Technical specification

advertisement
UGVCL-Specifications
Distribution Transformer
Distribution Transformer
Seal & Signature of Bidder
Page 1
UGVCL-Specifications
Distribution Transformer
Contents
1. Introduction
2. Code and Standards
3. System Description
4. Design Criteria
5. Specific Requirement
6. Tank
7. Cleaning & Painting
8. Cable End Boxes
9. Oil
10. Drying Out
11. Clamping of Leads
12. Phase Marking
13. Core & Coil
14. Insulation level
15. Losses
16. C.T.’s with accessories
17. Fittings and accessories
18. Tests
19. Contract Drawing
20. Conditions and Requirements
21. Inspection
22. Details in Data Sheet
23. Deviations
24. Schedules
Seal & Signature of Bidder
Page 2
UGVCL-Specifications
Distribution Transformer
1.
Introduction
1.1
UGVCL for their requirement of conversion of 11 kV overhead systems to
underground system for various areas need to procure 11000/433 voltage, oil
immersed distribution transformers. Qualified suppliers having state of the art
production facilities with R&D and adequate experience for at least 10 years in
supplying distribution transformers in India or comparable emerging countries.
1.2
It is not the intent to specify completely herein all the details of the design and
construction of material. However the product for supply shall confirm in all respects
high standards of Engineering, design and workmanship and shall be performing in
continuous operation in manner acceptable by the purchaser. The offer material
shall be complete with all components necessary for the intended purpose. The
design and components shall be deemed to be within the scope of vendor’s supply
irrespective of whether those are specifically brought out in this section and or the
commercial order or not.
2.
Code and Standards
2.1
All equipments and materials shall be designed manufactured and tested in
accordance with the latest applicable Indian Standard, IEC standard and CBIP
manuals except where modified and or supplemented this specification.
2.2
Equipment and material confirming to any other standard, which ensures equal and
or better quality, may be accepted. In such case copies of English version to the
standards adopted shall be submitted and got approved prior to the supply.
2.3
The Transformer offered for supply shall in general comply with the latest issues
including amendments of the following Indian Standards but not restricted to it.
3.
Title
Distribution Transformer
Method of Construction
Thermal Evaluation and classification of Electrical
Insulation.
Fittings
&
Accessories
for
Distribution
Transformers
Guide for loading of Oil Immersed Transformer
Bushings for Alternating Voltage
Dimensions
of
porcelain
bushings
for
transformers
Insulating oil for transformers and switchgears
System Description:
Seal & Signature of Bidder
I.S.Code
IS:2026
IS:1271
IEC Standard
IEC:60076
IEC:60616
-
IS:3639
-
IS:6600
IS:2029
IS:2099/3347
-
IS:335
-
Page 3
UGVCL-Specifications
Distribution Transformer
The distribution transformers shall be installed at outdoor/indoor locations along 11
kV distribution networks, which consist of both underground and overhead
networks. The HV winding shall be connected of HT SFU/OCB/VCB/SF6 CB of the ring
main unit through 11kV (E) XLPE/PILC cable. LV winding shall be connected to switch
type fuse section pillar through 1.1 kV I core 300 mm2 Aluminium conductor XLPE
cable.
4.
Design Criteria
4.1
The transformers shall be installed in hot, humid tropical atmosphere. All equipment
accessories and wiring shall be provided to withstand the specified load and prevent
fungus growth.
4.2
The transformers shall be capable for continuous operation at rated output under
the operating conditions of voltage and frequency variations as per statutory limits
governed by relevant Indian Standard and Electricity Act 2003 and its amendments in
force.
4.3
The transformer shall confirm the best engineering practice.
4.4
The designed material shall be capable to secure reliability, economy, safe and
convenient operation and shall include all specified or unspecified incidental items
necessary for similar equipment for convenient working in every respect.
4.5
The transformers shall be capable of withstanding the short circuit stresses due to
terminal fault between phase to phase and phase to ground on one winding with full
voltage maintained on the other windings for a minimum period of three seconds.
4.6
The transformers shall be free from annoying hum and or vibrations. The design shall
be such as not to cause and undesirable interference with radio or communication
circuits.
4.7
Atmospheric Conditions:
The equipment offered shall be suitable for continuous satisfactory operation in
following prevailing climatic conditions.
Ambient Air Temperature
Relative humidity
Rainfall
Basic wind speed as IS:875
Seismic Zone
5.
47 degree C to 35 degree C
100% Maximum
700 mm
44 m/sec
4
Specific Requirement:
Seal & Signature of Bidder
Page 4
UGVCL-Specifications
5.1
Distribution Transformer
11000/433 Volt oil immersed, 63 kVA,100 kVA,160 kVA,200 kVA,250 kVA,315 kVA
ONAN cooled, double wound, core type suitable for installation on pad or pole with
LV/HV end termination boxes with appropriate air clearance for specified voltages.
Winding: For 63 kVA to 200 kVA Aluminium Winding.
For 250 kVA and above Copper Winding.
5.2
Voltage Ratio: No load voltage 11000/433 volts within tolerance as stipulated in IS:
2026.
5.3
Rating: The transformer shall have a continuous rating as specified at any of the
specified tapping position and with the maximum temperature rise specified. The
rated kVA shall be the product of rated voltage in kV, and the corresponding rated
current and the phase factor 1.732.When the transformer is operated with the rated
primary voltage applied to the terminals of the primary winding ,the apparent power
(kVA) at the terminals of the secondary winding, when carrying the rated secondary
current differs from rated kVA by an amount corresponding to the regulation of the
transformer and is the product of the actual secondary voltage, the rated secondary
current and the phase factor 1.732.
5.4
System:
11000 volts A.C.,50 Hz supply having non effectively earthed
neutral(resistively earthed) system on HV side/ The 11kV systems shall have basic
insulation level of 28 kV for one minute/95 kVp impulse and maximum fault level of
26 kA. 433 volts A.C,50 Hz supply shall be rated for 1.1 kV grade and basic insulation
of 3 kV for one minute and 7,5 kVp impulse. The variations in input and output
supply shall be as per statutory variation governed by reluctant Indian Standard and
Electricity Act 2003 with latest amendments in force. The LV neutral shall be earthed
solidly at each transformer substation. The transformers will be connected in a
system consisting of both overhead and underground mains.
5.5
Temperature Rise: The maximum temperature rise at the specified maximum
continuous output shall not exceed 35 degree C by thermometer in the hottest
portion of the oil or 40 degree C measured by resistance of winding above ambient
temperature of 47 degree C.
5.6
Type of load: The transformer shall be suitable of carrying load within temperature
rise indicated in the Indian Standard specifications IS: 6600 `Guide for loading of oil
immersed Transformer.’
5.7
Overloads: The transformer shall be suitable for carrying overload within
temperature rise indicated in IS: 6600 `Guide for loading of oil immersed
Transformer.’
Seal & Signature of Bidder
Page 5
UGVCL-Specifications
Distribution Transformer
5.8
Connections: H.V Delta and L.V Star connected with neutral brought out on the
secondary side for connection to earth’ Vector group Dyn11 of IS: 2026.
5.9
Guarantee: All transformers shall be supplied with guarantee period of 5 years from
date of commissioning of transformer. Any deficiency during guarantee period will
be made up free of cost by the supplier either by the replacement or by repairs.
6.
Tank:
6.1
The transformer tank and cover shall be fabricated from robust M.S. plate steel
without pitting and shall have adequate thickness (Top cover 5 mm min., side plates
3.15 mm min. Bottom plate 5mm min.) with either external cooling tubes or
radiators as per purchaser’s requirement. The tank and cover shall be of welded
construction. All seams shall be welded and where practicable they shall be double
welded. All edges shall be double welded/ the tank wall shall be reinforced by stiffer
to ensure rigidity, so that it can withstand without any deformation the mechanical
shock during transportation.
All removable covers shall be provided with weather, proof, hot oil resistant,
resilient gaskets. The design shall be such as to prevent any leakage of water into or
oil from the tank.
6.2
The tank shall be subjected to a pressure test of 6.35 kg/cm2 with hot oil for 12
hours when transformer is complete with all fittings. During the test average oil
temperature of 45 degree C above ambient temperature shall be maintained
throughout test period by circulating suitable current in H.V winding and short
circulating L.V winding. There shall be no leakages during and after the test. No
deflection shall be found after the removal of pressure. The tests shall be carried out
in presence of purchaser, otherwise test Certificate in triplicate shall be produced
before dispatch of the consignment.
6.3
The top cover of the tank shall be suitably sloped to facilitate water drain off and
shall be so designed as to facilitate lifting of the same. In case required with
minimum disconnecting of pipe work and accessories. Air release plugs shall be
provided on main tank top cover to cover entire area suitably.
6.4
The color of the finishing coats shall be dark admiral gray confirming to No:-632 of
IS-5 of 1961.
7.
Cleaning & Painting.
7.1
All steel surfaces shall be thoroughly cleaned by Sand blasting or chemical agents, as
required to produce a smooth surface free of scales, grease and rust.
Seal & Signature of Bidder
Page 6
UGVCL-Specifications
Distribution Transformer
7.2
The terminal surfaces in contact with insulating oil shall be painted with heat
resistant and insulating –Oil resistant paint, which shall not react nor be soluble in
the insulating liquid used.
7.3
The external surfaces , after cleaning, shall be given two coats of high quality rust
resisting primer as per IS:2074 with latest amendments thereto followed by two
coats of weather resisting battleship poly urethane paint specially recommended for
transformer use.
7.4
Paints shall withstand tropical heat rain, and other environmental effects. The paint
shall not scale off or crinkle or removed by abrasion due to normal handling.
7.5
Sufficient quantity of paint shall be furnished for touching if any on site.
7.6
Rusting of hardware such as nuts, bolts and fittings during operation shall be avoided
by applying anti rusting solutions. All bushings and current carrying parts shall be
cleaned properly after final painting.
8
Cable End Boxes.
The transformer shall be fitted with suitable end termination boxes on 11 kV side to
terminate one 11 kV/ 3 core Aluminum conductor XLPE/PILC cable up to 300 mm2
size as per drawing. The HT cable box shall be prevented from ingress of moisture
into the box due to rainwater directly falling on the box. The H.T cable box shall be of
split type with plain faces and machined and fitted with suitable gasket and
complete with brass wiping gland to be mounted on separate split type gland plate
with nut bolt arrangement and M.S earthing clamp. The bushings of the cable box
shall be fitted with nuts and stem to take the cable cores without bending them. The
stem shall be of copper with copper nuts. The cross section of the connecting rods
shall be stated and shall be adequate for carrying the rated currents. On the HV side
the terminal rod shall have a diameter of not less than 12 mm. The material of
connecting shall be copper H.T Cable support clamp should be provided to avoid
tension due to cable weight. Required diameter of hole for cable entry shall be
provided.
The transformer shall be fitted with suitable LV cable end box having non-magnetic
material gland plate with appropriate size single compression brass glands as per the
attached drawing on LV side to terminate 1.1 kV/ 1 core XLPE armored cable as
mentioned herein below. Required diameter of holes for entry of LV 1 core 4 nos 300
mm2 XLPE cable shall be provided.
Terminal:
Primary: 12 kV Epoxy bushings as per IS: 2099 or Porcelain Bushings as per IS: 3347
as required by the purchaser for heavily polluted atmosphere having suitable
Seal & Signature of Bidder
Page 7
UGVCL-Specifications
Distribution Transformer
diameter with nuts and check nuts for pad and platform mounted transformer as per
drawing.
Secondary: Terminals shall be provided with 1.1 kV Epoxy bushings as per IS: 3347
for heavily polluted atmosphere having fixed palm type connectors with suitable
locking arrangement to restrict the rotation of palm assembly. Palm shall be of
copper and stud of copper duly brazed at the joint.
Suitable clamps with nuts and bolts for 1 core 300 mm2 XLPE/ PVC cables as per
details given for different size of transformers. Detachable clamps with nuts and
bolts for ease of removing LV cables shall be provided with Epoxy bushings Clamp
arrangement with copper/brass terminal assembly.
9.
Oil:
9.1
Transformer oil as per IS: 335 for filling transformer tank up to height above
minimum level of conservator tank. All test certificates shall be supplied by the
supplier.
9.2
Leakage of Oil: Suitable approved material “Neoprene” of RC 70 C grade as specified
in IS: 1866 shall be provided at all joints to prevent leakage of oil during continuous
operation of the transformer/
10
Drying Out:
The transformer windings shall be thoroughly dried out and kept oil immersed to
avoid further drying out and to immediately commission the transformer on receipt.
11
Clamping of leads
All leads from the coils to the terminals shall be suitably clamped to prevent
snagging and fouling with other parts and the tank.
12
Phase marking:
Phase marking with proper alignment as per IS: 2026 punched on small non
corrosion metallic tags shall be permanently fixed for HV just below the cable box
and above LV bushings.
13.
Core and Coil:
13.1
Core type transformer with core built of high grade, non aging, low loss, high
permeability, grain oriented and cold rolled silicon steel laminations especially
suitable for core material. Premium grade M-OH of better quality with appropriate
thickness core lamination shall be provided. The transformer shall be designed for
minimum humming noise.
Seal & Signature of Bidder
Page 8
UGVCL-Specifications
Distribution Transformer
13.2
The coils shall be manufactured from electrolytic copper/Aluminum fully insulated
for rated voltage and purchased from original manufacturer.
13.3
Insulating material shall be class `A’ specified as per IS : 1271 with latest
amendments thereto. Coils shall be so insulated that impulse and power frequency
voltage stresses are minimum for 11 kV at primary and 433 volts at secondary
connected to feeders in a lightning prevalent area.
13.4
Suitable support between adjacent sections of coil assembly shall be provided with
required bracing and other insulation so that free circulation of oil is ensured and
reduce hot spot of the winding.
13.5
All leads from the windings to the terminal board and bushings shall be rigidly
supported to prevent injury from vibration or short circuit stresses. Guide tube shall
be used wherever practicable.
13.6
No shifting or deformation to core and coil assembly during transit of transformer is
allowed. The core and coil assembly shall withstand such thermal and mechanical
effects of short circuit at the terminals of any winding as per IS: 2026 with latest
amendments thereto.
14.
Insulation level:
The transformer shall be designed to withstand the following.
Voltage
Impulse Voltage(kVP)
11000
415
95
7.5
Power
(kV)
28
3
Frequency
Voltage
15. LOSSES & LEBELLING :
This tender is for purchase of 11 KV Distribution Transformer having Amorphous /CRGO core and
with Capitalization cost.
For -200 KVA Transformer.
The Methodology for computing Total owning cost is as under.
TOC (Total Owning cost) = IC+ (A X Wi ) +(B X Wc)
IC = Initial cost (without tax) of transformer as quoted by the bidder.
Wi = No Load losses quoted by the bidder in Watt
Wc = Load losses quoted by the bidder in Watt
A Factor = Cost of no load losses in Rs/ Watt = Rs. 183.23 /Watt
B Factor = Cost of load losses in Rs. / Watt = Rs. 101.33 /Watt
Seal & Signature of Bidder
Page 9
UGVCL-Specifications
Distribution Transformer
LOSSES & LEBELLING: It is mandatory that transformers having rating 200 KVA shall be 4 Star
as per the BEE Guideline and shall be labeled accordingly as per the gazette notification
Dtd.06.07.2009 of BEE.
The transformer losses at 75 degree C and at normal tap without any positive tolerance
should full fill the minimum requirement of Four star as recommended by Beuro of Energy
efficiency (BEE) in the rating of 200 KVA are stated here under.
Rating (kVA)
200
Load loss in watts at 100% Load losses in watts at 50%
loading
loading
2300
780
Note: These are maximum permissible values with no positive tolerance. The supplied
should see that the losses do not exceed the values otherwise the unit shall be rejected.
Note: (1) It is mandatory that transformers having rating 200 KVA shall be 4 Star as per the BEE
Guideline. Bidder has to submit BEE certificate with their offer for respective star rating.
Offer without BEE certificate will be outright rejected without any correspondence.
Evaluation criteria: 1. The tender bids will be evaluated on the basis of TOC (Total owning Cost) combined
for CRGO & Amorphous Core Transformer.
2. Bidder can offer CRGO or Amorphous core material but they have to specify clearly
in their offer and price bid must be submitted for respective core separately.
3. Bidder can also offer both CRGO as well as Amorphous core for same rating, but
they have to separately submit GTP for both core material Transformers and they
have to submit on line price bid separately for both core material. Bidder has to
clearly mention offer quantity with core material in ANNEXURE-4
4. Price evaluation will be calculated (i.e. L1, L2, L3, ___) on base of TOC (Total owning
Cost) and ranking will be given on the base of T.O.C. only.
5. Negotiation/Price matching will be carried out on the base of TOC Only.
6. Permissible band of minimum and maximum loss level of Distribution Transformer is
as under.
Distribution
4 star rated Transformer
Transformer
*Total Load loss in watts at 100 % *Total Load loss in watts at
in KVA
loading should not be lower 100 % loading should not be
than(Not equal to)
higher than(Not equal to)
Seal & Signature of Bidder
Page 10
UGVCL-Specifications
200
Distribution Transformer
2100
2300
*Total Load Loss in watt at 100 % loading = No Load loss in watt + Full Load loss in watt at
75 Deg. C
If bidder is offering losses higher than upper limit of loss band shall be out rightly rejected.
While bids of parties offering losses less than lowest limit of loss band, difference in offered
losses and lowest limit of loss band shall be added to no load losses while calculating TOC
and accordingly tender will be evaluated.
Standard labeling shall be provided as per BEE guidelines.
Percentage Impedance:
The % impedance at 75° C for 200 KVA transformers shall be 5 %. The % impedance
shall be subject to tolerance specified in IS: 2026-1977.
Regulation: The regulation at 75°C at full load at unity and 0.8 power factor subject
to the usual tolerance as per IS : 2026 and shall be specified in the bid.
Over fluxing:
The transformer shall be suitable for over fluxing (due to combined effect of voltage and
frequency) upto 10 % of any tapping without injurious heating at full load conditions.
16.
C.T.’s with accessories:
The current transformers of rating as specified shall be provided on LV side of the
Transformer. C.T.’s shall be mounted on L.V. Bushing and supported by Bakelite sheet of
adequate thickness affixed to main tank by nut bolt arrangement so as to ensured easy
replacement of C.T.’s without disturbing L.T. bushings.
Sr. No. Particulars
63 kVA to 315 kVA
1
Current Ratio
400/5 Amps
2
Class of Accuracy
0.5
3
Burden
5 VA
4
Type
Resin cast, Ring type suitable for outdoor and indoor use.
The secondary terminals of the C.T.’s shall be brought out by using 2.5 mm2 multi core
flexible copper cable with color coding and ferrules at both ends in conduit to the sealable
junction box which shall be outside Transformer closure fixed at suitable height. Similarly
three phase voltages shall be tapped from the L.T bus bar and brought out in the junction
box.
17.
Fittings and & Accessories:
The following accessories confirming to IS: 3639 shall be provided/
17.1
Oil conservator with drain plug, oil filling hole with blanking plate and oil level indicator with
maximum level marking. Conservator tank shall be of capacity to store oil of 10% of total oil
Seal & Signature of Bidder
Page 11
UGVCL-Specifications
Distribution Transformer
in main tank. Oil level indicator shall be so designed to indicate 10% to 90% oil quantity in
the conservator tank. Normal level shall be marked at 50 % of oil level indicator/=.
17.2
Silica gel breather shall contain minimum 0.5 kg dehydrated silica gel for 63 to 315 kVA size
and shall be connected with conservator with pipe having ¾ “ diameter.
17.3
Pressure Relief vent for 200KVA and above ratings.
17.4
Earthing terminals 2 Nos.
17.5
Lifting lugs
17.6
Air release plug
17.7
Oil filling hole with plug
17.8
Oil drain outlet with full turn type valve along with valve guard at the bottom of the main
tank as per purchaser’s requirement.
17.9
Oil filter inlet without valve and with plug or with full turn type valve as per purchaser’s
requirement.
17.10 Jacking lugs
17.11 Four nos of unidirectional flat rollers to facilitate the rolling of transformer in the direction
parallel to the side where the terminals have been brought out for 200KVA and above
ratings.
17.12 L.V. cable frames with clamps to hold (as per drawing)
One or two nos of 300 mm2 1 core XLPE cable per phase for each transformer/and 1 no 31/2
core 70/120 mm2 PVC Armoured cable.
17.13 The rating plate shall be as per the sample provided by the purchased and shall indicate
particulars as may be specified including No load and full load losses date of manufacture,
order ,guarantee period etc.
18
Tests:
18.1
Following tests constitute the routine test. All transformers or a part of order quantity as
desired by the purchaser shall be subjected to routine tests as per IS: 2026. All results of the
tests shall be submitted in triplicate for approval/comments.
18.1.1 Measurement of winding resistance.
18.1.2 Ratio, Polarity and phase relationship.
18.1.3 Impedance voltage
18.1.4 No load losses and no load current
18.1.5 Load losses
Seal & Signature of Bidder
Page 12
UGVCL-Specifications
Distribution Transformer
18.1.6 Insulation resistance
18.1.7 Induce over voltage withstand test
18.1.8 Separate source voltage withstand test
18.1.9 Unbalance current test (unbalance current should not be more than 2 % of
full load current in neutral at full load condition)
18.2
Type Test (to be quoted separately)
18.2.1 Impulse voltage withstand test
18.2.2 Temperature rise test
18.2.3 Short circuit test
18.3
Test Certificates:
18.3.1 The above tests may or may not be the part of the order but the offer shall
specify the cost of these tests if any.
18.3.2 The equipment offered shall be fully type tested as per relevant standards. In
case tests are already done the bidder shall furnish the type test reports
along with the offer.
19
Contract Drawing:
All required drawings shall be submitted by the bidder.
20
Conditions & Requirements:
Bidder must specifically confirm that the following will be complied with
20.1
HV and LV bushings shall be on the opposite sides of the transformer main
tank. HV bushing shall be mounted at an angle perpendicular to the main
tank.
20.2
Transformer shall be designed for 11 kV non effectively earthed system.
21
Inspection:
21.1
All raw materials used for manufacture of the transformer such as core stamping,
winding conductors, insulating paper and oil shall bear test certificates, excise gate
pass of the manufacturer. The bidder shall furnish following documents along with
their offer in respect of raw materials.
21.1.1 Invoice of supplier
Seal & Signature of Bidder
Page 13
UGVCL-Specifications
Distribution Transformer
21.1.2 Supplier’s Certificate
21.1.3 Packing list
21.1.4 Bill of entry certificate by custom.
21.1.5 Bill of landing
21.2
Sufficient advance intimation to organize stage inspection for inspecting core and
winding shall be given.
21.3
Purchaser at its option open a transformer supplied to the stores and if any
particular vary than the Guaranteed Technical Particulars, the whole lot of
transformer will be rejected and risk purchase resorted to.
21.4
In addition the purchaser shall pick and transformer and carry type tests from
competent and authorized body at company’s cost, the bidder shall have to organize
packing of such transformer at stores for which extra charges will be paid. If the
transformer fails to meet the requirement of type tests, the quantity of the
transformer ordered will be forthwith rejected/
21.5
Original manufacturer’s test report for oil shall be submitted at the time of
inspection. Arrangements for testing the oil shall be made and the same be tested in
the presence of company’s representative or in an independent laboratory.
21.6
If company intends to have inspection by competent/ authorized body at
manufacturer’s premises during the manufacturing and testing process, the selection
of the party will be at sole discretion of the company and manufacturer will have to
trust and provide all the facilities.
21.7
Company can test distribution transformers by using their own testing instruments
at manufacturer’s premises.
21.8
During the witnessing of testing of transformer at the supplier’s works purchaser will
also connect meters and supplier has to agree for the same.
22
Details in the Data Sheet:
Details of transformer shall be furnished in Data sheet by the bidders. If this data
sheet is not filled completely your offer will not be considered for evaluation.
23
Deviations:
Bidders are not allowed to deviate from the specifications. However bidder will have
to submit with the bid in a relevant schedule a detailed list of all deviations without
ambiguity. In the absence of deviation list in the deviation schedules, it is understood
Seal & Signature of Bidder
Page 14
UGVCL-Specifications
Distribution Transformer
that such bid confirms to the Bid Specification and no post bid negotiations shall take
place in this regard.
24
Schedules:
The bidders shall fill following schedules as part of offer. If schedules are not
submitted duly filled in with the offer, the offer shall be liable for rejection.
Schedule A
:
General Particulars
Schedule B
:
Guaranteed Technical Particulars
Schedule C
:
Schedule of Deviations
Schedule D
:
Deviations from furnishing documents
Schedule E
:
Bidder’s Experience
a. The discrepancies in Schedule C and D for deviation i.e between the
specification and the catalogues and or literatures submitted as part of the
offer by the bidders, the same shall not be considered and representations
in this regard will not be entertained.
b. If deviations in guaranteed technical performances are found other than
those specified in the deviation schedules then such deviations shall be
treated as deviations.
c. All the schedules shall be prepared by the vendor and enclosed with the
bid.
SCHEDULE -A
ANNEXURE-I
GUARANTEED & OTHER PARTICULARS FOR DISTRIBUTION TRANSFORMERS
(To be furnished by the
Manufacturer)
Sr
Description
1.
Make & Manufacturer
2.
Place of Manufacture
3.
Voltage Ratio
Seal & Signature of Bidder
200 kVA
11000/433V
Page 15
UGVCL-Specifications
4.
Rating in kVA
5.
Core Material used and Grade
Distribution Transformer
200 kVA
a) Flux density
b) Over fluxing without
saturation (Curve to be furnished
by the Manufacturer in support
of his claim)
6.
Maximum temperature rise of
a) windings by resistance method
b) Oil by Thermometer
7.
Magnetizing (No load) Current at
a) Normal Voltage
b) Maximum Voltage
8.
Core loss in watts
a) Normal Voltage
b) Maximum Voltage
9.
Resistance of Windings at 20 deg. C
(with 5% tolerance)
a. HV Winding (ohms)
b. LV Winding (ohms)
10.
Full load losses (watts) at 75 deg.C.
11.
Total losses at 100% load at 75 deg. C
12.
Total losses at 50% load at 75 deg. C
13.
Clearances
a) Core & LV
b) LV & HV
Seal & Signature of Bidder
Page 16
UGVCL-Specifications
Distribution Transformer
c) HV Phase to Phase
d) End insulation clearance to Earth
e) Any point of winding to tank
14.
Efficiency at 75 deg.C.
a) Unity P.F. &
b) 0.8 P.F.
1) 125% load
2) 100% load
3) 75% load
4) 50% load
5) 25% load
15. Regulation at
a) Unity P.F.
b) 0.8 P.F. at 75 deg.C.
16. % Impedance at 75 deg.C.
17. Over potential Test Double Voltage &
Double frequency for 1 minute
18. Impulse test value in KVP
19
Weight content of
a) Core lamination (min)
b) Windings (min) Aluminum./Copper
c) Tank & Fittings
d) Oil
e) Oil qty (min)
f) Total Weight
20
Oil Data
Seal & Signature of Bidder
Page 17
UGVCL-Specifications
.
Distribution Transformer
1. Qty for first filling (min)
2. Grade of oil used
3. Maker’s name
4. BDV at the time of filling
21
Transformer:
1) Overall length x breadth x height
2) Tank length x breadth x height
3) Thickness of plates for
a) Side plate (min)
b) Top & Bottom plate (min)
4) Conservator Dimensions
22
Radiation:
1) Heat dissipation by tank walls exclusive top & bottom
2) Heat dissipation by cooling tube
3) Dia & thickness of cooling tube
4) Whether calculation sheet for selecting cooling
area to ensure that the transformer is capable
of giving continuous rated output without exceeding
temperature rise is enclosed.
23
Inter layer insulation provided in design for
1) Top & bottom layer
2) In between all layer
3) Details of end insulation
4) Whether wedges are provided at 50% turns of the HV coil
24
Insulation materials provided
a) For Conductors (1) HV (2) LV
b For Core
Seal & Signature of Bidder
Page 18
UGVCL-Specifications
25
Distribution Transformer
Material and Size of the wire used
1) HV a) SWG/mm
b) Dia
2) LV a) Strip size
b) No. of Conductors in parallel
c) Total area of cross section (sq.mm.)
26
Is the name plate gives all particulars as required in Tender
27
Particulars of Bushings HV / LV
1) Maker’s name
2) Type IS-3347/IS-1180
3) Rating as per I.S.
4) Dry power frequency voltage withstand test
5) Wet power frequency voltage withstand test
28
Current transformer
CT Ratio
Accuracy class
ISF
29
30
Total losses at 50% load at 75 deg. C
Current density used for
a) HV winding.
b) LV winding.
31
Flash Test
(a) HV 28 kV / 50 HZ for 1 minute - 11 KV
(b) HV 56 kV / 50 HZ for 1 minute - 22 KV
( c) LV 3 kV/50 Hz for 1 minute
NOTE:
The following shall be specifically confirmed
Seal & Signature of Bidder
Page 19
UGVCL-Specifications
Distribution Transformer
1.
Whether the offer conforms to the limits of impedance mentioned in the specification
2.
Whether the offer conforms to the limits of temperature rise mentioned in the specification
3.
Whether the losses of the transformers offered are within the limits specified
4.
Whether the transformer offered is already type tested for the design and test reports
enclosed.
SCHEDULE -A
ANNEXURE-II
ADDITIONAL DETAILS
Sl.No.
Description
1.
Core Grade
2.
Core diameter
mm
3.
Gross Core area
cm
4.
Net Core area
cm
5.
Flux density
Tesla
Seal & Signature of Bidder
Page 20
UGVCL-Specifications
6.
Wt. of Core
7.
Loss per kg. of Core at the
Distribution Transformer
kg.
specified Flux density
8.
Core window height
Watts
9.
Center to center distance of the core
mm
10.
No. of L.V. Turns
mm
11.
No. of H V turns
12.
Size of LV Conductor bare/ covered
mm
13.
Size of HV conductor bare/covered
mm
14.
No. of parallels
15.
Current density of LV winding
amps/sq.mm.
16.
Current density of HV winding
amps/sq.mm
17.
Wt. of the LV winding for Transformer
kg.
18.
Wt. of the HV winding for Transformer
kg.
19.
No. of LV Coils/phase
20.
No. of HV coils / phase
21.
Height of LV Windings
mm
22.
Height of HV winding
mm
23.
ID/OD of LV winding
mm
24.
ID/OD of LV winding
mm
25.
Size of the duct in LV winding
mm
26.
Size of the duct in HV winding
mm
27.
Size of the duct between HV & LV
mm
28.
HV winding to LV winding clearance
mm
29.
HV winding to tank clearance
mm
30.
Calculated impedance
%
31.
HV to earth creepage distance
mm
Seal & Signature of Bidder
Page 21
UGVCL-Specifications
32.
Distribution Transformer
LV to earth creepage distance
mm
SCHEDULE - A
ANNEXURE-III
SOURCE OF MATERIALS/PLACES OF MANUFACTURE, TESTING AND INSPECTION
Source
Material
Sl.No.
Item
1.
Laminations
2.
Copper Conductor/ Aluminum Conductor
Seal & Signature of Bidder
of Place of
Manufacture
Place of testing
and inspection
Page 22
UGVCL-Specifications
Distribution Transformer
3.
Insulated winding wires
4.
Oil
5.
Press Boards
6.
Kraft Paper
7.
MS Plates / Angles / Channels
8.
Gaskets
9.
Bushing HV / LV
10.
Paints
SCHEDULE-B
DEVIATIONS FROM SPECIFICATION
---------------------------------------------------------------------------------------------------------------SR.NO.
CLAUSE NO.
DETAILS OF DEVIATION
------------------------------------------------------------------------------------------------------------
Seal & Signature of Bidder
Page 23
UGVCL-Specifications
Distribution Transformer
NAME OF FIRM------------------------------------------
NAME & SIGNATURE
OF TENDERER
----------------------------------
DESIGNATION ------------------------------------------
DATE -------------------------------------------------------
SCHEDULE - C
SCHEDULE OF TENDERER’S EXPERIENCE
-----------------------------------------------------------------------------------------------------------Sr. Name of Client Value of
Period of supply
Name & address to whom
No. & Description
and commissioning
reference may be made
order alongWith cap. of
Transformer
Seal & Signature of Bidder
Page 24
UGVCL-Specifications
Distribution Transformer
-----------------------------------------------------------------------------------------------------------1
2
3
4
5
------------------------------------------------------------------------------------------------------------
NAME OF FIRM ______________________________
NAME & SIGNATURE
OF TENDERER
_________________________
DESIGNATION _____________________________
DATE
___________________________________
SCHEDULE - D
SCHEDULE OF DEVIATION FROM SPECIFIED STANDARDS
------------------------------------------------------------------------------------------------------Sr. Particulars
No.
Stipulation of
Specified standards
Stipulation of
Remarks
standard adopted
by tenderers
--------------------
-----------------------
Standard Stipul-
Standard Stipula-
Ref.
Ref.
ations
tions
------------------------------------------------------------------------------------------------------Seal & Signature of Bidder
Page 25
UGVCL-Specifications
Distribution Transformer
NAME OF FIRM ___________________________________
NAME & SIGNATURE
OF TENDERER
_______________________________
DESIGNATION __________________________________
DATE __________________________________________
Seal & Signature of Bidder
Page 26
UGVCL-Specifications
Distribution Transformer
SCHEDULE - E
DEVIATION FROM SPECIFIED TEST REQUIREMENTS SPECIFIED IN RELEVANT
AND PRESENT SPECIFICATIONS.
-----------------------------------------------------------------------------------------------------------Sr. Name of Test
Standard
No.
No. and
Requirement
of standards
Proposed
deviation
Reason for
deviation
Clause no.
------------------------------------------------------------------------------------------------------------
1. TYPE TEST
2. ADDITIONAL TEST
3. ACCEPTANCE TEST
4. ROUTINE TEST
NAME OF FIRM ___________________________________
NAME & SIGNATURE
OF TENDERER
______________________________
DESIGNATION ___________________________________
DATE __________________________________________
Seal & Signature of Bidder
Page 27
UGVCL-Specifications
Distribution Transformer
QUALITY ASSURANCE PLAN FOR DISTRIBUTION TRANSFORMERS
SCOPE AND PURPOSE:
This document indicates the requirement expected by the Purchaser from the manufacturer of
Transformers. Manufacturer shall submit for purchaser’s approval a quality assurance plan in line
with this document incorporating specific document numbers for “format of records”, “acceptance
norms” and “reference documents” for purchaser’s approval.
Quality assurance plan is the document setting out the specific quality practices, resources, and
sequence of activities relevant to a particular product. Quality plan helps both the purchaser and
supplier as it defines each and every material used, every stage of manufacturing process,
characteristics to be checked and extent of check, reference documents, acceptance norm and
format of record specifically.
Abbreviations:
PS
-
Plant Standard / Process Specification
TR
-
Test Report
IS
-
Indian/ International Standard
CS
-
Customer Specification
AD
-
Approved Document such as Drawing, Purchase Order
V
-
Verified by
P
-
Performed by
W
-
Witnessed by
H
-
Hold by Purchaser
1
-
Purchaser
2
-
Manufacturer
3
-
External laboratory
4
-
Sub Vendor QC
Seal & Signature of Bidder
Page 28
UGVCL-Specifications
Distribution Transformer
Notes:
1) Minor: The characteristics of a component, process or operation whose failure neither materially
reduce the usability of the product in operation, nor does it affect the aesthetic aspects.
2) Major: The characteristics of a component, process, or operation whose failure may cause
operation failure which cannot be readily corrected, at site cause substandard performance,
increase erection and maintenance cost, reduce life or seriously affect aesthetics.
3) Critical: The characteristic of a component, process, or operation failure of which will surely cause
operating failure or intermittent troubles which is difficult to rectify at site or render the unit unfit
for use or safety hazards.
4) Failure of a characteristic means failure to meet the ‘accepted norms’
5) Sampling: Generally sampling will be done in accordance with IS: 2500. Sampling will be as
under:If 100% “Witness” of tests is carried out by Prime supplier, Customer will witness on sample basis or
if 100% “Witness” of tests is carried out by Sub Vendor, Manufacturer will witness on sample basis.
Seal & Signature of Bidder
Page 29