Emergency lighting system with individual lamp monitoring Type ELS-SV Catalogue ELS/SV Sicherheitstechnik GmbH INOTEC a company with the target to create innovative and customer oriented solutions for the Emergency Lighting market. A dynamic team of highly professional and flexible employees covers all aspects regarding products, engineering and standards. Modern, technical products create world wide new standards, i.e. JOKER technology for Emergency Lighting Systems or the Dynamic Escape Routing concept realised in the D.E.R. System. Copyright: INOTEC Sicherheitstechnik GmbH, Ense Publications and copies, even partial, only with maufacturers permission. CH1 CH2 CH3 CH4 24V RTG B The ELS-SV emergency lighting system 3-4 ELS-SV and Joker technology 5-6 Installation sample 7 Central monitoring and data protection 8-9 Advantages of monitored systems 10-11 Components, technical data and specification text 12-15 Battery current and luminaire/ballast details 12 DPÜ - three phase monitor 12 MTB - mimic panel 12 SV - controller 13 SV - computer 13 ELS - SV emergency lighting system Batt.-Operation Operation Failure FS Page Electronic ballast's and SV-luminaire modules 14 Subject to technical changes 1 2 3 4 5 6 Content SL L N L N L N L N 230V / AC 50 / 60 Hz PE N L 15 output 1 2 3 4 N L PE N L PE N L PE N L PE Light Switch Remote Control Indicator Operation Menue Batt.-Operation Enter Failure Change Charging failure Test 3,15 AT 3,15 AT 3,15 AT 3,15 AT 3,15 AT ELS - SV The INOTEC emergency lighting system with JOKER - Technology The ELS - SV is the first ever built compact low load (480 Watt) emergency lighting system with JOKER - Technology. Features Supply and automatic function monitoring of upto 60 safety- and exit luminaries Operation of switched maintained-, maintained- and non-maintainedluminaries on one circuit Display of faulty luminaries with location (optional) Automatic function- and battery duration test of emergency lighting system with battery-circuit, internal circuits and every connected luminaire Display of failures, status information during normal operation and test conditions Selectable 1h or 3h operation time Compact and flexible Ideal for use within one fire-zone only Automatic function- and battery duration tests No data line required Connection possibilities to building managment systems or in-house central monitors Mix and match all possible switching modes on one circuit Easy to install Central battery replacement instead of time consuming changes on self-contained luminaries. High performance and safety-level due to decentralised installation Compact assembly, depth just 110mm Attractive, elegant housing with clear perspec door Centralised automatic failure info allows spot-on service 3 ELS - SV Control module, charger and change-over devices The free programmable control module with two-line liquid crystal display for plain text information has three main tasks: Every INOTEC emergency lighting system contains components guaranteeing, together with the connected luminaries, a maximum on function and safety. Monitor and control all internal functions and test-cycles, allow manual interaction Display all panel and luminaire information (failure and status info) Safe all information concerning tests, status of luminaries and panel for log-book purpose The display shows: Battery voltage Battery charging current Battery discharge current during test or emergency operation Charging failures - battery voltage to high / low - interrupted charge circuit - required duration test time not achieved Luminaire failure LED display the following mandatory status info: OperationBatt.-Operation (mains supply healthy) Operation Failure Battery operation 1 2 3 failure) 4 5 6 (test or mains FS 24V RTG B Failure (luminaire-, system- or mains Remote Control failure) The four push-buttons next to the display allow the programming of the system, the manual release of tests and the status- and failure interrogation for 230V / AC 50 / 60 Hz CH1 CH2 system. CH3 CH4The pre-set the individual tests SL L N L N L N L N (function-test usually every 7 PE days,N L battery duration test usually every 12 month) are free programmable. The Light Switch display textIndicator is adapted to the native language. The constant current charger 3 Amps is monitored via the control module. The battery recharging time is < 10 h. output Every1one of the devices 2 4 change-over 3 4 N L PE N L PE N L PE N L PE supplies up to 15 INOTEC safety- or exit luminaries. During mains supply 230V, 50/60Hz are present on the output; in emergency or test mode this supply comes from the battery pack. Charging failure 4 Operation Menue Batt.-Operation Enter Failure Change Charging failure Test 3,15 AT 3,15 AT 3,15 AT 3,15 AT 3,15 AT ELS - SV JOKER - Technology Joker-technology function Each ELS-SV change-over device is able to foster three differing luminaire switching modes on the same output at the same time (see page 4). In addition to the system, luminaries with Joker high frequency electronic ballast (common standard on INOTEC luminaries) or Joker switch modules, J/SV-module/S, for third party electronic ballast, must be used. These components allow the easy setting of monitoring address and luminaire mode. Advantages of the Joker-technology Cut down on installation time Simple design and engineering Higher load level for final end circuits Reduced installation material content (cable reductions, see page 6 - non-maintained mode, sense input) Switching mode settable on each luminaire Conventional installation requires 6 final end circuits circuit 1 circuit 3 circuit 4 circuit 2 The patented JOKER-technology of INOTEC reduces the design- and installation time and cuts down on material cost. The sample to the right shows the reduction on installation material and circuit layout. circuit 5 circuit 6 Conventional emergency lighting sys-tems and installations with the three possible standard switching modes maintained (DL)-, non-maintained (BL)- and switched maintained (gDL) mode, require 6 final end circuits to feed 9 luminaries in a part of the building shown. Joker-technology with 2 final end circuits circuit 1 circuit 2 The Joker-Technology reduces the number of circuits required. Our sample needs only 2 final end circuits to feed the same number of luminaries due to the fact that the operation of all switching modes on one circuit is possible. The maintained and switched main-tained luminaries are active during mains presence. During mains failure however, all luminaries will be switched on and supplied by the battery (see page 6). Maintained mode Non-maintained mode Switched maintained mode 5 ELS - SV Switching modes with JOKER - Technology Using the Joker-Technology the output of the ELS-SV system is set for maintained mode. The system changes to battery supply if mains supply fails. The luminaire modes are settable on the high frequency ballast (INOTEC J-EVG see page 14) or monitoring module (INOTEC J/SV-module see page 14). Maintained-, non-maintained- and switched maintained mode L N PE BL L PE N L sense - input from mains luminaire gDL sense - input PE WR1 J-EVG 4-13 SV tc tc=70°C max Betriebsart BL 3 4 DL 2 3 Adresse UN: 860 005 AC 230V 50 / 60Hz DC 176 - 264 V Temp.-Test NS Lampe: 4-13 W TL / TC / TCD- EL tc tc=70°C max INOTEC L+ λta:: 0,95 -15 bis 50°C EMC: gem./acc to EN 55015 L+ Geeignet für Anlagen gem. /acc. to EN 50172 3,15 AT LS LS 4-13 SV/S 2 3 AC 230V 7 8 INOTEC 0,95 ta: BL (-15 bis 65°C) DL (-15 bis 50°C) EMC: gem./acc to EN 55015 Geeignet für Anlagen gem. /acc. to EN 50172 J-EVG Zehner Einer 9 0 1 9 0 1 9 0 1 7 8 Temp.-Test AC 230V 50 / 60Hz DC 176 - 264 V NN- In λ: 860 004 4 5 6 Adresse UN: J-EVG 4-13 SV/S 1 2 J-EVG 4-13 SV 4 5 6 4 5 6 4 5 6 In L+ L+ 2 3 2 3 Lampe: 4-13 W TL / TC / TCD- EL Zehner Einer 7 8 NN- 9 0 1 230V / AC 50 / 60 Hz 7 8 N DL Betriebsart BL 1 2 NS 3 4 DL J-EVG 4-13 SV 9 0 1 2 3 4 5 6 7 8 In Adresse UN: J-EVG 4-13 SV 860 004 7 8 9 0 1 2 3 4 5 6 DC Zehner Einer Temp.-Test AC 230V 50 / 60Hz DC 176 - 264 V tc tc=70°C max INOTEC L+ λta:: 0,95 BL (-15 bis 65°C) DL (-15 bis 50°C) EMC: gem./acc to EN 55015 L+ Geeignet für Anlagen gem. /acc. to EN 50172 Betriebsart BL DL 1 2 Lampe: 4-13 W TL / TC / TCD- EL NN- 3 4 DC 10 AT 24V / Pb Maintained light (DL) Exit- and safety luminaries in maintained mode light in any Batt.-Operation operational state. Under mains Operation conditions they are supplied with Failure 1 2 350/60Hz 4 5 6 viaFS 24V RTG B 230/240V the change-over device and the output terminals (WR1-L,N,PE) Remote In the event of a mains failure theControl change-over contact switches to the battery side, the 24V battery voltage is converted into a higher DC voltage andOperation feeds the luminaries. 6 Non-maintained light (BL) Safety luminaries in non-maintained mode only light when the normal lighting fails (mains failure) or230V during a / AC manually or automatically released test 50 / 60 Hz CH1 CH2 CH3 CH4 SL L N L Nbattery L N L duration N PE N The L (functionor test). BL-setting of the electronic ballast blocks theLight function in mains supply. Switch Mails failure or test trigger the system Indicator to change over to battery supply. The converted DC voltage feeds now the lamp via the J-EVG or J/SV-module. Switched maintained light (gDL) Safety luminaire operating in switched maintained mode light up output if the 1 general2lighting3is switched 4 on N L PE N L PE N L PE N L PE if the mains supply fails during a manually or automatically released test. Menue Batt.-Operation Enter Failure Change Charging failure Test The "sense-input" (short cable runs to the next mains luminaire) allows the ballast to be active along with the normal mains luminaries. A general mains failure always triggers the ballast to work with the converted battery voltage. 3,15 AT 3,15 AT 3,15 AT 3,15 AT 3,15 AT ELS - SV Installation sample Sample with two 3-phase monitors, mimic panel and switched maintained output via light-switch monitor (LA4) L1 L2 L3 N PE L1 L2 L3 N PE UV/DB1 UV/DB2 DPÜ U< DPÜ U< light switch Betrieb Batt.-Betrieb Störung Aus MTB 14 14 14 14 13 13 13 13 5 5 5 5 4 4 4 4 3 3 3 3 2 2 2 2 1 1 1 1 mains 230V AC light switch light switch light switch mains luminaries remote switch 24V output batt.operation 1 2 3 4 5 6 F+ F– 24V G T R B B SL SL L N L N L N L N – + + – LA1 LA2 LA3 LA4 PE N operation 15 Ein 3 3 3 3 3,15AT failure 15 Fernschalter data line INOTEC 15 general lighting general lighting Meldetableau Notlicht 15 Mains operation Mains failure Charge fault Luminaire failure Deep discharge activated Function test Duration test 1/2 3/4 5/ 6 closed open open open closed closed closed closed open open open open open open open closed open open open closed closed 3,15AT 3,15AT N L PE N L PE N L PE N L PE WR 1 WR 2 WR 3 WR 4 L ELS/SV Terminal rail Voltfree contacts, max 24V, 3A AC/DC, external supply Mains operation 3,15AT RTG-data line Max. cable run Remote switch F+ / F- 3 x 0,5mm² 1000m Closed: 3 x 1.0mm² 1500m emergency function possible 3 x 1,5mm² 2000m Open: system blocked 7 ELS - SV Functiontest: Durationtest: Status Data line Em-light Systems Central monitoring and data-protection Button Operation Select Seminar room Button Operation Seminar room Button Operation Functions System 3 Information of INOTEC-standard SVPC can be found on page 13. Button Data line The data-line picture gives the general status per line. Each systems unique status is displayed on separate frames in the next level. Failures, i.e. lamp faults, are displayed in red. Com-Port Com-Port Functiontest: Durationtest: Status Data line Em-light Systems Luminaire status Battery status Seminar room Location SV - PC software for max. 2 x 32 systems (ELS / LPS / CPS Button Status Operation System address Systemtype Selection Button Button Luminaire location Workshop, mid-section Toilett-women, gf Kitchen Toilett-men, gf Main dist.-board Em Exit, corridor gf Back 230V 50/60HZ Workshop, left section Sales dept. Safe Mode manuel reset automat. FT Corridor, first floor Delivery/packing Stores Corridor basement RS blocks M-light RS blocks M-light and NM automat. DT Time delay 8_min. Button Log book No. Date 512 04.04.01 13:13 1 1 Operation 513 04.04.01 13:13 1 1 Operation 514 04.04.01 13:14 1 1 Sub.-dist. failure 515 04.04.01 16:25 1 1 Operation 516 04.04.01 16:26 1 1 Sub.-dist. failure 517 04.04.01 16:28 1 1 Funktiontest o.k. 518 04.04.01 09:16 1 1 DT interrupted Total no. 520 Time Address System Found 520 Event Selection Back F6 = Screen off FS 24V RTG B All stored log-book entries can be selected in various levels, i.e. display only lamp failures. Storage on disc, status- or luminaire failure print-out is always possible. Button Funktiontest Operation Address System Setting Durationtest Failure Sub.-db Charge failure Failure main-db From Date To D Transmission failure Blocked Manual reset ISO-failure Em-light Discharge protection System status Batt.-Operation F5 = Run manual 1 2 3 4 5 6 RTG interface Button F10 = Setting Operation Failure RTG interface Help Current: +0,0 A Voltage: 27,2 V Batterie circuit o.k. Functiontest: Durationtest: Status Data line Em-light Systems 230V 50/60HZ Button SL Button L N Button output 230V / AC 50 / 60 Hz CH1 CH2 CH3 CH4 L N Stores L N Functiontest: Durationtest: Status Data line Systems Workshop PE L N N L 1 2 N L PE N L PE 3 Selection N L PE Button Light Switch Remote Control As an option INOTEC offers the programming of a building plan including all safety and emergency Operation luminaries. This feature allows easy localisation of failures and gives, after Batt.-Operation releasing a print-out, even service Failure personal unfamiliar with the site a simple and fast orientation possibility. Charging failure 8 Indicator Women Office Layout Kitchen Men Button Sales dept. Seminar room Back Menue Button Enter Engineering Sekrt. MD Help Change Test 3,15 AT 3,15 AT 3,15 AT 3,15 AT 3,15 AT 4 N L PE ELS - SV Central monitoring and data-protection From SV-central or PC 15 15 15 15 14 14 14 14 13 13 13 13 5 5 5 5 4 4 4 4 3 3 3 3 2 2 2 2 1 1 1 1 Log book No. Date Time 1 12.06.01 14:53 Functiontest failure System typ:ELS Address: 3 Location:INOTEC Seminar room Current: -0,00 A Voltage: 0,0 V Module: 1 Luminaire failure 4: Toilett Women 2 12.06.01 15:00 Functiontest o.k. System typ:LPS 24 Address: 2 Location:INOTEC Seminar room Current: -0,00 A Voltage: 0,0 V 3 12.06.01 15:00 Functiontest o.k. System typ:ELS/SV Address: 3 Location:INOTEC Seminar room Current: -0,00 A Voltage: 0,0 V 4 12.06.01 15:27 Funktionstest failure System typ:CPS Address: 1 Location:INOTEC Seminar room Current: -0,00 A Voltage: 0,0 V Circuit failures: Module: 1/2 Typ: SU/SV 2x3A Luminaire failure: Corridor Date: 26.07.2001 Time: 08:59:22 Page: 001 SV-central for up to 32 systems L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE UV/DB1 UV/DB1 UV/DB1 UV/DB1 UV/DB1 DPÜ U< DPÜ U< DPÜ U< DPÜ U< DPÜ U< SV-central or PC L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE L1 L2 L3 N PE UV/DB1 UV/DB1 UV/DB1 UV/DB1 UV/DB1 DPÜ U< DPÜ U< DPÜ U< DPÜ U< DPÜ U< 9 ELS - SV Advantages of monitored emergency lighting systems Reliable emergency lighting requires a well thought concept. Engineering projects always create the same questions on installation, cost efficiency and connection to building management systems coming to the emergency lighting design. INOTEC Sicherheitstechnik offers experience, know-how and outstanding technical products. Investscosts Luminaries+ Em-light system To produce light and illuminate all exit paths sufficiently - these are the main features for emergency lighting systems in case of a mains fail condition or in an emergency situation. The building owner has to make certain, that these functions are perfectly working - even after years. kwh Energy costs Regular tests, maintenance and service are one backbone to ensure reliable function of all emergency lighting system components. Labour costs visual check Inline with national standards regulare visual checks, functiontests and system duration tests have to be performed. Test data and all relevant system information must be kept in a log-book. Lamps must be replaced and new batteries have to be installed. Visual test Routine test FT + + . Material costs - CH1 CH2 CH3 CH4 FS 24V RTG B To limit the expected costs and freeze the safety level at the highest point we use the INOTEC SV-monitoring system. Remote Control Emergency lighting systems and connected components bearing this prefix test and monitor themselves. The results can be displayed, printed or Operation stored. Labour costs FT/DT Lamps Battery Failure 10 - Lighting system costs DT This can create, depending on the building size and the installed system, quite substantial costs. The long-term spending sometimes outrun the initial costs by a long way. This should be considered to find the most favourable solution when starting the project Batt.-Operation engineering. Operation 1 2 3 4 5 6 Operation costs Labour costs for testing SL L N L N L N L N 230V / AC 50 / 60 Hz PE N L Maintenance output 1 N L PE Maintenance costs 2 3 4 N L PE N L PE N L PE Light Switch Indicator + - Labour costs Menue Batt.-Operation Enter Failure Change Charging failure Test 3,15 AT 3,15 AT 3,15 AT 3,15 AT 3,15 AT ELS - SV Advantages of monitored emergency lighting systems To create the monitoring as efficient and cost effective as possible data lines to monitor the luminaries are not required. L N I I Central Monitoring and data protection Location of emergency lighting systems The availability of information on the systems location is sufficient for smaller installations - larger objects need a more complete and complex approach. To find a good and safe location for an emergency lighting system is part of every planning. National standards have to be observed. I Each SV-system offers the possibility to centralise all data and display/store the information at one location only. The functional safety is, apart from short cable runs, ease of access and good display visibility, a major focus point. Each SV-emergency lighting system with all the connected luminaries will: monitor battery and charger permanently function test all components (e.g. lamps, electronic ballast's, system modules…) periodical automatically initiate the battery duration test (e.g. annually) and handle all events, information and results by logging and/or printout all system related data display any function failures and status information Smaller objects with a limited number of emergency lighting systems are ideal for the SV-Central (see page 9). Up to 16 systems can supervised including storage of all status/failure info, location of each connected luminaire and a logbook function. The included printer port allows selective or complete printout of data. The location text function for each luminaire is not possible if more systems (max. 32) are connected to one SV-Central. If a graphic display surface or the supervision of more than 16 panels including logbook function and individual luminaire location text is necessary, the SV-PC or a SV-PC software/interface package is the solution (see page 8). Building layout drawings with incorporated luminaire locations are available as well. Even the connection to a building management system or the transmission of information / service details of SV-systems via modem are part of the INOTEC product range (see page 13). The ELS-SV is designed for low load, to supply a small number of luminaries within a buildings fire zone. To install the ELS within the zone has the advantage, next to ease of access and short cable runs, of a high safety level for the complete building. Should a final end circuit fail, due to a local fire or a luminaire/line short circuit, no other circuit of the ELS will be effected. If the ELS is used to supply a circuit crossing various fire zone, or feeding luminaries in more than one zones, short circuits and failures of the system have an impact on the per-formance of luminaries in still safe or not endangered areas. The use of fire resistant cable is recommended for this application. E 30 Zone 2 Zone 1 11 ELS/SV Components and technical data DPÜ - Three Phase Monitor MTB - Mimic Panel MTB - Mimic Panel To detect phase- or circuit failures in general lighting sub-distribution panels With volt-free failure indication contact Three LED, controlled via volt-free ELS contacts, indicate - mains operation - battery operation - sum-failure Three LED, controlled via volt-free ELS contacts, indicate - mains operation - battery operation - sum-failure · LED-indication for L1, L2, L3 · free selectable phase connections · 1 change-over contact · monitoring low voltage and mains failure in three-phase networks · for single-phase monitoring too acc. to IEC 255 · for DIN rail mounting For the connection to INOTEC central- and group supply battery systems. Voltage: 230V/400V AC 50/60 Hz Threshold 0,85 x UN Perm. temp.: -20°C ... +60°C EMC protected to 55015 Dimension: H =58, W = 17,5, D = 90(mm) These LED-indicators are, even in case of a mains failure, supplied from the ELS-SV. Key switch with free programmable functions - maintained light On/Off - emergency light On/Off These LED-indicators are, even in case of a mains failure, supplied from the ELS-SV. Protection class: IP54 Key switch with free programmable functions - maintained light On/Off - emergency light On/Off For wall mounting Protection class: IP20 Dimensions: H=110, W=200, D=115 (mm) For recessed wall mounting Dimensions: ø 90 (mm), D = 6,5 mm 115 45 Betrieb Batt.-Betrieb Ein 74 90 58 47 165 Notlicht Störung Aus INOTEC 17,5 70 200 90 Safe-Mode with INOTEC-EVG`s Programming for 3 h max discharge current 17Ah=4,3A/34Ah=8,6A Power-Mode with INOTEC-EVG´s Programming for 1 h max discharge current 17Ah=10A / 34Ah=20A, Imax =6A circuit EVG-Type Lamp Load EVG 4-6 SV EVG 4-13 SV T16 4W Light output ratio 70% 1 Lamps 0,31 2 Lamps 0,49 3 Lamps 0,66 4 Lamps 0,83 5 Lamps 1,00 6 Lamps 1,18 7 Lamps 1,35 8 Lamps 1,53 9 Lamps 1,70 10 Lamps 1,87 11 Lamps 2,05 12 Lamps 2,22 13 Lamps 2,37 14 Lamps 2,56 15 Lamps 2,74 12 T16 6W 70% 0,40 0,67 0,93 1,19 1,45 ,72 1,98 2,24 2,50 2,77 3,03 3,29 3,55 3,82 4,08 EVG 18SV 6,5 N-EVG 36/100 T16 TC-DEL TC-EL TC-DEL T16 TC-DEL TC-DEL T26 8W 10W 11W 13W 18W 18W 26W 32W 70% 100% 100% 100% 100% 100% 100% 100% 0,51 0,71 0,72 0,83 1,02 1,12 1,56 1,88 0,88 1,28 1,31 1,52 1,91 2,10 2,97 3,63 1,25 1,86 1,89 2,22 2,79 3,08 4,39 5,37 1,62 2,43 2,47 2,91 3,67 4,06 5,81 - - 1,99 3,00 3,05 3,60 4,55 5,04 - - - - - 2,36 3,57 3,64 4,29 5,44 - - - - - --2,73 4,14 4,22 4,98 - - - - - - - - - - - 3,10 4,72 4,80 5,68 - - - - - - - - --3,47 5,29 5,39 - - - - - - - - - - - --3,84 5,86 5,97 - - - - - --- --- --4,22 - - - - - --- --- --- --- --4,59 - - - - - - - - - - - - - - --- --4,96 - - - - - --- --- ----- --5,33 - - - - - --- ----- --- --5,70 - - - - - --- --- ----- --- N-EVG 58/100 T26 50W 100% 2,86 5,59 --------------------------- EVG 4-6 SV EVG 4-13 SV EVG 18SV T16 T16 T16 TC-DEL TC-EL TC-DEL T16 TC-DEL 4W 6W 8W 10W 11W 13W 18W 18W 32% 32% 32% 50% 50% 50% 50% 50% 0,24 0,34 0,44 0,54 0,64 0,74 0,84 0,94 1,04 1,14 1,24 1,34 1,44 1,54 1,64 0,28 0,41 0,55 0,68 0,82 0,95 1,09 1,22 1,36 1,49 1,63 ,76 1,90 2,03 2,17 0,31 0,48 0,65 0,82 0,98 1,15 1,32 1,49 1,66 1,83 2,00 2,17 2,34 2,50 2,67 0,43 0,71 1,00 1,28 1,57 1,86 2,14 2,43 2,71 3,00 3,29 3,57 3,86 ----- 0,43 0,73 1,02 1,32 1,61 1,91 2,20 2,49 2,79 3,08 3,38 3,67 3,96 ----- 0,48 0,82 1,16 1,50 1,84 2,18 2,52 2,86 3,20 3,55 3,89 --------- 0,58 1,02 1,46 1,91 2,35 2,79 3,23 3,67 --------------- 0,63 1,12 1,61 2,10 2,59 --------------------- ELS/SV Komponenten zur Überwachung und Datensicherung mit Technischen Daten SV - Central SVPC Software / Interface Package J-ET 9/24 SV -Free programmable microprocessor controlled unit for max. 32 emergency lighting systems, c/w - four line liquid crystal display for status and failure info in plain text - four status / failure display LED - manual release / interruption of function (FT) - and battery duration (BT) test - automatic release of FT and BT - data bus (RTG) terminals 2,5mm² - suitable for ELS, LPS and CPS - programming, interrogation and supervision of all connected systems - keyboard interface for programming - centronics interface for external printers - logbook function; for up to 16 ELS-SV with individual luminaire location text - battery back-up during mains failure RTG-interface and PC-software for monitoring up to 32 emergency lighting systems ELS, LPS or CPS on one data line. Constant current luminaire module for the supply and monitoring of LEDs. Software Anforderungen: Windows 9X / NT/ 2000 / XP, serial interface, monitor 640 x 480 pixel, Pentium prozessor, 8 MB-RAM, hard drive 2 GB. The interface will be delivered with 230 V mains cable, Euro-plug, RTG data line and serial interface cable with plug. With easy accessible address-switch and Displayed information covers - mains operation - battery operation - sum-failure - charge failure - function test running - battery duration test running - blocked system - printer off-line - printing failure - luminaire failure for each individual system Active manual release / interruption of - function test - battery duration test for all connected systems and the complete data line. 90 145 97 The software automatically releases the required function- and battery duration test. Programming the SVPC allows to download the information (luminaire location, switching modes…) to each installed emergency lighting system (CPS,LPS,BNS). SVPC Software Options SVPC software "building drawing", to program and display building plans with location of emergency luminaires and emergency lighting systems. SV-Central, panel mounting, IP 20 cut-out 136 x 90 (mm), dimensions: H=97, W=145, D=155 (mm) 136 The software is used to monitor, display, store, download or print all relevant data of the complete emergency lighting installation. The configuration of each system and the complete installation is stored along with a complete log book of all events / failures. The log book contains details as location, failure type / date / time and allows selected visualising or partial / complete printing. Light output in mains adjustable. JOKER function, switch to select maintained or non-maintained mode and individual light source failure detection For the connection to INOTEC central- and group supply battery systems. Input voltage: 230V AC 50/60 Hz 220V DC ±20 % Output voltage: 24V DC Output current: 320 mA constant Perm. temp.: -15°C ... +50°C EMC protected to EN 55015 Dimension: H = 28, W = 40, D = 90(mm) Qty. LED Bat.-current Luxeon consumed 15 mA 1 20 mA 2 3 25 mA 4 30 mA 5 35 mA Load P/W 3,1 4,2 5,3 6,4 7,6 SVPC "timer" software, to program periods where the emergency lighting system is blocked (during unoccupied periods like weekends, holidays, bank holidays or night time) to save energy. 155 SV-Central, for wall mounting, IP 54 dimensions : H=237, W=255, D=250 (mm) SVPC "bms" software, for data transmission of 24V interface contact details to building management system. 85 237 SVPC "modem" hardware/software-option to gain access to log book and current system status info via phone, Advantageous for central service points. 255 235 13 ELS/SV Electronic ballast's and SV-luminaire modules with JOKER-Technology J-EVG 4-6 SV J-EVG 4-13 SV J-EVG 18 SV Compensated high frequency electronic ballast J-EVG 4-6 SV/S J-EVG 4-13 SV/S J-EVG 18 SV/S Compensated high frequency electronic ballast for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. The JOKER function allows luminaries to be operated in maintained and non-maintained mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low poweror central power battery systems like ELS or CPS. for fluorescent and compact fluorescent lamps TL/TC/TCD-EL 4-18 W, with easy accessible address switch, JOKER function and individual lamp monitoring. This electronic ballast features a sense-input or an inverted phase monitor too. J-EVG 4-6 SV designed for low power loss at 4 Watt. The JOKER/S function allows luminaires to be operated in maintained, non-maintained and switched mode on the same final end circuit. Automatic deactivation of electronics in case of lamp failure. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaires. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230V AC 50/60 Hz 220V DC ±20 % Perm. temp.: -15°C ... +50°C EMC protected to EN 55015 J-SV-Modul/S J-SV-Modul.2/S J-SV-Modul.3/S J-SV-Modul.4/S J-SV-Modul.L/S Single luminaire monitoring module for fluorescent- (T16/T5…) compact fluorescent, halogen and incandescent lamps. With easy accessible address switch, JOKER function and individual lamp monitoring. This module features a sense-input or an inverted phase monitor too. The JOKER/S function allows luminaries to be operated via these J-SV-modules in maintained, non-maintained and switched mode on the same final end circuit. Suitable for emergency lighting systems to EN 50171 / EN 50172. Designed to be installed inside of luminaries. For the connection to INOTEC low power- or central power battery systems like ELS or CPS. Voltage: 230V AC 50/60 Hz 220V DC ±20 % Voltage: 230 V AC, 50/60 Hz 220 V DC, ±20 % Perm. temp.: -15°C ... +50°C EMC protected to EN 55015 Perm. temp.: -15°C ... +50°C EMC protected to EN 55015 30 3 80 90 26,4 J-EVG 4-6/SV-S J-EVG 4-13/SV-S J-EVG 18/SV-S 80 90 7 240,4 17,9 J-SV Modul.L/S J-SV-Modul.L/S 235,4 249,4 4,2 40 4 40 4 3 28 4,2 J-EVG 4-6/SV J-EVG 4-13/SV J-EVG 18/SV J-Modul/S J-SV Modul/S J-ET 9/24 SV Individual lamp monitoring Component Type J-EVG 4-6 SV EVG J-EVG 4-13 SV EVG J-EVG 18 SV EVG J-EVG 4-6 SV/S EVG J-EVG 4-13 SV/S EVG J-EVG 18 SV/S EVG SV Modul.1 SV Modul.2 J-SV Modul/S J-SV Modul.2/S J-SV Modul.3/S J-SV Modul.4/S J-SV Modul.L/S 14 Modul Modul Modul Modul Modul Modul Modul Joker technology yes yes yes yes yes yes Load 4-6W 4-13W 18W 4-6W 4-13W 18W Sense-input no no no yes yes yes no no yes yes yes yes yes 5-120W 20-300W 5-120W 20-300W 2-30W 18-120W 5-120W no no yes yes yes yes yes Treshhold Failure < 10mA < 45mA < 10mA < 45mA < 8mA < 45mA < 10mA O.k > 20mA > 70mA > 20mA > 70mA > 12mA > 70mA > 20mA Order number 860008 860004 861003 860010 860005 861004 851001 851003 851002 851004 851025 851029 851026 ELS - SV 870 785 850 Specification text and technical data 325 100 400 INOTEC ELS-SV emergency lighting system with Joker-technology, for the supply and monitoring of up to 60 safety- or exit luminaries. Each outgoing circuit is for 15 luminaries in maintained, non-maintained or switched maintained mode either mixed or in one mode on the line. The ELS/SV system incorporates: - battery for 1h or 3h duration - charger - 4 converters, each suitable for 15 monitored luminaries, max. converter load 120W. - control module with two-line liquid crystal display for status information in national language - light-switch-monitor and Joker- technology - delay on mains return option (0 - 15 min) Mains supply: 230/240 V AC Output voltage mains: 230/240 V AC Output voltage battery: 220 V DC Rated duration: 1h or 3h Protection class I, protection category IP 40 Max. permissible ambient temp. : -5°C to +40°C Weight: With 17 Ah batteries 32kg With 34 Ah batteries 46kg Mechanical design: Powder coated (RAL 7032) sheet steel housing with separate battery compartment. OCTA-aluminium profile door with clear polycarbonate inlay, lhs door hinges. Separate internal covers for battery-, terminal- and electronic compartment. Block diagram with technical data on electronic compartment cover. Housing with internal earth contacts. Cable inlets top. Battery and terminal / electronics compartment with ventilation slots. The ELS-SV is suitable for wall mounting (fixing details 325 x 765 mm; hole ø 6 mm). 105 420 Electrical design: Supply- (max. 1 x 4 mm² ) and outgoing circuits (max. 2 x 2,5 mm² ) are prewired to terminals located on the central terminal rail. The cable inlets on the top of the enclosure are predrilled and closed with rubber blind plugs M20. Battery- and mains fuses for charger and each converter are included. Creepage- and clearance distances are in line to IEC standards. Three volt-free contacts (3xno) for the remote failure/status indication are available. Maintained and non-maintained circuits can be freely programmed via the control module. Mixed operation of maintained-, non-maintained- and switched maintained luminaries on any final end circuit (Joker-technology) is always possible. 24 V monitoring loop Each ELS-SV has the terminals to connect external phase monitors (DPÜ). They are used to monitor sub-distributions for general lighting or individual lighting circuits. The max. cable run allowed is 2000m with 1,5 mm². Charger 3A: Temperature controlled constant voltage charger, current limited, with boost charge function. Battery voltage monitoring and time -controlled trickle charge function. Chargers failures are visual via a red "charge failure" LED on the left side of the display area. Recharge time: <10h. for 17Ah and 34 Ah battery-sets. DC/DC converters: No-load and short -circuit-proof, internally monitored, constant load limit 120 W. Individually fused. Control module: Free programmable control module with two-line liquid crystal display, constant memory for two main functions: - display of actual luminaire / ELS-SV status - supervision and control of all system functions and test cycles. Displayed information includes: - function test - luminaire failure - battery duration test - battery current in test- and emergency mode - battery - charge current - rated duration time not achieved - charger failure - interrupted battery circuit - deep discharge protection "ON" Automatic tests are free programmable and can be released and stopped manually. Four LED indicate: - mains supply present/missing (green on/off) - luminaire- or system failure (red) - battery operation, test or emergency (amber) - battery- or charger failure (red) Central monitoring and remote information display: Each ELS-SV has 3 RTG-terminals for data-bus connection to other emergency lighting systems or a central supervising point. The total data bus length is for 3 x 1,5 mm² 2000m. Suitable central monitoring systems include mimic panels MTB, SV-controller, RTG interface/software package or a SV-PC-unit for central display and logging of configuration, test and failure information for all connected systems. Total ( H x W x D) 870 x 420 x 105 mm 15 Ausgabe 2007/01 INOTEC Sicherheitstechnik GmbH Am Buschgarten 17 D - 59 469 Ense Tel Fax 0 29 38/97 30-0 0 29 38/97 30-29 info@inotec-licht.de www.inotec-licht.de Sicherheitstechnik GmbH