Yaskawa MP Series Ethernet Driver Help

advertisement
Yaskawa MP Series
Ethernet Driver Help
© 2012 Kepware Technologies
Yaskawa MP Series Ethernet Driver Help
2
Table of Contents
Table of Contents
2
Yaskawa MP Series Ethernet Driver Help
4
Overview
4
Device Setup
5
Memory Mapping for MPxxxxiec Devices
6
Communications Parameters
7
Block Sizes
8
Hardware Configuration for MPxxxx (218IF Module)
9
Hardware Configuration for MPxxxxiec
15
Hardware Configuration for MPxxxx (218IF Module) - Ladders
20
Optimizing Yaskawa MP Series Ethernet Communications
29
Data Types Description
30
Address Descriptions for MPxxxx (218IF Module) Devices
31
Address Descriptions for MPxxxxiec Devices
Error Descriptions
32
34
34
Address Validation
Address '<address>' is out of range for the specified device or register
34
Array size is out of range for address '<address>'
35
Array support is not available for the specified address: '<address>'
35
Data Type '<type>' is not valid for device address '<address>'
35
Device address '<address>' contains a syntax error
35
Device address '<address>' is not supported by model '<model name>'
35
Device address '<address>' is Read Only
36
Missing address
36
36
Device Status Messages
Device '<device name>' is not responding
36
Unable to write to '<address>' on device '<device name>'
36
36
Device Specific Messages
Device '<device name>' block request [<start address> to <end address>] responded with exception
'<exception response>'
37
Failure to start Winsock communications
37
Illegal data address for tag '<tag address>' on device '<device name>'
37
Illegal data address in block [<start address> to <end address>] on device '<device name>'
38
Illegal data value for tag '<tag address>' on device '<device name>'
38
Illegal data value in block [<start address> to <end address>] on device '<device name>'
38
Illegal function code '<function code (hex)>' in block [<start address> to <end address>] on device
'<device name>'
38
Illegal function code '<hex function code>' for tag '<tag address>' on device '<device name>'
39
Slave device '<device name>' detected a memory parity error
39
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
3
Slave device '<device name>' has failed
39
Slave device '<device name>' is busy
39
Tag '<tag address>' on device '<device name>' responded with exception '<exception code>'
39
Unable to bind to adapter: '<adapter>'. Connect failed
40
Unable to create a socket connection for Device '<device>'
40
Unexpected response frame received for block [<start address> to <end address>] on device '<device
name>'
40
Unexpected response frame received for tag '<tag address>' on device '<device name>'
40
Winsock initialization failed (OS Error = <error code>)
40
Winsock shut down failed (OS Error = <error code>)
40
Winsock V1.1 or higher must be installed to use the Yaskawa MP Series Ethernet device driver
41
Index
42
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
4
Yaskawa MP Series Ethernet Driver Help
Help version 1.032
CONTENTS
Overview
What is the Yaskawa MP Series Ethernet Driver?
Device Setup
How do I configure a device for use with this driver?
Optimizing Your Yaskawa MP Series Ethernet Communications
How do I get the best performance from the Yaskawa MP Series Ethernet?
Data Types Description
What data types does the Yaskawa MP Series Ethernet Driver support?
Address Descriptions
How do I reference a data location in a Yaskawa MP Series Ethernet device?
Error Descriptions
What error messages does the Yaskawa MP Series Ethernet Driver produce?
Overview
The Yaskawa MP Series Ethernet Driver provides an easy and reliable way to connect Yaskawa MP Series Ethernet
devices to OPC Client applications, including HMI, SCADA, Historian, MES, ERP and countless custom applications. It is intended for any MPxxxx Series controller that uses the 218IF module or any MPxxxxiec Series controller that communicates via Modbus TCP.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
5
Device Setup
Supported Devices
MPxxxx (218IF Module). This includes any controller that uses the 218IF module.
MPxxxxiec. This includes all devices from the MP2000iec Series.
Communication Protocol
MPxxxx (218IF Module) Protocol: Memobus over TCP.
MPxxxxiec Protocol: Modbus TCP.
Device ID
Yaskawa MP Series Ethernet devices are networked using standard IP addressing. The Device ID has the following format: YYY.YYY.YYY.YYY, where YYY designates the device IP address. Each YYY byte should be in the
range of 0 to 255.
Connection Timeout
This parameter specifies the time that the driver will wait for a connection to be made with a device. Depending
on network load, the connect time may vary with each connection attempt. The default setting is 3 seconds. The
valid range is 1 to 60 seconds.
Request Timeout
This parameter specifies the time that the driver will wait on a response from the device before giving up and
going on to the next request. Longer timeouts only affect performance if a device is not responding. The default
setting is 1000 milliseconds. The valid range is 100 to 9999 milliseconds.
Retry Attempts
This parameter specifies the number of times that the driver will retry a message before giving up and going on
to the next message. The default setting is 3 retries. The valid range is 1 to 10.
See Also: Hardware Configuration
Cable Diagrams
Both the MPxxxx 218IF Ethernet communications module and the MPxxxxiec are connected to the network via an
Ethernet twisted pair transceiver. The pinout of the 218IF Ethernet connector is displayed in the table below.
Pin Number
Signal Name
Remarks
1
GND
Shield ground
2
CI+
Collision detection (+)
3
DO+
Send data (+)
4
GND
Shield ground
5
DI+
Receive data (+)
6
PWRGND
12 V power supply
7
N.C.
Not Connected
8
GND
Shield ground
9
CI-
Collision detection (-)
10
DO-
Send data (-)
11
GND
Shield ground
12
DI-
Receive data (-)
13
+12 V
12 V power supply
14
GND
Shield ground
15
N.C.
Not Connected
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
6
Memory Mapping for MPxxxxiec Devices
This driver (Master) communicates via Modbus TCP to MPxxxxiec Series controllers that are configured as a Modbus Server/Slave. The image below displays the Modbus memory map: it not only shows how it relates to the
Global Variables (iec memory) in the controller, but also shows the Modbus function codes (FC) that are used to
communicate between devices' application memory.
Note: The Yaskawa MP Series Ethernet Driver supports MPxxxxiec series devices, which includes the Yaskawa
MP2000iec Series. For more information, refer to the MP2000iec Series at the manufacturer's website.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
7
See Also: Address Descriptions for MPxxxxiec Devices
Communications Parameters
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
8
Description of the parameter is as follows:
l
Port Number: This parameter specifies the TCP/IP port number that the remote device is configured to
use. The default port number is 502.
Note: There should only be one device defined in the PLC per connection.
Block Sizes
Block Sizes for MPxxxx (218IF Module) Controllers
Bit Addresses
Input bits (IB) and output bits (MB) can be read from 8 to 800 points (bits) at a time. The default value is 32.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
9
Register Addresses
Input registers (IW, IL, IF) and output registers (MW, ML, MF) can be read from 1 to 120 locations (words) at a
time. The default value is 32.
Block Sizes for MPxxxxiec Controllers
Bit Addresses
Input bits (IX) and Output Bits (QX) can be read 8 to 128 points (bits) at a time. The default value is 32.
Register Addresses
Input registers (IW, ID, IL) and output registers (QW, QD, QL) can be read from 1 to 120 locations (words) at a
time. The default value is 32.
Reasons for Changing the Default Block Sizes
1. Future versions of the device may not support block Read/Write operations of the default size.
2. The device may contain non-contiguous addresses (such as when using binary space module). If this is the
case and the driver attempts to read a block of data that encompasses undefined memory, the device will most
likely reject the request.
Hardware Configuration for MPxxxx (218IF Module)
The 218IF module must be configured before Ethernet connections to it may be established. Note the following:
l
The Yaskawa MP Series Ethernet Driver will support any controller that uses the 218IF module.
l
Each connection point must be configured individually.
l
Up to 20 connections may be configured, though only 10 may be used at a time.
l
In the OPC server project, each device requires a corresponding connection configuration in a 218IF module. Connections for remote stations and other software applications must be configured in addition to
those required by the OPC server.
Configuring a 218IF Module
Follow the instructions below for information on configuring a 218IF Module.
Note: The examples shown are from MotionWorks (MPE720) v6.02.
1. Open the File Manager.
2. Create a project for the controller.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
10
3. Double-click on Scan Time Setting.
4. In Scan Time, note the High Speed Scan Setting and Low Speed Scan Setting fields. Yaskawa recommends 1ms for the High Scan setting and 20ms for the Low Scan setting.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
11
5. When the scan time settings are set, close the Scan Time dialog.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
12
6. Double-click on Module Configuration to open the Engineering Manager.
7. In the Engineering Manager, select the 218IF module.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
13
8. In Slot details, double-click 218IF to open the Ethernet Interface dialog.
9. Click on the Transmission Parameters tab.
l
By default, the IP address will be set to 192.168.1.200; Response Time and Count of Retry will be
0. Set the IP address to one that is supported by the network.
l
Set Response Time to 1, and Count of Retry to 1.
l
No connections will have been created in a new project. Select Connection 1 and enter a port
number in the Local Port field. The OPC server defaults to Port 502. If a different port number has
been set, make sure the device in the OPC server project also has the same port number.
l
Since this is a slave connection port, the Node IP Address and Node Port should both be set to 0.
l
Connect Type: TCP; Protocol Type: MEMOBUS; and Code: RTU.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
14
10. If there is the possibility of a device connection from another LAN, set the Network Subnet Mask and
Gateway IOP Address. To do so, select Edit | Local Port: TCP/IP Setting from the File Manager
main menu. In the Station Setting dialog, set the Subnet Mask and Gateway IP values. Then, click OK to
set and close.
11. Load the new configuration into the controller's Flash Memory.
12. Next, create the ladder programs as described in Hardware Configuration - Ladders.
Important: The ladders are absolutely necessary; otherwise, the driver will not be able to connect to the 218IF
module or exchange data with it.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
15
Hardware Configuration for MPxxxxiec
For information on configuring an MPxxxiec device, refer to the instructions below.
1. To start, install the programming software. In the following examples, MotionWorks IEC Pro 1.2.3.12 is
used.
2. Next, create a project. In the following examples, an MP2300Siec device is used.
3. Launch the Hardware Configuration by clicking the Hardware Configuration icon
figuration window should appear as shown below.
www. kepware.com
. The Hardware Con-
Yaskawa MP Series Ethernet Driver Help
16
4. In the upper-right corner, enter the device's IP Address. Then, click Connect.
5. In the Project Window Tree, beneath the name of the device, double-click on Modbus/TCP. In this
example, the device name is "MyMachine".
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
17
6. Then, do the following:
l
Check Enable Controller as a Modbus Slave.
l
In I/O Task Assignment, select FastTsk.
l
Leave the remaining parameters at their default setting.
7. Once finished, save the changes by clicking File | Save.
8. Next, return to the MotionWorks IEC Pro 1.2.3.12 main project window. Locate the Project Tree Window and then browse to Physical Hardware.
9. Expand the project tree by clicking Configuration: MP2000_Series | Resource:MP2300Siec. Then,
select Global_Variables.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
18
10. The following categories should be displayed:
11. To create a new variable, right-click on the desired group and then select Insert Variable.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
19
12. In the Address column, specify the MotionWorks IEC Pro 1.2.3.12 address.
13. Once all changes are complete, build the project by clicking Build | Make.
14. Next, launch the Project Control dialog by clicking the Project Control icon
project, click Download | Download. The following dialog will be invoked:
. To download the
Note: The Error button will be enabled if the project contains any errors. When clicked, it will display a
description of the error.
15. Next, locate State and verify that it is set to Run. Then, select Cold, Warm, or Hot. Descriptions of the
starts are as follows:
l
Cold: In this start, all data will be initialized.
l
Warm: In this start, only non-retentive data will be initialized.
l
Hot: In this start, no data will be initialized.
16. When finished, click File | Save.
Viewing Data
Users must be in debug mode in order to view data. For more information, refer to the instructions below.
1. First, click the Debug On/Off icon
.
2. Then, return to the Global_Variables window.
Note: Data should now be visible.
Editing Read/Write Data
1. First, right-click on the variable that will be edited. Then, select Debug Dialog.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
20
2. In Value, select or type the new value. Then, click Overwrite.
Hardware Configuration for MPxxxx (218IF Module) - Ladders
After the 218IF module has been configured, two ladders need to be created to handle communications. See
Also: Hardware Configuration.
Important: The ladders are absolutely necessary: otherwise, the driver will not be able to connect to the 218IF
module or exchange data.
Adding Ladders
To add a new ladder drawing, select Low Scan Programs in the Controller project. Then, select File|New
Drawing from the main menu.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
21
Note: The image below shows how the Input DWG Name dialog is displayed.
Drawing L in Low Scan Programs
The first ladder is Drawing L in the Low Scan Programs. It calls the ladder that initializes the Message Receive
function for the connection and also initializes and increments a scan counter.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
22
Ladder L01
The next ladder program is Ladder L01, which initializes the Message Receive parameters and manages the process.
Note: The ladder program image has been separated in order to simplify viewing and printing.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
23
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
24
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
25
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
26
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
27
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
28
Load and Save the Configuration
After the ladders have been edited, verify and load them to the Controller. Then, cycle the power on the controller
to initialize the Ethernet module.
Note: The Yaskawa MP Series Ethernet device may release the communications socket connection by default after
a 2 minute interval from when the last communications occurred between the device and the server.
In order to maintain a responsive connection to the Yaskawa MP Series Ethernet module, it is recommended that
the Set point value of the On Delay Timer at rung 12 of ladder L01 should be set greater than the slowest
group update rate occurring in the client application by ten or more seconds.
For example, if the client has a group update rate of 120 seconds (120000ms), the On Delay Timer set point
should be changed to at least 130 seconds (130000ms).
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
29
Optimizing Yaskawa MP Series Ethernet Communications
The Yaskawa MP Series Ethernet Driver has been designed to provide the best performance with the least amount
of impact on the system's overall performance. While the Yaskawa MP Series Ethernet Driver is fast, there are a
couple of guidelines that can be used in order to control and optimize the application and gain maximum performance.
Our server refers to communications protocols like Yaskawa MP Series Ethernet as a channel. Each channel
defined in the application represents a separate path of execution in the server. Once a channel has been
defined, a series of devices must then be defined under that channel. Each of these devices represents a single
Yaskawa Memobus Plus controller from which data will be collected. While this approach to defining the application will provide a high level of performance, it won't take full advantage of the Yaskawa MP Series Ethernet
Driver or the network. An example of how the application may appear when configured using a single channel is
shown below.
Each device appears under a single Yaskawa
MP Series Ethernet channel. In this configuration, the driver must move from one
device to the next as quickly as possible in
order to gather information at an effective
rate. As more devices are added or more information is requested from a single device, the
overall update rate begins to suffer.
If the Yaskawa MP Series Ethernet Driver could only define one single channel, then the example shown above
would be the only option available; however, the Yaskawa MP Series Ethernet Driver can define up to 16 channels. Using multiple channels distributes the data collection workload by simultaneously issuing multiple
requests to the network. An example of how the same application may appear when configured using multiple
channels to improve performance is shown below.
Each device has now been defined under its
own channel. In this new configuration, a single path of execution is dedicated to the task
of gathering data from each device. If the
application has 16 or fewer devices, it can be
optimized exactly how it is shown here.
The performance will improve even if the
application has more than 16 devices. While
16 or fewer devices may be ideal, the application will still benefit from additional channels. Although spreading the device load
across all channels will cause the server to
move from device to device again, it can now
do so with far less devices to process on a single channel.
Block Size, which is available on each defined device, can also affect the Aromat Matsushita/NAIS Ethernet driver's performance. Block Size refers to the number of bytes that may be requested from a device at one time. To
refine the performance of this driver, configure Block Size to 1 to 120 registers and 8 to 800 bits.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
30
Data Types Description
Data Type
Description
Boolean
Single bit
Word
Unsigned 16 bit value
bit 0 is the low bit
bit 15 is the high bit
Short
Signed 16 bit value
bit 0 is the low bit
bit 14 is the high bit
bit 15 is the sign bit
DWord
Unsigned 32 bit value
bit 0 is the low bit
bit 31 is the high bit
Long
Signed 32 bit value
bit 0 is the low bit
bit 30 is the high bit
bit 31 is the sign bit
BCD
Two byte packed BCD
Value range is 0-9999. Behavior is undefined for values beyond this
range.
LBCD
Four byte packed BCD
Value range is 0-99999999. Behavior is undefined for values beyond
this range.
Float
32 bit floating point value
The driver interprets two consecutive registers as a floating point
value by making the second register the high word and the first register the low word.
When accessing data from a thermocouple or resistance sensor input
module, the driver will use a single 16-bit register as a floating point
value.
Float Example
If register 40001 is specified as a float, bit 0 of register 40001 would
be bit 0 of the 32 bit word, and bit 15 of register 40002 would be bit
31 of the 32 bit word.
Double
64 bit floating point value
String
Null terminated ASCII string Support, includes HiLo
and LoHi byte order selection and even string lengths from 2 to 240
bytes.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
31
Address Descriptions for MPxxxx (218IF Module) Devices
The default data types for statically defined tags are shown in bold.
Memory Type
Range
Data Type
Access
Input Bits
IB0000.b-IBFFFE.b
Boolean
Read Only
Output Bits
MB00000.b-MB65534.b
Boolean
Read/Write
Input Registers
IW0000-IWFFFE
IW0000-IWFFFD
IW0000.b-IWFFFE.b
Short, Word, BCD
Long, DWord, LBCD,
Float
Boolean
Read Only
(b is bit number 0x0-0xF)
(b is bit number 0x0-0xF)
(b is bit number 0x0-0xF)
IL0000-ILFFFD
IF0000-IFFFFD
Output Registers
MW00000-MW65534
MW00000-MW65533
MW00000.b-MW65534.b
Long, DWord, LBCD
Float
Short, Word, BCD
Long, DWord, LBCD,
Float
Boolean
Read/Write
(b is bit number 0x0-0xF)
ML00000-ML65533
MF00000-MF65533
Output Registers as strings with HiLo byte
order
MSH00000.bbb-MSH65534.ddd
Long, DWord, LBCD
Float
String
Read/Write
String
Read/Write
(ddd is string length 2-240, even decimal)
Output Registers as strings with LoHi byte
order
MSL00000.bbb-MSL65534.bbb
(ddd is string length 2-240, even decimal)
Arrays
Arrays are supported for register addresses (IW, IL, IF, MW, ML, and MF). The syntax for declaring an array is
MMxxxxx[cols] and MMxxxxx[rows][cols], where "MM" is the memory type mnemonic and "xxxxx" is the base
address of the array data.
The last register of the array cannot exceed the end of the address range. The formula for the final address in an
array is base address + (rows * columns * x) - x.
Note 1: "x" is the total number of bytes in the data type. Word equals 2, DWord equals 4, and Double equals 8.
Users should note the following:
l
The last register of a Word, Short, and BCD array cannot exceed 65534.
l
Float, DWord, Long, and Long BCD arrays cannot exceed 65533.
l
Arrays do not allow the total number of registers being requested to exceed the register block size that
was specified for the device.
Note 2: Arrays are not supported for Boolean types (Ibxxxx.b, MBxxxxx.b, IWxxxx.b, and MWxxxxx.b).
String Support
This driver supports reading and writing output register memory as an ASCII string. When using output registers for string data, each register will contain two bytes of ASCII data. The order of the ASCII data within a given
register can be selected when the string is defined. The length of the string can be from 2 to 240 bytes and is
entered in place of a bit number. The length must be entered as an even decimal number.
Examples
1. To address a string starting at MW40200 with a length of 100 bytes and Hi-Lo byte order, enter:
MSH40200.100
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
32
2.To address a string starting at MW40500 with a length of 78 bytes and Lo-Hi byte order, enter:
MSL40500.78
Note 1: Input addresses (IB, IW, IL, IF) are in hex, while output addresses (MB, MW, ML, MF) are in decimal. Bit
numbers, "b" are always in hex. Array "rows" and "cols" are always in decimal.
Note 2: All output addresses map to the same memory area. For example, MB00001.F is the same as
MW00001.F. ML00001 and MF00001 both map to the same memory as MW00001 and MW00002. The same is
true for input addresses.
Note 3: Writes to MB00000-MB04095 are faster than writes to MB04096-MB65534 because they can take advantage of direct bit access Memobus commands. Writes to the higher bits requires the driver to perform a read modify write operation, taking approximately twice as long.
Important: The actual range of valid addresses is hardware specific and may be smaller than the range allowed
by this driver.
Address Descriptions for MPxxxxiec Devices
The default data types are shown in bold.
Memory Type
Range
Data Type
Access
Input Bits
%IX24560.b-%IX24575.b
(b is bit number 0-7)
Boolean
Read/Write
Output Bits
%QX24560.b-%QX24575.b
(b is bit number 0-7)
Boolean
Read Only
Input Registers
%IW28672-%IW30718
Short, Word, BCD
Read/Write
%IW28672.b-%IW30718.b
(b is bit number 0-15)
Boolean
%ID28672-%ID30716
Long, DWord, Float, LBCD
%IL28672-%IL30712
Double
%QW24576-%QW26622
%QW28672-%QW30718
Short, Word, BCD
%QW24576.b-%QW26622.b
%QW28672.b-%QW30718.b
(b is bit number 0-15)
Boolean
%QD24576-%QD26620
%QD28672-%QD30716
Long, DWord, Float, LBCD
%QL24576-%QL26616
%QL28672-%QL30712
Double
Output Registers
Read Only
Note: Strings are not supported.
See Also: Memory Mapping for MPxxxxiec Devices
Arrays
Arrays are supported for register addresses IW, IL, ID, QW, QL, QD. The syntax for declaring an array is
%MMxxxxx[cols] and %MMxxxxx[rows][cols], where "MM" is the memory type mnemonic and "xxxxx" is the base
address of the array data. When creating an array, the total number of registers requested by an array cannot
exceed the register block size that was specified for this device.
The last register of the array cannot exceed the end of the address range. The final address in an array may be
calculated through the following: base address + (rows * columns * x) - x.
Note: "x" is the total number of bytes in the data type. Word equals 2, DWord equals 4, and Double equals 8.
Input Register Arrays IW, IL, and ID Examples
1. Word Address %IW30712 [2][2] would be %IW30712 + ([2]*[2] * 2) - 2 = %IW30718.
2. DWord Address %ID30704 [2][2] would be %ID30704 + ([2]*[2]* 4) – 4 = %ID30716.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
33
3. Double Address %IL30688 [2][2] would be %IL30688 + ([2]*[2] * 8) – 8 = %IL30712.
Output Register Arrays QW, QL, and QD Examples
1. Word Address %QW26616 [2][2] would be %QW26616 + ([2]*[2] * 2) - 2 = %QW26622.
2. DWord Address %QD26608 [2][2] would be %QD26608 + ([2]*[2]* 4) – 4 = %QD26620.
3. Double Address %QL26592 [2][2] would be %QL26592 + ([2]*[2] * 8) – 8 = %QL26616.
Note: Arrays are not supported for Boolean types (%IXxxxx.b, %QXxxxxx.b, %IWxxxx.b, %QWxxxxx.b).
Location and Size Prefixes
The following iec memory types' ranges utilize both location and size prefixes. Description of the location prefixes
are as follows:
l
I: The physical input.
l
Q: The physical output.
Description of the size prefixes are as follows:
l
X: Single bit.
l
W: Word (16 bits).
l
D: Double Word (32 bits).
l
L: Long Word (64 bits).
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
34
Error Descriptions
The following error/warning messages may be generated. Click on the link for a description of the message.
Address Validation
Address '<address>' is out of range for the specified device or register
Array size is out of range for address '<address>'
Array support is not available for the specified address: '<address>'
Data Type '<type>' is not valid for device address '<address>'
Device address '<address>' contains a syntax error
Device address '<address>' is not supported by model '<model name>'
Device address '<address>' is Read Only
Missing address
Device Status Messages
Device '<device name>' is not responding
Unable to write to '<address>' on device '<device name>'
Device Specific Messages
Device '<device name>' block request [<start address> to <end address>] responded with exception '<exception response>'
Failure to start Winsock communications
Illegal data address for tag '<tag address>' on device '<device name>'
Illegal data address in block [<start address> to <end address>] on device '<device name>'
Illegal data value for tag '<tag address>' on device '<device name>'
Illegal data value in block [<start address> to <end address>] on device '<device name>'
Illegal function code '<function code (hex)>' in block [<start address> to <end address>] on
device '<device name>'
Illegal function code '<hex function code>' for tag '<tag address>' on device '<device name>'
Slave device '<device name>' detected a memory parity error
Slave device '<device name>' has failed
Slave device '<device name>' is busy
Tag '<tag address>' on device '<device name>' responded with exception '<exception code>'
Unable to bind to adapter: '<adapter>'. Connect failed
Unable to create a socket connection for Device '<device>'
Unexpected response frame received for block [<start address> to <end address>] on device
'<device name>'
Unexpected response frame received for tag '<tag address>' on device '<device name>'
Winsock initialization failed (OS Error = <error code>)
Winsock shut down failed (OS Error = <error code>)
Winsock V1.1 or higher must be installed to use the Yaskawa MP Series Ethernet device driver
Address Validation
The following error/warning messages may be generated. Click on the link for a description of the message.
Address Validation
Address '<address>' is out of range for the specified device or register
Array size is out of range for address '<address>'
Array support is not available for the specified address: '<address>'
Data Type '<type>' is not valid for device address '<address>'
Device address '<address>' contains a syntax error
Device address '<address>' is not supported by model '<model name>'
Device address '<address>' is Read Only
Missing address
Address '<address>' is out of range for the specified device or register
Error Type:
Warning
Possible Cause:
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
35
A tag address that has been specified statically references a location that is beyond the range of supported locations for the device.
Solution:
Verify that the address is correct; if it is not, re-enter it in the client application.
Array size is out of range for address '<address>'
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically is requesting an array size that is too large for the address type or
block size of the driver.
Solution:
Re-enter the address in the client application to specify a smaller value for the array or a different starting point.
Array support is not available for the specified address: '<address>'
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically contains an array reference for an address type that doesn't support arrays.
Solution:
Re-enter the address in the client application to remove the array reference or correct the address type.
Data Type '<type>' is not valid for device address '<address>'
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically has been assigned an invalid data type.
Solution:
Modify the requested data type in the client application.
Device address '<address>' contains a syntax error
Error Type:
Warning
Possible Cause:
An invalid tag address has been specified in a dynamic request.
Solution:
Re-enter the address in the client application.
Device address '<address>' is not supported by model '<model name>'
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically references a location that is valid for the communications protocol
but not supported by the target device.
Solution:
Verify that the address is correct and if not re-enter it in the client application. Also verify that the selected model
name for the device is correct.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
36
Device address '<address>' is Read Only
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically has a requested access mode that is not compatible with what the
device supports for that address.
Solution:
Change the access mode in the client application.
Missing address
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically has no length.
Solution:
Re-enter the address in the client application.
Device Status Messages
The following error/warning messages may be generated. Click on the link for a description of the message.
Device Status Messages
Device '<device name>' is not responding
Unable to write to '<address>' on device '<device name>'
Device '<device name>' is not responding
Error Type:
Serious
Possible Cause:
1. The connection between the device and the host PC is broken.
2. The communication parameters for the connection are incorrect.
3. The named device may have been assigned an incorrect Network ID.
4. The response from the device took longer to receive than the amount of time specified in the "Request Timeout"
device setting.
Solution:
1. Verify the cabling between the PC and the device.
2. Verify that the specified communication parameters match those of the device.
3. Verify that the Network ID given to the named device matches that of the actual device.
4. Increase the Request Timeout setting so that the entire response can be handled.
Unable to write to '<address>' on device '<device name>'
Error Type:
Serious
Possible Cause:
1. The named device may not be connected to the network.
2. The named device may have been assigned an incorrect Network ID.
3. The named device is not responding to write requests.
4. The address does not exist in the PLC.
Solution:
1. Check the PLC network connections.
2. Verify that the Network ID given to the named device matches that of the actual device.
Device Specific Messages
The following error/warning messages may be generated. Click on the link for a description of the message.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
37
Device Specific Messages
Device '<device name>' block request [<start address> to <end address>] responded with exception '<exception response>'
Failure to start Winsock communications
Illegal data address for tag '<tag address>' on device '<device name>'
Illegal data address in block [<start address> to <end address>] on device '<device name>'
Illegal data value for tag '<tag address>' on device '<device name>'
Illegal data value in block [<start address> to <end address>] on device '<device name>'
Illegal function code '<function code (hex)>' in block [<start address> to <end address>] on
device '<device name>'
Illegal function code '<hex function code>' for tag '<tag address>' on device '<device name>'
Slave device '<device name>' detected a memory parity error
Slave device '<device name>' has failed
Slave device '<device name>' is busy
Tag '<tag address>' on device '<device name>' responded with exception '<exception code>'
Unable to bind to adapter: '<adapter>'. Connect failed
Unable to create a socket connection for Device '<device>'
Unexpected response frame received for block [<start address> to <end address>] on device
'<device name>'
Unexpected response frame received for tag '<tag address>' on device '<device name>'
Winsock initialization failed (OS Error = <error code>)
Winsock shut down failed (OS Error = <error code>)
Winsock V1.1 or higher must be installed to use the Yaskawa MP Series Ethernet device driver
Device '<device name>' block request [<start address> to <end address>]
responded with exception '<exception response>'
Error Type:
Warning
Possible Cause:
The device returned a Modbus exception code.
Solution:
Determine the meaning of the exception code, and then fix accordingly.
Failure to start Winsock communications
Error Type:
Fatal
Possible Cause:
Could not negotiate with the operating systems Winsock 1.1 functionality.
Solution:
Verify that the winsock.dll is properly installed on the system.
Illegal data address for tag '<tag address>' on device '<device name>'
Error Type:
Warning
Possible Cause:
The data address received in this query is not allowed for the server or slave because the reference number and
transfer length combination is invalid.
Solution:
Ensure that the range of memory exists in the PLC.
Note:
For a controller with 100 registers, a request with offset 96 and length 4 would succeed. A request with an offset
96 and length 5, however, will generate exception 02.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
38
Illegal data address in block [<start address> to <end address>] on device
'<device name>'
Error Type:
Warning
Possible Cause:
The data address received in this query is not allowed for the server or slave because the reference number and
transfer length combination is invalid.
Solution:
Ensure that the range of memory exists in the PLC.
Note:
For a controller with 100 registers, a request with offset 96 and length 4 would succeed. A request with an offset
96 and length 5, however, will generate exception 02.
Illegal data value for tag '<tag address>' on device '<device name>'
Error Type:
Warning
Possible Cause:
A value contained in the query data field is not an allowed value for server or slave. This indicates an error in the
structure of the remainder of a complex request, such as that the implied length is incorrect.
Solution:
Correct the error in the structure , and then retry the complex request.
Note:
This error message does not mean that a data item submitted for storage in a register has a value outside the
expectation of the application program. The Modbus TCP Protocol is not aware of the significance of any particular
value of any particular register.
Illegal data value in block [<start address> to <end address>] on device
'<device name>'
Error Type:
Warning
Possible Cause:
A value contained in the query data field is not an allowed value for server or slave. This indicates an error in the
structure of the remainder of a complex request, such as that the implied length is incorrect.
Solution:
Correct the error in the structure , and then retry the complex request.
Note:
This error message does not mean that a data item submitted for storage in a register has a value outside the
expectation of the application program. The Modbus TCP Protocol is not aware of the significance of any particular
value of any particular register.
Illegal function code '<function code (hex)>' in block [<start address> to
<end address>] on device '<device name>'
Error Type:
Fatal
Possible Cause:
The function code received in the query is not allowed for the server or slave. This may be because the function
code is only applicable to newer devices, and was not implemented in the unit selected. It may also indicate that
the server or slave is in the wrong state to process this type of request (such as if it is not configured but is being
asked to return register values).
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
39
Solution:
Correct the function code, and then retry the query.
Illegal function code '<hex function code>' for tag '<tag address>' on device
'<device name>'
Error Type:
Fatal
Possible Cause:
The function code received in the query is not allowed for the server or slave. This may be because the function
code is only applicable to newer devices, and was not implemented in the unit selected. It may also indicate that
the server or slave is in the wrong state to process this type of request (such as if it is not configured but is being
asked to return register values).
Solution:
Correct the function code, and then retry the query.
Slave device '<device name>' detected a memory parity error
Error Type:
Warning
Possible Cause:
The slave attempted to read extended memory, and detected a parity error.
Solution:
The master can retry the request, but service may be required on the slave device.
Slave device '<device name>' has failed
Error Type:
Fatal
Possible Cause:
An unrecoverable error occurred while the server or slave was attempting to perform the requested action.
Solution:
Locate the cause of the error, and then re-attempt the action.
Slave device '<device name>' is busy
Error Type:
Warning
Possible Cause:
The slave is processing a long duration program command.
Solution:
The master should retransmit the message later when the slave is free.
Tag '<tag address>' on device '<device name>' responded with exception
'<exception code>'
Error Type:
Warning
Possible Cause:
The device returned a Modbus exception code.
Solution:
Determine the meaning of the exception code, and then fix accordingly.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
40
Unable to bind to adapter: '<adapter>'. Connect failed
Error Type:
Fatal
Possible Cause:
The device could not bind local IP address of specified adapter.
Solution:
1. Verify that the winsock.dll is properly installed on the system.
2. Verify that TCP/IP and Ethernet adapter is properly configured on the system.
Unable to create a socket connection for Device '<device>'
Error Type:
Fatal
Possible Cause:
The device could not create a socket for TCP/IP Ethernet communication.
Solution:
Verify that the winsock.dll is properly installed on the system.
Unexpected response frame received for block [<start address> to <end
address>] on device '<device name>'
Error Type:
Serious
Possible Cause:
1. The data is corrupted.
2. An unexpected frame was received.
Solution:
Re-attempt the query.
Unexpected response frame received for tag '<tag address>' on device
'<device name>'
Error Type:
Serious
Possible Cause:
1. The data is corrupted.
2. An unexpected frame was received.
Solution:
Re-attempt the query.
Winsock initialization failed (OS Error = <error code>)
Error Type:
Fatal
Possible Cause:
Could not negotiate with the operating systems winsock 1.1 functionality.
Solution:
Verify that the winsock.dll is properly installed on the system.
Winsock shut down failed (OS Error = <error code>)
Error Type:
Serious
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
41
Possible Cause:
The device could not negotiate with the operating systems winsock 1.1 functionality.
Solution:
Verify that the winsock.dll is properly installed on the system.
Winsock V1.1 or higher must be installed to use the Yaskawa MP Series Ethernet device driver
Error Type:
Fatal
Possible Cause:
The device could not negotiate with the operating systems winsock 1.1 functionality.
Solution:
Verify that the winsock.dll is properly installed on the system.
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
42
Index
A
Address '<address>' is out of range for the specified device or register
34
Address Descriptions for MPxxxx (218IF Module)
32
Address Descriptions for MPxxxx (218IF Module) Devices
31
Address Validation
34
Array size is out of range for address '<address>'
35
Array support is not available for the specified address
35
B
30
BCD
Block Sizes
8
Boolean
30
C
Communications Parameters
7
D
Data Type '<type>' is not valid for device address '<address>'
35
Data Types Description
30
Device '<device name>' block request [<start address> to <end address>] responded with
exception '<exception response>'
37
Device '<device name>' is not responding
36
Device address '<address>' contains a syntax error
35
Device address '<address>' is not supported by model '<model name>'
35
Device address '<address>' is Read Only
36
Device Setup
5
Device Specific Messages
36
Device Status Messages
36
Double
30
DWord
30
www. kepware.com
Yaskawa MP Series Ethernet Driver Help
43
E
Error Descriptions
34
F
Failure to start Winsock communications
37
Float
30
H
Hardware Configuration for MPxxxx (218IF Module)
9
Hardware Configuration for MPxxxx (218IF Module) - Ladders
20
Hardware Configuration for MPxxxxiec
15
I
Illegal data address for tag '<tag address>' on device '<device name>'
37
Illegal data address in block [<start address> to <end address>] on device '<device name>' 38
Illegal data value for tag '<tag address>' on device '<device name>'
38
Illegal data value in block [<start address> to <end address>] on device '<device name>'
38
Illegal function code '<function code (hex)>' in block [<start address> to <end address>] on 38
device '<device name>'
Illegal function code '<hex function code>' for tag '<tag address>' on device '<device
name>'
39
L
LBCD
30
Long
30
M
Memory Mapping for MPxxxxiec Devices
www. kepware.com
6
Yaskawa MP Series Ethernet Driver Help
44
Missing address
36
O
Optimizing Yaskawa MP Series Ethernet Communications
Overview
29
4
S
Short
30
Slave device '<device name>' has failed
39
String
30
T
Tag '<tag address>' on device '<device name>' responded with exception '<exception
code>'
39
U
Unable to bind to adapter <adapter> . Connect failed
40
Unable to create a socket connection for Device <device>
40
Unable to write to '<address>' on device '<device name>'
36
Unexpected response frame received for block [<start address> to <end address>] on
device '<device name>'
40
Unexpected response frame received for tag '<tag address>' on device '<device name>'
40
W
Winsock initialization failed OS Error = <error code>
40
Winsock shut down failed OS Error = <error code>
40
Winsock V1.1 or higher must be installed to use the Yaskawa MP Series Ethernet device
driver
41
Word
30
www. kepware.com