6000 Series Discrete Input/Output Modules -6050 Digital Input/Output Module 2. Pin Assignment NuDAM-6050 is a digital input and output module. The digital input channels can monitor active TTL signals, and sense passive switch on/off signal because of the internal pull high resistors. The convenient open collector output channels can sink up to 50mA current. Combining with the relay devices, it is possible to control the high power devices by programming output channel of the NuDAM-6050. 3. Application Wiring 4. Functional Block Diagram + 5V Power Input +10V ~ +30V DO 2 11 DO 1 DO 0 DI 0 DI 1 DI 3 DI 2 DI 4 20 DI 6 TTL Input DI 5 1. Introduction +5V Power Regulator & Filter 10Kohm TTL Buffer Features Digital Input u u u u u u u u Interface: RS-485, 2 wires Speed (bps): 600, 1200, 2400, 4800, 9600, 19.2k, 38.4k, 57.6k, 115.2k Digital Input: Channel number: 7 Logic level: TTL Pull up resistor: 10KΩ Maximum current: 0.5mA Digital Output: Channel number: 8 Output characteristic: open collector transistor Maximum current sink: 50mA Storage Temperature Range: -25 to 80 °C Operating Temperature Range: -10 to 70 °C Power Requirement: +10V to +30VDC Unregulated with against power reversal Power Consumption: 0.35W Case: ABS with captive mounting hardware CE Class A Conformity 7-bit Digital/Input DI0 1-bit Digital/Input Default* Pin 5. Installation 10Kohm TTL Buffer DI n Pin Definitions Pin # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Signal Name DO7 DO6 DO5 DO4 DO3 DEFAULT* (Y)DATA+ (G)DATA(R)+VS (B)GND DO2 DO1 DO0 DI0 DI1 DI2 DI3 DI4 DI5 DI6 Description Digital output channel 7 Digital output channel 6 Digital output channel 5 Digital output channel 4 Digital output channel 3 Initial state setting RS-485 signal, positive RS-485 signal, negative Power supply, +10V ~ +30Vdc Ground Digital output channel 2 Digital output channel 1 Digital output channel 0 Digital input channel 0 Digital input channel 1 Digital input channel 2 Digital input channel 3 Digital input channel 4 Digital input channel 5 Digital input channel 6 Switch or Push Button GND To Micro Processor Equipment for Installation A existing RS-485 network NuDAM modules DC Power supply (+10V~+30V) Wires for power, communication and I/O signal Installation Procedure Open Collector Output with Power Load LED, SSR, Relay etc. From Micro Processor open collector +Vs R DO n Power Loading External Power Supply 1. Configure every single NuDAM module under the administration utility. 2. The baud rate setting and calibration procedure must be done under the DEFAULT* mode. 3. The baud rate and check-sum status must be identity with the application network. The address ID must not be conflict with other modules on the network. 4. Plug the new module to the existing network. 5. Use the NuDAM administration utility to check the entire network. GND R : current limit resistor DO0 DO7 10 (B)GND (R)+Vs DO 7 Rec/Drv Micro Processor 8-bit Digital/Output +5V *The module is in DEFAULT mode when DEFAULT* pin connected to GND while applying power on the module. *Do not apply any power signal to DEFAULT* pin, just left it open or connected it to GND. The Optimal Choice for Harsh Environment RS-485 EEPROM Config Data Safe Value Digital Input Connect with Switch/Push Button Specifications u Data - (G)DATA- u Data + Bit 0-7 Bit 0-6 DEFAULT * u Digital Output (Y)DATA+ u GND Signal DO 3 u I/O Type DO 4 u To Micro Processor Digital Input/Output ND-6050 DO 5 u 7 bits digital input 8 bit open collector digital output programmable power on output state programmable in/out polarity setting programmable host watchdog timer for host failure protection internal watchdog timer for device failure protection easy programming by software easy installation and wiring DO 6 u DI n TTL Device 1 u Watchdog/Power Failure Supervisor GND DI6 6000 Series Discrete Input/Output Modules 6. Command Set There are three categories of NuDAM commands. The first is the general commands, including set configuration command, read configuration, reset, read module‘s name or firmware version, etc. Every NuDAM can response to the general commands. The second is the functional commands, which depends on functions of each module. Not every module can execute all function commands. The third is the special commands including functions about the programmable watchdog timer, safe values, and the programmable leading code. All the commands used in the NuDAM discrete input/output module are list in the following table. Command General Command Set Configuration Read Configuration Read Module Name Read Firmware Version Software Reset Reset Status Functional Command Digital Input Digital Output Synchronized Sampling Read Synchronized Data Syntax %(OldAddr)(NewAddr) (InputRange)(BaudRate) (DataFormat) $(Addr)2 $(Addr)M $(Addr)F $(Addr)RS $(Addr)5 $(Addr)6 #(Addr)(ChannelNo)(OutDa ta) #** $(Addr)4 Special Command Read Command Leading Code Setting Change Command Leading Code Setting Set Host Watchdog / Safety Value Read Host WatchDog / Safe Value Host is OK I/O Polarity Setting Read Polarity Setting ~(Addr)0 ~(Addr)10(C1)(C2)(C3) (C4)(C5)(C6) ~(Addr)2(Flag) (TimeOut)(SafeValue) ~(Addr)3 ~** ~(Addr)CP(State) ~(Addr)CR * The module accepts calibration command, baud rate and checksum configuration setting under the DEFAULT* mode. * Please refer the manual in PDF file format in the CD for detail description of these commands. The Optimal Choice for Harsh Environment 7. ADLINK on the Internet The full version manual can be download from website http://www.adlink.com.tw/download/manual/index.htm#6000 Homepage: Service: Technical Assistance: http://www.adlink.com.tw service@adlink.com.tw NuDAM@adlink.com.tw Copyright ï›™ 2000 ADLINK TECHNOLOGY INC. TEL: 886-2-82265877 FAX: 886-2-82265717 Contents and sp ecification subject to change without notice.  NuDAM is a registered trademark of ADLINK TECHNOLOGY INC. Other brands of products are trademarks or registered trademarks of their respective holders. AM-ND6050-E1.00