Specifications, Installation, and Operating Instructions
Model:
SP 50 Family
CAUTION: The installation of a surge protection device (SPD) must be done by qualified electrical
personnel. SPD must be grounded through the power system ground for proper operation.
WARNING: Before installing the suppressor, AC power must be off. Failure to do so could result in damage to
the suppressor and poses a potential electrical shock hazard to personnel.
WARNING: Read SPD label on side of the enclosure to verify voltage configuration.
WARNING: Discontinue installation if the measured voltage is not in the range of the model voltage configuration
of the SPD being installed. Contact Transtector’s technical support with any questions concerning the voltage
configuration prior to installation and application of power.
© Smiths Power 2015.
All Rights Reserved.
1
Table of Contents
Specifications
Pre-Installation Notes
Installation Procedure
Installation Checklist
Troubleshooting
Wiring Diagrams
3
5
6
7
7
8
Part
Number
Model
SP50-1201P
SP 50-1201P
MOV 50 kA, NEMA 4X plastic encl., Single phase
1
SP50-240SP
SP 50-240SP
MOV 50 kA, NEMA 4X plastic encl., 120/240 Split phase
2
SP50-2401P
SP 50-2401P
MOV 50 kA, NEMA 4X plastic encl., Single phase
1
SP50-1203Y
SP 50-1203Y
MOV 50 kA, NEMA 4X plastic encl., Wye
3
SP50-4803Y
SP 50-4803Y
MOV 50 kA, NEMA 4X plastic encl., Wye
3
SP50-6003Y
SP 50-6003Y
MOV 50 kA, NEMA 4X plastic encl., Wye
3
SP50-2403D
SP 50-2403D
MOV 50 kA, NEMA 4X plastic encl., Delta
4
SP50-4803D
SP 50-4803D
MOV 50 kA, NEMA 4X plastic encl., Delta
4
Description
Figure
Reference
© Smiths Power 2015.
All Rights Reserved.
2
Specifications:
All Models
Product Type
Type 1 SPD
Type 2 Canada Listed
Protection Provided
L-N, L-G, N-G (Single Phase)
L-L, L-N (120/240V Split Phase)
L-L, L-N (Wye)
L-L, L-G (Delta)
Maximum Surge Current
50 kA
Nominal Discharge Current (In)
20 kA (120, 120/240-SP, 240,
120/208-3Y, 240-3D)
10 kA (277/480-3Y, 347/600-3Y,
480-3D)
Maximum Load Current per Phase
Unlimited
Connection
Parallel
Operating Frequency
50/60 Hz
Surge Capacity per Mode
50 kA
Surge Capacity per Phase
50 kA
IEEE Location
C-High, B-Medium
Fault Rating (SCCR)
200 kA
Response Time
<1 ns
Weight (Max) lb, kg
1.3 lbs / 0.59 kg
Lead Length
≤ 1.5’ (recommended)
Wire Gauge
16” (0.4m) #12 AWG integral leads
provided
Breaker Connection
30 A (recommended)
Operating Temperature Range
-40°C to +85°C
Operating Humidity (noncondensing)
5% to 95%
© Smiths Power 2015.
All Rights Reserved.
3
Operating Altitude (feet)
Up to 12,000
Warranty
2 Years
Certifications
UL 1449 3rd Edition Listed
UL 96A (for 20 kA In models)
RoHS
NEC 100/285
ANSI/IEEE C62.41, C62.45
Model
V (Vac)
Phase
Mode(s)
@
VPR
(Vpk)
In (8/20 µs)
MCOV
SP 50-1201P
120
1
L-N
L-G
N-G
700
1200
600
20 kA
180 Vac (L-N)
SP 50-240SP
120/240
Split
L-N
L-L
700
1200
20 kA
180 Vac (L-N)
SP 50-2401P
240
1
L-N
L-G
N-G
1000
1500
700
20 kA
275 Vac (L-N)
SP 50-1203Y
120/208
3Y
L-N
L-L
700
1200
20 kA
180 Vac (L-N)
SP 50-4803Y
277/480
3Y
L-N
L-L
1200
2000
10 kA
320 Vac (L-N)
SP 50-6003Y
347/600
3Y
L-N
L-L
1500
2500
10 kA
420 Vac (L-N)
SP 50-2403D
240
3D
L-G
L-L
1000
1800
20 kA
275 Vac (L-G)
SP 50-4803D
480
3D
L-G
L-L
1800
3000
10 kA
550 Vac (L-G)
© Smiths Power 2015.
All Rights Reserved.
4
Pre-Installation Notes
•
•
•
•
•
•
Read entire installation manual prior to installing this SPD.
Unpack unit carefully, removing packing material. Inspect for damages during shipment.
If unit seems damaged, contact Transtector and shipping agency. Do not continue to
install unit.
Confirm install location temperature will not exceed SPD rating (-40°C to +85°C).
Verify all nuts and bolts have tight connections.
Verify install location meets SPD enclosure NEMA type 4X location requirements.
Electrical Specification for SPD Installation:
Verify voltage configuration of the SPD matches actual system voltage configuration of
service point. Ground resistance is less than 25 ohms and all wiring conductors are in
accordance with appropriate layout/installation drawing.
© Smiths Power 2015.
All Rights Reserved.
5
Installation Procedure
•
Length of leads and conductor size:
Leads must be as short as possible, not exceeding the recommended length of a foot
and a half (1.5’); and routed with gradual bends avoiding sharp or 90° bends. SPD
comes with #12 AWG wire pre-cut for installation. Extending existing wire by splicing is
not recommended.
•
Mounting:
1. Turn off all power supplied to
this equipment.
2. Panel Mount: Punch out 1/2”
enclosure knockout from panel
or mounting location as close as
possible to where the wires will
terminate.
Please
consult
Transtector application support
where another type of mounting
is required.
3. Insert a 1/2” close nipple to the
Myers Hub provided and
attached to the SP 50 SPD.
Insert SPD wires carefully through the knockout hole. Tighten a 1/2” steel conduit
lock nut to secure the SPD to the enclosure (as shown in Figure 1 Panel Mount).
4. Connect the wires as shown in the appropriate wiring diagram.
5. Overcurrent Protection: Type 1 SPDs are UL Listed and tested to be selfprotecting. They do not require upstream protection according to UL 1449 3rd
Edition and Section 285 of the NEC. However, it is recommended an upstream
disconnect or breaker be installed for maintenance and safety. Many switches
and circuit breakers have limitations regarding more than one wire in a
connector. Breaker manufacturers can provide information on limitations of
available terminals. Where additional wires are prohibited under the same
terminal, many times installing a new circuit breaker is convenient. Typical sizes
are 15, 20 and 30 amps.
6. For optimal device performance, use shortest wire length possible. Cut off
excess wire. Avoid sharp edges.
7. Before energizing, installer must verify service and separately derived system
Neutral to Ground bonding jumper per NEC requirements.
© Smiths Power 2015.
All Rights Reserved.
6
•
Final check:
Check installation of unit as indicated in installation drawings. Apply external AC power
to the SPD. The unit is operational if all green indicator lamps are illuminated. If not,
contact Transtector’s technical support at 800-882-9110 or 208-772-8515.
•
Visual inspection:
Operational status of the SPD is verified by observing the phase status indicator LED(s).
The LED, illuminated Green indicates normal operation with all protection modes
functioning.
Installation Checklist
YES
[ ]
NO
[ ]
[
[
[
[
[
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
]
]
]
]
]
Voltage configuration of SPD matches actual voltage configuration of service
point.
Ground resistance is less than 25 ohms.
All wiring conforms to national electric code (NEC).
All conductors are in accordance with appropriate layout/installation drawing.
All lead lengths are as short as possible.
SPD is installed in parallel with incoming phase conductors.
After installation, all lights are illuminated green.
All critical loads are protected by the SPD. If not, additional SPD(s) may be
required.
Troubleshooting
Problem
Solution
Status LED(s) are red
Indicates protection loss in phase(s). Unit needs replacement.
Status LED(s) are not
illuminated
Indicates power loss. Verify power is being supplied to service point. If
problem persists, call Transtector technical support.
Transtector Technical Support is available at 800-882-9110 or 208-772-8515.
© Smiths Power 2015.
All Rights Reserved.
7
Wiring Diagrams
Following section contains all layout/installation drawings found within the SP 50 Family. Locate
appropriate drawing based on the model number of your system.
© Smiths Power 2015.
All Rights Reserved.
8
Transtector Systems, Inc.
10701 Airport Drive, Hayden ID 83835
(TF) 800.882.9110 | (FX) 208.762.6034
www.Transtector.com | www.SmithsPower.com
DRAWN
Heather Bakke
DATE
6/16/15
ENG APPD
Jeff Molitor
7/29/15
PRODUCT MANAGER APPD
Vrajesh Davé.
July 29, 2015
MARKETING APPD
Linda Johnson
7/31/15
Notice:
The information and design in this document is the property of Transtector Systems.
All rights reserved.
SP50-S008 Rev A