Operation and Instruction Manual for Digital Panel Meters
This instruction manual is applicable for the following models of êbrit:
No user serviceable parts in the meters.
Warranty void if seal broken.
In case of any complaints, please contact our customer care cell.
Phone: 011 23235274
Email: customercare@hplindia.com/metersupport@hplindia.com
HPL Electric & Power Pvt. Ltd.
1/21, Atma Ram Mansion, Asaf Ali Road, New Delhi-110002
Phone : 23234411, 23234811, 23236811; Fax : 23232639
E-Mail : hpl@hplindia.com, Website : www.hplindia.com
This document is not contractual, HPL Electric & Power Pvt. Ltd. reserves the
right to modify features without prior notice in view of continued improvements.
Class 1.0
Class 0.5
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
êbrit
V11
V31
A11
A31
W 11
PM31
P11
P31
Class 0.2
V12
V32
A12
A32
W 12
PM32
êbrit F13
GCPK4EBRIT-R2
!
Model
Single Phase Voltmeter
Three Phase Voltmeter
Single Phase Ammeter
Three Phase Ammeter
Single Phase Kilowatt Meter
Three Phase Power Meter
Single Phase PF Meter
Three Phase PF Meter
Single Phase Frequency Meter
HPL Electric & Power Pvt. Ltd.
êbrit
êbrit
TEST CERTIFICATE
Digital Panel Meter for AC measurement
Contents
Accuracy:
Model:
1.
Preliminary Operations ...................................... 02
2.
Installation.......................................................... 02
3.
Wiring Instructions ............................................. 03
4.
Operation Mode................................................. 04
5.
Programming Mode ........................................... 08
6.
Technical Specification ...................................... 11
V11
V31
A11
A31
P11
W11
PM31
V12
V32
A12
A32
P31
W12
PM32
F13
Class 1.0
Class 0.5
Class 0.2
Range:
0-7A
0-750V
0 Lag-UPF-0 Lead
40.00-99.99 Hz
0-3.000 kW
0-3.300 kW/kVA/kVAr
Ordering Information
Model
Item Code for
Class 1.0
Item Code for
Class 0.5
Item Code for
Class 0.2
S/W Version
Single Phase Voltmeter
NPAMEBRITV11
NPAMEBRITV12
1.07 & above
Three Phase Voltmeter
NPAMEBRITV31
NPAMEBRITV32
1.07 & above
Single Phase Ammeter
NPAMEBRITA11
NPAMEBRITA12
1.07 & above
Three Phase Ammeter
NPAMEBRITA31
NPAMEBRITA32
1.07 & above
Single Phase Kilowatt Meter
NPAMEBRITW11
NPAMEBRITW12
3.04 & above
Three Phase Power Meter
PAMEBRITPM31
PAMEBRITPM32
5.03 & above
Single Phase PF Meter
NPAMEBRITP11
2.03 & above
Three Phase PF Meter
NPAMEBRITP31
6.00 & above
Single Phase Frequency Meter
Operation and Instruction Manual
NPAMEBRITF13
4.01 & above
1
Operation and Instruction Manual
14
êbrit
êbrit
I.
Programming
1. Preliminary Operations
Voltmeter/Ammeter/Kilowatt meter
CT Primary and Secondary Programmable
CT Primary
:
5 to 9999A for CT secondary 5A
:
1 to 9999A for CT secondary 1A
CT Secondary
:
5/1A (Selectable)
PT Primary and Secondary Programmable
PT Primary
:
110V, 1.1kV, 6.6kV, 11kV, 33kV
66kV, 132kV, 220kV or 440kV
PT Secondary
:
110V (Fixed)
For personal & product safety please read the contents of these operation instructions
carefully before connecting.
Check the following after receipt of package :
a.
Power Meter
CT Primary and Secondary Programmable
CT Primary
:
5 to 6550A for CT secondary 5A
:
1 to 6550A for CT secondary 1A
CT Secondary
:
5/1A (Selectable)
The Packing is in good condition.
b.
The Product is not been damaged during transit.
c.
The Product reference number confirms to the order placed.
d.
Operating Instructions as given in the manual.
2. Installation
2.1
Dimensions and cut-out
J. Default Factory Settings
+0.8mm
-0.0mm
Voltmeter/Kilowatt meter
CT Primary
:
CT Secondary
:
+0.8mm
-0.0mm
Ammeter/Kilowatt meter/Power meter
CT Primary
:
5A
CT Secondary
:
5A
110V
110V
Notes:
1. For Voltmeter and kilowatt meter without an external PT please use the
default PT Ratio of 110/110V.
2. Max. Value of power ratio for kW meter is 1000000.
Power Ratio = CT Ratio x PT Ratio.
Example: If user set CT as 9999 and then tries to set PT Ratio as 440kV
then PT Ratio will not set and meter will display FAIL.
96mm
3. For Ammeter if the value exceeds 9999A then the LED indication for kilo
will glow and meter will display
.
4. For Voltmeter if value becomes 1000V then LED indication for kilo will
glow and meter will display 1.000 on its display.
Operation and Instruction Manual
2.2 The panel meter is to be firmly fixed using the 4 transparent fixing clips
supplied with the meter.
Use 0.5 to 2.5mm2 cable for voltage terminals.
Use 3 to 6mm2 cable for current terminals.
13
Operation and Instruction Manual
2
êbrit
3. Wiring Instructions
êbrit
C. Resolution
Voltage (Direct measurement) : 0.1V
Current (Direct measurement) : 0.001 A
P.F.
: 0.01 (Single Phase PF Meter)
0.001 (Three Phase PF Meter)
Frequency
: 0.01Hz
Kilowatt (Direct measurement) : 0.001kW
Power (Direct measurement)
: 0.001kW/kVA/kVAr
3.1 Read the instruction manual carefully before installation.
3.2 Connect the meter as per wiring diagram shown.
3.3 Ensure that cable connections are properly tightened.
3.4 Use external fuses for voltage and auxiliary supply circuit.
3.5 Wiring Diagram.
For Ammeter
D. Display
80-300V
AC/DC
Display
Display Range
80-300V
AC/DC
FUSE 0.5A
FUSE 0.5A
AUXILIARY
SUPPLY
Decimal
Indications
AUXILIARY
SUPPLY
P N
P N
!
!
CURRENT
INPUT
I1
I3
I2
CURRENT
INPUT
S1 S2 S1 S2 S1 S2
S1 S2
: 14 mm Seven segment LED
: 0 to 9999
0 to 999 (For PF meter)
: Auto adjust
: R, Y, B Colored LED indication for 3 phase meters
: LED indication for kilo & mega (only for kW meter)
: Lag/Lead indication for PF meter
: Power indication (kW, kVA, kVAr) for Power Meter
E. Mechanical
P1
S1
P2
S2
P1
P2
S1
S2
P1
S1
P1
S1
Enclosure Material
Bezel Size
Panel Cutout
Weight
P2
S2
P2
S2
Three Phase Ammeter
Single Phase Ammeter
Voltmeter/Ammeter/Kilowatt meter/Power meter
Class 1.0
:
±1% of measured value
Class 0.5
:
±0.5% of measured value
:
±0.01%
PF meter
Frequency meter
Class 0.2
:
±0.2% of measured value
80-300V
AC/DC
FUSE 0.5A
FUSE 0.5A
AUXILIARY
SUPPLY
P N
!
AUXILIARY
SUPPLY
P N
VOLTAGE
INPUT
L1 L2 L3 N
!
G. Environmental
VOLTAGE
INPUT
Operational temperature :
Storage temperature
:
Relative humidity
:
L N
FUSE 0.5A
FUSE 0.5A
Three Phase Voltmeter
o
0 to 60 C
o
-20 to 70 C
0 to 95%
H. Safety
IP Protection
Device safety
Operation and Instruction Manual
Engineering Plastic
96 x 96 mm
92 x 92 mm
< 320g Approx.
F. Accuracy
For Voltmeter and Frequency Meter
80-300V
AC/DC
:
:
:
:
Single Phase Voltmeter/Frequency Meter
3
Operation and Instruction Manual
:
:
IP 54 on front plate
As per IEC 61010
IEC 61326 (Power Meter)
12
êbrit
êbrit
For Single Phase PF Meter and
Kilowatt Meter
G. To change the password
1. After acceptance of password, Press “
digit will start blinking.
D
” key for 3 sec. The left most
P
80-300V
AC/DC
2. Enter the new desired password from 0001 to 9999 as explained in
section 4.2.E.
N
P
80-300V
AC/DC
N
FUSE 0.5A
FUSE 0.5A
AUXILIARY
SUPPLY
AUXILIARY
SUPPLY
3. Press “
” key, display will show
. The new password is
programmed and the meter will automatically come out of the
programming mode.
!
For Three Phase PF Meter and
Power Meter
P
P
N
!
I1
CURRENT
INPUT
VOLTAGE
INPUT
L
S1 S2
Important: Please remember the password after changing it. Incase user forget
the password the user must send the meter to the factory for factory settings,
which cannot be done on site.
S1S2 S1S2 S1S2
L1
N
L1
P2
S1
S2
L1 L2
L3
N
N
FUSE 0.5A
P1
VOLTAGE
INPUT
I3
I2
N
!
CURRENT
INPUT
L2
L3
P1
S1
P2
S2
P1
S1
P2
S2
P1
S1
P2
S2
N
5. Technical Specification
4. Operation Mode
A. Electrical Specification
Auxiliary Power Supply
Auxiliary burden
Voltage circuit burden
Current circuit burden
:
:
:
:
4.1. Normal Mode
80-300V AC/DC, 50Hz
< 2.5VA at 230V
< 0.5VA
< 0.5VA
A. 1. Switch ON the Auxiliary Power Supply.
2.
3.
B. Measuring Range
Voltage (Direct measurement)
Current (Direct measurement)
P.F.
Frequency
Kilowatt (Direct measurement)
Power (Direct measurement)
:
:
:
:
:
:
0-750V AC
0-7A AC
Zero Lead-Unity-Zero Lag
40.00-99.99Hz
0-3.000 kW
0-3.300 kW/kVA/kVAr (Phase Wise Power)
0-9.900 kW/kVA/kVAr (Total Power)
Display will glow and display the message.
(u3/a3/u1/a1/fr/pf/pf3/p1/pr53) & Ver.No.as per the model.
After one second, meter starts displaying parameters in auto scroll mode.
B. (1). Auto Scroll Mode
a. Single Phase Meters: Single phase Voltmeter/Ammeter/Frequency
meter/PF meter/Kilowatt meter will show the respective parameter on
the screen.
b. Three Phase Voltmeter Star Connection: The following parameters scroll
one after another.
1. R Phase to Neutral Voltage
2. Y Phase to Neutral Voltage
Note: In case of power meter
Total active power is the absolute sum of all three phase active powers.
Total apparent power is the absolute sum of all three phase apparent powers.
Total reactive power is the algebraic sum of all three phase reactive powers.
3. B Phase to Neutral Voltage
4. R-Y Phase to Phase Voltage
5. Y-B Phase to Phase Voltage
6. R-B Phase to Phase Voltage
Operation and Instruction Manual
11
Operation and Instruction Manual
4
êbrit
êbrit
c. Three Phase Voltmeters Delta Connection: The following parameters
scroll one after another.
1. R-Y Phase to Phase Voltage
2. Y-B Phase to Phase Voltage
3. R-B Phase to Phase Voltage
d. Three Phase Ammeter: The following parameters scroll one after
another.
1. R Phase Current
2. Y Phase Current
3. B Phase Current
D
” key, display will show the present secondary current.
4. To change the secondary current, press “ D ” key for 3 sec. and
select desired value using “ D ” key (1A or 5A).
5. After selection press the “
” key, display will show SAUE. The selected
secondary current value is programmed.
6. Press “
7. Press “
” key, display will show
D
Note: (For power meter: 5 to 6550A for CT secondary 5A,1 to 6550A for
CT secondary 1A).
8. Press “
” key, display will show SA U E . The selected primary
current value is programmed.
Three Phase Power meter: The following parameters scroll one after
another for active, apparent power & reactive power.
9. Press “
” key, to exit the configuration mode.
E. To enter the digits
(i) Parameters display for active & apparent power:
1. R Phase Power
2. Y Phase Power
3. B Phase Power
4. Total Power
1. Press “
back.
2. Press “
D
” key to edit the left blinking digit, it will go from 0-9 and roll
” key to shift digit to right.
3. Follow Step 1 & 2 and enter the desired 4 digit value.
(ii) Parameters display for reactive power:
1. R Phase Power Sign
2. R Phase Power
3. Y Phase Power Sign
4. Y Phase Power
5. B Phase Power Sign
6. B Phase Power
7. Total Power Sign
8. Total Power
F. To change the power selection in Power meter (kW/kVAr/kVA)
1. After acceptance of the password, Press “
CT.
” key, display will show
2. Press “
” display will show present power selection as P-PO or rPO or 5-PO.
3. To change the power selection, press and hold “ D ” key for 3 seconds
and select desire power using “ D ” key (P-PO for kW or r-PO for kVAr
or 5-PO for kVA).
Note: If Voltage in any phase greater than 450V or secondary current greater than 7.5A
the meter will display
in corresponding phase.
4. After selection press “
power is selected.
In case if any CT is connected in reverse, the corresponding Phase LED will Blink.
Please correct the CT connection in such case.
5. Press “
Operation and Instruction Manual
.
” key again, it will show the present primary current value.
To change the primary current, press “ D ” key for 3 sec. and enter the
desired value as explained in sec. 4.2.E (5 to 9999A for CT secondary
5A,1 to 9999A for CT secondary 1A).
e. Three Phase PF meter: The following parameters scroll one after
another.
1. R Phase PF
2. Y Phase PF
3. B Phase PF
4. System PF
f.
3. Press “
5
” key, display will show
. The new
” key to exit the programming mode.
Operation and Instruction Manual
10
êbrit
êbrit
B. To change the PT ratio (Single Phase Voltmeter & Kilowatt
Meter/Three Phase Voltmeter)
1. After acceptance of the password, press “
PT (for Voltmeter).
2.
” key, display will show
1. LCD Check - 8.8.8.8
2. In case of KW meter after pressing “
” key display shows CT .
Now again press “
” key, display will show PT .
3. Press “
D
” key, display will show
2. PT
.
3. Present Primary Voltage
4. Press “ D ” key. The display will show secondary voltage as 110V
which is fixed.
5. Press the “
6. Press “
D
” key, display will show
0110 (If Primary Voltage of 110V is selected)
.
4. Present Secondary Voltage
” key, it will show the present primary voltage.
7. To change the value, Press “ D ” key for 3 sec. and select desired
value using the “ D ” key (110V, 1.1kV, 6.6kV, 11kV, 33kV, 66kV,
132kV, 220kV or 440kV).
0110 (Secondary Voltage is 110V which is fixed)
5. Present Network Selection (This will be shown in three phase
meter only)
or
as the case may be.
8. Then press the “
” key, display will show SA U E . The selected
Primary voltage value is programmed.
9. Press “
6. Finally meter will return to set parameters in the auto scroll mode.
” key to exit the configuration mode.
b. Ammeter (Single Phase and Three Phase): The following parameters
will be displayed by pressing “
” key once.
C. To change the Network selection (Three Phase Voltmeter)
1. After acceptance of the password, press “
PT .
2. Press “
” key, display will show
” key, display will show the present network
or
3. To change the network, Press & Hold “
desired network using “ D ” key.
4. Then press the “
is selected.
3. Present Primary Current
” key for 3 sec. & select
D
” key, display will show
. The new network
0100 (If primary current of 100A is selected)
4. Present Secondary Current
” key to exit the configuration mode.
D. To change the CT ratio (Single Phase Ammeter & Kilowatt
Meter/Three Phase Ammeter & Power meter)
1. After acceptance of the password, press “
CT .
2. Press “
1. LCD Check - 8.8.8.8
2. cT
.
5. Press “
Push Button Mode
a. Voltmeter (Single Phase & Three Phase): The following parameters will
be displayed by pressing “
” key once.
D
” key, display will show
Operation and Instruction Manual
0005 (If secondary current of 5A is selected)
” key, display will show
5. Finally meter will return to set parameters in the auto scroll mode.
.
9
Operation and Instruction Manual
6
êbrit
êbrit
c. Kilowatt Meter (Single Phase): The following parameters will be
displayed by pressing “
” key once.
4. Present Secondary Current
1. LCD Check - 8.8.8.8
0005 (If Secondary Current of 5A is selected)
2. cT
5. Present power selection P-PO (active power) or r-PO (reactive
power or 5-po (apparent power) as the case may be.
3. Present Primary Current
6. Finally meter will return to set parameters in the auto scroll mode.
0100 (If Primary Current of 100A is selected)
e. Press the “
only).
4. Present Secondary Current
f.
0005 (If Secondary Current of 5A is selected)
D
” key to scroll through the parameters (for 3 phase meters
Parameter Scroll Lock: (for 3 phase meters only)
5. pt
1. Press and HOLD “ D ” key till the display shows
will show only the selected parameter.
6. Present Primary Voltage
2. To unlock press “
” key.
3. In case of PF meter press “
” key once and display will show
.To unlock press “
” key again and display will show
0110 (If Primary Voltage of 110V is selected)
7. Present Secondary Voltage
.
4.2 Programming Mode
A. To Enter in the programming mode
0110 (Secondary Voltage is 110V which is fixed)
1. Press and HOLD “ D ” & “
” keys together for 3 sec. in order to
enter the configuration mode. Now the meter will ask for password
by displaying
on the screen.
8. Finally meter will return to set parameters in the auto scroll mode.
d. Power Meter (Three Phase): The following parameters will be displayed
by pressing “
” key once.
1. LCD Check - 8.8.8.8
2. The meter will then display 0001 with left most digit blinking.
This is the default password.
3. If required, this default password can be retained. In order to
proceed further in the programming mode press “ ” key 4 times.
2. cT
4. If the configuration password is not the default password then enter
the password as mentioned in Sec 4.2.E
3. Present Primary Current
5. On successfully entering the password the meter will display F in e .
0100 (If primary current of 100A is selected)
!
Operation and Instruction Manual
D
. The display
7
The default password to enter into the programming mode is 0001.
Operation and Instruction Manual
8