THE CLIMATEMASTER CLIMADRY® II REHEAT AND DEHUMIDIFICATION OPTION OVERVIEW Indoor Air Quality (IAQ) and Relative Humidity (RH) are increasingly becoming design issues that must be addressed by selecting heating and cooling equipment with advanced capabilities. The ClimateMaster ClimaDry® II reheat and dehumidification option offers unique features unlike anything currently available today. The patented ClimaDry® II option is an innovative means of providing fully modulating reheat without the complication of intricate refrigeration controls. ClimaDry® II is a form of Hot Gas Generated Reheat, which utilizes one of the biggest advantages of a water source heat pump (WSHP), the transfer of energy through the water piping system. ClimaDry® II simply diverts condenser water through a water-to-air coil that is placed after the evaporator coil. Figure 1 - Typical Hotgas Reheat Circuit RETURN WATER LEAVING AIR (TO WATER LOOP) WATER COIL SUPPLY WATER CHECK (FROM WATER LOOP) VALVE REVERSING VALVE HOTGAS REHEAT VALVE CHECK VALVE COMPRESSOR AIR COIL TXV º CLIMADRY II BENEFITS ClimaDry® II is like no other reheat option on the market. Proportional reheat is controlled to the desired leaving air temperature setpoint (factory setpoint of 72°F) no matter the water loop temperature. If condenser water is not warm enough, the internal circulating loop increases the water temperature with each pass through the condenser coil. Since dehumidification operation will occur under less than full load cooling conditions a good percentage of the time, it is important to have a reheat function that provides 100% reheat in the spring and fall when the water loop is cool. Competitors without the ClimaDry® II option typically use an on/off (non-modulating) refrigeration based reheat circuit, typically referred to as “Hot Gas Reheat” (HGR). By passing the hot discharge gas from the compressor through an air coil, these systems do provide the ability to reheat the leaving air. However, these systems must rely on complex controls to operate and contain many additional valves and complex piping schemes. In addition, the performance of HGR units typically fluctuates with the outside air temperature and thus provides a varying amount of dehumidification. Rarely will a HGR unit provide 100% reheat and provide supply air at a neutral temperature, like a ClimaDry® II system. The simplicity of the ClimaDry® II circuit makes it incredibly easy to maintain. No refrigerant switching valves or hard to diagnose leaky check valves are utilized. No unusual refrigerant pressures occur during the reheat mode. There is no requirement for antifreeze in the reheat circuit.* The refrigerant circuit is identical to a standard ClimateMaster unit (without reheat). Plus, the water loop portion of a ClimaDry® II unit is simple and easy to understand. ENTERING AIR Figure 2 - ClimaDry® II Circuit LEAVING AIR º REHEAT COIL RETURN WATER (TO WATER LOOP) SUPPLY WATER (FROM WATER LOOP) MODULATING MIXING VALVE INTERNAL CIRCULATING PUMP WATER COIL REVERSING VALVE COMPRESSOR TXV AIR COIL º ENTERING AIR CLIMADRY® II APPLICATIONS The ClimaDry® II option can be applied to a number of common applications, such as: • Classrooms • Computer rooms • Spaces with high latent loads like auditoriums, theaters, convention centers, etc. • Most anywhere humidity is a problem REHEAT FUNCTION With the ClimaDry® II option, the return air from the space is conditioned by the air-to-refrigerant (evaporator) coil, and then reheated by the water-to-air (reheat) coil to dehumidify the air, but maintain the same space temperature. The moisture removal capability of the heat pump is determined by the unit’s latent capacity rating. UNIT FEATURES • Fully modulating reheat for precise control of supply air temperatures • 100% reheat to operate as a dehumidifier • “Neutral” 72°F supply air temperature even at part load (non-design) conditions • Supply air temperature adjustable from 69°F to 75°F with optional potentiometer • Specially designed freeze-resistant reheat circuit does not require antifreeze* • Integrated reheat controls - simply attach a humidistat or dehumidistat • Microprocessor (DXM) controls standard • Simple AHRI certified refrigeration circuit • All water system eliminates refrigeration circuit modifications (same refrigeration circuit as units without ClimaDry® II) • Stable refrigeration pressures, even at low entering water temperatures • All components located inside the cabinet • Two-speed fan (direct drive units) automatically controlled for increased latent capacity in reheat mode AVAILABILITY The ClimaDry® II option is currently available on ClimateMaster Tranquility® 27 Series, Tranquility® 20 Series, Tranquility® Large (TL) Series, and Tranquility® TR Series units. Other units will soon have the ClimaDry® II option available. *Antifreeze may be required for normal operation depending on location but not specifically for ClimaDry® II operation. Reheat coil reheats the cool dehumidified air to “neutral” supply temperature Separation between evaporator coil and reheat coil to allow maximum moisture removal Standard evaporator coil Modulating mixing valve automatically adjusts reheat capacity based upon leaving air temperature and loop entering water temperature to provide 100% reheat and “neutral” supply air Standard DXM control takes input from either a humidistat or dehumidistat and controls the reheat function by interfacing with the modulating reheat valve U N I T F E AT U R E S Standard Features • • • • Tranquility® High Efficiency (TR) • • • • • • • • • • • • • • • • • • • • • • • Tranquility® 16 Compact (TC) • • • • • • • • • • • • • • • • • • • Tranquility® High Efficiency Two-Stage (TZ) • • • • • • • • • • • • • • • • Tranquility® 22 Compact Two-Stage (TY) • • • • • • • • • • • • • • • • Tranquility® Vertical Stack (TRM) • • • • • • • • • • • • • • • • • Tranquility® Console (TRC) • • • • • • • • • • • • • • • • Tranquility® Compact Belt Drive (TC) • • • • • • • • • • • • • • Tranquility® Large (TL) • • • • • • • • • • • • • • • • • • Tranquility® Water-to-Water (TMW) • • • • • • • • • • • • • Rooftop (TRE) • • • • • • • • • • • • • • • • • • • • • Rooftop (TRT) • • • • • • • • • • • • • • • • • • • • Rx Energy Recovery Ventilator (ERV) • • • • • • • • • • • • • • • • • • Internal Service Disconnect • • • • • • • vFlow™ Internal Variable Water Flow • • ECM Fan Motor • • ClimaDry® Reheat • • Coated Air Coil • • Internal Secondary Pump • • DDC Controller • • DXM Controller * • • Desuperheater Coil • • Two-Way Control Valve • • Downflow Configuration High Static Blower UltraQuiet (Mute) Package • • Auto-Flow Water Regulation Cupro-Nickel Coil ** • • Extended Entering Water Temperature Insulation *** Remote Reset at Thermostat • • Factory Installed Hanger Brackets (Horizontal Units) • • Scroll Compressors • • Multiple Access Panels for Installation and Service Ease • • Field Convertible Discharge (Horizontal Units) • • TXV • • Dual Level Compressor Vibration Isolation • • • Copper Water Coil ** • • Modulating Water Valve ‡ • • ECM Fan Motor Condensate Overflow Protection Extended Range Capable Refrigerant Circuit (20°F to 120°F) Microprocessor CXM Controls * • iGate™ Advanced Control EarthPure® (HFC-410A) Refrigerant Tranquility® 30 Two-Stage (TT) Tranquility® 20 Single-Stage (TS) Product Series * ** *** † ‡ Factory Installed Options • • • • • • • Vertical Dedicated Outdoor Air (TOV) • • • • • • Horizontal Dedicated Outdoor Air (TOH) • • • • • • • • † † • • • • • Some exceptions may apply to standard features and options, consult product submittal materials to determine availability. Control for TO Series is DDC with modulating HGR. Control for TMW 360-600 is DDC. Water coil construction for TO Series and TMW 360-600 is stainless steel. Standard on TMW Series Extended Range = 35°F–95°F EWT Low system pressure drop valve is a standard feature, high system pressure drop valve is optional 7300 S.W. 44th Street Oklahoma City, OK 73179 Phone: 405-745-6000 Fax: 405-745-6058 climatemaster.com ISO 9001:2008 Certified Quality: First & Always ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely ClimateMaster’s opinion or commendation of its products. The management system governing the manufacture of ClimateMaster’s products is ISO 9001:2000 certified. We are a proud supporter of the Geothermal Exchange Organization - GEO. For more information visit geoexchange.org ClimateMaster is a company of LSB Industries, New York Stock Exchange Symbol: LXU LC360 © ClimateMaster, Inc. 2010 Rev.: 20 August, 2012