Are you sure you know Medium Voltage terms perfectly ? Introduction to prefabricated metal-enclosed equipment We are reminding you of the main definitions in usual terms. Keep in mind the following points We are not giving you hereafter, the exact standard terms. The definitions are issued by the International Electrical Commission. oltage, current, frequency short circuit power are are the four main bases which define the electrical equipment. V e need to consider 5 criteria to specify the design of the compartments of a metal-enclosed equipment he insulation function, the control function and the protection function of electrical networks, are carried out through the switchgears. ll the documents, standards, regulations, recommendations and local customs are in reference to the electrical equipment and will not have the same legal impact. T date 1 08/9 1•1 - B• - ed revis 4 05/200 ■ Merlin Gerin ■ Square D ■ Telemecanique W A Presentation factory-built equipment Introduction In order to design a medium-voltage cubicle, you need to know the following basic magnitudes: # # # # Voltage Current Frequency Short-circuit power. The voltage, the rated current and the rated frequency are often known or can easily be defined, but how can we calculate the short-circuit power or current at a given point in an installation? Knowing the short-circuit power of the network allows us to choose the various parts of a switchboard which must withstand significant temperature rises and electrodynamic constraints. Knowing the voltage (kV) will allow us to define the dielectric withstand of the components. E.g.: circuit breakers, insulators, CT. Voltage Operating voltage U (kV) This is applied across the equipment terminals. Rated voltage Ur (kV) The rated voltage is the upper limit of the highest voltage of system for which the equipment is intended Example: # Operating voltage: 20 kV # Rated voltage: 24 kV # Power frequency voltage 50 Hz 1 mn: 50 kV rms. # Lighnting impulse voltage 125 kV peak. The rated voltage is always greater than the operating voltage and, is associated with an rated insulation level. Rated insulation level Ud (kV rms. 1 mn) and Up (kV peak) The rated insulation level is specified by the rated lighning impulse withstand voltage phase to earth (Up). It is linked to rated short duration power-frequency withstand voltage (Ud) Ud: rated short duration power-frequency withstand voltage It is simulated in a laboratory by the rated power-frequency withstand for one minute. Us: switching impulse voltage Up: rated lightning impulse withstand voltage The voltage wave that results is simulated in a laboratory date 1 08/9 1•1 - B• - evised r N.B.: IEC 60694, article 4 sets the various voltage values together with, in article 6, the dielectric testing conditions. 4 05/200 2 Presentation Metal-enclosed, factory-built equipment 0 Apart from special cases, MERLIN GERIN equipment is in conformity with list 2 hereunder Rated voltage Rated power-frequency withstand voltage Up 1 minute kV rms. Normal operating voltage Ur kV rms. Rated lightning impulse withstand voltage Up kV peak 7.2 12 17.5 24 36 list 1 40 60 75 95 145 20 28 38 50 70 3.3 to 6.6 10 to 11 13.8 to 15 20 to 22 25.8 to 36 list 2 60 75 95 125 170 kV rms. Insulation levels apply to switchgear under operating conditions in accordance with IEC 60694 §2.1If not, derating should be considered. Each insulation level corresponds to a distance in air which guarantees equipment withstand without a test certificate.(IEC60071-2) Rated voltage kV rms. 7.2 12 17.5 24 36 Rated impulse withstand voltage 1.2/50 µs kV peak Distance/earth in air cm 60 75 95 125 170 10 12 16 22 32 STANDARD IEC VOLTAGE U Um 0,5 Um t rated voltage 0 rated short duration power-frequency withstand voltage rated withstand voltage values for lightning impulse voltage 20 7,2 12 28 38 50 70 Ud date 1 08/9 1•1 - B• 17,5 24 36 Ur 60 75 95 125 170 Up NOTE:different "across the isolating distance" values are mentioned for the switchning device to meet the safety requirements specified for disconnectors ed revis 4 05/200 3 Metal-enclosed, factory-built equipment 0 Current Rated normal current: Ir (A) This is the rms. value of current that equipment can withstand when closed, without exceeding the temperature rise allowed in standards. The table below gives the temperature rises authorised by the IEC according to the type of contacts. Rated normal current: Type of mechanism of material Max. values Max. temperature Max. temp. rise of conductor (°C) = tmax°- 40 °C contacts in air bare copper or copper alloy 75 silver or nickel plated 105 tin-plated 90 bolted connections or equivalent devices bare copper, bare copper alloy or aluminium alloy 90 silver or nickel plated 115 tin-plated 105 35 65 50 50 75 65 N.B.: rated currents usually used by Merlin Gerin are: 400, 630, 1 250, 2 500 and 3 150 A. Examples: Operating current: I (A) # For a switchboard with a 630 kW motor feeder and a 1 250 kVA transformer feeder at 5.5 kV operating voltage. This is calculated from the consumption of the devices connected to the circuit in question. It is the current that really passes through the equipment. If we do not have the information to calculate it, the customer has to provide us with its value. The operating current can be calculated when we know the power of the current consumers. 5 calculating the operating current of the transformer feeder: Apparent power: S = UI 3 S 1 250 - = 130A I = ----------- = ------------------------5 ,5 / 1 ,732 U 3 5 calculating the operating current of the motor feeder: cosϕ = power factor = 0.9 η = motor efficiency = 0.9 630 P I = ----------------------------- = ----------------------------------------------------------- =82A 5.5 • 1.732 • 0.9 • 0.9 U 3 cos ϕη date 1 08/9 1•1 - B• - evised r 4 05/200 4 Presentation Metal-enclosed, factory-built equipment 0 Minimal short-circuit current: Isc (kA rms.) (see explanation in "Short-circuit currents" chapter.) Rated short-time withstand current (Ik) (kA rms. 1 s or 3 s) the r.m.s value of the current which the switchgear can carry in the closed position during a specified rated duration (generally 1s or 3s) Rated peak withstand current (Ip) (kA peak) value of the initial peak in the transient period for a rated frequency of 50Hz and below it is equal to 2.5 Ik (2.6 for 60Hz) Note: some installations,close generator for example, can have higher Rated frequency fr (Hz) peak coefficient. # Two frequencies are usually used throughout the world: 5 50 Hz in Europe 5 60 Hz in America. For other value of frequency, contact the technical department (the IEC standard values of the rated frequency are 16 2/3; 25; 50; 60 Hz) Switchgear functions Designation and symbol function operating current fault current switching breaking Disconnecter isolates Earthing disconnecter earthes Switch ✔ switches, does not isolate Disconnecter switch switches isolates ✔ Fixed circuit breaker ✔ switches protects does not isolate ✔ Withdrawable circuit breaker switches / protects isolates in some case if withdrawn ✔ ✔ Fixed contactor switches does not isolate ✔ Withdrawable contactor switches isolates in some case if withdrawn ✔ Fuse protects does not isolate date 1 08/9 ✔ (once) ✔ = YES 1•1 - B• ed revis 4 05/200 5 Presentation is al vocabulary Electrotechnic IEC 60694 defined by the Metal-enclosed, factory-built equipment The insulation function, the control function and the protection function of electrical networks, are carried out through the switchgear. T he term “Switchgear” is a general one. It is applied to apparatus with mechanical contacts and their arrangement with devices, of control, measurement and protection. It equally concerns the grouping of such apparatus with connections, accessories and enclosures… THE INSULATION FUNCTION The insulation function establishes or isolates an unloaded circuit. THE DISCONNECTOR The disconnector is a mechanical switching device which provides in the open position, an isolating distance which ensures the 2 sub-installations to run separatly. The disconnector has two stable positions : open and closed. As the disconnector does not have breaking and closing capacity, the opening and closing must be unloaded. In the “open” position, the isolating distance allows the dielectric withstand between input and output. To ensure the dielectrical independence of the 2 sub-installations, the input/output distance is superior to the phase/earth distance. In the “closed” position, it has to withstand the service current and the short circuit current during the specified duration. The two positions must have a locking device forbidding the manœuvre when the circuit is on load. THE EARTHING SWITCH The earthing switch is a disconnector used to earth the circuit. It is capable of supporting the short circuit currents within one second and to feed the discharged current of the cables. The earthing switch can have, in certain cases, closing capacity. The earthing switch must have a locking device in the “closed” position. date 1 08/9 1•1 - B• - ed revis 4 05/200 6 Presentation THE CONTROL FUNCTION Metal-enclosed, factory-built equipment The control function of the switchgear is used to close and to open the circuits on load. here are three types of control devices : the switch, the switch disconnector and the contactor. All this equipment has to withstand the short-circuit currents within a specified time. T THE SWITCH The switch is a control device with two stable positions, open and closed, which allows the feeding of a circuit (transformer, distribution cables…) making. and breaking the service current. THE SWITCH DISCONNECTOR The switch disconnector is a switch which, in the “open” position, complies with the insulation conditions of the disconnector. THE CONTACTOR The contactor is an apparatus, electrically controlled, able to establish or to break a circuit will a strong rhythm of manœuvres. In general, it is used in motor feeder cubicles. It is often associated with fuses to limit the peak and to break the shortcircuit current. date 1 08/9 1•1 - B• - ed revis 4 05/200 7 Presentation THE PROTECTION FUNCTION Metal-enclosed, factory-built equipment The protection function has to quickly eliminate all overcurrent, overload or short-circuit, in a network to assure the safety of the personnel and to limit all damages. W e use fuses or circuit breakers in association with protective systems. FUSES The fuses are protective devices which have to open the circuit by blowing up one or several of its elements, when the current passes within a specified time, to a determined value. A fuse is designed to eliminate the short-circuits. If the overcurrent is too low, the fuse may fail and not break properly. A fuse is specified by its melting curve (see technical leaflets). ☞ remarks : the choice of fuses depends on the voltage, the service current, the type of feeder, the starting currents and its manufacturer. In general, the service current = nominal current 2 THE CIRCUIT BREAKER The circuit breaker is an apparatus which assures the control and the protection of a network. The circuit breaket is establish, to withstand and break the service currents as well as the short-circuit currents. The tripping is automatically released by means of a protection chain (TC, TP, relay, tripping coil). When the circuit breaker is in a withdrawn position, it assures the insulation function and is similar to a disconnector when tested in accordance. date 1 08/9 1•1 - B• - ed revis 4 05/200 8 Metal-enclosed, factory-built equipment Presentation 5 criteria have to be considered to specify compartments in accordance with the customer's need -architecture and accessibility s -service continuity of the switchgear -partition class -degree of protection (IP) of the enclosure -internal arc classification METAL-ENCLOSED COMPARTMENT CHARACTERISTICS . ARCHITECTURE AND ACCESSIBILITY: four types of compartment Three accessible to the user, one non-accessible non-accessible compartment: the opening may destroy the integrity of the compartment. For example: welded tank of a RMU. ; completely welded GIS tank.... Accessible compartments - "interlock-controlled accessible compartment" : use of interlocks to ensure that all live parts inside are dead and earthed before opening - "procedure-based accessible compartment": relies on user procedure and locking , use of padlocks or equivalent - "tool-based accessible compartment": no built-in feature to ensure electrical safety before opening. They need tools to be opened date 1 08/9 1•1 - B• - ed revis 4 05/200 9 Presentation Metal-enclosed, factory-built equipment SERVICE CONTINUITY OF THE SWITCHGEAR (LSC1,2A,2B) ONLY FOR ACCESSIBLE COMPARTMENT For switchgear and controlgear, the Loss of Service Continuity (LSC) describes the extent to which the other compartments and/or functional units may remain energized when the main circuit is opened Category LSC1: this form does not provide service continuity during maintenance and require complete disconnection of the swithgear from the system and making dead before accessing the interior of the enclosure. Ex: the complete installation (HV cables; busbars..) must be shut down before opening the CB enclosure Category LSC2A: when accessing components of one functional unit ,the other functional units of the switchgear may be kept in service. Ex: the busbar may be kept alive (also the other cubicles of the switchgear) during the maintenance of the circuit breaker. Category LSC2B:this form is intended to allow the maximum continuity of service. Ex: during the maintenance of the circuit breaker , MV cables and busbar may stay alive. PARTITION CLASSES There are 2 types of partitioning class Class PM:when an accessible compartment is open the equipment is always in accordance with the metal-enclose criteria. The opened compartment is surrounded by earthed metallic partition and shutters No electric field is present in the opening compartment and no electrical field change may occur in the surrounding compartments. Class PI:is not a PM class, there are one or more non-metallic partitions or shutters between opened accessible compartments and live parts of the main circuit. date 1 08/9 1•1 - B• - ed revis 4 05/200 10 Presentation Metal-enclosed, factory-built equipment DEGREE OF PROTECTION OF THE ENCLOSURE see 5.13 of IEC 60694 The degree of protection of persons provided by an enclosure against access to hazardous parts of the main circuit is indicated in the here under table Metal-enclosed swithgear satisfies as a minimum IP2X INTERNAL ARC CLASSIFICATION Metal-enclosed swithgear that satisfies the requirements of the IECstandard is designed to prevent the occurrence of internal fault. Experience has shown that faults are . more likely to occur in some locations inside an enclosure . Designs which have been successfully tested according to Annex A of IEC 62271-200 are classified as IAC date 1 08/9 1•1 - B• - Where the risk is considered negligible, IAC class is not necessary Where the risk is considered to be relevant, only metal-enclosed switchgear IAC classified should be used. ed revis 4 05/200 11 Presentation Metal-enclosed, factory-built equipment All the documents, standards, regulations, recommendations, and local customs do not have the same legal value. THE REGULATIONS In order to describe the equipment, each contract refers to a gathering of regular texts, standards, recommendations and local customs. The objective of these regulations is to guarantee the safety of people and to limit the damage. THE REGULATIONS The regulations, either fixed a circular, must be respected imperatively by the constructors. THE STANDARDS The standard has a contractual character and acts as a reference. Only when a fixed or a decree imposes it, must it be respected imperatively by the supplier. The standards define the switchgear and controlgear and their field of application. THE RECOMMENDATIONS The standards are nationwide and are often inspired by international recommendations (eg. the IEC). THE LOCAL CUSTOMS The local customs, though theoretically negociable, are difficult to pass. We have to work with these. date 1 08/9 1•1 - B• - ed revis 4 05/200 12 Metal-enclosed, factory-built equipment Presentation THE REGULATIONS MAIN NATIONAL STANDARDS (cont’d) France Germany UTE DIN-VDE-TGL Great Britain Belgium BS NBN Spain USA Italy UNE ANSI CEI* * Comitato Electrotecnico Italiano. INTERNATIONAL REFERENCES Three recommendations often act as international references : ■ I.E.C. : International Electrical Commission. ■ A.N.S.I. : American National Standard Institute (US). ■ N.E.M.A. : National Electrical Manufacturer Association (US). MAIN IEC PUBLICATIONS ON MEDIUM VOLTAGE THE 298 publications IEC Publication 60050: International Electrotechnical Vocabulary Publication 60265: high voltage switches. ■ Publication 60470: high-voltage alternating current contactors and contactors-based motor-starters ■ Publication 60529: degrees of protection provided by enclosures (IP Code) ■ Publication 60694 :common clauses for high voltage switchgear and controlgear standards. ■ Publication 62271: high-voltage switchgear and controlgear part 100: high-voltage alternating current circuit breakers part 102: alternating current disconnectors and earthing switches part 105: alternating current switch-fuse combinations part 200: AC metal-enclosed switchgear and controlgear for rated voltage above 1kV and up and including 52kV part 203: gas-insulation metal-enclosed swithgear for rated voltages > 52kV . duty T100a part 308: guide for asymmetrical short circuit breaking test ■ ■ WHERE CAN YOU ORDER THE IEC PUBLICATIONS ? Central Office at the International Electrotechnical Commission, 3 rue de Varembé PO Box 131 CH-1211Geneva 20- Switzerland you may find the IEC standard on Intranet or Email: inmail@iec.ch date 1 08/9 1•1 - B• - ed revis 4 05/200 13