GENERAL NOTES: A. B. C. D. LINE VOLTAGE E. CCT. BREAKER AT SOURCE PANELBOARD CCT. BREAKER AT SOURCE PANELBOARD 3-WAY 4-WAY LIGHTING LOAD OR RELAY/CONTACTOR COIL AS APPLICABLE 3-WAY F. ALIGN ALL DEVICES SHOWN ON PLANS AT SAME DIMENSION FROM DOOR FRAME OR WALL. CONDUIT/CABLES SHALL BE ROUTED WHEREVER NECESSARY TO KEEP DEVICES ALIGNED. ALL DEVICES MOUNTED AT SAME HEIGHT TO BE ALIGNED HORIZONTALLY. ENSURE ALL DEVICES ARE LEVEL AND PLUMB AFTER INSTALLATION. FOR MULTI-GANG DEVICES, ALIGN DEVICES AT CENTER OF GROUP. PROVIDE SINGLE FACEPLATE FOR GROUPS OF DEVICES WHERE APPLICABLE. COORDINATE WITH ALL TRADES CASE-BY-CASE. BRANDSTETTER CARROLL INC ARCHITECTS ENGINEERS PLANNERS 2360 Chauvin Drive, Lexington, KY 40517 p. 859.268.1933 www.brandstettercarroll.com LIGHTING LOAD OR RELAY/CONTACTOR COIL AS APPLICABLE LOCAL WALL SWITCH(ES) LOAD CONTACT(S) OF OCCUPANCY SENSOR(S) GENERAL NOTES: A. MECHANICAL/ELECTRICAL ENGINEERS NOTE THAT THIS DETAIL IS SCHEMATIC IN NATURE, INTENDED TO INDICATE HOW LOCAL SWITCHING IS TO INTERACT WITH RELATED OCCUPANCY SENSORS. THERE MAY ALSO BE OTHER LIGHTING CONTROL ELEMENTS THAT ALSO APPLY IN ANY PARTICULAR AREA, WHICH SHALL ALSO BE PROVIDED BY THE INSTALLING CONTRACTOR. 265100.00-13 WWW.KLHENGRS.COM 1538 ALEXANDRIA PIKE, SUITE 11 FT. THOMAS, KENTUCKY 41075 800-354-9783 859-442-8050 859-442-8058 FAX SCHEMATIC LOCAL OVERRIDE-OFF SWITCH SCALE: NONE 260502.00-01 PROVIDE DUPLEX GFCI RECEPTACLE PER ADJACENT PEDESTAL OUTLET DETAIL, TO BE USED FOR ANY NEEDED MAINTENANCE AT THE METER PIT. COORDINATE LOCATION WITH PIT INSTALLER, ARCHITECT AND OWNER PRIOR TO COMMENCING WITH ANY RELATED WORK. PROVIDE DUPLEX GFCI RECEPTACLE WITHIN PIT FOR SUMP PUMP. FIRE-SERVICE WATER METER PIT WITH TAMPER SWITCH AT POST INDICATOR VALVE. PROVIDE FIRE ALARM WIRING AND CONNECTIONS TO THE TAMPER SWITCH FOR STATUS MONITORING. PROVIDE WATER-TIGHT JUNCTION BOX ON PIT WALL AT TOP OF PIT FOR REMOTE READING OF WATER METER. COORDINATE LOCATION WITH PIT INSTALLER. DEVICE MOUNTING ALIGNMENT DETAIL SCALE: NONE KEYED NOTES: 1. "W" CHAMFER EDGES "X" FIRE PROTECTION SERVICE TO BUILDING WATER MAIN FINISHED PAVEMENT OR GRADE TS PROVIDE XHHW-2 COLOR CODED ANALOG FIRE ALARM WIRING TO INDOOR MONITOR MODULE. INSTALL MONITOR MODULE AT FIRE ALARM CONTROL PANEL OR AT INCOMING SPRINKLER RISER. DO NOT INSTALL MONITOR MODULE OR ANY OTHER ELECTRONIC OR DIGITAL DEVICES OUTDOORS OR IN PIT. INSTALL ANALOG WIRING IN MINIMUM 1" GALVANIZED RIGID CONDUIT BELOW GRADE. PROVIDE WATER-TIGHT WORK IN PIT. PROVIDE MINIMUM (2) #10 AND (1) #10 GROUND IN MINIMUM 1" GALVANIZED RIGID ELECTRICAL CONDUIT BELOW GRADE TO (1) 20A/1P BRANCH CIRCUIT BREAKER IN SOURCE PANELBOARD. PROVIDE (1) 1-1/4" EMPTY GALVANIZED RIGID CONDUIT BELOW GRADE (WITH DRAG LINE) TO TELEPHONE SERVICE ENTRANCE EQUIPMENT BOARD. LEXINGTON, KENTUCKY COLUMBUS, OHIO DAYTON, OHIO NEW YORK, NEW YORK PROVIDE 1" MINIMUM SCHEDULE 40 ELECTRICAL PVC CONDUIT. BACKFILL WITH EXCAVATED OR BORROWED MATERIAL. MATERIAL SHALL BE FREE OF ROCKS 1" DIAMETER AND LARGER. COMPACT TO 90% IN MAX 8" LIFTS OF LOOSE SOIL. THIS NOTE IS TYPICAL FOR ALL UNDERGROUND CONDUITS IN THIS DETAIL. 2. 3000# CONCRETE BASE (CLASS A FORMED WHERE EXPOSED). 3. PROVIDE SOLID COPPER (#10 AWG MINIMUM) BONDING JUMPER, BONDED TO BOX AND TO GALVANIZED STRUT. 4. PROVIDE ROUND CONCRETE BASE. 5. PROVIDE ONE DUPLEX GFCI WR-RATED RECEPTACLE, WITH WEATHERPROOF COVER RATED NEMA 3R WHILE-IN-USE. 6. PROVIDE 5/8" X 10' GROUND ROD WITH GROUND CLAMP. 7. 1/2" SCHEDULE 40 ELECTRICAL PVC FOR GROUND WIRE. 8. PROVIDE GALVANIZED STRUT FOR BOX MOUNTING. INSERT MIN 18 INCHES DOWN INTO CONCRETE BASE. 9. PROVIDE (3) #4 REBAR RUN VERTICAL WITHIN CONCRETE BASE SEPARATED BY 120 DEGREES AND NO LESS THAN 2" FROM OUTER EDGE. 10. CONDUITS AS NEEDED, 1" MINIMUM, WITH MINIMUM 24" RADIUS. "Y" METER PIT PLAN VIEW SCHEMATIC GENERAL NOTES: A. B. C. D. "Z" VERIFY EXACT LOCATIONS OF ALL WORK WITHIN THE PIT WITH THE PLUMBING CONTRACTOR AND WITH THE LOCAL WATER UTILITY. INSTALL ALL WORK IN THE PIT SO THAT ALL DEVICES AND BOXES ARE READILY ACCESSIBLE FOR MAINTENANCE. CONVERT ALL CONDUITS TO RIGID STEEL BEFORE TURNING UP THROUGH THE BUILDING SLAB (SEE SPECS). REFER TO CIVIL SITE PLAN FOR PROPOSED LOCATION OF PIT. VERIFY IN FIELD WITH SITE PLUMBING CONTRACTOR 260590.00-05 "X" "Y" "Z" NOTES TO DETAIL EDITOR: 1) MAKE SURE CONDUIT SIZES & QUANTITIES CAN FIT INTO BOX OPENING. STARTING POINTS FOR EDITING "W", "X", "Y" & "Z" MATRIX ARE AS FOLLOWS. SECTION VIEW FIRE-SERVICE WATER METER PIT DETAIL PLAN VIEW "W" 4" FOR CONCRETE BASES THAT ARE MORE THAN 6" ABOVE GRADE AND FOR SPECIAL LANDSCAPE APPLICATIONS WHERE IT IS DESIRED TO KEEP THE PROFILE AS LOW AS POSSIBLE (BE MINDFUL OF WATER AND SNOW ENTRY INTO OUTLETS THOUGH). 6" TO 12" IN LAWN AREAS WHERE THE CONCRETE BASE IS ONLY 6" ABOVE GRADE. "X" 0" IN PAVED PEDESTRIAN AREAS. 6" IN LAWN AREAS. (USE TRUCK AND BUS VERSION OF THIS DETAIL IF IN VEHICULAR TRAFFIC AND PARKING AREAS, OR IF WITHIN 3'-0" OF THESE AREAS. CONSIDER INCREASING HEIGHT TO 36" IF THE LOCATION GETS REGULAR TRUCK OR BUS TRAFFIC) "Y" 24" FOR LAWN/LANDSCAPE TYPE APPLICATIONS. "Z" 12" FOR LAWN/LANDSCAPE APPLICATIONS. PEDESTAL OUTLET DETAIL SCALE: NONE On/Off Control Device (Wall Switch, Power Pack, Relay, for Control System) Normal Panel "W" Normal Lighting Normal Line Normal Neutral Emergency Lighting "Switching" Line "Sensing" Line INVERTER Normal Switched Sense Emergency Power Out Normal Neutral Emergency Neutral Normal Power Sense Emergency Power In ELCU Emergency Line Emergency Neutral B. EMERGENCY LIGHTING CONTROL UNIT SCALE: NONE University of Kentucky Locker Room A. 265113.00-04 Revisions: Issue Date: October 2, 2014 C. PROVIDE EMERGENCY LIGHTING CONTROL UNIT THAT IS UL OR ETL LISTED TO UL STANDARD 924. PROVIDE CONTACTS RATED AT LEAST 20 AMPERES UP TO AT LEAST 277 VOLTS. BASIS OF DESIGN FOR THIS DETAIL IS WATTSTOPPER ELCU-200. MODIFY IF REQUIRED FOR OTHER MANUFACTURERS. BASIS OF DESIGN FOR THIS DETAIL IS WATTSTOPPER ELCU-200 SERIES. LC&D, DOUGLAS LIGHTING AND LVS CONTROLS ARE CONSIDERED EQUIVALENT. LOW VOLTAGE DIMMED LIGHTING SHALL RETURN TO 100% ON UPON POWER LOSS. College Way at Softball/Soccer Complex Lexington, KY 40506 ELECTRIC DETAILS Architect Project No. E1 ELECTRIC DETAILS 13106 Consultant Project No. 15935 Owner Project No. 2401.0 EP-200