GENERAL NOTES:
A.
B.
C.
D.
LINE VOLTAGE
E.
CCT. BREAKER
AT SOURCE
PANELBOARD
CCT. BREAKER
AT SOURCE
PANELBOARD
3-WAY
4-WAY
LIGHTING LOAD OR
RELAY/CONTACTOR
COIL AS APPLICABLE
3-WAY
F.
ALIGN ALL DEVICES SHOWN ON PLANS AT SAME
DIMENSION FROM DOOR FRAME OR WALL.
CONDUIT/CABLES SHALL BE ROUTED WHEREVER
NECESSARY TO KEEP DEVICES ALIGNED.
ALL DEVICES MOUNTED AT SAME HEIGHT TO BE
ALIGNED HORIZONTALLY.
ENSURE ALL DEVICES ARE LEVEL AND PLUMB
AFTER INSTALLATION.
FOR MULTI-GANG DEVICES, ALIGN DEVICES AT
CENTER OF GROUP. PROVIDE SINGLE
FACEPLATE FOR GROUPS OF DEVICES WHERE
APPLICABLE.
COORDINATE WITH ALL TRADES CASE-BY-CASE.
BRANDSTETTER
CARROLL INC
ARCHITECTS ENGINEERS PLANNERS
2360 Chauvin Drive, Lexington, KY 40517
p. 859.268.1933
www.brandstettercarroll.com
LIGHTING LOAD OR
RELAY/CONTACTOR
COIL AS APPLICABLE
LOCAL WALL
SWITCH(ES)
LOAD
CONTACT(S)
OF
OCCUPANCY
SENSOR(S)
GENERAL NOTES:
A.
MECHANICAL/ELECTRICAL ENGINEERS
NOTE THAT THIS DETAIL IS SCHEMATIC IN NATURE, INTENDED TO INDICATE HOW LOCAL
SWITCHING IS TO INTERACT WITH RELATED OCCUPANCY SENSORS. THERE MAY ALSO
BE OTHER LIGHTING CONTROL ELEMENTS THAT ALSO APPLY IN ANY PARTICULAR
AREA, WHICH SHALL ALSO BE PROVIDED BY THE INSTALLING CONTRACTOR.
265100.00-13
WWW.KLHENGRS.COM
1538 ALEXANDRIA PIKE, SUITE 11
FT. THOMAS, KENTUCKY 41075 800-354-9783
859-442-8050
859-442-8058 FAX
SCHEMATIC LOCAL OVERRIDE-OFF SWITCH
SCALE: NONE
260502.00-01
PROVIDE DUPLEX GFCI RECEPTACLE PER
ADJACENT PEDESTAL OUTLET DETAIL, TO BE USED
FOR ANY NEEDED MAINTENANCE AT THE METER
PIT. COORDINATE LOCATION WITH PIT INSTALLER,
ARCHITECT AND OWNER PRIOR TO COMMENCING
WITH ANY RELATED WORK.
PROVIDE DUPLEX GFCI RECEPTACLE WITHIN
PIT FOR SUMP PUMP.
FIRE-SERVICE WATER METER PIT WITH TAMPER
SWITCH AT POST INDICATOR VALVE. PROVIDE
FIRE ALARM WIRING AND CONNECTIONS TO THE
TAMPER SWITCH FOR STATUS MONITORING.
PROVIDE WATER-TIGHT JUNCTION BOX ON PIT
WALL AT TOP OF PIT FOR REMOTE READING
OF WATER METER. COORDINATE LOCATION
WITH PIT INSTALLER.
DEVICE MOUNTING ALIGNMENT DETAIL
SCALE: NONE
KEYED NOTES:
1.
"W"
CHAMFER
EDGES
"X"
FIRE PROTECTION SERVICE TO BUILDING
WATER MAIN
FINISHED
PAVEMENT
OR GRADE
TS
PROVIDE XHHW-2 COLOR CODED ANALOG FIRE
ALARM WIRING TO INDOOR MONITOR MODULE.
INSTALL MONITOR MODULE AT FIRE ALARM
CONTROL PANEL OR AT INCOMING SPRINKLER
RISER. DO NOT INSTALL MONITOR MODULE OR
ANY OTHER ELECTRONIC OR DIGITAL DEVICES
OUTDOORS OR IN PIT. INSTALL ANALOG WIRING
IN MINIMUM 1" GALVANIZED RIGID CONDUIT
BELOW GRADE. PROVIDE WATER-TIGHT WORK
IN PIT.
PROVIDE MINIMUM (2) #10 AND (1) #10
GROUND IN MINIMUM 1" GALVANIZED RIGID
ELECTRICAL CONDUIT BELOW GRADE TO (1)
20A/1P BRANCH CIRCUIT BREAKER IN
SOURCE PANELBOARD.
PROVIDE (1) 1-1/4" EMPTY GALVANIZED
RIGID CONDUIT BELOW GRADE (WITH
DRAG LINE) TO TELEPHONE SERVICE
ENTRANCE EQUIPMENT BOARD.
LEXINGTON, KENTUCKY
COLUMBUS, OHIO
DAYTON, OHIO
NEW YORK, NEW YORK
PROVIDE 1" MINIMUM SCHEDULE 40 ELECTRICAL PVC CONDUIT. BACKFILL WITH
EXCAVATED OR BORROWED MATERIAL. MATERIAL SHALL BE FREE OF ROCKS 1"
DIAMETER AND LARGER. COMPACT TO 90% IN MAX 8" LIFTS OF LOOSE SOIL.
THIS NOTE IS TYPICAL FOR ALL UNDERGROUND CONDUITS IN THIS DETAIL.
2. 3000# CONCRETE BASE (CLASS A FORMED WHERE EXPOSED).
3. PROVIDE SOLID COPPER (#10 AWG MINIMUM) BONDING JUMPER, BONDED TO
BOX AND TO GALVANIZED STRUT.
4. PROVIDE ROUND CONCRETE BASE.
5. PROVIDE ONE DUPLEX GFCI WR-RATED RECEPTACLE, WITH WEATHERPROOF
COVER RATED NEMA 3R WHILE-IN-USE.
6. PROVIDE 5/8" X 10' GROUND ROD WITH GROUND CLAMP.
7. 1/2" SCHEDULE 40 ELECTRICAL PVC FOR GROUND WIRE.
8. PROVIDE GALVANIZED STRUT FOR BOX MOUNTING. INSERT MIN 18 INCHES
DOWN INTO CONCRETE BASE.
9. PROVIDE (3) #4 REBAR RUN VERTICAL WITHIN CONCRETE BASE SEPARATED BY
120 DEGREES AND NO LESS THAN 2" FROM OUTER EDGE.
10. CONDUITS AS NEEDED, 1" MINIMUM, WITH MINIMUM 24" RADIUS.
"Y"
METER PIT PLAN VIEW SCHEMATIC
GENERAL NOTES:
A.
B.
C.
D.
"Z"
VERIFY EXACT LOCATIONS OF ALL WORK WITHIN THE PIT WITH THE PLUMBING CONTRACTOR AND
WITH THE LOCAL WATER UTILITY.
INSTALL ALL WORK IN THE PIT SO THAT ALL DEVICES AND BOXES ARE READILY ACCESSIBLE FOR
MAINTENANCE.
CONVERT ALL CONDUITS TO RIGID STEEL BEFORE TURNING UP THROUGH THE BUILDING SLAB (SEE
SPECS).
REFER TO CIVIL SITE PLAN FOR PROPOSED LOCATION OF PIT. VERIFY IN FIELD WITH SITE PLUMBING
CONTRACTOR
260590.00-05
"X"
"Y"
"Z"
NOTES TO DETAIL EDITOR:
1)
MAKE SURE CONDUIT SIZES & QUANTITIES CAN FIT INTO BOX OPENING.
STARTING POINTS FOR EDITING "W", "X", "Y" & "Z" MATRIX ARE AS FOLLOWS.
SECTION VIEW
FIRE-SERVICE WATER METER PIT DETAIL
PLAN VIEW
"W"
4" FOR CONCRETE BASES THAT ARE MORE THAN 6" ABOVE GRADE AND FOR SPECIAL LANDSCAPE
APPLICATIONS WHERE IT IS DESIRED TO KEEP THE PROFILE AS LOW AS POSSIBLE (BE MINDFUL OF WATER AND
SNOW ENTRY INTO OUTLETS THOUGH).
6" TO 12" IN LAWN AREAS WHERE THE CONCRETE BASE IS ONLY 6" ABOVE GRADE.
"X"
0" IN PAVED PEDESTRIAN AREAS.
6" IN LAWN AREAS.
(USE TRUCK AND BUS VERSION OF THIS DETAIL IF IN VEHICULAR TRAFFIC AND PARKING AREAS, OR IF WITHIN
3'-0" OF THESE AREAS. CONSIDER INCREASING HEIGHT TO 36" IF THE LOCATION GETS REGULAR TRUCK OR BUS
TRAFFIC)
"Y"
24" FOR LAWN/LANDSCAPE TYPE APPLICATIONS.
"Z"
12" FOR LAWN/LANDSCAPE APPLICATIONS.
PEDESTAL OUTLET DETAIL
SCALE: NONE
On/Off Control
Device
(Wall Switch, Power
Pack, Relay, for
Control System)
Normal
Panel
"W"
Normal
Lighting
Normal Line
Normal Neutral
Emergency
Lighting
"Switching" Line
"Sensing" Line
INVERTER
Normal Switched Sense
Emergency Power Out
Normal Neutral
Emergency Neutral
Normal Power Sense
Emergency Power In
ELCU
Emergency Line
Emergency Neutral
B.
EMERGENCY LIGHTING CONTROL UNIT
SCALE: NONE
University of Kentucky
Locker Room
A.
265113.00-04
Revisions:
Issue Date: October 2, 2014
C.
PROVIDE EMERGENCY LIGHTING CONTROL UNIT THAT IS UL
OR ETL LISTED TO UL STANDARD 924. PROVIDE CONTACTS
RATED AT LEAST 20 AMPERES UP TO AT LEAST 277 VOLTS.
BASIS OF DESIGN FOR THIS DETAIL IS WATTSTOPPER
ELCU-200. MODIFY IF REQUIRED FOR OTHER
MANUFACTURERS.
BASIS OF DESIGN FOR THIS DETAIL IS WATTSTOPPER
ELCU-200 SERIES. LC&D, DOUGLAS LIGHTING AND LVS
CONTROLS ARE CONSIDERED EQUIVALENT.
LOW VOLTAGE DIMMED LIGHTING SHALL RETURN TO 100% ON
UPON POWER LOSS.
College Way at Softball/Soccer Complex
Lexington, KY 40506
ELECTRIC
DETAILS
Architect Project No.
E1
ELECTRIC DETAILS
13106
Consultant Project No.
15935
Owner Project No.
2401.0
EP-200