-6050 Digital Input/Output Module

advertisement
6000 Series Discrete Input/Output Modules
-6050 Digital Input/Output Module
2. Pin Assignment
NuDAM-6050 is a digital input and output module. The
digital input channels can monitor active TTL signals, and
sense passive switch on/off signal because of the internal pull
high resistors. The convenient open collector output channels
can sink up to 50mA current. Combining with the relay
devices, it is possible to control the high power devices by
programming output channel of the NuDAM-6050.
3. Application Wiring
4. Functional Block Diagram
+ 5V
Power Input
+10V ~ +30V
DO 2
11
DO 1
DO 0
DI 0
DI 1
DI 3
DI 2
DI 4
20
DI 6
TTL Input
DI 5
1. Introduction
+5V
Power
Regulator & Filter
10Kohm
TTL Buffer
Features
Digital Input
u
u
u
u
u
u
u
u
Interface:
RS-485, 2 wires
Speed (bps): 600, 1200, 2400, 4800, 9600, 19.2k,
38.4k, 57.6k, 115.2k
Digital Input:
Channel number: 7
Logic level: TTL
Pull up resistor: 10KΩ
Maximum current: 0.5mA
Digital Output:
Channel number: 8
Output characteristic: open collector transistor
Maximum current sink: 50mA
Storage Temperature Range: -25 to 80 °C
Operating Temperature Range: -10 to 70 °C
Power Requirement: +10V to +30VDC Unregulated with
against power reversal
Power Consumption: 0.35W
Case: ABS with captive mounting hardware
CE Class A Conformity
7-bit
Digital/Input
DI0
1-bit
Digital/Input
Default*
Pin
5. Installation
10Kohm
TTL Buffer
DI n
Pin Definitions
Pin #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Signal Name
DO7
DO6
DO5
DO4
DO3
DEFAULT*
(Y)DATA+
(G)DATA(R)+VS
(B)GND
DO2
DO1
DO0
DI0
DI1
DI2
DI3
DI4
DI5
DI6
Description
Digital output channel 7
Digital output channel 6
Digital output channel 5
Digital output channel 4
Digital output channel 3
Initial state setting
RS-485 signal, positive
RS-485 signal, negative
Power supply, +10V ~ +30Vdc
Ground
Digital output channel 2
Digital output channel 1
Digital output channel 0
Digital input channel 0
Digital input channel 1
Digital input channel 2
Digital input channel 3
Digital input channel 4
Digital input channel 5
Digital input channel 6
Switch
or
Push Button
GND
To
Micro Processor
Equipment for Installation
A existing RS-485 network
NuDAM modules
DC Power supply (+10V~+30V)
Wires for power, communication and I/O signal
Installation Procedure
Open Collector Output with Power Load
LED, SSR, Relay etc.
From
Micro Processor
open
collector
+Vs
R
DO n
Power
Loading
External
Power
Supply
1.
Configure every single NuDAM module under the
administration utility.
2.
The baud rate setting and calibration procedure
must be done under the DEFAULT* mode.
3.
The baud rate and check-sum status must be identity
with the application network. The address ID must
not be conflict with other modules on the network.
4.
Plug the new module to the existing network.
5.
Use the NuDAM administration utility to check the
entire network.
GND
R : current limit resistor
DO0
DO7
10
(B)GND
(R)+Vs
DO 7
Rec/Drv
Micro
Processor
8-bit
Digital/Output
+5V
*The module is in DEFAULT mode when DEFAULT* pin
connected to GND while applying power on the module.
*Do not apply any power signal to DEFAULT* pin, just left
it open or connected it to GND.
The Optimal Choice for Harsh Environment
RS-485
EEPROM
Config Data
Safe Value
Digital Input Connect with Switch/Push Button
Specifications
u
Data -
(G)DATA-
u
Data +
Bit 0-7
Bit 0-6
DEFAULT *
u
Digital Output
(Y)DATA+
u
GND
Signal
DO 3
u
I/O Type
DO 4
u
To
Micro Processor
Digital
Input/Output
ND-6050
DO 5
u
7 bits digital input
8 bit open collector digital output
programmable power on output state
programmable in/out polarity setting
programmable host watchdog timer for host failure
protection
internal watchdog timer for device failure protection
easy programming by software
easy installation and wiring
DO 6
u
DI n
TTL
Device
1
u
Watchdog/Power Failure
Supervisor
GND
DI6
6000 Series Discrete Input/Output Modules
6. Command Set
There are three categories of NuDAM commands. The first
is the general commands, including set configuration
command, read configuration, reset, read module‘s name or
firmware version, etc. Every NuDAM can response to the
general commands. The second is the functional commands,
which depends on functions of each module. Not every
module can execute all function commands. The third is the
special commands including functions about the
programmable watchdog timer, safe values, and the
programmable leading code. All the commands used in the
NuDAM discrete input/output module are list in the following
table.
Command
General Command
Set Configuration
Read Configuration
Read Module Name
Read Firmware Version
Software Reset
Reset Status
Functional Command
Digital Input
Digital Output
Synchronized Sampling
Read Synchronized Data
Syntax
%(OldAddr)(NewAddr)
(InputRange)(BaudRate)
(DataFormat)
$(Addr)2
$(Addr)M
$(Addr)F
$(Addr)RS
$(Addr)5
$(Addr)6
#(Addr)(ChannelNo)(OutDa
ta)
#**
$(Addr)4
Special Command
Read Command Leading Code
Setting
Change Command Leading
Code Setting
Set Host Watchdog / Safety
Value
Read Host WatchDog / Safe
Value
Host is OK
I/O Polarity Setting
Read Polarity Setting
~(Addr)0
~(Addr)10(C1)(C2)(C3)
(C4)(C5)(C6)
~(Addr)2(Flag)
(TimeOut)(SafeValue)
~(Addr)3
~**
~(Addr)CP(State)
~(Addr)CR
* The module accepts calibration command, baud rate and
checksum configuration setting under the DEFAULT*
mode.
* Please refer the manual in PDF file format in the CD for
detail description of these commands.
The Optimal Choice for Harsh Environment
7. ADLINK on the Internet
The full version manual can be download from website
http://www.adlink.com.tw/download/manual/index.htm#6000
Homepage:
Service:
Technical Assistance:
http://www.adlink.com.tw
service@adlink.com.tw
NuDAM@adlink.com.tw
Copyright ï›™ 2000 ADLINK TECHNOLOGY INC.
TEL: 886-2-82265877
FAX: 886-2-82265717
Contents and sp ecification subject to change without notice.

NuDAM is a registered trademark of ADLINK TECHNOLOGY
INC. Other brands of products are trademarks or registered
trademarks of their respective holders. AM-ND6050-E1.00
Download