System Design Guide SYSTEM DESIGN GUIDE This System Design Guide provides general guidance regarding lighting control sequences and applications in commercial and institutional buildings. Furthermore, engineers, electrical contractors and property managers will find all the necessary information on how to design a Kameleon system according to their control needs and specifications. For any additional information on the Kameleon systems, we invite you to visit our web site at www.kameleonlighting.com or to contact your local representative. TYPICAL APPLICATIONS Gentec's Kameleon K Series offers a wide range of solutions to suit any lighting control requirement. From the field programmable K4 Series for small to medium size applications to the Echelon based console-operated K8 Series with dimming capabilities and BACnet base networked K6 series, the Kameleon K Series will adapt to all possible configuration needed by the end-user. COMMON CONTROL SEQUENCES COMMON CONTROL SEQUENCES CONTENTS K8 Series Configurations Parts Index SYSTEM COMPONENTS Kameleon K Series Components K4 Series Configurations PART INDEX Typical Applications Kameleon K Series Overview SYSTEM CONFIGURATION Common control sequences SYSTEM DESIGN GUIDE COMMON CONTROL SEQUENCES COMMON CONTROL SEQUENCES THE FOLLOWING SECTION – CONTROL SEQUENCES, DESCRIBES THE MOST COMMONLY USED LIGHTING CONTROL SEQUENCES IN A COMMERCIAL BUILDING. TIMED SCHEDULES The sweep ON/OFF Operation is used to turn preset lights ON and OFF automatically according to pre-programmed schedules*. To permit off-hours activities, such as overtime and janitorial work, scheduling can be overridden through different actions such as manual ON/OFF and motion detection. TYPICAL APPLICATIONS *The schedule programming is performed directly on the KC-411 8 Channel Time Clock for the K4 Series and through the Kameleon Software for the K8 Series. OVERRIDE SWITCHING The manual ON/OFF Operation gives occupants total control of the lighting in each of the zones equipped with a switch-based device. Manual ON/OFF is the most common override operation. Switches and/or ON action and/or OFF action can be disabled separately according to time schedules*. SYSTEM CONFIGURATION *Available only with the K8 Series. HOLD ON TIME / TIME ON EXTENSION The Time ON Extension Mode (TOE) causes the Time Clock* to start a timer when the relay is switched ON. Upon time expiry (generally a building-wide standard period**), the relay is switched OFF. The TOE mode can be enabled and disabled according to a time schedule. Thus, switches work normally during business hours and in TOE mode during off-work hours. SYSTEM COMPONENTS * KC-411 for the K4 Series or KC-811 for the K8. ** The period is set at two hours with the K4 Series and adjustable with the K8 Series. FLICK WARN The Flick Warn Function is used to remind occupants that lights will be switched OFF after a pre-programmed countdown*. After a pre-set hold time period, the Occupancy sensor will switch lighting OFF again if no presence is being detected*. Occupancy sensors and/or On action and/or Off action can be enabled and disabled separately according to time schedules**. PART INDEX * Variable hold-time periods can be programmed on a schedule base for each occupancy sensor with the K8 Series. ** Available only with the K8 Series SYSTEM DESIGN GUIDE COMMON CONTROL SEQUENCES The Motion Sensing Operation will switch lighting ON upon the detection of a person entering the zone covered by the sensor beam. After a pre-set period, the motion sensor will switch lighting OFF again if no presence is being detected. Motion sensors can be enabled and disabled according to time schedules. Also, the occupancy sensor can be used to turn ON lights in the morning. The OFF sequence triggered by the sensor will then be only permitted after the end of normal business hours. COMMON CONTROL SEQUENCES OCCUPANCY SENSING Enabled during off-work hours, the Cleaning/Security Function will allow authorized employees (janitor, guard, landlord, etc.) to switch the lights ON/OFF in preset areas without disturbing the occupants. The Cleaning/Security Function is generally performed through the use of key switches. When the key switch is activated, the system memorizes the current status of all the relays in the area. An ON activation of the key switch will turn ON all the OFF relays in the area. The OFF activation of the key switch will only turn OFF the relays that were already OFF before the ON activation. *Available only with the K8 Series. TYPICAL APPLICATIONS CLEANING/SECURITY* DAYLIGHTING AND DAYLIGHT HARVESTING a. Daylighting control is used to generate energy savings. Through the use of daylight sensor and dimmable ballasts, the light level in peripheral areas is automatically adjusted according to the amount of natural light available. PHOTOMETRIC CONTROL The Photometric Function will turn the exterior or interior lights ON and OFF according to the ambient light level. Time Control can be used to override the photocell effect and to switch lights OFF. ASTRONOMICAL CONTROL Through the use of the time zone, the latitude, the longitude and the date, the astronomical clock can calculate the sunset and sunrise times. Light can be programmed to switch at these calculated times. An offset can be programmed to cause the switching to occur sooner or later than the actual sunset and sunrise. SYSTEM COMPONENTS *Available only with the K8 Series PART INDEX Dimming control is used to adjust light level according to specific needs. In most cases, dimming sequences will be programmed and will follow pre-set scenes that will include targeted light level, fade time and hold time. The activation of these scenes is done through the use of schedules, switches or occupancy sensors. Dimming Controllers* are used to control the analog (0-10v) or the digital (DMX-512, Dali) dimmable ballast tied to the lights. SYSTEM CONFIGURATION DIMMING SYSTEM DESIGN GUIDE TYPICAL APPLICATIONS LD DE SC ER OV TIM ED TYPICAL APPLICATIONS COMPONENT REQUIREMENTS RI HE DU LE S SW ITC ON OC HI TIM CU NG PA E CL NC EA YS NI EN NG DA /SE SIN YL IG C UR G HT FL ITY I IC K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L OFFICE BUILDINGS HO COMMON CONTROL SEQUENCES THE FOLLOWING SECTION – TYPICAL APPLICATIONS, PRESENTS THE MOST COMMONLY USED CONTROL SEQUENCES INSIDE COMMERCIAL BUILDINGS. FOR EACH APPLICATION, THE REQUIRED LIGHTING CONTROL COMPONENTS ARE LISTED. • K6 or K8 Series Panels • Low Voltage Switches with Pilot LEDs • Key Switches • Motion Detectors • Constant Light Controllers • Exterior Photocell • Kameleon Software (K8) • Link to the Building Management System** • Dimming Controllers* HE DU RI LE DE HO S LD SW ITC ON OC H T CU IN PA IME G CL NC EA Y NI S E NG DA N /SE SIN YL IG G CU HT FL RI I IC TY K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L SCHOOLS ER TIM ED OV SYSTEM COMPONENTS SC SYSTEM CONFIGURATION *If centralized dimming control is required ** Optional COMPONENT REQUIREMENTS • K4, K6 or K8 Series Panels • Toggle Switches • Key Switches • Motion Detectors • Constant Light Controllers • Exterior Photocell • Link to Building Management System* PART INDEX *Optional (available only with K8 Series) SYSTEM DESIGN GUIDE COMMONAPPLICATIONS TYPICAL CONTROL SEQUENCES • K4, K6 or K8 Series Panels • Low Voltage Switches with Pilot LEDs • Motion Detectors • Constant Light Controllers • Exterior Photocell • Link to Building Management System* *Optional (available only with K8 Series) IT ON TIM CHIN PA G E NC EA YS NI E N DA G/S NS YL EC ING IG UR HT FL ITY IN IC G KW AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L • K4 Series Panels or K8 Series Panels • Low Voltage Switches with Pilot LEDs • Occupancy Sensors • Exterior Photocell • Dimming Controllers* *If centralized dimming control is required (available only with K8 Series) COMMON CONTROL SEQUENCES COMPONENTS REQUIREMENTS • K4 Series Panels • Low Voltage Switches with Pilot LEDs • Constant Light Controllers • Exterior Photocell PART INDEX ER OV TIM ED SC H ED RI UL DE HO ES LD S ON WITC OC HI T CU IM NG PA E CL NC EA Y NI NG SEN DA /SE SIN YL IG G CU HT FL RI IN IC TY G KW AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L CAR DEALERS SYSTEM COMPONENTS CL OC CU COMPONENTS REQUIREMENTS SYSTEM CONFIGURATION SW LD DE HO RI ER OV TIM ED SC HE DU LE S RESTAURANTS TYPICAL APPLICATIONS COMPONENTS REQUIREMENTS OV TIM ED SC HE ER DU RI LE DE HO S LD SW ON I TC OC HI TIM CU NG PA E CL NC EA YS NI EN NG DA /SE SIN YL IG C UR G HT FL ITY I IC K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L RETAIL STORES SYSTEM DESIGN GUIDE TYPICAL APPLICATIONS COMPONENT REQUIREMENTS • K4, K6 or K8 Series* Panels • Low Voltage Switches with Pilot LEDs • Motion Detectors • Exterior Photocell • Dimming Controllers* *if centralized dimming control is required COLLEGES HE ER DU RI LE DE HO S LD SW ON ITC OC H T CU IM IN PA G E CL NC EA Y NI S E NG DA N /SE SIN YL IG G CU HT FL RI I IC TY K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES TIM ED SC OV HE ER DU RI LE DE HO S LD SW ON I TC OC H T CU IM IN PA G E CL NC EA Y NI S EN NG DA /SE SIN YL IG G CU HT FL RI I IC TY K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L FACILITIES** ED TIM OV • K6 or K8 Series Panels • Low Voltage Switches with Pilot LEDs • Key Switches • Motion Detectors • Constant Light Controllers • Exterior Photocell • Kameleon Software (K8) • Link to the Building Management System • Dimming Controllers* *if centralized dimming control is required HE ER DU RI LE DE HO S LD SW ON ITC OC T H CU IM IN E PA G CL NC EA Y NI S EN NG DA /SE SIN YL IG G CU HT FL RI I IC TY K W NG AR DI MM N I PH NG OT OM AS ET TR RI C ON CO OM NT IC RO AL L CO NT RO L PARKING LOTS ED TIM PART INDEX OV SC SYSTEM COMPONENTS SYSTEM CONFIGURATION SC COMPONENT REQUIREMENTS COMPONENT REQUIREMENTS • K4 or K8 Series Panels • Exterior Photocell SYSTEM DESIGN GUIDE COMMONCONFIGURATION SYSTEM CONTROL SEQUENCES MD A COMPLETE LINE K8 SERIES SYSTEM VERSATILITY AND CONNECTIVITY COMMON CONTROL SEQUENCES K ameleon Lighting Control Systems offer highly customizable configurations that are designed to fully adapt to the occupants, as well as providing cost-savings opportunities to the owners. In its efforts to provide a solution for all types of needs, Gentec R&D Team has been developing three complementary systems: the K4, K6 and the K8-Series. K4 and K6 SERIES SYSTEM FIELD PROGRAMMABLE TYPICAL APPLICATIONS KAMELEON SOFTWARE KC-84x DIMMING CONTROLLER KC-401 Relay Controller KC-811 TIME CLOCK CONTROLLER KC-821 INPUT CONTROLLER BACnet Node SYSTEM'S FEATURES 8,16, 32 & 64 8,16, 32 & 64 8,16, 32 & 64 8,16, 32 & 64 * * - * ** Limited - - - +BAS - *** - * Optional ** Only if not equipped with the KC-811 Time Clock Controller *** 2-hour Fixed Time BAS: Building Automation System +BAS SYSTEM COMPONENTS - +BAS +BAS +BAS +BAS - - PART INDEX Relay Panels Capacity Two-Wire, 20A, H.I.D., 1 Pole, Latching Relay Two-Wire, 20A Plug-In Relays, 1 Pole, Latching Relay Two-Wire, 20A, H.I.D., Breaker-Relay, Latching Relay On-Site Programmable Time Clock (8 Channels) On-Site Group Configuration Network Capability Interoperability – LonMark / LonWork Interoperability -- BACnet Software Interface Telephone/Modem Interface and Internet Connection Switches/Sensors/Photocells Connection Dataline devices (Detector-Switch…) Warning Flick Time-On Extension Delay On/Off Advanced Scheduling Programming Logger Dimming Control Scene Controller DMX-512 Compatible Load Shedding Capabilities Daylight Harvesting SYSTEM CONFIGURATION KC-83X OUTPUT CONTROLLER Conectivity SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION ~ 8 RELAY SYSTEM AVAILABLE CONTROL SEQUENCES • Sweep ON/OFF • Sweep OFF • Manual ON/OFF • Hold On Time / Time On Extension • Flick Warning • Occupancy Sensing To Low-Voltage / Dry-contacts Accessories KC-411 Time Clock/ Relay Controller CONTROL CAPACITY • Outputs: Up to 8 • Inputs: 2 + 2 Photocells • Grounds: Groups: Up to 2 + 2 Photocells ~ TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES THE FOLLOWING SECTION – K4 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE K4 SERIES IN TERMS OF CONTROL CAPACITY. Photocells SYSTEM CONFIGURATION ~ 16 RELAY SYSTEM AVAILABLE CONTROL SEQUENCES • Same as the 8 Relay System To Low-Voltage / Dry-contacts Accessories CONTROL CAPACITY • Outputs: UP TO 16 • Inputs: 6 + 2 PHOTOCELLS • Grounds: UP TO 6 + 2 PHOTOCELLS KC-401 Relay Controller ~ KC-411 Time Clock/ Relay Controller 32 RELAY SYSTEM ~ SYSTEM COMPONENTS Photocells AVAILABLE CONTROL SEQUENCES • Same as the 8 Relay System CONTROL CAPACITY • Outputs: UP TO 32 • Inputs: 10 + 2 PHOTOCELLS • Groups: UP TO 10 + 2 KC-411 Time Clock/ Relay Controller KC-401 Relay Controller ~ PART INDEX PHOTOCELLS To Low-Voltage / Dry-contacts Accessories Photocells link KC-401 Relay Controller SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION FIELD PROGRAMMABLE SYSTEM SPECIFICATIONS • Power supply: 24VAC, 125 MA • IEC Standard compliance: Fast Transient Disturbance Tests & Electrostatic Discharge Immunity Test • Dimensions: 4.2 in x 7.0 in (107 mm x 180mm) TYPICAL APPLICATIONS • Field programmable time clock controller • 8 output (channels or relays) • Up to 2 groups (zones) configuration • A kc-411 can be networked with a kc-401 to Control up to 24 relays and 6 groups • Multi group relay assignment capability • Lcd display (4 lines - 20 characters) • Membrane keypad • Push button switch tone • Palm pilot programming/operation capabilities (irda) • Multiple input combination (2 devices) • Photocell (indoor and outdoor) dedicated input (2) • Daylight savings • Astronomical clock • 365-day, 7-day and 24 - hour programming • Up to 256 schedules (once, daily, weekly, monthly, yearly) • Event priority management • Automatic opposite action programming • Energy code certified features SYSTEM CONFIGURATION DESCRIPTION COMMON CONTROL SEQUENCES KC-411 TIME CLOCK/RELAY CONTROLLER KC-401 RELAY CONTROLLER • Field programming relay controller • 16 output (20a hid relay controller) • Up to 4 groups (zones) configuration • Two controllers can be networked and therefore control up to 32 relays and 8 groups • Multi group relay assignment capability • Real time system status feed back provided through different led patterns • Multiple input combination (4 devices) • Energy code certified features SYSTEM COMPONENTS DESCRIPTION • Power supply: 24VAC, 125 MA • IEC Standard compliance: Fast Transient Disturbance Tests & Electrostatic Discharge Immunity Test • Distance : Up to 1,000 ft in bus mode and up to 175 ft in free topology, without repeater • Dimensions: 4.2 in x 7.0 in (107 mm x 180mm) PART INDEX SPECIFICATIONS SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES THE FOLLOWING SECTION – K6 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE K6 SERIES IN TERMS OF CONTROL SEQUENCES AND CAPACITY. BASIC SYSTEM 8-16-32-64 Relay System To Low Voltage Control Devices AVAILABLE CONTROL SEQUENCES • Sweep ON/OFF • Sweep OFF • Manual ON/OFF • Time ON Extension • Flick Warning • Occupency Sensing • Daylight Harvesting CONTROL CAPACITY • Output 8 to 64 • Input 12 + 2 P • Groups UP to 12 + 2 • Photocells NETWORK SYSTEM Remote Acces Capabilities Central Building Automation System KC401 Relay Controller BACnet Node SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION K4 #1 K4 #2 K4 #3 COMMON CONTROL SEQUENCES BACnet CONFIGURATION K4 #4 Gentec KC601 BACnet Gateway Lighting Controller PC with BACnet Console TYPICAL APPLICATIONS BACnet Communication SYSTEM COMPONENTS Communication PART INDEX Configuration SYSTEM CONFIGURATION PC with KC601 Configuration Console SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION KC-601 BACnet NODE COMMON CONTROL SEQUENCES DESCRIPTION • Field programmable and configurable • 1 Inpout RS485 "BACnet communication • 1 Input RS232 port / PC • 5 LED indicating light - Communication and operation status • 1 Reset buttom • 4 Output RS485 Communication port / KC401 Controller TYPICAL APPLICATIONS SPECIFICATIONS • Power by 24 V ac 10VA • IEC Standards compliance: Fast Transient Disturbance • Test & Electrostatic Discharge Immunity Test • Dimension: 4.25 in x 7.0 in (107mm x 180 mmm) • Terminal DB9-RS232 port • Terminal RJ11 output RS485 communication port • Quick Connector for BACnet RS485 KC-401 RELAY CONTROLLER PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION DESCRIPTION • Field programming relay controller • 16 output (20a hid relay controller) • Up to 4 groups (zones) configuration • Two controllers can be networked and therefore control up to 32 relays and 8 groups • Multi group relay assignment capability • Real time system status feed back provided through different led patterns • Multiple input combination (4 devices) • Energy code certified features SPECIFICATIONS • Power supply: 24VAC, 125 MA • IEC Standard compliance: Fast Transient Disturbance Tests & Electrostatic Discharge Immunity Test • Distance : Up to 1,000 ft in bus mode and up to 175 ft in free topology, without repeater • Dimensions: 4.2 in x 7.0 in (107 mm x 180mm) SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION COMMON CONTROL SEQUENCES the adoption of LonWork® open system technology by Echelon®, the Kameleon K8 and K8D Dimming Series serve the objective of bringing the complete hardware and software package capability of operating stand-alone or whith a complete control network. Like the namesake, the adapt perfectly to any environment they are put in as BAS Building Automation System. HVAC Security Photocells Motion Detectors Fire Alarm Dimmer Blinds Control Modem Relay Panel 1 SYSTEM CONFIGURATION Chilling and Cooling Control Computer (optional) Rela y Pan el 2 Rela y Pan el 3 Rela y Pan el xx SYSTEM COMPONENTS Telephone Interface PART INDEX Light Sensors TYPICAL APPLICATIONS Switches SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION COMMON CONTROL SEQUENCES THE FOLLOWING SECTION – K8 SERIES CONFIGURATIONS, PRESENTS THE EXPANSION CAPABILITIES OF THE K8 SERIES IN TERMS OF CONTROL SEQUENCES AND CAPACITY. BASIC SYSTEM AVAILABLE CONTROL SEQUENCES RESET SERVICE RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE SER RX TX +5V INI KC-811 Digital Time Clock 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TYPICAL APPLICATIONS AC2 N24 L24 CT SER N24 AC2 L24 AC2 AC2 CONTROL CAPACITY CT • Sweep ON/OFF • Sweep OFF • Flick Warning • Hold On Time / Time On Extension KC-831 Output Controller* • Outputs : 16 per KC-831 • Inputs : none • Groups : 16 per KC-831 Remote Acces Capabilities - Computer - Modem - Internet OVERRIDE OPTIONS (SWITCHES) ADDED CONTROL SEQUENCES AC2 N24 L24 SER CT N24 AC2 L24 AC2 CT AC2 RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE SER 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 TX +5V INI Keyed Switches KC-811 Digital Time Clock RESET KC-831 Output Controller RX RX 0 1 2 4 3 5 7 6 8 10 11 9 12 14 13 15 SYSTEM COMPONENTS TX +5V INI FTT-10A ECHELON Remote Acces Capabilities - Computer - Modem - Internet NEURON CHIP PART INDEX N24 SER AC2 CT AC2 N24 L24 AC2 L24 AC2 CT • Outputs : 16 per KC-831 • Inputs : 8 Low-voltage / 16 Dry-contacts per KC-821 • Groups : 16 per KC-831 SERVICE CONTROL CAPACITY Switches RESET • Manual ON/OFF • Time ON Extension • Cleaning/Security • Flick Warning SERVICE SYSTEM CONFIGURATION *Output controllers are available for 3-wire, breaker-relays or solid states relays. KC-821 Input Controller SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION ADDED CONTROL SEQUENCES • Occupancy Control Switches RESET SERVICE Occupancy Sensor N24 SER AC2 L24 CT N24 AC2 L24 AC2 AC2 CT RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE SER 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 KC-831 Output Controller RX Keyed Switches TX +5V INI KC-811 Digital Time Clock COMMON CONTROL SEQUENCES OVERRIDE OPTIONS (OCCUPANCY SENSOR) RESET SERVICE L24 N24 SER AC2 CT AC2 N24 L24 AC2 AC2 CT RX TX +5V INI FTT-10A ECHELON NEURON CHIP 0 1 2 4 3 5 7 6 8 13 10 11 9 12 15 14 Remote Acces Capabilities - Computer - Modem - Internet TYPICAL APPLICATIONS KC-821 Input Controller NATURAL LIGHTING (PHOTOCELLS) ADDED CONTROL SEQUENCES • Daylight Harvesting Switches RESET SERVICE MOTION DETECTOR AC2 N24 L24 CT SER AC2 N24 AC2 L24 AC2 CT RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 KC-831 Output Controller RX Keyed Switches TX +5V INI PHOTOCELL KC-811 Digital Time Clock RESET SERVICE AC2 CT AC2 L24 N24 SER AC2 N24 L24 AC2 CT RX TX +5V FTT-10A ECHELON NEURON CHIP INI 3 0 1 2 5 7 6 4 9 8 10 12 14 13 15 11 Remote Acces Capabilities - Computer - Modem - Internet KC-821 Input Controller SYSTEM COMPONENTS LOCAL DIMMING CONTROL ADDED CONTROL SEQUENCES Constant light controller RESET SERVICE AC2 N24 L24 SER CT N24 AC2 L24 AC2 AC2 CT • Dimming (with scene control, fade time and delay) SYSTEM CONFIGURATION SER RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE CONTROL SER TX +5V INI 0 1 2 3 4 5 6 7 KC-811 Digital KC-84x Output Time Clock Controller(s) RESET SERVICE L24 N24 SER AC2 CT AC2 N24 L24 AC2 AC2 CT RX TX +5V FTT-10A ECHELON NEURON CHIP INI 0 1 2 4 3 5 7 6 8 13 10 11 9 12 15 14 Remote Acces Capabilities - Computer - Modem - Internet KC-821 Input Controller PART INDEX 8 9 10 11 12 13 14 15 • Constant Output (%) • Constant Ambient Light (lux) RX SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION CENTRALIZED DIMMING CONTROL Dmx 512 Input & Output • Light Harvesting RESET Constant light controller (echelon based) SER AC2 N24 L24 CT N24 AC2 AC2 L24 AC2 CT • Dimming SERVICE RX TX +5V INI FTT-10A ECHELON NEURON CHIP N24 L24 AC2 CT AC2 RESET NEURON CHIP ECHELON FTT-10A SERVICE SER RX TX +5V INI 0 1 2 3 4 5 6 7 DIMMING CONTROL KC-811 Digital CAPABILITIES Time Clock KC-841 Output Controller • Analog : Dimming Ballast • Digital : Dimming Rack (dmx 512) • groups : up to 6 zones • per KC 84x ctrl 8 9 10 11 12 13 14 15 COMMON CONTROL SEQUENCES ADDED CONTROL SEQUENCES TYPICAL APPLICATIONS Remote Acces Capabilities - Computer - Modem - Internet KC-84x Dimming Controller * Dimming controllers are available for digital (dmx-512) control NETWORK SYSTEM SYSTEM CONFIGURATION Panel 2 INTEGRATED NETWORK SYSTEM HVAC Security PART INDEX Fire Alarm ... Gateway (Optional) TO BUILDING AUTOMATION SYSTEMS SYSTEM COMPONENTS Remote Acces Capabilities - Computer - Modem - Internet Panel 3 Panel x Dali SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION KAMELEON SOFTWARE - K8 SOFT Echelon - Base COMPLETE CONTROL AT YOUR FINGERTIPS • Kameleon Software’ operating system runs under Windows environments • It can easily run simultaneously on multiple platforms in a client/server fashion • Its graphic interface is simple and intuitive, making it easy to configure, program and operate COMMON CONTROL SEQUENCES DESCRIPTION SYSTEM CONFIGURATION SYSTEM COMPONENTS SYSTEM OPERATION • General system architecture monitoring • Override capability by a single mouse-click • Rescheduling capability • Individual lighting circuit, group or zone real-time status view PART INDEX SYSTEM CONFIGURATION • Each user level is protected by password • Easy addition, replacement and troubleshooting of boards • Network management: - Multiple channels allow for a network extension - Usage of different communication means (twisted pair, power line, TCP/IP) • LNS (LonWorks Network Services) compatibility - Plug-in based configuration tools - Integration of third-party LonWorks devices • Group and zone configuration capability - Schedules definition for each group and zone - Switch(es)-relay(s) link configuration TYPICAL APPLICATIONS SPECIFICATIONS SYSTEM DESIGN GUIDE SYSTEM CONFIGURATION KAMELEON SOFTWARE PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES SPECIFICATIONS SOFTWARE SCHEDULER • Ability to Program delayed operating schedules. (I.e.) a special schedule for the Summer Period can be programmed in advance. • Predefined lists of holidays (Canada & USA) • Astronomical programming capability • Flexibility in schedule programming; day of the week, week within a month, first Monday of September etc... DATA LOGGER • Record of chronological sequence of events • Compilation of operating hours • Pre-defined report generator The gathered information could be used to evaluate life expectancy of bulbs or generate electricity bills for lighting use outside of regular business hours ADVANCED FUNCTIONS Kameleon software also offers these important programming options: • Dimming (scene control, fade time and delay options) • Schedule with flick warning • Schedule extension delay • Start-up or shut-down delay • Enabling events • Exclusion of devices (switch, sensor, ...) • Maintenance/cleaning function • Etc... SYSTEM DESIGN GUIDE SYSTEM COMPONENTS KC-83x OUTPUT CONTROLLER COMMON CONTROL SEQUENCES DESCRIPTION • Part numbers: KC-831 (two-wire Relay controller) • Part numbers: KC-832 (three-wire relay controller), • Part numbers: KC-833 (breaker-relay controller) • Part numbers: KC-834 (solid state relay controller) • Simple wiring. Uses a twisted pair for the network • Easy programmation and commissionning • Uses LonWorks network communication SPECIFICATIONS SYSTEM CONFIGURATION 3 wires Breaker relay 2 wires Solide State relay SYSTEM COMPONENTS 3 Wires relay – RR7 PART INDEX 2 Wires Relay -WR6161 TYPICAL APPLICATIONS • Microprocessor EchelonÆ 3150® • Output 16 two-wire or Solid State relays, 8 three-wire relays or Breaker Relays • Transceiver FTT-10A • Communication network LonWorks®, Echelon® Pair of twisted # 22 wire • Distance Up to 2,700 meters (1,000 ft) in bus mode and up to 500 meters (175 ft) in free topology, without repeater • Power supply 24 V AC and 18 V AC, with mid-point tap • Terminal blocks Plug-in / Screws • Dimensions 110 mm x 180 mm (4.3 in x 7.0 in) • Iec standards compliance IEC 60255-22-4: Fast transcient disturbance tests SYSTEM DESIGN GUIDE SYSTEM COMPONENTS KC-811 TIME CLOCK CONTROLLER COMMON CONTROL SEQUENCES DESCRIPTION • Astronomical clock • Built-in scheduler • Uses for scheduler or serial port • Simple wiring • Easy programmation and commissionning • Uses LonWorks network communication • Flash Memory SYSTEM CONFIGURATION TYPICAL APPLICATIONS SPECIFICATIONS • Microprocessor: EchelonÆ 3150Æ • Frequency: 10 MHz • Volatile memory: 32 KB • Non-volatile memory: 64 KB • Communication ports: RS-232, RS-422 or RS-485 (optional) • Speed: Tx 115 kbps; Rx 4.8 kbps • Addressable switches: One wire, (optional) • Can address up to 16 switches,With or without LED • Transmitter-receiver: FTT-10A • Communication network: LonWorksÆ, EchelonÆ • Distance: Up to 2,700 meters in bus mode, without repeater • Analog input: Two 0-10 V input or resistive (photoelectric cell) • Power supply: 8 V AC, with mid-point tap • Terminal blocks: Plug-in • Dimensions: 4.3 in x 4.3 in KC-821 INPUT CONTROLLER DESCRIPTION PART INDEX SYSTEM COMPONENTS • Interfaces 8 low voltage switches or 16 dry contacts • Simple wiring. Uses a twisted pair for the network • Easy programmation and commissionning • Uses LonWorks network communication SPECIFICATIONS • Microprocessor EchelonÆ 3150Æ • Output 8 low voltage switches, with or without LED or 16 dry contacts • Transceiver FTT-10A • Communication network LonWorksÆ, EchelonÆ Pair of twisted # 22 wire • Distance Up to 2,700 meters (1,000 ft)in bus • mode and up to 500 meters (175 ft) in free topology, without repeater • Power supply 24 V AC and 18 V AC, with mid-point tap • Terminal blocks: Plug-in • Dimensions 4.3 in x 7.0 in SYSTEM DESIGN GUIDE SYSTEM COMPONENTS KC-841-842-843 DIMMING CONTROLLER • Power supply 24vac, 125 ma • Outputs 8 (analog) - 100 ballasts/outputs 0-10vdc • Microprocessor echelon 3150 • Transmitter - receiver echelon ftt-10a • Iec standards compliance iec 60255-22-4: fast transient disturbance tests, Iec 61000-4-2: electrostatic discharge immunity test • Terminal blocks pug-in & screws • Temperature 32 f to 122 f (0c to 50c) • Dimensions 7 in x 9 in (178 mm x 229mm) KC-844 DIMMING CONTROLLER KC-842 Input : Echelon (9) Ouput : 0-10 Vcc KC-843 Input : Echelon Ouput : Echelon TYPICAL APPLICATIONS SPECIFICATIONS KC-841 Input : Contact (16) Ouput : On/Off SYSTEM CONFIGURATION • Control capacity: 6 channels per controller, 15 scenes per channel • Complete remote settings of the echelon based sensor • Open loop pattern for pre-set controls • Close loop pattern for daylighting control • Fade and delay time programming • On board on - off - auto manual override • On board 0-100% manual setting • Occupancy sensor interface for dual level • Up - down override setting capability through the kameleon software or from wall switches COMMON CONTROL SEQUENCES DESCRIPTION • Prgogrammable 16 channels relay controller • Provide DMX control of mechanical or plug-in relays • Selectable threshold of 25% or 75% • DMX Softpatch: assign any DMX512 ad-dress to any relay • Two programmable master switch inputs • Input/Output diagnostic functions • Status LED's SYSTEM COMPONENTS DESCRIPTION • Power Supply: 16-24VAC or DC, 150mA (not included) • Relay Coil Supply: 24VAC (not included) • Inputs: DMX512 or master switch momentary On & Off • Outputs: Momentary or maintained • Relay Coil Drive: 250mA Maximum. Use a pilot relay for higher • current requirements • Terminal blocks: Two piece compression screw terminals • Dimensions: 5.5 in X 7.5 in (139.7 mm x 190.5 mm) PART INDEX SPECIFICATIONS SYSTEM DESIGN GUIDE SYSTEM COMPONENTS K-SERIES RELAY PANEL TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES DESCRIPTION • Practical design offering ease of installation and efficient running • Standard sizes for 8, 16, 32 and 64 relays • Removable hinged door with key lock • Panel accepts heavy duty and/or plug-in relays as well as electronic cards • Panel comes with transformer, supply terminal block and supply card • Box knockouts are located on both sides of the panel to facilitate panel junction and wire entry with conduit nipples • Easy handling mounting plate equipped with rubber protected hedge handle • Relay panel comes with covered wiring duct • Movable protection plate between high and low voltage sections • Control Transformer Class 2 (120/277/347 VAC) SPECIFICATIONS • Enclosures and steel doors are coated with ANSI/ASA 61 gray baked enamel • 8 and 16 relay panel made of cold-rolled 16 gauge steel • 32, 48 and 64 relay panels made of cold-rolled 14 gauge steel • Yellow zinc plated removable mounting plate • Yellow zinc plated protection plates part number system SYSTEM CONFIGURATION AVAILABLE OPTIONS SYSTEM COMPONENTS 16 RELAY PANEL PART INDEX K • Multi-voltage transformer (120/277/347 VAC) • Multi-voltage separator • Door for flush mount, invisible screws • Custom panel design on request (color, drip hood, reversible door, ...) x Model K4(4) K8(8) xx Capacity 8, 16, 32, 48, 64 x Surface mount (s) Flush mount (f) 16 RELAY PANEL - Nx nemacode SYSTEM DESIGN GUIDE SYSTEM COMPONENTS DIMENSIONS AND LAYOUT 8 relay panel CET APPAREIL COMPORTE PLUSIEURS CIRCUITS SOUS TENSION MORE THAN ONE LIVE CIRCUIT SEE DIAGRAM KAMELEON Model # KX series Kx-8 Kx-16 Kx-32 Kx-64 Height inch mm 15 381 23.3 592 33.5 850 49.2 1250 Wide Depth Weight inch mm inch mm lbs kg 15 381 4.1 101 26 12 15 381 4.1 101 42 19 20 508 4.1 101 83 38 20 508 4.1 101 140 64 COMMON CONTROL SEQUENCES dimensions CET APPAREIL COMPORTE PLUSIEURS CIRCUITS SOUS TENSION MORE THAN ONE LIVE CIRCUIT SEE DIAGRAM KAMELEON 64 relay panel TYPICAL APPLICATIONS 16 relay panel CET APPAREIL COMPORTE PLUSIEURS CIRCUITS SOUS TENSION MORE THAN ONE LIVE CIRCUIT SEE DIAGRAM SYSTEM CONFIGURATION KAMELEON 32 relay panel CET APPAREIL COMPORTE PLUSIEURS CIRCUITS SOUS TENSION MORE THAN ONE LIVE CIRCUIT SEE DIAGRAM PART INDEX SYSTEM COMPONENTS KAMELEON SYSTEM DESIGN GUIDE SYSTEM COMPONENTS BACK PLATE AND LAYOUT COMMON CONTROL SEQUENCES 8 relay back panel dimensions Back Plate Version 8 relay 16 relay 32 relay 64 relay Fixation Stud/Bolt - Dimension Height Wide inch mm inch mm 12.75 323 13.75 348 21 534 13.75 348 30.75 780 18.75 474 46.5 1180 18.75 474 PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS 16 relay back panel 64 relay back panel 32 relay back panel SYSTEM DESIGN GUIDE SYSTEM COMPONENTS 2-WIRE HID RELAY COMMON CONTROL SEQUENCES DESCRIPTION • Two-wire relay used for monitoring and control • No derating for inductive lighting loads • Manual operation lever with ON/OFF indicator built-in for easy maintenance • Screw terminals on load and control sides • Powerful contact opening mechanism withstands 2,000 amp inrush current and 1,500 amp short circuit current. TYPICAL APPLICATIONS part number # of poles ul rating csa rating isolated auxiliary contact 1 n/a 20a / 300vac 20a / 347vac wr-6161-81 20a / 300vac 20a / 347vac 1 yes 1a 125v ac spst wr-6161-381 wr-6172-81 n/a 20a / 480vac 20a / 347vac 2 CHARACTERISTICS SYSTEM CONFIGURATION • Electrical life 30,000 operations or more at full load, at 20cpm • Mechanical life 60,000 operations or more at 20cpm • Inrush capability 2,000A • Short cirsuit current 14ka • Max. operating speed 20 cpm at nominal load • Operate time Approx. 20 msec • Release time Approx. 20 msec • Initial insulation resistance more than 100M at 500V DC • Dieletric between open contacts 1,694V for one minute • strengh between contacts and coil 2,500V for one minute • Ambient temperature -30 to +50C (-22 to +122F) • Temperature rise (at normal voltage) Max. 65C (149F) MOUNTING METHODS • Use DIN rail, DIN 46277, 35mm width for DIN type relays. • Use accessory WR9910 mounting bracket. Can be broken-off for needed numbers. PRINCIPALS OF OPERATION ON CONDITION AC POWER SUPPLY RED RED BLUE BLUE N CHANGEOVER SWITCH AC POWER SUPPLY RED BLUE RED BLUE CONTROL DEVICE CONTROL DEVICE Internal changeover switch is mechanically linked to main contact. No current flows due to the diode direction. The main contact closes and the mechanically-linked changeover switch operates to shut off the current flow. WHEN CONTROL DEVICE IS TURN ON WHEN CONTROL DEVICE IS TURN OFF N HID RELAY MAIN CONTACT CHANGEOVER SWITCH AC POWER SUPPLY RED RED BLUE BLUE CONTROL DEVICE The coil current flows to operate the relay. TO LOAD TO LOAD HID RELAY MAIN CONTACT N SYSTEM COMPONENTS N HID RELAY MAIN CONTACT CHANGEOVER SWITCH TO LOAD TO LOAD HID RELAY MAIN CONTACT CHANGEOVER SWITCH AC POWER SUPPLY RED BLUE RED BLUE CONTROL DEVICE The coil current flows in the opposite direction to operate the relay. The main contact will open and the changeover switch will operate. PART INDEX OFF CONDITION SYSTEM DESIGN GUIDE SYSTEM COMPONENTS OFF WR-6161 COMMON CONTROL SEQUENCES 1 pole 24.5 .965 relay inside view main contact terminal manual lever with ON/OFF indicator internal changeover switch input terminal 96 3.78 13.5 .531 13.5 .531 TYPICAL APPLICATIONS staggered connection for easy wiring auxiliary contact terminal (optional) compulsory opening lever polarized solenoid OFF WR-6161-81/381 DIN rail mounting strap (optional) 13.5 .531 13.5 .531 SYSTEM COMPONENTS SYSTEM CONFIGURATION 11.433 PART INDEX 49.5 1.949 2 poles CIRCUIT-BREAKER RELAY DESCRIPTION • The Cutler Hammer Solenoid-Operated circuit breakers are designed for use in panel board and are ideally suited for retrofit lighting control applications. In replacement of conventionnal branch circuit protection, they include a unique solenoid-operated mechanism that provides for efficient breaker pulse-on and pulse-off operation. These breakers can be mixed with a group of standard breakers in the same breaker distribution panel. CHARACTERISTICS • Operating voltage: 24 V AC for an cycle • Three Position Handle: OFF, TRIP (center), ON • Electrical performance: Fluorescent lamp 20 A, 347 V AC H.I.D. Rated 20 A, 347 V AC I.C. (Sym, 50/60 Hz) 65 kA at 120, 240 Volts 14 kA at 277/480 Volts Pole(s): 1 or 2 poles Auxiliary switch for Control Circuit Feedback (Status) • Test condition: Switching cycle, 6 times/minute • Bi-Metal Assembly for Thermal Overlaod Protection 96 3.78 WR-6172-81 13.5 .531 13.5 .531 11.433 SYSTEM DESIGN GUIDE SYSTEM COMPONENTS DESCRIPTION Specifications • Wall mount rocker or key type momentary contact relay switch. • Mount to standard wall boxes • To operate rocker type switch, activate button up for ON, and down for OFF • To operate key type switch, turn key to the right for ON, to the left for OFF • 3Amp. 24V. Reversible polarity pulse • Maximum of 4 relays operable with one switch • No limit of switches connected to the relay SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS MC-1138-0 (No LED) MC-1138-1 (1 LED) MC-1138-2 (2 LED) MC-1138-C (Key Switch) COMMON CONTROL SEQUENCES MC-1138 HEAVY DUTY SWITCH MC-1138-C (key switch) PART INDEX MC-1138-2 (2 led) SYSTEM DESIGN GUIDE SYSTEM COMPONENTS DESCRIPTION Specifications • Wall mount rocker type relay switch • To operate, press rocker to one side for ON and to the other side for OFF • 3 WR-8001 can fit into one gang size, WN-3700 Mounting Strap required • 3 Amp. 24 V. Reversible polarity pulse • Maximum of 8 relays operable • No limit to number of switches connected to a relay PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES WR-8001 ROCKER SWITCH WR-5092 KEY SWITCH DESCRIPTION Specifications • Wall mount key operated Enable/Disable switch • 3 WN 5092 can fit into one gang size, WN 3700 Mounting Strap required • Typical application is for security, maintenance and cleaning tour • Use switch to interrupt common (white) to switch(es) to disable wall switch • 3 Amp. 24 V. • Single pole, double throw key switch • CAN NOT BE DIRECTLY CONNECTED TO RELAYS SYSTEM DESIGN GUIDE SYSTEM COMPONENTS SWITCHES ACCESSORIES depth ----0.43” --- COMMON CONTROL SEQUENCES length 3.27” 1.9” 1.73” --- WN-3700 • Switch lid made of clear plastic • Cover for 1 gang / 1, 2 or 3 device opening • Auto-adhesive cover • Steel, plated finish • Mounts to standard wall boxes • 1,2 OR 3 devices can be installed into each strap WN-3020 WN-7700 • Use filler chip to fill device spaces • Color of filler chip identical to cream white of Gentec • Vandal-proof switch enclosure • Lockable door • All colors available • Flush or surface mount SYSTEM COMPONENTS WN-2700 TYPICAL APPLICATIONS width 1.27” 4.4” 0.91” --- SYSTEM CONFIGURATION WN-2700 WN-3700 WN-3020 WN-7700 WN 7700 Series WN 7722-* WN 7733-* WN 7744-* WN 7755-* WN 7766-* 2 Gang Enclosure 3 Gang Enclosure 4 Gang Enclosure 5 Gang Enclosure 6 Gang Enclosure WN 7788-* WN 772525-* WN 772626-* WN 772828-* * - S Surface Mounted 8 Gang Enclosure 2x5 Gang Enclosure 2x6 Gang Enclosure 2x8 Gang Enclosure - F Flush Mounted PART INDEX dimensions SYSTEM DESIGN GUIDE SYSTEM COMPONENTS COMMON CONTROL SEQUENCES WR-8051 AND WR-8503 PUSH BUTTON SWITCHES DESCRIPTION Specifications • Wall mount LED indicating push button relay switch • To operate, press for ON, press again for OFF • Clear plastic cap on button holds switch function label • 1.5 Amp. 24 V. Reversible Polarity Pulse • Maximum of 4 relays operable with one switch • Limit of 6 LED switches connected to one relay • WN 8503 has a built-in Mounting Strap • All 3 switches from WR 8503 obtain the input from a common terminal SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS • 3 WR 8501 can fit into one gang size, WN 3700 Mounting Strap required PART INDEX WR-8501 WR-8503 SYSTEM DESIGN GUIDE SYSTEM COMPONENTS SWITCHES PLATES COMMON CONTROL SEQUENCES DESCRIPTION TYPICAL APPLICATIONS • MC 1158 Series: Brushed stainless steel visible screw for MC 1138 Switch Series MC 1158 Series PART NUMBERS DIMENSIONS SYSTEM CONFIGURATION MC-1158-1 PROFIL MC-1158-2 MC-1158-4 MC1158-2 MC1158-3 MC1158-1 MC-1158-5 SYSTEM COMPONENTS MC-1158-3 MC-1158-6 MC1158-5 MC1158-6 PART INDEX MC1158-4 SYSTEM DESIGN GUIDE SYSTEM COMPONENTS SWITCHES PLATES SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES DESCRIPTION • WN 7600 Series: Brushed stainless steel visibles crew for WR Switch Series • WN 6000 Series: Plastic cover plates – Beige color, gloss finish – Snap-on cover plate and a screw-on trim plate – Mounting screws are hidden for WR Switch Series • WN 7100x Series: Plastic cover plates – Matte finish – Snap-on cover plate and a screw-on trim plate – Invisible screws for WR Switch Series – W: white – H: grey – Y: beige PART NUMBERS WN-XX15 1 gang 1 device 5 gang 15 device WN-XX02 WN-XX18 1 gang 2 device 6 gang 18 device WN-XX03 WN-XX72 1 gang 3 device 2 gang 2 device WN-XX04 WN-XX74 2 gang 4 device 2 gang 3+1 device WN-XX05 WN-XX79 2 gang 5 device 3 gang 1+1+1 device WN-XX06 WN-XX91 2 gang 6 device 1 gang blank WN-XX09 WN-XX92 WN-XX12 4 gang 12 device Wn 6000 Series Wn 7100X Series DIMENSIONS WN-XX01 3 gang 9 device PART INDEX Wn 7600 Series PROFIL WNXX03 WNXX02 WNXX01 WNXX09 WNXX12 2 gang blank WN-XX93 3 gang blank WNXX15 WNXX18 SYSTEM DESIGN GUIDE MODEL # Wr-6161-81 Wr-6161-381 DESCRIPTION 2-wire, 1-pole Hid Latching Relay 20a: 120/277/347 V 2-wire, 1-pole Hid Latching Relay W. Auxiliary Contact 20a: 120/277/347 V 2-wire, 2-pole Hid Latching Relay 20a: 120/277/347 V 2-wire, 2-pole Hid Latching Relay 20a: 120/277/347/480 V 2-wire Hid, 2 Poles Wr-6166-81 Wr-6172-81 Wr-6366 Controllers PART # 35459-01 35563-02 35459-01 36314-07 36317-02 36317-01 36317-03 36317-05 36317-01 35374-00 MODEL # Kc-401 Kc-411 Kc451 Kc-811 Kc-821 Kc-831 Kc-832 Kc-833 Kc-834 Kc-841 Kc-842 Kc-843 Kc-844 Kc-845 Kc-601 DESCRIPTION K4 Relay Controller, 16 Outputs, 4 Inputs K4 Astronomical Time Clock/relay Controller, 8 Outputs, 2 Inputs + 2 Photocells Dedicated Inputs K8 Astronomical Time Clock Controller, Lonworks Ftt-10 K8 Input Controller, 8 Lv Or 16 Contact Inputs, Lonworks Ftt-10 K8 Output Controller, 16 2-wire Relays, Lonworks Ftt-10 K8 Output Controller, 8 3-wire Relays, Lonworks Ftt-10 K8 Output Controller, 8 Breaker-relays, Lonworks Ftt-10 K8 Output Controller, 16 Solid State Relays, Lonworks Ftt-10 K8 Analog Dimming Controller 0 To 10 Vdc K8 Analog Dimming Controller Lonworks Ftt-10 K8 Analog Dimming Controller K8 Dmx-512 Dimming Controller (Input) K8 Dmx-512 Dimming Controller (Output) K6 Bacnet Node PART # 19124 MODEL # K8-soft K6-config DESCRIPTION K8 Series Kameleon Lighting Control Software K6 Series Kameleon Bacnet Configuration Node PART # 25632 25630 25123 24677 26822 MODEL # Ilon 10 Ilon 100 U10-usb Lpr-10 Dt-55 DESCRIPTION Ip Network Interface Lonworks Ip Internet Server Lonworks Router Lonworks Router Lonworks Telephone Interface PART # 30449 30451 30884 20530 30338 MODEL # MC-1138-0 MC-1138-2 MC-1138-C WR-8001 WR-8501 WR-8503 WN-5092 DESCRIPTION Leviton Type, Ivory Leviton Type, 2-indicator Led Leviton Type, Key Switch Rocker Switch, No Indicators 2 Indicators, Push Button Switch 2 Indicators, Push Button Switch, 3 Devices/1 Gang Key Switch 36314-09 37774-00 Software Lonworks Networking Devices Switches 24913 TYPICAL APPLICATIONS PART # Relays SYSTEM CONFIGURATION CONTACT FACTORY DESCRIPTION Kx (K4, K6, K8) 8 Relay Panel Surface Mounted Nema 1 Kx (K4, K6, K8) 16 Relay Panel Surface Door Nema 1 Kx (K4, K6, K8) 32 Relay Panel Surface Mounted Nema 1 Kx (K4, K6, K8) 64 Relay Panel Surface Mounted Nema 1 Kx (K4, K6, K8) 8 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 16 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 32 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 64 Relay Panel Flush Mounted Nema X Kx (K4, K6, K8) 8 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 16 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 32 Relay Panel Flush Mounted Nema 1 Kx (K4, K6, K8) 64 Relay Panel Flush Mounted Nema X SYSTEM COMPONENTS ABOUT NEMA … X 3R – 4 – 4X AND 12 Standard MODEL # Kx – 8pa – S1 Kx – 16pa – S1 Kx – 32pa – S1 Kx – 64pa – S1 Kx – 8pa – F1 Kx – 16pa – F1 Kx – 32pa – F1 Kx – 64pa – F1 Kx – 8pa – F1 Kx – 16pa – F1 Kx – 32pa – F1 Kx – 64pa – F1 PART INDEX Relay Panels PART # 35930 35931 35971 35973 36291 36292 36561 30157 COMMON CONTROL SEQUENCES PART INDEX SYSTEM DESIGN GUIDE Switches Plates For Mc-1138 Series Switches Plates For Wr-8xxx Series TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES PART INDEX PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION Switch Accessories Detectors Sensors PART # 30354 30355 30356 30357 30987 MODEL # Mc1158-1 Mc1158-2 Mc1158-3 Mc1158-4 Mc1158-6 DESCRIPTION 1 Gang/1 Device 2 Gangs/2 Devices 3 Gangs/3 Devices 4 Gangs/4 Devices 6 Gangs/6 Devices 25030 30347 25032 30348 25033 30349 25034 30995 25035 30996 24308 24309 24759 24760 Wn-6001 Wn-7601 Wn-6002 Wn-7602 Wn-6003 Wn-7603 Wn-6004 Wn-7672 Wn-6006 Wn-7606 Wn-7609 Wn-7612 Wn-7615 Wn-7618 1 Gang/1 Device (Plastic) 1 Gang/1 Device (Stainless Steel) 1 Gang/2 Devices (Plastic) 1 Gang/2 Devices (Stainless Steel) 1 Gang/3 Devices (Plastic) 1 Gang/3 Devices (Stainless Steel) 2 Gangs/4 Devices (Plastic) 2 Gangs/4 Devices (Stainless Steel) 2 Gangs/6 Devices (Plastic) 2 Gangs/6 Devices (Stainless Steel) 3 Gangs/9 Devices (Stainless Steel) 4 Gangs/12 Devices (Stainless Steel) 5 Gangs/15 Devices (Stainless Steel) 6 Gangs/18 Devices (Stainless Steel) PART # 24310 24912 38163 30346 MODEL # Wn-3020 Wn-2700 Wn-7700 Wn-3700 DESCRIPTION Filler Chip Protective Plastic Lid Steel Switch Enclosure Mounting Bracket 1, 2 Or 3 Devices PART # 31091-01 26172 26820 26814 26170 26818 26817 26171 26809 26815 MODEL # Et-15 Cm-pc Wsd-pdt-w Wsd-w Cm-9-r Cm-10-r Cm-pdt-r Cm-pdt-10-r Wv-16-r Wv-pdt-r DESCRIPTION Outdoor Photocell C/w Relay Indoor Photocell Wall Switch Detector – Pdt – Line Voltage Wall Switch Decora – Pir – Line Voltage 120 / 277 V Ceiling Mount Std Range 360° Pir Low Voltage C/w Relay Ceiling Mount Ext Range 360° Pir Low Voltage C/w Relay Ceiling Mount Std Range 360° Pir Low Voltage C/w Relay Ceiling Mount Ext Range 360° Pir Low Voltage C/w Relay Wide View, Pir, Low Voltage C/w Output Relay Wide View, Pdt, Low Voltage C/w Output Relay NOTES NOTES Printed in Canada NIG 26979 PART INDEX SYSTEM COMPONENTS SYSTEM CONFIGURATION TYPICAL APPLICATIONS COMMON CONTROL SEQUENCES