GENESIS R70/R80/R90 OPERATOR`S MANUAL

advertisement
GENESIS R70/R80/R90
OPERATOR’S MANUAL
This guide has been prepared for the operator of Carrier Transicold
GENESIS R70/R80/R90 refrigeration units. It contains basic
instructions for the daily operation of the refrigeration unit as well as
safety information, trouble shooting tips, and other information that
will help you to deliver the load in the best possible condition. Please
take the time to read the information contained in this booklet and
refer to it when ever you have a question about the operation of your
Carrier Transicold GENESIS R70/R80/R90 units.
Your refrigeration unit has been engineered to provide long,
trouble--free performance when it is properly operated and
maintained. The checks outlined in this guide will help minimize
problems.
Maintenance program will also help to control operating costs,
increase the unit’s working life, and improve performance.
Carrier Transicold has an on--going product quality upgrade policy.
As a result, specifications are liable to change without notice.
4
CONTENTS
Page
UNIT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
PRETRIP INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
UNIT OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
Starting the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation with auxiliary control panel (option) . . . . . . . . .
Change setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lock the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unlock the control panel . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
25
25
26
27
27
28
PRODUCT LOADING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
RECOMMENDED TRANSPORT TEMPERATURES . . . . . .
33
PROBLEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
UNIT MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40
Unit maintenance schedules . . . . . . . . . . . . . . . . . . . . . . . .
Description of maintenance operations . . . . . . . . . . . . . . .
Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
43
44
48
STANDBY OPERATION GUIDELINES . . . . . . . . . . . . . . . . . .
49
MANUFACTURER INFORMATION . . . . . . . . . . . . . . . . . . . . .
50
“A.T.P. EUROPE” REGULATION EXTRACT . . . . . . . . . . . . .
54
EMERGENCY ROAD SERVICE . . . . . . . . . . . . . . . . . . . . . . . .
56
5
G
B
UNIT IDENTIFICATION
CONDENSER
The nameplate identifies:
: serial number
: refrigerant charge and quantity
: date in service
* gives you all the information when calling 24 hour Assistance.
6
UNIT IDENTIFICATION
EVAPORATORS
G
B
MTD 2200 model (dual discharge)
MTS 700 model (single discharge)
7
SAFETY
Your Carrier Transicold refrigeration unit has been designed with the
safety of the operator in mind. During normal operation, all moving
parts are fully enclosed to help prevent injury. During all pre--trip
inspections, daily inspections, and problem troubleshooting, you
may be exposed to moving parts; please stay clear of these moving
parts when the unit is in operation and when the main power switch
is in the Run (On) position.
The evaporator and condenser are made of finned tubes. The fins
can cause injury on contact with skin. It is recommended to wear
protective gloves during all handling operations.
During operation, certain components such as the exhaust pipe,
discharge outlet, and cooling circuit radiator can become extremely
hot. During routine service operations, wear protective gloves.
AUTO-- START/STOP
Your refrigeration unit is equipped with Auto-Start/Stop, a valuable
fuel saving feature. When the unit is set for Auto-Start/Stop
operation it may start at any time. When performing any check of
the refrigeration unit (e.g., checking the belts, checking the oil),
make certain that the main power switch is in the OFF (0) position.
ENGINE COOLANT
The engine, as with all diesel engines, is equipped with a
pressurized cooling system. Under normal operating conditions, the
coolant in the engine and radiator is under high pressure and is very
hot. Contact with hot coolant can cause severe burns. Do not
remove the cap from a hot radiator; if the cap must be removed, do
so very slowly in order to release the pressure without spraying.
REFRIGERANTS
The refrigerant contained in the refrigeration system of your unit can
cause frostbite, severe burns, or blindness when in direct contact
with the skin or eyes. For this reason, and because of legislation
regarding the handling of refrigerants during system service,
whenever your unit requires service of the refrigeration system, we
recommend that you contact your nearest Carrier Transicold
authorized repair facility for service.
8
SAFETY
BATTERY
This unit is equipped with a lead--acid type battery. The battery
normally vents small amounts of flammable hydrogen gas. Keep
any flame, any lighted object (cigarette etc.) or any source of sparks
away from the battery elements. A battery explosion can cause
serious physical harm and/or blindness.
AUTOMATIC START UP IN DIESEL
WHEN LOSS OF STANDBY
FROM EPROM 4.05
To activate this function: TIME STRT set up in functionnal
parameters.
When the unit is started in standby, the “ROAD” light is flashing
and the “STANDBY” light is lit.
After 5 minutes of loss of power, the unit automatically
starts in diesel. 5 minutes after the power comes back, the unit
starts again automatically in electric mode. The “STANDBY
MOTOR” alarm appears, alarm that you would have to clear.
* This function will be active even after a stop (OFF) of the unit.
To deactivate it: set up TEMP STRT in functionnal parameters.
DEACTIVATE THIS FUNCTION WHEN UNIT IS
RUNNING IN A CLOSED AREA !
9
G
B
FEATURES
This refrigeration unit is equipped with a wide range of features that
are designed to improve reliability and temperature control within
the body.
The group can be delivered fitted with a microprocessor controller.
MICROPROCESSOR CONTROLS
17.
1.
16.
2.
15.
3.
14.
4.
13.
5.
12.
11.
6.
7.
8.
9.
1. Display
2. Up and down arrow keys
3. Function change key
4. Run/Stop switch
5. Road key
6. Comp. 1 ON/OFF switch
7. City speed key
8. Comp. 2 ON/OFF switch
9. Manual defrost key
10
10.
10. Comp. 3 ON/OFF switch
11. Buzzer off key
12. Standby key
13. Pretrip key
14. Auto-start/Stop key
15. Unit data key
16. Fault alarm led
17. Enter key
FEATURES
The microprocessor controls incorporated into this unit are the most
reliable control system available. It is also designed to be the easiest
to use, offering great flexibility in control, yet minimal user input for
normal operation: a true “set it and forget it” design.
1. Display window: shows set--point, box temperature, operating
mode, alarm displays, as well as data on the unit itself (battery
voltage, water temperature etc.).
Function Change key
The function change key is used to display the
operating parameters. Each time this key is pressed
the display will advance to the next parameter. This
key, in conjunction with the up/down arrow and enter
keys, will allow the user to change the parameters.
Arrows key
The UP ARROW and DOWN ARROW keys are
used to alter the set--point. Press the up or down
arrow keys until the desired setpoint is displayed on
the left--hand side of the display window. When the
correct set--point is displayed, press the ENTER key
to confirm the setting.
The UP ARROW and DOWN ARROW keys are also
used to change the unit functions and scroll through
the FUNCTION and UNIT DATA screens.
Enter key
The ENTER key confirms changes made to unit
operation. It must be pressed to change the setpoint
after using the arrow keys to adjust it. If the ENTER
key is not pressed, the setpoint will revert to the
previously entered setting.
The ENTER key must also be pressed whenever a
FUNCTION setting is being altered. If this key is not
pressed, the function will revert to its previous
setting.
11
G
B
FEATURES
RUN/STOP switch
The main unit RUN/STOP switch controls the unit
operation. When switched to the Run (I) position, the
unit will start in the operating mode last entered
(Road or Standby). The set--point will be at the last
set--point entered on the keypad.
Road key
The ROAD key puts the unit into Road (or engine)
operation when the unit has been previously
operated in the Standby mode.
City Speed key
The CITY SPEED key toggles the unit between high
speed and low speed (diesel mode). When City
Speed is selected, the unit will run only in low speed
except during defrost cycles. This feature is useful in
areas where noise is restricted.
Manual defrost key
The MANUAL DEFROST key places the unit in a
defrost cycle. Under most conditions it is not
necessary to defrost the unit manually as this is done
automatically with the air switch or the defrost timer.
Manual defrost may become necessary due to ice
accumulated on the evaporator coil during frequent
door openings in humid environments.
Buzzer Off key
The BUZZER OFF key temporarily turns off the
FAULT ALARM buzzer. The red light “Fault alarm”
remains illuminated on the command cab.
12
FEATURES
Standby key
The STANDBY key places the unit in Standby (or
electric) mode when the previous mode of operation
has been Road.
Pretrip Check key
The PRETRIP key initiates a check of all normal
operating modes. The temperature inside the box
must be below 5EC p 1EC (35EF p 2EF) to start this
check. Upon initiation, the unit will cycle through all
operating modes at 30 second intervals. The display
will show “PPPP” at the beginning and will show
various unit data during the pre--trip cycle. Upon
completion of the pre--trip cycle the unit will be
placed into the defrost mode.
Auto Start/Stop Continuous key
The AUTO--START/STOP key toggles the unit
operating mode between Auto--Start/Stop and
continuous run. When the unit is set for
Auto--Start/Stop operation, the unit will run until the
box temperature reaches set--point and then cycle
off (after the minimum run time has been met) until
further cooling or heating is necessary. When in the
continuous mode, the unit will cycle between heat
and cool as required to maintain the set temperature
in the body. If the setpoint is below -12EC (10EF) the
unit will not heat, it will run continuously in low speed
cool.
13
G
B
FEATURES
Unit Data key
i
This key scrolls the display through the various
operating condition displays, engine temperature or
battery voltage, for example. A more complete
description of the function is found later in this
chapter.
Compartment 1 ON/OFF switch
When switched to (I) the unit and compartment 1
will start in the operating mode last entered
(cooling or heating).
Compartment 2 ON/OFF switch
When switched to (I) the unit and compartment 2
will start in the operating mode last entered
(cooling or heating).
Compartment 3 ON/OFF switch
When switched to (I) the unit and compartment 3
will start in the operating mode last entered
(cooling or heating).
16. Fault Alarm led: illuminates when an alarm is detected.
14
FEATURES
OPTION
G
B
Important: If the cab control displays nothing, check the position
of the RUN switch located on the microprocessor box.
1
2
1. Main unit operation switch (RS)
Turn the switch to (1) “RUN” in order to control the unit from
the cab control.
2. Turn the Glow and Manual start switch of the unit to
“ROAD” -- diesel engine start--up (MGC) -- Optionnal.
GLOW: preheat
CRANK: start--up
15
FEATURES
i
TO DISPLAY UNIT DATA
The unit data list can be scrolled through by pressing the UNIT
DATA key. The list will advance by one with each key press; or, press
the UNIT DATA key once and use the UP or DOWN ARROW keys
to scroll through the list more quickly. Press the ENTER key to
display the data for 30 seconds.
UNIT DATA
CODE
ENGLISH
CD1
SUCT
Suction pressure
DATA
CD2
ENG
Engine hours
CD3
WT
CD4
1 RA
Compartment 1 -- Return air temperature
CD6
2 DT
Compartment 2 -- Defrost thermistor sensor
CD7
3 DT
Compartment 3 -- Defrost thermistor sensor
CD8
1 DTS
Compartment 1 -- Defrost thermistor sensor
Engine temperature
CD9
CDT
Compressor discharge temperature
CD10
BATT
Battery voltage
Standby hours
CD11
SBY
CD12
MOD V
Future expansion
CD13
REV
Software revision
CD14
SERL
Serial number low
CD15
SERU
Serial number upper
CD16
2RA
Compartment 2 -- Return air temperature
CD17
3RA
Compartment 3 -- Return air temperature
CD18
MHR1
Maintenance hour meter 1
CD19
MHR2
Maintenance hour meter 2
CD20
SON
16
Switch on hour meter
FEATURES
G
B
TO CHANGE A FUNCTION
1. Press the FUNCTION CHANGE key until the function you
want to change appears on the display.
2. Press ENTER.
3. Press the UP or DOWN ARROW key until the function
setting you want appear on the display.
4. Press ENTER.
FUNCTION PARAMETERS
CODE
ENGLISH
AVAILABLE SELECTIONS
FN0
DEFR
FN1 ON
CITY SPEED
Defrost interval 1.5, 3, 6, or 12 hr
Low speed only
FN1 OFF
HIGH SPEED
Low and High speed
FN2
OFF T
Minimum off-time 10,20, 30, 45 or 90 mn
FN3
ON T
On-time 4 or 7 min.
FN4
Degrees
EC or EF
FN5 ON
TIME STRT
Temperature Unit (EC or EF)
Maximum Off-time 30 min*
Desactivate FN2
FN5 OFF
TEMP STRT
Minimum time 10, 20, 30, 45, 90 min
FN6
MOP STD
Future expansion
Reactivate FN2
FN7 ON
AUTO OP
Auto start operation
FN7 OFF
MAN OP
Manual start operation
FN8
T RANGE
Out of range (A=2EC / B= 3EC/ C=4EC)
CODES or ENGLISH
NORMAL GLOW
OVERRIDE
Code or English display format
Normal of add 30 seconds
ALARM CLR
No alarm active
ALARM RST
Alarm reset required
* From EPROM 4.05 version -- see WARNING here after
17
FEATURES
AUTOMATIC START UP IN DIESEL
WHEN LOSS OF STANDBY
FROM EPROM 4.05
To activate this function: TIME STRT set up in functionnal
parameters.
When the unit is started in standby, the “ROAD” light is flashing
and the “STANDBY” light is lit.
After 5 minutes of loss of power, the unit automatically
starts in diesel. 5 minutes after the power comes back, the unit
starts again automatically in electric mode. The “STANDBY
MOTOR” alarm appears, alarm that you would have to clear.
* This function will be active even after a stop (OFF) of the unit.
To deactivate it: set up TEMP STRT in functionnal parameters.
DEACTIVATE THIS FUNCTION WHEN UNIT IS
RUNNING IN A CLOSED AREA !
18
FEATURES
G
B
CONTROL PANEL (OPTION)
User-friendly indicator and operator control panels clearly show
individual compartment temperatures with easy-to-read displays.
These compact panels can be mounted to suit the individual
operator’s preferences.
(Example: on the front bulkhead, in the cab or in the refrigerated
compartment -- including mounting in the truck wall itself.)
Control panel
9.
8.
7.
1.
6.
2.
3.
1. Compartment ON/OFF key
2. Control panel power on
3. Unit ON/OFF key
4. Manual defrost key
5. Control panel locking
6. Up and down arrow keys
4.
5.
7. Heating operating mode light of
a compartment
8. Cooling operating mode light of
a compartment
9. Temperature indicated in EC or
EF
19
FEATURES
From this control panel (option) you can:
switch on the unit;
check compartement 1, 2 or 3 temperatures;
change setpoints;
energize a manual defrost.
20
PRETRIP INSPECTION
The pre--trip inspection should be performed before picking up any
load. This inspection is essential to anticipate and help minimize the
possibility of “over--the--road” problems. These checks take only a
few minutes.
1. Place the unit’s main switch in the STOP (0) position.
2. Fuel -- Drain any water and impurities from the sump of the
refrigeration unit fuel tank by opening the drain--cock located
on the bottom of the tank (if so equipped). Close the valve
when only pure fuel emerges. Check the fuel level in the
tank, ensuring that the fuel supply is adequate for unit
operation. Refuel if necessary.
3. Belts -- Check the belt tension by depressing the belt with
your thumb, near the center of the longest free run of each
belt. Under moderate pressure each belt should deflect
approximately 6 mm to 13 mm (1/4 inch to 1/2 inch). If the
belts deflect more than this they should be tightened (loose
belts may slip, generating heat and reducing belt life). If the
belts are too tight they should be loosened; tight belts can
reduce bearing life.
4. Battery -- On unit equipped with serviceable batteries, the
level of the electrolyte in each of the cells should be
checked. If the level is low, distilled water should be added
to the correct level. Most units, however, are equipped with
low or no--maintenance batteries. Check battery
connections and battery supports.
21
G
B
PRETRIP INSPECTION
5. Engine Oil -- The engine oil should be checked last since it
is necessary for oil to drain out of the block and into the oil
pan to obtain a correct reading. Remove the plug/dip--stick
(1), wipe it off and re--insert it fully into the engine block.
Once again, remove the dip--stick and observe the oil level;
it should be somewhere between the full and add marks. If it
is below the add mark, add oil until the level is correct.
1
6. Over--all Unit inspection -- Visually inspect the entire unit for
leaks, loose bolts, frayed, loose, or broken wires, etc. The
radiator and condenser coils of the unit should be free of
dirt, bugs, cardboard, or any other debris that may obstruct
airflow across the coils. The evaporator (located inside the
body) should be free of debris also, especially shrink--wrap,
which is often used during transport to prevent cargo
shifting.
7. Truck body -- The body should be inspected prior to loading.
Check the door and vent seals for damage and wear.
Inspect the entire interior and exterior of the body to detect
any damage including in the inner and outer skins of the
body. Damage to the insulation may compromise the unit’s
ability to maintain the product temperature by increasing the
amount of heat gain across the truck body.
22
UNIT OPERATION
STARTING THE UNIT
Complete the pre-trip inspection described in the previous section.
:
Road operation
2.
1.
3.
1. Place the RUN/STOP switch (O/I) to the RUN position (I).
2. Press the ROAD operation key (only if the unit has been
previously used in standby mode).
3. Place either one, two or three compartments OFF/ON
switches to ON (I).
4. Then, the unit will:
perform a complete diagnostic check on the
microprocessor controller;
pre-heat for the required amount of time based on the
engine temperature;
starts automatically.
23
G
B
UNIT OPERATION
:
On Standby
1.
2.
3.
Be certain that the unit is connected to an
appropriate power source.
1. Place the RUN/STOP switch (O/I) to the RUN position (I).
2. Press the STANDBY operation key.
3. Place either one, two or three compartments OFF/ON
switches to ON (I).
4. Then, the unit will begin to run on electric power.
24
UNIT OPERATION
CHANGING THE SETPOINT
G
B
The sequence is the same for each compartment.
2.
1. Start the unit.
2. When the setpoint box temperature is displayed, press the
UP or DOWN ARROW key to change the temperature setpoint.
STOP THE UNIT
2.
1.
1. Place C1, C2 and C3 switches to the OFF position (O).
2. Place the RUN/STOP switch (O/I) to the OFF (O) position.
To shut down the unit, ALWAYS use the cab command
or the general switch (RS) located on the control box.
25
UNIT OPERATION
OPERATION WITH AUXILIARY CONTROL PANEL
(OPTION)
1. Start the unit as mentioned before.
3.
2.
2. Press the SYSTEM ON/OFF key. Power light will go ON.
3. Press the ON/OFF key to energize selected compartment.
4. DISPLAY
waiting for communication with unit
compartment temperature display
setpoint temperature display
evaporator status (heat or cool or null)
compartment shut-down via remote
control
defrost compartment
temperature sensor malfunction
26
UNIT OPERATION
CHANGE SETPOINT
Setpoint change can be made from control panel or cab control.
1.
1. Press the UP or DOWN ARROW key to increase or
decrease setpoint. This is the same operation for each
compartment.
LOCK THE CONTROL PANEL
2.
1.
1. Press the CARRIER logo 1 s.
2. The indicator comes on.
27
G
B
UNIT OPERATION
UNLOCK THE CONTROL PANEL
2.
1.
1. Press the CARRIER logo for about 10 s.
2. The indicator goes off.
REMARK
It is not necessary for the compartment to be running in order
to modify or see the setpoint value and the temperature of the
compartment.
The unit can be shut down both with the cab command and the
general switch.
28
PRODUCT LOADING
Proper air circulation in the truck body, air that can move around and
through the load, is a critical element in maintaining product quality
during transport. If air cannot circulate completely around the load,
hot spots or top--freeze can occur.
The use of pallets is highly recommended. Pallets, when loaded so
air can flow freely through the pallets to return to the evaporator,
help protect the product from heat passing through the floor of the
truck. When using pallets, it is important to refrain from stacking
extra boxes on the floor at the rear of the truck, because this will cut
off the airflow.
Product stacking is another important factor in protecting the
product. Products that generate heat, fruits and vegetables for
example, should be stacked so the air can flow through the product
to remove the heat; this is called “air stacking” the product. Products
that do not create heat, meats and frozen products, should be
stacked tightly in the center of the truck. All products should be kept
away from the sidewalls of the body, allowing air to flow between the
body and the load; this prevents heat filtering through the walls from
affecting the product.
It is important to check the temperature of the product being loaded
to ensure that it is at the correct temperature for transport. The
refrigeration unit is designed to maintain the temperature of the
product at the temperature at which it was loaded; it was not
designed to cool a warm product.
29
G
B
PRODUCT LOADING
OPTIONS FOR INSULATED BODIES
- Mobile partition
The mobile partition must be placed at a minimum distance from the
evaporator of 1 m for: MTS700 / MTS1100 / MTS1450 / MTS2200.
- Ducting of evaporator air outlet
Ventilation ducts must never be covered.
SOME ADVICE
Before loading
- Pre--cool the inside of the insulated body by lowering the
temperature for about 15 minutes.
- Evacuate the humidity existing inside the box by carrying out a
manual defrost. This can only take place when enabled by the
defrost thermostat (box temperature lower than 3EC during
pulldown and 8EC during heating).
- Evaporator fans are protected by safety grills. In the event of
heavy duty use of the unit, ice can accumulate on the grills. It is
therefore recommended to clean them regularly by means of a
small brush. The operation MUST be done when the unit has been
SHUT DOWN.
30
PRODUCT LOADING
When loading
G
B
- To be carried out with the unit stopped.
- It is recommended to open doors as little as possible to avoid the
intake of hot air and humidity.
- Select the temperature by means of the thermostat, according to
the transported goods.
- Check the internal temperature of the goods being loaded (using
a probe thermometer).
- Take care not to obstruct the air intakes on the evaporator section
and the ventilation ducts.
Load spacers
Load on pallets
- Leave a free space of about:
6 to 8 cm between load and frontwall,
20 cm between the top of the load and the roof,
between the floor and the load (gratings, pallets).
- Do not forget to close the doors.
- Before closing the doors, check your load once more and see that
nobody is shut inside the box.
31
PRODUCT LOADING
NOTE:
For stationnary utilization, we recommend to place the body in the
shade.
IMPORTANT
Never leave your unit more than a month without running.
32
RECOMMENDED TRANSPORT
TEMPERATURES
Below are some general recommendations on product transport
temperatures and operating modes for the unit. These are included
for reference only and should not be considered pre--emptive of the
set--point required by the shipper or receiver.
More detailed information can be obtained from your Carrier
Transicold dealer.
Product
Bananas
Set--point Range
Operating
mode*
15EC
60EF
Continuous
EC to
+6EC
EF to
+43EF
Continuous
EC
EF
Auto--Start/Stop
or continuous
+2EC to
+6EC
+36EF to
+43EF
Auto--Start/Stop
or continuous
Ice
--20EC
15EF to
20EF
Auto--Start/Stop
Frozen fruits
and vegetables
--18EC
0EF
Auto--Start/Stop
Frozen meats
and seafood
--20EC
--10EF to
0EF
Auto--Start/Stop
Ice cream
--25EC
--20EF
Auto--Start/Stop
Fresh fruits and
vegetables
Fresh meats
and seefood
Dairy Products
* During delivery cycles that include frequent stops and door
openings, it is recommended that the unit always be operated in the
continuous run mode to help insure product quality.
It is essential to shut down the compartment during the periods
when the doors are open, in order to maintain the temperature of the
cargo in the other compartments and keep the unit operating
correctly. To do so, the main O/I switch (O: stop/I: start) should be
switched to O).
33
G
B
PROBLEMS
Everything possible has been done to ensure that your unit is the
most reliable, trouble--free equipment available on the market
today. If, however, you run into problems, the following section may
be of assistance.
If you do not find the trouble that you have experienced listed below,
please call your Carrier Transicold dealer for assistance.
General Problems
UNIT WON’T CRANK, BY THE STARTER
CHECK BATTERY CONDITION.
CHECK BATTERY CONNECTIONS.
CHECK ALL FUSES.
UNIT
WON’T START
CHECK FUEL LEVEL.
CHECK ALL FUSES.
UNIT
WON’T RUN
CHECK FUEL LEVEL.
CHECK ENGINE OIL LEVEL.
CHECK ALL FUSES.
UNIT
DIES
CHECK BELTS.
CHECK ENGINE OIL LEVEL.
CHECK COOLANT LEVEL.
CHECK FUEL LEVEL.
CHECK ALL FUSES.
UNIT
NOT COOLING PROPERLY
DEFROST UNIT.
CHECK EVAPORATOR FOR AIRFLOW
RESTRICTION.
CHECK CONDENSER FOR AIRFLOW
RESTRICTION.
CHECK BODY FOR DAMAGE OR AIR
LEAKS.
34
PROBLEMS
FAULT ALARM DISPLAY AND SAFETY FEATURES
Display will alternate between an alarm message and the normal
display whenever any of the failures listed below occur.
NOTE: Whenever the fault light is on, check display for fault
message.
-- Reset the micro to start the unit.
-- Press FUNCTION CHANGE key.
-- Press the UP/DOWN ARROW keys until ALARM RST is
displayed.
-- Press enter to clear alarm. Alarm CLR will now be displayed and
unit will restart.
Other method to reset: move RUN/STOP switch to STOP. Unit
resets and will start when RUN/STOP switch is moved to run
position.
ALARM DISPLAY °= FAULT LIGHT ON
CODE
ENGLISH
DESCRIPTION
AL0
ENG OIL
° Low Oil Pressure
AL1
ENG HOT
° High coolant Temperature
AL2
HI PRESS
° High Discharge Pressure
AL3
START FAIL
° Start failure
AL4
LOW BATT
° Low battery voltage
AL5
HI BATT
° High battery voltage
AL6
DEFRFAIL
AL7
ALT AUX
(°) No Alternator Auxiliary Output
AL8
STARTER
° Starter Motor Fault
AL9
1RA SENSOR
° Return Air Sensor Compartment 1
Fault
AL10
2RA SENSOR
° Return Air Sensor Compartment 2
Fault
AL11
WT SENSOR
Coolant temperature sensor
Defrost Override
35
G
B
PROBLEMS
ALARM DISPLAY °= FAULT LIGHT ON
CODE
ENGLISH
AL12
HIGH CDT
° High discharge temperature
DESCRIPTION
AL13
CD SENSOR
Discharge temperature sensor
AL14
SBY MOTOR
° Standby motor overload
AL15
FUSE BAD
AL16
3RA SENSOR
AL17
DISPLAY
AL18
SERVICE 1
Maintenance Hour meter 1
AL19
SERVICE 2
Maintenance Hour meter 2
AL20
1RA OUT
° Compartment 1 Out-of-Range
AL21
2RA OUT
° Compartment 2 Out-of-Range
AL22
3RA OUT
° Compartment 3 Out-of-Range
AL23
NO POWER
° Fuse open
° Return Air Sensor Compartment 3
Fault
Display
No power supply
° = fault light ON
WARNING : AL0 (ENG OIL) could come up if alternator is badly
connected.
36
PROBLEMS
FUSES
The fuses which protect the circuits of the control system are
located in the box on the left-hand side of the unit.
The fuses are accessed by loosening the screws that hold the
control panel closed.
:
Old model
37
G
B
PROBLEMS
Rep.
F1
F2
F3
F4
F5
F6
F7
F8
F9
F11
38
FUSE IDENTIFICATION
Item
General
Controller MP
Run fuse
Speed control solenoid
Hot gas valve
Fuel heater (option)
Compartment 1
Compartment 2
Compartment 3
Flashing relay
Amps
80 A
5A
25 A
15 A
7.5 A
25 A
10 A
10 A
10 A
5A
PROBLEMS
:
Rep.
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
New model
FUSE IDENTIFICATION
Item
General fuse
Controller microprocessor fuse
Run fuse
Main heat valve fuse
Speed control solenoid fuse
Unloader fuse
Liquid solenoid valve fuse (comp. 1)
Liquid solenoid valve fuse (comp. 2)
Liquid solenoid valve fuse (comp. 3)
Fuel pump fuse
Hot gas valve fuse (comp. 1)
Hot gas valve fuse (comp. 2)
Hot gas valve fuse (comp. 3)
G
B
Amps
60 A
5A
15 A
5A
10 A
3A
3A
3A
3A
5A
10 A
10 A
10 A
39
UNIT MAINTENANCE
Engine oil -- the oils recommended for use in your refrigeration unit
must comply with the American Petroleum Institute’s (API) SG/CD
rating. The use of any oil that does not meet this rating may affect
the warranty on the engine in the unit. The use of oil of the proper
weight (viscosity) is also essential. The following chart indicates the
SAE Weight Rating of the oil to be used in various climates:
EF
30 W or
15W40
20 W or 15W40
10 W or 10W30
EC
40
UNIT MAINTENANCE
The following oils are accepted for use in Europe with these units.
RECOMMENDED OILS
CARRIER
AGIP
ANTAR
BP
ELF
FIAT
FINA
HAFA
IGOL
IMPERATOR
LABO
MOBIL
OPAL
ORLY
POLAROIL
RENAULT
TEXACO
TOTAL
SHELL
UNIL
YACCO
CARRIER TD+15W- 40
SIGMA TURBO SHPD 15W--40
GRAPHITE R 15W--40
VANELLUS C3 EXTRA 15W--40
VANELLUS FE 15W30
MULTIPERFORMANCE4D 15W--40
PERFORMANCE TROPHY 15W--40
URANIA TURBO 15W--40
KAPPA LDO 15W--40
KAPPA TD PLUS 15W--40
KAPPA EXTRA 15W--40
DETERGENTE 4DM 15W--40
STRADEX 900 ECO 15W--40
SYNTHIDEX ECO 15W--40
RALLYE TURBO 4E 15W--40
RALLYE TURBO 4E LD 15W--40
RAFF SUPER HPDO 15W--40
MEGAMAXI 15W--40
DELVAC SHC 15W--40
DELVAC 1400 SUPER
OPALGET D 500 15W--40
TURBO 2002 15W--40
POLATRUCK 15W--40
KMX 2 PLUS 15W--30
KMX 2 PLUS 15W--40
MV5 “EUROPE”
URSA SUPER TD 15W--40
RUBIA TIR MAX 15W40
MYRINA TX 15W--40
MYRINA T 15W--30
SUPER ROC 3D 15W--40
TURBO DX 15W--40
SM 4D + 15W--40
The above oil equivalents are based on the recommendations
contained in the suppliers’s technical literature.
41
G
B
UNIT MAINTENANCE
UNIT MAINTENANCE SCHEDULES
For the most reliable operation and for maximum life, your unit
requires regular maintenance. This includes oil and filter changes,
fuel and air filter replacement, coolant replacement, belts etc.
Genesis R70/R80
Required
R
i d
service
Genesis R90
Hours
With
bypass
oil filter
(option)
Hours
Remote
oil filter
Hours
A
250
A
250
A
250
AB
1000
AB
1250
AB
1250
A
1750
ABC
2250
ABC
2250
ABC
2500
AB
3250
AB
3250
A
3250
ABD
4250
ABD
4250
ABD
4000
ABC
5250
ABC
5250
A
4750
AB
6250
AB
6250
ABC
5500
AB
7250
AB
7250
A
6250
ABCD
8250
ABCD
8250
AB
7000
AB
9250
AB
9250
AD
7750
AB
10250
AB
10250
Without
bypass
oil filter
In addition to the above service requirements, please adhere to the
following:
The engine oil should be changed at least once per year, even if the
engine has not run the necessary number of hours.The coolant
(anti-freeze) should be replaced after a maximum of two years.
42
UNIT MAINTENANCE
DESCRIPTION OF MAINTENANCE OPERATIONS
G
B
Service Operations
SERVICE A
:
:
:
:
:
:
:
SERVICE B
:
:
:
:
:
:
:
:
:
:
SERVICE C
SERVICE D
:
:
:
:
:
:
:
Drain the engine oil, replace oil filter
Check engine cooling system
Clean the cartridge of the dry air filter
Check air cleaner and change air cleaner oil
Check all bolts, screws and unit mounting bolts for
tightness. Tighten as required (1st service only)
Check all belts
Check engine speed under load
Replace fuel filter
Check fuel pump filter
Replace the cartridge of the dry air filter
Check the battery terminals and fluid level
Check compressor oil level
Check alternator brushes
Check engine thermostat for proper operation
Check defrost:
Check timer setting and function
Check refrigerant control valves for proper operation
Fans stop
Defrost ends automatically
Water drains from evaporator
Check and adjust rocker arms
Replace belts as necessary
Clean radiator and condenser
Check refrigerant level
Check and rebuild the alternator
Clean and adjust fuel injectors (140 kg/cm2)
Check all belt tension pulleys
Change anti--freeze in diesel engine
Check bearings in clutch(es) and electric motors
43
UNIT MAINTENANCE
BELTS
GENESIS R70
Alternator
12VDC
Water pump
2.
Electric motor
3.
5.
4.
Diesel engine
Compressor
1.
Generator
Quantity
44
1.
Engine to compressor v-belt
2
2.
Alternator v-belt
1
3.
Electric motor to compressor v-belt
1
4.
Engine to water pump
1
5.
Electric motor to generator
1
UNIT MAINTENANCE
GENESIS R80
G
B
Alternator
12VDC
Water pump
Electric motor
3.
5.
4.
Compressor
Diesel engine
1.
Generator
Quantity
1.
Engine to compressor v-belt
1
2.
Alternator v-belt
0
3.
Electric motor to compressor v-belt
1
4.
Engine to water pump
1
5.
Electric motor to generator
1
45
UNIT MAINTENANCE
GENESIS R90
Alternator
12VDC
Water pump
Electric motor
3.
5.
4.
Compressor
Diesel engine
1.
Generator
Quantity
46
1.
Engine to compressor v-belt
2
2.
Alternator v-belt
0
3.
Electric motor to compressor v-belt
2
4.
Engine to water pump
1
5.
Electric motor to generator
1
UNIT MAINTENANCE
Too little belt tension cause slippage and excessive belt wear. Too
much tension shortens belt and bearing life. Belt deflection should
be equal to belt thickness.
Properly adjusted belts give long lasting and efficient service (refer
to maintenance schedule).
Important: During intervention on twin mounted belts, replace
IMPERATIVELY both belts and make sure they are both in the
same package.
47
G
B
UNIT MAINTENANCE
FILTERS
3.
1.
2.
1. Diesel fuel filter
2. Oil filter
3. Air filter, dry type
For code numbers consult the corresponding spare parts manual.
48
STANDBY OPERATION GUIDELINES
For safe, reliable operation in Standby mode, it is important to
consider the following guidelines:
- Never plug the unit in to the power source with the main switch in
the RUN position. The main switch should always be in the STOP
position when connecting the unit to the power source.
- The fusing and extension cable used for Standby operation
should conform to the following:
Unit
Fuse
200/240/3/50 Hz
220/256/3/60 Hz
Fuse
350/415/3/50 Hz
380/460/3/60 Hz
Standardized extension
cable
H.07.RNF
220 volts
380 volts
Genesis
R70
23 A
13 A
4 x 6 mm2
4 x 6 mm2
Genesis
R80
23 A
13 A
4 x 6 mm2
4 x 6 mm2
Genesis
R90
40 A
29 A
4 x 6 mm2
4 x 6 mm2
- The unit connection cable must be fitted with a ground connection.
The cable must be connected to earth.
- On the 380 V supply, it is recommended to use a differential
protection on each plug.
- When performing service and/or maintenance procedures on a
refrigeration unit, make certain that the unit is disconnected from
the power source and that the main unit switch is turned OFF.
- Operations on the 380 V supply for the unit must only be carried
out by authorized personnel.
- Warning: changing the operation of a unit from 380 V to 220 V
implies a change in the electrical coupling, adjustment of the
overload relay and for certain unit models, the replacement of
some components. Please consult our technical service.
49
G
B
MANUFACTURER INFORMATION
WARRANTY
As soon as you receive your warranty card, please keep it in a safe
place.
The card will be requested for any intervention under warranty
which needs to be performed on your equipment. Always update the
service chart which is to be found inside the front cover.
This manual refers to the standard model.
Some options may not appear in it, and in such cases you are
requested to consult our Technical Services.
Carrier Transicold constantly seeks to improve the quality of its
products and therefore reserve the right to modify them without prior
notice.
INSTALLATION
During assembly and routine service operations, access to the
unit may involve certain risks.
TAKE EVERY SAFETY MEASURE TO ACCESS THE UNIT (e.g.:
standard ladders, running board with railing, safety belt etc.)
Installation of this unit requires no special knowledge of
refrigeration. To fit the nosemount unit to the vehicle body, it is
necessary only to slide the evaporator section into the opening in
the front panel and secure using the bolts provided.
Advice
When handling, use suitable lifting gear attached to the lifting points
provided for this purpose on the unit.
Note: The unit should not protude out of the body.
BATTERY
Maintenance:
Never leave a unit more than a month without running. In case of
long standstill, charge the battery independently.
50
MANUFACTURER INFORMATION
Before performing any welding on the chassis, take care to
disconnect the battery of the vehicle and the 12VDC and 3 phase
alternator, and any other electronic system.
Never try to start the vehicle with a booster because this could
damage the electronic components in the unit or on the vehicle.
1.
Check that all mounting bolts are well tightened and suitable
for use.
2.
When you drill holes in the unit or in the body of the vehicle, be
careful not to pierce the refrigeration tubes or the electrical
wiring.
3.
When you are working next to the unit (condenser and
evaporator) be careful not to cut yourself on the sharp edges.
4.
When the unit is running, keep your hands away from belts and
fan motors.
5.
Never close the discharge valves of the compressor when
the unit is running.
6.
In case of repair, only use manometer by--pass hoses which
are in a good condition and avoid their contact with belts, pulley
and fan motor.
7.
The refrigerant liquid must be handled with great care.
8.
Next to a flame the refrigerant liquid gives off a phosgene gas
which has an unpleasant smell and irritates the lungs.
9.
Never heat up a closed cooling circuit with a flame, the cooling
system must be handled with great care.
10. When liquid refrigerant is in contact with the atmosphere, it
evaporates and freezes everything it makes contact with.
51
G
B
MANUFACTURER INFORMATION
First aid in case of frost--bite:
a) Cover up the frost--bitten part.
b) Warm up quickly the frost--bitten part by dipping it into lukewarm
water (not hot).
c) In case you do not have water wrap the wounded place in a clean
cloth.
d) If refrigerant fluid has been splashed into your eyes, rinse them
immediately with clean water; as a precaution, you are
recommended to have a medical examination as well.
11. Cooling oil
Synthetic or derived from fuel
- Avoid contact with skin.
- Wash carefully after handling.
REMARKS ABOUT SAFETY:
Diesel engine
NEVER START THE ENGINE IN A CLOSED ROOM, THE
EXHAUST GAS IS POISONOUS.
It is colourless and adourless and created by incomplete
combustion of hydrocarbons.
Exhaust gas is poisonous; breathing it in induces drowsiness and
may lead to loss of consciousness.
The following symptons indicate an exhaust gas inhalation:
- Blackout
- Intense headache
- Sudden weakness and sleepiness
- Vomiting
- Muscular contractions
- Beating temples
52
MANUFACTURER INFORMATION
If you feel one of the above mentioned symptoms, go out and
breathe fresh air.
The maintenance operation should be done at the recommended
intervals on your equipment. Check the exhaust gas system to
avoid gas inhalation.
If you notice a noise or modification of the exhaust system stop
immediately the engine and call sales service center for checking
and repair.
Standby and start/stop:
The unit will start automatically, keep away from belts, pulleys and
fans.
53
G
B
“A.T.P. EUROPE” REGULATION EXTRACT
(Date: March 1974)
Approval of vehicles intended for the carriage of perishable goods.
Before putting a refrigerated vehicle into service, it is necessary to
have it approved by the Regional Health Department.
CHARACTERISTICS OF VEHICLES USED FOR CARRYING
PERISHABLE GOODS; REFRIGERATION UNIT.
The refrigeration unit is an insulated unit with a cooling system
which makes it possible, with a mean outside temperature of
+30EC, to lower the temperature inside the empty body and to
maintain this low temperature in the following way:
CLASS A
Refrigeration unit furnished with a cooling system whereby a
temperature between +12EC and 0EC inclusive can be chosen.
CLASS B
Refrigeration unit furnished with a cooling system whereby a
temperature between +12EC and --10EC inclusive can be chosen.
CLASS C
Refrigeration unit furnished with a cooling system whereby a
temperature between +12EC and --20EC inclusive can be chosen.
The cooling capacity of a unit is determined by a test carried out in
one of the approved testing stations and ratified by an official report.
Note: The “K“ factor of bodies intended to be classified as C must
be equal to or lower than 0.4 W/m2 EC.
54
“A.T.P. EUROPE” REGULATION EXTRACT
G
B
SIGNS, IDENTIFICATION MARKS AND PLATES TO BE
ATTACHED TO REFRIGERATION UNITS
Refrigeration Plate
This reference must be followed by identification marks according
to the following list:
Standard refrigeration unit Class A
FNA
Reinforced refrigeration unit Class A
FRA
Reinforced refrigeration unit Class B
FRB
Reinforced refrigeration unit Class C
FRC
In addition to the above identification marks, the date (month and
year) of expiry of the approval certificate must be indicated.
Example:
FRC
6--2000
(6 = month (June) 2000 = year)
Very important
Regularly check the expiry date of the approval certificate. During
transport, the approval certificate or provisional certificate should be
shown on request of qualified agents. To have an insulated unit
approved as a refrigeration unit, an application to modify the
approval certificate should be sent to the regional health office.
55
EMERGENCY ROAD SERVICE
At Carrier Transicold we’re working hard to give you complete
service when and where you need it. That implies a worldwide
network of dealers and available an emergency service. These
service centers are manned by factory--trained service personnel
and backed by extensive parts inventories that will assure you of
prompt repair.
Should you encounter a unit problem with your refrigeration unit
during transit, follow your company’s emergency procedure or
contact the nearest Carrier Transicold service center. Consult the
directory to locate the service center nearest you. This directory
may be obtained from your Carrier Transicold dealer.
If you are unable to reach a service center, call Carrier Transicold’s
24 Hour Assistance:
In Europe, please use the following free phone numbers from:
A
B
CH
D
DK
E
F
FIN
GB
GR
H
I
IRL
L
RUS
N
NL
P
PL
S
56
AUSTRIA
BELGIUM
SWITZERLAND
GERMANY
DENMARK
SPAIN
FRANCE
FINLAND
GREAT BRITAIN
GREECE
HUNGARY
ITALY
IRELAND
LUXEMBURG
RUSSIA
NORWAY
THE NETHERLANDS
PORTUGAL
POLAND
SWEDEN
0800 291039
0800 99310
0800 838839
0800 1808180
808 81832
900 993213
0800 913148
0800 113221
0800 9179067
00800 3222523
00800 13526
800 791033
1800 553286
0800 3581
810 800 200 31032
800 11435
0800 0224894
8008 32283
00800 3211238
020 790470
EMERGENCY ROAD SERVICE
From other countries: +32 9 255 67 89
G
B
Direct: +32 9 255 67 89
In Canada or United States, call 1 -- 800 -- 448 -- 1661.
When calling, please have the following information ready for
fastest service:
- Your name, the name of your company, and your location.
- A telephone number where you can be called back.
- Refrigeration unit model number and serial number.
- Box temperature, set--point and product.
- Brief description of the problem you are having, and what you
have already done to correct the problem.
We will do everything we can to get your problem taken care of and
get you back on the road.
57
Download