ma 302 digital ammeter - selec

advertisement
MA 302 DIGITAL AMMETER SELEC
FEATURES
!
!
!
C
4 Digit, 7 segment LED
Wide Range
Available in 240V AC/DC & 24V AC/DC (On Request)
US
PENDING
1/4 DIN
96mm x 96mm
ORDERING INFORMATION
Part No.
Display Range
Input Range
Measurement Range Overrange Indication Resolution Continuous Max.
Input Rating
AC
MA302-110V
0 – 4960A
0 - 5A
0 – 6.2A
Input > 6.2A
0.001
6.2A
MA302-AC-20A-110V
0 – 24.8A
0 – 20A
0 – 24.8A
Input > 24.8A
0.01
24.8A
MA302-AC-1A-110V
0 – 4960A
0 – 1A
0 – 1.24A
Input > 1.24A
0.001
1.24A
Input > 6.2A
0.001
6.2A
DC
MA302-DC-75mV-110V
0 – 4960A
0 – 75mV (0 - 5A) 0 – 6.2A
TERMINAL CONNECTIONS
TECHNICAL SPECIFICATIONS
#
AC Models (CT Type )
P1
INPUT SPECIFICATIONS
P2
Accuracy
N
1
2
L
S1
3
4
C.T. Settings
#
1
2
L
P1
3
4
150, 200,250,300,400, 500, 600, 800,
P2
1000,1200, 1500, 1600, 2000, 2500,
3000, 4000
MA302-AC-1A
#
DC Models (Shunt Type )
AC:
MA302
5,10, 20, 30, 40, 50, 60, 75, 80, 100,
AC Models (Direct Type )
N
AC: 0.5 class
DC: 0.5 class
S2
P2
1, 10, 20, 30, 40, 50, 60, 75, 80,100,150,
200, 250, 300, 400, 500, 600, 800, 1000,
P1
1200, 1500, 1600, 2000, 2500, 3000,
N
1
2
L
3
4
4000
MA302-AC-20A
Direct Type
+
Cable Size (AWG): 13 ; Stud Hole for Lug (inch): 0.137 ; Tightening Torque (Lb-inch): 4.5
2
Cable Size (mm ): 2.5 ; Stud Hole for Lug (mm): 3.5 ; Tightening Torque (N-m): 0.5
Shunt Settings
DC:
MA302-DC-75mV
5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 80,
100, 125, 150, 200, 250, 300, 400, 500,
600, 750, 800, 1000, 1200, 1500, 1600,
#
NOTE
1) CT Type: There is an internal CT with CT setting. Above 5A (0-5A model)
or 1A (0-1A model) external CT is required.
2) Shunt Type: External Shunt (0-75mV DC) is required for measurement.
2000, 2500, 3000, 4000
3) Direct Type: Current is directly applied at the input terminal and the unit shows the
reading.
Method
True RMS
FUNCTIONAL SPECIFICATIONS
Measuring Element Drop
Sampling Rate
one 91-22-4039 4200 / 4202 | Fax 91-22-2847 1733
0.07V at 5A
3 samples / second
Dielectric withstand
2kV AC between auxiliary supply &
Voltage
measuring input
Rated Impulse
withstand Voltage
3.5kV (1.2/50µS)
MA302
DIGITAL AMMETER
DIMENSIONS
TECHNICAL SPECIFICATIONS
Front
Side
GENERAL SPECIFICATIONS
99mm
Supply Voltage
AC (Shunt type)
9 9m m
9 1 mm
110V AC ( 50 / 60Hz) ±20%
AC (Direct Type)
110V AC ( 50 / 60Hz) ±20%
DC (Shunt type)
110V AC ( 50 / 60Hz) ±20%
Available on request:
240V AC ( 50 / 60Hz) ±20%
24V AC
46mm
5mm
Panel Cutout
92m
m
92mm
Power Consumption
3VA max
Temperature
Operating: 0 to 50oC (32 to 122oF)
o
o
Storage: 0 to 70 C (32 to 158 F)
Humidity (non-condensing)
Weight
All dimensions are in mm (to convert to inches, multiply by 0.03937)
95% RH
190 g (0.418 lbs)
Protection Level
IP65 for faceplate
Also Selec Make Economical PLC and HMI
www.selec.
For Quote and Solutions mail us at
selectautomation@airtelmail.in
www.selec.com | sales@selec.com | Phone 91-22-4039 4200 / 4202 | Fax 91-22-2847 1733
Visit Us at
www.selectautomation.net
Download