has been prepared for the operator of Carrier Transicold GENESIS R70/R80/R90 refrigeration units. It contains basic instructions for the daily operation of the refrigeration unit as well as safety information, trouble shooting tips, and other information that will help you to deliver the load in the best possible condition. Please take the time to read the information contained in this booklet and refer to it when ever you have a question about the operation of your Carrier Transicold GENESIS R70/R80/R90 units. Your refrigeration unit has been engineered to provide long, trouble--free performance when it is properly operated and maintained. The checks outlined in this guide will help minimize problems. Maintenance program will also help to control operating costs, increase the unit’s working life, and improve performance. Carrier Transicold has an on--going product quality upgrade policy. As a result, specifications are liable to change without notice. 4 CONTENTS Page UNIT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 PRETRIP INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Starting the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing the setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Stop the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation with auxiliary control panel (option) . . . . . . . . . Change setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lock the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unlock the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 25 25 26 27 27 28 PRODUCT LOADING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 RECOMMENDED TRANSPORT TEMPERATURES . . . . . . 33 PROBLEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 UNIT MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Unit maintenance schedules . . . . . . . . . . . . . . . . . . . . . . . . Description of maintenance operations . . . . . . . . . . . . . . . Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 43 44 48 STANDBY OPERATION GUIDELINES . . . . . . . . . . . . . . . . . . 49 MANUFACTURER INFORMATION . . . . . . . . . . . . . . . . . . . . . 50 “A.T.P. EUROPE” REGULATION EXTRACT . . . . . . . . . . . . . 54 EMERGENCY ROAD SERVICE . . . . . . . . . . . . . . . . . . . . . . . . 56 5 G B UNIT IDENTIFICATION CONDENSER The nameplate identifies: : serial number : refrigerant charge and quantity : date in service * gives you all the information when calling 24 hour Assistance. 6 UNIT IDENTIFICATION EVAPORATORS G B MTD 2200 model (dual discharge) MTS 700 model (single discharge) 7 SAFETY Your Carrier Transicold refrigeration unit has been designed with the safety of the operator in mind. During normal operation, all moving parts are fully enclosed to help prevent injury. During all pre--trip inspections, daily inspections, and problem troubleshooting, you may be exposed to moving parts; please stay clear of these moving parts when the unit is in operation and when the main power switch is in the Run (On) position. The evaporator and condenser are made of finned tubes. The fins can cause injury on contact with skin. It is recommended to wear protective gloves during all handling operations. During operation, certain components such as the exhaust pipe, discharge outlet, and cooling circuit radiator can become extremely hot. During routine service operations, wear protective gloves. AUTO-- START/STOP Your refrigeration unit is equipped with Auto-Start/Stop, a valuable fuel saving feature. When the unit is set for Auto-Start/Stop operation it may start at any time. When performing any check of the refrigeration unit (e.g., checking the belts, checking the oil), make certain that the main power switch is in the OFF (0) position. ENGINE COOLANT The engine, as with all diesel engines, is equipped with a pressurized cooling system. Under normal operating conditions, the coolant in the engine and radiator is under high pressure and is very hot. Contact with hot coolant can cause severe burns. Do not remove the cap from a hot radiator; if the cap must be removed, do so very slowly in order to release the pressure without spraying. REFRIGERANTS The refrigerant contained in the refrigeration system of your unit can cause frostbite, severe burns, or blindness when in direct contact with the skin or eyes. For this reason, and because of legislation regarding the handling of refrigerants during system service, whenever your unit requires service of the refrigeration system, we recommend that you contact your nearest Carrier Transicold authorized repair facility for service. 8 SAFETY BATTERY This unit is equipped with a lead--acid type battery. The battery normally vents small amounts of flammable hydrogen gas. Keep any flame, any lighted object (cigarette etc.) or any source of sparks away from the battery elements. A battery explosion can cause serious physical harm and/or blindness. AUTOMATIC START UP IN DIESEL WHEN LOSS OF STANDBY FROM EPROM 4.05 To activate this function: TIME STRT set up in functionnal parameters. When the unit is started in standby, the “ROAD” light is flashing and the “STANDBY” light is lit. After 5 minutes of loss of power, the unit automatically starts in diesel. 5 minutes after the power comes back, the unit starts again automatically in electric mode. The “STANDBY MOTOR” alarm appears, alarm that you would have to clear. * This function will be active even after a stop (OFF) of the unit. To deactivate it: set up TEMP STRT in functionnal parameters. DEACTIVATE THIS FUNCTION WHEN UNIT IS RUNNING IN A CLOSED AREA ! 9 G B FEATURES This refrigeration unit is equipped with a wide range of features that are designed to improve reliability and temperature control within the body. The group can be delivered fitted with a microprocessor controller. MICROPROCESSOR CONTROLS 17. 1. 16. 2. 15. 3. 14. 4. 13. 5. 12. 11. 6. 7. 8. 9. 1. Display 2. Up and down arrow keys 3. Function change key 4. Run/Stop switch 5. Road key 6. Comp. 1 ON/OFF switch 7. City speed key 8. Comp. 2 ON/OFF switch 9. Manual defrost key 10 10. 10. Comp. 3 ON/OFF switch 11. Buzzer off key 12. Standby key 13. Pretrip key 14. Auto-start/Stop key 15. Unit data key 16. Fault alarm led 17. Enter key FEATURES The microprocessor controls incorporated into this unit are the most reliable control system available. It is also designed to be the easiest to use, offering great flexibility in control, yet minimal user input for normal operation: a true “set it and forget it” design. 1. Display window: shows set--point, box temperature, operating mode, alarm displays, as well as data on the unit itself (battery voltage, water temperature etc.). Function Change key The function change key is used to display the operating parameters. Each time this key is pressed the display will advance to the next parameter. This key, in conjunction with the up/down arrow and enter keys, will allow the user to change the parameters. Arrows key The UP ARROW and DOWN ARROW keys are used to alter the set--point. Press the up or down arrow keys until the desired setpoint is displayed on the left--hand side of the display window. When the correct set--point is displayed, press the ENTER key to confirm the setting. The UP ARROW and DOWN ARROW keys are also used to change the unit functions and scroll through the FUNCTION and UNIT DATA screens. Enter key The ENTER key confirms changes made to unit operation. It must be pressed to change the setpoint after using the arrow keys to adjust it. If the ENTER key is not pressed, the setpoint will revert to the previously entered setting. The ENTER key must also be pressed whenever a FUNCTION setting is being altered. If this key is not pressed, the function will revert to its previous setting. 11 G B FEATURES RUN/STOP switch The main unit RUN/STOP switch controls the unit operation. When switched to the Run (I) position, the unit will start in the operating mode last entered (Road or Standby). The set--point will be at the last set--point entered on the keypad. Road key The ROAD key puts the unit into Road (or engine) operation when the unit has been previously operated in the Standby mode. City Speed key The CITY SPEED key toggles the unit between high speed and low speed (diesel mode). When City Speed is selected, the unit will run only in low speed except during defrost cycles. This feature is useful in areas where noise is restricted. Manual defrost key The MANUAL DEFROST key places the unit in a defrost cycle. Under most conditions it is not necessary to defrost the unit manually as this is done automatically with the air switch or the defrost timer. Manual defrost may become necessary due to ice accumulated on the evaporator coil during frequent door openings in humid environments. Buzzer Off key The BUZZER OFF key temporarily turns off the FAULT ALARM buzzer. The red light “Fault alarm” remains illuminated on the command cab. 12 FEATURES Standby key The STANDBY key places the unit in Standby (or electric) mode when the previous mode of operation has been Road. Pretrip Check key The PRETRIP key initiates a check of all normal operating modes. The temperature inside the box must be below 5EC p 1EC (35EF p 2EF) to start this check. Upon initiation, the unit will cycle through all operating modes at 30 second intervals. The display will show “PPPP” at the beginning and will show various unit data during the pre--trip cycle. Upon completion of the pre--trip cycle the unit will be placed into the defrost mode. Auto Start/Stop Continuous key The AUTO--START/STOP key toggles the unit operating mode between Auto--Start/Stop and continuous run. When the unit is set for Auto--Start/Stop operation, the unit will run until the box temperature reaches set--point and then cycle off (after the minimum run time has been met) until further cooling or heating is necessary. When in the continuous mode, the unit will cycle between heat and cool as required to maintain the set temperature in the body. If the setpoint is below -12EC (10EF) the unit will not heat, it will run continuously in low speed cool. 13 G B FEATURES Unit Data key i This key scrolls the display through the various operating condition displays, engine temperature or battery voltage, for example. A more complete description of the function is found later in this chapter. Compartment 1 ON/OFF switch When switched to (I) the unit and compartment 1 will start in the operating mode last entered (cooling or heating). Compartment 2 ON/OFF switch When switched to (I) the unit and compartment 2 will start in the operating mode last entered (cooling or heating). Compartment 3 ON/OFF switch When switched to (I) the unit and compartment 3 will start in the operating mode last entered (cooling or heating). 16. Fault Alarm led: illuminates when an alarm is detected. 14 FEATURES OPTION G B Important: If the cab control displays nothing, check the position of the RUN switch located on the microprocessor box. 1 2 1. Main unit operation switch (RS) Turn the switch to (1) “RUN” in order to control the unit from the cab control. 2. Turn the Glow and Manual start switch of the unit to “ROAD” -- diesel engine start--up (MGC) -- Optionnal. GLOW: preheat CRANK: start--up 15 FEATURES i TO DISPLAY UNIT DATA The unit data list can be scrolled through by pressing the UNIT DATA key. The list will advance by one with each key press; or, press the UNIT DATA key once and use the UP or DOWN ARROW keys to scroll through the list more quickly. Press the ENTER key to display the data for 30 seconds. UNIT DATA CODE ENGLISH CD1 SUCT Suction pressure DATA CD2 ENG Engine hours CD3 WT CD4 1 RA Compartment 1 -- Return air temperature CD6 2 DT Compartment 2 -- Defrost thermistor sensor CD7 3 DT Compartment 3 -- Defrost thermistor sensor CD8 1 DTS Compartment 1 -- Defrost thermistor sensor Engine temperature CD9 CDT Compressor discharge temperature CD10 BATT Battery voltage Standby hours CD11 SBY CD12 MOD V Future expansion CD13 REV Software revision CD14 SERL Serial number low CD15 SERU Serial number upper CD16 2RA Compartment 2 -- Return air temperature CD17 3RA Compartment 3 -- Return air temperature CD18 MHR1 Maintenance hour meter 1 CD19 MHR2 Maintenance hour meter 2 CD20 SON 16 Switch on hour meter FEATURES G B TO CHANGE A FUNCTION 1. Press the FUNCTION CHANGE key until the function you want to change appears on the display. 2. Press ENTER. 3. Press the UP or DOWN ARROW key until the function setting you want appear on the display. 4. Press ENTER. FUNCTION PARAMETERS CODE ENGLISH AVAILABLE SELECTIONS FN0 DEFR FN1 ON CITY SPEED Defrost interval 1.5, 3, 6, or 12 hr Low speed only FN1 OFF HIGH SPEED Low and High speed FN2 OFF T Minimum off-time 10,20, 30, 45 or 90 mn FN3 ON T On-time 4 or 7 min. FN4 Degrees EC or EF FN5 ON TIME STRT Temperature Unit (EC or EF) Maximum Off-time 30 min* Desactivate FN2 FN5 OFF TEMP STRT Minimum time 10, 20, 30, 45, 90 min FN6 MOP STD Future expansion Reactivate FN2 FN7 ON AUTO OP Auto start operation FN7 OFF MAN OP Manual start operation FN8 T RANGE Out of range (A=2EC / B= 3EC/ C=4EC) CODES or ENGLISH NORMAL GLOW OVERRIDE Code or English display format Normal of add 30 seconds ALARM CLR No alarm active ALARM RST Alarm reset required * From EPROM 4.05 version -- see WARNING here after 17 FEATURES AUTOMATIC START UP IN DIESEL WHEN LOSS OF STANDBY FROM EPROM 4.05 To activate this function: TIME STRT set up in functionnal parameters. When the unit is started in standby, the “ROAD” light is flashing and the “STANDBY” light is lit. After 5 minutes of loss of power, the unit automatically starts in diesel. 5 minutes after the power comes back, the unit starts again automatically in electric mode. The “STANDBY MOTOR” alarm appears, alarm that you would have to clear. * This function will be active even after a stop (OFF) of the unit. To deactivate it: set up TEMP STRT in functionnal parameters. DEACTIVATE THIS FUNCTION WHEN UNIT IS RUNNING IN A CLOSED AREA ! 18 FEATURES G B CONTROL PANEL (OPTION) User-friendly indicator and operator control panels clearly show individual compartment temperatures with easy-to-read displays. These compact panels can be mounted to suit the individual operator’s preferences. (Example: on the front bulkhead, in the cab or in the refrigerated compartment -- including mounting in the truck wall itself.) Control panel 9. 8. 7. 1. 6. 2. 3. 1. Compartment ON/OFF key 2. Control panel power on 3. Unit ON/OFF key 4. Manual defrost key 5. Control panel locking 6. Up and down arrow keys 4. 5. 7. Heating operating mode light of a compartment 8. Cooling operating mode light of a compartment 9. Temperature indicated in EC or EF 19 FEATURES From this control panel (option) you can: switch on the unit; check compartement 1, 2 or 3 temperatures; change setpoints; energize a manual defrost. 20 PRETRIP INSPECTION The pre--trip inspection should be performed before picking up any load. This inspection is essential to anticipate and help minimize the possibility of “over--the--road” problems. These checks take only a few minutes. 1. Place the unit’s main switch in the STOP (0) position. 2. Fuel -- Drain any water and impurities from the sump of the refrigeration unit fuel tank by opening the drain--cock located on the bottom of the tank (if so equipped). Close the valve when only pure fuel emerges. Check the fuel level in the tank, ensuring that the fuel supply is adequate for unit operation. Refuel if necessary. 3. Belts -- Check the belt tension by depressing the belt with your thumb, near the center of the longest free run of each belt. Under moderate pressure each belt should deflect approximately 6 mm to 13 mm (1/4 inch to 1/2 inch). If the belts deflect more than this they should be tightened (loose belts may slip, generating heat and reducing belt life). If the belts are too tight they should be loosened; tight belts can reduce bearing life. 4. Battery -- On unit equipped with serviceable batteries, the level of the electrolyte in each of the cells should be checked. If the level is low, distilled water should be added to the correct level. Most units, however, are equipped with low or no--maintenance batteries. Check battery connections and battery supports. 21 G B PRETRIP INSPECTION 5. Engine Oil -- The engine oil should be checked last since it is necessary for oil to drain out of the block and into the oil pan to obtain a correct reading. Remove the plug/dip--stick (1), wipe it off and re--insert it fully into the engine block. Once again, remove the dip--stick and observe the oil level; it should be somewhere between the full and add marks. If it is below the add mark, add oil until the level is correct. 1 6. Over--all Unit inspection -- Visually inspect the entire unit for leaks, loose bolts, frayed, loose, or broken wires, etc. The radiator and condenser coils of the unit should be free of dirt, bugs, cardboard, or any other debris that may obstruct airflow across the coils. The evaporator (located inside the body) should be free of debris also, especially shrink--wrap, which is often used during transport to prevent cargo shifting. 7. Truck body -- The body should be inspected prior to loading. Check the door and vent seals for damage and wear. Inspect the entire interior and exterior of the body to detect any damage including in the inner and outer skins of the body. Damage to the insulation may compromise the unit’s ability to maintain the product temperature by increasing the amount of heat gain across the truck body. 22 UNIT OPERATION STARTING THE UNIT Complete the pre-trip inspection described in the previous section. : Road operation 2. 1. 3. 1. Place the RUN/STOP switch (O/I) to the RUN position (I). 2. Press the ROAD operation key (only if the unit has been previously used in standby mode). 3. Place either one, two or three compartments OFF/ON switches to ON (I). 4. Then, the unit will: perform a complete diagnostic check on the microprocessor controller; pre-heat for the required amount of time based on the engine temperature; starts automatically. 23 G B UNIT OPERATION : On Standby 1. 2. 3. Be certain that the unit is connected to an appropriate power source. 1. Place the RUN/STOP switch (O/I) to the RUN position (I). 2. Press the STANDBY operation key. 3. Place either one, two or three compartments OFF/ON switches to ON (I). 4. Then, the unit will begin to run on electric power. 24 UNIT OPERATION CHANGING THE SETPOINT G B The sequence is the same for each compartment. 2. 1. Start the unit. 2. When the setpoint box temperature is displayed, press the UP or DOWN ARROW key to change the temperature setpoint. STOP THE UNIT 2. 1. 1. Place C1, C2 and C3 switches to the OFF position (O). 2. Place the RUN/STOP switch (O/I) to the OFF (O) position. To shut down the unit, ALWAYS use the cab command or the general switch (RS) located on the control box. 25 UNIT OPERATION OPERATION WITH AUXILIARY CONTROL PANEL (OPTION) 1. Start the unit as mentioned before. 3. 2. 2. Press the SYSTEM ON/OFF key. Power light will go ON. 3. Press the ON/OFF key to energize selected compartment. 4. DISPLAY waiting for communication with unit compartment temperature display setpoint temperature display evaporator status (heat or cool or null) compartment shut-down via remote control defrost compartment temperature sensor malfunction 26 UNIT OPERATION CHANGE SETPOINT Setpoint change can be made from control panel or cab control. 1. 1. Press the UP or DOWN ARROW key to increase or decrease setpoint. This is the same operation for each compartment. LOCK THE CONTROL PANEL 2. 1. 1. Press the CARRIER logo 1 s. 2. The indicator comes on. 27 G B UNIT OPERATION UNLOCK THE CONTROL PANEL 2. 1. 1. Press the CARRIER logo for about 10 s. 2. The indicator goes off. REMARK It is not necessary for the compartment to be running in order to modify or see the setpoint value and the temperature of the compartment. The unit can be shut down both with the cab command and the general switch. 28 PRODUCT LOADING Proper air circulation in the truck body, air that can move around and through the load, is a critical element in maintaining product quality during transport. If air cannot circulate completely around the load, hot spots or top--freeze can occur. The use of pallets is highly recommended. Pallets, when loaded so air can flow freely through the pallets to return to the evaporator, help protect the product from heat passing through the floor of the truck. When using pallets, it is important to refrain from stacking extra boxes on the floor at the rear of the truck, because this will cut off the airflow. Product stacking is another important factor in protecting the product. Products that generate heat, fruits and vegetables for example, should be stacked so the air can flow through the product to remove the heat; this is called “air stacking” the product. Products that do not create heat, meats and frozen products, should be stacked tightly in the center of the truck. All products should be kept away from the sidewalls of the body, allowing air to flow between the body and the load; this prevents heat filtering through the walls from affecting the product. It is important to check the temperature of the product being loaded to ensure that it is at the correct temperature for transport. The refrigeration unit is designed to maintain the temperature of the product at the temperature at which it was loaded; it was not designed to cool a warm product. 29 G B PRODUCT LOADING OPTIONS FOR INSULATED BODIES - Mobile partition The mobile partition must be placed at a minimum distance from the evaporator of 1 m for: MTS700 / MTS1100 / MTS1450 / MTS2200. - Ducting of evaporator air outlet Ventilation ducts must never be covered. SOME ADVICE Before loading - Pre--cool the inside of the insulated body by lowering the temperature for about 15 minutes. - Evacuate the humidity existing inside the box by carrying out a manual defrost. This can only take place when enabled by the defrost thermostat (box temperature lower than 3EC during pulldown and 8EC during heating). - Evaporator fans are protected by safety grills. In the event of heavy duty use of the unit, ice can accumulate on the grills. It is therefore recommended to clean them regularly by means of a small brush. The operation MUST be done when the unit has been SHUT DOWN. 30 PRODUCT LOADING When loading G B - To be carried out with the unit stopped. - It is recommended to open doors as little as possible to avoid the intake of hot air and humidity. - Select the temperature by means of the thermostat, according to the transported goods. - Check the internal temperature of the goods being loaded (using a probe thermometer). - Take care not to obstruct the air intakes on the evaporator section and the ventilation ducts. Load spacers Load on pallets - Leave a free space of about: 6 to 8 cm between load and frontwall, 20 cm between the top of the load and the roof, between the floor and the load (gratings, pallets). - Do not forget to close the doors. - Before closing the doors, check your load once more and see that nobody is shut inside the box. 31 PRODUCT LOADING NOTE: For stationnary utilization, we recommend to place the body in the shade. IMPORTANT Never leave your unit more than a month without running. 32 RECOMMENDED TRANSPORT TEMPERATURES Below are some general recommendations on product transport temperatures and operating modes for the unit. These are included for reference only and should not be considered pre--emptive of the set--point required by the shipper or receiver. More detailed information can be obtained from your Carrier Transicold dealer. Product Bananas Set--point Range Operating mode* 15EC 60EF Continuous EC to +6EC EF to +43EF Continuous EC EF Auto--Start/Stop or continuous +2EC to +6EC +36EF to +43EF Auto--Start/Stop or continuous Ice --20EC 15EF to 20EF Auto--Start/Stop Frozen fruits and vegetables --18EC 0EF Auto--Start/Stop Frozen meats and seafood --20EC --10EF to 0EF Auto--Start/Stop Ice cream --25EC --20EF Auto--Start/Stop Fresh fruits and vegetables Fresh meats and seefood Dairy Products * During delivery cycles that include frequent stops and door openings, it is recommended that the unit always be operated in the continuous run mode to help insure product quality. It is essential to shut down the compartment during the periods when the doors are open, in order to maintain the temperature of the cargo in the other compartments and keep the unit operating correctly. To do so, the main O/I switch (O: stop/I: start) should be switched to O). 33 G B PROBLEMS Everything possible has been done to ensure that your unit is the most reliable, trouble--free equipment available on the market today. If, however, you run into problems, the following section may be of assistance. If you do not find the trouble that you have experienced listed below, please call your Carrier Transicold dealer for assistance. General Problems UNIT WON’T CRANK, BY THE STARTER CHECK BATTERY CONDITION. CHECK BATTERY CONNECTIONS. CHECK ALL FUSES. UNIT WON’T START CHECK FUEL LEVEL. CHECK ALL FUSES. UNIT WON’T RUN CHECK FUEL LEVEL. CHECK ENGINE OIL LEVEL. CHECK ALL FUSES. UNIT DIES CHECK BELTS. CHECK ENGINE OIL LEVEL. CHECK COOLANT LEVEL. CHECK FUEL LEVEL. CHECK ALL FUSES. UNIT NOT COOLING PROPERLY DEFROST UNIT. CHECK EVAPORATOR FOR AIRFLOW RESTRICTION. CHECK CONDENSER FOR AIRFLOW RESTRICTION. CHECK BODY FOR DAMAGE OR AIR LEAKS. 34 PROBLEMS FAULT ALARM DISPLAY AND SAFETY FEATURES Display will alternate between an alarm message and the normal display whenever any of the failures listed below occur. NOTE: Whenever the fault light is on, check display for fault message. -- Reset the micro to start the unit. -- Press FUNCTION CHANGE key. -- Press the UP/DOWN ARROW keys until ALARM RST is displayed. -- Press enter to clear alarm. Alarm CLR will now be displayed and unit will restart. Other method to reset: move RUN/STOP switch to STOP. Unit resets and will start when RUN/STOP switch is moved to run position. ALARM DISPLAY °= FAULT LIGHT ON CODE ENGLISH DESCRIPTION AL0 ENG OIL ° Low Oil Pressure AL1 ENG HOT ° High coolant Temperature AL2 HI PRESS ° High Discharge Pressure AL3 START FAIL ° Start failure AL4 LOW BATT ° Low battery voltage AL5 HI BATT ° High battery voltage AL6 DEFRFAIL AL7 ALT AUX (°) No Alternator Auxiliary Output AL8 STARTER ° Starter Motor Fault AL9 1RA SENSOR ° Return Air Sensor Compartment 1 Fault AL10 2RA SENSOR ° Return Air Sensor Compartment 2 Fault AL11 WT SENSOR Coolant temperature sensor Defrost Override 35 G B PROBLEMS ALARM DISPLAY °= FAULT LIGHT ON CODE ENGLISH AL12 HIGH CDT ° High discharge temperature DESCRIPTION AL13 CD SENSOR Discharge temperature sensor AL14 SBY MOTOR ° Standby motor overload AL15 FUSE BAD AL16 3RA SENSOR AL17 DISPLAY AL18 SERVICE 1 Maintenance Hour meter 1 AL19 SERVICE 2 Maintenance Hour meter 2 AL20 1RA OUT ° Compartment 1 Out-of-Range AL21 2RA OUT ° Compartment 2 Out-of-Range AL22 3RA OUT ° Compartment 3 Out-of-Range AL23 NO POWER ° Fuse open ° Return Air Sensor Compartment 3 Fault Display No power supply ° = fault light ON WARNING : AL0 (ENG OIL) could come up if alternator is badly connected. 36 PROBLEMS FUSES The fuses which protect the circuits of the control system are located in the box on the left-hand side of the unit. The fuses are accessed by loosening the screws that hold the control panel closed. : Old model 37 G B PROBLEMS Rep. F1 F2 F3 F4 F5 F6 F7 F8 F9 F11 38 FUSE IDENTIFICATION Item General Controller MP Run fuse Speed control solenoid Hot gas valve Fuel heater (option) Compartment 1 Compartment 2 Compartment 3 Flashing relay Amps 80 A 5A 25 A 15 A 7.5 A 25 A 10 A 10 A 10 A 5A PROBLEMS : Rep. F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 New model FUSE IDENTIFICATION Item General fuse Controller microprocessor fuse Run fuse Main heat valve fuse Speed control solenoid fuse Unloader fuse Liquid solenoid valve fuse (comp. 1) Liquid solenoid valve fuse (comp. 2) Liquid solenoid valve fuse (comp. 3) Fuel pump fuse Hot gas valve fuse (comp. 1) Hot gas valve fuse (comp. 2) Hot gas valve fuse (comp. 3) G B Amps 60 A 5A 15 A 5A 10 A 3A 3A 3A 3A 5A 10 A 10 A 10 A 39 UNIT MAINTENANCE Engine oil -- the oils recommended for use in your refrigeration unit must comply with the American Petroleum Institute’s (API) SG/CD rating. The use of any oil that does not meet this rating may affect the warranty on the engine in the unit. The use of oil of the proper weight (viscosity) is also essential. The following chart indicates the SAE Weight Rating of the oil to be used in various climates: EF 30 W or 15W40 20 W or 15W40 10 W or 10W30 EC 40 UNIT MAINTENANCE The following oils are accepted for use in Europe with these units. RECOMMENDED OILS CARRIER AGIP ANTAR BP ELF FIAT FINA HAFA IGOL IMPERATOR LABO MOBIL OPAL ORLY POLAROIL RENAULT TEXACO TOTAL SHELL UNIL YACCO CARRIER TD+15W- 40 SIGMA TURBO SHPD 15W--40 GRAPHITE R 15W--40 VANELLUS C3 EXTRA 15W--40 VANELLUS FE 15W30 MULTIPERFORMANCE4D 15W--40 PERFORMANCE TROPHY 15W--40 URANIA TURBO 15W--40 KAPPA LDO 15W--40 KAPPA TD PLUS 15W--40 KAPPA EXTRA 15W--40 DETERGENTE 4DM 15W--40 STRADEX 900 ECO 15W--40 SYNTHIDEX ECO 15W--40 RALLYE TURBO 4E 15W--40 RALLYE TURBO 4E LD 15W--40 RAFF SUPER HPDO 15W--40 MEGAMAXI 15W--40 DELVAC SHC 15W--40 DELVAC 1400 SUPER OPALGET D 500 15W--40 TURBO 2002 15W--40 POLATRUCK 15W--40 KMX 2 PLUS 15W--30 KMX 2 PLUS 15W--40 MV5 “EUROPE” URSA SUPER TD 15W--40 RUBIA TIR MAX 15W40 MYRINA TX 15W--40 MYRINA T 15W--30 SUPER ROC 3D 15W--40 TURBO DX 15W--40 SM 4D + 15W--40 The above oil equivalents are based on the recommendations contained in the suppliers’s technical literature. 41 G B UNIT MAINTENANCE UNIT MAINTENANCE SCHEDULES For the most reliable operation and for maximum life, your unit requires regular maintenance. This includes oil and filter changes, fuel and air filter replacement, coolant replacement, belts etc. Genesis R70/R80 Required R i d service Genesis R90 Hours With bypass oil filter (option) Hours Remote oil filter Hours A 250 A 250 A 250 AB 1000 AB 1250 AB 1250 A 1750 ABC 2250 ABC 2250 ABC 2500 AB 3250 AB 3250 A 3250 ABD 4250 ABD 4250 ABD 4000 ABC 5250 ABC 5250 A 4750 AB 6250 AB 6250 ABC 5500 AB 7250 AB 7250 A 6250 ABCD 8250 ABCD 8250 AB 7000 AB 9250 AB 9250 AD 7750 AB 10250 AB 10250 Without bypass oil filter In addition to the above service requirements, please adhere to the following: The engine oil should be changed at least once per year, even if the engine has not run the necessary number of hours.The coolant (anti-freeze) should be replaced after a maximum of two years. 42 UNIT MAINTENANCE DESCRIPTION OF MAINTENANCE OPERATIONS G B Service Operations SERVICE A : : : : : : : SERVICE B : : : : : : : : : : SERVICE C SERVICE D : : : : : : : Drain the engine oil, replace oil filter Check engine cooling system Clean the cartridge of the dry air filter Check air cleaner and change air cleaner oil Check all bolts, screws and unit mounting bolts for tightness. Tighten as required (1st service only) Check all belts Check engine speed under load Replace fuel filter Check fuel pump filter Replace the cartridge of the dry air filter Check the battery terminals and fluid level Check compressor oil level Check alternator brushes Check engine thermostat for proper operation Check defrost: Check timer setting and function Check refrigerant control valves for proper operation Fans stop Defrost ends automatically Water drains from evaporator Check and adjust rocker arms Replace belts as necessary Clean radiator and condenser Check refrigerant level Check and rebuild the alternator Clean and adjust fuel injectors (140 kg/cm2) Check all belt tension pulleys Change anti--freeze in diesel engine Check bearings in clutch(es) and electric motors 43 UNIT MAINTENANCE BELTS GENESIS R70 Alternator 12VDC Water pump 2. Electric motor 3. 5. 4. Diesel engine Compressor 1. Generator Quantity 44 1. Engine to compressor v-belt 2 2. Alternator v-belt 1 3. Electric motor to compressor v-belt 1 4. Engine to water pump 1 5. Electric motor to generator 1 UNIT MAINTENANCE GENESIS R80 G B Alternator 12VDC Water pump Electric motor 3. 5. 4. Compressor Diesel engine 1. Generator Quantity 1. Engine to compressor v-belt 1 2. Alternator v-belt 0 3. Electric motor to compressor v-belt 1 4. Engine to water pump 1 5. Electric motor to generator 1 45 UNIT MAINTENANCE GENESIS R90 Alternator 12VDC Water pump Electric motor 3. 5. 4. Compressor Diesel engine 1. Generator Quantity 46 1. Engine to compressor v-belt 2 2. Alternator v-belt 0 3. Electric motor to compressor v-belt 2 4. Engine to water pump 1 5. Electric motor to generator 1 UNIT MAINTENANCE Too little belt tension cause slippage and excessive belt wear. Too much tension shortens belt and bearing life. Belt deflection should be equal to belt thickness. Properly adjusted belts give long lasting and efficient service (refer to maintenance schedule). Important: During intervention on twin mounted belts, replace IMPERATIVELY both belts and make sure they are both in the same package. 47 G B UNIT MAINTENANCE FILTERS 3. 1. 2. 1. Diesel fuel filter 2. Oil filter 3. Air filter, dry type For code numbers consult the corresponding spare parts manual. 48 STANDBY OPERATION GUIDELINES For safe, reliable operation in Standby mode, it is important to consider the following guidelines: - Never plug the unit in to the power source with the main switch in the RUN position. The main switch should always be in the STOP position when connecting the unit to the power source. - The fusing and extension cable used for Standby operation should conform to the following: Unit Fuse 200/240/3/50 Hz 220/256/3/60 Hz Fuse 350/415/3/50 Hz 380/460/3/60 Hz Standardized extension cable H.07.RNF 220 volts 380 volts Genesis R70 23 A 13 A 4 x 6 mm2 4 x 6 mm2 Genesis R80 23 A 13 A 4 x 6 mm2 4 x 6 mm2 Genesis R90 40 A 29 A 4 x 6 mm2 4 x 6 mm2 - The unit connection cable must be fitted with a ground connection. The cable must be connected to earth. - On the 380 V supply, it is recommended to use a differential protection on each plug. - When performing service and/or maintenance procedures on a refrigeration unit, make certain that the unit is disconnected from the power source and that the main unit switch is turned OFF. - Operations on the 380 V supply for the unit must only be carried out by authorized personnel. - Warning: changing the operation of a unit from 380 V to 220 V implies a change in the electrical coupling, adjustment of the overload relay and for certain unit models, the replacement of some components. Please consult our technical service. 49 G B MANUFACTURER INFORMATION WARRANTY As soon as you receive your warranty card, please keep it in a safe place. The card will be requested for any intervention under warranty which needs to be performed on your equipment. Always update the service chart which is to be found inside the front cover. This manual refers to the standard model. Some options may not appear in it, and in such cases you are requested to consult our Technical Services. Carrier Transicold constantly seeks to improve the quality of its products and therefore reserve the right to modify them without prior notice. INSTALLATION During assembly and routine service operations, access to the unit may involve certain risks. TAKE EVERY SAFETY MEASURE TO ACCESS THE UNIT (e.g.: standard ladders, running board with railing, safety belt etc.) Installation of this unit requires no special knowledge of refrigeration. To fit the nosemount unit to the vehicle body, it is necessary only to slide the evaporator section into the opening in the front panel and secure using the bolts provided. Advice When handling, use suitable lifting gear attached to the lifting points provided for this purpose on the unit. Note: The unit should not protude out of the body. BATTERY Maintenance: Never leave a unit more than a month without running. In case of long standstill, charge the battery independently. 50 MANUFACTURER INFORMATION Before performing any welding on the chassis, take care to disconnect the battery of the vehicle and the 12VDC and 3 phase alternator, and any other electronic system. Never try to start the vehicle with a booster because this could damage the electronic components in the unit or on the vehicle. 1. Check that all mounting bolts are well tightened and suitable for use. 2. When you drill holes in the unit or in the body of the vehicle, be careful not to pierce the refrigeration tubes or the electrical wiring. 3. When you are working next to the unit (condenser and evaporator) be careful not to cut yourself on the sharp edges. 4. When the unit is running, keep your hands away from belts and fan motors. 5. Never close the discharge valves of the compressor when the unit is running. 6. In case of repair, only use manometer by--pass hoses which are in a good condition and avoid their contact with belts, pulley and fan motor. 7. The refrigerant liquid must be handled with great care. 8. Next to a flame the refrigerant liquid gives off a phosgene gas which has an unpleasant smell and irritates the lungs. 9. Never heat up a closed cooling circuit with a flame, the cooling system must be handled with great care. 10. When liquid refrigerant is in contact with the atmosphere, it evaporates and freezes everything it makes contact with. 51 G B MANUFACTURER INFORMATION First aid in case of frost--bite: a) Cover up the frost--bitten part. b) Warm up quickly the frost--bitten part by dipping it into lukewarm water (not hot). c) In case you do not have water wrap the wounded place in a clean cloth. d) If refrigerant fluid has been splashed into your eyes, rinse them immediately with clean water; as a precaution, you are recommended to have a medical examination as well. 11. Cooling oil Synthetic or derived from fuel - Avoid contact with skin. - Wash carefully after handling. REMARKS ABOUT SAFETY: Diesel engine NEVER START THE ENGINE IN A CLOSED ROOM, THE EXHAUST GAS IS POISONOUS. It is colourless and adourless and created by incomplete combustion of hydrocarbons. Exhaust gas is poisonous; breathing it in induces drowsiness and may lead to loss of consciousness. The following symptons indicate an exhaust gas inhalation: - Blackout - Intense headache - Sudden weakness and sleepiness - Vomiting - Muscular contractions - Beating temples 52 MANUFACTURER INFORMATION If you feel one of the above mentioned symptoms, go out and breathe fresh air. The maintenance operation should be done at the recommended intervals on your equipment. Check the exhaust gas system to avoid gas inhalation. If you notice a noise or modification of the exhaust system stop immediately the engine and call sales service center for checking and repair. Standby and start/stop: The unit will start automatically, keep away from belts, pulleys and fans. 53 G B “A.T.P. EUROPE” REGULATION EXTRACT (Date: March 1974) Approval of vehicles intended for the carriage of perishable goods. Before putting a refrigerated vehicle into service, it is necessary to have it approved by the Regional Health Department. CHARACTERISTICS OF VEHICLES USED FOR CARRYING PERISHABLE GOODS; REFRIGERATION UNIT. The refrigeration unit is an insulated unit with a cooling system which makes it possible, with a mean outside temperature of +30EC, to lower the temperature inside the empty body and to maintain this low temperature in the following way: CLASS A Refrigeration unit furnished with a cooling system whereby a temperature between +12EC and 0EC inclusive can be chosen. CLASS B Refrigeration unit furnished with a cooling system whereby a temperature between +12EC and --10EC inclusive can be chosen. CLASS C Refrigeration unit furnished with a cooling system whereby a temperature between +12EC and --20EC inclusive can be chosen. The cooling capacity of a unit is determined by a test carried out in one of the approved testing stations and ratified by an official report. Note: The “K“ factor of bodies intended to be classified as C must be equal to or lower than 0.4 W/m2 EC. 54 “A.T.P. EUROPE” REGULATION EXTRACT G B SIGNS, IDENTIFICATION MARKS AND PLATES TO BE ATTACHED TO REFRIGERATION UNITS Refrigeration Plate This reference must be followed by identification marks according to the following list: Standard refrigeration unit Class A FNA Reinforced refrigeration unit Class A FRA Reinforced refrigeration unit Class B FRB Reinforced refrigeration unit Class C FRC In addition to the above identification marks, the date (month and year) of expiry of the approval certificate must be indicated. Example: FRC 6--2000 (6 = month (June) 2000 = year) Very important Regularly check the expiry date of the approval certificate. During transport, the approval certificate or provisional certificate should be shown on request of qualified agents. To have an insulated unit approved as a refrigeration unit, an application to modify the approval certificate should be sent to the regional health office. 55 EMERGENCY ROAD SERVICE At Carrier Transicold we’re working hard to give you complete service when and where you need it. That implies a worldwide network of dealers and available an emergency service. These service centers are manned by factory--trained service personnel and backed by extensive parts inventories that will assure you of prompt repair. Should you encounter a unit problem with your refrigeration unit during transit, follow your company’s emergency procedure or contact the nearest Carrier Transicold service center. Consult the directory to locate the service center nearest you. This directory may be obtained from your Carrier Transicold dealer. If you are unable to reach a service center, call Carrier Transicold’s 24 Hour Assistance: In Europe, please use the following free phone numbers from: A B CH D DK E F FIN GB GR H I IRL L RUS N NL P PL S 56 AUSTRIA BELGIUM SWITZERLAND GERMANY DENMARK SPAIN FRANCE FINLAND GREAT BRITAIN GREECE HUNGARY ITALY IRELAND LUXEMBURG RUSSIA NORWAY THE NETHERLANDS PORTUGAL POLAND SWEDEN 0800 291039 0800 99310 0800 838839 0800 1808180 808 81832 900 993213 0800 913148 0800 113221 0800 9179067 00800 3222523 00800 13526 800 791033 1800 553286 0800 3581 810 800 200 31032 800 11435 0800 0224894 8008 32283 00800 3211238 020 790470 EMERGENCY ROAD SERVICE From other countries: +32 9 255 67 89 G B Direct: +32 9 255 67 89 In Canada or United States, call 1 -- 800 -- 448 -- 1661. When calling, please have the following information ready for fastest service: - Your name, the name of your company, and your location. - A telephone number where you can be called back. - Refrigeration unit model number and serial number. - Box temperature, set--point and product. - Brief description of the problem you are having, and what you have already done to correct the problem. We will do everything we can to get your problem taken care of and get you back on the road. 57