System Design Guide

advertisement
System
Design
Guide
SYSTEM DESIGN GUIDE
This System Design Guide provides general guidance regarding lighting
control sequences and applications in commercial and institutional buildings.
Furthermore, engineers, electrical contractors and property managers will
find all the necessary information on how to design a Kameleon system
according to their control needs and specifications.
For any additional information on the Kameleon systems, we invite you to visit
our web site at www.kameleonlighting.com or to contact your local
representative.
TYPICAL
APPLICATIONS
Gentec's Kameleon K Series offers a wide range of solutions to suit any
lighting control requirement. From the field programmable K4 Series for
small to medium size applications to the Echelon based console-operated K8
Series with dimming capabilities and BACnet base networked K6 series, the
Kameleon K Series will adapt to all possible configuration needed by the
end-user.
COMMON CONTROL
SEQUENCES
COMMON CONTROL SEQUENCES
CONTENTS
K8 Series Configurations
Parts Index
SYSTEM
COMPONENTS
Kameleon K Series Components
K4 Series Configurations
PART INDEX
Typical Applications
Kameleon K Series Overview
SYSTEM
CONFIGURATION
Common control sequences
SYSTEM DESIGN GUIDE
COMMON CONTROL SEQUENCES
COMMON CONTROL
SEQUENCES
THE FOLLOWING SECTION – CONTROL SEQUENCES, DESCRIBES THE MOST COMMONLY USED LIGHTING CONTROL
SEQUENCES IN A COMMERCIAL BUILDING.
TIMED SCHEDULES
The sweep ON/OFF Operation is used to turn preset lights ON and OFF automatically
according to pre-programmed schedules*. To permit off-hours activities, such as
overtime and janitorial work, scheduling can be overridden through different actions
such as manual ON/OFF and motion detection.
TYPICAL
APPLICATIONS
*The schedule programming is performed directly on the KC-411 8 Channel Time Clock for the K4 Series and through
the Kameleon Software for the K8 Series.
OVERRIDE SWITCHING
The manual ON/OFF Operation gives occupants total control of the lighting in each
of the zones equipped with a switch-based device. Manual ON/OFF is the most common
override operation. Switches and/or ON action and/or OFF action can be disabled
separately according to time schedules*.
SYSTEM
CONFIGURATION
*Available only with the K8 Series.
HOLD ON TIME / TIME ON EXTENSION
The Time ON Extension Mode (TOE) causes the Time Clock* to start a timer
when the
relay is switched ON. Upon time expiry (generally a building-wide standard period**),
the relay is switched OFF. The TOE mode can be enabled and disabled according to a time
schedule. Thus, switches work normally during business hours and in TOE mode during
off-work hours.
SYSTEM
COMPONENTS
* KC-411 for the K4 Series or KC-811 for the K8.
** The period is set at two hours with the K4 Series and adjustable with the K8 Series.
FLICK WARN
The Flick Warn Function is used to remind occupants that lights will be
switched
OFF after a pre-programmed countdown*. After a pre-set hold time period, the Occupancy
sensor will switch lighting OFF again if no presence is being detected*. Occupancy
sensors and/or On action and/or Off action can be enabled and disabled separately
according to time schedules**.
PART INDEX
* Variable hold-time periods can be programmed on a schedule base for each occupancy sensor with the K8 Series.
** Available only with the K8 Series
SYSTEM DESIGN GUIDE
COMMON CONTROL SEQUENCES
The Motion Sensing Operation will switch lighting ON upon the detection of a person entering
the zone covered by the sensor beam. After a pre-set period, the motion sensor will switch
lighting OFF again if no presence is being detected. Motion sensors can be enabled and disabled
according to time schedules. Also, the occupancy sensor can be used to turn ON lights in the
morning. The OFF sequence triggered by the sensor will then be only permitted after the end of
normal business hours.
COMMON CONTROL
SEQUENCES
OCCUPANCY SENSING
Enabled during off-work hours, the Cleaning/Security Function will allow authorized employees
(janitor, guard, landlord, etc.) to switch the lights ON/OFF in preset areas without disturbing
the occupants. The Cleaning/Security Function is generally performed through the use of key
switches. When the key switch is activated, the system memorizes the current status of all the
relays in the area. An ON activation of the key switch will turn ON all the OFF relays in the area.
The OFF activation of the key switch will only turn OFF the relays that were already OFF before
the ON activation.
*Available only with the K8 Series.
TYPICAL
APPLICATIONS
CLEANING/SECURITY*
DAYLIGHTING AND DAYLIGHT HARVESTING
a. Daylighting control is used to generate energy savings. Through the use of daylight sensor
and dimmable ballasts, the light level in peripheral areas is automatically adjusted according
to the amount of natural light available.
PHOTOMETRIC CONTROL
The Photometric Function will turn the exterior or interior lights ON and OFF according to the
ambient light level. Time Control can be used to override the photocell effect and to switch
lights OFF.
ASTRONOMICAL CONTROL
Through the use of the time zone, the latitude, the longitude and the date, the astronomical
clock can calculate the sunset and sunrise times. Light can be programmed to switch at these
calculated times. An offset can be programmed to cause the switching to occur sooner or later
than the actual sunset and sunrise.
SYSTEM
COMPONENTS
*Available only with the K8 Series
PART INDEX
Dimming control is used to adjust light level according to specific needs. In most cases, dimming
sequences will be programmed and will follow pre-set scenes that will include targeted light
level, fade time and hold time. The activation of these scenes is done through the use of
schedules, switches or occupancy sensors. Dimming Controllers* are used to control the
analog (0-10v) or the digital (DMX-512, Dali) dimmable ballast tied to the lights.
SYSTEM
CONFIGURATION
DIMMING
SYSTEM DESIGN GUIDE
TYPICAL APPLICATIONS
LD
DE
SC
ER
OV
TIM
ED
TYPICAL
APPLICATIONS
COMPONENT REQUIREMENTS
RI
HE
DU
LE
S
SW
ITC
ON
OC
HI
TIM
CU
NG
PA
E
CL
NC
EA
YS
NI
EN
NG
DA
/SE SIN
YL
IG
C
UR G
HT
FL
ITY
I
IC
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
OFFICE BUILDINGS
HO
COMMON CONTROL
SEQUENCES
THE FOLLOWING SECTION – TYPICAL APPLICATIONS, PRESENTS THE MOST COMMONLY USED CONTROL SEQUENCES
INSIDE COMMERCIAL BUILDINGS. FOR EACH APPLICATION, THE REQUIRED LIGHTING CONTROL COMPONENTS ARE
LISTED.
• K6 or K8 Series Panels
• Low Voltage Switches with Pilot LEDs
• Key Switches
• Motion Detectors
• Constant Light Controllers
• Exterior Photocell
• Kameleon Software (K8)
• Link to the Building Management System**
• Dimming Controllers*
HE
DU
RI
LE
DE
HO
S
LD
SW
ITC
ON
OC
H
T
CU
IN
PA IME
G
CL
NC
EA
Y
NI
S
E
NG
DA
N
/SE SIN
YL
IG
G
CU
HT
FL
RI
I
IC
TY
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
SCHOOLS
ER
TIM
ED
OV
SYSTEM
COMPONENTS
SC
SYSTEM
CONFIGURATION
*If centralized dimming control is required
** Optional
COMPONENT REQUIREMENTS
• K4, K6 or K8 Series Panels
• Toggle Switches
• Key Switches
• Motion Detectors
• Constant Light Controllers
• Exterior Photocell
• Link to Building Management System*
PART INDEX
*Optional (available only with K8 Series)
SYSTEM DESIGN GUIDE
COMMONAPPLICATIONS
TYPICAL
CONTROL SEQUENCES
• K4, K6 or K8 Series Panels
• Low Voltage Switches with Pilot LEDs
• Motion Detectors
• Constant Light Controllers
• Exterior Photocell
• Link to Building Management System*
*Optional (available only with K8 Series)
IT
ON
TIM CHIN
PA
G
E
NC
EA
YS
NI
E
N
DA
G/S NS
YL
EC ING
IG
UR
HT
FL
ITY
IN
IC
G
KW
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
• K4 Series Panels or K8 Series Panels
• Low Voltage Switches with Pilot LEDs
• Occupancy Sensors
• Exterior Photocell
• Dimming Controllers*
*If centralized dimming control is required
(available only with K8 Series)
COMMON CONTROL
SEQUENCES
COMPONENTS REQUIREMENTS
• K4 Series Panels
• Low Voltage Switches with Pilot LEDs
• Constant Light Controllers
• Exterior Photocell
PART INDEX
ER
OV
TIM
ED
SC
H
ED
RI
UL
DE
HO
ES
LD
S
ON WITC
OC
HI
T
CU
IM
NG
PA
E
CL
NC
EA
Y
NI
NG SEN
DA
/SE SIN
YL
IG
G
CU
HT
FL
RI
IN
IC
TY
G
KW
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
CAR DEALERS
SYSTEM
COMPONENTS
CL
OC
CU
COMPONENTS REQUIREMENTS
SYSTEM
CONFIGURATION
SW
LD
DE
HO
RI
ER
OV
TIM
ED
SC
HE
DU
LE
S
RESTAURANTS
TYPICAL
APPLICATIONS
COMPONENTS REQUIREMENTS
OV
TIM
ED
SC
HE
ER
DU
RI
LE
DE
HO
S
LD
SW
ON
I TC
OC
HI
TIM
CU
NG
PA
E
CL
NC
EA
YS
NI
EN
NG
DA
/SE SIN
YL
IG
C
UR G
HT
FL
ITY
I
IC
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
RETAIL STORES
SYSTEM DESIGN GUIDE
TYPICAL APPLICATIONS
COMPONENT REQUIREMENTS
• K4, K6 or K8 Series* Panels
• Low Voltage Switches with Pilot LEDs
• Motion Detectors
• Exterior Photocell
• Dimming Controllers*
*if centralized dimming control is required
COLLEGES
HE
ER
DU
RI
LE
DE
HO
S
LD
SW
ON
ITC
OC
H
T
CU
IM
IN
PA
G
E
CL
NC
EA
Y
NI
S
E
NG
DA
N
/SE SIN
YL
IG
G
CU
HT
FL
RI
I
IC
TY
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
TIM
ED
SC
OV
HE
ER
DU
RI
LE
DE
HO
S
LD
SW
ON
I TC
OC
H
T
CU
IM
IN
PA
G
E
CL
NC
EA
Y
NI
S
EN
NG
DA
/SE SIN
YL
IG
G
CU
HT
FL
RI
I
IC
TY
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
FACILITIES**
ED
TIM
OV
• K6 or K8 Series Panels
• Low Voltage Switches with Pilot LEDs
• Key Switches
• Motion Detectors
• Constant Light Controllers
• Exterior Photocell
• Kameleon Software (K8)
• Link to the Building Management System
• Dimming Controllers*
*if centralized dimming control is required
HE
ER
DU
RI
LE
DE
HO
S
LD
SW
ON
ITC
OC
T
H
CU
IM
IN
E
PA
G
CL
NC
EA
Y
NI
S
EN
NG
DA
/SE SIN
YL
IG
G
CU
HT
FL
RI
I
IC
TY
K W NG
AR
DI
MM
N
I
PH NG
OT
OM
AS
ET
TR
RI
C
ON
CO
OM
NT
IC
RO
AL
L
CO
NT
RO
L
PARKING LOTS
ED
TIM
PART INDEX
OV
SC
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
SC
COMPONENT REQUIREMENTS
COMPONENT
REQUIREMENTS
• K4 or K8 Series Panels
• Exterior Photocell
SYSTEM DESIGN GUIDE
COMMONCONFIGURATION
SYSTEM
CONTROL SEQUENCES
MD
A COMPLETE LINE
K8 SERIES SYSTEM
VERSATILITY AND CONNECTIVITY
COMMON CONTROL
SEQUENCES
K
ameleon Lighting Control Systems offer highly customizable configurations that are designed to fully adapt to
the occupants, as well as providing cost-savings opportunities to the owners. In its efforts to provide a solution
for all types of needs, Gentec R&D Team has been developing three complementary systems: the K4, K6 and
the K8-Series.
K4 and K6 SERIES SYSTEM
FIELD PROGRAMMABLE
TYPICAL
APPLICATIONS
KAMELEON SOFTWARE
KC-84x DIMMING
CONTROLLER
KC-401
Relay Controller
KC-811 TIME CLOCK
CONTROLLER
KC-821 INPUT
CONTROLLER
BACnet Node
SYSTEM'S FEATURES
8,16, 32 & 64 8,16, 32 & 64 8,16, 32 & 64 8,16, 32 & 64
*
*
-
*
**
Limited
-
-
-
+BAS
-
***
-
* Optional ** Only if not equipped with the KC-811 Time Clock Controller *** 2-hour Fixed Time
BAS: Building Automation System
+BAS
SYSTEM
COMPONENTS
-
+BAS
+BAS
+BAS
+BAS
-
-
PART INDEX
Relay Panels Capacity
Two-Wire, 20A, H.I.D., 1 Pole, Latching Relay
Two-Wire, 20A Plug-In Relays, 1 Pole, Latching Relay
Two-Wire, 20A, H.I.D., Breaker-Relay, Latching Relay
On-Site Programmable Time Clock (8 Channels)
On-Site Group Configuration
Network Capability
Interoperability – LonMark / LonWork
Interoperability -- BACnet
Software Interface
Telephone/Modem Interface and Internet Connection
Switches/Sensors/Photocells Connection
Dataline devices (Detector-Switch…)
Warning Flick
Time-On Extension
Delay On/Off
Advanced Scheduling Programming
Logger
Dimming Control
Scene Controller
DMX-512 Compatible
Load Shedding Capabilities
Daylight Harvesting
SYSTEM
CONFIGURATION
KC-83X OUTPUT
CONTROLLER
Conectivity
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
~
8 RELAY SYSTEM
AVAILABLE CONTROL SEQUENCES
• Sweep ON/OFF
• Sweep OFF
• Manual ON/OFF
• Hold On Time / Time On Extension
• Flick Warning
• Occupancy Sensing
To Low-Voltage / Dry-contacts
Accessories
KC-411
Time Clock/
Relay Controller
CONTROL CAPACITY
• Outputs: Up to 8
• Inputs: 2 + 2 Photocells
• Grounds: Groups: Up to 2 + 2 Photocells
~
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
THE FOLLOWING SECTION – K4 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE
K4 SERIES IN TERMS OF CONTROL CAPACITY.
Photocells
SYSTEM
CONFIGURATION
~
16 RELAY SYSTEM
AVAILABLE CONTROL SEQUENCES
• Same as the 8 Relay System
To Low-Voltage / Dry-contacts
Accessories
CONTROL CAPACITY
• Outputs: UP TO 16
• Inputs: 6 + 2 PHOTOCELLS
• Grounds: UP TO 6 + 2 PHOTOCELLS
KC-401
Relay Controller
~
KC-411
Time Clock/
Relay Controller
32 RELAY SYSTEM
~
SYSTEM
COMPONENTS
Photocells
AVAILABLE CONTROL SEQUENCES
• Same as the 8 Relay System
CONTROL CAPACITY
• Outputs: UP TO 32
• Inputs: 10 + 2 PHOTOCELLS
• Groups: UP TO 10 + 2
KC-411
Time Clock/
Relay Controller
KC-401
Relay Controller
~
PART INDEX
PHOTOCELLS
To Low-Voltage / Dry-contacts
Accessories
Photocells
link
KC-401
Relay Controller
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
FIELD PROGRAMMABLE SYSTEM
SPECIFICATIONS
• Power supply: 24VAC, 125 MA
• IEC Standard compliance: Fast Transient Disturbance
Tests & Electrostatic Discharge Immunity Test
• Dimensions: 4.2 in x 7.0 in (107 mm x 180mm)
TYPICAL
APPLICATIONS
• Field programmable time clock controller
• 8 output (channels or relays)
• Up to 2 groups (zones) configuration
• A kc-411 can be networked with a kc-401 to
Control up to 24 relays and 6 groups
• Multi group relay assignment capability
• Lcd display (4 lines - 20 characters)
• Membrane keypad
• Push button switch tone
• Palm pilot programming/operation capabilities (irda)
• Multiple input combination (2 devices)
• Photocell (indoor and outdoor) dedicated input (2)
• Daylight savings
• Astronomical clock
• 365-day, 7-day and 24 - hour programming
• Up to 256 schedules (once, daily, weekly,
monthly, yearly)
• Event priority management
• Automatic opposite action programming
• Energy code certified features
SYSTEM
CONFIGURATION
DESCRIPTION
COMMON CONTROL
SEQUENCES
KC-411 TIME CLOCK/RELAY CONTROLLER
KC-401 RELAY CONTROLLER
• Field programming relay controller
• 16 output (20a hid relay controller)
• Up to 4 groups (zones) configuration
• Two controllers can be networked and therefore
control up to 32 relays and 8 groups
• Multi group relay assignment capability
• Real time system status feed back provided
through different led patterns
• Multiple input combination (4 devices)
• Energy code certified features
SYSTEM
COMPONENTS
DESCRIPTION
• Power supply: 24VAC, 125 MA
• IEC Standard compliance: Fast Transient Disturbance
Tests & Electrostatic Discharge Immunity Test
• Distance : Up to 1,000 ft in bus mode and up to 175 ft
in free topology, without repeater
• Dimensions: 4.2 in x 7.0 in (107 mm x 180mm)
PART INDEX
SPECIFICATIONS
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
THE FOLLOWING SECTION – K6 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE
K6 SERIES IN TERMS OF CONTROL SEQUENCES AND CAPACITY.
BASIC SYSTEM
8-16-32-64 Relay System
To Low Voltage Control Devices
AVAILABLE CONTROL SEQUENCES
• Sweep ON/OFF
• Sweep OFF
• Manual ON/OFF
• Time ON Extension
• Flick Warning
• Occupency Sensing
• Daylight Harvesting
CONTROL CAPACITY
• Output 8 to 64
• Input 12 + 2 P
• Groups UP to 12 + 2
• Photocells
NETWORK SYSTEM
Remote Acces Capabilities
Central Building
Automation System
KC401
Relay Controller
BACnet Node
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
K4 #1
K4 #2
K4 #3
COMMON CONTROL
SEQUENCES
BACnet CONFIGURATION
K4 #4
Gentec KC601
BACnet Gateway
Lighting Controller
PC with BACnet Console
TYPICAL
APPLICATIONS
BACnet
Communication
SYSTEM
COMPONENTS
Communication
PART INDEX
Configuration
SYSTEM
CONFIGURATION
PC with KC601
Configuration
Console
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
KC-601 BACnet NODE
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Field programmable and configurable
• 1 Inpout RS485 "BACnet communication
• 1 Input RS232 port / PC
• 5 LED indicating light - Communication and operation status
• 1 Reset buttom
• 4 Output RS485 Communication port / KC401 Controller
TYPICAL
APPLICATIONS
SPECIFICATIONS
• Power by 24 V ac 10VA
• IEC Standards compliance: Fast Transient Disturbance
• Test & Electrostatic Discharge Immunity Test
• Dimension: 4.25 in x 7.0 in (107mm x 180 mmm)
• Terminal DB9-RS232 port
• Terminal RJ11 output RS485 communication port
• Quick Connector for BACnet RS485
KC-401 RELAY CONTROLLER
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
DESCRIPTION
• Field programming relay controller
• 16 output (20a hid relay controller)
• Up to 4 groups (zones) configuration
• Two controllers can be networked and therefore
control up to 32 relays and 8 groups
• Multi group relay assignment capability
• Real time system status feed back provided
through different led patterns
• Multiple input combination (4 devices)
• Energy code certified features
SPECIFICATIONS
• Power supply: 24VAC, 125 MA
• IEC Standard compliance: Fast Transient Disturbance
Tests & Electrostatic Discharge Immunity Test
• Distance : Up to 1,000 ft in bus mode and up to 175 ft
in free topology, without repeater
• Dimensions: 4.2 in x 7.0 in (107 mm x 180mm)
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
COMMON CONTROL
SEQUENCES
the adoption of LonWork® open system technology by Echelon®, the Kameleon K8 and K8D Dimming
Series serve the objective of bringing the complete hardware and software package capability of
operating stand-alone or whith a complete control network.
Like the namesake, the adapt perfectly to any environment they are put in as BAS Building
Automation System.
HVAC
Security
Photocells
Motion
Detectors
Fire Alarm
Dimmer
Blinds Control
Modem
Relay Panel 1
SYSTEM
CONFIGURATION
Chilling and
Cooling Control
Computer
(optional)
Rela
y Pan
el 2
Rela
y Pan
el 3
Rela
y Pan
el xx
SYSTEM
COMPONENTS
Telephone
Interface
PART INDEX
Light
Sensors
TYPICAL
APPLICATIONS
Switches
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
COMMON CONTROL
SEQUENCES
THE FOLLOWING SECTION – K8 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE
K8 SERIES IN TERMS OF CONTROL SEQUENCES AND CAPACITY.
BASIC SYSTEM
AVAILABLE CONTROL SEQUENCES
RESET
SERVICE
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
SER
RX
TX +5V INI
KC-811 Digital
Time Clock
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TYPICAL
APPLICATIONS
AC2
N24
L24
CT
SER
N24
AC2
L24
AC2
AC2
CONTROL CAPACITY
CT
• Sweep ON/OFF
• Sweep OFF
• Flick Warning
• Hold On Time / Time On Extension
KC-831 Output
Controller*
• Outputs : 16 per KC-831
• Inputs : none
• Groups : 16 per KC-831
Remote Acces Capabilities
- Computer
- Modem
- Internet
OVERRIDE OPTIONS (SWITCHES)
ADDED CONTROL SEQUENCES
AC2
N24
L24
SER
CT
N24
AC2
L24
AC2
CT
AC2
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
SER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TX +5V INI
Keyed Switches
KC-811 Digital
Time Clock
RESET
KC-831 Output
Controller
RX
RX
0
1
2
4
3
5
7
6
8
10
11
9
12
14
13
15
SYSTEM
COMPONENTS
TX +5V INI
FTT-10A
ECHELON
Remote Acces Capabilities
- Computer
- Modem
- Internet
NEURON
CHIP
PART INDEX
N24
SER
AC2
CT
AC2
N24
L24
AC2
L24
AC2
CT
• Outputs : 16 per KC-831
• Inputs : 8 Low-voltage /
16 Dry-contacts per KC-821
• Groups : 16 per KC-831
SERVICE
CONTROL CAPACITY
Switches
RESET
• Manual ON/OFF
• Time ON Extension
• Cleaning/Security
• Flick Warning
SERVICE
SYSTEM
CONFIGURATION
*Output controllers are available for 3-wire, breaker-relays or solid states relays.
KC-821 Input
Controller
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
ADDED CONTROL SEQUENCES
• Occupancy Control
Switches
RESET
SERVICE
Occupancy Sensor
N24
SER
AC2
L24
CT
N24
AC2
L24
AC2
AC2
CT
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
SER
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
KC-831 Output
Controller
RX
Keyed Switches
TX +5V INI
KC-811 Digital
Time Clock
COMMON CONTROL
SEQUENCES
OVERRIDE OPTIONS (OCCUPANCY SENSOR)
RESET
SERVICE
L24
N24
SER
AC2
CT
AC2
N24
L24
AC2
AC2
CT
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
0
1
2
4
3
5
7
6
8
13
10
11
9
12
15
14
Remote Acces Capabilities
- Computer
- Modem
- Internet
TYPICAL
APPLICATIONS
KC-821 Input
Controller
NATURAL LIGHTING (PHOTOCELLS)
ADDED CONTROL SEQUENCES
• Daylight Harvesting
Switches
RESET
SERVICE
MOTION DETECTOR
AC2
N24
L24
CT
SER
AC2
N24
AC2
L24
AC2
CT
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
KC-831 Output
Controller
RX
Keyed Switches
TX +5V INI
PHOTOCELL
KC-811 Digital
Time Clock
RESET
SERVICE
AC2
CT
AC2
L24
N24
SER
AC2
N24
L24
AC2
CT
RX
TX +5V
FTT-10A
ECHELON
NEURON
CHIP
INI
3
0
1
2
5
7
6
4
9
8
10
12
14
13
15
11
Remote Acces Capabilities
- Computer
- Modem
- Internet
KC-821 Input
Controller
SYSTEM
COMPONENTS
LOCAL DIMMING CONTROL
ADDED CONTROL SEQUENCES
Constant light
controller
RESET
SERVICE
AC2
N24
L24
SER
CT
N24
AC2
L24
AC2
AC2
CT
• Dimming
(with scene control,
fade time and delay)
SYSTEM
CONFIGURATION
SER
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
CONTROL
SER
TX +5V INI
0
1
2
3
4
5
6
7
KC-811 Digital
KC-84x Output Time Clock
Controller(s)
RESET
SERVICE
L24
N24
SER
AC2
CT
AC2
N24
L24
AC2
AC2
CT
RX
TX +5V
FTT-10A
ECHELON
NEURON
CHIP
INI
0
1
2
4
3
5
7
6
8
13
10
11
9
12
15
14
Remote Acces Capabilities
- Computer
- Modem
- Internet
KC-821 Input
Controller
PART INDEX
8
9
10
11
12
13
14
15
• Constant Output (%)
• Constant Ambient Light (lux)
RX
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
CENTRALIZED DIMMING CONTROL
Dmx 512
Input & Output
• Light Harvesting
RESET
Constant light
controller
(echelon based)
SER
AC2
N24
L24
CT
N24
AC2
AC2
L24
AC2
CT
• Dimming
SERVICE
RX
TX +5V INI
FTT-10A
ECHELON
NEURON
CHIP
N24
L24
AC2
CT
AC2
RESET
NEURON
CHIP
ECHELON
FTT-10A
SERVICE
SER
RX
TX +5V INI
0
1
2
3
4
5
6
7
DIMMING CONTROL
KC-811 Digital
CAPABILITIES
Time Clock
KC-841 Output
Controller
• Analog : Dimming Ballast
• Digital : Dimming Rack (dmx 512)
• groups : up to 6 zones
• per KC 84x ctrl
8
9
10
11
12
13
14
15
COMMON CONTROL
SEQUENCES
ADDED CONTROL SEQUENCES
TYPICAL
APPLICATIONS
Remote Acces Capabilities
- Computer
- Modem
- Internet
KC-84x Dimming
Controller
* Dimming controllers are available for digital (dmx-512) control
NETWORK SYSTEM
SYSTEM
CONFIGURATION
Panel 2
INTEGRATED NETWORK SYSTEM
HVAC
Security
PART INDEX
Fire Alarm
...
Gateway
(Optional)
TO BUILDING AUTOMATION
SYSTEMS
SYSTEM
COMPONENTS
Remote Acces Capabilities
- Computer
- Modem
- Internet
Panel 3
Panel x
Dali
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
KAMELEON SOFTWARE - K8 SOFT
Echelon - Base
COMPLETE CONTROL AT YOUR FINGERTIPS
• Kameleon Software’ operating system runs under Windows environments
• It can easily run simultaneously on multiple platforms in a client/server fashion
• Its graphic interface is simple and intuitive, making it easy to configure, program and operate
COMMON CONTROL
SEQUENCES
DESCRIPTION
SYSTEM
CONFIGURATION
SYSTEM
COMPONENTS
SYSTEM OPERATION
• General system architecture monitoring
• Override capability by a single mouse-click
• Rescheduling capability
• Individual lighting circuit, group
or zone real-time status view
PART INDEX
SYSTEM CONFIGURATION
• Each user level is protected by password
• Easy addition, replacement
and troubleshooting of boards
• Network management:
- Multiple channels allow for a network extension
- Usage of different communication means
(twisted pair, power line, TCP/IP)
• LNS (LonWorks Network Services) compatibility
- Plug-in based configuration tools
- Integration of third-party LonWorks devices
• Group and zone configuration capability
- Schedules definition for each group and zone
- Switch(es)-relay(s) link configuration
TYPICAL
APPLICATIONS
SPECIFICATIONS
SYSTEM DESIGN GUIDE
SYSTEM CONFIGURATION
KAMELEON SOFTWARE
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
SPECIFICATIONS
SOFTWARE SCHEDULER
• Ability to Program delayed operating schedules.
(I.e.) a special schedule for the Summer Period
can be programmed in advance.
• Predefined lists of holidays (Canada & USA)
• Astronomical programming capability
• Flexibility in schedule programming;
day of the week, week within
a month, first Monday of September etc...
DATA LOGGER
• Record of chronological sequence of events
• Compilation of operating hours
• Pre-defined report generator
The gathered information could be used
to evaluate life expectancy of bulbs or generate
electricity bills for lighting use outside of
regular business hours
ADVANCED FUNCTIONS
Kameleon software also offers
these important programming options:
• Dimming (scene control, fade time and delay options)
• Schedule with flick warning
• Schedule extension delay
• Start-up or shut-down delay
• Enabling events
• Exclusion of devices (switch, sensor, ...)
• Maintenance/cleaning function
• Etc...
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
KC-83x OUTPUT CONTROLLER
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Part numbers: KC-831 (two-wire Relay controller)
• Part numbers: KC-832 (three-wire relay controller),
• Part numbers: KC-833 (breaker-relay controller)
• Part numbers: KC-834 (solid state relay controller)
• Simple wiring. Uses a twisted pair for the network
• Easy programmation and commissionning
• Uses LonWorks network communication
SPECIFICATIONS
SYSTEM
CONFIGURATION
3 wires
Breaker relay
2 wires
Solide State relay
SYSTEM
COMPONENTS
3 Wires
relay – RR7
PART INDEX
2 Wires
Relay -WR6161
TYPICAL
APPLICATIONS
• Microprocessor EchelonÆ 3150®
• Output 16 two-wire or Solid State relays,
8 three-wire relays or Breaker Relays
• Transceiver FTT-10A
• Communication network LonWorks®, Echelon®
Pair of twisted # 22 wire
• Distance Up to 2,700 meters (1,000 ft) in bus
mode and up to 500 meters (175 ft) in free topology,
without repeater
• Power supply 24 V AC and 18 V AC, with mid-point tap
• Terminal blocks Plug-in / Screws
• Dimensions 110 mm x 180 mm (4.3 in x 7.0 in)
• Iec standards compliance IEC 60255-22-4:
Fast transcient disturbance tests
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
KC-811 TIME CLOCK CONTROLLER
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Astronomical clock
• Built-in scheduler
• Uses for scheduler or serial port
• Simple wiring
• Easy programmation and commissionning
• Uses LonWorks network communication
• Flash Memory
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
SPECIFICATIONS
• Microprocessor: EchelonÆ 3150Æ
• Frequency: 10 MHz
• Volatile memory: 32 KB
• Non-volatile memory: 64 KB
• Communication ports: RS-232, RS-422 or RS-485 (optional)
• Speed: Tx 115 kbps; Rx 4.8 kbps
• Addressable switches: One wire, (optional)
• Can address up to 16 switches,With or without LED
• Transmitter-receiver: FTT-10A
• Communication network: LonWorksÆ, EchelonÆ
• Distance: Up to 2,700 meters in bus mode, without repeater
• Analog input: Two 0-10 V input or resistive (photoelectric cell)
• Power supply: 8 V AC, with mid-point tap
• Terminal blocks: Plug-in
• Dimensions: 4.3 in x 4.3 in
KC-821 INPUT CONTROLLER
DESCRIPTION
PART INDEX
SYSTEM
COMPONENTS
• Interfaces 8 low voltage switches or 16 dry contacts
• Simple wiring. Uses a twisted pair for the network
• Easy programmation and commissionning
• Uses LonWorks network communication
SPECIFICATIONS
• Microprocessor EchelonÆ 3150Æ
• Output 8 low voltage switches, with or
without LED or 16 dry contacts
• Transceiver FTT-10A
• Communication network LonWorksÆ, EchelonÆ
Pair of twisted # 22 wire
• Distance Up to 2,700 meters (1,000 ft)in bus
• mode and up to 500 meters (175 ft)
in free topology, without repeater
• Power supply 24 V AC and 18 V AC,
with mid-point tap
• Terminal blocks: Plug-in
• Dimensions 4.3 in x 7.0 in
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
KC-841-842-843 DIMMING CONTROLLER
• Power supply 24vac, 125 ma
• Outputs 8 (analog) - 100 ballasts/outputs 0-10vdc
• Microprocessor echelon 3150
• Transmitter - receiver echelon ftt-10a
• Iec standards compliance iec 60255-22-4:
fast transient disturbance tests,
Iec 61000-4-2: electrostatic discharge immunity test
• Terminal blocks pug-in & screws
• Temperature 32 f to 122 f (0c to 50c)
• Dimensions 7 in x 9 in (178 mm x 229mm)
KC-844 DIMMING CONTROLLER
KC-842 Input : Echelon
(9) Ouput : 0-10 Vcc
KC-843 Input : Echelon
Ouput : Echelon
TYPICAL
APPLICATIONS
SPECIFICATIONS
KC-841 Input : Contact
(16) Ouput : On/Off
SYSTEM
CONFIGURATION
• Control capacity: 6 channels per controller,
15 scenes per channel
• Complete remote settings of the echelon based sensor
• Open loop pattern for pre-set controls
• Close loop pattern for daylighting control
• Fade and delay time programming
• On board on - off - auto manual override
• On board 0-100% manual setting
• Occupancy sensor interface for dual level
• Up - down override setting capability
through the kameleon software or from
wall switches
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Prgogrammable 16 channels relay controller
• Provide DMX control of mechanical or plug-in relays
• Selectable threshold of 25% or 75%
• DMX Softpatch: assign any DMX512 ad-dress
to any relay
• Two programmable master switch inputs
• Input/Output diagnostic functions
• Status LED's
SYSTEM
COMPONENTS
DESCRIPTION
• Power Supply: 16-24VAC or DC, 150mA (not included)
• Relay Coil Supply: 24VAC (not included)
• Inputs: DMX512 or master switch momentary On & Off
• Outputs: Momentary or maintained
• Relay Coil Drive: 250mA Maximum. Use a pilot relay for higher
• current requirements
• Terminal blocks: Two piece compression screw terminals
• Dimensions: 5.5 in X 7.5 in (139.7 mm x 190.5 mm)
PART INDEX
SPECIFICATIONS
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
K-SERIES RELAY PANEL
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Practical design offering ease of installation and efficient running
• Standard sizes for 8, 16, 32 and 64 relays
• Removable hinged door with key lock
• Panel accepts heavy duty and/or plug-in relays as well as electronic cards
• Panel comes with transformer, supply terminal block and supply card
• Box knockouts are located on both sides of the panel to facilitate
panel junction and wire entry with conduit nipples
• Easy handling mounting plate equipped with rubber
protected hedge handle
• Relay panel comes with covered wiring duct
• Movable protection plate between high and low voltage sections
• Control Transformer Class 2 (120/277/347 VAC)
SPECIFICATIONS
• Enclosures and steel doors are coated
with ANSI/ASA 61 gray baked enamel
• 8 and 16 relay panel made of cold-rolled 16 gauge steel
• 32, 48 and 64 relay panels made of cold-rolled 14 gauge steel
• Yellow zinc plated removable mounting plate
• Yellow zinc plated protection plates
part number system
SYSTEM
CONFIGURATION
AVAILABLE OPTIONS
SYSTEM
COMPONENTS
16 RELAY PANEL
PART INDEX
K
• Multi-voltage transformer (120/277/347 VAC)
• Multi-voltage separator
• Door for flush mount, invisible screws
• Custom panel design on request (color, drip hood, reversible door, ...)
x
Model
K4(4)
K8(8)
xx Capacity
8, 16, 32,
48, 64
x
Surface mount (s)
Flush mount (f)
16 RELAY PANEL
- Nx
nemacode
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
DIMENSIONS AND LAYOUT
8 relay panel
CET APPAREIL COMPORTE PLUSIEURS
CIRCUITS SOUS TENSION
MORE THAN ONE LIVE CIRCUIT
SEE DIAGRAM
KAMELEON
Model #
KX series
Kx-8
Kx-16
Kx-32
Kx-64
Height
inch mm
15 381
23.3 592
33.5 850
49.2 1250
Wide
Depth Weight
inch mm inch mm lbs kg
15 381 4.1 101 26
12
15 381 4.1 101 42
19
20 508 4.1 101 83
38
20 508 4.1 101 140
64
COMMON CONTROL
SEQUENCES
dimensions
CET APPAREIL COMPORTE PLUSIEURS
CIRCUITS SOUS TENSION
MORE THAN ONE LIVE CIRCUIT
SEE DIAGRAM
KAMELEON
64 relay panel
TYPICAL
APPLICATIONS
16 relay panel
CET APPAREIL COMPORTE PLUSIEURS
CIRCUITS SOUS TENSION
MORE THAN ONE LIVE CIRCUIT
SEE DIAGRAM
SYSTEM
CONFIGURATION
KAMELEON
32 relay panel
CET APPAREIL COMPORTE PLUSIEURS
CIRCUITS SOUS TENSION
MORE THAN ONE LIVE CIRCUIT
SEE DIAGRAM
PART INDEX
SYSTEM
COMPONENTS
KAMELEON
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
BACK PLATE AND LAYOUT
COMMON CONTROL
SEQUENCES
8 relay back panel
dimensions
Back Plate
Version
8 relay
16 relay
32 relay
64 relay
Fixation Stud/Bolt - Dimension
Height
Wide
inch
mm
inch
mm
12.75
323
13.75
348
21
534
13.75
348
30.75
780
18.75
474
46.5
1180
18.75
474
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
16 relay back panel
64 relay back panel
32 relay back panel
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
2-WIRE HID RELAY
COMMON CONTROL
SEQUENCES
DESCRIPTION
• Two-wire relay used for monitoring and control
• No derating for inductive lighting loads
• Manual operation lever with ON/OFF indicator built-in
for easy maintenance
• Screw terminals on load and control sides
• Powerful contact opening mechanism withstands 2,000 amp
inrush current and 1,500 amp short circuit current.
TYPICAL
APPLICATIONS
part number # of poles ul rating
csa rating isolated auxiliary contact
1
n/a
20a / 300vac 20a / 347vac
wr-6161-81
20a / 300vac 20a / 347vac
1
yes 1a 125v ac spst
wr-6161-381
wr-6172-81
n/a
20a / 480vac 20a / 347vac
2
CHARACTERISTICS
SYSTEM
CONFIGURATION
• Electrical life 30,000 operations or more at full load, at 20cpm
• Mechanical life 60,000 operations or more at 20cpm
• Inrush capability 2,000A
• Short cirsuit current 14ka
• Max. operating speed 20 cpm at nominal load
• Operate time Approx. 20 msec
• Release time Approx. 20 msec
• Initial insulation resistance more than 100M at 500V DC
• Dieletric between open contacts 1,694V for one minute
• strengh between contacts and coil 2,500V for one minute
• Ambient temperature -30 to +50C (-22 to +122F)
• Temperature rise (at normal voltage) Max. 65C (149F)
MOUNTING METHODS
• Use DIN rail, DIN 46277, 35mm width for DIN type relays.
• Use accessory WR9910 mounting bracket. Can be broken-off for needed numbers.
PRINCIPALS OF OPERATION
ON CONDITION
AC
POWER SUPPLY
RED
RED
BLUE
BLUE
N
CHANGEOVER SWITCH
AC
POWER SUPPLY
RED
BLUE
RED
BLUE
CONTROL DEVICE
CONTROL DEVICE
Internal changeover switch is mechanically linked to main
contact. No current flows due to the diode direction.
The main contact closes and the mechanically-linked changeover
switch operates to shut off the current flow.
WHEN CONTROL DEVICE IS TURN ON
WHEN CONTROL DEVICE IS TURN OFF
N
HID RELAY
MAIN
CONTACT
CHANGEOVER SWITCH
AC
POWER SUPPLY
RED
RED
BLUE
BLUE
CONTROL DEVICE
The coil current flows to operate the relay.
TO LOAD
TO LOAD
HID RELAY
MAIN
CONTACT
N
SYSTEM
COMPONENTS
N
HID RELAY
MAIN
CONTACT
CHANGEOVER SWITCH
TO LOAD
TO LOAD
HID RELAY
MAIN
CONTACT
CHANGEOVER SWITCH
AC
POWER SUPPLY
RED
BLUE
RED
BLUE
CONTROL DEVICE
The coil current flows in the opposite direction to operate
the relay. The main contact will open and the changeover
switch will operate.
PART INDEX
OFF CONDITION
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
OFF
WR-6161
COMMON CONTROL
SEQUENCES
1 pole
24.5
.965
relay inside view
main
contact
terminal
manual lever
with ON/OFF
indicator
internal
changeover
switch
input
terminal
96
3.78
13.5
.531
13.5
.531
TYPICAL
APPLICATIONS
staggered
connection for
easy wiring
auxiliary
contact
terminal
(optional)
compulsory
opening lever
polarized
solenoid
OFF
WR-6161-81/381
DIN rail mounting
strap (optional)
13.5
.531
13.5
.531
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
11.433
PART INDEX
49.5
1.949
2 poles
CIRCUIT-BREAKER RELAY
DESCRIPTION
• The Cutler Hammer Solenoid-Operated circuit breakers are
designed for use in panel board and are ideally suited for
retrofit lighting control applications. In replacement of
conventionnal branch circuit protection, they include a
unique solenoid-operated mechanism that provides for
efficient breaker pulse-on and pulse-off operation. These
breakers can be mixed with a group of standard breakers
in the same breaker distribution panel.
CHARACTERISTICS
• Operating voltage: 24 V AC for an cycle
• Three Position Handle: OFF, TRIP (center), ON
• Electrical performance:
Fluorescent lamp 20 A, 347 V AC
H.I.D. Rated 20 A, 347 V AC
I.C. (Sym, 50/60 Hz) 65 kA at 120, 240 Volts
14 kA at 277/480 Volts
Pole(s): 1 or 2 poles
Auxiliary switch for Control Circuit Feedback (Status)
• Test condition: Switching cycle, 6 times/minute
• Bi-Metal Assembly for Thermal Overlaod Protection
96
3.78
WR-6172-81
13.5
.531
13.5
.531
11.433
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
DESCRIPTION
Specifications
• Wall mount rocker or key type
momentary contact relay switch.
• Mount to standard wall boxes
• To operate rocker type switch,
activate button up for ON,
and down for OFF
• To operate key type switch,
turn key to the right for ON,
to the left for OFF
• 3Amp. 24V. Reversible polarity pulse
• Maximum of 4 relays operable with one switch
• No limit of switches connected to the relay
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
MC-1138-0 (No LED)
MC-1138-1 (1 LED)
MC-1138-2 (2 LED)
MC-1138-C (Key Switch)
COMMON CONTROL
SEQUENCES
MC-1138 HEAVY DUTY SWITCH
MC-1138-C (key switch)
PART INDEX
MC-1138-2 (2 led)
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
DESCRIPTION
Specifications
• Wall mount rocker type relay switch
• To operate, press rocker to one side
for ON and to the other side for OFF
• 3 WR-8001 can fit into one gang size,
WN-3700 Mounting Strap required
• 3 Amp. 24 V. Reversible polarity pulse
• Maximum of 8 relays operable
• No limit to number of switches
connected to a relay
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
WR-8001 ROCKER SWITCH
WR-5092 KEY SWITCH
DESCRIPTION
Specifications
• Wall mount key operated
Enable/Disable switch
• 3 WN 5092 can fit into one gang size,
WN 3700 Mounting Strap required
• Typical application is for security,
maintenance and cleaning tour
• Use switch to interrupt common (white)
to switch(es) to disable wall switch
• 3 Amp. 24 V.
• Single pole, double throw key switch
• CAN NOT BE DIRECTLY CONNECTED TO RELAYS
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
SWITCHES ACCESSORIES
depth
----0.43”
---
COMMON CONTROL
SEQUENCES
length
3.27”
1.9”
1.73”
---
WN-3700
• Switch lid made
of clear plastic
• Cover for 1 gang /
1, 2 or 3 device
opening
• Auto-adhesive
cover
• Steel, plated finish
• Mounts to standard
wall boxes
• 1,2 OR 3 devices
can be installed
into each strap
WN-3020
WN-7700
• Use filler chip
to fill device
spaces
• Color of
filler chip
identical to cream
white of Gentec
• Vandal-proof
switch enclosure
• Lockable door
• All colors
available
• Flush or
surface mount
SYSTEM
COMPONENTS
WN-2700
TYPICAL
APPLICATIONS
width
1.27”
4.4”
0.91”
---
SYSTEM
CONFIGURATION
WN-2700
WN-3700
WN-3020
WN-7700
WN 7700 Series
WN 7722-*
WN 7733-*
WN 7744-*
WN 7755-*
WN 7766-*
2 Gang Enclosure
3 Gang Enclosure
4 Gang Enclosure
5 Gang Enclosure
6 Gang Enclosure
WN 7788-*
WN 772525-*
WN 772626-*
WN 772828-*
* - S Surface Mounted
8 Gang Enclosure
2x5 Gang Enclosure
2x6 Gang Enclosure
2x8 Gang Enclosure
- F Flush Mounted
PART INDEX
dimensions
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
COMMON CONTROL
SEQUENCES
WR-8051 AND WR-8503 PUSH BUTTON SWITCHES
DESCRIPTION
Specifications
• Wall mount LED indicating
push button relay switch
• To operate, press for ON,
press again for OFF
• Clear plastic cap on button
holds switch function label
• 1.5 Amp. 24 V. Reversible Polarity Pulse
• Maximum of 4 relays operable with one switch
• Limit of 6 LED switches connected to one relay
• WN 8503 has a built-in
Mounting Strap
• All 3 switches from
WR 8503 obtain
the input from a
common terminal
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
• 3 WR 8501 can fit into
one gang size, WN 3700
Mounting Strap required
PART INDEX
WR-8501
WR-8503
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
SWITCHES PLATES
COMMON CONTROL
SEQUENCES
DESCRIPTION
TYPICAL
APPLICATIONS
• MC 1158 Series: Brushed stainless steel
visible screw for MC 1138 Switch Series
MC 1158 Series
PART NUMBERS
DIMENSIONS
SYSTEM
CONFIGURATION
MC-1158-1
PROFIL
MC-1158-2
MC-1158-4
MC1158-2
MC1158-3
MC1158-1
MC-1158-5
SYSTEM
COMPONENTS
MC-1158-3
MC-1158-6
MC1158-5
MC1158-6
PART INDEX
MC1158-4
SYSTEM DESIGN GUIDE
SYSTEM COMPONENTS
SWITCHES PLATES
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
DESCRIPTION
• WN 7600 Series: Brushed stainless steel
visibles crew for WR Switch Series
• WN 6000 Series: Plastic cover plates –
Beige color, gloss finish – Snap-on cover plate
and a screw-on trim plate – Mounting screws
are hidden for WR Switch Series
• WN 7100x Series: Plastic cover plates –
Matte finish – Snap-on cover plate and a
screw-on trim plate – Invisible screws for
WR Switch Series – W: white – H: grey – Y: beige
PART NUMBERS
WN-XX15
1 gang
1 device
5 gang
15 device
WN-XX02
WN-XX18
1 gang
2 device
6 gang
18 device
WN-XX03
WN-XX72
1 gang
3 device
2 gang
2 device
WN-XX04
WN-XX74
2 gang
4 device
2 gang
3+1 device
WN-XX05
WN-XX79
2 gang
5 device
3 gang
1+1+1 device
WN-XX06
WN-XX91
2 gang
6 device
1 gang blank
WN-XX09
WN-XX92
WN-XX12
4 gang
12 device
Wn 6000 Series
Wn 7100X Series
DIMENSIONS
WN-XX01
3 gang
9 device
PART INDEX
Wn 7600 Series
PROFIL
WNXX03
WNXX02
WNXX01
WNXX09
WNXX12
2 gang blank
WN-XX93
3 gang blank
WNXX15
WNXX18
SYSTEM DESIGN GUIDE
MODEL #
Wr-6161-81
Wr-6161-381
DESCRIPTION
2-wire, 1-pole Hid Latching Relay 20a: 120/277/347 V
2-wire, 1-pole Hid Latching Relay W. Auxiliary Contact 20a: 120/277/347 V
2-wire, 2-pole Hid Latching Relay 20a: 120/277/347 V
2-wire, 2-pole Hid Latching Relay 20a: 120/277/347/480 V
2-wire Hid, 2 Poles
Wr-6166-81
Wr-6172-81
Wr-6366
Controllers
PART #
35459-01
35563-02
35459-01
36314-07
36317-02
36317-01
36317-03
36317-05
36317-01
35374-00
MODEL #
Kc-401
Kc-411
Kc451
Kc-811
Kc-821
Kc-831
Kc-832
Kc-833
Kc-834
Kc-841
Kc-842
Kc-843
Kc-844
Kc-845
Kc-601
DESCRIPTION
K4 Relay Controller, 16 Outputs, 4 Inputs
K4 Astronomical Time Clock/relay Controller, 8 Outputs, 2 Inputs + 2
Photocells Dedicated Inputs
K8 Astronomical Time Clock Controller, Lonworks Ftt-10
K8 Input Controller, 8 Lv Or 16 Contact Inputs, Lonworks Ftt-10
K8 Output Controller, 16 2-wire Relays, Lonworks Ftt-10
K8 Output Controller, 8 3-wire Relays, Lonworks Ftt-10
K8 Output Controller, 8 Breaker-relays, Lonworks Ftt-10
K8 Output Controller, 16 Solid State Relays, Lonworks Ftt-10
K8 Analog Dimming Controller 0 To 10 Vdc
K8 Analog Dimming Controller Lonworks Ftt-10
K8 Analog Dimming Controller
K8 Dmx-512 Dimming Controller (Input)
K8 Dmx-512 Dimming Controller (Output)
K6 Bacnet Node
PART #
19124
MODEL #
K8-soft
K6-config
DESCRIPTION
K8 Series Kameleon Lighting Control Software
K6 Series Kameleon Bacnet Configuration Node
PART #
25632
25630
25123
24677
26822
MODEL #
Ilon 10
Ilon 100
U10-usb
Lpr-10
Dt-55
DESCRIPTION
Ip Network Interface Lonworks
Ip Internet Server Lonworks
Router Lonworks
Router Lonworks
Telephone Interface
PART #
30449
30451
30884
20530
30338
MODEL #
MC-1138-0
MC-1138-2
MC-1138-C
WR-8001
WR-8501
WR-8503
WN-5092
DESCRIPTION
Leviton Type, Ivory
Leviton Type, 2-indicator Led
Leviton Type, Key Switch
Rocker Switch, No Indicators
2 Indicators, Push Button Switch
2 Indicators, Push Button Switch, 3 Devices/1 Gang
Key Switch
36314-09
37774-00
Software
Lonworks
Networking
Devices
Switches
24913
TYPICAL
APPLICATIONS
PART #
Relays
SYSTEM
CONFIGURATION
CONTACT
FACTORY
DESCRIPTION
Kx (K4, K6, K8) 8 Relay Panel Surface Mounted Nema 1
Kx (K4, K6, K8) 16 Relay Panel Surface Door Nema 1
Kx (K4, K6, K8) 32 Relay Panel Surface Mounted Nema 1
Kx (K4, K6, K8) 64 Relay Panel Surface Mounted Nema 1
Kx (K4, K6, K8) 8 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 16 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 32 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 64 Relay Panel Flush Mounted Nema X
Kx (K4, K6, K8) 8 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 16 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 32 Relay Panel Flush Mounted Nema 1
Kx (K4, K6, K8) 64 Relay Panel Flush Mounted Nema X
SYSTEM
COMPONENTS
ABOUT
NEMA … X
3R – 4 – 4X
AND 12
Standard
MODEL #
Kx – 8pa – S1
Kx – 16pa – S1
Kx – 32pa – S1
Kx – 64pa – S1
Kx – 8pa – F1
Kx – 16pa – F1
Kx – 32pa – F1
Kx – 64pa – F1
Kx – 8pa – F1
Kx – 16pa – F1
Kx – 32pa – F1
Kx – 64pa – F1
PART INDEX
Relay
Panels
PART #
35930
35931
35971
35973
36291
36292
36561
30157
COMMON CONTROL
SEQUENCES
PART INDEX
SYSTEM DESIGN GUIDE
Switches
Plates For
Mc-1138 Series
Switches
Plates For
Wr-8xxx Series
TYPICAL
APPLICATIONS
COMMON CONTROL
SEQUENCES
PART INDEX
PART INDEX
SYSTEM
COMPONENTS
SYSTEM
CONFIGURATION
Switch
Accessories
Detectors Sensors
PART #
30354
30355
30356
30357
30987
MODEL #
Mc1158-1
Mc1158-2
Mc1158-3
Mc1158-4
Mc1158-6
DESCRIPTION
1 Gang/1 Device
2 Gangs/2 Devices
3 Gangs/3 Devices
4 Gangs/4 Devices
6 Gangs/6 Devices
25030
30347
25032
30348
25033
30349
25034
30995
25035
30996
24308
24309
24759
24760
Wn-6001
Wn-7601
Wn-6002
Wn-7602
Wn-6003
Wn-7603
Wn-6004
Wn-7672
Wn-6006
Wn-7606
Wn-7609
Wn-7612
Wn-7615
Wn-7618
1 Gang/1 Device (Plastic)
1 Gang/1 Device (Stainless Steel)
1 Gang/2 Devices (Plastic)
1 Gang/2 Devices (Stainless Steel)
1 Gang/3 Devices (Plastic)
1 Gang/3 Devices (Stainless Steel)
2 Gangs/4 Devices (Plastic)
2 Gangs/4 Devices (Stainless Steel)
2 Gangs/6 Devices (Plastic)
2 Gangs/6 Devices (Stainless Steel)
3 Gangs/9 Devices (Stainless Steel)
4 Gangs/12 Devices (Stainless Steel)
5 Gangs/15 Devices (Stainless Steel)
6 Gangs/18 Devices (Stainless Steel)
PART #
24310
24912
38163
30346
MODEL #
Wn-3020
Wn-2700
Wn-7700
Wn-3700
DESCRIPTION
Filler Chip
Protective Plastic Lid
Steel Switch Enclosure
Mounting Bracket 1, 2 Or 3 Devices
PART #
31091-01
26172
26820
26814
26170
26818
26817
26171
26809
26815
MODEL #
Et-15
Cm-pc
Wsd-pdt-w
Wsd-w
Cm-9-r
Cm-10-r
Cm-pdt-r
Cm-pdt-10-r
Wv-16-r
Wv-pdt-r
DESCRIPTION
Outdoor Photocell C/w Relay
Indoor Photocell
Wall Switch Detector – Pdt – Line Voltage
Wall Switch Decora – Pir – Line Voltage 120 / 277 V
Ceiling Mount Std Range 360° Pir Low Voltage C/w Relay
Ceiling Mount Ext Range 360° Pir Low Voltage C/w Relay
Ceiling Mount Std Range 360° Pir Low Voltage C/w Relay
Ceiling Mount Ext Range 360° Pir Low Voltage C/w Relay
Wide View, Pir, Low Voltage C/w Output Relay
Wide View, Pdt, Low Voltage C/w Output Relay
NOTES
NOTES