High Voltage Fuses
German DIN Standard
HHD
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
The striker pin system is connected by means of a high
resistance parallel conductor. After melting the main fuse
elements, the striker pin indicates the operating status of
the fuse and actuates a microswitch for remote indication, and/or triggers a load break switch or a circuit breaker to open.
The temperature limiting function of
the fuse striker pin
Design and construction
SIBA HV Fuse-links have parallel connected pure silver
fuse-elements. The design and method of production of
the elements ensure narrow tolerances of time-curren
characteristics.
The fuse elements are wound on a ceramic support and
are attached to the silver plated connection caps by
means of spot-welding. The connection caps are fitted
inside the silver plated copper end caps by spot welding.
The copper end caps themselves are press-fitted onto
the porcelain tube, which is glazed inside and outside.
The end caps are mechanically fixed to the porcelain
tube and additionally sealed by a durable elastic sealing
medium. This sealing method has been proven over
many decades of positive field experience and ensures
tightness against ingress of humidity.
Striker pin
SIBA HV Fuse-links are available with striker pins of
force:
• 80 N (Part No. 30 … 13 for basic-type) and
• 120 N (Part No. 30 … 14 for variant-type)
The characteristics of both striker pins correspond to
IEC 60282-1, VDE 0670 Part 4, and are of the energycategory “medium”.
www.siba.de
SIBA HV Fuse-links up to and including 160 A with a
striker pin of 80 N are equipped with an integrated
temperature limiter as standard. The temperature limiter
is fitted inside the striker pin system. The SIBA striker pin
system therefore includes the following functions:
• thermal protection of adjacent equipment, especially
SF6 insulated switchgear
• limitation of failure current at the overload region
• improved properties for the switch-fuse combinations
according to IEC 62271-105
The integrated temperature limiter avoids unacceptably
high temperatures – no matter why they are generated –
in gas-insulated switchgear or narrow switchgears enclosures. By means of a melting activator, temperatures
inside the fuse link enclosure are limited to below 100°C.
This design especially considers continuity of current
supply for the end user for as long as possible. The
system reacts in such a way that short time overloads do
not
cause
the
fuse
to
interrupt
the
circuit unnecessarily. Only when inadmissible values are
exceeded, the fuse will open the switch via the striker
pin.
Higher temperatures on plastic fuse enclosures in SF6insulated switchgear can be caused by:
• selection of a fuse rating too low for proper transformer
protection
• fuses loaded with fault currents below the minimum
breaking current
• deterioration of fuse links caused by transient fault
currents (e.g. lightning strike)
• transformer fault currents (e.g. winding short-circuit)
• additional temperature rise because of poor clip fitting
Fuse-links with an integrated temperature limiter are
compatible with standard fuse links. All coordination
schedules can be used.
Further information on our temperature limiter, design
and construction, can be obtained from our website:
www.siba.de
HHD 1
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
German DIN Standard
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
Selection Guide
Rated Voltage
AC
[kV]
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
3/7.2
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
6/12
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
10/17.5
DIN Size
E
[mm]
192 *
192 *
192 *
192 *
292
292
292
292
442
442
442
192
192
292 *
292 *
292 *
292 *
442
442
442
442
537
537
292
292
292
367 *
367 *
367 *
367 *
442
442
442
Class
Part No.
Selection
Guide
[Page]
Techn.
Data
[Page]
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
30 002 13
30 010 13
30 018 13
30 018 14
30 098 13
30 099 13
30 100 13
30 100 14
30 109 13
30 110 13
30 110 14
30 119 13
30 267 13
30 004 13
30 012 13
30 020 13
30 020 14
30 101 13
30 102 13
30 103 13
30 103 14
30 211 13
30 211 14
30 255 13
30 221 13
30 222 13
30 176 13
30 177 13
30 178 13
30 178 14
30 231 13
30 232 13
30 233 13
HHD 5
HHD 5
HHD 5
HHD 5
HHD 6
HHD 6
HHD 6
HHD 6
HHD 7
HHD 7
HHD 7
HHD 8
HHD 8
HHD 9
HHD 9
HHD 9
HHD 9
HHD 10
HHD 10
HHD 10
HHD 10
HHD 11
HHD 11
HHD 12
HHD 12
HHD 12
HHD 13
HHD 13
HHD 13
HHD 13
HHD 14
HHD 14
HHD 14
HHD 23
HHD 23
HHD 23
HHD 23
HHD 23
HHD 23
HHD 23
HHD 23
HHD 24
HHD 24
HHD 24
HHD 25
HHD 25
HHD 25
HHD 25
HHD 25
HHD 25
HHD 26
HHD 26
HHD 26
HHD 26
HHD 26
HHD 26
HHD 27
HHD 27
HHD 27
HHD 27
HHD 27
HHD 27
HHD 27
HHD 28
HHD 28
HHD 28
* Standard size
HHD 2
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
German DIN Standard
HHD
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
Selection Guide
Rated Voltage
AC
[kV]
10/24
10/24
10/24
10/24
10/24
10/24
10/24
10/24
10/24
20/36
20/36
20/36
20/36
38,5
38,5
38,5
6/12
6/12
6/12
10/24
10/24
10/24
*Standard size
DIN Size
E
[mm]
292
292
442 *
442 *
442 *
537
537
537
537
442
537 *
537 *
537 *
537
537
537
292
292
292
442
442
442
Class
Part No.
Selection
Guide
[Page]
Techn.
Data
[Page]
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
Back-up
General-purpose
General-purpose
General-purpose
General-purpose
General-purpose
General-purpose
30 180 13
30 225 13
30 006 13
30 014 13
30 022 13
30 203 13
30 204 13
30 196 13
30 196 14
30 181 13
30 008 13
30 016 13
30 024 13
30 337 13
30 338 13
30 338 13
30 004 93
30 012 93
30 020 93
30 006 93
30 014 93
30 022 93
HHD 15
HHD 15
HHD 16
HHD 16
HHD 16
HHD 17
HHD 17
HHD 17
HHD 17
HHD 18
HHD 19
HHD 19
HHD 19
HHD 19
HHD 19
HHD 19
HHD 21
HHD 21
HHD 21
HHD 22
HHD 22
HHD 22
HHD 29
HHD 29
HHD 29
HHD 29
HHD 29
HHD 30
HHD 30
HHD 30
HHD 30
HHD 31
HHD 31
HHD 31
HHD 31
HHD 31
HHD 31
HHD 31
HHD 32
HHD 32
HHD 32
HHD 32
HHD 32
HHD 32
Selection Guide Fuse-Bases
Article
Rated Voltage
AC
[kV]
DIN-Size
E
[mm]
Part No.
Techn.
Data
[Page]
Indoor Fuse-bases
7.2
12
24
36
24
7.2
12
24
36
192
292
442
537
292
192
292
292
537
31 001 02
31 003 02
31 005 02
31 007 02
31 221 01
31 002 01
31 004 01
31 006 01
31 008 01
HHD 40
HHD 40
HHD 40
HHD 40
HHD 40
HHD 41
HHD 41
HHD 41
HHD 41
Outdoor Fuse-bases
www.siba.de
HHD 3
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
Selection Guide Microswitch Fitting
Article
Length
Part No.
Techn.
Data
[Page]
Contact Clip
31 001 16
31 001 10
31 001 14
31 001 17
34 002 01
HHD 42
HHD 42
HHD 42
HHD 42
HHD 43
Distance Plate
31 002 01.3
HHD 43
[mm]
Micro switch
250
660
900
1 200
Selection Guide Accessories
Article
Rated
Voltage
[kV]
Extension Adapter
Test Fuse-link for gas
insulated switchgear
Contact Clip 200 A
indoor and outdoor
Contact Clip
heavy duty
Storage Holder
HHD 4
Part No.
Techn.
Data
[Page]
12/24
34 006 01
HHD 44
24
33 010 03
HHD 45
31 003 02.20
HHD 46
34 001 01.20
HHD 46
33 004 01
33 006 01
33 008 01
HHD 47
HHD 47
HHD 47
12
24
36
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E=192 mm
AC 3/7.2 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
30 002 13.6.3
30 002 13.10
30 002 13.16
30 002 13.20
30 002 13.25
30 002 13.31.5
30 002 13.40
30 002 13.50
30 010 13.63
30 010 13.80
30 010 13.100
30 010 13.125
30 018 13.160
30 018 14.200
D = Diameter
HHD
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
53
53
53
53
53
53
53
53
67
67
67
67
85
85
63
63
63
63
63
63
63
63
63
63
63
63
63
50
Weight
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.5
1.5
1.5
1.5
2.9
2.9
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Preferred Standard Size 3/7.2 kV
A
F
O
N
www.siba.de
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 5
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
A
F
O
N
DIN
Rated Voltage
Class
E= 292 mm
AC 3/7.2 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
250
315
355
30 098 13.6.3
30 098 13.10
30 098 13.16
30 098 13.20
30 098 13.25
30 098 13.31.5
30 098 13.40
30 098 13.50
30 099 13.63
30 099 13.80
30 099 13.100
30 099 13.125
30 100 13.160
30 100 14.200
30 100 14.250
30 100 14.315
30 100 14.355
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 6
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
3.35
3.35
3.35
53
53
53
53
53
53
53
53
67
67
67
67
85
85
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
50
50
50
50
50
Weight
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
3.8
3.8
3.8
3.8
3.8
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 442 mm
AC 3/7.2 kV
Back-up
Rated
Current
[A]
Part No.
100
125
160
200
250
315
355
400
500
30 109 13.100
30 109 13.125
30 110 13.160
30 110 14.200
30 110 14.250
30 110 14.315
30 110 14.355
30 110 14.400
30 110 14.500
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.64
2.64
3.35
3.35
3.35
3.35
3.35
3.35
3.35
67
67
85
85
85
85
85
85
85
63
63
63
50
50
50
50
50
50
Weight
2.9
2.9
5.4
5.4
5.4
5.4
5.4
5.4
5.4
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 7
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
German DIN Standard
DIN
Rated Voltage
Class
E= 192 mm
AC 6/12 kV
Back-up
Rated
Current
[A]
6.3
10
16
20
25
31.5
40
50
63
A
F
O
N
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 8
Part No.
30 119 13.6.3
30 119 13.10
30 119 13.16
30 267 13.20
30 267 13.25
30 267 13.31.5
30 267 13.40
30 267 13.50
30 267 13.63
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.64
2.64
2.64
2.64
2.64
2.64
53
53
53
67
67
67
67
67
67
63
63
63
63
63
63
63
63
63
Weight
1.2
1.2
1.2
1.5
1.5
1.5
1.5
1.5
1.5
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 292 mm
AC 6/12 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
30 004 13.6.3
30 004 13.10
30 004 13.16
30 004 13.20
30 004 13.25
30 004 13.31.5
30 004 13.40
30 004 13.50
30 012 13.63
30 012 13.80
30 012 13.100
30 012 13.125
30 020 13.160
30 020 14.200
D = Diameter
HHD
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
53
53
53
53
53
53
53
53
67
67
67
67
85
85
63
63
63
63
63
63
63
63
63
63
63
63
63
50
Weight
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
3.8
3.8
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Preferred Standard Size 6/12 kV
A
F
O
N
www.siba.de
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 9
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
German DIN Standard
A
F
O
N
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
DIN
Rated Voltage
Class
E= 442 mm
AC 6/12 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
250
30 101 13.6.3
30 101 13.10
30 101 13.16
30 101 13.20
30 101 13.25
30 101 13.31.5
30 101 13.40
30 101 13.50
30 102 13.63
30 102 13.80
30 102 13.100
30 102 13.125
30 103 13.160
30 103 14.200
30 103 14.250
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 10
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
3.35
53
53
53
53
53
53
53
53
67
67
67
67
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
63
50
50
Weight
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.9
2.9
2.9
2.9
5.4
5.4
5.4
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated voltage
Class
E= 537 mm
AC 6/12 kV
Back-up
Rated
Current
[A]
Part No.
100
125
160
200
250
315
30 211 13.100
30 211 13.125
30 211 13.160
30 211 14.200
30 211 14.250
30 211 14.315
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
3.35
3.35
3.35
3.35
3.35
3.35
85
85
85
85
85
85
63
63
63
50
50
50
Weight
6.8
6.8
6.8
6.8
6.8
6.8
Pack
[kg/1]
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 11
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
A
F
O
N
DIN
Rated Voltage
Class
E= 292 mm
AC 10/17.5 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
30 255 13.6.3
30 255 13.10
30 255 13.16
30 221 13.20
30 221 13.25
30 221 13.31.5
30 221 13.40
30 221 13.50
30 221 13.63
30 222 13.80
30 222 13.100
30 222 13.125
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 12
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.64
2.64
2.64
2.64
2.64
2.64
3.35
3.35
3.35
53
53
53
67
67
67
67
67
67
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
Weight
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
3.8
3.8
3.8
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 367 mm
AC 10/17.5 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 176 13.6.3
30 176 13.10
30 176 13.16
30 176 13.20
30 176 13.25
30 177 13.31.5
30 177 13.40
30 177 13.50
30 177 13.63
30 178 13.80
30 178 13.100
30 178 13.125
30 178 13.160
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
3.35
3.35
53
53
53
53
53
67
67
67
67
85
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
63
Weight
2.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
4.8
4.8
4.8
4.5
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 13
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
A
F
O
N
DIN
Rated Voltage
Class
E= 442 mm
AC 10/17.5 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 231 13.6.3
30 231 13.10
30 231 13.16
30 231 13.20
30 231 13.25
30 231 13.31.5
30 231 13.40
30 232 13.50
30 232 13.63
30 232 13.80
30 233 13.100
30 233 13.125
30 233 13.160
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
3.35
3.35
3.35
53
53
53
53
53
53
53
67
67
67
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
63
Weight
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.9
2.9
2.9
5.4
5.4
5.4
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
1.77 ” (45 mm)
1.30 ” (33 mm)
0.40 ” (10 mm)
1.38 ” (35 mm)
HHD 14
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 292 mm
AC 10/24 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
30 180 13.6.3
30 180 13.10
30 180 13.16
30 225 13.20
30 225 13.25
30 225 13.31.5
30 225 13.40
30 225 13.50
30 225 13.63
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.64
2.64
2.64
2.64
2.64
2.64
53
53
53
67
67
67
67
67
67
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
Weight
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 15
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 442 mm
AC 10/24 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 006 13.6.3
30 006 13.10
30 006 13.16
30 006 13.20
30 006 13.25
30 006 13.31.5
30 006 13.40
30 014 13.50
30 014 13.63
30 014 13.80
30 022 13.100
30 022 13.125
30 022 13.160
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
3.35
3.35
3.35
53
53
53
53
53
53
53
67
67
67
85
85
85
63
63
63
63
63
63
63
63
63
63
63
40
31.5
Weight
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.9
2.9
2.9
5.4
5.4
5.4
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
Preferred Standard Size 10/24 kV
A
F
O
N
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 16
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 537 mm
AC 10/24 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 203 13.6.3
30 203 13.10
30 203 13.16
30 203 13.20
30 203 13.25
30 203 13.31.5
30 203 13.40
30 204 13.50
30 204 13.63
30 204 13.80
30 196 13.100
30 196 13.125
30 196 13.160
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.10
2.10
2.64
2.64
2.64
3.35
3.35
3.35
53
53
53
53
53
53
53
67
67
67
85
85
85
63
63
63
63
63
63
63
63
63
63
63
40
31.5
Weight
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.7
3.7
3.7
6.8
6.8
6.8
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 17
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 442 mm
AC 20/36 kV
Back-up
Rated
Current
[A]
6.3
10
16
A
F
O
N
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 18
Part No.
30 181 13.6.3
30 181 13.10
30 181 13.16
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
53
53
53
20
20
20
Weight
2.2
2.2
2.2
Pack
[kg/1]
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 537 mm
AC 20/36 kV
Back-up
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
50
63
80
100
30 008 13.6.3
30 008 13.10
30 008 13.16
30 008 13.20
30 008 13.25
30 016 13.31.5
30 016 13.40
30 024 13.50
30 024 13.63
30 024 13.80
30 024 13.100
D = Diameter
HHD
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.10
2.10
2.10
2.64
2.64
3.35
3.35
3.35
3.35
53
53
53
53
53
67
67
85
85
85
85
40
40
40
40
40
40
40
40
40
40
40
Weight
2.6
2.6
2.6
2.6
2.6
3.5
3.5
6.0
6.0
6.0
6.0
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
Preferred Standard Size 20/36 kV
DIN
Rated Voltage
Class
E= 537 mm
AC 38,5 kV
Back-up
Rated
Current
[A]
6.3
10
16
20
25
31.5
40
50
63
Part No.
30 337 13.6.3
30 337 13.10
30 338 13.16
30 338 13.20
30 338 13.25
30 338 13.31.5
30 339 13.40
30 339 13.50
30 339 13.63
D = Diameter
Standard
DIN 43625 · IEC 60282-1
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.10
2.64
2.64
2.64
2.64
3.35
3.35
3.35
53
53
67
67
67
67
85
85
85
40
40
40
40
40
40
40
40
40
Weight
2.6
2.6
3.5
3.5
3.5
3.5
6.0
6.0
6.0
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 19
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard – General-Purpose
According IEC 60 282-1 and VDE 0670 Part
4, a general-purpose fuse interrupts fault
currents between the rated breaking current
and the current, which causes melting within one hour. The protection range of the
SIBA-VS-protector extends this basic
demand. The minimum breaking current
starts at some rated currents at 1.5 times
the rated current. In combination with the
temperature released striker pin and the
3pol. trip-free release of the switchgear a
full range protection is possible. Additional
feature is the small powerloss of the VSProtector. It is up to 40 % lower than the
standard DIN-fuse.
The
VS-Protector for the overload and
short-circuit range
dimensions of the VS-Protector are
according to DIN 43625. The rated voltages
12 and 24 kV and also the available current
ratings allow protection of transformers up
to 630 kVA.
The function of the VS-Protector is compa-
rable to a typical back-up fuse-link. The
melting elements of pure silver are wound
inside onto a ceramic support. A short
section in the center of the fuse is
designed as a “heat chamber”. Inside this
chamber the elements are made of silveralloy. At overload this generates a certain
temperature level that brings the fuse to
switch off after corresponding time. Below
the rated currend the fuse shows an ageing
free behaviour also in encapsulated switchgear.
HHD 20
www.siba.de
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
DIN
Rated Voltage
Class
E= 292 mm
AC 6/12 kV
General-Purpose
Rated
Current
[A]
Part No.
6.3
8
10
16
20
25
31.5
40
50
63
80
100
30 004 93.6.3
30 012 13.8
30 012 93.10
30 012 93.16
30 012 93.20
30 012 93.25
30 012 93.31.5
30 012 93.40
30 020 93.50
30 020 93.63
30 020 93.80
30 020 93.100
D = Diameter
Standard
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.64
2.64
2.64
2.64
2.64
2.64
2.64
3.35
3.35
3.35
3.35
53
67
67
67
67
67
67
67
85
85
85
85
63
63
63
63
63
63
63
63
63
63
63
63
DIN 43625 · IEC 60282-1
Weight
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
3.8
3.8
3.8
3.8
Pack
[kg/1]
1
1
1
1
1
1
1
1
1
1
1
1
A
F
O
N
www.siba.de
HHD
1.77 ”
1.30 ”
0.40 ”
1.38 ”
(45 mm)
(33 mm)
(10 mm)
(35 mm)
HHD 21
HHD
SICHERUNGEN/FUSES
High Voltage Fuses
For Air & Gas Insulated Switchgear
Indoor and Outdoor Application
German DIN Standard
A
F
O
N
DIN
Rated Voltage
Class
E= 442 mm
AC 10/24 kV
General-purpose
Rated
Current
[A]
Part No.
6.3
10
16
20
25
31.5
40
30 006 93.6.3
30 014 93.10
30 014 93.16
30 014 93.20
30 014 93.25
30 022 93.31.5
30 022 93.40
1.77 ”
1.30 ”
0.40 ”
1.38 ”
HHD 22
D = Diameter
Standard
[inch]
[mm]
Rated Breaking
Current
[kA]
2.10
2.64
2.64
2.64
2.64
3.35
3.35
53
67
67
67
67
85
85
40
40
40
40
40
40
40
DIN 43625 · IEC 60282-1
Weight
2.2
2.9
2.9
2.9
2.9
5.4
5.4
Pack
[kg/1]
1
1
1
1
1
1
1
(45 mm)
(33 mm)
(10 mm)
(35 mm)
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 192 mm
AC 3/7.2 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
30 002 13.6.3
30 002 13.10
30 002 13.16
30 002 13.20
30 002 13.25
30 002 13.31.5
30 002 13.40
30 002 13.50
30 010 13.63
30 010 13.80
30 010 13.100
30 010 13.125
30 018 13.160
30 018 14.200
Rated
Breaking
Current
[kA]
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
63
63
63
63
63
63
63
63
63
63
63
63
63
50
22
34
56
70
90
110
140
170
210
280
320
390
600
800
178.0
113.0
50.0
27.0
21.0
17.0
13.0
9.3
6.8
4.8
3.8
3.3
2.4
1.9
DIN
Rated Voltage
Class
E= 292 mm
AC 3/7.2 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
250
315
355
30 098 13.6.3
30 098 13.10
30 098 13.16
30 098 13.20
30 098 13.25
30 098 13.31.5
30 098 13.40
30 098 13.50
30 099 13.63
30 099 13.80
30 099 13.100
30 099 13.125
30 100 13.160
30 100 14.200
30 100 14.250
30 100 14.315
30 100 14.355
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
63
63
50
50
50
50
10
17
17
13
16
21
27
30
38
47
64
98
124
146
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
800
1 000
1 260
1 420
178.0
113.0
50.0
27.0
21.0
17.0
13.0
9.3
6.8
4.8
3.8
3.3
2.3
1.9
1.6
1.2
1.1
10
17
17
13
16
21
27
30
38
47
64
98
103
134
191
281
336
Pre-arcing
I2t-value
Total I2t-value
@ 3 kV
@ 7.2 kV
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
230 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
480 000
Pre-arcing
I2t-value
HHD
[A2s]
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
704 000
Total I2t-value
@ 3 kV
@ 7.2 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
230 000
371000
545 000
825 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
480 000
750 000
1 066 000
1 420 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
704 000
1 101 000
1 616 000
2 225 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
www.siba.de
HHD 23
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 442 mm
AC 3/7.2 kV
Back-up
Rated
Current
Part No.
[A]
100
125
160
200
250
315
355
400
500
30 109 13.100
30 109 13.125
30 110 13.160
30 110 14.200
30 110 14.250
30 110 14.315
30 110 14.355
30 110 14.400
30 110 14.500
Rated
Breaking
Current
[kA]
63
63
63
50
50
50
50
50
50
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
320
390
600
800
1.000
1.260
1.420
1.600
2.000
3.8
3.3
2.3
2.1
1.8
1.5
1.3
1.1
0.85
64
98
85
155
233
281
320
347
430
Pre-arcing
I2t-value
Total I2t-value
@ 3 kV
@ 7.2 kV
[A2s]
[A2s]
[A2s]
33 000
47 000
90 000
230 000
371 000
545 000
825 000
1 000 000
1 668 000
130 000
180 000
330 000
480 000
750 000
1 066 000
1 420 000
1 900 000
3 162 000
210 000
390 000
570 000
704 000
1 101 000
1 616 000
2 225 000
2 528 000
4 500 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
HHD 24
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 192 mm
AC 6/12 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
30 119 13.6.3
30 119 13.10
30 119 13.16
30 267 13.20
30 267 13.25
30 267 13.31.5
30 267 13.40
30 267 13.50
30 267 13.63
Rated
Breaking
Current
[kA]
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
63
63
63
63
63
63
63
63
63
22
34
56
70
90
110
140
170
210
297
189
87
46
36
29
22
16
12
DIN
Rated Voltage
Class
E= 292 mm
AC 6/12 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
30 004 13.6.3
30 004 13.10
30 004 13.16
30 004 13.20
30 004 13.25
30 004 13.31.5
30 004 13.40
30 004 13.50
30 012 13.63
30 012 13.80
30 012 13.100
30 012 13.125
30 020 13.160
30 020 14.200
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
63
63
50
16
28
28
23
29
38
50
56
63
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
800
297.0
189.0
84.0
45.0
34.0
28.0
22.0
16.0
12.0
8.5
6.5
5.5
3.9
3.0
16
28
28
23
29
38
50
56
63
76
104
159
173
234
Pre-arcing
I2t-value
HHD
Total I2t-value
@ 6 kV
@ 12 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
Pre-arcing
I2t-value
Total I2t-value
@ 6 kV
@ 12 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
230 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
480 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
704 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
www.siba.de
HHD 25
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 442 mm
AC 6/12 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
200
250
30 101 13.6.3
30 101 13.10
30 101 13.16
30 101 13.20
30 101 13.25
30 101 13.31.5
30 101 13.40
30 101 13.50
30 102 13.63
30 102 13.80
30 102 13.100
30 102 13.125
30 103 13.160
30 103 14.200
30 103 14.250
Rated
Breaking
Current
[kA]
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
63
63
63
63
63
63
63
63
63
63
63
63
63
50
50
22
34
56
70
90
110
140
170
210
280
320
390
600
800
1 000
297.0
189.0
87.0
46.0
36.0
29.0
22.0
16.0
12.0
8.5
6.5
5.5
3.9
2.9
2.6
DIN
Rated Voltage
Class
E= 537 mm
AC 6/12 kV
Back-up
Rated
Current
Part No.
[A]
100
125
160
200
250
315
30 211 13.100
30 211 13.125
30 211 13.160
30 211 14.200
30 211 14.250
30 211 14.315
Rated
Breaking
Current
[kA]
63
63
63
50
50
50
16
28
19
22
28
37
48
54
58
70
96
147
172
193
269
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
320
390
600
800
1 000
1 260
6.5
5.5
3.9
3.2
2.6
2.2
96
147
172
193
274
382
Pre-arcing
I2t-value
Total I2t-value
@ 6 kV
@ 12 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
230 000
371 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
480 000
750 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
704 000
1 101 000
Pre-arcing
I2t-value
Total I2t-value
@ 6 kV
@ 12 kV
[A2s]
[A2s]
[A2s]
33 000
47 000
90 000
230 000
371000
545 000
130 000
180 000
330 000
480 000
750 000
1 066 000
210 000
390 000
570 000
704 000
1 101 000
1 616 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
HHD 26
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 292 mm
AC10/17.5 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
30 255 13.6.3
30 255 13.10
30 255 13.16
30 221 13.20
30 221 13.25
30 221 13.31.5
30 221 13.40
30 221 13.50
30 222 13.63
30 222 13.80
30 222 13.100
30 222 13.125
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
63
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
397.0
252.0
116.0
62.0
48.0
39.0
29.0
21.0
16.0
11.0
8.7
7.5
DIN
Rated Voltage
Class
E= 367 mm
AC 10/17.5 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 176 13.6.3
30 176 13.10
30 176 13.16
30 176 13.20
30 176 13.25
30 177 13.31.5
30 177 13.40
30 177 13.50
30 177 13.63
30 178 13.80
30 178 13.100
30 178 13.125
30 178 13.160
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
63
63
21
38
37
40
56
65
84
101
106
137
182
235
Minimum
Cold
Power
Breaking Resistance Loss
Current
[A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
397.0
252.0
116.0
62.0
48.0
39.0
29.0
21.0
16.0
11.0
8.7
7.5
5.5
21
38
37
40
56
65
84
101
106
137
182
235
200
Pre-arcing
I2t-value
HHD
Total I2t-value
@ 10 kV
@ 17.5 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
Pre-arcing
I2t-value
Total I2t-value
@ 10 kV
@ 17.5 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
www.siba.de
HHD 27
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 442 mm
AC 10/17.5 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 231 13.6.3
30 231 13.10
30 231 13.16
30 231 13.20
30 231 13.25
30 231 13.31.5
30 231 13.40
30 232 13.50
30 232 13.63
30 232 13.80
30 233 13.100
30 233 13.125
30 233 13.160
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
63
63
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
397.0
252.0
116.0
62.0
48.0
39.0
29.0
21.0
16.0
11.0
8.7
7.5
5.2
21
38
37
42
56
60
84
101
106
137
182
235
290
Pre-arcing
I2t-value
Total I2t-value
@ 10 kV
@ 17.5 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
HHD 28
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 292 mm
AC 10/24 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
30 180 13.6.3
30 180 13.10
30 180 13.16
30 225 13.20
30 225 13.25
30 225 13.31.5
30 225 13.40
30 225 13.50
30 225 13.63
Rated
Breaking
Current
[kA]
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
546
347
160
86
66
53
41
29
21
DIN
Rated Voltage
Class
E= 442 mm
AC 10/24 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 006 13.6.3
30 006 13.10
30 006 13.16
30 006 13.20
30 006 13.25
30 006 13.31.5
30 006 13.40
30 014 13.50
30 014 13.63
30 014 13.80
30 022 13.100
30 022 13.125
30 022 13.160
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
40
31.5
29
52
59
46
56
72
106
108
132
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
546
347
151
83
62
52
41
29
22
16
13
11
8
29
52
59
46
56
72
106
108
132
174
234
320
381
Pre-arcing
I2t-value
HHD
Total I2t-value
@ 10 kV
@ 24 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1,050
1,700
2,900
5,700
10,700
210
350
1,100
2,900
4,700
6,600
12,000
20,000
40,000
360
560
2,000
4,800
7,500
12,000
19,000
33,000
66,000
Pre-arcing
I2t-value
Total I2t-value
@ 10 kV
@ 24 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1.050
1.700
2.900
5.700
10.700
21.000
33,000
47,000
90,000
210
350
1.100
2.900
4.700
6.600
12.000
20.000
40.000
78.000
130,000
180,000
330,000
360
560
2.000
4.800
7.500
12.000
19.000
33.000
66.000
140.000
210,000
390,000
570,000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
www.siba.de
HHD 29
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 537 mm
AC 10/24 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
125
160
30 203 13.6.3
30 203 13.10
30 203 13.16
30 203 13.20
30 203 13.25
30 203 13.31.5
30 203 13.40
30 204 13.50
30 204 13.63
30 204 13.80
30 196 13.100
30 196 13.125
30 196 13.160
Rated
Breaking
Current
[kA]
63
63
63
63
63
63
63
63
63
63
63
40
31.5
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
280
320
390
600
546.0
347.0
160.0
86.0
66.0
53.0
43.0
29.0
21.0
16.0
13.0
11.0
8.0
29
52
57
45
55
70
103
101
121
147
240
320
381
Pre-arcing
I2t-value
Total I2t-value
@ 10 kV
@ 24 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
47 000
90 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
180 000
330 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
390 000
570 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
HHD 30
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 442 mm
AC 20/36 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
30 181 13.6.3
30 181 13.10
30 181 13.16
Rated
Breaking
Current
[kA]
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
20
20
20
22
34
56
819
521
241
DIN
Rated Voltage
Class
E= 537 mm
AC 20/36 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
80
100
30 008 13.6.3
30 008 13.10
30 008 13.16
30 008 13.20
30 008 13.25
30 016 13.31.5
30 016 13.40
30 024 13.50
30 024 13.63
30 024 13.80
30 024 13.100
Rated
Breaking
Current
[kA]
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
40
40
40
40
40
40
40
40
40
40
40
22
34
56
70
90
110
140
170
210
280
320
819
521
241
129
99
80
60
44
32
23
21
DIN
Rated Voltage
Class
E= 537 mm
AC 38.5 kV
Back-up
Rated
Current
Part No.
[A]
6.3
10
16
20
25
31.5
40
50
63
30 337 13.6.3
30 337 13.10
30 338 13.16
30 338 13.20
30 338 13.25
30 338 13.31.5
30 339 13.40
30 339 13.50
30 339 13.63
Rated
Breaking
Current
[kA]
40
40
40
40
40
40
40
40
40
44
78
74
44
78
79
66
87
102
144
186
224
280
408
Minimum
Cold
Power
Breaking Resistance Loss
Current
A]
[mOhm]
[W]
22
34
56
70
90
110
140
170
210
943
590
293
148
114
93
70
51
30
51
86
85
76
100
108
152
196
236
Pre-arcing
I2t-value
HHD
Total I2t-value
@ 20 kV
@ 36 kV
[A2s]
[A2s]
[A2s]
45
75
250
210
350
1 100
360
560
3 000
Pre-arcing
I2t-value
Total I2t-value
@ 20 kV
@ 36 kV
[A2s]
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
21 000
33 000
210
350
1 100
2 900
4 700
6 600
12 000
20 000
40 000
78 000
130 000
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
140 000
210 000
Pre-arcing
I2t-value
Total I2t-value
@ 38.5 kV
[A2s]
[A2s]
45
75
250
640
1 050
1 700
2 900
5 700
10 700
360
560
2 000
4 800
7 500
12 000
19 000
33 000
66 000
Time-current characteristics and cut-off current diagram
please refer to pages HHD 33 and HHD 35
www.siba.de
HHD 31
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
DIN
Rated Voltage
Class
E= 292 mm
AC 6/12 kV
General-Purpose
Rated
Current
[A]
6.3
8
10
16
20
25
31.5
40
50
63
80
100
Part No.
30 004 93.6.3
30 012 93.8
30 012 93.10
30 012 93.16
30 012 93.20
30 012 93.25
30 012 93.31.5
30 012 93.40
30 020 93.50
30 020 93.60
30 020 93.80
30 020 93.100
Breaking
Cold
Power
Current Resistance Loss
[kA]
[mOhm]
[W]
63
63
63
63
63
63
63
63
63
63
63
63
150
120
100
40
31
25
20
16
15
12
9
7.7
7
9
12
12
15
18
23
29
42
54
79
108
Pre-arcing
I2t-value
[A2s]
Total I2t-value
@ 12 kV
[A2s]
110
180
240
530
850
1 330
2 100
3 400
5 500
8 500
16 200
23 500
900
1 400
2 000
4 400
7 000
11 000
18 000
28 000
33 000
68 000
142 000
183 000
DIN
Rated Voltage
Class
E= 442 mm
AC 10/24 kV
General-Purpose
Rated
Current
[A]
6.3
8
10
16
20
25
31.5
40
Part No.
30 006 93.6.3
30 014 93.8
30 014 93.10
30 014 93.16
30 014 93.20
30 014 93.25
30 022 93.31.5
30 022 93.40
Breaking
Cold
Power
Current Resistance Loss
[kA]
[mOhm]
[W]
40
40
40
40
40
40
40
40
273
220
180
70
55
45
41
33
13
17
22
19
27
38
54
77
Pre-arcing
I2t-value
[A2s]
Total I2t-value
@ 24 kV
[A2s]
110
180
240
530
850
1 330
2 100
3 400
900
1 400
2 000
4 400
7 000
11 000
18 000
28 000
Time-current characteristics and cut-off current diagram
please refer to page HHD 36
HHD 32
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
Time-Current Characteristics
Minimum Melting
HHD
Back-up
Virtual Pre-arcing Time
t(s)
RMS Prospective Current
I(A)
Time-Current Characteristics
Total Clearing
Back-up
Virtual Pre-arcing Time
t(s)
RMS Prospective Current
www.siba.de
I(A)
HHD 33
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
Time-Current Characteristics
Minimum Melting
Back-up
Virtual Pre-arcing Time
t(s)
RMS Prospective Current
I(A)
Time-Current Characteristics
Total Clearing
Back-up
Virtual Pre-arcing Time
t(s)
RMS Prospective Current
HHD 34
I(A)
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
Cut-Off Current Diagram
HHD
Back-up
Cut-off Current Peak
Îc
(kA)
Prospective Short Circuit Current
I(kA)
Cut-Off Current Diagram
Back-up
Cut-off Current Peak
Îc
(kA)
Prospective Short Circuit Current
www.siba.de
I(kA)
HHD 35
HHD
Electrical Characteristics
SICHERUNGEN/FUSES
Time-Current Characteristics
General-Purpose
Virtual Pre-arcing Time
t(s)
RMS Prospective Current
I(A)
Cut-Off Current Diagram
General-Purpose
Cut-off Current Peak
Îc
(kA)
Prospective Short Circuit Current
HHD 36
I(kA)
www.siba.de
Electrical Characteristics
SICHERUNGEN/FUSES
HHD
HV Fuse-link
Vertical Cross Section
Weather resistant label
Integrated temperature limiter
Sealing compound
Shaped cap
Melting element support
Thermal Zone
(at General-purpose fuse only)
Ceramic insulating tube
Silver melting element
welded to contact strap
Connecting straps fastened to
contact cap by resistance welding
Force / Distance Diagram
80 N
120 N
Quartz sand
mm
www.siba.de
mm
HHD 37
HHD
SICHERUNGEN/FUSES
Recommendation for the Protection of Main Transformer
with HV-Fuse-links DIN Standard
Protection using LV-Fuse-links*
Operating Class gG / gL on the Low Voltage Site
Transformer
Rated Capacity
[kVA]
6 - 7.2
50
100
125
160
200
250
315
400
500
630
800
1 000
1 250
1 600
2 000
10 - 16
20 - 31.5
25 - 40
31.5 - 50
40 - 63
50 - 80
63 - 100
80 - 100
100 - 125
125 - 160
160
160 - 200
250
2 x 160
2 x 200
Line Voltage [kV]
10 - 12
20 - 24
Rated Current of the HV-Fuse [A]
10
16 - 20
16 - 25
20 - 31.5
25 - 40
31.5 - 50
40 - 50
50 - 80
63 - 80
80 - 125
100 - 125
125 - 160
160
200
250
6.3
10
10 - 16
16 - 20
16 - 20
20 - 25
20 - 25
25 - 40
31.5 - 50
40 - 63
63
63 - 80
80
100
125
Type A
30 - 36
LV-Fuse
gG / gL
[A]
4 - 6.3
6.3 - 10
10
10 - 16
16
16 - 20
20 - 25
20 - 25
25 - 31.5
31.5 - 40
40 - 50
40 - 50
50
63
80
63
125
160
200
250
315
400
500
630
800
1 000
1 250
–
–
–
* Use of the recommended HV fuse-links in connection with LV fuse-links of other manufacturer must be checked before installation
TYPE A
SIBA HV
SIBA
LV - gG / gL
SIBA LV - gG / gL
HHD 38
www.siba.de
SICHERUNGEN/FUSES
HHD
Recommendation for the Protection of Main Transformer
with HV-Fuse-links DIN Standard
Protection without using a common LV-Fuse-link on the Low Voltage Side;
the individual Cable exits are protected with a LV-Fuse-link
Operating Class gG / gL
Transformer
Rated Capacity
[kVA]
6 - 7.2
10 - 12
Line Voltage [kV]
15 - 17.5
20 - 24
Rated Current of the HV-Fuse [A]
50
100
125
160
200
250
315
400
500
630
800
1 000
1 250
1 600
2 000
10 - 16
16 - 31.5
20 - 40
31.5 - 50
31.5 - 63
40 - 80
50 - 100
63 - 100
80 - 125
100 - 160
125 - 160
160 - 200
250
2 x 160
2 x 200
10
16 - 25
16 - 31.5
20 - 31.5
25 - 40
25 - 40
31.5 - 50
40 - 63
50 - 80
63 - 100
80 - 125
100 - 160
160
200
250
6.3 - 10
16
20
20 - 25
20 - 31.5
25 - 31.5
31.5
31.5 - 50
31.5 - 63
40 - 80
63 - 100
63 - 100
100
125
160
6.3
10
10 - 16
16 - 20
16 - 20
16 - 25
16 - 25
20 - 40
25 - 50
31.5 - 63
40 - 63
50 - 80
80
100
125
Type B
30 - 36
4 - 6.3
6.3 - 10
6.3 - 10
10 - 16
10 - 16
10 - 20
16 - 25
16 - 25
20 - 31.5
20 - 40
25 - 50
31.5 - 50
50
63
80
TYPE B
SIBA HV
SIBA LV - gG / gL
www.siba.de
HHD 39
HHD
SICHERUNGEN/FUSES
Application Recommendation for Protection of Capacitors
with HV-Fuse-links DIN Standard
Assignment of Rated Currents of HV-Fuse-links
acc. DIN Standard to Capacitor Rated Capacities
Capacitor
Rated Capacity
[kVA]
6 - 7.2
50
100
200
250
300
400
500
750
1 000
1 250
1 600
2 000
10
20
40
50
63
80
100
160
200
250
315
315
Line Voltage [kV]
10 - 12
20 - 24
Rated Current of the HV-Fuse [A]
6.3
10
20
25
31.5
40
50
80
100
125
160
200
6.3
6.3
10
16
16
20
25
40
50
63
80
100
To control the occuring voltage during switch off Fuse link should be chosen from the next higher voltage range.
e.g. 10 kV Capacitor with 20 kV Fuse links. (See also IEC 549, Chapter II, § 3.2)
HHD 40
www.siba.de
SICHERUNGEN/FUSES
HHD
HV-Fuse-bases for Indoor Application
Rated Voltage 7.2 kV
Part No. 31 001 02
A
B
C
D
E
F
G
H
I
J
K
L
13.78 ” (350 mm)
1.38 ” (35 mm)
3.35 ” (85 mm)
0.70 ” (18 mm)
7.60 ” (193 mm)
6.14 ” (156 mm)
12.20 ” (310 mm)
9.53 ” (242 mm)
0.60 ” (15 mm)
2.17 ” (55 mm)
1.38 ” (35 mm)
14.96 ” (380 mm)
Rated Voltage 12 kV
Part No. 31 003 02
Rated Voltage 24 kV
Part No. 31 005 02
Rated Voltage 36 kV
Part No. 31 007 02
Rated Voltage 24 kV
Part No. 31 221 01*
A
B
C
D
E
F
G
H
I
J
17.72 ” (450 mm)
1.38 ” (35 mm)
3.35 ” (85 mm)
0.70 ” (18 mm)
11.54 ” (293 mm)
6.14 ” (156 mm)
16.14 ” (410 mm)
9.53 ” (242 mm)
0.60 ” (15 mm)
7.10 ” (180 mm)
A
B
C
D
E
F
G
H
I
J
23.62 ” (600 mm)
1.38 ” (35 mm)
3.35 ” (85 mm)
0.70 ” (18 mm)
17.44 ” (443 mm)
9.30 ” (236 mm)
22.60 ” (574 mm)
12.68 ” (322 mm)
0.60 ” (15 mm)
11.80 ” (300 mm)
A
B
C
D
E
F
G
H
I
J
27.36 ” (695 mm)
1.38 ” (35 mm)
3.35 ” (85 mm)
0.70 ” (18 mm)
21.18 ” (538 mm)
12.83 ” (326 mm)
26.60 ” (676 mm)
16.22 ” (412 mm)
0.60 ” (15 mm)
14.96 ” (380 mm)
A
B
C
D
E
F
G
H
I
J
17.72 ” (450 mm)
1.38 ” (35 mm)
3.35 ” (85 mm)
0.70 ” (18 mm)
11.54 ” (293 mm)
9.30 ” (236 mm)
16.14 ” (410 mm)
12.68 ” (322 mm)
0.60 ” (15 mm)
7.10 ” (180 mm)
L
18.90 ” (480 mm)
L
24.80 ” (630 mm)
L
28.54 ” (725 mm)
L
18.90 ” (480 mm)
* Reduced Length for 24 kV
Fuse-links E= 292 mm
www.siba.de
HHD 41
HHD
SICHERUNGEN/FUSES
HV-Fuse-bases for Outdoor Application
Rated Voltage 7.2 kV
Part No. 31 002 01
A
B
C
D
E
F
G
H
I
J
K
L
N
O
P
HHD 42
13.78 ” (350 mm)
1.38 ” (35 mm)
4.72 ” (120 mm)
0.80 ” (20 mm)
7.60 ” (193 mm)
9.33 ” (237 mm)
16.14 ” (410 mm)
12.80 ” (325 mm)
0.60 ” (15 mm)
2.17 ” (55 mm)
1.38 ” (35 mm)
14.96 ” (380 mm)
3.15 ” (80 mm)
0.43 ” (11 mm)
14.57 ” (370 mm)
Rated Voltage 12 kV
Part No. 31 004 01
Rated Voltage 24 kV
Part No. 31 006 01
Rated Voltage 36 kV
Part No. 31 008 01
A
B
C
D
E
F
G
H
I
J
17.72 ” (450 mm)
1.38 ” (35 mm)
4.72 ” (120 mm)
0.80 ” (20 mm)
11.54 ” (293 mm)
9.33 ” (237 mm)
20.08 ” (510 mm)
12.80 ” (325 mm)
0.60 ” (15 mm)
7.10 ” (180 mm)
A
B
C
D
E
F
G
H
I
J
23.62 ” (600 mm)
1.38 ” (35 mm)
4.72 ” (120 mm)
0.80 ” (20 mm)
17.44 ” (443 mm)
12.10 ” (307 mm)
25.98 ” (660 mm)
15.55 ” (395 mm)
0.60 ” (15 mm)
11.80 ” (300 mm)
A
B
C
D
E
F
G
H
I
J
27.36 ” (695 mm)
1.38 ” (35 mm)
4.72 ” (120 mm)
0.80 ” (20 mm)
21.18 ” (538 mm)
15.24 ” (387 mm)
30.90 ” (785 mm)
18.70 ” (475 mm)
0.60 ” (15 mm)
14.96 ” (380 mm)
L
N
O
P
18.90 ” (480 mm)
3.15 ” (80 mm)
0.43 ” (11 mm)
18.50 ” (470 mm)
L
N
O
P
24.80 ” (630 mm)
3.15 ” (80 mm)
0.43 ” (11 mm)
24.40 ” (620 mm)
L
N
O
P
28.54 ” (725 mm)
3.15 ” (80 mm)
0.43 ” (11 mm)
29.33 ” (745 mm)
www.siba.de
HHD
SICHERUNGEN/FUSES
Micro Switch Fitting to HV-Fuse-bases
L= 660 mm
L= 900 mm
L= 250 mm
L= 1200 mm
Part No.
31 001 10
31 001 14
31 001 16
31 001 17
The SIBA microswitch installation set for high voltage fuse-bases, allows supervision of the switching status of high voltage fuse-links. By means of a flexible bowden drive, the movement of the
fuse-link striker will be transferred to a microswitch. The microswitch itself has a change over
contact and is suitable for 250 V AC, 6 A.
The fitting accessories of this installation set match with the bolting holes of SIBA high
voltage fuse-bases. Therefore, when such microswitch systems are added to SIBA high voltage
fuse-bases later on, no additional drillings have to be done. Adaption to fuses-bases of other
manufacturers is, however, possible. Furthermore, the set can also be fitted if only SIBA spring
clip contacts part no. 3400201 are used, and not a complete fuse-base.
Depending on the service voltage of the high voltage fuse-link, the microswitch can be fitted within a maximum distance of ”L” from the fuse-link. A minimum radius of the flexible bowden drive
of 250 mm has to be observed.
If the panel builder only uses the spring clip contact part no. 3100302.20 (see catalogue HHD
page 47), the spacer part no. 3100201.3 must be used instead of the connection tag part no.
3100302.2.
Micro switch
Part No. 28 001 04
250 V / 6 A
1 change over contact
Flexible
Cable
Connection bar
of the
spring clip contact
Part No. 34 002 01
HV-Fuse-cap
www.siba.de
HHD 43
HHD
SICHERUNGEN/FUSES
Fuse-Clip
HV-Spring Clip Contact with Connection Bar
Rated Fuse Current
≤ 200 A
Part No.
34 002 01
A
B
F
G
H
L
M
1.38 ”
1.26 ”
0.24 ”
2.80 ”
3.74 ”
3.66 ”
M 10
(35 mm)
(32 mm)
(6 mm)
(71.5 mm)
(95 mm)
(93 mm)
Fuse-Clip
HV-Spring Clip Contact with Connection Bar
Rated Fuse Current
> 200 A
Part No.
34 001 02
A
B
F
G
H
L
M
1.38 ”
1.26 ”
0.24 ”
2.90 ”
4.92”
3.66 ”
M 10
(35 mm)
(32 mm)
(6 mm)
(73.5 mm)
(125 mm)
(93 mm)
Spacer
Part No.
34 002 01.3
A
B
C
D
E
F
G
1.26 ”
1.38 ”
0.24 ”
0.40 ”
0.20 ”
0.70 ”
0.26 ”
HHD 44
(32 mm)
(35 mm)
(6 mm)
(10,5 mm)
(5 mm)
(18 mm)
(6.5 mm)
www.siba.de
SICHERUNGEN/FUSES
HHD
24 kV Extension Adapter for High Voltage Fuses 12kV
Part No.
34 006 01
A
B
C
D
F
G
H
L
1.77 ”
0.06 ”
2.00 ”
1.73 ”
1.77 ”
0.20 ”
2.76 ”
7.28 ”
(45 mm)
(1.5 mm)
(51 mm)
(44 mm)
(45 mm)
(5 mm)
(70 mm)
(185 mm)
A
E1
E2
F
L
1.77 ” (45 mm)
11.50 ” (292 mm)
17.40 ” (442 mm)
1.30 ” (33 mm)
20.00 ” (508 mm)
HV-Fuse with 24 kV Extension Adapter
www.siba.de
HHD 45
00
HHD
SICHERUNGEN/FUSES
Test-Fuse
With Time Delayed Release
For Testing the Release Mechanism in Enclosed Medium Voltage Switchgear
Part No.
33 010 03
1.77 ” (45 mm)
2.76 ” (70 mm)
7.56 ” (192 mm)
1.34 ” (34 mm)
0.30 ” (8 mm)
1.06 ” (27 mm)
10.24 ” (260 mm)
Force (N)
A
D
E
F
G
H
L
Clamp lever
for timer
To change E an adaptor is available
from 192 mm to 292 mm Part No. 34 004 02
from 192 mm to 442 mm Part No. 34 006 02
Travel (mm)
HHD 46
www.siba.de
SICHERUNGEN/FUSES
HV-Contact Clip
Rated Fuse Current
≤200 A
HHD
For Indoor and Outdoor Application
Part No.
31 003 02.20
B
G
H
HV-Contact Clip
Rated Fuse Current
> 200 A
1.26 ” (32 mm)
2.80 ” (71.5 mm)
3.74 ” (95 mm)
For Indoor and Outdoor Application
Part No.
34 001 01.20
B
G
H
www.siba.de
1.26 ” (32 mm)
2.90 ” (73.5 mm)
4.92 ” (125 mm)
HHD 47
00
HHD
SICHERUNGEN/FUSES
Storage Holder
for HV- and LV-Fuse-links
Rated
Voltage
[kV]
Part No.
12
24
36
33 004 01
33 006 01
33 008 01
HHD 48
HV-Fuses
LV-Fuses
[Pieces]
[Pieces]
3
3
3
6
6
6
L
B
T
Weight
[inch] [mm] [inch] [mm] [inch] [mm]
11.96 304 16.06 408
17.87 454 16.06 408
21.65 550 16.06 408
4.13
4.13
4.13
105
105
105
[kg/1]
1.0
1.4
1.9