GEa 01 e 22/07/98 10:33 Page 1 HV/LV distribution transformers pole mounted immersed transformers from 50 to 160 kVA insulation < 24 kV / 400 V << Go back description options This range consists of transformers complying with the following specification: m three-phase transformers, for pole mounting in overhead systems. For the hanging on poles, in an inclined position, they are equipped with a hook in accordance with EDF technical specification HN 52 S 20 (1986); m step-down type (1); m rated frequency: 50 Hz (6); m maximum ambient temperature : 40°C (5); m mineral oil immersed (1); m hermetically sealed with integral filling (1); m bolted cover on corrugated tank; m ONAN type natural cooling; m anti-corrosive treatment : tank and cover fully hot dip galvanized; m anti-corrosive coating; m final colour grey RAL 7033. The following fittings may be provided as an option: m 3 special “seaside” HV porcelain bushings; m 3 HV mobile plug-in connectors 250 A / 24 kV, straight or elbow (the cable characteristics should always be specified); m polyester box equipped with Gardy circuitbreakers: M D 165 for 50 and 100 kVA; M D 265 T for 160 kVA, protection through thermal image tripping device: M 3T/6T bicalibre up to 100 kVA inclusive; M 7T for 160 kVA; Note: Gardy circuit-breakers are in accordance with EDF specifications HN 63 S 11 (1984) and approved by EDF technical departments. m manual mechanical control, lockable in both positions (connected or disconnected). The circuit-breaker box and its mechanical control can not be mounted on poles of different section or nature. standards These transformers comply with (1): – IEC standards; – French standards NF C 52-100 (1990) and NF C 52-112-1 (1994); – “Electricité de France” technical specification HN 52 S 20 (1986); – CENELEC harmonization document PR-HD 428-5. 50 kVA - 20 kV/400 V Note : the above options concern usual cases and are not restrictive. For other information, please consult us. basic fittings Each tranformer includes: m 1 off-circuit tappings switch with padlocking located on the cover ; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value; m 3 HV porcelain bushings on the cover; m 4 LV porcelain bushings - 250 A on the small side of the tank; m 1 LV bushing protection (only for storage and handling); m 1 earthing terminal on the hanging device; m 2 lifting and untanking lugs; m 1 rating plate fixed on the small side of the tank; m 1 filling plug; m protection index IP 00. s vec de alisé a t ranti ré tout élémen a g t s ateur e exempts de pollué rm té é fo s n ir t Ce tra nts neufs e ptible d’avo a e constitu pération susc u en de réc CB. as be P rmer h lly par des transfo and is tota is th ’s. at rial ant th h new mate ted with PCB rr a w We d wit s pollu rt re a tu p c d fa n manu nd ha ers. m seco nsform free fro n all tra o k c tu Label s France Transfo guarantees that its transformers are assembled using components that are both new and PCB-free (< 2 ppm level), in strict compliance with the current standards. 100 kVA - 20 kV/400 V electrical characteristics rated power (kVA) (1) rated voltage primary (1) secondary at no-load (1) rated insulation level (3) HV tapping range (off voltage) vector group losses (W) primary no-load load (2) rated impedance voltage (%) (2) no-load current (%) P.F. = 1 voltage drop at full load (%) P.F. = 0.8 P.F. = 1 efficiencies at full load (%) P.F. = 0.8 noise level (4) acoustic power LWA dB(A) acoustic pressure LPA at 0,3 metre 50 100 15 or 20 kV 400 V between phases, 231 V phase to neutral 24 kV for 20 kV 17.5 kV for 15 kV ± 2.5 % or ± 5 % (1) star - zigzag neutral brought-out, Yzn 11 for 50 kVA. delta - star neutral brought-out, Dyn 11 for 100 and 160 kVA. 145 210 1350 2150 4 4 2.9 2.5 2.68 2.16 3.92 3.73 97.10 97.69 96.40 97.13 50 49 40 39 160 460(4) 2350 4 2.3 1.54 3.43 98.27 97.85 62 52 (1) others possibilities upon request, consult us. (2) load losses and rated impedance voltage at 75°C. (3) reminder of insulation levels : insulation level (kV) 7.2 12 17.5 24 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 kV B.I.L. 1.2/50 µs 60 75 95 125 (4) Noise measure in compliance with the IEC 551 standard. (5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon request, consult us. (6) other rated frequency (60 Hz) upon request, consult us. GEa 01 e 22/07/98 10:34 Page 2 HV/LV distribution transformers pole mounted immersed transformers from 50 to 160 kVA insulation < 24 kV / 400 V F dimensions and weights M12 F lifting lug 35 330 30 b c n M12 C J A B 350 A B filling plug N. B. The terminal marking is in accordance with NFC 52 100 (1990), see attached diagram. Upon request, it can be done in accordance with IEC standards 616 (1978). C dimensions (mm) kVA A B C F J weights (kg) 50 880 610 770 260 730 100 960 680 820 265 750 160 1170 700 830 265 800 total mineral oil 340 90 490 110 615 150 M12 35 lifting lug 480 30 b c a n M12 C J A off-circuit tappings switch 350 A transformers with special “seaside” HV porcelain bushings B 355 B filling plug C 355 dimensions (mm) kVA A B C J weights (kg) 50 930 610 770 730 100 960 680 820 750 160 1170 700 830 800 total mineral oil 350 90 500 110 625 150 Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings. Due to the evolution of standards and materials, the present document will bind us only after confirmation from our technical department. France Transfo BP 10140 F 57281 Maizières-lès-Metz Cedex tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16 Ref : GEa 01 e • Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 06/98 off-circuit tappings switch transformers with standards HV porcelain bushings a Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers. They are provided for 20 kV / 400 V transformers with electrical characteristics, as described in the previous table. For other electrical characteristics (voltage, losses, etc…) or other dielectric, dimensions and weights would be different, please consult us. GEa.02 e 22/07/98 14:40 Page 1 HV/LV distribution transformers ground mounted immersed transformers from 100 to 3150 kVA - insulation < 24 kV / 400 V IEC standards m description This range consists of transformers complying with the following specification: m three-phase transformers, for indoor or outdoor use (installation to be specified); m step-down type (1); m rated frequency : 50 Hz (6); m maximum ambient temperature : 40°C (5); m mineral oil immersed (other dielectric upon request); m hermetically sealed with integral filling (7); m cover bolted on tank; m ONAN type natural cooling; m standard anti-corrosion surface treatment and coating (1); m final colour grey RAL 7033 (1). standards These transformers comply with the following standards: – IEC standards; – French standard NFC 52 100 (1990); – CENELEC harmonization document HD 398-1 to 398-5. basic fittings Each transformer includes: m 1 off-circuit tappings switch with padlocking located on the cover; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value; m 3 fixed plug-in connectors parts HN 52 S 61 250 A / 24 kV - HV side; m 4 LV flat-bars, from 250 kVA only; for 100 and 160 kVA: 4 LV porcelain bushings; m 2 earthing terminals on the cover; m 4 bi-directional flat rollers from 160 kVA; m 2 lifting and untanking lugs; m 1 rating plate to be fixed on 1 of the 4 sides; m 1 filling plug; m ISO 9 0 01 AFAQ N 1990/113b 1 draining device; protection index IP 00. options The following fittings may be provided as an option: m 3 HV mobile plug-in connectors 250 A / 24 kV, straight or elbow (the cable characteristics should always be specified); m 3 HV porcelain bushings; m 4 LV porcelain bushings from 250 kVA; m Locking device (lock not supplied) for plug-in connectors; m LV air-insulated terminal cover to be sealed (possible only with plug-in connectors on HV side and flat-bars on LV side); m Protection devices : thermometer, thermostat, DGPT2 relay, etc. 1000 kVA - 20 kV / 400 V Note : the above options concern usual cases and are not restrictive. For other information, please consult us. es avec d t n réalisé aranti e tout éléme g t s e r d pollué rmateu et exempts té é fo s n ir a o d’av Ce tr eufs ants n eptible constitu pération susc u c en de ré as be PCB. rmer h lly par des transfo and is tota is th ’s. at rial ant th h new mate ted with PCB rr a w u it ll o w We p d s part cture manufa second hand ers. m ansform free fro n o all tr k c tu s Label 250 kVA - 20 kV / 400 V France Transfo guarantees that its transformers are assembled using components that are both new and PCB-free (< 2 ppm level), in strict compliance with the current standards. * non standard ratings available on request. (1) others upon request, consult us. (2) load losses and rated impedance voltage, at 75°C. (3) classification of dielectrics according to NF C 27-300 : m O1 for mineral oil ; m K3 for silicone oil. (4) reminder of insulation levels : insulation level (kV) 7.2 12 17.5 24 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 kV B.I.L. 1.2/50 µs 60 75 95 125 (5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon request, consult us. (6) other rated frequency (60 Hz) upon request, consult us. (7) breathing type transformer with conservator upon request, consult us. 800 kVA - 20 kV / 400 V electrical characteristics rated power (kVA) (1) primary (1) rated voltage secondary at no-load (1) rated insulation level (4) primary HV tapping range (off-voltage) vector group losses (W) no-load load (2) rated impedance voltage (%) (2) no load current (%) P.F. = 1 voltage drop at full load (%) P.F. = 0.8 P.F. = 1 load 100 % P.F. = 0.8 efficiencies (%) P.F. = 1 load 75 % P.F. = 0.8 noise level (dBA) power acoustic LWA acoustic pressure Lpa at 0.3 metre 100 160 250 315* 400 500* 630 15 or 20 kV 400 V between phases, 231 V phase to neutral 17.5 kV for 15 kV 24 kV for 20 kV ± 2.5 % or ± 5 % or ± 2.5 % ± 5 % (1) Dyn 11 (1) (delta; star neutral brought-out) 210 460 650 800 930 1100 1300 2150 2350 3250 3900 4600 5500 6500 4 4 4 4 4 4 4 2.5 2.3 2.1 2 1.9 1.9 1.8 2.21 1.54 1.37 1.31 1.22 1.17 1.11 3.75 3.43 3.33 3.30 3.25 3.22 3.17 97.69 98.27 98.46 98.53 98.64 98.70 98.78 97.13 97.85 98.09 98.17 98.30 98.387 98.48 98.14 98.54 98.70 98.75 98.84 98.89 98.96 97.69 98.18 98.37 98.44 98.56 98.62 98.71 53 59 62 64 65 67 67 42 48 50 52 53 54 54 800 1000 1250 1600 2000 2500 3150 1220 10700 6 2.5 1.51 4.65 98.53 98.17 98.81 98.51 68 55 1470 13000 6 2.4 1.47 4.63 98.57 98.22 98.84 98.56 68 55 1800 16000 6 2.2 1.45 4.62 98.60 98.25 98.86 98.58 70 56 2300 20000 6 2 1.42 4.60 98.63 98.29 98.88 98.61 71 58 2750 25500 6 1.9 1.45 4.61 98.61 98.27 98.87 98.60 72 58 3350 32000 6 1.8 1.45 4.62 98.61 98.26 98.87 98.60 74 59 4380 33000 7 1.7 1.29 5.11 98.83 98.54 99.04 98.80 74 59 GEa.02 e 22/07/98 14:40 Page 2 HV/LV distribution transformers ground mounted immersed transformers from 100 to 3150 kVA - insulation < 24 kV / 400 V IEC standards dimensions and weights off-circuit tappings switch earthing terminal lifting lug Groupe Merlin Gerin · Usine de Maizières-lès-Metz (Moselle) France Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers. They are provided for 20 kV / 400 V transformers with electrical characteristics, as described in the previous table. For other electrical characteristics (voltage, losses, etc.) or other dielectric, dimensions and weights would be different (please consult us). nº 216540 D* C 40 (2) J A F F N. B. The terminal marking is in accordance with IEC standards 616 (1978), see attached diagram. 38 (3) J B K Ø = 125(1) (1) (2) (3) off-circuit tappings switch for 3150, Ø = 200 for 3150, 80 for 3150, 60 earthing terminal 1W 1V 1U 2W 2V 2U 2N C n B c A a b D* : height over LV protection cover ; assembly possible only if the HV is fitted with plug-in connectors. filling plug rating plate H H cooling fins at the corners for rated powers > 630 kVA. H dimensions (mm) kVA A B C D* F H J K flat-bars porcelain LV 100 1000 700 900 1250 265 75 520 105 — 250A 160 1100 710 965 1315 265 75 520 105 — 250A 550 110 700 150 250 315 400 1160 1295 1315 860 895 915 1010 1060 1150 1360 1410 1500 265 265 265 150 150 150 520 670 670 105 105 105 1250A 1250A 1250A 630A 630A 630A 500 1495 925 1215 1565 265 150 670 105 1250A 1000A 630 800 1510 1695 940 975 1225 1395 1575 1745 265 265 150 150 670 670 105 105 1250A 1250A 1000A 1600A 1000 1250 1810 1850 975 1000 1495 1555 1905 1965 265 265 150 170 670 670 85 85 1600A 2500A 1600A 2500A 1600 2000 1930 2160 1220 1250 1575 1685 1985 2195 265 265 170 170 820 820 85 85 2500A 3150A 2500A 3150A 2500 3150 2550 2700 1830 1840 1690 1795 2200 2305 265 265 170 170 820 820 85 85 5000A 5000A 4000A 5300A weights (kg) total mineral oil 1000 215 1165 275 1350 310 1545 350 1740 380 2100 450 2390 580 LV flat-bars (from 250 kVA only) 1600A 1250A M 12 35 165 250 A Ø 16 h10 60 Ø 30 h10 120 120 80 300 630 A 1000 A 1600 A 2500 A with straight mobile connector M 12 100 300 350 315 3150 A locking lug Ø 65 h10 35 295 250 215 87 HV porcelain bushings Ø 63 h10 160 140 with elbow mobile connector 5000A Ø 56 h10 Ø 50 h10 locking lug 45 3150A LV porcelain bushings (compulsory for 100 and 160 kVA) Ø 40 h10 255 Ø 18 Ø 18 2500A 5730 1230 290 50 45 Ø 14,5 Ø 11 250 31,5 Ø 14,5 4640 1130 200 20 25 50 135 35 50 50 52 31,5 Ø 11 3880 870 12 50 250 31,5 52 Ø 14,5 52 Ø 11 155 31,5 31,5 120 12 106,5 12 221 31,5 31,5 31,5 12 97,5 63 31,5 31,5 3500 790 HV fixed plug-in connectors 250 A - 24 kV 310 100 63 31,5 120 50 2850 670 330 4000A 5300A Note : never use HV porcelain bushings with LV protected by a terminal cover. 250A Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings. Due to the evolution of standards and materials, the present document will bind us only after confirmation from our technical department. France Transfo BP 10140 F 57281 Maizières-lès-Metz Cedex tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16 Ref : GEa.02 e Edition France Transfo - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 09/96 earthing terminal GEa.04d 22/07/98 14:45 Page 1 HV/HV power transformers immersed transformers from 2500 to 5000 kVA - for 7.2 to 36 kV systems IEC standards ISO 9001-1994 AFAQ N 1993/1275 description options This range consists of transformers complying with the following specification : m three-phase transformers, for indoor or outdoor use (installation to be specified) ; m step-down type (1) ; m rated frequency : 50 Hz (6) ; m maximum ambient temperature : 40°C (5) ; m mineral oil immersed (other dielectric upon request)(3) ; m hermetically sealed with integral filling (7) ; m cover bolted on tank ; m ONAN type natural cooling ; m standard anti-corrosion surface treatment and coating (1) ; m final colour grey RAL 7033 (1). The following fittings may be provided as an option : m 1 conservator (for breathing type transformer) with : M 1 level indicator tube ; m 1 Buchholz relay with 2 contacts (alarm and tripping) ; M 1 silicagel airdryer; m HV fixed plug-in connectors HN 52 S 61 : M 250, 400, 630 or 1250 A / 24 kV ; M 400 A / 36 kV. m HV plug-in mobile connectors HN 52 S 61 (the cable characteristics should always be specified) ; m 1 locking device (lock not supplied) for plug-in connectors ; m 1 DGPT2 relay (automation 2000) ; m 1 thermostat two contacts (alarm and tripping) ; m 1 dial type thermometer (with or without contact) ; m 1 wiring box with terminals board for connecting optional electrical equipment (Buchholz relay, thermostat, thermometer, etc…). standards These transformers comply with the following standards (1) : – IEC standards ; – French standards NFC 52 100 (1990); – and CENELEC harmonization document HD 398-1 to 398-5. mineral oil immersed transformer 5000 kVA, 20 - 13.75/5.5 - 3.2 kV. basic fittings Each transformer includes : m 1 off-circuit tappings switch with padlocking located on the cover ; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value ; m porcelain bushings on primary and secondary sides ; m 2 earthing terminals on the cover ; m 4 bi-directional flat rollers ; m 2 lifting and untanking lugs ; m 1 rating plate to be fixed on 1 of the 4 sides ; m 1 filling plug ; m 1 draining device ; m protection index IP 00. Note : the above options concern usual cases and are not restrictive. For other information, please consult us. des é avec ti réalis ut élément n ra a g to st llué ateur e exempts de été po nsform Ce tra nts neufs et ptible d’avoir a e constitu pération susc u de réc CB. been P r has par des sforme d is totally n a tr is n that th w material a with PCB’s. e arrant We w tured with n parts polluted c manufa second hand . m formers free fro all trans tuck on s l e b a L mineral oil immersed transformer 5000 kVA, 20/6 kV. France Transfo guarantees that its transformers are asembled using components that are both new and PCB-free (< 2 ppm level), in strict compliance with the current standards. electrical characteristics rated power (kVA) (1) primary rated insulation level (4) secondary HV tapping range (off-voltage) vector group no-load losses (kW) load (2) rated impedance voltage (%) (2) no-load current (%) P.F. = 1 voltage drop at full load (%) P.F. = 0.8 load P.F. = 1 100 % P.F. = 0.8 efficiencies (%) load P.F. = 1 75 % P.F. = 0.8 2500 3150 4000 7.2 - 12 - 17.5 - 24 7.2 -12 ± 5 (1) Dyn 11 or YynO (1) 3.35 4.5 5 32 29 33 6 7 7 1.8 1.6 1.4 1.45 1.16 1.07 4.62 5.02 4.96 98.61 98.95 99.06 98.26 98.69 98.83 99.87 99.13 99.22 98.60 98.91 99.03 5000 2500 3150 4000 36 7.2 - 17.5 ± 5 (1) Dyn 11 or YynO (1) 6 4 4.5 5.5 40 25 30 34 7.5 6.5 7 7 1.3 2.1 1.9 1.8 1.08 1.21 1.19 1.09 5.26 4.76 5.05 4.98 99.09 98.85 98.92 99.02 98.86 98.57 98.65 98.78 99.25 99.05 99.10 99.19 99.06 98.81 98.88 98.98 5000 6.5 41 7.5 1.6 1.10 5.28 99.06 98.83 99.22 99.02 (1) others upon request, consult us. (2) load losses and rated impedance voltage at 75°C. (3) classification of dielectrics according to NF C 27-300 : m O1 for mineral oil ; m K3 for silicone oil. (4) reminder of insulation levels : rated insulation level (kV) 7.2 12 17.5 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 70 kV B.I.L. 1,2/50 µs 60 75 95 125 170 24 36 (5) other ambient temperature (45°C, 50°C, 55°C, etc…) upon request, consult us. (6) other rated frequency (60 Hz) upon request, consult us. (7) breathing type with conservator, upon request, consult us. GEa.04d 22/07/98 14:45 Page 2 HV/HV power transformers immersed transformers from 2500 to 5000 kVA - for 7.2 to 36 kV systems IEC standards dimensions and weights off-circuit tappings switch Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers. They correspond to transformers intented for systems of 7.2 to 36 kV having electrical characteristics, as described in the previous table. For other electrical characteristics (voltage, losses, etc…) or other dielectric, dimensions and weights would be different, please, consult us. lifting lug rating plate C Groupe Merlin Gerin · Usine de Maizières-lès-Metz (Moselle) France nº 216540 N. B. The terminal marking is in accordance with IEC standards 616 (1978), see attached diagram. draining device E earthing terminal A filling plug 2N 2U 2V 2W earthing terminal 1U B 1V 1W off-circuit tappings switch rated power (kVA) dimensions (mm) A B primary 7.2 - 12 - 17.5 - 24 kV (HV secondary) 2500 2200 1800 3150 2700 1800 4000 3000 2000 5000 3200 2200 primary 36 kV (HV secondary) 2500 2500 1800 3150 2800 1900 4000 3100 2100 5000 3300 2300 weights (kg) total mineral oil C (1) D E 2070 2140 2500 2700 1430 1520 1700 1800 820 820 1000 1000 4900 5550 7200 8500 1000 1100 1500 1700 2070 2170 2600 2800 1430 1550 1800 1900 820 820 1000 1000 4900 6000 8000 9300 1000 1200 1880 2080 HV porcelain bushings Ø 30 M 12 80 490 (36kV) 35 330 (23/24kV) 250 (7,2/23kV) Ø 16 407 62 312 630A 250A 1000A HV fixed plug-in connectors HN 52 S 61 - 250 A - 24 kV (2) 200 290 255 locking lug with elbow mobile connector 87 locking lug with straight mobile connector (1) Breathing type transformer with conservator. (2) For dimensions of other plug-in connectors, please, consult us. Casual arrangements such as bars and cables supports, flexible connectors, etc… are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings. Due to the evolution of standards and materials, the present document will bind us only after confirmation from our technical department. France Transfo BP 140 F 57211 Maizières-lès-Metz Cedex tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16 Ref : GEa.4 d Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 02/96 D GEa.05 c 22/07/98 14:51 Page 1 HV/HV power transformers immersed transformers from 5 to 60 MVA for 7.2 to 123 kV systems ISO 9 0 01 AFAQ N 1990/113b description This range consists of transformers complying with the following specification: m three-phase transformers, 50 or 60 Hz, for indoor or outdoor use (installation to be specified); m maximum ambient temperature: 40°C (5); m mineral oil immersed (other dielectric upon request); m breathing type with conservator ; m cover bolted on tank or welded bell type as per specification; m ONAN, ONAF, ODAF or ODWF cooling type; m standard anti-corrosion surface treatment and coating (1); m final colour grey RAL 7033 (1). standards These transformers comply with the following standards (1): – IEC standards; – French standards NFC 52 100 (1990). basic fittings Each tranformer includes: m 1 off-circuit tappings switch with padlocking located on the cover ; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value (generally ± 5%, 3 or 5 positions); m porcelain bushings on primary and secondary sides; m 2 earthing terminals; m 1 conservator with level indicator tube; m 1 silicagel airdryer; m 1 Buchholz relay with 2 contacts (alarm and tripping); m 1 thermostat with two contact (alarm and tripping); m 1 dial type thermometer (without contact); m 4 directional flat rollers; m lifting and/or untanking lugs; m 1 rating plate; m 1 filling plug; m 1 draining device and treatment valve with sampler. options M 1 protective relay and eventually, on request: 1 parallel operation device; M 1 voltage regulator with voltage drop equalizer; M 1 remote indicator of tap changer position. m magnetic level indicator (with or without contact, please specify); m HV fixed plug-in connectors HN 52 S 61: M 250, 400, 630 or 1250 A - 24 kV; M 400, 630 or 1250 A - 36 kV. m HV mobile plug-in connectors HN 52 S 61, straight or elbow (the cable characteristics should be specified); m condenser bushings; m increased creepage distance bushings; m 1 bonnet on HV bushings: M in the air for connection by dry cables or busducts (except rated insulation level 72.5 kV) ; M oil immersed, hermetically sealed for cable connection; M SF6 immersed, hermetically sealed for connection by busbars on oil/SF6 bushings; m winding temperature indicator by thermal image ; m current transformer: M “bushing” type around terminals; M standard type for earth fault current detector; m 1 overpressure valve (with or without contact, please specify); m 1 automatic oil retaining valve (between conservator and tank); m “Atmoseal” oil protection system; m 1 treatment valve at the upper part of the tank; m 1 insulation valve for radiators; m 4 jacking lugs with hauling eyes. M Note : the above options concern usual cases and are not restrictive. For other information, please consult us. Transformer 36 MVA, 62.5/18.4 kV with on-load tap changer, ODAF type cooling. ec des lisé av nti réa ut élément ra a g t to s llué ateur e exempts de été po nsform Ce tra nts neufs et ptible d’avoir a e constitu pération susc u de réc CB. been P er has par des ansform and is totally tr is B’s. that th w material with PC e arrant We w tured with n parts polluted c d fa manu nd han . m seco formers free fro all trans tuck on s l e b a L The following fittings may be provided as an option: m 1 on-load tap changer in the main tank (generally ± 12% - 19 positions maximum) with: M 1 motor drive unit fitted on tank; M 1 tap changer compartment in the conservator with a level indicator; France Transfo guarantees that its transformers are assembled using components that are both new and PCB-free (< 2 ppm level), in strict compliance with the current standards. electrical characteristics él Typical characteristics are indicated in the table below up to 30 MVA / 72.5 kV. Above, please consult us. They correspond to transformers of ONAN type cooling (3), with or without tap changer. It is possible to develop equipment with totally different values of voltage and rated impedance voltage. In this case, dimensions and weights are also different. rated power (3) 5 10 20 (MVA) primary 24-36 rated insulation secondary 7.2 - 12 - 17.5 - 24 level (kV) (4) no-load 6 10 17 losses (kW) load (2) 43 71 120 8 9 10 rated impedance voltage (%) (2) Transformer 20/25 MVA, 65/20 kV with on-load tap changer, ONAN/ONAF type cooling. 25 5 10 20 25 30 72.5 7.2 - 12 - 17.5 - 24 21 140 11 7 43 8 11 71 9 (1) other possibilities upon request, please consult us. (2) load losses and rated impedance voltage at 75°C. (3) each type of cooling device comes with its particular type of equipment (circulators, ventilators, etc.). cooling type ONAN of oil m natural through thermosiphon directional through circulators of natural through tank air convection forced through fans forced through water circulation ODAF ONAF ODWF m m m m m m m (4) reminder of insulation levels: rated insulation level (kV) 18 120 10 22 140 11 25 160 11 7.2 12 17.5 24 36 52 72.5 90 123 70 95 140 185 230 kV r.m.s. 50 Hz - 1 mn 20 28 38 50 kV B.I.L. 1.2/50 µs 60 75 95 125 170 250 325 450 550 (5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon request, consult us. GEa.05 c 22/07/98 14:51 Page 2 HV/HV power transformers immersed transformers from 5 to 60 MVA for 7.2 to 123 kV systems dimensions and weights Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers, completely set up* with a standard type cooling. They correspond to transformers intented for systems of 7.2 to 72.5 kV having electrical characteristics as indicated in the previous table. For other voltages, other characteristics or when the transformers are immersed in another dielectric, dimensions and weights would be different, please, consult us. ONAN type cooling C E B A Transformers 5 MVA, with off-voltage tappings switch. D* : hauteur sur capot de protection BT ; montage possible uniquement lorsque la MT C est équipée de prises embrochables. B E A Transformers 5 MVA with on-load tap changer, or 10 to 25 MVA with off-voltage tappings switch or with on-load tap changer. ODAF type cooling rated power with off-voltage tappings switch with on-load tap changer (MVA) dimensions (mm) total dimensions (mm) total A B C weight (kg) A B C weight (kg) rated insulation level 72.5 kV 20 3500 2700 4000 21000 4500 3000 4000 23000 25 4000 3000 4300 25000 4700 3000 4300 28000 rated insulation level > 72.5 kV, consult us. C B A Transformers 20 to 25 MVA, with off-voltage switch or on-load tap changer. * For the protection of some components or the compliance with the railway or road regulations, the transformers could be delivered partially dismantled. Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings. Due to the evolution of standards and materials, the present document will bind us only after confirmation from our technical department. France Transfo BP 10140 F 57281 Maizières-lès-Metz Cedex tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16 Ref : GEa.05 c Edition France Transfo - SA au capital de 10 280 000 FRF - RCS Metz B 357 801 109 • Imprimé en France • Composition et illustrations : COREDIT • 09/96 rated power with off-voltage tappings switch with on-load tap changer (MVA) dimensions (mm) total dimensions (mm) total A B C E weight (kg) A B C E weight (kg) rated insulation level 24 kV 5 2700 2100 2500 1000 8500 3400 2200 2550 1000 10000 10 3750 2450 3500 1500 17000 3800 2500 3500 1500 19000 20 4300 3900 3600 1500 26500 4600 3900 3600 1500 27000 25 4000 3900 3800 1500 35000 4100 3900 3800 1500 37000 31 à 60 consult us rated insulation level 36 kV 5 3300 2400 2950 1000 11000 3600 2400 3000 1000 13000 10 3900 3300 3600 1500 18000 3900 3400 3600 1500 20000 20 4400 3950 3700 1500 27000 4700 4000 3700 1500 29000 25 4200 4300 4000 1500 36000 4800 4300 4000 1500 38000 31 to 60 consult us rated insulation level 72.5 kV 5 4100 2600 3300 1000 17000 10 3900 3400 3500 1500 18000 4000 3900 3600 1500 22000 20 4500 4000 4000 1500 27000 5000 4100 4000 1500 32000 25 4400 4600 4300 1500 41000 5000 4600 4300 1500 43000 30 consult us