HV/LV distribution transformers
pole mounted immersed transformers
from 50 to 160 kVA
insulation < 24 kV / 400 V
<< Go back
description
options
This range consists of transformers complying
with the following specification:
m three-phase transformers, for pole mounting
in overhead systems. For the hanging on poles,
in an inclined position, they are equipped with a
hook in accordance with EDF technical specification HN 52 S 20 (1986);
m step-down type (1);
m rated frequency: 50 Hz (6);
m maximum ambient temperature : 40°C (5);
m mineral oil immersed (1);
m hermetically sealed with integral filling (1);
m bolted cover on corrugated tank;
m ONAN type natural cooling;
m anti-corrosive treatment : tank and cover fully
hot dip galvanized;
m anti-corrosive coating;
m final colour grey RAL 7033.
The following fittings may be provided as an
option:
m 3 special “seaside” HV porcelain bushings;
m 3 HV mobile plug-in connectors 250 A / 24 kV,
straight or elbow (the cable characteristics
should always be specified);
m polyester box equipped with Gardy circuitbreakers:
M D 165 for 50 and 100 kVA;
M D 265 T for 160 kVA,
protection through thermal image tripping device:
M 3T/6T bicalibre up to 100 kVA inclusive;
M 7T for 160 kVA;
Note: Gardy circuit-breakers are in accordance
with EDF specifications HN 63 S 11 (1984) and
approved by EDF technical departments.
m manual mechanical control, lockable in both
positions (connected or disconnected).
The circuit-breaker box and its mechanical
control can not be mounted on poles of different section or nature.
standards
These transformers comply with (1):
– IEC standards;
– French standards NF C 52-100 (1990) and
NF C 52-112-1 (1994);
– “Electricité de France” technical specification
HN 52 S 20 (1986);
– CENELEC harmonization document
PR-HD 428-5.
50 kVA - 20 kV/400 V
Note : the above options concern usual cases
and are not restrictive. For other information,
please consult us.
basic fittings
Each tranformer includes:
m 1 off-circuit tappings switch with padlocking
located on the cover ; this switch operates on
the highest rated voltage to bring the transformer to the supply voltage-actual value;
m 3 HV porcelain bushings on the cover;
m 4 LV porcelain bushings - 250 A on the small
side of the tank;
m 1 LV bushing protection (only for storage and
handling);
m 1 earthing terminal on the hanging device;
m 2 lifting and untanking lugs;
m 1 rating plate fixed on the small side of the
tank;
m 1 filling plug;
m protection index IP 00.
s
vec de
alisé a
t
ranti ré tout élémen
a
g
t
s
ateur e exempts de
pollué
rm
té
é
fo
s
n
ir
t
Ce tra nts neufs e ptible d’avo
a
e
constitu pération susc
u
en
de réc CB.
as be
P
rmer h
lly
par des
transfo and is tota
is
th
’s.
at
rial
ant th h new mate ted with PCB
rr
a
w
We
d wit
s pollu
rt
re
a
tu
p
c
d
fa
n
manu
nd ha
ers.
m seco
nsform
free fro
n all tra
o
k
c
tu
Label s
France Transfo guarantees that its transformers are
assembled using components that are both new and
PCB-free (< 2 ppm level), in strict compliance with the
current standards.
100 kVA - 20 kV/400 V
electrical characteristics
rated power (kVA) (1)
rated voltage
primary (1)
secondary at no-load (1)
rated insulation
level (3)
HV tapping range (off voltage)
vector group
losses (W)
primary
no-load
load (2)
rated impedance voltage (%) (2)
no-load current (%)
P.F. = 1
voltage drop
at full load (%)
P.F. = 0.8
P.F. = 1
efficiencies
at full load (%)
P.F. = 0.8
noise level (4)
acoustic power LWA
dB(A)
acoustic pressure LPA at 0,3 metre
50
100
15 or 20 kV
400 V between phases,
231 V phase to neutral
24 kV for 20 kV
17.5 kV for 15 kV
± 2.5 % or ± 5 % (1)
star - zigzag neutral brought-out,
Yzn 11 for 50 kVA.
delta - star neutral brought-out,
Dyn 11 for 100 and 160 kVA.
145
210
1350
2150
4
4
2.9
2.5
2.68
2.16
3.92
3.73
97.10
97.69
96.40
97.13
50
49
40
39
160
460(4)
2350
4
2.3
1.54
3.43
98.27
97.85
62
52
(1) others possibilities upon request, consult us.
(2) load losses and rated impedance voltage at 75°C.
(3) reminder of insulation levels :
insulation level (kV)
7.2
12
17.5
24
kV r.m.s. 50 Hz - 1 mn
20
28
38
50
kV B.I.L. 1.2/50 µs
60
75
95
125
(4) Noise measure in compliance with the IEC 551 standard.
(5) other ambient temperature (45°C, 50°C, 55°C, etc.)
upon request, consult us.
(6) other rated frequency (60 Hz) upon request, consult us.
GEa 01 e
22/07/98 10:34
Page 2
HV/LV distribution transformers
pole mounted immersed transformers
from 50 to 160 kVA
insulation < 24 kV / 400 V
F
dimensions and weights
M12
F
lifting lug
35
330
30
b
c
n
M12
C
J
A
B
350
A
B
filling plug
N. B.
The terminal marking is in accordance with
NFC 52 100 (1990), see attached diagram.
Upon request, it can be done in accordance
with IEC standards 616 (1978).
C
dimensions (mm)
kVA
A
B
C
F
J
weights (kg)
50
880
610
770
260
730
100
960
680
820
265
750
160
1170
700
830
265
800
total
mineral oil
340
90
490
110
615
150
M12
35
lifting lug
480
30
b
c
a
n
M12
C
J
A
off-circuit
tappings switch
350
A
transformers with
special “seaside”
HV porcelain bushings
B
355
B
filling plug
C
355
dimensions (mm)
kVA
A
B
C
J
weights (kg)
50
930
610
770
730
100
960
680
820
750
160
1170
700
830
800
total
mineral oil
350
90
500
110
625
150
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present
document will bind us only after confirmation from our technical department.
France Transfo
BP 10140
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16
Ref : GEa 01 e
• Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 06/98
off-circuit
tappings switch
transformers with
standards HV
porcelain bushings
a
Typical dimensions and weights are indicated in
the table below for mineral oil immersed transformers.
They are provided for 20 kV / 400 V transformers
with electrical characteristics, as described in
the previous table.
For other electrical characteristics (voltage,
losses, etc…) or other dielectric, dimensions and
weights would be different, please consult us.
GEa.02 e
22/07/98 14:40
Page 1
HV/LV distribution transformers
ground mounted immersed transformers
from 100 to 3150 kVA - insulation < 24 kV / 400 V
IEC standards
m
description
This range consists of transformers complying
with the following specification:
m three-phase transformers, for indoor or outdoor use (installation to be specified);
m step-down type (1);
m rated frequency : 50 Hz (6);
m maximum ambient temperature : 40°C (5);
m mineral oil immersed (other dielectric upon
request);
m hermetically sealed with integral filling (7);
m cover bolted on tank;
m ONAN type natural cooling;
m standard anti-corrosion surface treatment
and coating (1);
m final colour grey RAL 7033 (1).
standards
These transformers comply with the following
standards:
– IEC standards;
– French standard NFC 52 100 (1990);
– CENELEC harmonization document
HD 398-1 to 398-5.
basic fittings
Each transformer includes:
m 1 off-circuit tappings switch with padlocking
located on the cover; this switch operates on the
highest rated voltage to bring the transformer to
the supply voltage-actual value;
m 3 fixed plug-in connectors parts HN 52 S 61
250 A / 24 kV - HV side;
m 4 LV flat-bars, from 250 kVA only; for 100 and
160 kVA: 4 LV porcelain bushings;
m 2 earthing terminals on the cover;
m 4 bi-directional flat rollers from 160 kVA;
m 2 lifting and untanking lugs;
m 1 rating plate to be fixed on 1 of the 4 sides;
m 1 filling plug;
m
ISO 9 0 01
AFAQ
N
1990/113b
1 draining device;
protection index IP 00.
options
The following fittings may be provided as an
option:
m 3 HV mobile plug-in connectors 250 A / 24 kV,
straight or elbow (the cable characteristics
should always be specified);
m 3 HV porcelain bushings;
m 4 LV porcelain bushings from 250 kVA;
m Locking device (lock not supplied) for plug-in
connectors;
m LV air-insulated terminal cover to be sealed
(possible only with plug-in connectors on HV
side and flat-bars on LV side);
m Protection devices : thermometer, thermostat,
DGPT2 relay, etc.
1000 kVA - 20 kV / 400 V
Note : the above options concern usual cases
and are not restrictive. For other information,
please consult us.
es
avec d t
n
réalisé
aranti e tout éléme
g
t
s
e
r
d
pollué
rmateu et exempts
té
é
fo
s
n
ir
a
o
d’av
Ce tr
eufs
ants n
eptible
constitu pération susc
u
c
en
de ré
as be
PCB.
rmer h
lly
par des
transfo and is tota
is
th
’s.
at
rial
ant th h new mate ted with PCB
rr
a
w
u
it
ll
o
w
We
p
d
s
part
cture
manufa second hand
ers.
m
ansform
free fro
n
o all tr
k
c
tu
s
Label
250 kVA - 20 kV / 400 V
France Transfo guarantees that its transformers are
assembled using components that are both new and
PCB-free (< 2 ppm level), in strict compliance with the
current standards.
* non standard ratings available on request.
(1) others upon request, consult us.
(2) load losses and rated impedance voltage, at 75°C.
(3) classification of dielectrics according to NF C 27-300 :
m O1 for mineral oil ;
m K3 for silicone oil.
(4) reminder of insulation levels :
insulation level (kV)
7.2
12
17.5
24
kV r.m.s. 50 Hz - 1 mn
20
28
38
50
kV B.I.L. 1.2/50 µs
60
75
95
125
(5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon
request, consult us.
(6) other rated frequency (60 Hz) upon request, consult us.
(7) breathing type transformer with conservator upon request,
consult us.
800 kVA - 20 kV / 400 V
electrical characteristics
rated power (kVA) (1)
primary (1)
rated voltage
secondary at no-load (1)
rated insulation level (4)
primary
HV tapping range (off-voltage)
vector group
losses (W)
no-load
load (2)
rated impedance voltage (%) (2)
no load current (%)
P.F. = 1
voltage drop at
full load (%)
P.F. = 0.8
P.F. = 1
load
100 % P.F. = 0.8
efficiencies (%)
P.F. = 1
load
75 % P.F. = 0.8
noise level (dBA) power acoustic LWA
acoustic pressure Lpa at 0.3 metre
100
160
250 315*
400 500*
630
15 or 20 kV
400 V between phases, 231 V phase to neutral
17.5 kV for 15 kV
24 kV for 20 kV
± 2.5 % or ± 5 % or ± 2.5 % ± 5 % (1)
Dyn 11 (1) (delta; star neutral brought-out)
210
460
650
800
930 1100 1300
2150 2350 3250 3900 4600 5500 6500
4
4
4
4
4
4
4
2.5
2.3
2.1
2
1.9
1.9
1.8
2.21 1.54
1.37 1.31 1.22 1.17
1.11
3.75 3.43
3.33 3.30 3.25 3.22
3.17
97.69 98.27 98.46 98.53 98.64 98.70 98.78
97.13 97.85 98.09 98.17 98.30 98.387 98.48
98.14 98.54 98.70 98.75 98.84 98.89 98.96
97.69 98.18 98.37 98.44 98.56 98.62 98.71
53
59
62
64
65
67
67
42
48
50
52
53
54
54
800
1000
1250
1600
2000
2500
3150
1220
10700
6
2.5
1.51
4.65
98.53
98.17
98.81
98.51
68
55
1470
13000
6
2.4
1.47
4.63
98.57
98.22
98.84
98.56
68
55
1800
16000
6
2.2
1.45
4.62
98.60
98.25
98.86
98.58
70
56
2300
20000
6
2
1.42
4.60
98.63
98.29
98.88
98.61
71
58
2750
25500
6
1.9
1.45
4.61
98.61
98.27
98.87
98.60
72
58
3350
32000
6
1.8
1.45
4.62
98.61
98.26
98.87
98.60
74
59
4380
33000
7
1.7
1.29
5.11
98.83
98.54
99.04
98.80
74
59
GEa.02 e
22/07/98 14:40
Page 2
HV/LV distribution transformers
ground mounted immersed transformers
from 100 to 3150 kVA - insulation < 24 kV / 400 V
IEC standards
dimensions and weights
off-circuit tappings switch
earthing terminal
lifting lug
Groupe Merlin Gerin · Usine de Maizières-lès-Metz (Moselle) France
Typical dimensions and weights are indicated in
the table below for mineral oil immersed
transformers.
They are provided for 20 kV / 400 V transformers
with electrical characteristics, as described in
the previous table.
For other electrical characteristics (voltage,
losses, etc.) or other dielectric, dimensions and
weights would be different (please consult us).
nº 216540
D*
C
40 (2)
J
A
F
F
N. B.
The terminal marking is in accordance with IEC
standards 616 (1978), see attached diagram.
38 (3)
J
B
K
Ø = 125(1)
(1)
(2)
(3)
off-circuit tappings switch
for 3150, Ø = 200
for 3150, 80
for 3150, 60
earthing
terminal
1W
1V
1U
2W 2V 2U 2N
C
n
B
c
A
a
b
D* : height over LV protection cover ; assembly
possible only if the HV is fitted with plug-in
connectors.
filling
plug
rating plate
H
H
cooling fins at the corners
for rated powers > 630 kVA.
H
dimensions (mm)
kVA
A
B
C
D*
F
H
J
K
flat-bars
porcelain LV
100
1000
700
900
1250
265
75
520
105
—
250A
160
1100
710
965
1315
265
75
520
105
—
250A
550
110
700
150
250
315
400
1160
1295
1315
860
895
915
1010
1060
1150
1360
1410
1500
265
265
265
150
150
150
520
670
670
105
105
105
1250A 1250A 1250A
630A
630A
630A
500
1495
925
1215
1565
265
150
670
105
1250A
1000A
630
800
1510
1695
940
975
1225
1395
1575
1745
265
265
150
150
670
670
105
105
1250A 1250A
1000A 1600A
1000
1250
1810
1850
975
1000
1495
1555
1905
1965
265
265
150
170
670
670
85
85
1600A 2500A
1600A 2500A
1600
2000
1930
2160
1220
1250
1575
1685
1985
2195
265
265
170
170
820
820
85
85
2500A 3150A
2500A 3150A
2500
3150
2550
2700
1830
1840
1690
1795
2200
2305
265
265
170
170
820
820
85
85
5000A 5000A
4000A 5300A
weights (kg)
total
mineral oil
1000
215
1165
275
1350
310
1545
350
1740
380
2100
450
2390
580
LV flat-bars (from 250 kVA only)
1600A
1250A
M 12
35
165
250 A
Ø 16
h10
60
Ø 30 h10
120
120
80
300
630 A
1000 A
1600 A
2500 A
with straight mobile
connector
M 12
100
300
350
315
3150 A
locking
lug
Ø 65 h10
35
295
250
215
87
HV porcelain bushings
Ø 63 h10
160
140
with elbow mobile
connector
5000A
Ø 56
h10
Ø 50
h10
locking
lug
45
3150A
LV porcelain bushings (compulsory for 100 and 160 kVA)
Ø 40
h10
255
Ø 18
Ø 18
2500A
5730
1230
290
50
45
Ø 14,5
Ø 11
250
31,5
Ø 14,5
4640
1130
200
20
25
50
135
35
50
50
52
31,5
Ø 11
3880
870
12
50
250
31,5
52
Ø 14,5
52
Ø 11
155
31,5
31,5
120
12
106,5
12
221
31,5
31,5
31,5
12
97,5
63
31,5
31,5
3500
790
HV fixed plug-in connectors
250 A - 24 kV
310
100
63
31,5
120
50
2850
670
330
4000A
5300A
Note : never use HV
porcelain bushings
with LV protected
by a terminal cover.
250A
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present
document will bind us only after confirmation from our technical
department.
France Transfo
BP 10140
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16
Ref : GEa.02 e
Edition France Transfo - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 09/96
earthing
terminal
GEa.04d
22/07/98 14:45
Page 1
HV/HV power transformers
immersed transformers
from 2500 to 5000 kVA - for 7.2 to 36 kV systems
IEC standards
ISO 9001-1994
AFAQ
N
1993/1275
description
options
This range consists of transformers complying
with the following specification :
m three-phase transformers, for indoor or outdoor use (installation to be specified) ;
m step-down type (1) ;
m rated frequency : 50 Hz (6) ;
m maximum ambient temperature : 40°C (5) ;
m mineral oil immersed (other dielectric upon
request)(3) ;
m hermetically sealed with integral filling (7) ;
m cover bolted on tank ;
m ONAN type natural cooling ;
m standard anti-corrosion surface treatment
and coating (1) ;
m final colour grey RAL 7033 (1).
The following fittings may be provided as an
option :
m 1 conservator (for breathing type transformer)
with :
M 1 level indicator tube ;
m 1 Buchholz relay with 2 contacts (alarm and
tripping) ;
M 1 silicagel airdryer;
m HV fixed plug-in connectors HN 52 S 61 :
M 250, 400, 630 or 1250 A / 24 kV ;
M 400 A / 36 kV.
m HV plug-in mobile connectors HN 52 S 61 (the
cable characteristics should always be specified) ;
m 1 locking device (lock not supplied) for plug-in
connectors ;
m 1 DGPT2 relay (automation 2000) ;
m 1 thermostat two contacts (alarm and tripping) ;
m 1 dial type thermometer (with or without
contact) ;
m 1 wiring box with terminals board for connecting optional electrical equipment (Buchholz
relay, thermostat, thermometer, etc…).
standards
These transformers comply with the following
standards (1) :
– IEC standards ;
– French standards NFC 52 100 (1990);
– and CENELEC harmonization document
HD 398-1 to 398-5.
mineral oil immersed transformer
5000 kVA, 20 - 13.75/5.5 - 3.2 kV.
basic fittings
Each transformer includes :
m 1 off-circuit tappings switch with padlocking
located on the cover ; this switch operates on
the highest rated voltage to bring the transformer to the supply voltage-actual value ;
m porcelain bushings on primary and secondary
sides ;
m 2 earthing terminals on the cover ;
m 4 bi-directional flat rollers ;
m 2 lifting and untanking lugs ;
m 1 rating plate to be fixed on 1 of the 4 sides ;
m 1 filling plug ;
m 1 draining device ;
m protection index IP 00.
Note : the above options concern usual cases
and are not restrictive. For other information,
please consult us.
des
é avec
ti réalis ut élément
n
ra
a
g
to
st
llué
ateur e exempts de
été po
nsform
Ce tra nts neufs et ptible d’avoir
a
e
constitu pération susc
u
de réc CB.
been
P
r has
par des
sforme d is totally
n
a
tr
is
n
that th w material a with PCB’s.
e
arrant
We w tured with n parts polluted
c
manufa second hand
.
m
formers
free fro
all trans
tuck on
s
l
e
b
a
L
mineral oil immersed transformer
5000 kVA, 20/6 kV.
France Transfo guarantees that its transformers are
asembled using components that are both new and
PCB-free (< 2 ppm level), in strict compliance with the
current standards.
electrical characteristics
rated power (kVA) (1)
primary
rated insulation
level (4)
secondary
HV tapping range (off-voltage)
vector group
no-load
losses (kW)
load (2)
rated impedance voltage (%) (2)
no-load current (%)
P.F. = 1
voltage drop at
full load (%)
P.F. = 0.8
load P.F. = 1
100 % P.F. = 0.8
efficiencies (%)
load P.F. = 1
75 % P.F. = 0.8
2500 3150 4000
7.2 - 12 - 17.5 - 24
7.2 -12
± 5 (1)
Dyn 11 or YynO (1)
3.35
4.5
5
32
29
33
6
7
7
1.8
1.6
1.4
1.45 1.16 1.07
4.62 5.02 4.96
98.61 98.95 99.06
98.26 98.69 98.83
99.87 99.13 99.22
98.60 98.91 99.03
5000 2500 3150 4000
36
7.2 - 17.5
± 5 (1)
Dyn 11 or YynO (1)
6
4
4.5
5.5
40
25
30
34
7.5
6.5
7
7
1.3
2.1
1.9
1.8
1.08 1.21 1.19 1.09
5.26 4.76 5.05 4.98
99.09 98.85 98.92 99.02
98.86 98.57 98.65 98.78
99.25 99.05 99.10 99.19
99.06 98.81 98.88 98.98
5000
6.5
41
7.5
1.6
1.10
5.28
99.06
98.83
99.22
99.02
(1) others upon request, consult us.
(2) load losses and rated impedance voltage at 75°C.
(3) classification of dielectrics according to NF C 27-300 :
m O1 for mineral oil ;
m K3 for silicone oil.
(4) reminder of insulation levels :
rated insulation
level (kV)
7.2
12
17.5
kV r.m.s. 50 Hz - 1 mn
20
28
38
50
70
kV B.I.L. 1,2/50 µs
60
75
95
125
170
24
36
(5) other ambient temperature (45°C, 50°C, 55°C, etc…) upon
request, consult us.
(6) other rated frequency (60 Hz) upon request, consult us.
(7) breathing type with conservator, upon request, consult us.
GEa.04d
22/07/98 14:45
Page 2
HV/HV power transformers
immersed transformers
from 2500 to 5000 kVA - for 7.2 to 36 kV systems
IEC standards
dimensions and weights
off-circuit tappings switch
Typical dimensions and weights are indicated in
the table below for mineral oil immersed transformers.
They correspond to transformers intented for
systems of 7.2 to 36 kV having electrical characteristics, as described in the previous table.
For other electrical characteristics (voltage,
losses, etc…) or other dielectric, dimensions and
weights would be different, please, consult us.
lifting lug
rating plate
C
Groupe Merlin Gerin · Usine de Maizières-lès-Metz (Moselle) France
nº 216540
N. B.
The terminal marking is in accordance with IEC
standards 616 (1978), see attached diagram.
draining
device
E
earthing
terminal
A
filling
plug
2N 2U 2V 2W
earthing
terminal
1U
B
1V 1W
off-circuit tappings switch
rated power
(kVA)
dimensions (mm)
A
B
primary 7.2 - 12 - 17.5 - 24 kV (HV secondary)
2500
2200
1800
3150
2700
1800
4000
3000
2000
5000
3200
2200
primary 36 kV (HV secondary)
2500
2500
1800
3150
2800
1900
4000
3100
2100
5000
3300
2300
weights (kg)
total mineral
oil
C (1)
D
E
2070
2140
2500
2700
1430
1520
1700
1800
820
820
1000
1000
4900
5550
7200
8500
1000
1100
1500
1700
2070
2170
2600
2800
1430
1550
1800
1900
820
820
1000
1000
4900
6000
8000
9300
1000
1200
1880
2080
HV porcelain bushings
Ø 30
M 12
80
490 (36kV)
35
330 (23/24kV)
250 (7,2/23kV)
Ø 16
407
62
312
630A
250A
1000A
HV fixed plug-in connectors HN 52 S 61 - 250 A - 24 kV (2)
200
290
255
locking
lug
with elbow mobile connector
87
locking
lug
with straight mobile connector
(1) Breathing type transformer with conservator.
(2) For dimensions of other plug-in connectors, please,
consult us.
Casual arrangements such as bars and cables supports, flexible connectors, etc… are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present
document will bind us only after confirmation from our technical
department.
France Transfo
BP 140
F 57211 Maizières-lès-Metz Cedex
tel. (+33) 87 70 57 57 - fax (+33) 87 51 10 16
Ref : GEa.4 d
Edition France Transfo - BP140 F57211 Maizières-les-Metz Cedex - Limited company - Social capital 10 280 000 FRF - RCS Metz B 357 801 109 • Printed in France • Composition and illustrations : COREDIT • 02/96
D
GEa.05 c
22/07/98 14:51
Page 1
HV/HV power transformers
immersed transformers
from 5 to 60 MVA
for 7.2 to 123 kV systems
ISO 9 0 01
AFAQ
N
1990/113b
description
This range consists of transformers complying
with the following specification:
m three-phase transformers, 50 or 60 Hz,
for indoor or outdoor use (installation to be
specified);
m maximum ambient temperature: 40°C (5);
m mineral oil immersed (other dielectric upon
request);
m breathing type with conservator ;
m cover bolted on tank or welded bell type as
per specification;
m ONAN, ONAF, ODAF or ODWF cooling type;
m standard anti-corrosion surface treatment
and coating (1);
m final colour grey RAL 7033 (1).
standards
These transformers comply with the following
standards (1):
– IEC standards;
– French standards NFC 52 100 (1990).
basic fittings
Each tranformer includes:
m 1 off-circuit tappings switch with padlocking
located on the cover ; this switch operates on
the highest rated voltage to bring the
transformer to the supply voltage-actual value
(generally ± 5%, 3 or 5 positions);
m porcelain bushings on primary and secondary
sides;
m 2 earthing terminals;
m 1 conservator with level indicator tube;
m 1 silicagel airdryer;
m 1 Buchholz relay with 2 contacts (alarm and
tripping);
m 1 thermostat with two contact (alarm and
tripping);
m 1 dial type thermometer (without contact);
m 4 directional flat rollers;
m lifting and/or untanking lugs;
m 1 rating plate;
m 1 filling plug;
m 1 draining device and treatment valve with
sampler.
options
M
1 protective relay and eventually, on request:
1 parallel operation device;
M 1 voltage regulator with voltage drop equalizer;
M 1 remote indicator of tap changer position.
m magnetic level indicator (with or without
contact, please specify);
m HV fixed plug-in connectors HN 52 S 61:
M 250, 400, 630 or 1250 A - 24 kV;
M 400, 630 or 1250 A - 36 kV.
m HV mobile plug-in connectors HN 52 S 61,
straight or elbow (the cable characteristics
should be specified);
m condenser bushings;
m increased creepage distance bushings;
m 1 bonnet on HV bushings:
M in the air for connection by dry cables or busducts (except rated insulation level 72.5 kV) ;
M oil immersed, hermetically sealed for cable
connection;
M SF6 immersed, hermetically sealed for
connection by busbars on oil/SF6 bushings;
m winding temperature indicator by thermal
image ;
m current transformer:
M “bushing” type around terminals;
M standard type for earth fault current detector;
m 1 overpressure valve (with or without
contact, please specify);
m 1 automatic oil retaining valve (between
conservator and tank);
m “Atmoseal” oil protection system;
m 1 treatment valve at the upper part of the tank;
m 1 insulation valve for radiators;
m 4 jacking lugs with hauling eyes.
M
Note : the above options concern usual cases
and are not restrictive. For other information,
please consult us.
Transformer 36 MVA, 62.5/18.4 kV with on-load tap
changer, ODAF type cooling.
ec des
lisé av
nti réa ut élément
ra
a
g
t
to
s
llué
ateur e exempts de
été po
nsform
Ce tra nts neufs et ptible d’avoir
a
e
constitu pération susc
u
de réc CB.
been
P
er has
par des
ansform and is totally
tr
is
B’s.
that th w material
with PC
e
arrant
We w tured with n parts polluted
c
d
fa
manu
nd han
.
m seco
formers
free fro
all trans
tuck on
s
l
e
b
a
L
The following fittings may be provided as an
option:
m 1 on-load tap changer in the main tank
(generally ± 12% - 19 positions maximum) with:
M 1 motor drive unit fitted on tank;
M 1 tap changer compartment in the conservator
with a level indicator;
France Transfo guarantees that its transformers are
assembled using components that are both new and
PCB-free (< 2 ppm level), in strict compliance with the
current standards.
electrical characteristics
él
Typical characteristics are indicated in the table
below up to 30 MVA / 72.5 kV. Above, please
consult us. They correspond to transformers of
ONAN type cooling (3), with or without tap
changer.
It is possible to develop equipment with totally
different values of voltage and rated impedance
voltage. In this case, dimensions and weights
are also different.
rated power (3)
5
10
20
(MVA)
primary 24-36
rated
insulation
secondary 7.2 - 12 - 17.5 - 24
level (kV) (4)
no-load
6
10
17
losses
(kW)
load (2)
43
71
120
8
9
10
rated
impedance voltage (%) (2)
Transformer 20/25 MVA, 65/20 kV with on-load tap
changer, ONAN/ONAF type cooling.
25
5
10
20
25
30
72.5
7.2 - 12 - 17.5 - 24
21
140
11
7
43
8
11
71
9
(1) other possibilities upon request, please consult us.
(2) load losses and rated impedance voltage at 75°C.
(3) each type of cooling device comes with its particular type
of equipment (circulators, ventilators, etc.).
cooling
type
ONAN
of
oil
m
natural through
thermosiphon
directional through
circulators
of
natural through
tank air convection
forced
through fans
forced through
water circulation
ODAF
ONAF
ODWF
m
m
m
m
m
m
m
(4) reminder of insulation levels:
rated insulation
level (kV)
18
120
10
22
140
11
25
160
11
7.2
12 17.5 24
36
52 72.5
90 123
70
95 140 185 230
kV r.m.s. 50 Hz - 1 mn
20
28
38 50
kV B.I.L. 1.2/50 µs
60
75
95 125 170 250 325 450 550
(5) other ambient temperature (45°C, 50°C, 55°C, etc.) upon
request, consult us.
GEa.05 c
22/07/98 14:51
Page 2
HV/HV power transformers
immersed transformers
from 5 to 60 MVA
for 7.2 to 123 kV systems
dimensions and weights
Typical dimensions and weights are indicated in
the table below for mineral oil immersed
transformers, completely set up* with a standard
type cooling.
They correspond to transformers intented for
systems of 7.2 to 72.5 kV having electrical
characteristics as indicated in the previous table.
For other voltages, other characteristics or
when the transformers are immersed in another
dielectric, dimensions and weights would be
different, please, consult us.
ONAN type cooling
C
E
B
A
Transformers 5 MVA, with off-voltage tappings switch.
D* : hauteur sur capot de protection BT ;
montage possible uniquement lorsque la MT
C
est équipée de prises embrochables.
B
E
A
Transformers 5 MVA with on-load tap changer, or 10
to 25 MVA with off-voltage tappings switch or with
on-load tap changer.
ODAF type cooling
rated power with off-voltage tappings switch
with on-load tap changer
(MVA)
dimensions (mm)
total
dimensions (mm)
total
A
B
C
weight (kg) A
B
C
weight (kg)
rated insulation level 72.5 kV
20
3500 2700 4000
21000
4500 3000 4000
23000
25
4000 3000 4300
25000
4700 3000 4300
28000
rated insulation level > 72.5 kV, consult us.
C
B
A
Transformers 20 to 25 MVA, with off-voltage switch or
on-load tap changer.
* For the protection of some components or the compliance
with the railway or road regulations, the transformers could
be delivered partially dismantled.
Casual arrangements such as bars and cables supports, flexible connectors, etc. are to be provided the contractors in order to avoid mechanical stresses on the transformer flat-bars and bushings.
Due to the evolution of standards and materials, the present
document will bind us only after confirmation from our
technical department.
France Transfo
BP 10140
F 57281 Maizières-lès-Metz Cedex
tel. (+33) 03 87 70 57 57 - fax (+33) 03 87 51 10 16
Ref : GEa.05 c
Edition France Transfo - SA au capital de 10 280 000 FRF - RCS Metz B 357 801 109 • Imprimé en France • Composition et illustrations : COREDIT • 09/96
rated power with off-voltage tappings switch
with on-load tap changer
(MVA)
dimensions (mm)
total
dimensions (mm)
total
A
B
C
E
weight (kg) A
B
C
E
weight (kg)
rated insulation level 24 kV
5
2700 2100 2500 1000
8500
3400 2200 2550 1000
10000
10
3750 2450 3500 1500
17000
3800 2500 3500 1500
19000
20
4300 3900 3600 1500
26500
4600 3900 3600 1500
27000
25
4000 3900 3800 1500
35000
4100 3900 3800 1500
37000
31 à 60
consult us
rated insulation level 36 kV
5
3300 2400 2950 1000
11000
3600 2400 3000 1000
13000
10
3900 3300 3600 1500
18000
3900 3400 3600 1500
20000
20
4400 3950 3700 1500
27000
4700 4000 3700 1500
29000
25
4200 4300 4000 1500
36000
4800 4300 4000 1500
38000
31 to 60
consult us
rated insulation level 72.5 kV
5
4100 2600 3300 1000
17000
10
3900 3400 3500 1500
18000
4000 3900 3600 1500
22000
20
4500 4000 4000 1500
27000
5000 4100 4000 1500
32000
25
4400 4600 4300 1500
41000
5000 4600 4300 1500
43000
30
consult us