SICHERUNGEN/FUSES High Voltage Fuses German DIN Standard HHD For Air & Gas Insulated Switchgear Indoor and Outdoor Application The striker pin system is connected by means of a high resistance parallel conductor. After melting the main fuse elements, the striker pin indicates the operating status of the fuse and actuates a microswitch for remote indication, and/or triggers a load break switch or a circuit breaker to open. The temperature limiting function of the fuse striker pin Design and construction SIBA HV Fuse-links have parallel connected pure silver fuse-elements. The design and method of production of the elements ensure narrow tolerances of time-curren characteristics. The fuse elements are wound on a ceramic support and are attached to the silver plated connection caps by means of spot-welding. The connection caps are fitted inside the silver plated copper end caps by spot welding. The copper end caps themselves are press-fitted onto the porcelain tube, which is glazed inside and outside. The end caps are mechanically fixed to the porcelain tube and additionally sealed by a durable elastic sealing medium. This sealing method has been proven over many decades of positive field experience and ensures tightness against ingress of humidity. Striker pin SIBA HV Fuse-links are available with striker pins of force: • 80 N (Part No. 30 … 13 for basic-type) and • 120 N (Part No. 30 … 14 for variant-type) The characteristics of both striker pins correspond to IEC 60282-1, VDE 0670 Part 4, and are of the energycategory “medium”. www.siba.de SIBA HV Fuse-links up to and including 160 A with a striker pin of 80 N are equipped with an integrated temperature limiter as standard. The temperature limiter is fitted inside the striker pin system. The SIBA striker pin system therefore includes the following functions: • thermal protection of adjacent equipment, especially SF6 insulated switchgear • limitation of failure current at the overload region • improved properties for the switch-fuse combinations according to IEC 62271-105 The integrated temperature limiter avoids unacceptably high temperatures – no matter why they are generated – in gas-insulated switchgear or narrow switchgears enclosures. By means of a melting activator, temperatures inside the fuse link enclosure are limited to below 100°C. This design especially considers continuity of current supply for the end user for as long as possible. The system reacts in such a way that short time overloads do not cause the fuse to interrupt the circuit unnecessarily. Only when inadmissible values are exceeded, the fuse will open the switch via the striker pin. Higher temperatures on plastic fuse enclosures in SF6insulated switchgear can be caused by: • selection of a fuse rating too low for proper transformer protection • fuses loaded with fault currents below the minimum breaking current • deterioration of fuse links caused by transient fault currents (e.g. lightning strike) • transformer fault currents (e.g. winding short-circuit) • additional temperature rise because of poor clip fitting Fuse-links with an integrated temperature limiter are compatible with standard fuse links. All coordination schedules can be used. Further information on our temperature limiter, design and construction, can be obtained from our website: www.siba.de HHD 1 HHD SICHERUNGEN/FUSES High Voltage Fuses German DIN Standard For Air & Gas Insulated Switchgear Indoor and Outdoor Application Selection Guide Rated Voltage AC [kV] 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 DIN Size E [mm] 192 * 192 * 192 * 192 * 292 292 292 292 442 442 442 192 192 292 * 292 * 292 * 292 * 442 442 442 442 537 537 292 292 292 367 * 367 * 367 * 367 * 442 442 442 Class Part No. Selection Guide [Page] Techn. Data [Page] Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up 30 002 13 30 010 13 30 018 13 30 018 14 30 098 13 30 099 13 30 100 13 30 100 14 30 109 13 30 110 13 30 110 14 30 119 13 30 267 13 30 004 13 30 012 13 30 020 13 30 020 14 30 101 13 30 102 13 30 103 13 30 103 14 30 211 13 30 211 14 30 255 13 30 221 13 30 222 13 30 176 13 30 177 13 30 178 13 30 178 14 30 231 13 30 232 13 30 233 13 HHD 5 HHD 5 HHD 5 HHD 5 HHD 6 HHD 6 HHD 6 HHD 6 HHD 7 HHD 7 HHD 7 HHD 8 HHD 8 HHD 9 HHD 9 HHD 9 HHD 9 HHD 10 HHD 10 HHD 10 HHD 10 HHD 11 HHD 11 HHD 12 HHD 12 HHD 12 HHD 13 HHD 13 HHD 13 HHD 13 HHD 14 HHD 14 HHD 14 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 24 HHD 24 HHD 24 HHD 25 HHD 25 HHD 25 HHD 25 HHD 25 HHD 25 HHD 26 HHD 26 HHD 26 HHD 26 HHD 26 HHD 26 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 28 HHD 28 HHD 28 * Standard size HHD 2 www.siba.de SICHERUNGEN/FUSES High Voltage Fuses German DIN Standard HHD For Air & Gas Insulated Switchgear Indoor and Outdoor Application Selection Guide Rated Voltage AC [kV] 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 38,5 38,5 38,5 6/12 6/12 6/12 10/24 10/24 10/24 *Standard size DIN Size E [mm] 292 292 442 * 442 * 442 * 537 537 537 537 442 537 * 537 * 537 * 537 537 537 292 292 292 442 442 442 Class Part No. Selection Guide [Page] Techn. Data [Page] Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up Back-up General-purpose General-purpose General-purpose General-purpose General-purpose General-purpose 30 180 13 30 225 13 30 006 13 30 014 13 30 022 13 30 203 13 30 204 13 30 196 13 30 196 14 30 181 13 30 008 13 30 016 13 30 024 13 30 337 13 30 338 13 30 338 13 30 004 93 30 012 93 30 020 93 30 006 93 30 014 93 30 022 93 HHD 15 HHD 15 HHD 16 HHD 16 HHD 16 HHD 17 HHD 17 HHD 17 HHD 17 HHD 18 HHD 19 HHD 19 HHD 19 HHD 19 HHD 19 HHD 19 HHD 21 HHD 21 HHD 21 HHD 22 HHD 22 HHD 22 HHD 29 HHD 29 HHD 29 HHD 29 HHD 29 HHD 30 HHD 30 HHD 30 HHD 30 HHD 31 HHD 31 HHD 31 HHD 31 HHD 31 HHD 31 HHD 31 HHD 32 HHD 32 HHD 32 HHD 32 HHD 32 HHD 32 Selection Guide Fuse-Bases Article Rated Voltage AC [kV] DIN-Size E [mm] Part No. Techn. Data [Page] Indoor Fuse-bases 7.2 12 24 36 24 7.2 12 24 36 192 292 442 537 292 192 292 292 537 31 001 02 31 003 02 31 005 02 31 007 02 31 221 01 31 002 01 31 004 01 31 006 01 31 008 01 HHD 40 HHD 40 HHD 40 HHD 40 HHD 40 HHD 41 HHD 41 HHD 41 HHD 41 Outdoor Fuse-bases www.siba.de HHD 3 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard Selection Guide Microswitch Fitting Article Length Part No. Techn. Data [Page] Contact Clip 31 001 16 31 001 10 31 001 14 31 001 17 34 002 01 HHD 42 HHD 42 HHD 42 HHD 42 HHD 43 Distance Plate 31 002 01.3 HHD 43 [mm] Micro switch 250 660 900 1 200 Selection Guide Accessories Article Rated Voltage [kV] Extension Adapter Test Fuse-link for gas insulated switchgear Contact Clip 200 A indoor and outdoor Contact Clip heavy duty Storage Holder HHD 4 Part No. Techn. Data [Page] 12/24 34 006 01 HHD 44 24 33 010 03 HHD 45 31 003 02.20 HHD 46 34 001 01.20 HHD 46 33 004 01 33 006 01 33 008 01 HHD 47 HHD 47 HHD 47 12 24 36 www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E=192 mm AC 3/7.2 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 30 002 13.6.3 30 002 13.10 30 002 13.16 30 002 13.20 30 002 13.25 30 002 13.31.5 30 002 13.40 30 002 13.50 30 010 13.63 30 010 13.80 30 010 13.100 30 010 13.125 30 018 13.160 30 018 14.200 D = Diameter HHD Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 63 63 63 63 63 63 63 63 63 63 63 63 63 50 Weight 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.9 2.9 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Preferred Standard Size 3/7.2 kV A F O N www.siba.de 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 5 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard A F O N DIN Rated Voltage Class E= 292 mm AC 3/7.2 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 250 315 355 30 098 13.6.3 30 098 13.10 30 098 13.16 30 098 13.20 30 098 13.25 30 098 13.31.5 30 098 13.40 30 098 13.50 30 099 13.63 30 099 13.80 30 099 13.100 30 099 13.125 30 100 13.160 30 100 14.200 30 100 14.250 30 100 14.315 30 100 14.355 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 6 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 50 50 50 50 50 Weight 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 3.8 3.8 3.8 3.8 3.8 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 442 mm AC 3/7.2 kV Back-up Rated Current [A] Part No. 100 125 160 200 250 315 355 400 500 30 109 13.100 30 109 13.125 30 110 13.160 30 110 14.200 30 110 14.250 30 110 14.315 30 110 14.355 30 110 14.400 30 110 14.500 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.64 2.64 3.35 3.35 3.35 3.35 3.35 3.35 3.35 67 67 85 85 85 85 85 85 85 63 63 63 50 50 50 50 50 50 Weight 2.9 2.9 5.4 5.4 5.4 5.4 5.4 5.4 5.4 Pack [kg/1] 1 1 1 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 7 HHD SICHERUNGEN/FUSES High Voltage Fuses German DIN Standard DIN Rated Voltage Class E= 192 mm AC 6/12 kV Back-up Rated Current [A] 6.3 10 16 20 25 31.5 40 50 63 A F O N For Air & Gas Insulated Switchgear Indoor and Outdoor Application 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 8 Part No. 30 119 13.6.3 30 119 13.10 30 119 13.16 30 267 13.20 30 267 13.25 30 267 13.31.5 30 267 13.40 30 267 13.50 30 267 13.63 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 53 53 53 67 67 67 67 67 67 63 63 63 63 63 63 63 63 63 Weight 1.2 1.2 1.2 1.5 1.5 1.5 1.5 1.5 1.5 Pack [kg/1] 1 1 1 1 1 1 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 292 mm AC 6/12 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 30 004 13.6.3 30 004 13.10 30 004 13.16 30 004 13.20 30 004 13.25 30 004 13.31.5 30 004 13.40 30 004 13.50 30 012 13.63 30 012 13.80 30 012 13.100 30 012 13.125 30 020 13.160 30 020 14.200 D = Diameter HHD Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 63 63 63 63 63 63 63 63 63 63 63 63 63 50 Weight 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 3.8 3.8 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Preferred Standard Size 6/12 kV A F O N www.siba.de 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 9 HHD SICHERUNGEN/FUSES High Voltage Fuses German DIN Standard A F O N For Air & Gas Insulated Switchgear Indoor and Outdoor Application DIN Rated Voltage Class E= 442 mm AC 6/12 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 250 30 101 13.6.3 30 101 13.10 30 101 13.16 30 101 13.20 30 101 13.25 30 101 13.31.5 30 101 13.40 30 101 13.50 30 102 13.63 30 102 13.80 30 102 13.100 30 102 13.125 30 103 13.160 30 103 14.200 30 103 14.250 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 10 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 Weight 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 2.9 5.4 5.4 5.4 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated voltage Class E= 537 mm AC 6/12 kV Back-up Rated Current [A] Part No. 100 125 160 200 250 315 30 211 13.100 30 211 13.125 30 211 13.160 30 211 14.200 30 211 14.250 30 211 14.315 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 3.35 3.35 3.35 3.35 3.35 3.35 85 85 85 85 85 85 63 63 63 50 50 50 Weight 6.8 6.8 6.8 6.8 6.8 6.8 Pack [kg/1] 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 11 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard A F O N DIN Rated Voltage Class E= 292 mm AC 10/17.5 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 30 255 13.6.3 30 255 13.10 30 255 13.16 30 221 13.20 30 221 13.25 30 221 13.31.5 30 221 13.40 30 221 13.50 30 221 13.63 30 222 13.80 30 222 13.100 30 222 13.125 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 12 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 67 67 67 67 67 67 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 Weight 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 3.8 3.8 3.8 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 367 mm AC 10/17.5 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 176 13.6.3 30 176 13.10 30 176 13.16 30 176 13.20 30 176 13.25 30 177 13.31.5 30 177 13.40 30 177 13.50 30 177 13.63 30 178 13.80 30 178 13.100 30 178 13.125 30 178 13.160 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 53 53 53 53 53 67 67 67 67 85 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 63 Weight 2.0 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 4.8 4.8 4.8 4.5 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 13 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard A F O N DIN Rated Voltage Class E= 442 mm AC 10/17.5 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 231 13.6.3 30 231 13.10 30 231 13.16 30 231 13.20 30 231 13.25 30 231 13.31.5 30 231 13.40 30 232 13.50 30 232 13.63 30 232 13.80 30 233 13.100 30 233 13.125 30 233 13.160 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 53 53 53 53 67 67 67 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 63 Weight 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 5.4 5.4 5.4 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 1.77 ” (45 mm) 1.30 ” (33 mm) 0.40 ” (10 mm) 1.38 ” (35 mm) HHD 14 www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 292 mm AC 10/24 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 30 180 13.6.3 30 180 13.10 30 180 13.16 30 225 13.20 30 225 13.25 30 225 13.31.5 30 225 13.40 30 225 13.50 30 225 13.63 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 53 53 53 67 67 67 67 67 67 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 Weight 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 Pack [kg/1] 1 1 1 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 15 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 442 mm AC 10/24 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 006 13.6.3 30 006 13.10 30 006 13.16 30 006 13.20 30 006 13.25 30 006 13.31.5 30 006 13.40 30 014 13.50 30 014 13.63 30 014 13.80 30 022 13.100 30 022 13.125 30 022 13.160 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 53 53 53 53 67 67 67 85 85 85 63 63 63 63 63 63 63 63 63 63 63 40 31.5 Weight 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 5.4 5.4 5.4 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 Preferred Standard Size 10/24 kV A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 16 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 537 mm AC 10/24 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 203 13.6.3 30 203 13.10 30 203 13.16 30 203 13.20 30 203 13.25 30 203 13.31.5 30 203 13.40 30 204 13.50 30 204 13.63 30 204 13.80 30 196 13.100 30 196 13.125 30 196 13.160 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 53 53 53 53 67 67 67 85 85 85 63 63 63 63 63 63 63 63 63 63 63 40 31.5 Weight 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.7 3.7 3.7 6.8 6.8 6.8 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 17 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 442 mm AC 20/36 kV Back-up Rated Current [A] 6.3 10 16 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 18 Part No. 30 181 13.6.3 30 181 13.10 30 181 13.16 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 53 53 53 20 20 20 Weight 2.2 2.2 2.2 Pack [kg/1] 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 537 mm AC 20/36 kV Back-up Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 50 63 80 100 30 008 13.6.3 30 008 13.10 30 008 13.16 30 008 13.20 30 008 13.25 30 016 13.31.5 30 016 13.40 30 024 13.50 30 024 13.63 30 024 13.80 30 024 13.100 D = Diameter HHD Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.10 2.10 2.10 2.64 2.64 3.35 3.35 3.35 3.35 53 53 53 53 53 67 67 85 85 85 85 40 40 40 40 40 40 40 40 40 40 40 Weight 2.6 2.6 2.6 2.6 2.6 3.5 3.5 6.0 6.0 6.0 6.0 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 Preferred Standard Size 20/36 kV DIN Rated Voltage Class E= 537 mm AC 38,5 kV Back-up Rated Current [A] 6.3 10 16 20 25 31.5 40 50 63 Part No. 30 337 13.6.3 30 337 13.10 30 338 13.16 30 338 13.20 30 338 13.25 30 338 13.31.5 30 339 13.40 30 339 13.50 30 339 13.63 D = Diameter Standard DIN 43625 · IEC 60282-1 [inch] [mm] Rated Breaking Current [kA] 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 53 53 67 67 67 67 85 85 85 40 40 40 40 40 40 40 40 40 Weight 2.6 2.6 3.5 3.5 3.5 3.5 6.0 6.0 6.0 Pack [kg/1] 1 1 1 1 1 1 1 1 1 A F O N www.siba.de 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 19 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard – General-Purpose According IEC 60 282-1 and VDE 0670 Part 4, a general-purpose fuse interrupts fault currents between the rated breaking current and the current, which causes melting within one hour. The protection range of the SIBA-VS-protector extends this basic demand. The minimum breaking current starts at some rated currents at 1.5 times the rated current. In combination with the temperature released striker pin and the 3pol. trip-free release of the switchgear a full range protection is possible. Additional feature is the small powerloss of the VSProtector. It is up to 40 % lower than the standard DIN-fuse. The VS-Protector for the overload and short-circuit range dimensions of the VS-Protector are according to DIN 43625. The rated voltages 12 and 24 kV and also the available current ratings allow protection of transformers up to 630 kVA. The function of the VS-Protector is compa- rable to a typical back-up fuse-link. The melting elements of pure silver are wound inside onto a ceramic support. A short section in the center of the fuse is designed as a “heat chamber”. Inside this chamber the elements are made of silveralloy. At overload this generates a certain temperature level that brings the fuse to switch off after corresponding time. Below the rated currend the fuse shows an ageing free behaviour also in encapsulated switchgear. HHD 20 www.siba.de SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard DIN Rated Voltage Class E= 292 mm AC 6/12 kV General-Purpose Rated Current [A] Part No. 6.3 8 10 16 20 25 31.5 40 50 63 80 100 30 004 93.6.3 30 012 13.8 30 012 93.10 30 012 93.16 30 012 93.20 30 012 93.25 30 012 93.31.5 30 012 93.40 30 020 93.50 30 020 93.63 30 020 93.80 30 020 93.100 D = Diameter Standard [inch] [mm] Rated Breaking Current [kA] 2.10 2.64 2.64 2.64 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 53 67 67 67 67 67 67 67 85 85 85 85 63 63 63 63 63 63 63 63 63 63 63 63 DIN 43625 · IEC 60282-1 Weight 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 3.8 3.8 3.8 3.8 Pack [kg/1] 1 1 1 1 1 1 1 1 1 1 1 1 A F O N www.siba.de HHD 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 21 HHD SICHERUNGEN/FUSES High Voltage Fuses For Air & Gas Insulated Switchgear Indoor and Outdoor Application German DIN Standard A F O N DIN Rated Voltage Class E= 442 mm AC 10/24 kV General-purpose Rated Current [A] Part No. 6.3 10 16 20 25 31.5 40 30 006 93.6.3 30 014 93.10 30 014 93.16 30 014 93.20 30 014 93.25 30 022 93.31.5 30 022 93.40 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 22 D = Diameter Standard [inch] [mm] Rated Breaking Current [kA] 2.10 2.64 2.64 2.64 2.64 3.35 3.35 53 67 67 67 67 85 85 40 40 40 40 40 40 40 DIN 43625 · IEC 60282-1 Weight 2.2 2.9 2.9 2.9 2.9 5.4 5.4 Pack [kg/1] 1 1 1 1 1 1 1 (45 mm) (33 mm) (10 mm) (35 mm) www.siba.de Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 192 mm AC 3/7.2 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 30 002 13.6.3 30 002 13.10 30 002 13.16 30 002 13.20 30 002 13.25 30 002 13.31.5 30 002 13.40 30 002 13.50 30 010 13.63 30 010 13.80 30 010 13.100 30 010 13.125 30 018 13.160 30 018 14.200 Rated Breaking Current [kA] Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 63 63 63 63 63 63 63 63 63 63 63 63 63 50 22 34 56 70 90 110 140 170 210 280 320 390 600 800 178.0 113.0 50.0 27.0 21.0 17.0 13.0 9.3 6.8 4.8 3.8 3.3 2.4 1.9 DIN Rated Voltage Class E= 292 mm AC 3/7.2 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 250 315 355 30 098 13.6.3 30 098 13.10 30 098 13.16 30 098 13.20 30 098 13.25 30 098 13.31.5 30 098 13.40 30 098 13.50 30 099 13.63 30 099 13.80 30 099 13.100 30 099 13.125 30 100 13.160 30 100 14.200 30 100 14.250 30 100 14.315 30 100 14.355 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 50 50 10 17 17 13 16 21 27 30 38 47 64 98 124 146 Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 800 1 000 1 260 1 420 178.0 113.0 50.0 27.0 21.0 17.0 13.0 9.3 6.8 4.8 3.8 3.3 2.3 1.9 1.6 1.2 1.1 10 17 17 13 16 21 27 30 38 47 64 98 103 134 191 281 336 Pre-arcing I2t-value Total I2t-value @ 3 kV @ 7.2 kV [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 230 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 480 000 Pre-arcing I2t-value HHD [A2s] 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 704 000 Total I2t-value @ 3 kV @ 7.2 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 230 000 371000 545 000 825 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 480 000 750 000 1 066 000 1 420 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 704 000 1 101 000 1 616 000 2 225 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 www.siba.de HHD 23 HHD Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 442 mm AC 3/7.2 kV Back-up Rated Current Part No. [A] 100 125 160 200 250 315 355 400 500 30 109 13.100 30 109 13.125 30 110 13.160 30 110 14.200 30 110 14.250 30 110 14.315 30 110 14.355 30 110 14.400 30 110 14.500 Rated Breaking Current [kA] 63 63 63 50 50 50 50 50 50 Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 320 390 600 800 1.000 1.260 1.420 1.600 2.000 3.8 3.3 2.3 2.1 1.8 1.5 1.3 1.1 0.85 64 98 85 155 233 281 320 347 430 Pre-arcing I2t-value Total I2t-value @ 3 kV @ 7.2 kV [A2s] [A2s] [A2s] 33 000 47 000 90 000 230 000 371 000 545 000 825 000 1 000 000 1 668 000 130 000 180 000 330 000 480 000 750 000 1 066 000 1 420 000 1 900 000 3 162 000 210 000 390 000 570 000 704 000 1 101 000 1 616 000 2 225 000 2 528 000 4 500 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 HHD 24 www.siba.de Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 192 mm AC 6/12 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 30 119 13.6.3 30 119 13.10 30 119 13.16 30 267 13.20 30 267 13.25 30 267 13.31.5 30 267 13.40 30 267 13.50 30 267 13.63 Rated Breaking Current [kA] Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 63 63 63 63 63 63 63 63 63 22 34 56 70 90 110 140 170 210 297 189 87 46 36 29 22 16 12 DIN Rated Voltage Class E= 292 mm AC 6/12 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 30 004 13.6.3 30 004 13.10 30 004 13.16 30 004 13.20 30 004 13.25 30 004 13.31.5 30 004 13.40 30 004 13.50 30 012 13.63 30 012 13.80 30 012 13.100 30 012 13.125 30 020 13.160 30 020 14.200 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 63 63 50 16 28 28 23 29 38 50 56 63 Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 800 297.0 189.0 84.0 45.0 34.0 28.0 22.0 16.0 12.0 8.5 6.5 5.5 3.9 3.0 16 28 28 23 29 38 50 56 63 76 104 159 173 234 Pre-arcing I2t-value HHD Total I2t-value @ 6 kV @ 12 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 Pre-arcing I2t-value Total I2t-value @ 6 kV @ 12 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 230 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 480 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 704 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 www.siba.de HHD 25 HHD Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 442 mm AC 6/12 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 200 250 30 101 13.6.3 30 101 13.10 30 101 13.16 30 101 13.20 30 101 13.25 30 101 13.31.5 30 101 13.40 30 101 13.50 30 102 13.63 30 102 13.80 30 102 13.100 30 102 13.125 30 103 13.160 30 103 14.200 30 103 14.250 Rated Breaking Current [kA] Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 22 34 56 70 90 110 140 170 210 280 320 390 600 800 1 000 297.0 189.0 87.0 46.0 36.0 29.0 22.0 16.0 12.0 8.5 6.5 5.5 3.9 2.9 2.6 DIN Rated Voltage Class E= 537 mm AC 6/12 kV Back-up Rated Current Part No. [A] 100 125 160 200 250 315 30 211 13.100 30 211 13.125 30 211 13.160 30 211 14.200 30 211 14.250 30 211 14.315 Rated Breaking Current [kA] 63 63 63 50 50 50 16 28 19 22 28 37 48 54 58 70 96 147 172 193 269 Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 320 390 600 800 1 000 1 260 6.5 5.5 3.9 3.2 2.6 2.2 96 147 172 193 274 382 Pre-arcing I2t-value Total I2t-value @ 6 kV @ 12 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 230 000 371 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 480 000 750 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 704 000 1 101 000 Pre-arcing I2t-value Total I2t-value @ 6 kV @ 12 kV [A2s] [A2s] [A2s] 33 000 47 000 90 000 230 000 371000 545 000 130 000 180 000 330 000 480 000 750 000 1 066 000 210 000 390 000 570 000 704 000 1 101 000 1 616 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 HHD 26 www.siba.de Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 292 mm AC10/17.5 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 30 255 13.6.3 30 255 13.10 30 255 13.16 30 221 13.20 30 221 13.25 30 221 13.31.5 30 221 13.40 30 221 13.50 30 222 13.63 30 222 13.80 30 222 13.100 30 222 13.125 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 63 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 DIN Rated Voltage Class E= 367 mm AC 10/17.5 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 176 13.6.3 30 176 13.10 30 176 13.16 30 176 13.20 30 176 13.25 30 177 13.31.5 30 177 13.40 30 177 13.50 30 177 13.63 30 178 13.80 30 178 13.100 30 178 13.125 30 178 13.160 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 63 63 21 38 37 40 56 65 84 101 106 137 182 235 Minimum Cold Power Breaking Resistance Loss Current [A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 5.5 21 38 37 40 56 65 84 101 106 137 182 235 200 Pre-arcing I2t-value HHD Total I2t-value @ 10 kV @ 17.5 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 Pre-arcing I2t-value Total I2t-value @ 10 kV @ 17.5 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 www.siba.de HHD 27 HHD Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 442 mm AC 10/17.5 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 231 13.6.3 30 231 13.10 30 231 13.16 30 231 13.20 30 231 13.25 30 231 13.31.5 30 231 13.40 30 232 13.50 30 232 13.63 30 232 13.80 30 233 13.100 30 233 13.125 30 233 13.160 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 63 63 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 5.2 21 38 37 42 56 60 84 101 106 137 182 235 290 Pre-arcing I2t-value Total I2t-value @ 10 kV @ 17.5 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 HHD 28 www.siba.de Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 292 mm AC 10/24 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 30 180 13.6.3 30 180 13.10 30 180 13.16 30 225 13.20 30 225 13.25 30 225 13.31.5 30 225 13.40 30 225 13.50 30 225 13.63 Rated Breaking Current [kA] 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 546 347 160 86 66 53 41 29 21 DIN Rated Voltage Class E= 442 mm AC 10/24 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 006 13.6.3 30 006 13.10 30 006 13.16 30 006 13.20 30 006 13.25 30 006 13.31.5 30 006 13.40 30 014 13.50 30 014 13.63 30 014 13.80 30 022 13.100 30 022 13.125 30 022 13.160 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 40 31.5 29 52 59 46 56 72 106 108 132 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 546 347 151 83 62 52 41 29 22 16 13 11 8 29 52 59 46 56 72 106 108 132 174 234 320 381 Pre-arcing I2t-value HHD Total I2t-value @ 10 kV @ 24 kV [A2s] [A2s] [A2s] 45 75 250 640 1,050 1,700 2,900 5,700 10,700 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 Pre-arcing I2t-value Total I2t-value @ 10 kV @ 24 kV [A2s] [A2s] [A2s] 45 75 250 640 1.050 1.700 2.900 5.700 10.700 21.000 33,000 47,000 90,000 210 350 1.100 2.900 4.700 6.600 12.000 20.000 40.000 78.000 130,000 180,000 330,000 360 560 2.000 4.800 7.500 12.000 19.000 33.000 66.000 140.000 210,000 390,000 570,000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 www.siba.de HHD 29 HHD Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 537 mm AC 10/24 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 125 160 30 203 13.6.3 30 203 13.10 30 203 13.16 30 203 13.20 30 203 13.25 30 203 13.31.5 30 203 13.40 30 204 13.50 30 204 13.63 30 204 13.80 30 196 13.100 30 196 13.125 30 196 13.160 Rated Breaking Current [kA] 63 63 63 63 63 63 63 63 63 63 63 40 31.5 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 280 320 390 600 546.0 347.0 160.0 86.0 66.0 53.0 43.0 29.0 21.0 16.0 13.0 11.0 8.0 29 52 57 45 55 70 103 101 121 147 240 320 381 Pre-arcing I2t-value Total I2t-value @ 10 kV @ 24 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 47 000 90 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 180 000 330 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 390 000 570 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 HHD 30 www.siba.de Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 442 mm AC 20/36 kV Back-up Rated Current Part No. [A] 6.3 10 16 30 181 13.6.3 30 181 13.10 30 181 13.16 Rated Breaking Current [kA] Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 20 20 20 22 34 56 819 521 241 DIN Rated Voltage Class E= 537 mm AC 20/36 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 80 100 30 008 13.6.3 30 008 13.10 30 008 13.16 30 008 13.20 30 008 13.25 30 016 13.31.5 30 016 13.40 30 024 13.50 30 024 13.63 30 024 13.80 30 024 13.100 Rated Breaking Current [kA] Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 40 40 40 40 40 40 40 40 40 40 40 22 34 56 70 90 110 140 170 210 280 320 819 521 241 129 99 80 60 44 32 23 21 DIN Rated Voltage Class E= 537 mm AC 38.5 kV Back-up Rated Current Part No. [A] 6.3 10 16 20 25 31.5 40 50 63 30 337 13.6.3 30 337 13.10 30 338 13.16 30 338 13.20 30 338 13.25 30 338 13.31.5 30 339 13.40 30 339 13.50 30 339 13.63 Rated Breaking Current [kA] 40 40 40 40 40 40 40 40 40 44 78 74 44 78 79 66 87 102 144 186 224 280 408 Minimum Cold Power Breaking Resistance Loss Current A] [mOhm] [W] 22 34 56 70 90 110 140 170 210 943 590 293 148 114 93 70 51 30 51 86 85 76 100 108 152 196 236 Pre-arcing I2t-value HHD Total I2t-value @ 20 kV @ 36 kV [A2s] [A2s] [A2s] 45 75 250 210 350 1 100 360 560 3 000 Pre-arcing I2t-value Total I2t-value @ 20 kV @ 36 kV [A2s] [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 21 000 33 000 210 350 1 100 2 900 4 700 6 600 12 000 20 000 40 000 78 000 130 000 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 140 000 210 000 Pre-arcing I2t-value Total I2t-value @ 38.5 kV [A2s] [A2s] 45 75 250 640 1 050 1 700 2 900 5 700 10 700 360 560 2 000 4 800 7 500 12 000 19 000 33 000 66 000 Time-current characteristics and cut-off current diagram please refer to pages HHD 33 and HHD 35 www.siba.de HHD 31 HHD Electrical Characteristics SICHERUNGEN/FUSES DIN Rated Voltage Class E= 292 mm AC 6/12 kV General-Purpose Rated Current [A] 6.3 8 10 16 20 25 31.5 40 50 63 80 100 Part No. 30 004 93.6.3 30 012 93.8 30 012 93.10 30 012 93.16 30 012 93.20 30 012 93.25 30 012 93.31.5 30 012 93.40 30 020 93.50 30 020 93.60 30 020 93.80 30 020 93.100 Breaking Cold Power Current Resistance Loss [kA] [mOhm] [W] 63 63 63 63 63 63 63 63 63 63 63 63 150 120 100 40 31 25 20 16 15 12 9 7.7 7 9 12 12 15 18 23 29 42 54 79 108 Pre-arcing I2t-value [A2s] Total I2t-value @ 12 kV [A2s] 110 180 240 530 850 1 330 2 100 3 400 5 500 8 500 16 200 23 500 900 1 400 2 000 4 400 7 000 11 000 18 000 28 000 33 000 68 000 142 000 183 000 DIN Rated Voltage Class E= 442 mm AC 10/24 kV General-Purpose Rated Current [A] 6.3 8 10 16 20 25 31.5 40 Part No. 30 006 93.6.3 30 014 93.8 30 014 93.10 30 014 93.16 30 014 93.20 30 014 93.25 30 022 93.31.5 30 022 93.40 Breaking Cold Power Current Resistance Loss [kA] [mOhm] [W] 40 40 40 40 40 40 40 40 273 220 180 70 55 45 41 33 13 17 22 19 27 38 54 77 Pre-arcing I2t-value [A2s] Total I2t-value @ 24 kV [A2s] 110 180 240 530 850 1 330 2 100 3 400 900 1 400 2 000 4 400 7 000 11 000 18 000 28 000 Time-current characteristics and cut-off current diagram please refer to page HHD 36 HHD 32 www.siba.de Electrical Characteristics SICHERUNGEN/FUSES Time-Current Characteristics Minimum Melting HHD Back-up Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Time-Current Characteristics Total Clearing Back-up Virtual Pre-arcing Time t(s) RMS Prospective Current www.siba.de I(A) HHD 33 HHD Electrical Characteristics SICHERUNGEN/FUSES Time-Current Characteristics Minimum Melting Back-up Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Time-Current Characteristics Total Clearing Back-up Virtual Pre-arcing Time t(s) RMS Prospective Current HHD 34 I(A) www.siba.de Electrical Characteristics SICHERUNGEN/FUSES Cut-Off Current Diagram HHD Back-up Cut-off Current Peak Îc (kA) Prospective Short Circuit Current I(kA) Cut-Off Current Diagram Back-up Cut-off Current Peak Îc (kA) Prospective Short Circuit Current www.siba.de I(kA) HHD 35 HHD Electrical Characteristics SICHERUNGEN/FUSES Time-Current Characteristics General-Purpose Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Cut-Off Current Diagram General-Purpose Cut-off Current Peak Îc (kA) Prospective Short Circuit Current HHD 36 I(kA) www.siba.de Electrical Characteristics SICHERUNGEN/FUSES HHD HV Fuse-link Vertical Cross Section Weather resistant label Integrated temperature limiter Sealing compound Shaped cap Melting element support Thermal Zone (at General-purpose fuse only) Ceramic insulating tube Silver melting element welded to contact strap Connecting straps fastened to contact cap by resistance welding Force / Distance Diagram 80 N 120 N Quartz sand mm www.siba.de mm HHD 37 HHD SICHERUNGEN/FUSES Recommendation for the Protection of Main Transformer with HV-Fuse-links DIN Standard Protection using LV-Fuse-links* Operating Class gG / gL on the Low Voltage Site Transformer Rated Capacity [kVA] 6 - 7.2 50 100 125 160 200 250 315 400 500 630 800 1 000 1 250 1 600 2 000 10 - 16 20 - 31.5 25 - 40 31.5 - 50 40 - 63 50 - 80 63 - 100 80 - 100 100 - 125 125 - 160 160 160 - 200 250 2 x 160 2 x 200 Line Voltage [kV] 10 - 12 20 - 24 Rated Current of the HV-Fuse [A] 10 16 - 20 16 - 25 20 - 31.5 25 - 40 31.5 - 50 40 - 50 50 - 80 63 - 80 80 - 125 100 - 125 125 - 160 160 200 250 6.3 10 10 - 16 16 - 20 16 - 20 20 - 25 20 - 25 25 - 40 31.5 - 50 40 - 63 63 63 - 80 80 100 125 Type A 30 - 36 LV-Fuse gG / gL [A] 4 - 6.3 6.3 - 10 10 10 - 16 16 16 - 20 20 - 25 20 - 25 25 - 31.5 31.5 - 40 40 - 50 40 - 50 50 63 80 63 125 160 200 250 315 400 500 630 800 1 000 1 250 – – – * Use of the recommended HV fuse-links in connection with LV fuse-links of other manufacturer must be checked before installation TYPE A SIBA HV SIBA LV - gG / gL SIBA LV - gG / gL HHD 38 www.siba.de SICHERUNGEN/FUSES HHD Recommendation for the Protection of Main Transformer with HV-Fuse-links DIN Standard Protection without using a common LV-Fuse-link on the Low Voltage Side; the individual Cable exits are protected with a LV-Fuse-link Operating Class gG / gL Transformer Rated Capacity [kVA] 6 - 7.2 10 - 12 Line Voltage [kV] 15 - 17.5 20 - 24 Rated Current of the HV-Fuse [A] 50 100 125 160 200 250 315 400 500 630 800 1 000 1 250 1 600 2 000 10 - 16 16 - 31.5 20 - 40 31.5 - 50 31.5 - 63 40 - 80 50 - 100 63 - 100 80 - 125 100 - 160 125 - 160 160 - 200 250 2 x 160 2 x 200 10 16 - 25 16 - 31.5 20 - 31.5 25 - 40 25 - 40 31.5 - 50 40 - 63 50 - 80 63 - 100 80 - 125 100 - 160 160 200 250 6.3 - 10 16 20 20 - 25 20 - 31.5 25 - 31.5 31.5 31.5 - 50 31.5 - 63 40 - 80 63 - 100 63 - 100 100 125 160 6.3 10 10 - 16 16 - 20 16 - 20 16 - 25 16 - 25 20 - 40 25 - 50 31.5 - 63 40 - 63 50 - 80 80 100 125 Type B 30 - 36 4 - 6.3 6.3 - 10 6.3 - 10 10 - 16 10 - 16 10 - 20 16 - 25 16 - 25 20 - 31.5 20 - 40 25 - 50 31.5 - 50 50 63 80 TYPE B SIBA HV SIBA LV - gG / gL www.siba.de HHD 39 HHD SICHERUNGEN/FUSES Application Recommendation for Protection of Capacitors with HV-Fuse-links DIN Standard Assignment of Rated Currents of HV-Fuse-links acc. DIN Standard to Capacitor Rated Capacities Capacitor Rated Capacity [kVA] 6 - 7.2 50 100 200 250 300 400 500 750 1 000 1 250 1 600 2 000 10 20 40 50 63 80 100 160 200 250 315 315 Line Voltage [kV] 10 - 12 20 - 24 Rated Current of the HV-Fuse [A] 6.3 10 20 25 31.5 40 50 80 100 125 160 200 6.3 6.3 10 16 16 20 25 40 50 63 80 100 To control the occuring voltage during switch off Fuse link should be chosen from the next higher voltage range. e.g. 10 kV Capacitor with 20 kV Fuse links. (See also IEC 549, Chapter II, § 3.2) HHD 40 www.siba.de SICHERUNGEN/FUSES HHD HV-Fuse-bases for Indoor Application Rated Voltage 7.2 kV Part No. 31 001 02 A B C D E F G H I J K L 13.78 ” (350 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 7.60 ” (193 mm) 6.14 ” (156 mm) 12.20 ” (310 mm) 9.53 ” (242 mm) 0.60 ” (15 mm) 2.17 ” (55 mm) 1.38 ” (35 mm) 14.96 ” (380 mm) Rated Voltage 12 kV Part No. 31 003 02 Rated Voltage 24 kV Part No. 31 005 02 Rated Voltage 36 kV Part No. 31 007 02 Rated Voltage 24 kV Part No. 31 221 01* A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 11.54 ” (293 mm) 6.14 ” (156 mm) 16.14 ” (410 mm) 9.53 ” (242 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) A B C D E F G H I J 23.62 ” (600 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 17.44 ” (443 mm) 9.30 ” (236 mm) 22.60 ” (574 mm) 12.68 ” (322 mm) 0.60 ” (15 mm) 11.80 ” (300 mm) A B C D E F G H I J 27.36 ” (695 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 21.18 ” (538 mm) 12.83 ” (326 mm) 26.60 ” (676 mm) 16.22 ” (412 mm) 0.60 ” (15 mm) 14.96 ” (380 mm) A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 11.54 ” (293 mm) 9.30 ” (236 mm) 16.14 ” (410 mm) 12.68 ” (322 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) L 18.90 ” (480 mm) L 24.80 ” (630 mm) L 28.54 ” (725 mm) L 18.90 ” (480 mm) * Reduced Length for 24 kV Fuse-links E= 292 mm www.siba.de HHD 41 HHD SICHERUNGEN/FUSES HV-Fuse-bases for Outdoor Application Rated Voltage 7.2 kV Part No. 31 002 01 A B C D E F G H I J K L N O P HHD 42 13.78 ” (350 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 7.60 ” (193 mm) 9.33 ” (237 mm) 16.14 ” (410 mm) 12.80 ” (325 mm) 0.60 ” (15 mm) 2.17 ” (55 mm) 1.38 ” (35 mm) 14.96 ” (380 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 14.57 ” (370 mm) Rated Voltage 12 kV Part No. 31 004 01 Rated Voltage 24 kV Part No. 31 006 01 Rated Voltage 36 kV Part No. 31 008 01 A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 11.54 ” (293 mm) 9.33 ” (237 mm) 20.08 ” (510 mm) 12.80 ” (325 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) A B C D E F G H I J 23.62 ” (600 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 17.44 ” (443 mm) 12.10 ” (307 mm) 25.98 ” (660 mm) 15.55 ” (395 mm) 0.60 ” (15 mm) 11.80 ” (300 mm) A B C D E F G H I J 27.36 ” (695 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 21.18 ” (538 mm) 15.24 ” (387 mm) 30.90 ” (785 mm) 18.70 ” (475 mm) 0.60 ” (15 mm) 14.96 ” (380 mm) L N O P 18.90 ” (480 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 18.50 ” (470 mm) L N O P 24.80 ” (630 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 24.40 ” (620 mm) L N O P 28.54 ” (725 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 29.33 ” (745 mm) www.siba.de HHD SICHERUNGEN/FUSES Micro Switch Fitting to HV-Fuse-bases L= 660 mm L= 900 mm L= 250 mm L= 1200 mm Part No. 31 001 10 31 001 14 31 001 16 31 001 17 The SIBA microswitch installation set for high voltage fuse-bases, allows supervision of the switching status of high voltage fuse-links. By means of a flexible bowden drive, the movement of the fuse-link striker will be transferred to a microswitch. The microswitch itself has a change over contact and is suitable for 250 V AC, 6 A. The fitting accessories of this installation set match with the bolting holes of SIBA high voltage fuse-bases. Therefore, when such microswitch systems are added to SIBA high voltage fuse-bases later on, no additional drillings have to be done. Adaption to fuses-bases of other manufacturers is, however, possible. Furthermore, the set can also be fitted if only SIBA spring clip contacts part no. 3400201 are used, and not a complete fuse-base. Depending on the service voltage of the high voltage fuse-link, the microswitch can be fitted within a maximum distance of ”L” from the fuse-link. A minimum radius of the flexible bowden drive of 250 mm has to be observed. If the panel builder only uses the spring clip contact part no. 3100302.20 (see catalogue HHD page 47), the spacer part no. 3100201.3 must be used instead of the connection tag part no. 3100302.2. Micro switch Part No. 28 001 04 250 V / 6 A 1 change over contact Flexible Cable Connection bar of the spring clip contact Part No. 34 002 01 HV-Fuse-cap www.siba.de HHD 43 HHD SICHERUNGEN/FUSES Fuse-Clip HV-Spring Clip Contact with Connection Bar Rated Fuse Current ≤ 200 A Part No. 34 002 01 A B F G H L M 1.38 ” 1.26 ” 0.24 ” 2.80 ” 3.74 ” 3.66 ” M 10 (35 mm) (32 mm) (6 mm) (71.5 mm) (95 mm) (93 mm) Fuse-Clip HV-Spring Clip Contact with Connection Bar Rated Fuse Current > 200 A Part No. 34 001 02 A B F G H L M 1.38 ” 1.26 ” 0.24 ” 2.90 ” 4.92” 3.66 ” M 10 (35 mm) (32 mm) (6 mm) (73.5 mm) (125 mm) (93 mm) Spacer Part No. 34 002 01.3 A B C D E F G 1.26 ” 1.38 ” 0.24 ” 0.40 ” 0.20 ” 0.70 ” 0.26 ” HHD 44 (32 mm) (35 mm) (6 mm) (10,5 mm) (5 mm) (18 mm) (6.5 mm) www.siba.de SICHERUNGEN/FUSES HHD 24 kV Extension Adapter for High Voltage Fuses 12kV Part No. 34 006 01 A B C D F G H L 1.77 ” 0.06 ” 2.00 ” 1.73 ” 1.77 ” 0.20 ” 2.76 ” 7.28 ” (45 mm) (1.5 mm) (51 mm) (44 mm) (45 mm) (5 mm) (70 mm) (185 mm) A E1 E2 F L 1.77 ” (45 mm) 11.50 ” (292 mm) 17.40 ” (442 mm) 1.30 ” (33 mm) 20.00 ” (508 mm) HV-Fuse with 24 kV Extension Adapter www.siba.de HHD 45 00 HHD SICHERUNGEN/FUSES Test-Fuse With Time Delayed Release For Testing the Release Mechanism in Enclosed Medium Voltage Switchgear Part No. 33 010 03 1.77 ” (45 mm) 2.76 ” (70 mm) 7.56 ” (192 mm) 1.34 ” (34 mm) 0.30 ” (8 mm) 1.06 ” (27 mm) 10.24 ” (260 mm) Force (N) A D E F G H L Clamp lever for timer To change E an adaptor is available from 192 mm to 292 mm Part No. 34 004 02 from 192 mm to 442 mm Part No. 34 006 02 Travel (mm) HHD 46 www.siba.de SICHERUNGEN/FUSES HV-Contact Clip Rated Fuse Current ≤200 A HHD For Indoor and Outdoor Application Part No. 31 003 02.20 B G H HV-Contact Clip Rated Fuse Current > 200 A 1.26 ” (32 mm) 2.80 ” (71.5 mm) 3.74 ” (95 mm) For Indoor and Outdoor Application Part No. 34 001 01.20 B G H www.siba.de 1.26 ” (32 mm) 2.90 ” (73.5 mm) 4.92 ” (125 mm) HHD 47 00 HHD SICHERUNGEN/FUSES Storage Holder for HV- and LV-Fuse-links Rated Voltage [kV] Part No. 12 24 36 33 004 01 33 006 01 33 008 01 HHD 48 HV-Fuses LV-Fuses [Pieces] [Pieces] 3 3 3 6 6 6 L B T Weight [inch] [mm] [inch] [mm] [inch] [mm] 11.96 304 16.06 408 17.87 454 16.06 408 21.65 550 16.06 408 4.13 4.13 4.13 105 105 105 [kg/1] 1.0 1.4 1.9 www.siba.de